Loading...
HomeMy WebLinkAboutFINAL ELD 7-23-2019Exclusive Providers for MDleak® MSleak® DPleak® and PHDleak® Testing Technologies Page 1 of 3 Test Type: Facility Name: Job #: 3978 Prepared For: PO #: NA Site Address: City: Primary Test Leak Rate: 0.005 gph State and Zip: CA 93304 Secondary Test Leak Rate: 0.1 gph Start Date:End Date: SYSTEM TK-1 87 TK-2 91 TK-3 DSL TK-4 E-85 Product Primary:PASS PASS PASS PASS Product Secondary:PASS PASS PASS PASS Vent Primary:PASS PASS PASS PASS Vent Secondary:PASS PASS PASS PASS VR Primary:PASS PASS NA NA VR Secondary:PASS PASS NA NA MCleak ELD Tank:PASS PASS PASS PASS Turbine Sump:PASS PASS PASS PASS Turbine Sump Elect:PASS PASS PASS PASS Turbine Head:PASS PASS PASS PASS Fill/Vapor Sump:PASS PASS PASS PASS UDC's:PASS PASS PASS PASS Fill Bucket Primary:PASS PASS PASS PASS Vapor Bucket Primary:PASS PASS NA PASS Fill Spill Bucket Hydo:PASS PASS PASS PASS Vapor Bucket Hydro:PASS PASS NA PASS Vent Box:PASS PASS PASS PASS Certifying Field Technician: Ricardo Gonzalez State Lic. # : Certification Leak Rate: 0.005 gph Certifying Technician Signature: Date: Statement Confirmed by: Date: 7/26/2019 Office use only I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is true and correct to the best of my knowledge. If you have any questions on the testing please do not hesitate to call. @ 855-255-5325. 04-1695 This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak sensitivity listed above by using one or more of the following DPleak®,MDleak®and PHDleak®EPA aproved Methods. The DPleak®,MDleak®and PHDleak®Methods are the most versatile and comprehensive testing procedures offered to the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®and PHDleak®Method can be assured that their facility has passed the Nation's highest standard in preventative leak detection. 7/23/2019 7/23/20197/22/2019 2600 White Lane Bakersfield Complete Fueling Solutions Facility Certification CONFIDENTIAL California ELD New Construction Test MSleak White DJY Inc. Exclusive Providers for MDleak® MSleak® DPleak® and PHDleak® Testing Technologies Page 2 of 3 2600 White Lane Log of Repaired Leak/s CONFIDENTIAL TK-1 87 TK-2 91 TK-3 DSL TK-4 E-85 Tank Volume: 12000 8000 8000 12,00-0 Manufacture: Modern Modern Modern Modern Interstice: Dry Dry Dry Dry Depth To Tank: 74"75"75"74" Tank Dia: 10 ft 10 ft 10 ft 10 ft Depth to Fuel: NA NA NA NA Tank Sump Boots Turbine Bravo Smith Red Jacket 5 Gilbarco Emco-Wheaton Smith Smith Smith Fire-Flex PhilTite EVR: Healy Reference #Date Time Status System Component Manufacture 68 7/22/19 10:10 Leak Final TK-1 87 Drain on fill bucket leaking.PhilTite 103 7/22/19 13:38 Leak Final TK-1 87 87 shear valve leaking 104 7/22/19 13:39 Leak Final TK-2 91 91 Cap on shear valve leaking. 114 7/22/19 13:52 Leak Pretest TK-1 87 Fill bucket to riser leaking 115 7/22/19 13:53 Leak Pretest TK-1 87 STP Sump 116 7/22/19 13:54 Leak Pretest TK-2 91 VR bucket to riser leaking 117 7/22/19 13:55 Leak Pretest TK-2 91 STP Sump 118 7/22/19 13:56 Leak Pretest TK-3 DSL Fill bucket to riser leaking 119 7/22/19 13:57 Leak Pretest TK-3 DSL STP Sump 137 7/22/19 16:13 Leak Final TK-1 87 Shear valve is still leaking. 183 7/23/19 7:20 Leak Final TK-1 87 Shear valve leaking. The one they replaced. Reference #Date Time Status System Component Manufacture None Log of Repaired Leaks Log of Unrepaired Leaks Tank Information Containment Boots: Piping Information Manufacture Spill Buckets: Number of Dispensers: Manufacture: Shear Valve Manufacture: Flex: Product Lines: Vapor Return / Vent: UDC/Dispensers Information Depth to Ground Water: Manufacture: NA Exclusive Providers for MDleak® MSleak® DPleak® and PHDleak® Testing Technologies Page 3 of 3 2600 White Lane Reference Addendum CONFIDENTIAL Site Photo