HomeMy WebLinkAboutCathodicProtectionReport-STUARTS PETRO, F ST, 2019Sessions P.O. Box 308 Oceano, CA 93475-0308 (661) 833-9501 Fax (805) 202-8475 License 844326A/HAZ SESSTANK@AOL.COM April 10, 2019 Stuart’s Petroleum 11 East 4th Street Bakersfield, CA 93307 Re: Jim’s Mobil 3200 F Street Bakersfield, CA 93301 A Cathodic Protection certification test was performed at the above location on April 8, 2019. Upon arrival at the site a visual inspection was performed on the anode connections, rectifier and cathodic protection test leads. The rectifier settings and outputs were noted and the test was performed using a copper-copper sulfate reference cell in contact with the earth and a digital multimeter. The following readings were then obtained: On (mv) Off (mv) Tank 1 -995 -546 Tank 2 -995 -545 The above structure-to-soil potentials were measured with a digital volt meter connected between the underground storage tank and a saturated copper-copper sulfate reference electrode in contact with the earth. The readings were taken with the cathodic protection test leads. The copper- copper sulfate cell was placed in the northwest planter. Structure-to-soil potentials measurements for each tank exceed the recognized NACE International criteria of -850 millivolts and 300 millivolts shift for full cathodic protection. The Rectifier settings and outputs are as follows: Output Volts 20 D.C. Amps 2 Setting Coarse B Fine 1 Hourmeter 65917 This survey was conducted in accordance with the procedures described in the NACE International Standard Recommended Practice RP0285-95, Corrosion Control of Underground Storage Tank Systems by Cathodic Protection and American Petroleum Institute (API) Recommended Practice 1632, Cathodic Protection of Underground Petroleum Storage Tanks and Piping Systems. This system is operating as designed and all underground storage tanks are receiving the required protective current. Thank you for the opportunity to assist you in this phase of your corrosion mitigation program. Should you have any questions or concerns please do not hesitate to contact us at any time. Respectfully, Juliana Sessions, Contractor Certified by: Anthony Hazelwood II NACE Corrosion Specialist #4385