Loading...
HomeMy WebLinkAbout2021 FMC RESULTSCERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION Installation Repair 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either;Monitoring System Set-up Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? Secondary containment systems are free of damage, debris, or liquid? Are the audible and visual alarms operational? All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? The monitoring system set-up was reviewed, and proper settings confirmed? Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply)Sump UDC If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Page 4 of 6 7. LINE LEAK DETECTOR TESTING Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) 3 GPH 0.1 GPH 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? For electronic LLDs, does the turbine automatically shut off when a release is detected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? Were all items on the equipment manufacturer’s maintenance checklist completed? Were all LLDs confirmed operational within regulatory requirements? LLD ID LLD Model Lines Monitored Pass Fail Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Page 5 of 6 8. IN-TANK GAUGING TESTING Check this box if tank gauging is used only for inventory control. Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? Was accuracy of system’s product level readings tested? Was accuracy of system’s water level readings tested? Were all probes reinstalled properly? Were all items on the equipment manufacturer’s maintenance checklist completed? Probe ID Probe Model Tanks Monitored Pass Fail 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council, OPE = Overfill Prevention Equipment Page 1 of 2 TYPE OF ACTION Installation Repair 36 Month 1. FACILITY INFORMATION CERS ID Inspection Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Inspection Phone Mailing Address Service Technician Performing Inspection Contractor/Tank Tester License Number ICC Number Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. INSPECTION PROCEDURES INFORMATION Inspection Procedures Used Components Inspected 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING INSPECTION I hereby certify that the OPE was inspected in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.2; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages Additional copies of this page may be attached. Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) Page 2 of 2 6. OVERFILL PREVENTION EQUIPMENT DETAILS Tank ID (one OPE per column) Are both vent and tank riser piping secondarily contained? Yes No Yes No Yes No Yes No OPE Model What is the OPE response when activated? (Check all that apply.) Shut off Flow Restricts Flow Audible Alarm Visual Alarm Shut off Flow Restricts Flow Audible Alarm Visual Alarm Shut off Flow Restricts Flow Audible Alarm Visual Alarm Shut off Flow Restricts Flow Audible Alarm Visual Alarm Are flow restrictors installed on vent piping that may interfere with the OPE operation? Yes* No Yes* No Yes* No Yes* No At what level in the tank is the OPE set to activate? (Inches from bottom of tank) What is the percent capacity of the tank at which the OPE activates? Is the OPE in proper operating condition to respond when the stored substance reaches the designated regulatory level? Yes No Yes* No Yes* No Yes* No 7. SUMMARY OF TESTING RESULTS OPE Inspection Results Pass Fail Pass Fail Pass Fail Pass Fail 1 8. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. * Mark here if: Flow restrictors interfere with overfill prevention and equipment repairs required. Additional copies of this page may be attached. Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) Page 2 of 2 6. OVERFILL PREVENTION EQUIPMENT DETAILS Tank ID (one OPE per column) Are both vent and tank riser piping secondarily contained? Yes No Yes No Yes No Yes No OPE Model What is the OPE response when activated? (Check all that apply.) Shut off Flow Restricts Flow Audible Alarm Visual Alarm Shut off Flow Restricts Flow Audible Alarm Visual Alarm Shut off Flow Restricts Flow Audible Alarm Visual Alarm Shut off Flow Restricts Flow Audible Alarm Visual Alarm Are flow restrictors installed on vent piping that may interfere with the OPE operation? Yes* No Yes* No Yes* No Yes* No At what level in the tank is the OPE set to activate? (Inches from bottom of tank) What is the percent capacity of the tank at which the OPE activates? Is the OPE in proper operating condition to respond when the stored substance reaches the designated regulatory level? Yes No Yes* No Yes* No Yes* No 7. SUMMARY OF TESTING RESULTS OPE Inspection Results Pass Fail Pass Fail Pass Fail Pass Fail 1 8. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. * Mark here if: Flow restrictors interfere with overfill prevention and equipment repairs required. CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION Installation Repair 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection Nonmetallic Other Nonmetallic Other Nonmetallic Other Nonmetallic Other Is the spill container minimum capacity five gallons excluding riser volume? Yes No* Yes No* Yes No* Yes No* Method to keep spill container empty Drain Pump Other Drain Pump Other Drain Pump Other Drain Pump Other Spill Container Test Results Pass Fail Pass Fail Pass Fail Pass Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection Nonmetallic Other Nonmetallic Other Nonmetallic Other Nonmetallic Other Is the spill container minimum capacity five gallons excluding riser volume? Yes No* Yes No* Yes No* Yes No* Method to keep spill container empty Drain Pump Other Drain Pump Other Drain Pump Other Drain Pump Other Spill Container Test Results Pass Fail Pass Fail Pass Fail Pass Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] +=============================================================+| Monitoring System Report using Report Utility by FASTECH || Version: Version 6.0.0.100 |+=============================================================+ Connected on PC Port: COM3 Settings: 9600 Odd 7, 1 Connect Time/Date from PC Clock: Thursday, May 27, 2021 - 9:55:47 AM Connect Date from Monitoring System: 210527Connect Time from Monitoring System Clock: 09:56 Site Label: 207901 Costco 6883800 Rosedale HighwaBakersfield, CA ============================Request: 1 - I10200 - System ConfigurationRequest Source: Alarm History Request - Line: 1 _________________________ I10200MAY 27, 2021 10:07 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 164811 163438 2 INTERSTITIAL BD 202288 201549 3 INTERSTITIAL BD 201905 200814 4 7SMARTSENSOR BD 512457 510501 5 8SMARTSENSOR BD 39718 39619 6 4 PRB 4 LQD BD 338292 336815 7 PLLD SENSOR BD 3917 3929 8 INTERSTITIAL BD 202040 200952 9 RELAY BOARD 14986 14964 10 PLLD POWER BD 100943 100660 11 PLLD POWER BD 101593 101278 12 COMBO I/O BOARD 9988 9963 13 UNUSED 4906847 4845809 14 UNUSED 4906847 4838526 15 UNUSED 4903664 4837848 16 UNUSED 4899233 4839457 COMM 1 ELEC DISP INT. 100965 100660 COMM 2 SERIAL SAT BD 481567 481101 COMM 3 SERIAL SAT BD 484430 482867 COMM 4 UNUSED 4902395 4833000 COMM 5 RS485 SERIAL BD 68755 68572 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] COMM 6 RS232 SERIAL BD 14986 15007 ============================Request: 2 - I90200 - System Revision LevelRequest Source: Alarm History Request - Line: 2 _________________________ I90200MAY 27, 2021 10:07SOFTWARE REVISION LEVELVERSION 336.00SOFTWARE# 346336-100-A CREATED - 19.12.13.15.19 S-MODULE# 330160-164-aSYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR ISD/APMPLLD 0.10 AUTO 0.20 REPETITIVWPLLD 0.10 AUTO 0.20 REPETITIV ============================Request: 3 - I11100 - Priority Alarm HistoryRequest Source: Alarm History Request - Line: 3 _________________________ I11100MAY 27, 2021 10:07 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA PRIORITY ALARM HISTORYID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIMEQ 4 OTHER DIESEL PLLD SHUTDOWN ALARM CLEAR MAY 27 2021 10:05Q 4 OTHER DIESEL GROSS LINE FAIL CLEAR MAY 27 2021 10:05Q 3 OTHER PREMIUM PLLD SHUTDOWN ALARM CLEAR MAY 27 2021 10:04Q 3 OTHER PREMIUM GROSS LINE FAIL CLEAR MAY 27 2021 10:04Q 2 OTHER UNLEADED 87B PLLD SHUTDOWN ALARM CLEAR MAY 27 2021 10:00Q 2 OTHER UNLEADED 87B GROSS LINE FAIL CLEAR MAY 27 2021 10:00Q 1 OTHER UNLEADED 87A PLLD SHUTDOWN ALARM CLEAR MAY 27 2021 9:57Q 1 OTHER UNLEADED 87A GROSS LINE FAIL CLEAR MAY 27 2021 9:57Q 3 OTHER PREMIUM PLLD SHUTDOWN ALARM ALARM MAY 27 2021 9:41Q 3 OTHER PREMIUM GROSS LINE FAIL ALARM MAY 27 2021 9:41Q 4 OTHER DIESEL PLLD SHUTDOWN ALARM ALARM MAY 27 2021 9:32 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] Q 4 OTHER DIESEL GROSS LINE FAIL ALARM MAY 27 2021 9:32T 4 TANK Gas Additive PROBE OUT CLEAR MAY 27 2021 9:26T 4 TANK Gas Additive PROBE OUT ALARM MAY 27 2021 9:18T 4 TANK Gas Additive PROBE OUT CLEAR MAY 27 2021 9:16T 4 TANK Gas Additive PROBE OUT ALARM MAY 27 2021 9:15T 4 TANK Gas Additive PROBE OUT CLEAR MAY 27 2021 9:15Q 3 OTHER PREMIUM PLLD SHUTDOWN ALARM CLEAR MAY 27 2021 9:14T 3 TANK Premium HIGH WATER ALARM CLEAR MAY 27 2021 9:14T 3 TANK Premium HIGH WATER ALARM ALARM MAY 27 2021 9:13Q 3 OTHER PREMIUM PLLD SHUTDOWN ALARM ALARM MAY 27 2021 9:13T 4 TANK Gas Additive PROBE OUT ALARM MAY 27 2021 9:13T 4 TANK Gas Additive OVERFILL ALARM CLEAR MAY 27 2021 9:13Q 3 OTHER PREMIUM PLLD SHUTDOWN ALARM CLEAR MAY 27 2021 9:13T 3 TANK Premium HIGH WATER ALARM CLEAR MAY 27 2021 9:13T 4 TANK Gas Additive OVERFILL ALARM ALARM MAY 27 2021 9:12T 3 TANK Premium PROBE OUT CLEAR MAY 27 2021 9:11T 4 TANK Gas Additive LOW PRODUCT ALARM CLEAR MAY 27 2021 9:10T 3 TANK Premium PROBE OUT ALARM MAY 27 2021 9:10Q 1 OTHER UNLEADED 87A PLLD SHUTDOWN ALARM ALARM MAY 27 2021 9:10Q 1 OTHER UNLEADED 87A GROSS LINE FAIL ALARM MAY 27 2021 9:10T 4 TANK Gas Additive PROBE OUT CLEAR MAY 27 2021 9:10T 4 TANK Gas Additive PROBE OUT ALARM MAY 27 2021 9:08T 4 TANK Gas Additive LOW PRODUCT ALARM ALARM MAY 27 2021 9:08T 4 TANK Gas Additive PROBE OUT CLEAR MAY 27 2021 9:07T 4 TANK Gas Additive PROBE OUT ALARM MAY 27 2021 9:07T 4 TANK Gas Additive PROBE OUT CLEAR MAY 27 2021 9:06T 4 TANK Gas Additive PROBE OUT ALARM MAY 27 2021 9:06L16 ANNULAR ADDITIVE ANNULAR FUEL ALARM CLEAR MAY 27 2021 9:05L16 ANNULAR ADDITIVE ANNULAR FUEL ALARM ALARM MAY 27 2021 9:05T 3 TANK Premium OVERFILL ALARM CLEAR MAY 27 2021 9:05L17 DISP PAN ADDITIVE VENT BOX FUEL ALARM CLEAR MAY 27 2021 9:05L17 DISP PAN ADDITIVE VENT BOX FUEL ALARM ALARM MAY 27 2021 9:04L17 DISP PAN ADDITIVE VENT BOX SENSOR OUT ALARM CLEAR MAY 27 2021 9:04L17 DISP PAN ADDITIVE VENT BOX SENSOR OUT ALARM ALARM MAY 27 2021 9:04T 3 TANK Premium OVERFILL ALARM ALARM MAY 27 2021 9:03T 3 TANK Premium HIGH WATER ALARM ALARM MAY 27 2021 9:02Q 3 OTHER PREMIUM PLLD SHUTDOWN ALARM ALARM MAY 27 2021 9:02Q 2 OTHER UNLEADED 87B PLLD SHUTDOWN ALARM ALARM MAY 27 2021 9:00Q 2 OTHER UNLEADED 87B GROSS LINE FAIL ALARM MAY 27 2021 9:00 ============================Request: 4 - I11200 - Non-Priority Alarm historyRequest Source: Alarm History Request - Line: 4 _________________________ I11200MAY 27, 2021 10:07 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA NON-PRIORITY ALARM HISTORYID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] T 3 TANK Premium HIGH WATER WARNING CLEAR MAY 27 2021 9:14T 3 TANK Premium HIGH WATER WARNING ALARM MAY 27 2021 9:13T 3 TANK Premium HIGH WATER WARNING CLEAR MAY 27 2021 9:13T 4 TANK Gas Additive DELIVERY NEEDED CLEAR MAY 27 2021 9:10T 4 TANK Gas Additive DELIVERY NEEDED ALARM MAY 27 2021 9:08T 3 TANK Premium HIGH WATER WARNING ALARM MAY 27 2021 9:02T 3 TANK Premium HIGH PRODUCT ALARM CLEAR MAY 27 2021 8:59T 3 TANK Premium HIGH PRODUCT ALARM ALARM MAY 27 2021 8:58T 3 TANK Premium HIGH PRODUCT ALARM CLEAR MAY 27 2021 8:56T 3 TANK Premium HIGH PRODUCT ALARM ALARM MAY 27 2021 8:53T 2 TANK Unleaded 87B HIGH PRODUCT ALARM CLEAR MAY 27 2021 8:51T 2 TANK Unleaded 87B HIGH PRODUCT ALARM ALARM MAY 27 2021 8:46T 5 TANK Diesel HIGH PRODUCT ALARM CLEAR MAY 27 2021 8:35T 5 TANK Diesel LOW TEMP WARNING CLEAR MAY 27 2021 8:32T 5 TANK Diesel LOW TEMP WARNING ALARM MAY 27 2021 8:32T 5 TANK Diesel HIGH PRODUCT ALARM ALARM MAY 27 2021 8:32L 9 STP SUMP PREMIUM STP LIQUID WARNING CLEAR MAY 27 2021 8:12L 9 STP SUMP PREMIUM STP LIQUID WARNING ALARM MAY 27 2021 8:11L 8 PIPE PREMIUM FILL LIQUID WARNING CLEAR MAY 27 2021 8:10L 8 PIPE PREMIUM FILL LIQUID WARNING ALARM MAY 27 2021 8:10L 6 STP SUMP UNLEADED 87B STP LIQUID WARNING CLEAR MAY 27 2021 8:08L 6 STP SUMP UNLEADED 87B STP LIQUID WARNING ALARM MAY 27 2021 8:07L 5 PIPE UNLEADED 87B FILL LIQUID WARNING CLEAR MAY 27 2021 8:07L 5 PIPE UNLEADED 87B FILL LIQUID WARNING ALARM MAY 27 2021 8:06L 2 PIPE UNLEADED 87A FILL LIQUID WARNING CLEAR MAY 27 2021 8:04L 2 PIPE UNLEADED 87A FILL LIQUID WARNING ALARM MAY 27 2021 8:03 SYSTEM PRINTER ERROR CLEAR MAY 24 2021 13:02 SYSTEM PAPER OUT CLEAR MAY 24 2021 13:02 SYSTEM PRINTER ERROR ALARM MAY 24 2021 13:02 SYSTEM PAPER OUT ALARM MAY 24 2021 13:02 SYSTEM PRINTER ERROR CLEAR MAY 17 2021 17:01 SYSTEM PAPER OUT CLEAR MAY 17 2021 17:01 SYSTEM PRINTER ERROR ALARM MAY 17 2021 17:01 SYSTEM PAPER OUT ALARM MAY 17 2021 17:01h 2 OTHER FP2: BLEND2 DEGRD COLLECT WARN CLEAR MAY 17 2021 12:43h 1 OTHER FP1: BLEND2 DEGRD COLLECT WARN CLEAR MAY 17 2021 12:42h 1 OTHER FP1: BLEND2 DEGRD COLLECT WARN ALARM MAY 14 2021 5:01h 2 OTHER FP2: BLEND2 DEGRD COLLECT WARN ALARM MAY 13 2021 5:01 SYSTEM PRINTER ERROR CLEAR MAY 11 2021 20:38 SYSTEM PAPER OUT CLEAR MAY 11 2021 20:38 SYSTEM PAPER OUT ALARM MAY 11 2021 20:38 SYSTEM PRINTER ERROR ALARM MAY 11 2021 20:38T 5 TANK Diesel DELIVERY NEEDED CLEAR MAY 11 2021 17:25T 5 TANK Diesel DELIVERY NEEDED ALARM MAY 11 2021 13:01h 1 OTHER FP1: BLEND2 DEGRD COLLECT WARN CLEAR MAY 10 2021 15:08h 1 OTHER FP1: BLEND2 DEGRD COLLECT WARN ALARM MAY 8 2021 5:01 SYSTEM PRINTER ERROR CLEAR MAY 6 2021 8:22 SYSTEM PRINTER ERROR ALARM MAY 6 2021 8:22h 2 OTHER FP2: BLEND2 DEGRD COLLECT WARN CLEAR MAY 6 2021 5:00 SYSTEM PRINTER ERROR CLEAR MAY 4 2021 19:42 ============================Request: 5 - I20600 - In-Tank Alarm historyRequest Source: Alarm History Request - Line: 5 _________________________ file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] I20600MAY 27, 2021 10:07 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA TANK ALARM HISTORY TANK 1 Unleaded 87A OVERFILL ALARM MAY 27, 2021 8:26 APR 10, 2021 1:23 MAR 11, 2021 21:46 PROBE OUT MAY 27, 2021 8:26 MAY 27, 2021 8:22 MAR 11, 2021 21:57 DELIVERY NEEDED APR 20, 2021 14:07 APR 5, 2021 16:26 LOW TEMP WARNING MAR 11, 2021 21:58 TANK 2 Unleaded 87B HIGH WATER ALARM MAY 27, 2020 8:00 OVERFILL ALARM MAY 27, 2021 8:45 MAR 11, 2021 21:46 NOV 30, 2020 8:53 HIGH PRODUCT ALARM MAY 27, 2021 8:46 MAR 11, 2021 21:44 MAY 27, 2020 8:00 PROBE OUT MAY 27, 2021 8:50 MAY 27, 2021 8:44 MAR 11, 2021 21:59 HIGH WATER WARNING MAY 27, 2020 8:00 DELIVERY NEEDED APR 21, 2021 8:55 APR 20, 2021 13:55 APR 14, 2021 17:52 TANK 3 Premium HIGH WATER ALARM MAY 27, 2021 9:13 MAY 27, 2021 9:02 OVERFILL ALARM MAY 27, 2021 9:03 MAR 20, 2021 10:36 MAR 11, 2021 21:51 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] HIGH PRODUCT ALARM MAY 27, 2021 8:58 MAY 27, 2021 8:53 MAR 11, 2021 21:45 PROBE OUT MAY 27, 2021 9:10 MAY 27, 2021 8:57 MAY 27, 2021 8:52 HIGH WATER WARNING MAY 27, 2021 9:13 MAY 27, 2021 9:02 DELIVERY NEEDED APR 16, 2021 17:26 APR 10, 2021 12:10 APR 5, 2021 20:12 TANK 4 Gas Additive OVERFILL ALARM MAY 27, 2021 9:12 MAR 11, 2021 20:56 MAY 27, 2020 8:07 LOW PRODUCT ALARM MAY 27, 2021 9:08 PROBE OUT MAY 27, 2021 9:18 MAY 27, 2021 9:15 MAY 27, 2021 9:13 DELIVERY NEEDED MAY 27, 2021 9:08 LOW TEMP WARNING MAY 27, 2020 8:07 TANK 5 Diesel OVERFILL ALARM MAY 27, 2021 8:33 MAY 8, 2021 9:56 APR 7, 2021 19:30 HIGH PRODUCT ALARM MAY 27, 2021 8:32 MAR 11, 2021 21:48 MAY 27, 2020 7:57 PROBE OUT MAY 27, 2021 8:35 MAY 27, 2021 8:31 MAY 27, 2021 7:59 DELIVERY NEEDED MAY 11, 2021 13:01 JAN 26, 2021 17:08 JAN 26, 2021 7:42 MAX PRODUCT ALARM MAR 11, 2021 21:53 LOW TEMP WARNING MAY 27, 2021 8:32 APR 5, 2021 23:32 TANK 9 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 ============================Request: 6 - I38200 - Pressure line Leak Alarm HistoryRequest Source: Alarm History Request - Line: 6 _________________________ I38200MAY 27, 2021 10:08 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:UNLEADED 87A MAY 27, 2021 9:10 PLLD SHUTDOWN ALARM MAY 27, 2021 9:10 GROSS LINE FAIL MAY 27, 2021 8:34 PLLD SHUTDOWN ALARM MAY 27, 2021 8:33 PLLD SHUTDOWN ALARM MAY 27, 2021 8:32 PLLD SHUTDOWN ALARM MAY 27, 2021 8:32 PLLD SHUTDOWN ALARM MAY 27, 2021 8:31 PLLD SHUTDOWN ALARM MAY 27, 2021 8:30 PLLD SHUTDOWN ALARM MAY 27, 2021 8:30 PLLD SHUTDOWN ALARM MAY 27, 2021 8:29 PLLD SHUTDOWN ALARM Q 2:UNLEADED 87B MAY 27, 2021 9:00 PLLD SHUTDOWN ALARM MAY 27, 2021 9:00 GROSS LINE FAIL MAY 27, 2021 8:34 PLLD SHUTDOWN ALARM MAY 27, 2021 8:33 PLLD SHUTDOWN ALARM MAY 27, 2021 8:32 PLLD SHUTDOWN ALARM MAY 27, 2021 8:32 PLLD SHUTDOWN ALARM MAY 27, 2021 8:31 PLLD SHUTDOWN ALARM MAY 27, 2021 8:30 PLLD SHUTDOWN ALARM MAY 27, 2021 8:30 PLLD SHUTDOWN ALARM MAY 27, 2021 8:29 PLLD SHUTDOWN ALARM Q 3:PREMIUM file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] MAY 27, 2021 9:41 PLLD SHUTDOWN ALARM MAY 27, 2021 9:41 GROSS LINE FAIL MAY 27, 2021 9:13 PLLD SHUTDOWN ALARM MAY 27, 2021 9:02 PLLD SHUTDOWN ALARM MAY 27, 2021 8:34 PLLD SHUTDOWN ALARM MAY 27, 2021 8:33 PLLD SHUTDOWN ALARM MAY 27, 2021 8:32 PLLD SHUTDOWN ALARM MAY 27, 2021 8:32 PLLD SHUTDOWN ALARM MAY 27, 2021 8:31 PLLD SHUTDOWN ALARM MAY 27, 2021 8:30 PLLD SHUTDOWN ALARM Q 4:DIESEL MAY 27, 2021 9:32 PLLD SHUTDOWN ALARM MAY 27, 2021 9:32 GROSS LINE FAIL MAY 27, 2021 8:30 PLLD SHUTDOWN ALARM MAY 27, 2021 8:29 PLLD SHUTDOWN ALARM MAY 27, 2021 8:28 PLLD SHUTDOWN ALARM MAY 27, 2021 8:28 PLLD SHUTDOWN ALARM MAY 27, 2021 8:27 PLLD SHUTDOWN ALARM MAY 27, 2021 8:25 PLLD SHUTDOWN ALARM MAY 27, 2021 8:23 PLLD SHUTDOWN ALARM MAY 27, 2021 8:23 PLLD SHUTDOWN ALARM ============================Request: 7 - I30200 - Liquid Sensor Alarm historyRequest Source: Alarm History Request - Line: 7 _________________________ I30200MAY 27, 2021 10:08 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNLEADED 87A ANNULAR MAY 27, 2021 8:03 HIGH LIQUID ALARM MAY 27, 2021 8:02 LOW LIQUID ALARM MAY 27, 2021 8:00 SENSOR OUT ALARM 2 UNLEADED 87A FILL MAY 27, 2021 8:03 LIQUID WARNING MAY 27, 2021 8:00 SENSOR OUT ALARM MAR 11, 2021 22:13 LIQUID WARNING 3 UNLEADED 87A STP MAY 27, 2021 8:04 FUEL ALARM MAY 27, 2021 8:00 SENSOR OUT ALARM MAR 11, 2021 22:10 FUEL ALARM 4 UNLEADED 87B ANNULAR MAY 27, 2021 8:06 HIGH LIQUID ALARM MAY 27, 2021 8:05 LOW LIQUID ALARM file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] MAY 27, 2021 8:00 SENSOR OUT ALARM 5 UNLEADED 87B FILL MAY 27, 2021 8:06 LIQUID WARNING MAY 27, 2021 8:00 SENSOR OUT ALARM MAR 11, 2021 22:15 LIQUID WARNING 6 UNLEADED 87B STP MAY 27, 2021 8:07 LIQUID WARNING MAY 27, 2021 8:01 SENSOR OUT ALARM MAY 27, 2021 8:01 FUEL ALARM 7 PREMIUM ANNULAR MAY 27, 2021 8:09 HIGH LIQUID ALARM MAY 27, 2021 8:08 LOW LIQUID ALARM MAY 27, 2021 8:00 SENSOR OUT ALARM 8 PREMIUM FILL MAY 27, 2021 8:10 LIQUID WARNING MAY 27, 2021 8:00 SENSOR OUT ALARM MAR 11, 2021 22:20 LIQUID WARNING 9 PREMIUM STP MAY 27, 2021 8:11 LIQUID WARNING MAY 27, 2021 7:59 SENSOR OUT ALARM MAR 11, 2021 22:18 LIQUID WARNING 10 DISPENSER PAN 1-2 MAY 27, 2021 8:33 FUEL ALARM MAY 27, 2021 7:59 SENSOR OUT ALARM MAR 11, 2021 22:23 FUEL ALARM 11 DISPENSER PAN 3-4 MAY 27, 2021 8:34 FUEL ALARM MAY 27, 2021 7:59 SENSOR OUT ALARM APR 20, 2021 1:54 FUEL ALARM 12 DISPENSER PAN 5-6 MAY 27, 2021 8:32 FUEL ALARM MAY 27, 2021 7:59 SENSOR OUT ALARM MAR 11, 2021 22:24 FUEL ALARM 13 DISPENSER PAN 7-8 MAY 27, 2021 8:32 FUEL ALARM MAY 27, 2021 7:59 SENSOR OUT ALARM APR 1, 2021 22:01 FUEL ALARM 14 DISPENSER PAN 9-10 MAY 27, 2021 8:30 FUEL ALARM MAY 27, 2021 7:59 SENSOR OUT ALARM MAR 11, 2021 22:27 FUEL ALARM 15 DISPENSER PAN 11-12 MAY 27, 2021 8:31 FUEL ALARM MAY 27, 2021 7:59 SENSOR OUT ALARM MAR 11, 2021 22:26 FUEL ALARM 16 ADDITIVE ANNULAR MAY 27, 2021 9:05 FUEL ALARM MAY 27, 2021 8:00 SENSOR OUT ALARM MAR 11, 2021 21:49 SENSOR OUT ALARM 17 ADDITIVE VENT BOX MAY 27, 2021 9:04 FUEL ALARM MAY 27, 2021 9:04 SENSOR OUT ALARM MAY 27, 2021 7:59 SENSOR OUT ALARM 21 DIESEL ANNULAR MAY 27, 2021 8:13 HIGH LIQUID ALARM MAY 27, 2021 8:12 LOW LIQUID ALARM MAY 27, 2021 7:59 SENSOR OUT ALARM file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] 22 DISPENSER PAN 13-14 MAY 27, 2021 8:30 FUEL ALARM MAY 27, 2021 8:29 SENSOR OUT ALARM MAY 27, 2021 8:28 LOW LIQUID ALARM 23 DISPENSER PAN 15-16 MAY 27, 2021 8:28 FUEL ALARM MAY 27, 2021 8:27 SENSOR OUT ALARM MAY 27, 2021 8:25 LOW LIQUID ALARM 24 DIESEL FILL MAY 27, 2021 8:17 SENSOR OUT ALARM MAY 27, 2021 8:17 FUEL ALARM MAY 27, 2021 8:16 SENSOR OUT ALARM 25 DIESEL STP MAY 27, 2021 8:23 SENSOR OUT ALARM MAY 27, 2021 8:20 SENSOR OUT ALARM MAY 27, 2021 8:19 FUEL ALARM 26 DIESEL VENT MAY 27, 2021 8:15 FUEL ALARM MAY 27, 2021 8:14 SENSOR OUT ALARM MAY 27, 2021 8:14 LOW LIQUID ALARM 27 ARID VENT BOX MAY 27, 2021 8:40 FUEL ALARM MAY 27, 2021 8:39 SENSOR OUT ALARM MAY 27, 2021 7:58 SENSOR OUT ALARM ============================Request: 8 - I31600 - Smart Sensor Alarm historyRequest Source: Alarm History Request - Line: 8 _________________________ I31600MAY 27, 2021 10:08 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VFM 13-14 MAR 11, 2021 21:50 COMMUNICATION ALARM 2 VFM 15,16 MAR 11, 2021 21:49 COMMUNICATION ALARM 3 DIESEL PRODUCT VAC. MAY 27, 2021 8:23 NO VACUUM ALARM MAY 27, 2021 8:20 HIGH LIQUID ALARM MAR 11, 2021 21:54 NO VACUUM ALARM 4 DIESEL VENT VAC. MAY 27, 2021 8:22 NO VACUUM ALARM MAY 27, 2021 8:20 HIGH LIQUID ALARM MAR 11, 2021 21:53 NO VACUUM ALARM 8 ATM P 9 VFM 1-2 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] MAR 11, 2021 21:49 COMMUNICATION ALARM 10 VFM 3-4 MAR 11, 2021 21:49 COMMUNICATION ALARM 11 VFM 5-6 MAR 11, 2021 21:49 COMMUNICATION ALARM SEP 4, 2020 10:30 COMMUNICATION ALARM 12 VFM 7-8 MAR 11, 2021 21:49 COMMUNICATION ALARM 13 VFM 9-10 MAR 11, 2021 21:50 COMMUNICATION ALARM 14 VFM 11-12 MAR 11, 2021 21:50 COMMUNICATION ALARM 16 PRESURE SENSOR 3-4 MAR 11, 2021 21:48 COMMUNICATION ALARM ============================Request: 9 - I40200 - Input Alarm HistoryRequest Source: Alarm History Request - Line: 9 _________________________ I40200MAY 27, 2021 10:08 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA INPUT LOCATION 1 ARID FAULT APR 22, 2021 21:38 EXTERN INPUT ALARM APR 15, 2021 7:54 EXTERN INPUT ALARM APR 15, 2021 7:06 EXTERN INPUT ALARM APR 22, 2021 23:27 EXTERN INPUT NORMAL APR 15, 2021 7:55 EXTERN INPUT NORMAL APR 15, 2021 7:06 EXTERN INPUT NORMAL 2 ARID ACTIVE APR 15, 2021 7:43 EXTERN INPUT ALARM APR 15, 2021 7:45 EXTERN INPUT NORMAL ============================Request: 10 - I40300 - Input-Generator Alarm HistoryRequest Source: Alarm History Request - Line: 10 _________________________ I40300MAY 27, 2021 10:08 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] INPUT / GENERATOR ALARM HISTORY REPORT INPUT LOCATION 1 ARID FAULT APR 22, 2021 21:38 EXTERN INPUT ALARM APR 15, 2021 7:54 EXTERN INPUT ALARM APR 15, 2021 7:06 EXTERN INPUT ALARM APR 22, 2021 23:27 EXTERN INPUT NORMAL APR 15, 2021 7:55 EXTERN INPUT NORMAL APR 15, 2021 7:06 EXTERN INPUT NORMAL 2 ARID ACTIVE APR 15, 2021 7:43 EXTERN INPUT ALARM APR 15, 2021 7:45 EXTERN INPUT NORMAL ============================Request: 11 - I34200 - Type A 2 Wire CL Alarm HistoryRequest Source: Alarm History Request - Line: 11 _________________________ I34200MAY 27, 2021 10:08 ============================Request: 12 - I34700 - Type B 3 Wire CL Alarm HistoryRequest Source: Alarm History Request - Line: 12 _________________________ I34700MAY 27, 2021 10:08 ============================Request: 13 - IV0100 - ISD Alarm Status Request Source: Alarm History Request - Line: 13 _________________________ IV0100MAY 27, 2021 10:08 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSISTISD TYPE: 01.06VAPOR PROCESSOR TYPE: ARID PERMEATOR OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :NOTEST file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688alarm.txt[6/3/2021 5:46:34 PM] ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% VAPOR PROCESSOR :PASS WARNING ALARMSDATE TIME DESCRIPTION READING VALUE21-05-17 05:01:09 A/L RATIO DEGRADATION FP 2 BLEND2 0.6821-05-17 05:01:09 A/L RATIO DEGRADATION FP 1 BLEND2 0.6921-05-16 05:01:36 A/L RATIO DEGRADATION FP 2 BLEND2 0.7221-05-16 05:01:36 A/L RATIO DEGRADATION FP 1 BLEND2 0.7121-05-15 05:01:33 A/L RATIO DEGRADATION FP 2 BLEND2 0.7321-05-15 05:01:33 A/L RATIO DEGRADATION FP 1 BLEND2 0.7121-05-14 05:01:24 A/L RATIO DEGRADATION FP 2 BLEND2 0.7721-05-14 05:01:24 A/L RATIO DEGRADATION FP 1 BLEND2 0.7221-05-13 05:01:09 A/L RATIO DEGRADATION FP 2 BLEND2 0.7921-05-10 05:01:09 A/L RATIO DEGRADATION FP 1 BLEND2 0.76 FAILURE ALARMSDATE TIME DESCRIPTION READING VALUE19-12-02 05:01:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND2 BLKD19-07-10 05:01:12 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.7119-05-13 05:01:17 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.4915-11-03 00:00:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.62 SHUTDOWN & MISCELLANEOUS EVENTSDATE TIME DESCRIPTION ACTION/NAME21-05-27 05:01:09 READINESS ISD:PP EVR:PNP EVR READINESS PENDING21-05-26 05:01:09 READINESS ISD:PP EVR:PNP EVR READINESS PENDING21-05-25 13:41:16 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED 21-05-25 13:41:14 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 21-05-25 13:07:01 READINESS ISD:PP EVR:NNN EVR READINESS PENDING21-05-25 13:07:01 ISD STARTUP 21-05-25 13:06:58 ISD SHUTDOWN 21-05-17 12:43:00 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED 21-05-17 12:42:58 COLLECTION TEST HH01 GRADE TEST MANUALLY CLEARED 21-05-10 15:08:26 COLLECTION TEST HH01 GRADE TEST MANUALLY CLEARED End of Report: 210527 +============================================================================| Monitoring System Report Saved at: Thursday, May 27, 2021 - 10:09:09 AM| (Report Saved Date/Time from PC Clock)| Using Monitoring System Report Utility by FASTECH || Version: Version 6.0.0.100 |+============================================================================ file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] +=============================================================+| Monitoring System Report using Report Utility by FASTECH || Version: Version 6.0.0.100 |+=============================================================+ Connected on PC Port: COM3 Settings: 9600 Odd 7, 1 Connect Time/Date from PC Clock: Thursday, May 27, 2021 - 9:55:47 AM Connect Date from Monitoring System: 210527Connect Time from Monitoring System Clock: 09:56 Site Label: 207901 Costco 6883800 Rosedale HighwaBakersfield, CA ============================Request: 1 - 200 - Site LocationRequest Source: Monitor System Configuration Requests - Line: 1 _________________________ 200207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA MAY 27, 2021 9:56 TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 Unleaded 87A 14420 80.56 0.0 76.1 4749 2 Unleaded 87B 13963 80.24 0.0 76.0 4614 3 Premium 13924 79.59 0.0 75.4 4892 4 Gas Additive 416 16.30 87.4 784 5 Diesel 12636 87.81 0.0 75.0 2093 ============================Request: 2 - I90500 - System Revision LevelRequest Source: Monitor System Configuration Requests - Line: 2 _________________________ I90500MAY 27, 2021 9:56SOFTWARE REVISION LEVELVERSION 336.00SOFTWARE# 346336-100-A CREATED - 19.12.13.15.19 S-MODULE# 330160-164-aSYSTEM FEATURES: file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS BIR ISD/APMPLLD 0.10 AUTO 0.20 REPETITIVWPLLD 0.10 AUTO 0.20 REPETITIV ============================Request: 3 - I50500 - System Type & languageRequest Source: Monitor System Configuration Requests - Line: 3 _________________________ I50500MAY 27, 2021 9:56 SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S.SYSTEM LANGUAGE ENGLISHSYSTEM DATE/TIME FORMATMON DD YYYY HH:MM:SS ============================Request: 4 - I50201 - Shift Start Time 1Request Source: Monitor System Configuration Requests - Line: 4 _________________________ I50201MAY 27, 2021 9:56 SHIFT TIME 1 : DISABLED ============================Request: 5 - I50202 - Shift Start Time 2Request Source: Monitor System Configuration Requests - Line: 5 _________________________ I50202MAY 27, 2021 9:56 SHIFT TIME 2 : DISABLED ============================Request: 6 - I50203 - Shift Start Time 3 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] Request Source: Monitor System Configuration Requests - Line: 6 _________________________ I50203MAY 27, 2021 9:56 SHIFT TIME 3 : DISABLED ============================Request: 7 - I50204 - Shift Start Time 4Request Source: Monitor System Configuration Requests - Line: 7 _________________________ I50204MAY 27, 2021 9:56 SHIFT TIME 4 : DISABLED ============================Request: 8 - I54600 - Tank Periodic Test Needed WarningRequest Source: Monitor System Configuration Requests - Line: 8 _________________________ I54600MAY 27, 2021 9:56 TANK PER TST NEEDED WRN: DISABLED ============================Request: 9 - I54900 - Tank Annual Test Needed WarningRequest Source: Monitor System Configuration Requests - Line: 9 _________________________ I54900MAY 27, 2021 9:56 TANK ANN TST NEEDED WRN: DISABLED ============================Request: 10 - I55300 - Line Re-Enable MethodRequest Source: Monitor System Configuration Requests - Line: 10 _________________________ I55300MAY 27, 2021 9:57 LINE RE-ENABLE METHODPASS LINE TEST file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] ============================Request: 11 - I55600 - Line periodic Test Needed WarningRequest Source: Monitor System Configuration Requests - Line: 11 _________________________ I55600MAY 27, 2021 9:57 LINE PER TST NEEDED WRN: DISABLED ============================Request: 12 - I55900 - Line Annual Test Needed WarningRequest Source: Monitor System Configuration Requests - Line: 12 _________________________ I55900MAY 27, 2021 9:57 LINE ANN TST NEEDED WRN: DISABLED ============================Request: 13 - I50D00 - Print Temperature CompensationRequest Source: Monitor System Configuration Requests - Line: 13 _________________________ I50D00MAY 27, 2021 9:57 PRINT TC VOLUMESENABLED ============================Request: 14 - I50E00 - Temperature Compensation ValueRequest Source: Monitor System Configuration Requests - Line: 14 _________________________ I50E00MAY 27, 2021 9:57 TEMP COMPENSATIONVALUE (DEG F ): 60.0 ============================Request: 15 - I60B00 - Tank Stick Height Function EnableRequest Source: Monitor System Configuration Requests - Line: 15 _________________________ file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] I60B00MAY 27, 2021 9:57 STICK HEIGHT OFFSET ENABLE STATUSDISABLED ============================Request: 16 - I51400 - H-Protocol Height-Volume FormatRequest Source: Monitor System Configuration Requests - Line: 16 _________________________ I51400MAY 27, 2021 9:57 H-PROTOCOL DATA FORMATHEIGHT ============================Request: 17 - I51A01 - Auto Daylight Saving TimeRequest Source: Monitor System Configuration Requests - Line: 17 _________________________ I51A01MAY 27, 2021 9:57 DAYLIGHT SAVING TIMEENABLED ON ============================Request: 18 - I51B00 - Start-End Daylight Saving TimeRequest Source: Monitor System Configuration Requests - Line: 18 _________________________ I51B00MAY 27, 2021 9:57 DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM ============================Request: 19 - I51600 - Re-Direct Local PrintoutRequest Source: Monitor System Configuration Requests - Line: 19 _________________________ I51600 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] MAY 27, 2021 9:57 RE-DIRECT LOCAL PRINTOUTDISABLED ============================Request: 20 - I50400 - RS-232 Security CodeRequest Source: Monitor System Configuration Requests - Line: 20 _________________________ I50400MAY 27, 2021 9:57 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED ============================Request: 21 - I21900 - Tank Chart SecurityRequest Source: Monitor System Configuration Requests - Line: 21 _________________________ I21900MAY 27, 2021 9:57 TANK CHART SECURITYDISABLED ============================Request: 22 - I5BD00 - Custom AlarmsRequest Source: Monitor System Configuration Requests - Line: 22 _________________________ I5BD00MAY 27, 2021 9:57 CUSTOM ALARM LABELS DISABLED ============================ file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] Request: 23 - I56000 - Mass Density Enable-DisableRequest Source: Monitor System Configuration Requests - Line: 23 _________________________ I56000MAY 27, 2021 9:57 MASS/DENSITY DISABLED ============================Request: 24 - I88101 - Comm Port 1 SettingsRequest Source: Monitor System Configuration Requests - Line: 24 _________________________ I88101MAY 27, 2021 9:57PORT SETTINGS: COMM BOARD : 1 (EDIM )RS-232 SECURITYCODE : DISABLED ============================Request: 25 - I88102 - Comm Port 2 SettingsRequest Source: Monitor System Configuration Requests - Line: 25 _________________________ I88102MAY 27, 2021 9:57PORT SETTINGS: COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATARS-232 SECURITYCODE : DISABLED DTR NORMAL STATE: HIGH ============================Request: 26 - I88103 - Comm Port 3 SettingsRequest Source: Monitor System Configuration Requests - Line: 26 _________________________ I88103MAY 27, 2021 9:57PORT SETTINGS: file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] COMM BOARD : 3 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATARS-232 SECURITYCODE : DISABLED DTR NORMAL STATE: HIGH ============================Request: 27 - I88104 - Comm Port 4 SettingsRequest Source: Monitor System Configuration Requests - Line: 27 _________________________ I88104MAY 27, 2021 9:57 ============================Request: 28 - I88105 - Comm Port 5 SettingsRequest Source: Monitor System Configuration Requests - Line: 28 _________________________ I88105MAY 27, 2021 9:57PORT SETTINGS: COMM BOARD : 5 (RS-485) BAUD RATE : 9600 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATARS-232 SECURITYCODE : DISABLED ============================Request: 29 - I88106 - Comm Port 6 SettingsRequest Source: Monitor System Configuration Requests - Line: 29 _________________________ I88106MAY 27, 2021 9:57PORT SETTINGS: COMM BOARD : 6 (RS-232) BAUD RATE : 9600 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATARS-232 SECURITYCODE : DISABLED file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] ============================Request: 30 - I52000 - Receiver Auto Dial Type and Start TimeRequest Source: Monitor System Configuration Requests - Line: 30 _________________________ I52000MAY 27, 2021 9:57 RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE AUG 29, 2013 DISABLED 2 ON DATE AUG 29, 2013 DISABLED 3 ON DATE AUG 29, 2013 DISABLED 4 ON DATE AUG 29, 2013 DISABLED 5 ON DATE AUG 29, 2013 DISABLED 6 ON DATE AUG 29, 2013 DISABLED 7 ON DATE AUG 29, 2013 DISABLED 8 WEEKLY THR 4:39 PM ============================Request: 31 - I60100 - Tank ConfigurationRequest Source: Monitor System Configuration Requests - Line: 31 _________________________ I60100MAY 27, 2021 9:57 TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 Unleaded 87A ON 2 Unleaded 87B ON 3 Premium ON 4 Gas Additive ON 5 Diesel ON 6 Diesel Additive OFF 7 OFF 8 OFF ============================Request: 32 - I60200 - Tank Product LabelRequest Source: Monitor System Configuration Requests - Line: 32 _________________________ I60200MAY 27, 2021 9:57 TANK PRODUCT LABEL TANK PRODUCT LABEL file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 1 Unleaded 87A 2 Unleaded 87B 3 Premium 4 Gas Additive 5 Diesel 6 Diesel Additive 7 8 ============================Request: 33 - I60300 - Tank Product CodeRequest Source: Monitor System Configuration Requests - Line: 33 _________________________ I60300MAY 27, 2021 9:57 TANK PRODUCT CODE TANK PRODUCT LABEL 1 Unleaded 87A 1 2 Unleaded 87B 1 3 Premium 2 4 Gas Additive 3 5 Diesel 4 6 Diesel Additive 5 7 7 8 8 ============================Request: 34 - I60900 - Tank Thermal Expansion Coefficient Request Source: Monitor System Configuration Requests - Line: 34 _________________________ I60900MAY 27, 2021 9:57 TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 Unleaded 87A 0.000700 2 Unleaded 87B 0.000700 3 Premium 0.000700 4 Gas Additive 0.000405 5 Diesel 0.000450 6 Diesel Additive 0.000405 7 0.000000 8 0.000000 ============================Request: 35 - I60700 - Tank DiameterRequest Source: Monitor System Configuration Requests - Line: 35 _________________________ file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] I60700MAY 27, 2021 9:57 TANK DIAMETER TANK PRODUCT LABEL INCHES 1 Unleaded 87A 111.91 2 Unleaded 87B 110.30 3 Premium 111.50 4 Gas Additive 47.00 5 Diesel 113.30 6 Diesel Additive 0.00 7 0.00 8 0.00 ============================Request: 36 - I60A00 - Tank Full VolumeRequest Source: Monitor System Configuration Requests - Line: 36 _________________________ I60A00MAY 27, 2021 9:57 TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 Unleaded 87A 20 PTS 19169 2 Unleaded 87B 20 PTS 18577 3 Premium 20 PTS 18816 4 Gas Additive LINEAR 1200 5 Diesel 20 PTS 14729 6 Diesel Additive 1 PT 0 7 1 PT 0 8 1 PT 0 ============================Request: 37 - I60400 - Tank 1 Point Full Volume HeightRequest Source: Monitor System Configuration Requests - Line: 37 _________________________ I60400MAY 27, 2021 9:57 TANK FULL VOLUME file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 19169 2 Unleaded 87B 18577 3 Premium 18816 4 Gas Additive 1200 5 Diesel 14729 6 Diesel Additive 0 7 0 8 0 ============================Request: 38 - I60500 - Tank 4 Point Full, 3/4, 1/2. 1/4 VolumesRequest Source: Monitor System Configuration Requests - Line: 38 _________________________ I60500MAY 27, 2021 9:57 TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 19169 15086 9145 3336 2 Unleaded 87B 18577 14451 8639 3027 3 Premium 18816 14723 8829 3118 4 Gas Additive 1200 0 0 0 5 Diesel 14729 11711 7094 2567 6 Diesel Additive 0 0 0 0 7 0 0 0 0 8 0 0 0 0 ============================Request: 39 - I60600 - Tank 20 Point Full, 95%, 90%, ...volumesRequest Source: Monitor System Configuration Requests - Line: 39 _________________________ I60600MAY 27, 2021 9:57 TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 19169 18676 17966 17108 16140 15086 13967 12800 11598 10375 9145 7919 6712 5535 4405 3336 2347 1463 717 168 2 Unleaded 87B 18577 18042 17315 16455 15492 14451 13350 12205 11029 9836 8639 7448 6278 5141 4053 3027 2086 1252 562 83 3 Premium 18816 18303 17589 16734 15770 14723 13611 12452 11259 10047 8829 7618 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 6427 5270 4161 3118 2160 1312 607 110 4 Gas Additive 1200 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 Diesel 14729 14393 13879 13244 12514 11711 10850 9946 9011 8056 7094 6136 5192 4274 3394 2567 1806 1130 564 147 6 Diesel Additive 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ============================Request: 40 - I61500 - BIR Meter Data PresentRequest Source: Monitor System Configuration Requests - Line: 40 _________________________ I61500MAY 27, 2021 9:57 TANK PRODUCT LABEL METER DATA 1 Unleaded 87A YES 2 Unleaded 87B YES 3 Premium YES 4 Gas Additive NO 5 Diesel YES 6 Diesel Additive NO 7 NO 8 NO ============================Request: 41 - I62F00 - Mag Probe Float SizeRequest Source: Monitor System Configuration Requests - Line: 41 _________________________ I62F00MAY 27, 2021 9:57 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 Unleaded 87A 4.0 IN. 2 Unleaded 87B 4.0 IN. 3 Premium 4.0 IN. 4 Gas Additive 4.0 IN. 5 Diesel 2.0 IN. ============================Request: 42 - I62700 - Tank Height Water warning limitRequest Source: Monitor System Configuration Requests - Line: 42 _________________________ I62700MAY 27, 2021 9:57 TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 Unleaded 87A 1.0 2 Unleaded 87B 1.0 3 Premium 1.0 5 Diesel 0.8 ============================Request: 43 - I64200 - Tank Water Filter LimitRequest Source: Monitor System Configuration Requests - Line: 43 _________________________ I64200MAY 27, 2021 9:57 WATER ALARM FILTER TANK PRODUCT LABEL 1 Unleaded 87A LOW 2 Unleaded 87B LOW 3 Premium LOW 5 Diesel LOW ============================Request: 44 - I62400 - Tank High Water Level LimitRequest Source: Monitor System Configuration Requests - Line: 44 _________________________ I62400MAY 27, 2021 9:57 TANK HIGH WATER LEVEL LIMIT file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] TANK PRODUCT LABEL INCHES 1 Unleaded 87A 1.5 2 Unleaded 87B 1.0 3 Premium 1.0 5 Diesel 2.0 ============================Request: 45 - I62800 - Tank Maximum Volume LimitRequest Source: Monitor System Configuration Requests - Line: 45 _________________________ I62800MAY 27, 2021 9:57 TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 19169 2 Unleaded 87B 18577 3 Premium 18816 4 Gas Additive 1200 5 Diesel 14729 6 Diesel Additive 0 7 0 8 0 ============================Request: 46 - I62300 - Tank Overfill Level limitRequest Source: Monitor System Configuration Requests - Line: 46 _________________________ I62300MAY 27, 2021 9:57 TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 17252 2 Unleaded 87B 16719 3 Premium 16934 4 Gas Additive 1081 5 Diesel 13256 6 Diesel Additive 0 7 0 8 0 ============================Request: 47 - I62200 - Tank High Level LimitRequest Source: Monitor System Configuration Requests - Line: 47 _________________________ I62200MAY 27, 2021 9:57 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 18019 2 Unleaded 87B 17462 3 Premium 17687 4 Gas Additive 1141 5 Diesel 13845 6 Diesel Additive 0 7 0 8 0 ============================Request: 48 - I62900 - Tank Delivery Required limitRequest Source: Monitor System Configuration Requests - Line: 48 _________________________ I62900MAY 27, 2021 9:57 TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 3834 2 Unleaded 87B 3715 3 Premium 3763 4 Gas Additive 132 5 Diesel 2946 6 Diesel Additive 0 7 0 8 0 ============================Request: 49 - I62100 - Tank Low Level LimitRequest Source: Monitor System Configuration Requests - Line: 49 _________________________ I62100MAY 27, 2021 9:57 TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 575 2 Unleaded 87B 557 3 Premium 564 4 Gas Additive 132 5 Diesel 442 6 Diesel Additive 0 7 0 8 0 ============================Request: 50 - I62600 - Tank Leak Alarm LimitRequest Source: Monitor System Configuration Requests - Line: 50 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] _________________________ I62600MAY 27, 2021 9:57 TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 8 2 Unleaded 87B 8 3 Premium 8 4 Gas Additive 8 5 Diesel 8 6 Diesel Additive 99 7 99 8 99 ============================Request: 51 - I62500 - Tank Sudden Loss LimitRequest Source: Monitor System Configuration Requests - Line: 51 _________________________ I62500MAY 27, 2021 9:57 TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 25 2 Unleaded 87B 25 3 Premium 25 4 Gas Additive 25 5 Diesel 25 6 Diesel Additive 99 7 99 8 99 ============================Request: 52 - I60800 - Tank TiltRequest Source: Monitor System Configuration Requests - Line: 52 _________________________ I60800MAY 27, 2021 9:57 TANK TILT TANK PRODUCT LABEL INCHES 1 Unleaded 87A 0.00 2 Unleaded 87B 0.00 3 Premium 0.00 4 Gas Additive 0.00 5 Diesel 0.00 6 Diesel Additive 0.00 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 7 0.00 8 0.00 ============================Request: 53 - I60B00 - Tank Stick Height Function EnableRequest Source: Monitor System Configuration Requests - Line: 53 _________________________ I60B00MAY 27, 2021 9:57 STICK HEIGHT OFFSET ENABLE STATUSDISABLED ============================Request: 54 - I60C00 - Tank Stick Height offsetRequest Source: Monitor System Configuration Requests - Line: 54 _________________________ I60C00MAY 27, 2021 9:57 TANK STICK HEIGHT OFFSETTANK PRODUCT LABEL INCHES 1 Unleaded 87A 0.00 2 Unleaded 87B 0.00 3 Premium 0.00 4 Gas Additive 0.00 5 Diesel 0.00 6 Diesel Additive 0.00 7 0.00 8 0.00 ============================Request: 55 - I61200 - Tank Siphon Manifold partnersRequest Source: Monitor System Configuration Requests - Line: 55 _________________________ I61200MAY 27, 2021 9:57 TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 Unleaded 87A 2 NONE 2 Unleaded 87B 1 NONE 3 Premium NONE NONE 4 Gas Additive NONE NONE 5 Diesel NONE NONE 6 Diesel Additive NONE NONE 7 NONE NONE 8 NONE NONE file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] ============================Request: 56 - I63600 - Tank Periodic Leak Test Minimum VolumeRequest Source: Monitor System Configuration Requests - Line: 56 _________________________ I63600MAY 27, 2021 9:57 PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 15960 2 Unleaded 87B 15960 3 Premium 15960 4 Gas Additive 12083 5 Diesel 12083 6 Diesel Additive 0 7 0 8 0 ============================Request: 57 - I62A00 - Tank Annual Leak Test Minimum VolumeRequest Source: Monitor System Configuration Requests - Line: 57 _________________________ I62A00MAY 27, 2021 9:57 ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 15960 2 Unleaded 87B 15960 3 Premium 15960 4 Gas Additive 0 5 Diesel 12083 6 Diesel Additive 0 7 0 8 0 ============================Request: 58 - I62C00 - Tank Periodic Test TypeRequest Source: Monitor System Configuration Requests - Line: 58 _________________________ I62C00MAY 27, 2021 9:57 TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 Unleaded 87A STANDARD 2 Unleaded 87B STANDARD 3 Premium STANDARD file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 4 Gas Additive STANDARD 5 Diesel STANDARD 6 Diesel Additive STANDARD 7 STANDARD 8 STANDARD ============================Request: 59 - I62D00 - Enable-Disable Tank Test Leak Fail AlarmsRequest Source: Monitor System Configuration Requests - Line: 59 _________________________ I62D00MAY 27, 2021 9:57 TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 Unleaded 87A GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 Unleaded 87B GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 Premium GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 Gas Additive GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 5 Diesel GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 6 Diesel Additive GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 7 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 8 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED ============================Request: 60 - I63100 - Tank Leak Test AveragingRequest Source: Monitor System Configuration Requests - Line: 60 _________________________ file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] I63100MAY 27, 2021 9:57 TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 Unleaded 87A OFF OFF 2 Unleaded 87B OFF OFF 3 Premium OFF OFF 4 Gas Additive OFF OFF 5 Diesel OFF OFF 6 Diesel Additive OFF OFF 7 OFF OFF 8 OFF OFF ============================Request: 61 - I63000 - Tank Leak Test notifyRequest Source: Monitor System Configuration Requests - Line: 61 _________________________ I63000MAY 27, 2021 9:57 IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 Unleaded 87A OFF 2 Unleaded 87B OFF 3 Premium OFF 4 Gas Additive OFF 5 Diesel OFF 6 Diesel Additive OFF 7 OFF 8 OFF ============================Request: 62 - I63200 - Tank Test Siphon BreakRequest Source: Monitor System Configuration Requests - Line: 62 _________________________ I63200MAY 27, 2021 9:57 TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 Unleaded 87A OFF 2 Unleaded 87B OFF 3 Premium OFF 4 Gas Additive OFF 5 Diesel OFF 6 Diesel Additive OFF file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 7 OFF 8 OFF ============================Request: 63 - I61000 - Tank delivery DelayRequest Source: Monitor System Configuration Requests - Line: 63 _________________________ I61000MAY 27, 2021 9:57 TANK DELIVERY DELAY TANK PRODUCT LABEL 1 Unleaded 87A 1 2 Unleaded 87B 1 3 Premium 1 4 Gas Additive 1 5 Diesel 1 6 Diesel Additive 1 7 1 8 1 ============================Request: 64 - I63A00 - Tank low Level Threshold for Line Manifold Request Source: Monitor System Configuration Requests - Line: 64 _________________________ I63A00MAY 27, 2021 9:57 LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 Unleaded 87A 10.00% 2 Unleaded 87B 10.00% 3 Premium 10.00% 4 Gas Additive 10.00% 5 Diesel 10.00% 6 Diesel Additive 10.00% 7 10.00% 8 10.00% ============================Request: 65 - I61100 - Tank Leak Test Type and Start TimeRequest Source: Monitor System Configuration Requests - Line: 65 _________________________ I61100MAY 27, 2021 9:57 LEAK TEST METHOD file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] - - - - - - - - - - - -TEST ON DATE : ALL TANKAUG 10, 2012START TIME : DISABLEDTEST RATE :0.20 GAL/HRDURATION : 2 HOURS TST EARLY STOP:DISABLED ============================Request: 66 - I61300 - CSLD Probability of DetectionRequest Source: Monitor System Configuration Requests - Line: 66 _________________________ I61300MAY 27, 2021 9:57CSLD PROBABLITY OF DETECTION ============================Request: 67 - I61400 - CSLD Climate FactorRequest Source: Monitor System Configuration Requests - Line: 67 _________________________ I61400MAY 27, 2021 9:57CSLD CLIMATE FACTOR ============================Request: 68 - I61600 - Accuchart Update SchedulingRequest Source: Monitor System Configuration Requests - Line: 68 _________________________ I61600MAY 27, 2021 9:57 TANK PRODUCT LABEL CAL UPDATE 1 Unleaded 87A IMMEDIATE 2 Unleaded 87B IMMEDIATE 3 Premium NEVER 4 Gas Additive NEVER 5 Diesel IMMEDIATE 6 Diesel Additive NEVER 7 NEVER 8 NEVER ============================Request: 69 - I61A00 - In-Tank Leak Test Early StopRequest Source: Monitor System Configuration Requests - Line: 69 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] _________________________ I61A00MAY 27, 2021 9:57 IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 Unleaded 87A DISABLED 2 Unleaded 87B DISABLED 3 Premium DISABLED 4 Gas Additive DISABLED 5 Diesel DISABLED 6 Diesel Additive DISABLED 7 DISABLED 8 DISABLED ============================Request: 70 - I61B00 - In-Tank Static Gross Test Auto-ConfirmRequest Source: Monitor System Configuration Requests - Line: 70 _________________________ I61B00MAY 27, 2021 9:57 IN-TANK LEAK GROSS TEST AUTO-CONFIRM ============================Request: 71 - I61C00 - CSLD Report Only modeRequest Source: Monitor System Configuration Requests - Line: 71 _________________________ I61C00MAY 27, 2021 9:57 CSLD REPORT ONLY ============================Request: 72 - I62B00 - Tank Last Annual TestRequest Source: Monitor System Configuration Requests - Line: 72 _________________________ I62B00MAY 27, 2021 9:57 TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 Unleaded 87A ??? 0, 0 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 2 Unleaded 87B ??? 0, 0 3 Premium ??? 0, 0 4 Gas Additive ??? 0, 0 5 Diesel ??? 0, 0 6 Diesel Additive ??? 0, 0 7 ??? 0, 0 8 ??? 0, 0 ============================Request: 73 - I63300 - Leak Test Report TypeRequest Source: Monitor System Configuration Requests - Line: 73 _________________________ I63300MAY 27, 2021 9:58 LEAK TEST REPORT FORMAT: NORMAL ============================Request: 74 - I63400 - Tank HRM Reconciliation Warning limitRequest Source: Monitor System Configuration Requests - Line: 74 _________________________ I63400MAY 27, 2021 9:58 RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 0 2 Unleaded 87B 0 3 Premium 0 4 Gas Additive 0 5 Diesel 0 6 Diesel Additive 0 7 0 8 0 ============================Request: 75 - I63500 - Tank HEM Reconciliation AlarmRequest Source: Monitor System Configuration Requests - Line: 75 _________________________ I63500MAY 27, 2021 9:58 RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 Unleaded 87A 1 2 Unleaded 87B 1 3 Premium 1 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 4 Gas Additive 1 5 Diesel 1 6 Diesel Additive 1 7 1 8 1 ============================Request: 76 - I63900 - Tank Accuchart End Shape Type and FactorRequest Source: Monitor System Configuration Requests - Line: 76 _________________________ I63900MAY 27, 2021 9:58 ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 Unleaded 87A END FACTOR: HEMISPHER 2 Unleaded 87B END FACTOR: HEMISPHER 3 Premium END FACTOR: OTHEREND VALUE: 1.0 4 Gas Additive END FACTOR: OTHEREND VALUE: 0.8 5 Diesel END FACTOR: OTHEREND VALUE: 0.8 6 Diesel Additive END FACTOR: NONE 7 END FACTOR: NONE 8 END FACTOR: NONE ============================Request: 77 - I78000 - PLLD SetupRequest Source: Monitor System Configuration Requests - Line: 77 _________________________ file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] I78000MAY 27, 2021 9:58 PRESSURE LINE LEAK SETUP Q 1:UNLEADED 87A TYP:USER DEFINED1ST LINE LEN: 210 FEET 2ND LINE LEN: 0 FEET 1ST LINE DIAM: 1.50 IN.1ST BULK MOD: 1000 PSITHERMAL COEFF :0.0007000.20 GPH TEST: REPETITIV0.10 GPH TEST: AUTOPASSIVE 0.10 GPH: NO SHUTDOWN RATE: 3.0 GPHLOW PRESSURE SHUTOFF:YESLOW PRESSURE : 5 PSI T 1:Unleaded 87A DISPENSE MODE:STANDARDSENSOR: HIGH PRESSUREPRESSURE OFFSET: 0.0PSI MECHANICAL BLENDER: NO Q 2:UNLEADED 87B TYP:USER DEFINED1ST LINE LEN: 210 FEET 2ND LINE LEN: 0 FEET 1ST LINE DIAM: 1.50 IN.1ST BULK MOD: 1000 PSITHERMAL COEFF :0.0007000.20 GPH TEST: REPETITIV0.10 GPH TEST: AUTOPASSIVE 0.10 GPH: NO SHUTDOWN RATE: 3.0 GPHLOW PRESSURE SHUTOFF:YESLOW PRESSURE : 5 PSI T 2:Unleaded 87B DISPENSE MODE:STANDARDSENSOR: HIGH PRESSUREPRESSURE OFFSET: 0.0PSI MECHANICAL BLENDER: NO Q 3:PREMIUM TYP:USER DEFINED1ST LINE LEN: 305 FEET 2ND LINE LEN: 0 FEET file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 1ST LINE DIAM: 1.50 IN.1ST BULK MOD: 1000 PSITHERMAL COEFF :0.0007000.20 GPH TEST: REPETITIV0.10 GPH TEST: AUTOPASSIVE 0.10 GPH: NO SHUTDOWN RATE: 3.0 GPHLOW PRESSURE SHUTOFF:YESLOW PRESSURE : 5 PSI T 3:Premium DISPENSE MODE:STANDARDSENSOR: HIGH PRESSUREPRESSURE OFFSET: 0.0PSI MECHANICAL BLENDER: NO Q 4:DIESEL TYP:2.0/3.0IN FIBERGLASS2.0IN DIA LEN: 150 FEET 3.0IN DIA LEN: 0 FEET 0.20 GPH TEST: REPETITIV0.10 GPH TEST: AUTOSHUTDOWN RATE: 3.0 GPHLOW PRESSURE SHUTOFF:YESLOW PRESSURE : 5 PSI T 5:Diesel DISPENSE MODE:STANDARDSENSOR: NON-VENTEDPRESSURE OFFSET: 0.0PSI MECHANICAL BLENDER: NO ============================Request: 78 - I77700 - PLLD Primary Line DiameterRequest Source: Monitor System Configuration Requests - Line: 78 _________________________ I77700MAY 27, 2021 9:58 PRESSURE LINE LEAK PRIMARY PIPE DIAMETER LINE 1ST LINE DIAMETER Q 1:UNLEADED 87A 1.50 INCHESQ 2:UNLEADED 87B 1.50 INCHESQ 3:PREMIUM 1.50 INCHES ============================Request: 79 - I77800 - PLLD Secondary Line Diameter file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] Request Source: Monitor System Configuration Requests - Line: 79 _________________________ I77800MAY 27, 2021 9:58 ============================Request: 80 - I78C00 - PLLD 0.20 GPH Test ScheduleRequest Source: Monitor System Configuration Requests - Line: 80 _________________________ I78C00MAY 27, 2021 9:58 PRESSURE LINE LEAK 0.20 TEST SCHEDULE LINE 0.20 GPH TESTQ 1:UNLEADED 87A REPETITIVQ 2:UNLEADED 87B REPETITIVQ 3:PREMIUM REPETITIVQ 4:DIESEL REPETITIVQ 5:DIE DISABLEDQ 6: DISABLED ============================Request: 81 - I78300 - PLLD 0.10 GPH Test ScheduleRequest Source: Monitor System Configuration Requests - Line: 81 _________________________ I78300MAY 27, 2021 9:58 PRESSURE LINE LEAK 0.10 TEST SCHEDULE LINE 0.10 GPH TESTQ 1:UNLEADED 87A AUTOQ 2:UNLEADED 87B AUTOQ 3:PREMIUM AUTOQ 4:DIESEL AUTOQ 5:DIE DISABLEDQ 6: DISABLED ============================Request: 82 - I78F00 - PLLD Dispense ThresholdRequest Source: Monitor System Configuration Requests - Line: 82 _________________________ I78F00MAY 27, 2021 9:58 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] PRESSURE LINE LEAK DISPENSE THRESHOLD LINE LOW PRESSUREQ 1:UNLEADED 87A 5 PSIQ 2:UNLEADED 87B 5 PSIQ 3:PREMIUM 5 PSIQ 4:DIESEL 5 PSIQ 5:DIE 0 PSIQ 6: 0 PSI ============================Request: 83 - I78700 - PLLD Disable Alarm AssignmentsRequest Source: Monitor System Configuration Requests - Line: 83 _________________________ I78700MAY 27, 2021 9:58 PRESSURE LLD SETUP REPORT Q 1:UNLEADED 87A IN-TANK ALARMS T 1:HIGH WATER ALARM T 1:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 6:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L22:FUEL ALARM L23:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L15:SENSOR OUT ALARM L22:SENSOR OUT ALARM L23:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 6:SHORT ALARM file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM L15:SHORT ALARM L22:SHORT ALARM L23:SHORT ALARM L 1:HIGH LIQUID ALARM L 2:HIGH LIQUID ALARM L 3:HIGH LIQUID ALARM L 6:HIGH LIQUID ALARM L22:HIGH LIQUID ALARM L23:HIGH LIQUID ALARM L 1:LOW LIQUID ALARM L 2:LOW LIQUID ALARM L 3:LOW LIQUID ALARM L 6:LOW LIQUID ALARM L22:LOW LIQUID ALARM L23:LOW LIQUID ALARM L 2:LIQUID WARNING L 3:LIQUID WARNING L 6:LIQUID WARNING L22:LIQUID WARNING L23:LIQUID WARNING PRESSURE LINE LEAK ALL:PLLD OPEN ALARM ALL:CONT HANDLE ALM ALL:LN EQUIP FAULT ALM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL MISSING HOSE SETUP ISD SETUP FAIL ISD SENSOR OUT FAIL PC-ISD FAILURE ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL Q 2:UNLEADED 87B IN-TANK ALARMS T 2:HIGH WATER ALARM T 2:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 3:FUEL ALARM L 4:FUEL ALARM file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] L 5:FUEL ALARM L 6:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L22:FUEL ALARM L23:FUEL ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L15:SENSOR OUT ALARM L22:SENSOR OUT ALARM L23:SENSOR OUT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM L15:SHORT ALARM L22:SHORT ALARM L23:SHORT ALARM L 3:HIGH LIQUID ALARM L 4:HIGH LIQUID ALARM L 5:HIGH LIQUID ALARM L 6:HIGH LIQUID ALARM L22:HIGH LIQUID ALARM L23:HIGH LIQUID ALARM L 3:LOW LIQUID ALARM L 4:LOW LIQUID ALARM L 5:LOW LIQUID ALARM L 6:LOW LIQUID ALARM L22:LOW LIQUID ALARM L23:LOW LIQUID ALARM L 3:LIQUID WARNING L 5:LIQUID WARNING L 6:LIQUID WARNING L22:LIQUID WARNING L23:LIQUID WARNING PRESSURE LINE LEAK ALL:PLLD OPEN ALARM ALL:CONT HANDLE ALM ALL:LN EQUIP FAULT ALM file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL PC-ISD FAILURE ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL Q 3:PREMIUM IN-TANK ALARMS T 3:HIGH WATER ALARM T 3:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L22:FUEL ALARM L23:FUEL ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L15:SENSOR OUT ALARM L22:SENSOR OUT ALARM L23:SENSOR OUT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM L15:SHORT ALARM L22:SHORT ALARM L23:SHORT ALARM L 7:HIGH LIQUID ALARM file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] L 8:HIGH LIQUID ALARM L 9:HIGH LIQUID ALARM L22:HIGH LIQUID ALARM L23:HIGH LIQUID ALARM L 7:LOW LIQUID ALARM L 8:LOW LIQUID ALARM L 9:LOW LIQUID ALARM L22:LOW LIQUID ALARM L23:LOW LIQUID ALARM L 8:LIQUID WARNING L 9:LIQUID WARNING L22:LIQUID WARNING L23:LIQUID WARNING PRESSURE LINE LEAK ALL:PLLD OPEN ALARM ALL:CONT HANDLE ALM ALL:LN EQUIP FAULT ALM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL PC-ISD FAILURE ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL Q 4:DIESEL IN-TANK ALARMS T 5:HIGH WATER ALARM T 5:LOW PRODUCT ALARM LIQUID SENSOR ALMS L21:FUEL ALARM L22:FUEL ALARM L23:FUEL ALARM L24:FUEL ALARM L25:FUEL ALARM L26:FUEL ALARM L21:SENSOR OUT ALARM L22:SENSOR OUT ALARM L23:SENSOR OUT ALARM L24:SENSOR OUT ALARM L25:SENSOR OUT ALARM L26:SENSOR OUT ALARM L21:SHORT ALARM L22:SHORT ALARM L23:SHORT ALARM file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] L24:SHORT ALARM L25:SHORT ALARM L26:SHORT ALARM L21:HIGH LIQUID ALARM L22:HIGH LIQUID ALARM L23:HIGH LIQUID ALARM L25:HIGH LIQUID ALARM L26:HIGH LIQUID ALARM L21:LOW LIQUID ALARM L22:LOW LIQUID ALARM L23:LOW LIQUID ALARM L24:LOW LIQUID ALARM L25:LOW LIQUID ALARM L26:LOW LIQUID ALARM L21:LIQUID WARNING L22:LIQUID WARNING L23:LIQUID WARNING L24:LIQUID WARNING L25:LIQUID WARNING L26:LIQUID WARNING PRESSURE LINE LEAK ALL:PLLD OPEN ALARM ALL:CONT HANDLE ALM ALL:LN EQUIP FAULT ALM SMARTSENSOR ALARMS s 3:HIGH LIQUID WARNING s 4:HIGH LIQUID WARNING s 3:HIGH LIQUID ALARM s 4:HIGH LIQUID ALARM s 3:SENSOR FAULT WARN s 4:SENSOR FAULT WARN s 3:VACUUM WARNING s 3:NO VACUUM ALARM s 4:NO VACUUM ALARM Q 5:DIE - NO ALARM ASSIGNMENTS - Q 6: - NO ALARM ASSIGNMENTS - ============================Request: 84 - I70200 - Liquid Sensor Location LabelRequest Source: Monitor System Configuration Requests - Line: 84 _________________________ I70200MAY 27, 2021 9:59 LIQUID LABEL file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] DEVICE LABEL 1 UNLEADED 87A ANNULAR 2 UNLEADED 87A FILL 3 UNLEADED 87A STP 4 UNLEADED 87B ANNULAR 5 UNLEADED 87B FILL 6 UNLEADED 87B STP 7 PREMIUM ANNULAR 8 PREMIUM FILL 9 PREMIUM STP 10 DISPENSER PAN 1-2 11 DISPENSER PAN 3-4 12 DISPENSER PAN 5-6 13 DISPENSER PAN 7-8 14 DISPENSER PAN 9-10 15 DISPENSER PAN 11-12 16 ADDITIVE ANNULAR 17 ADDITIVE VENT BOX 18 19 20 21 DIESEL ANNULAR 22 DISPENSER PAN 13-14 23 DISPENSER PAN 15-16 24 DIESEL FILL 25 DIESEL STP 26 DIESEL VENT 27 ARID VENT BOX 28 ============================Request: 85 - I70300 - Liquid Sensor TypeRequest Source: Monitor System Configuration Requests - Line: 85 _________________________ I70300MAY 27, 2021 9:59 LIQUID TYPE SENSOR LOCATION TYPE 1 UNLEADED 87A ANNULAR DUAL POINT HYDROSTATIC 2 UNLEADED 87A FILL DUAL FLT. HIGH VAPOR 3 UNLEADED 87A STP TRI-STATE (SINGLE FLOAT) 4 UNLEADED 87B ANNULAR DUAL POINT HYDROSTATIC 5 UNLEADED 87B FILL DUAL FLT. HIGH VAPOR 6 UNLEADED 87B STP DUAL FLT. DISCRIMINATING 7 PREMIUM ANNULAR DUAL POINT HYDROSTATIC 8 PREMIUM FILL DUAL FLT. HIGH VAPOR 9 PREMIUM STP DUAL FLT. HIGH VAPOR 10 DISPENSER PAN 1-2 TRI-STATE (SINGLE FLOAT) 11 DISPENSER PAN 3-4 TRI-STATE (SINGLE FLOAT) 12 DISPENSER PAN 5-6 TRI-STATE (SINGLE FLOAT) 13 DISPENSER PAN 7-8 TRI-STATE (SINGLE FLOAT) 14 DISPENSER PAN 9-10 TRI-STATE (SINGLE FLOAT) file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 15 DISPENSER PAN 11-12 TRI-STATE (SINGLE FLOAT) 16 ADDITIVE ANNULAR TRI-STATE (SINGLE FLOAT) 17 ADDITIVE VENT BOX TRI-STATE (SINGLE FLOAT) 18 TRI-STATE (SINGLE FLOAT) 19 TRI-STATE (SINGLE FLOAT) 20 TRI-STATE (SINGLE FLOAT) 21 DIESEL ANNULAR DUAL POINT HYDROSTATIC 22 DISPENSER PAN 13-14 DW SUMP 2-1 23 DISPENSER PAN 15-16 DW SUMP 2-1 24 DIESEL FILL DW SUMP 2-1 25 DIESEL STP DW SUMP 2-1 26 DIESEL VENT DW SUMP 2-1 27 ARID VENT BOX TRI-STATE (SINGLE FLOAT) 28 TRI-STATE (SINGLE FLOAT) ============================Request: 86 - I70400 - Liquid Sensor CategoryRequest Source: Monitor System Configuration Requests - Line: 86 _________________________ I70400MAY 27, 2021 9:59 LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNLEADED 87A ANNULAR ANNULAR SPACE 2 UNLEADED 87A FILL PIPING SUMP 3 UNLEADED 87A STP STP SUMP 4 UNLEADED 87B ANNULAR ANNULAR SPACE 5 UNLEADED 87B FILL PIPING SUMP 6 UNLEADED 87B STP STP SUMP 7 PREMIUM ANNULAR ANNULAR SPACE 8 PREMIUM FILL PIPING SUMP 9 PREMIUM STP STP SUMP 10 DISPENSER PAN 1-2 DISPENSER PAN 11 DISPENSER PAN 3-4 DISPENSER PAN 12 DISPENSER PAN 5-6 DISPENSER PAN 13 DISPENSER PAN 7-8 DISPENSER PAN 14 DISPENSER PAN 9-10 DISPENSER PAN 15 DISPENSER PAN 11-12 DISPENSER PAN 16 ADDITIVE ANNULAR ANNULAR SPACE 17 ADDITIVE VENT BOX DISPENSER PAN 18 OTHER SENSORS 19 OTHER SENSORS 20 OTHER SENSORS 21 DIESEL ANNULAR ANNULAR SPACE 22 DISPENSER PAN 13-14 DISPENSER PAN 23 DISPENSER PAN 15-16 DISPENSER PAN 24 DIESEL FILL OTHER SENSORS 25 DIESEL STP STP SUMP 26 DIESEL VENT DISPENSER PAN 27 ARID VENT BOX PIPING SUMP 28 OTHER SENSORS file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] ============================Request: 87 - I74200 - Type "A" 2 Wire Sensor Location LabelRequest Source: Monitor System Configuration Requests - Line: 87 _________________________ I74200MAY 27, 2021 9:59 ============================Request: 88 - I74300 - Type "A" 2 Wire Sensor TypeRequest Source: Monitor System Configuration Requests - Line: 88 _________________________ I74300MAY 27, 2021 9:59 ============================Request: 89 - I74400 - Type "A" 2 Wire Sensor CategoryRequest Source: Monitor System Configuration Requests - Line: 89 _________________________ I74400MAY 27, 2021 9:59 ============================Request: 90 - I74700 - Type "B" 3 Wire Sensor Location LabelRequest Source: Monitor System Configuration Requests - Line: 90 _________________________ I74700MAY 27, 2021 9:59 ============================Request: 91 - I74800 - Type "B" 3 Wire Sensor TypeRequest Source: Monitor System Configuration Requests - Line: 91 _________________________ I74800MAY 27, 2021 9:59 ============================Request: 92 - I74900 - Type "B" Sensor CategoryRequest Source: Monitor System Configuration Requests - Line: 92 _________________________ file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] I74900MAY 27, 2021 9:59 ============================Request: 93 - I7BC00 - I/O Device Line Disable AssignmentsRequest Source: Monitor System Configuration Requests - Line: 93 _________________________ I7BC00MAY 27, 2021 9:59 ============================Request: 94 - I80200 - I/O Input location LabelRequest Source: Monitor System Configuration Requests - Line: 94 _________________________ I80200MAY 27, 2021 9:59 EXTERNAL INPUT LABEL DEVICE LABEL 1 ARID FAULT 2 ARID ACTIVE ============================Request: 95 - I80300 - I/O Input TypeRequest Source: Monitor System Configuration Requests - Line: 95 _________________________ I80300MAY 27, 2021 9:59 EXTERNAL INPUT TYPE INPUT NAME TYPE ORIENTATION TANK# 1 ARID FAULT VP PROCESSOR NORMALLY CLOSED 2 ARID ACTIVE VP PROCESSR2 NORMALLY OPEN ============================Request: 96 - I80400 - I/O Input Dispense modeRequest Source: Monitor System Configuration Requests - Line: 96 _________________________ I80400MAY 27, 2021 9:59 ============================ file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] Request: 97 - I80700 - I/O Relay location labelRequest Source: Monitor System Configuration Requests - Line: 97 _________________________ I80700MAY 27, 2021 9:59 RELAY LABEL DEVICE LABEL 1 OUTSIDE OVERFILL 2 MEMBERSHIP V-R ALARM 3 ADDITIVE SHUTDOWN 4 5 6 ============================Request: 98 - I80900 - I/O Relay OrientationRequest Source: Monitor System Configuration Requests - Line: 98 _________________________ I80900MAY 27, 2021 9:59 RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 OUTSIDE OVERFILL NORMALLY OPEN 2 MEMBERSHIP V-R ALARM NORMALLY OPEN 3 ADDITIVE SHUTDOWN NORMALLY CLOSED 4 NORMALLY OPEN 5 NORMALLY OPEN 6 NORMALLY OPEN ============================Request: 99 - I80B00 - I/O Relay Tank AssignmentRequest Source: Monitor System Configuration Requests - Line: 99 _________________________ I80B00MAY 27, 2021 9:59 RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 OUTSIDE OVERFILL NONE 2 MEMBERSHIP V-R ALARM NONE 3 ADDITIVE SHUTDOWN 4 4 NONE 5 NONE 6 NONE file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] ============================Request: 100 - I80A00 - I/O Relay TypeRequest Source: Monitor System Configuration Requests - Line: 100 _________________________ I80A00MAY 27, 2021 9:59 RELAY TYPE RELAY DESIGNATION TYPE 1 OUTSIDE OVERFILL STANDARD 2 MEMBERSHIP V-R ALARM STANDARD 3 ADDITIVE SHUTDOWN STANDARD 4 STANDARD 5 STANDARD 6 STANDARD ============================Request: 101 - I80C00 - I/O External input TypeRequest Source: Monitor System Configuration Requests - Line: 101 _________________________ I80C00MAY 27, 2021 9:59 EXTERNAL INPUT TYPE INPUT NAME TYPE ORIENTATION TANK# 1 ARID FAULT VP PROCESSOR NORMALLY CLOSED 2 ARID ACTIVE VP PROCESSR2 NORMALLY OPEN ============================Request: 102 - I80800 - I/O Relay Alarm AssignmentsRequest Source: Monitor System Configuration Requests - Line: 102 _________________________ I80800MAY 27, 2021 9:59 RELAY SETUP REPORT R 1:OUTSIDE OVERFILL TYPE: STANDARDNORMALLY OPEN TANK #: NONE file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM R 2:MEMBERSHIP V-R ALARMTYPE: STANDARDNORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:LEAK ALARM ALL:HIGH WATER ALARM ALL:OVERFILL ALARM ALL:LOW PRODUCT ALARM ALL:SUDDEN LOSS ALARM ALL:HIGH PRODUCT ALARM ALL:INVALID FUEL LEVEL ALL:PROBE OUT ALL:HIGH WATER WARNING ALL:DELIVERY NEEDED ALL:MAX PRODUCT ALARM ALL:LOW TEMP WARNING ALL:FUEL QUALITY ALARM LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM ALL:HIGH LIQUID ALARM ALL:LOW LIQUID ALARM ALL:LIQUID WARNING PRESSURE LINE LEAK ALL:GROSS LINE FAIL ALL:ANNUAL LINE FAIL ALL:PER TST NEEDED WRN ALL:PER TST NEEDED ALM ALL:PLLD OPEN ALARM ALL:PLLD SHUTDOWN ALARM ALL:PERIODIC LINE FAIL ALL:ANN TST NEEDED WRN ALL:ANN TST NEEDED ALM ALL:LOW PRESSURE ALARM ALL:CONT HANDLE ALM ALL:FUEL OUT ALL:LN EQUIP FAULT ALM ALL:GRS TST NEEDED ALM ISD SITE ALARMS ISD STAGE I WARN ISD GROSS PRES WARN ISD GROSS PRES FAIL file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] ISD DEGRD PRES WARN ISD DEGRD PRES FAIL ISD VAPOR LEAK WARN ISD VAPOR LEAK FAIL ISD VP PRES WARN ISD VP PRES FAIL ISD VP STATUS WARN ISD VP STATUS FAIL MISSING RELAY SETUP MISSING HOSE SETUP MISSING TANK SETUP MISS VAPOR FLOW MTR MISS VAPOR PRES SEN MISSING VP INPUT ISD SETUP WARN ISD SETUP FAIL ISD SENSOR OUT WARN ISD SENSOR OUT FAIL PMC ALARMS VP RUNTIME FAULT VP EMISSIONS WARN VP EMISSIONS FAIL VP PRESSURE WARN VP PRESSURE FAIL VP DUTY CYCLE WARN VP DUTY CYCLE FAIL PMC SETUP FAIL PMC SENSOR FAULT R 3:ADDITIVE SHUTDOWN TYPE: STANDARDNORMALLY CLOSED TANK #: 4 IN-TANK ALARMS T 4:HIGH WATER ALARM T 4:LOW PRODUCT ALARM LIQUID SENSOR ALMS L16:FUEL ALARM L17:FUEL ALARM L16:SENSOR OUT ALARM L17:SENSOR OUT ALARM L16:SHORT ALARM L17:SHORT ALARM R 4: TYPE: STANDARDNORMALLY OPEN file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] TANK #: NONE - NO ALARM ASSIGNMENTS - R 5: TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 6: TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - ============================Request: 103 - I79000 - DIM Software RevisionRequest Source: Monitor System Configuration Requests - Line: 103 _________________________ I79000MAY 27, 2021 10:00 EDIM:1 VR:349806-002-A 5 TD:16.12.14.16.18 ============================Request: 104 - I79100 - Mechanical Dispenser Interface StringRequest Source: Monitor System Configuration Requests - Line: 104 _________________________ I79100MAY 27, 2021 10:00 ============================Request: 105 - I72300 - Smart Sensor CategoryRequest Source: Monitor System Configuration Requests - Line: 105 _________________________ I72300MAY 27, 2021 10:00 207901 Costco 688 3800 Rosedale Highwa file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] Bakersfield, CA SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY01 VFM 13-14 AIR FLOW METER02 VFM 15,16 AIR FLOW METER03 DIESEL PRODUCT VAC. VAC SENSOR04 DIESEL VENT VAC. VAC SENSOR05 UNKNOWN06 UNKNOWN07 UNKNOWN08 ATM P ATM P SENSOR09 VFM 1-2 AIR FLOW METER10 VFM 3-4 AIR FLOW METER11 VFM 5-6 AIR FLOW METER12 VFM 7-8 AIR FLOW METER13 VFM 9-10 AIR FLOW METER14 VFM 11-12 AIR FLOW METER15 UNKNOWN16 PRESURE SENSOR 3-4 VAPOR PRESSURE17 UNKNOWN18 UNKNOWN19 UNKNOWN20 UNKNOWN21 UNKNOWN22 UNKNOWN23 UNKNOWN24 UNKNOWN25 UNKNOWN26 UNKNOWN27 UNKNOWN28 UNKNOWN29 UNKNOWN30 UNKNOWN31 UNKNOWN32 UNKNOWN33 UNKNOWN34 UNKNOWN35 UNKNOWN36 UNKNOWN37 UNKNOWN38 UNKNOWN39 UNKNOWN40 UNKNOWN ============================Request: 106 - IV4E00 - ISD EVR TypeRequest Source: Monitor System Configuration Requests - Line: 106 _________________________ IV4E00MAY 27, 2021 10:00 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA EVR/ISD SETUPTYPE: VACUUM ASSISTVACUUM ASSIST TYPE: HEALY VAC ============================Request: 107 - IV4F00 - ISD Nozzle TypeRequest Source: Monitor System Configuration Requests - Line: 107 _________________________ IV4F00MAY 27, 2021 10:00 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA NOZZLE A/L RANGEA/L RATIO: 0.95 - 1.15 ============================Request: 108 - IV4000 - Vapor Processor TypeRequest Source: Monitor System Configuration Requests - Line: 108 _________________________ IV4000MAY 27, 2021 10:00 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA VAPOR PROCESSOR TYPEARID PERMEATOR ============================Request: 109 - IV4700 - ISD Assessment Start and Post DelayRequest Source: Monitor System Configuration Requests - Line: 109 _________________________ IV4700MAY 27, 2021 10:00 207901 Costco 688 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 3800 Rosedale Highwa Bakersfield, CA ASSESSMENT TIMESTART TIME: 05:00TIME DELAY MINUTES: 1 ============================Request: 110 - IV5200 - High ORVR ConfigurationRequest Source: Monitor System Configuration Requests - Line: 110 _________________________ IV5200MAY 27, 2021 10:00 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA ACCEPT HIGH ORVR: NO ============================Request: 111 - IV4A00 - ISD Hose TableRequest Source: Monitor System Configuration Requests - Line: 111 _________________________ IV4A00MAY 27, 2021 10:00 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 UU BLEND2 02 02 02 01 UU BLEND2 03 03 03 02 UU BLEND2 04 04 04 02 UU BLEND2 05 05 05 03 UU BLEND2 06 06 06 03 UU BLEND2 07 07 07 04 UU BLEND2 08 08 08 04 UU BLEND2 09 09 09 05 UU BLEND2 10 10 10 05 UU BLEND2 11 11 11 06 UU BLEND2 12 12 12 06 UU BLEND2 13 13 13 07 UU BLEND2 14 14 14 07 UU BLEND2 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 15 15 15 08 UU BLEND2 16 16 16 08 UU BLEND2 ============================Request: 112 - IV4B00 - ISD Grade TableRequest Source: Monitor System Configuration Requests - Line: 112 _________________________ IV4B00MAY 27, 2021 10:00 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H401 01 00/01 01/01 xx/xx xx/xx02 01 00/02 01/02 xx/xx xx/xx03 02 00/03 01/03 xx/xx xx/xx04 02 00/04 01/04 xx/xx xx/xx05 03 00/05 01/05 xx/xx xx/xx06 03 00/06 01/06 xx/xx xx/xx07 04 00/07 01/07 xx/xx xx/xx08 04 00/08 01/08 xx/xx xx/xx09 05 00/09 01/09 xx/xx xx/xx10 05 00/10 01/10 xx/xx xx/xx11 06 00/11 01/11 xx/xx xx/xx12 06 00/12 01/12 xx/xx xx/xx13 07 00/13 01/13 xx/xx xx/xx14 07 00/14 01/14 xx/xx xx/xx15 08 00/15 01/15 xx/xx xx/xx16 08 00/16 01/16 xx/xx xx/xx ============================Request: 113 - IV4900 - ISD Hose Label TableRequest Source: Monitor System Configuration Requests - Line: 113 _________________________ IV4900MAY 27, 2021 10:00 207901 Costco 688 3800 Rosedale Highwa Bakersfield, CA LABEL TABLEID LABEL01 UNASSIGNED02 BLEND3 file:///C/...uments/Monitoring%20Information/Costco%20Monitor%20Certs/Monitor%20Certs.%202021/%23688%20Bakersfield/688setup.txt[6/3/2021 5:46:55 PM] 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 ============================Request: 114 - IV1000 - ISD VersionRequest Source: Monitor System Configuration Requests - Line: 114 _________________________ IV1000MAY 27, 2021 10:00 ISD VERSION: 01.06 End of Report: 210527 +============================================================================| Monitoring System Report Saved at: Thursday, May 27, 2021 - 10:06:20 AM| (Report Saved Date/Time from PC Clock)| Using Monitoring System Report Utility by FASTECH || Version: Version 6.0.0.100 |+============================================================================ (10') DWT-6 TYPE II 20,000 GALLON DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS 1/8 6 6 1/8 365 12 1/8 997 18 1/8 1811 24 1/8 2764 30 1/8 3828 1/4 9 6 1/4 376 12 1/4 1012 18 1/4 1829 24 1/4 2785 30 1/4 3851 3/8 12 6 3/8 387 12 3/8 1028 18 3/8 1848 24 3/8 2806 30 3/8 3874 1/2 16 6 1/2 398 12 1/2 1043 18 1/2 1866 24 1/2 2827 30 1/2 3897 5/8 20 6 5/8 410 12 5/8 1059 18 5/8 1885 24 5/8 2849 30 5/8 3920 3/4 24 6 3/4 421 12 3/4 1074 18 3/4 1904 24 3/4 2870 30 3/4 3944 7/8 28 6 7/8 432 12 7/8 1090 18 7/8 1923 24 7/8 2891 30 7/8 3967 1 32 7 444 13 1106 19 1942 25 2913 31 3990 1 1/8 37 7 1/8 455 13 1/8 1121 19 1/8 1961 25 1/8 2934 31 1/8 4014 1 1/4 42 7 1/4 467 13 1/4 1137 19 1/4 1980 25 1/4 2956 31 1/4 4037 1 3/8 48 7 3/8 479 13 3/8 1153 19 3/8 1999 25 3/8 2977 31 3/8 4061 1 1/2 53 7 1/2 491 13 1/2 1169 19 1/2 2018 25 1/2 2999 31 1/2 4084 1 5/8 59 7 5/8 503 13 5/8 1185 19 5/8 2037 25 5/8 3020 31 5/8 4108 1 3/4 64 7 3/4 515 13 3/4 1202 19 3/4 2056 25 3/4 3042 31 3/4 4131 1 7/8 71 7 7/8 527 13 7/8 1218 19 7/8 2076 25 7/8 3064 31 7/8 4155 2 77 8 540 14 1234 20 2095 26 3086 32 4179 2 1/8 83 8 1/8 552 14 1/8 1251 20 1/8 2114 26 1/8 3107 32 1/8 4202 2 1/4 90 8 1/4 565 14 1/4 1267 20 1/4 2134 26 1/4 3129 32 1/4 4226 2 3/8 96 8 3/8 577 14 3/8 1284 20 3/8 2153 26 3/8 3151 32 3/8 4250 2 1/2 103 8 1/2 590 14 1/2 1300 20 1/2 2173 26 1/2 3173 32 1/2 4274 2 5/8 110 8 5/8 603 14 5/8 1317 20 5/8 2193 26 5/8 3195 32 5/8 4298 2 3/4 118 8 3/4 616 14 3/4 1334 20 3/4 2212 26 3/4 3217 32 3/4 4321 2 7/8 125 8 7/8 629 14 7/8 1350 20 7/8 2232 26 7/8 3239 32 7/8 4345 3 133 9 642 15 1367 21 2252 27 3261 33 4369 3 1/8 140 9 1/8 655 15 1/8 1384 21 1/8 2272 27 1/8 3283 33 1/8 4393 3 1/4 148 9 1/4 668 15 1/4 1401 21 1/4 2292 27 1/4 3306 33 1/4 4417 3 3/8 156 9 3/8 682 15 3/8 1418 21 3/8 2312 27 3/8 3328 33 3/8 4441 3 1/2 164 9 1/2 695 15 1/2 1435 21 1/2 2332 27 1/2 3350 33 1/2 4465 3 5/8 173 9 5/8 709 15 5/8 1453 21 5/8 2352 27 5/8 3373 33 5/8 4490 3 3/4 181 9 3/4 722 15 3/4 1470 21 3/4 2372 27 3/4 3395 33 3/4 4514 3 7/8 190 9 7/8 736 15 7/8 1487 21 7/8 2392 27 7/8 3417 33 7/8 4538 4 198 10 750 16 1505 22 2412 28 3440 34 4562 4 1/8 207 10 1/8 764 16 1/8 1522 22 1/8 2433 28 1/8 3462 34 1/8 4586 4 1/4 216 10 1/4 778 16 1/4 1540 22 1/4 2453 28 1/4 3485 34 1/4 4611 4 3/8 225 10 3/8 792 16 3/8 1557 22 3/8 2473 28 3/8 3507 34 3/8 4635 4 1/2 234 10 1/2 806 16 1/2 1575 22 1/2 2494 28 1/2 3530 34 1/2 4659 4 5/8 244 10 5/8 820 16 5/8 1593 22 5/8 2514 28 5/8 3553 34 5/8 4684 4 3/4 253 10 3/4 834 16 3/4 1611 22 3/4 2535 28 3/4 3575 34 3/4 4708 4 7/8 263 10 7/8 849 16 7/8 1628 22 7/8 2555 28 7/8 3598 34 7/8 4732 5 273 11 863 17 1646 23 2576 29 3621 35 4757 5 1/8 282 11 1/8 878 17 1/8 1664 23 1/8 2597 29 1/8 3644 35 1/8 4781 5 1/4 292 11 1/4 892 17 1/4 1682 23 1/4 2617 29 1/4 3666 35 1/4 4806 5 3/8 302 11 3/8 907 17 3/8 1701 23 3/8 2638 29 3/8 3689 35 3/8 4830 5 1/2 313 11 1/2 922 17 1/2 1719 23 1/2 2659 29 1/2 3712 35 1/2 4855 5 5/8 323 11 5/8 937 17 5/8 1737 23 5/8 2680 29 5/8 3735 35 5/8 4879 5 3/4 333 11 3/4 952 17 3/4 1755 23 3/4 2701 29 3/4 3758 35 3/4 4904 5 7/8 344 11 7/8 967 17 7/8 1774 23 7/8 2722 29 7/8 3781 35 7/8 4929 6 355 12 982 18 1792 24 2743 30 3804 36 4953 Containment Solutions, Inc.1 (10') DWT-6 TYPE II 20,000 GALLON DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS 36 1/8 4978 42 1/8 6196 48 1/8 7462 54 1/8 8759 60 1/8 10072 66 1/8 11383 36 1/4 5003 42 1/4 6222 48 1/4 7488 54 1/4 8786 60 1/4 10099 66 1/4 11410 36 3/8 5028 42 3/8 6248 48 3/8 7515 54 3/8 8814 60 3/8 10126 66 3/8 11437 36 1/2 5053 42 1/2 6274 48 1/2 7542 54 1/2 8841 60 1/2 10154 66 1/2 11464 36 5/8 5077 42 5/8 6300 48 5/8 7569 54 5/8 8868 60 5/8 10181 66 5/8 11491 36 3/4 5102 42 3/4 6326 48 3/4 7596 54 3/4 8895 60 3/4 10208 66 3/4 11519 36 7/8 5127 42 7/8 6352 48 7/8 7622 54 7/8 8923 60 7/8 10236 66 7/8 11546 37 5152 43 6378 49 7649 55 8950 61 10263 67 11573 37 1/8 5177 43 1/8 6404 49 1/8 7676 55 1/8 8977 61 1/8 10291 67 1/8 11600 37 1/4 5202 43 1/4 6430 49 1/4 7703 55 1/4 9005 61 1/4 10318 67 1/4 11627 37 3/8 5227 43 3/8 6456 49 3/8 7730 55 3/8 9032 61 3/8 10345 67 3/8 11654 37 1/2 5252 43 1/2 6482 49 1/2 7757 55 1/2 9059 61 1/2 10373 67 1/2 11681 37 5/8 5277 43 5/8 6508 49 5/8 7784 55 5/8 9086 61 5/8 10400 67 5/8 11708 37 3/4 5302 43 3/4 6534 49 3/4 7811 55 3/4 9114 61 3/4 10427 67 3/4 11736 37 7/8 5327 43 7/8 6561 49 7/8 7838 55 7/8 9141 61 7/8 10455 67 7/8 11763 38 5352 44 6587 50 7865 56 9168 62 10482 68 11790 38 1/8 5378 44 1/8 6613 50 1/8 7891 56 1/8 9196 62 1/8 10510 68 1/8 11817 38 1/4 5403 44 1/4 6639 50 1/4 7918 56 1/4 9223 62 1/4 10537 68 1/4 11844 38 3/8 5428 44 3/8 6666 50 3/8 7945 56 3/8 9250 62 3/8 10564 68 3/8 11871 38 1/2 5453 44 1/2 6692 50 1/2 7972 56 1/2 9278 62 1/2 10592 68 1/2 11898 38 5/8 5478 44 5/8 6718 50 5/8 7999 56 5/8 9305 62 5/8 10619 68 5/8 11925 38 3/4 5504 44 3/4 6745 50 3/4 8026 56 3/4 9332 62 3/4 10646 68 3/4 11952 38 7/8 5529 44 7/8 6771 50 7/8 8053 56 7/8 9360 62 7/8 10674 68 7/8 11979 39 5554 45 6797 51 8080 57 9387 63 10701 69 12006 39 1/8 5580 45 1/8 6824 51 1/8 8107 57 1/8 9414 63 1/8 10728 69 1/8 12033 39 1/4 5605 45 1/4 6850 51 1/4 8135 57 1/4 9442 63 1/4 10756 69 1/4 12060 39 3/8 5631 45 3/8 6876 51 3/8 8162 57 3/8 9469 63 3/8 10783 69 3/8 12087 39 1/2 5656 45 1/2 6903 51 1/2 8189 57 1/2 9497 63 1/2 10810 69 1/2 12114 39 5/8 5681 45 5/8 6929 51 5/8 8216 57 5/8 9524 63 5/8 10838 69 5/8 12141 39 3/4 5707 45 3/4 6956 51 3/4 8243 57 3/4 9551 63 3/4 10865 69 3/4 12168 39 7/8 5732 45 7/8 6982 51 7/8 8270 57 7/8 9579 63 7/8 10892 69 7/8 12195 40 5758 46 7009 52 8297 58 9606 64 10920 70 12221 40 1/8 5784 46 1/8 7035 52 1/8 8324 58 1/8 9633 64 1/8 10947 70 1/8 12248 40 1/4 5809 46 1/4 7062 52 1/4 8351 58 1/4 9661 64 1/4 10974 70 1/4 12275 40 3/8 5835 46 3/8 7088 52 3/8 8378 58 3/8 9688 64 3/8 11001 70 3/8 12302 40 1/2 5860 46 1/2 7115 52 1/2 8406 58 1/2 9716 64 1/2 11029 70 1/2 12329 40 5/8 5886 46 5/8 7142 52 5/8 8433 58 5/8 9743 64 5/8 11056 70 5/8 12356 40 3/4 5912 46 3/4 7168 52 3/4 8460 58 3/4 9770 64 3/4 11083 70 3/4 12383 40 7/8 5937 46 7/8 7195 52 7/8 8487 58 7/8 9798 64 7/8 11110 70 7/8 12409 41 5963 47 7221 53 8514 59 9825 65 11138 71 12436 41 1/8 5989 47 1/8 7248 53 1/8 8541 59 1/8 9852 65 1/8 11165 71 1/8 12463 41 1/4 6015 47 1/4 7275 53 1/4 8569 59 1/4 9880 65 1/4 11192 71 1/4 12490 41 3/8 6040 47 3/8 7301 53 3/8 8596 59 3/8 9907 65 3/8 11219 71 3/8 12516 41 1/2 6066 47 1/2 7328 53 1/2 8623 59 1/2 9935 65 1/2 11247 71 1/2 12543 41 5/8 6092 47 5/8 7355 53 5/8 8650 59 5/8 9962 65 5/8 11274 71 5/8 12570 41 3/4 6118 47 3/4 7381 53 3/4 8677 59 3/4 9989 65 3/4 11301 71 3/4 12597 41 7/8 6144 47 7/8 7408 53 7/8 8705 59 7/8 10017 65 7/8 11328 71 7/8 12623 42 6170 48 7435 54 8732 60 10044 66 11356 72 12650 Containment Solutions, Inc.2 (10') DWT-6 TYPE II 20,000 GALLON DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS 72 1/8 12677 78 1/8 13937 84 1/8 15146 90 1/8 16285 96 1/8 17334 102 1/8 18269 72 1/4 12703 78 1/4 13962 84 1/4 15170 90 1/4 16308 96 1/4 17355 102 1/4 18287 72 3/8 12730 78 3/8 13988 84 3/8 15195 90 3/8 16331 96 3/8 17375 102 3/8 18305 72 1/2 12757 78 1/2 14014 84 1/2 15219 90 1/2 16353 96 1/2 17396 102 1/2 18323 72 5/8 12783 78 5/8 14040 84 5/8 15243 90 5/8 16376 96 5/8 17417 102 5/8 18341 72 3/4 12810 78 3/4 14065 84 3/4 15268 90 3/4 16399 96 3/4 17437 102 3/4 18359 72 7/8 12836 78 7/8 14091 84 7/8 15292 90 7/8 16421 96 7/8 17458 102 7/8 18376 73 12863 79 14117 85 15317 91 16444 97 17478 103 18394 73 1/8 12889 79 1/8 14142 85 1/8 15341 91 1/8 16467 97 1/8 17498 103 1/8 18412 73 1/4 12916 79 1/4 14168 85 1/4 15365 91 1/4 16489 97 1/4 17519 103 1/4 18429 73 3/8 12943 79 3/8 14193 85 3/8 15389 91 3/8 16512 97 3/8 17539 103 3/8 18447 73 1/2 12969 79 1/2 14219 85 1/2 15414 91 1/2 16534 97 1/2 17559 103 1/2 18464 73 5/8 12995 79 5/8 14244 85 5/8 15438 91 5/8 16556 97 5/8 17579 103 5/8 18481 73 3/4 13022 79 3/4 14270 85 3/4 15462 91 3/4 16579 97 3/4 17600 103 3/4 18499 73 7/8 13048 79 7/8 14295 85 7/8 15486 91 7/8 16601 97 7/8 17620 103 7/8 18516 74 13075 80 14321 86 15510 92 16623 98 17640 104 18533 74 1/8 13101 80 1/8 14346 86 1/8 15534 92 1/8 16646 98 1/8 17660 104 1/8 18550 74 1/4 13128 80 1/4 14372 86 1/4 15558 92 1/4 16668 98 1/4 17680 104 1/4 18567 74 3/8 13154 80 3/8 14397 86 3/8 15582 92 3/8 16690 98 3/8 17699 104 3/8 18584 74 1/2 13180 80 1/2 14422 86 1/2 15606 92 1/2 16712 98 1/2 17719 104 1/2 18601 74 5/8 13207 80 5/8 14448 86 5/8 15630 92 5/8 16734 98 5/8 17739 104 5/8 18618 74 3/4 13233 80 3/4 14473 86 3/4 15654 92 3/4 16756 98 3/4 17759 104 3/4 18635 74 7/8 13259 80 7/8 14498 86 7/8 15678 92 7/8 16778 98 7/8 17778 104 7/8 18651 75 13286 81 14523 87 15701 93 16800 99 17798 105 18668 75 1/8 13312 81 1/8 14549 87 1/8 15725 93 1/8 16822 99 1/8 17817 105 1/8 18684 75 1/4 13338 81 1/4 14574 87 1/4 15749 93 1/4 16844 99 1/4 17837 105 1/4 18701 75 3/8 13364 81 3/8 14599 87 3/8 15773 93 3/8 16866 99 3/8 17856 105 3/8 18717 75 1/2 13391 81 1/2 14624 87 1/2 15796 93 1/2 16888 99 1/2 17876 105 1/2 18734 75 5/8 13417 81 5/8 14649 87 5/8 15820 93 5/8 16909 99 5/8 17895 105 5/8 18750 75 3/4 13443 81 3/4 14674 87 3/4 15843 93 3/4 16931 99 3/4 17914 105 3/4 18766 75 7/8 13469 81 7/8 14699 87 7/8 15867 93 7/8 16953 99 7/8 17933 105 7/8 18782 76 13495 82 14724 88 15891 94 16974 100 17953 106 18798 76 1/8 13521 82 1/8 14749 88 1/8 15914 94 1/8 16996 100 1/8 17972 106 1/8 18814 76 1/4 13548 82 1/4 14774 88 1/4 15937 94 1/4 17017 100 1/4 17991 106 1/4 18830 76 3/8 13574 82 3/8 14799 88 3/8 15961 94 3/8 17039 100 3/8 18010 106 3/8 18846 76 1/2 13600 82 1/2 14824 88 1/2 15984 94 1/2 17060 100 1/2 18029 106 1/2 18861 76 5/8 13626 82 5/8 14849 88 5/8 16008 94 5/8 17081 100 5/8 18047 106 5/8 18877 76 3/4 13652 82 3/4 14874 88 3/4 16031 94 3/4 17103 100 3/4 18066 106 3/4 18893 76 7/8 13678 82 7/8 14899 88 7/8 16054 94 7/8 17124 100 7/8 18085 106 7/8 18908 77 13704 83 14924 89 16077 95 17145 101 18104 107 18924 77 1/8 13730 83 1/8 14948 89 1/8 16101 95 1/8 17166 101 1/8 18122 107 1/8 18939 77 1/4 13756 83 1/4 14973 89 1/4 16124 95 1/4 17187 101 1/4 18141 107 1/4 18954 77 3/8 13782 83 3/8 14998 89 3/8 16147 95 3/8 17209 101 3/8 18159 107 3/8 18969 77 1/2 13808 83 1/2 15023 89 1/2 16170 95 1/2 17230 101 1/2 18178 107 1/2 18985 77 5/8 13833 83 5/8 15047 89 5/8 16193 95 5/8 17251 101 5/8 18196 107 5/8 19000 77 3/4 13859 83 3/4 15072 89 3/4 16216 95 3/4 17271 101 3/4 18214 107 3/4 19015 77 7/8 13885 83 7/8 15096 89 7/8 16239 95 7/8 17292 101 7/8 18233 107 7/8 19029 78 13911 84 15121 90 16262 96 17313 102 18251 108 19044 Containment Solutions, Inc.3 (10') DWT-6 TYPE II 20,000 GALLON DIPSTICK GALLONS DIPSTICK GALLONS 108 1/8 19059 114 1/8 19659 108 1/4 19074 114 1/4 19669 108 3/8 19088 114 3/8 19679 108 1/2 19103 114 1/2 19689 108 5/8 19117 114 5/8 19698 108 3/4 19131 114 3/4 19708 108 7/8 19146 114 7/8 19717 109 19160 115 19726 109 1/8 19174 115 1/8 19735 109 1/4 19188 115 1/4 19744 109 3/8 19202 115 3/8 19753 109 1/2 19215 115 1/2 19762 109 5/8 19229 115 5/8 19770 109 3/4 19243 115 3/4 19779 109 7/8 19256 115 7/8 19787 110 19270 116 19795 110 1/8 19283 116 1/8 19803 110 1/4 19296 116 1/4 19811 110 3/8 19310 116 3/8 19819 110 1/2 19323 116 1/2 19826 110 5/8 19336 116 5/8 19834 110 3/4 19349 116 3/4 19841 110 7/8 19361 116 7/8 19848 111 19374 117 19855 111 1/8 19387 117 1/8 19862 111 1/4 19399 117 1/4 19868 111 3/8 19412 117 3/8 19875 111 1/2 19424 117 1/2 19881 111 5/8 19436 117 5/8 19887 111 3/4 19448 117 3/4 19893 111 7/8 19460 117 7/8 19898 112 19472 118 19904 112 1/8 19484 118 1/8 19909 112 1/4 19496 118 1/4 19914 112 3/8 19508 118 3/8 19919 112 1/2 19519 118 1/2 19923 112 5/8 19530 118 5/8 19928 112 3/4 19542 118 3/4 19932 112 7/8 19553 118 7/8 19936 113 19564 119 19939 113 1/8 19575 119 1/8 19942 113 1/4 19586 119 1/4 19945 113 3/8 19597 119 3/8 19948 113 1/2 19607 119 1/2 19950 113 5/8 19618 119 5/8 19951 113 3/4 19628 113 7/8 19639 114 19649 How To Properly Gauge Your Tank Underground storage tanks require periodic measurement to determine current inventory level. Using the proper methods when gauging your tank's contents will insure the most accurate reading and insure that you do not damage your tank. The following procedure should be followed whenever you use a gauge stick to determine the amount of product that is in your tank: 1) Use a wood dipstick with a rubber or nylon tip. Metallic dipsticks are not recommended. This will insure that frequent tank gaugings or an accidental dropping of the gauge stick into the tank will not damage the tank bottom. 2) Slowly lower your gauge stick into the fill port until it touches the tank bottom. Never free drop the gauge stick. This can result in inaccurate measurements due to product splashing. Free dropping can also result in gauge stick damage and tank damage. 3) Remove your dipstick slowly and read the product level directly from the gauge stick. Water Paste Detection To detect water in the tank bottom, water detection paste is available from petroleum equipment distributors. However, some water detection paste cannot detect antifreeze mixtures. If antifreeze mixtures are used for the cavity monitoring fluid, the following product is capable of detecting water or antifreeze (brine or up to 50 percent glycol) solution in the tank water bottoms: WATER FINDER #7686-1870 DAYCO/NATIONAL DAYTON, OH TEL: 1-800-283-2926 FAX: 1-800-688-4854 Caution Pressurized deliveries are not recommended. If the delivery vehicle uses pumps to fill the tank, install overfill shutoff equipment in the tank and truck to prevent the tank from being overfilled. Overfilling the tank under pressure will damage the tank even if the tank vent is unrestricted. Containment Solutions, Inc. 5150 Jefferson Chemical Road Conroe, TX 77301 Tel: 936-756-7731 Fax: 936-756-7766 Note: Calibration chart is based on the fluid level above a 5/16" deflector plate. Containment Solutions, Inc.4 (4') DWT-6 TYPE II 1,500 GALLON DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS DIPSTICK GALLONS 1/8 2 6 1/8 117 12 1/8 306 18 1/8 533 24 1/8 775 30 1/8 1016 1/4 3 6 1/4 120 12 1/4 311 18 1/4 537 24 1/4 780 30 1/4 1021 3/8 4 6 3/8 124 12 3/8 315 18 3/8 542 24 3/8 785 30 3/8 1026 1/2 5 6 1/2 127 12 1/2 320 18 1/2 547 24 1/2 790 30 1/2 1031 5/8 7 6 5/8 131 12 5/8 324 18 5/8 552 24 5/8 795 30 5/8 1036 3/4 8 6 3/4 134 12 3/4 329 18 3/4 557 24 3/4 800 30 3/4 1040 7/8 9 6 7/8 138 12 7/8 333 18 7/8 562 24 7/8 805 30 7/8 1045 1 11 7 141 13 338 19 567 25 811 31 1050 1 1/8 12 7 1/8 145 13 1/8 342 19 1/8 572 25 1/8 816 31 1/8 1055 1 1/4 14 7 1/4 149 13 1/4 347 19 1/4 577 25 1/4 821 31 1/4 1060 1 3/8 16 7 3/8 152 13 3/8 351 19 3/8 582 25 3/8 826 31 3/8 1065 1 1/2 18 7 1/2 156 13 1/2 356 19 1/2 587 25 1/2 831 31 1/2 1069 1 5/8 19 7 5/8 159 13 5/8 360 19 5/8 592 25 5/8 836 31 5/8 1074 1 3/4 21 7 3/4 163 13 3/4 365 19 3/4 597 25 3/4 841 31 3/4 1079 1 7/8 23 7 7/8 167 13 7/8 370 19 7/8 602 25 7/8 846 31 7/8 1084 2 25 8 171 14 374 20 607 26 851 32 1088 2 1/8 27 8 1/8 174 14 1/8 379 20 1/8 612 26 1/8 856 32 1/8 1093 2 1/4 30 8 1/4 178 14 1/4 383 20 1/4 617 26 1/4 861 32 1/4 1098 2 3/8 32 8 3/8 182 14 3/8 388 20 3/8 622 26 3/8 866 32 3/8 1103 2 1/2 34 8 1/2 186 14 1/2 393 20 1/2 628 26 1/2 871 32 1/2 1107 2 5/8 36 8 5/8 190 14 5/8 397 20 5/8 633 26 5/8 877 32 5/8 1112 2 3/4 39 8 3/4 194 14 3/4 402 20 3/4 638 26 3/4 882 32 3/4 1117 2 7/8 41 8 7/8 198 14 7/8 407 20 7/8 643 26 7/8 887 32 7/8 1121 3 44 9 202 15 412 21 648 27 892 33 1126 3 1/8 46 9 1/8 205 15 1/8 416 21 1/8 653 27 1/8 897 33 1/8 1131 3 1/4 49 9 1/4 209 15 1/4 421 21 1/4 658 27 1/4 902 33 1/4 1135 3 3/8 51 9 3/8 213 15 3/8 426 21 3/8 663 27 3/8 907 33 3/8 1140 3 1/2 54 9 1/2 217 15 1/2 430 21 1/2 668 27 1/2 912 33 1/2 1145 3 5/8 56 9 5/8 222 15 5/8 435 21 5/8 673 27 5/8 917 33 5/8 1149 3 3/4 59 9 3/4 226 15 3/4 440 21 3/4 678 27 3/4 922 33 3/4 1154 3 7/8 62 9 7/8 230 15 7/8 445 21 7/8 683 27 7/8 927 33 7/8 1158 4 65 10 234 16 450 22 688 28 932 34 1163 4 1/8 67 10 1/8 238 16 1/8 454 22 1/8 693 28 1/8 937 34 1/8 1168 4 1/4 70 10 1/4 242 16 1/4 459 22 1/4 699 28 1/4 942 34 1/4 1172 4 3/8 73 10 3/8 246 16 3/8 464 22 3/8 704 28 3/8 947 34 3/8 1177 4 1/2 76 10 1/2 250 16 1/2 469 22 1/2 709 28 1/2 952 34 1/2 1181 4 5/8 79 10 5/8 255 16 5/8 474 22 5/8 714 28 5/8 957 34 5/8 1186 4 3/4 82 10 3/4 259 16 3/4 479 22 3/4 719 28 3/4 962 34 3/4 1190 4 7/8 85 10 7/8 263 16 7/8 483 22 7/8 724 28 7/8 967 34 7/8 1195 5 88 11 267 17 488 23 729 29 972 35 1199 5 1/8 91 11 1/8 272 17 1/8 493 23 1/8 734 29 1/8 977 35 1/8 1203 5 1/4 94 11 1/4 276 17 1/4 498 23 1/4 739 29 1/4 982 35 1/4 1208 5 3/8 97 11 3/8 280 17 3/8 503 23 3/8 744 29 3/8 987 35 3/8 1212 5 1/2 101 11 1/2 284 17 1/2 508 23 1/2 749 29 1/2 992 35 1/2 1217 5 5/8 104 11 5/8 289 17 5/8 513 23 5/8 755 29 5/8 996 35 5/8 1221 5 3/4 107 11 3/4 293 17 3/4 518 23 3/4 760 29 3/4 1001 35 3/4 1225 5 7/8 110 11 7/8 298 17 7/8 523 23 7/8 765 29 7/8 1006 35 7/8 1230 6 114 12 302 18 528 24 770 30 1011 36 1234 Containment Solutions, Inc.1 (4') DWT-6 TYPE II 1,500 GALLON DIPSTICK GALLONS DIPSTICK GALLONS 36 1/8 1238 42 1/8 1420 36 1/4 1243 42 1/4 1423 36 3/8 1247 42 3/8 1426 36 1/2 1251 42 1/2 1429 36 5/8 1255 42 5/8 1432 36 3/4 1260 42 3/4 1435 36 7/8 1264 42 7/8 1438 37 1268 43 1441 37 1/8 1272 43 1/8 1444 37 1/4 1276 43 1/4 1447 37 3/8 1280 43 3/8 1450 37 1/2 1285 43 1/2 1452 37 5/8 1289 43 5/8 1455 37 3/4 1293 43 3/4 1458 37 7/8 1297 43 7/8 1460 38 1301 44 1463 38 1/8 1305 44 1/8 1466 38 1/4 1309 44 1/4 1468 38 3/8 1313 44 3/8 1471 38 1/2 1317 44 1/2 1473 38 5/8 1321 44 5/8 1475 38 3/4 1324 44 3/4 1478 38 7/8 1328 44 7/8 1480 39 1332 45 1482 39 1/8 1336 45 1/8 1485 39 1/4 1340 45 1/4 1487 39 3/8 1344 45 3/8 1489 39 1/2 1347 45 1/2 1491 39 5/8 1351 45 5/8 1493 39 3/4 1355 45 3/4 1495 39 7/8 1358 45 7/8 1497 40 1362 46 1498 40 1/8 1366 46 1/8 1500 40 1/4 1369 46 1/4 1502 40 3/8 1373 46 3/8 1503 40 1/2 1376 46 1/2 1505 40 5/8 1380 46 5/8 1506 40 3/4 1383 46 3/4 1508 40 7/8 1387 46 7/8 1509 41 1390 47 1510 41 1/8 1394 47 1/8 1511 41 1/4 1397 47 1/4 1512 41 3/8 1400 47 3/8 1513 41 1/2 1404 47 1/2 1514 41 5/8 1407 47 5/8 1514 41 3/4 1410 41 7/8 1414 42 1417 HOW TO PROPERLY GAUGE YOUR TANK: Underground storage tanks require periodic measurement to determine current inventory level.Using the proper methodswhen gauging your tank's contents will insure themost accurate reading and insure that you do not damage your tank.The following procedureshould be followed whenever you use a gauge stick to determine the amount of product that is in your tank: 1)Use a wood dipstick with a rubber or nylon tip.Metallic dipsticks arenot recommended.This will insure thatfrequenttank gaugings or an accidental dropping of the gauge stick into the tank will not damage the tank bottom. 2)Slowly lower your gauge stick into the fill port until it touches the tank bottom.Never free drop the gauge stick.This can result in inaccurate measurements due to product splashing. Free dropping can also result in gauge stick damage and tank damage. 3) Remove your dipstick slowly and read the product level directly from the gauge stick. Water Paste Detection To detect water in the tank bottom,water detection paste is available from petroleum equipment distributors.However,some water detection paste cannot detect antifreeze mixtures.If antifreeze mixtures are used for the cavity monitoring fluid,the following product is capable of detecting water or antifreeze (brine or up to 50 percent glycol) solution in the tank water bottoms: WATER FINDER #7686-1870 DAYCO/NATIONAL DAYTON, OH TEL: 1-800-283-2926 FAX: 1-800-688-4854 Caution Pressurized deliveries are not recommended.If the delivery vehicle uses pumps to fill the tank,install overfill shutoff equipment in the tank and truck to prevent the tank from being overfilled.Overfilling the tank under pressure will damage the tank even if the tank vent is unrestricted. Containment Solutions, Inc. 5150 Jefferson Chemical Road Conroe, TX 77301 Tel: 936-756-7731 Fax: 936-756-7766 Note: Calibration chart is based on the fluid level above a 5/16" deflector plate. Pub. No. CAL 8415-DWT Containment Solutions, Inc.2 24 Overfill Protection Testing Scope This procedure will provide a Veeder-Root ATG certified technician a procedure to safely test tank overfill protection. Reference Documents •Veeder-Root TLS-3XX Operators Manual (576013-610) •Veeder-Root TLS-3XX Setup Manual (576013-623) •Veeder-Root TLS-450 Setup and Operation Screens Manual (577013-940) •Veeder-Root TLS-450PLUS/TLS4 Operator’s Manual (577014-110) •Veeder-Root TLS4 Quick Start (577014-034) •Veeder-Root Overfill Alarm Installation Guide (576013-589) Consoles TLS-450PLUS, TLS4c, TLS4i, TLS-450 and TLS3XX Requirements TLS-450PLUS, TLS4c, TLS4i, TLS-450: Automatic Event: Device Task programmed to trigger on Tank Overfill and close a relay feeding voltage to the Overfill alarm device. TLS-3XX: Output relay programmed to close a relay on a Tank Overfill alarm feeding voltage to the Overfill alarm device. Testing Procedure 1. Inspection a. Verify the levels in the tank to make sure there is product in the tank and that the tank is enabled. b. If the site is currently receiving a delivery, wait until the delivery is complete. c. If the tank is performing a SLD tank test, stop the test. 2. Preparation a. Turn Alarm filtering off, as this will allow you to clear alarms quicker. Refer to TLS-3XX Setup manual (576013-623) or TLS4XX on-line help. b. Program Delivery delay to 1 minute, this will allow the delivery to be completed quicker. 1. Note the customers original value, so you can restore it after the test. Overfill Protection Testing Testing Procedure 25 c. Print the Tank Inventory Report. d. Test the relay assigned to the external Overfill alarm (if present) to insure the Overfill alarm works. 1. If the Overfill alarm does not sound, repair the device before continuing testing. Testing ATurn off power to the console. BDisconnect the probe from the field wiring and remove it from the riser. If you are testing more than one tank remove all the probes from their risers. CLay the probe safely on the ground and reattach the field wiring. DPosition the water float at the bottom of the probe and the product float 25% up from the bottom of the