HomeMy WebLinkAbout3401 S Chester ELD 12-11-2018 UST System Well Proximity Test Report
ELD Test Date:
Customer:
Location:
Tested By: CGRS, Inc.
5444 Dry Creek Road
Sacramento, CA 95838
Project No:6-13769-17159-9535
Chester Liquor and Market
Chester Liquor & Market
3401 S. Chester Ave.
Bakersfield, CA 93304
3401 S. Chester Ave.
Bakersfield, CA 93304
December 11, 2018
Location:CGRS Project No :
Test Date:
CGRS Techs:
CA Tank Tech Signature: 12/11/2018
Sergio L. Nunez CA Tank Tester #06-1727 Date
Reviewed by: 1/21/2019
Chris Murphy Director of CA Operations Date
Well Proximity ELD Test Results
10k Primary Containment System PASS
3401 S. Chester Ave.
10k Primary Containment System PASS
87 Octane
91 Octane
Test Certification
Well Proximity Enhanced Leak Detection (ELD)
Chester Liquor & Market December 11, 2018
6-13769-17159-9535
Bakersfield, CA 93304
Sergio L. Nunez
This document certifies that the UST systems listed below at the above referenced location has been tested and passed the
Enhanced Tracer Tight, tightness test. CGRS further certifies that this test meets the testing requirements for underground
storage tank systems as per the California Code Regulations, Title 23, Chapter 16 Section 2644.1 (a) (1& 2).
Test Date:Technicians:
Site Information Contractor Information
Facility:Contractor Name :
Address:Address:
City, State, Zip:City, State, Zip:
County:Contact:
CUPA Contact:Telephone/Email:
CUPA Phone/Email:
Tank No.Capacity (gal.)Product Type Manufacturer Depth to GW Product Level (in.)Brine
Tank 1 10,000 87 Octane SW Steel Plasteel >-90 51 No
Tank 2 10,000 91 Octane SW Steel Plasteel >-90 61 No
Tank Top Sumps Manufacturer Diameter (in.)Depth (in.)Volume (gal.)
S1 Unknown 38 40 196.38
S2 Unknown 38 40 196.38
S3 Unknown 38 40 196.38
S4 Unknown 38 40 196.38
UDCs Manufacturer Length (in.)Width (in.)Depth (in.)Volume (gal.)
UDC1 Bravo 42 22 36 144.00
UDC2 Bravo 42 22 36 144.00
Transition Sump Manufacturer Length (in.)Width (in.)Depth (in.)Volume (gal.)
N/A N/A N/A N/A N/A N/A
Spill Buckets Tank Diameter (cm.)Depth (cm.)Initial Time Initial Reading (in.)Final Reading (in.)
87 Fill 87 Tank 27 30 13:00 12 12
87 Vapor 87 Tank 27 30 13:00 10 10
91 Fill 91 Tank 27 30 13:00 14 14
91 Vapor 91 Tank 27 30 13:00 10 10
Product Piping Manufacturer Type Size (in.)Length (ft.)
87 PL1 ATP DW Flex 1.5 30
87 PL2 ATP DW Flex 1.5 50
91 PL1 ATP DW Flex 1.5 30
91 PL2 ATP DW Flex 1.5 50
Vent Piping Manufacturer Type Size (in.)Length (ft.)
87 Vent A.O. Smith SW Fiberglass 2 65
91 Vent A.O. Smith SW Fiberglass 2 75
Vapor Piping Manufacturer Type Size (in.)Length (ft.)
VR A.O. Smith SW Fiberglass 2 70
Reviewed By Date CA Tank Tester Signature Date
12/11/18
CGRS
Sergio L. Nunez
5444 Dry Creek Rd.3401 S. Chester Ave.
Sacramento, CA 95838
12/11/2018
Chris Murphy
PIPING
COMPONENTS IN CONTAINMENT
TANKS
916-991-1100/tpearce@cgrs.com
Kern
Howard Wines; CT Perkins; Shane Gardner; Kris Karns
hwines@BakersfieldFire.us; ctperkins@bakersfieldfire.us;
sgardner@bakersfieldfire.us; kkarns@bakersfieldfire.us
Bakersfield, CA 93304
Well Proximity Project Worksheet
Chester Liquor & Market
The following fueling system information has been provided by the customer and is what was observed at the site.
CA License No.
1/21/2019 06-1727
Test Date:Technicians:
Site Information Contractor Information
Facility:Contractor Name :
Address:Address:
City, State, Zip:City, State, Zip:
County:Contact:
CUPA Contact:Telephone/Email:
CUPA Phone/Email:
Date Sample ID Compound Conc., ug/L12/11/2018 Probe #1 R 0ug/L
12/11/2018 Probe #2 R 0ug/L
12/11/2018 Probe #3 R 0ug/L
12/11/2018 Probe #4 R 0ug/L
12/11/2018 Probe #5 R 0ug/L
12/11/2018 Probe #6 R 0ug/L
12/11/2018 Probe #7 R 0ug/L
12/11/2018 Probe #8 R 0ug/L
12/11/2018 Probe #9 R 0ug/L
12/11/2018 Probe #10 R 0ug/L
12/11/2018 Probe #11 R 0ug/L
12/11/2018 Probe #12 R 0ug/L
12/11/2018 Probe #13 R 0ug/L
12/11/2018 Probe #14 R 0ug/L
12/11/2018 Probe #15 R 0ug/L
12/11/2018 Probe #16 R 0ug/L
12/11/2018 Probe #17 R 0ug/L
12/11/2018 Probe #18 R 0ug/L
12/11/2018 Probe #19 R 0ug/L
Well Proximity Project Worksheet
The following fueling system information has been provided by the customer and is what was observed at the site.
12/11/18 Sergio L. Nunez
CGRSChester Liquor & Market
Probe Information
Howard Wines; CT Perkins; Shane Gardner; Kris Karns 916-991-1100/tpearce@cgrs.comhwines@BakersfieldFire.us; ctperkins@bakersfieldfire.us;
sgardner@bakersfieldfire.us; kkarns@bakersfieldfire.us
3401 S. Chester Ave.5444 Dry Creek Rd.
Bakersfield, CA 93304 Sacramento, CA 95838
Kern Chris Murphy
1 PROBE LOCATION
LEGEND
TURBINE SUMPTS
1 DISPENSER
UNDERGROUND PIPING
DATE:REVIEW:
PROJECT:DRAFT:
1/9/2019
9535aa
3401 SOUTH CHESTER AVENU
BAKERSFIELD, CALIFORNIA 93304
CHESTER LIQUOR AND MARKET
PROBE LAYOUT
DRS
17 18
16
19
4
3
2
15
6
7
8
9
10
11
12
13
14
15
VENTS
1 2
TS
TS
SUMP
SUMP
91 TA
N
K
87 TA
N
K