HomeMy WebLinkAbout2106 TAFT CATHODICSessions P.O. Box 308 Oceano, CA 93475-0308 (661) 833-9501 Fax (805) 202-8475 License 844326A/HAZ SESSTANK@AOL.COM February 7, 2018 EZ Mart Mobil 2106 Taft Highway Bakersfield, CA 93313 Re: EZ Mart Mobil 2106 Taft Highway Bakersfield, CA 93313 A Cathodic Protection certification test was performed at the above location on February 5, 2018. Upon arrival at the site a visual inspection was performed on the anode connections, rectifier and cathodic protection test leads. The rectifier settings and outputs were noted and the test was performed using a copper-copper sulfate reference cell in contact with the earth and a digital multimeter. The following readings were then obtained: On (mv) Off (mv) Tank 1 -1041 -445 Tank 2 Tank 3 -957 -959 -444 -442 The above structure-to-soil potentials were measured with a digital volt meter connected between the underground storage tank and a saturated copper-copper sulfate reference electrode in contact with the earth. The readings were obtained at the tank fills. The copper-copper sulfate cell was placed in the Cathodic Protection test box. Structure-to-soil potentials measurements for each tank exceed the recognized NACE International criteria of -850 millivolts and 300 millivolt shift for full cathodic protection. The Rectifier settings and outputs are as follows: Output Volts 22 V D.C. Amps 3 Setting Coarse B Fine 3 Hourmeter 15523 The setting was adjusted from A4 to B3. This survey was conducted in accordance with the procedures described in the NACE International Standard Recommended Practice RP0285-95, Corrosion Control of Underground Storage Tank Systems by Cathodic Protection and American Petroleum Institute (API) Recommended Practice 1632, Cathodic Protection of Underground Petroleum Storage Tanks and Piping Systems. This system is operating as designed and all underground storage tanks are receiving the required protective current. Thank you for the opportunity to assist you in this phase of your corrosion mitigation program. Should you have any questions or concerns please do not hesitate to contact us at any time. Respectfully, Juliana Sessions, Contractor Certified by: Anthony Hazelwood II NACE Corrosion Specialist #4385