HomeMy WebLinkAbout2022 FMC Results - PassAppendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10125616 01-25-2022 Express Gas 928 Flower Street Bakersfield 93305 Confidence UST Services, Inc.(800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Ronald Clark 1073967 9482314 06-15-2022 Veeder-Root C27795 08-26-2022 01-25-2022 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Gilbarco Veeder-Root TLS-350 Plus 336.01 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 794380-420 87-91 Annular L2 794380-208 87 STP L3 794380-208 87 Fill L4 794380-208 91 STP L5 794380-208 91 FILL L6 794380-208 Disp 1-2 L7 794380-208 Disp 3-4 L8 794380-208 Disp 5-6 L10 794380-208 Disp 9-10 L11 794380-208 Disp 11-12 L12 794380-208 Disp 7-8 Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 reg unleade Fx1v Unleaded T2 super unlea Fx1v Supreme Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10125616 01-25-2022 Express Gas 928 Flower Street Bakersfield 93305 Confidence UST Services, Inc.(800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Ronald Clark 1073967 9482314 06-15-2022 FFS 1014543712 12-04-2022 Hydrostatic Spill buckets 01-25-2022 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1 regular unleaded Phil-Tite T2 super unleaded Phil-Tite Setup for flower st 200 FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 JAN 25, 2022 12:28 PM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 REGULAR UNL 7894 61.24 0.0 58.8 4133 2 SUPER UNL 2123 32.12 0.0 63.9 6066 I90500 JAN 25, 2022 12:28 PM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JAN 25, 2022 12:28 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JAN 25, 2022 12:28 PM SHIFT TIME 1 : 2:00 AM I50202 JAN 25, 2022 12:28 PM SHIFT TIME 2 : DISABLED I50203 JAN 25, 2022 12:28 PM SHIFT TIME 3 : DISABLED I50204 JAN 25, 2022 12:28 PM SHIFT TIME 4 : DISABLED I54600 JAN 25, 2022 12:28 PM TANK PER TST NEEDED WRN: DISABLED I54900 JAN 25, 2022 12:28 PM TANK ANN TST NEEDED WRN: DISABLED I55300 JAN 25, 2022 12:28 PM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JAN 25, 2022 12:28 PM LINE PER TST NEEDED WRN: DISABLED I55900 JAN 25, 2022 12:28 PM LINE ANN TST NEEDED WRN: DISABLED I50D00 JAN 25, 2022 12:28 PM PRINT TC VOLUMES ENABLED I50E00 JAN 25, 2022 12:28 PM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JAN 25, 2022 12:28 PM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JAN 25, 2022 12:28 PM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JAN 25, 2022 12:28 PM DAYLIGHT SAVING TIME DISABLED I51B00 JAN 25, 2022 12:28 PM I51600 JAN 25, 2022 12:28 PM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JAN 25, 2022 12:28 PM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JAN 25, 2022 12:28 PM TANK CHART SECURITY DISABLED I5BD00 JAN 25, 2022 12:28 PM CUSTOM ALARM LABELS DISABLED I56000 JAN 25, 2022 12:28 PM MASS/DENSITY DISABLED I88101 JAN 25, 2022 12:28 PM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JAN 25, 2022 12:28 PM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 1200 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88103 JAN 25, 2022 12:28 PM I88104 JAN 25, 2022 12:28 PM I88105 JAN 25, 2022 12:28 PM I88106 JAN 25, 2022 12:28 PM I52000 JAN 25, 2022 12:28 PM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE JUN 26, 2015 DISABLED 2 ON DATE JUN 26, 2015 DISABLED 3 ON DATE JUN 26, 2015 DISABLED 4 ON DATE JUN 26, 2015 DISABLED 5 ON DATE JUN 26, 2015 DISABLED 6 ON DATE JUN 26, 2015 DISABLED 7 ON DATE JUN 26, 2015 DISABLED 8 ON DATE JUN 26, 2015 DISABLED I60100 JAN 25, 2022 12:29 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 REGULAR UNL ON 2 SUPER UNL ON 3 OFF 4 OFF I60200 JAN 25, 2022 12:29 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 REGULAR UNL 2 SUPER UNL 3 4 I60300 JAN 25, 2022 12:29 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 REGULAR UNL 1 2 SUPER UNL 2 3 3 4 4 I60900 JAN 25, 2022 12:29 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 REGULAR UNL 0.000700 2 SUPER UNL 0.000700 3 0.000000 4 0.000000 I60700 JAN 25, 2022 12:29 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 REGULAR UNL 109.00 2 SUPER UNL 109.00 3 0.00 4 0.00 I60A00 JAN 25, 2022 12:29 PM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 REGULAR UNL 20 PTS 12027 2 SUPER UNL 20 PTS 8189 3 1 PT 0 4 1 PT 0 I60400 JAN 25, 2022 12:29 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 12027 2 SUPER UNL 8189 3 0 4 0 I60500 JAN 25, 2022 12:29 PM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 12027 10372 6531 2759 2 SUPER UNL 8189 6711 4229 1698 3 0 0 0 0 4 0 0 0 0 I60600 JAN 25, 2022 12:29 PM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 12027 11916 11547 11066 10511 10372 9655 9356 8538 7693 6531 5965 5124 4321 3532 2759 2032 1372 795 485 2 SUPER UNL 8189 8089 7850 7520 7141 6711 6259 5770 5269 4751 4229 3699 3180 2667 2175 1698 1258 847 490 198 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JAN 25, 2022 12:29 PM TANK PRODUCT LABEL METER DATA 1 REGULAR UNL NO 2 SUPER UNL NO 3 NO 4 NO I62F00 JAN 25, 2022 12:29 PM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 REGULAR UNL 4.0 IN. 2 SUPER UNL 4.0 IN. I62700 JAN 25, 2022 12:29 PM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 REGULAR UNL 3.0 2 SUPER UNL 3.0 I64200 JAN 25, 2022 12:29 PM WATER ALARM FILTER TANK PRODUCT LABEL 1 REGULAR UNL LOW 2 SUPER UNL LOW I62400 JAN 25, 2022 12:29 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 REGULAR UNL 2.0 2 SUPER UNL 2.0 I62800 JAN 25, 2022 12:29 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 12027 2 SUPER UNL 8189 3 0 4 0 I62300 JAN 25, 2022 12:29 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 10824 2 SUPER UNL 7370 3 0 4 0 I62200 JAN 25, 2022 12:29 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 11426 2 SUPER UNL 7780 3 0 4 0 I62900 JAN 25, 2022 12:29 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 1203 2 SUPER UNL 819 3 0 4 0 I62100 JAN 25, 2022 12:29 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 222 2 SUPER UNL 400 3 0 4 0 I62600 JAN 25, 2022 12:29 PM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 99 2 SUPER UNL 99 3 99 4 99 I62500 JAN 25, 2022 12:30 PM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 99 2 SUPER UNL 99 3 99 4 99 I60800 JAN 25, 2022 12:30 PM TANK TILT TANK PRODUCT LABEL INCHES 1 REGULAR UNL 0.00 2 SUPER UNL 0.00 3 0.00 4 0.00 I60B00 JAN 25, 2022 12:30 PM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JAN 25, 2022 12:30 PM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 REGULAR UNL 0.00 2 SUPER UNL 0.00 3 0.00 4 0.00 I61200 JAN 25, 2022 12:30 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 REGULAR UNL NONE NONE 2 SUPER UNL NONE NONE 3 NONE NONE 4 NONE NONE I63600 JAN 25, 2022 12:30 PM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 1202 2 SUPER UNL 818 3 0 4 0 I62A00 JAN 25, 2022 12:30 PM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 1202 2 SUPER UNL 818 3 0 4 0 I62C00 JAN 25, 2022 12:30 PM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 REGULAR UNL STANDARD 2 SUPER UNL STANDARD 3 STANDARD 4 STANDARD I62D00 JAN 25, 2022 12:30 PM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 REGULAR UNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 SUPER UNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JAN 25, 2022 12:30 PM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 REGULAR UNL OFF OFF 2 SUPER UNL OFF OFF 3 OFF OFF 4 OFF OFF I63000 JAN 25, 2022 12:30 PM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 REGULAR UNL OFF 2 SUPER UNL OFF 3 OFF 4 OFF I63200 JAN 25, 2022 12:30 PM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 REGULAR UNL OFF 2 SUPER UNL OFF 3 OFF 4 OFF I61000 JAN 25, 2022 12:30 PM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 REGULAR UNL 1 2 SUPER UNL 1 3 1 4 1 I63A00 JAN 25, 2022 12:30 PM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 REGULAR UNL 10.00% 2 SUPER UNL 10.00% 3 10.00% 4 10.00% I61100 JAN 25, 2022 12:30 PM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK OCT 1, 2014 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JAN 25, 2022 12:30 PM CSLD PROBABLITY OF DETECTION I61400 JAN 25, 2022 12:30 PM CSLD CLIMATE FACTOR I61600 JAN 25, 2022 12:30 PM TANK PRODUCT LABEL CAL UPDATE 1 REGULAR UNL IMMEDIATE 2 SUPER UNL IMMEDIATE 3 IMMEDIATE 4 IMMEDIATE I61A00 JAN 25, 2022 12:30 PM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 REGULAR UNL DISABLED 2 SUPER UNL DISABLED 3 DISABLED 4 DISABLED I61B00 JAN 25, 2022 12:30 PM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JAN 25, 2022 12:30 PM CSLD REPORT ONLY I62B00 JAN 25, 2022 12:30 PM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 REGULAR UNL ??? 0, 0 2 SUPER UNL ??? 0, 0 3 ??? 0, 0 4 ??? 0, 0 I63300 JAN 25, 2022 12:30 PM LEAK TEST REPORT FORMAT: NORMAL I63400 JAN 25, 2022 12:31 PM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 0 2 SUPER UNL 0 3 0 4 0 I63500 JAN 25, 2022 12:31 PM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 REGULAR UNL 1 2 SUPER UNL 1 3 1 4 1 I63900 JAN 25, 2022 12:31 PM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 REGULAR UNL END FACTOR: NONE 2 SUPER UNL END FACTOR: NONE 3 END FACTOR: NONE 4 END FACTOR: NONE I78000 JAN 25, 2022 12:31 PM I77700 JAN 25, 2022 12:31 PM I77800 JAN 25, 2022 12:31 PM I78C00 JAN 25, 2022 12:31 PM I78300 JAN 25, 2022 12:31 PM I78F00 JAN 25, 2022 12:31 PM I78700 JAN 25, 2022 12:31 PM I70200 JAN 25, 2022 12:31 PM LIQUID LABEL DEVICE LABEL 1 87-91 ANNULAR 2 87 STP 3 87 FILL 4 91 STP 5 91 FILL 6 DISP 1-2 7 DISP 3-4 8 DISP 5-6 9 DISP 7-8 10 DISP 9-10 11 DISP 11-12 12 DISP 7-8 13 14 15 16 I70300 JAN 25, 2022 12:31 PM LIQUID TYPE SENSOR LOCATION TYPE 1 87-91 ANNULAR TRI-STATE (SINGLE FLOAT) 2 87 STP TRI-STATE (SINGLE FLOAT) 3 87 FILL TRI-STATE (SINGLE FLOAT) 4 91 STP TRI-STATE (SINGLE FLOAT) 5 91 FILL TRI-STATE (SINGLE FLOAT) 6 DISP 1-2 TRI-STATE (SINGLE FLOAT) 7 DISP 3-4 TRI-STATE (SINGLE FLOAT) 8 DISP 5-6 TRI-STATE (SINGLE FLOAT) 9 DISP 7-8 TRI-STATE (SINGLE FLOAT) 10 DISP 9-10 TRI-STATE (SINGLE FLOAT) 11 DISP 11-12 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JAN 25, 2022 12:31 PM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 87-91 ANNULAR ANNULAR SPACE 2 87 STP STP SUMP 3 87 FILL PIPING SUMP 4 91 STP STP SUMP 5 91 FILL PIPING SUMP 6 DISP 1-2 DISPENSER PAN 7 DISP 3-4 DISPENSER PAN 8 DISP 5-6 DISPENSER PAN 9 DISP 7-8 DISPENSER PAN 10 DISP 9-10 DISPENSER PAN 11 DISP 11-12 DISPENSER PAN 12 DISP 7-8 DISPENSER PAN 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 JAN 25, 2022 12:31 PM I74300 JAN 25, 2022 12:31 PM I74400 JAN 25, 2022 12:31 PM I74700 JAN 25, 2022 12:31 PM I74800 JAN 25, 2022 12:31 PM I74900 JAN 25, 2022 12:31 PM I7BC00 JAN 25, 2022 12:31 PM I80200 JAN 25, 2022 12:31 PM I80300 JAN 25, 2022 12:31 PM I80400 JAN 25, 2022 12:31 PM I80700 JAN 25, 2022 12:31 PM RELAY LABEL DEVICE LABEL 1 REGULAR UNL 2 SUPER UNL 3 OVERFILL 4 I80900 JAN 25, 2022 12:31 PM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 REGULAR UNL NORMALLY CLOSED 2 SUPER UNL NORMALLY CLOSED 3 OVERFILL NORMALLY OPEN 4 NORMALLY OPEN I80B00 JAN 25, 2022 12:31 PM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 REGULAR UNL 1 2 SUPER UNL 2 3 OVERFILL NONE 4 NONE I80A00 JAN 25, 2022 12:31 PM RELAY TYPE RELAY DESIGNATION TYPE 1 REGULAR UNL STANDARD 2 SUPER UNL STANDARD 3 OVERFILL STANDARD 4 STANDARD I80C00 JAN 25, 2022 12:31 PM I80800 JAN 25, 2022 12:31 PM RELAY SETUP REPORT R 1:REGULAR UNL TYPE: STANDARD NORMALLY CLOSED TANK #: 1 IN-TANK ALARMS T 1:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 2:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 2:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 2:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP EMISSIONS FAIL VP PRESSURE FAIL VP DUTY CYCLE FAIL PMC SETUP FAIL R 2:SUPER UNL TYPE: STANDARD NORMALLY CLOSED TANK #: 2 IN-TANK ALARMS T 2:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 4:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 4:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP EMISSIONS FAIL VP PRESSURE FAIL VP DUTY CYCLE FAIL R 3:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 JAN 25, 2022 12:32 PM EDIM:1 VR:349643-001-B TD:97.10.27.11.25 I79100 JAN 25, 2022 12:32 PM I72300 JAN 25, 2022 12:32 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VAPOR PRESSUR VAPOR PRESSURE 02 FM 1-2 AIR FLOW METER 03 FM 3-4 AIR FLOW METER 04 FM 5-6 AIR FLOW METER 05 FM 7-8 AIR FLOW METER 06 FM 9-10 AIR FLOW METER 07 FM 11-12 AIR FLOW METER 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JAN 25, 2022 12:32 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JAN 25, 2022 12:32 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JAN 25, 2022 12:32 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 VAPOR PROCESSOR TYPE NONE IV4700 JAN 25, 2022 12:32 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 ASSESSMENT TIME START TIME: 1:15 PM TIME DELAY MINUTES: 1 IV5200 JAN 25, 2022 12:32 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 ACCEPT HIGH ORVR: NO IV4A00 JAN 25, 2022 12:33 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 02 BLEND3 02 02 02 01 02 BLEND3 03 03 03 02 02 BLEND3 04 04 04 02 02 BLEND3 05 05 05 03 02 BLEND3 06 06 06 03 02 BLEND3 07 07 07 04 02 BLEND3 08 08 08 04 02 BLEND3 09 09 09 05 02 BLEND3 10 16 10 05 02 BLEND3 11 17 11 06 02 BLEND3 12 18 12 06 02 BLEND3 IV4B00 JAN 25, 2022 12:33 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 09/01 01/01 xx/xx 02 01 02/02 09/02 01/02 xx/xx 03 02 02/03 09/03 01/03 xx/xx 04 02 02/04 09/04 01/04 xx/xx 05 03 02/05 09/05 01/05 xx/xx 06 03 02/06 09/06 01/06 xx/xx 07 04 02/07 09/07 01/07 xx/xx 08 04 09/08 02/08 01/08 xx/xx 09 05 02/09 09/09 01/09 xx/xx 16 05 02/10 09/10 01/10 xx/xx 17 06 02/11 09/11 01/11 xx/xx 18 06 02/12 09/12 01/12 xx/xx IV4900 JAN 25, 2022 12:33 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JAN 25, 2022 12:33 PM ISD VERSION: 01.06 Flower St. Alarm before I10200 JAN 25, 2022 8:59 AM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 10338915 10514376 2 UNUSED 10296801 10401319 3 UNUSED 10293976 10394767 4 8SMARTSENSOR BD 39519 39534 5 4 PROBE / G.T. 163516 163571 6 INTERSTITIAL BD 201358 201637 7 INTERSTITIAL BD 201563 201771 8 UNUSED 10302035 10401513 9 UNUSED 10288122 10384898 10 RELAY BOARD 14978 14986 11 UNUSED 10295874 10391751 12 UNUSED 10296334 10382901 13 UNUSED 10290465 10379678 14 UNUSED 10283523 10377466 15 UNUSED 10292523 10383223 16 UNUSED 10289195 10375855 COMM 1 ELEC DISP INT. 100618 100653 COMM 2 RS232 SERIAL BD 14912 14921 COMM 3 UNUSED 10299707 10382707 COMM 4 UNUSED 10287705 10374587 COMM 5 UNUSED 10286808 10373255 COMM 6 UNUSED 10284990 10369947 I90200 JAN 25, 2022 8:59 AM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JAN 25, 2022 8:59 AM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD GROSS PRES FAIL CLEAR 11-28-21 1:30PM OTHER ISD GROSS PRES FAIL ALARM 11-28-21 1:17PM OTHER ISD GROSS PRES FAIL CLEAR 11-28-21 1:17PM OTHER ISD GROSS PRES FAIL ALARM 11-27-21 1:17PM OTHER ISD GROSS PRES FAIL CLEAR 11-13-21 1:30PM OTHER ISD GROSS PRES FAIL ALARM 11-13-21 1:17PM T 1 TANK REGULAR UNL OVERFILL ALARM CLEAR 10-25-21 4:56PM T 1 TANK REGULAR UNL OVERFILL ALARM ALARM 10-25-21 4:50PM L 5 PIPE 91 FILL FUEL ALARM ALARM 10-25-21 11:43AM E 1 OTHER G COMMUNICATION ALARM CLEAR 10-18-21 2:37AM E 1 OTHER G COMMUNICATION ALARM ALARM 10-18-21 2:36AM E 1 OTHER G COMMUNICATION ALARM CLEAR 10-12-21 6:58AM E 1 OTHER G COMMUNICATION ALARM ALARM 10-12-21 6:58AM T 1 TANK REGULAR UNL OVERFILL ALARM CLEAR 9-23-21 1:05AM T 1 TANK REGULAR UNL OVERFILL ALARM ALARM 9-23-21 1:01AM T 1 TANK REGULAR UNL OVERFILL ALARM CLEAR 6-01-21 7:39PM T 1 TANK REGULAR UNL OVERFILL ALARM ALARM 6-01-21 7:36PM E 1 OTHER G COMMUNICATION ALARM CLEAR 5-13-21 12:11PM E 1 OTHER G COMMUNICATION ALARM ALARM 5-13-21 11:11AM E 1 OTHER G COMMUNICATION ALARM CLEAR 5-13-21 11:10AM E 1 OTHER G COMMUNICATION ALARM ALARM 5-13-21 11:07AM T 1 TANK REGULAR UNL OVERFILL ALARM CLEAR 5-10-21 8:53AM T 1 TANK REGULAR UNL OVERFILL ALARM ALARM 5-10-21 8:45AM T 1 TANK REGULAR UNL OVERFILL ALARM CLEAR 5-10-21 8:45AM T 1 TANK REGULAR UNL OVERFILL ALARM ALARM 5-10-21 8:43AM T 1 TANK REGULAR UNL OVERFILL ALARM CLEAR 5-10-21 8:43AM T 1 TANK REGULAR UNL OVERFILL ALARM ALARM 5-10-21 8:40AM T 1 TANK REGULAR UNL PROBE OUT CLEAR 4-28-21 1:24PM T 1 TANK REGULAR UNL OVERFILL ALARM CLEAR 4-28-21 1:23PM T 1 TANK REGULAR UNL PROBE OUT ALARM 4-28-21 1:23PM T 1 TANK REGULAR UNL OVERFILL ALARM ALARM 4-28-21 1:23PM T 1 TANK REGULAR UNL PROBE OUT CLEAR 4-28-21 1:22PM T 1 TANK REGULAR UNL PROBE OUT ALARM 4-28-21 1:18PM L 4 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L 3 PIPE 87 FILL SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L 5 PIPE 91 FILL SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L 2 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L 1 ANNULAR 87-91 ANNULAR SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L11 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L10 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 4-28-21 1:17PM L 4 STP SUMP 91 STP SENSOR OUT ALARM ALARM 4-28-21 1:16PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 4-28-21 1:16PM L 3 PIPE 87 FILL SENSOR OUT ALARM ALARM 4-28-21 1:16PM L11 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 4-28-21 1:16PM L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 4-28-21 1:16PM L10 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 4-28-21 1:16PM I11200 JAN 25, 2022 9:00 AM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD GROSS PRES WARN CLEAR 1-25-22 8:53AM OTHER ISD GROSS PRES WARN ALARM 1-23-22 1:18PM OTHER ISD GROSS PRES WARN CLEAR 1-17-22 3:31AM SYSTEM PRINTER ERROR CLEAR 1-16-22 5:14PM SYSTEM PAPER OUT CLEAR 1-16-22 5:14PM SYSTEM PRINTER ERROR ALARM 1-16-22 5:14PM SYSTEM PAPER OUT ALARM 1-16-22 5:14PM OTHER ISD GROSS PRES WARN ALARM 1-12-22 1:18PM OTHER ISD GROSS PRES WARN CLEAR 1-06-22 11:48AM OTHER ISD GROSS PRES WARN ALARM 1-02-22 1:18PM OTHER ISD GROSS PRES WARN CLEAR 12-27-21 9:21AM OTHER ISD GROSS PRES WARN ALARM 12-24-21 1:18PM SYSTEM PRINTER ERROR CLEAR 12-20-21 1:25PM SYSTEM PAPER OUT CLEAR 12-20-21 1:25PM SYSTEM PRINTER ERROR ALARM 12-20-21 1:25PM SYSTEM PAPER OUT ALARM 12-20-21 1:25PM SYSTEM PRINTER ERROR CLEAR 12-20-21 1:25PM SYSTEM PAPER OUT CLEAR 12-20-21 1:25PM SYSTEM PAPER OUT ALARM 12-20-21 1:24PM SYSTEM PRINTER ERROR ALARM 12-20-21 1:24PM SYSTEM PRINTER ERROR CLEAR 12-20-21 1:24PM SYSTEM PAPER OUT CLEAR 12-20-21 1:24PM SYSTEM PRINTER ERROR ALARM 12-20-21 1:24PM SYSTEM PAPER OUT ALARM 12-20-21 1:24PM SYSTEM PRINTER ERROR CLEAR 12-20-21 1:24PM SYSTEM PAPER OUT CLEAR 12-20-21 1:24PM SYSTEM PRINTER ERROR ALARM 12-20-21 1:24PM SYSTEM PAPER OUT ALARM 12-20-21 1:24PM OTHER ISD GROSS PRES WARN CLEAR 12-17-21 1:49PM OTHER ISD GROSS PRES WARN ALARM 12-12-21 1:18PM T 1 TANK REGULAR UNL DELIVERY NEEDED CLEAR 12-10-21 4:07PM T 1 TANK REGULAR UNL INVALID FUEL LEVEL CLEAR 12-10-21 4:06PM T 1 TANK REGULAR UNL INVALID FUEL LEVEL ALARM 12-10-21 12:54PM T 1 TANK REGULAR UNL DELIVERY NEEDED ALARM 12-10-21 8:55AM T 1 TANK REGULAR UNL DELIVERY NEEDED CLEAR 12-06-21 5:06PM T 1 TANK REGULAR UNL INVALID FUEL LEVEL CLEAR 12-06-21 5:05PM T 1 TANK REGULAR UNL INVALID FUEL LEVEL ALARM 12-06-21 4:28PM T 1 TANK REGULAR UNL DELIVERY NEEDED ALARM 12-06-21 2:05PM OTHER ISD GROSS PRES WARN CLEAR 12-06-21 7:49AM OTHER ISD GROSS PRES WARN ALARM 12-05-21 1:17PM SYSTEM PRINTER ERROR CLEAR 11-29-21 8:12AM SYSTEM PAPER OUT CLEAR 11-29-21 8:12AM SYSTEM PRINTER ERROR ALARM 11-29-21 8:11AM SYSTEM PAPER OUT ALARM 11-29-21 8:11AM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 11-28-21 1:31PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 11-28-21 1:17PM OTHER ISD GROSS PRES WARN CLEAR 11-27-21 1:15PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 11-27-21 1:15PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 11-25-21 1:17PM OTHER ISD GROSS PRES WARN ALARM 11-20-21 1:17PM I20600 JAN 25, 2022 9:01 AM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 TANK ALARM HISTORY TANK 1 REGULAR UNL OVERFILL ALARM OCT 25, 2021 4:50 PM SEP 23, 2021 1:01 AM JUN 1, 2021 7:36 PM HIGH PRODUCT ALARM MAY 10, 2021 8:49 AM APR 28, 2021 1:23 PM INVALID FUEL LEVEL DEC 10, 2021 12:54 PM DEC 6, 2021 4:28 PM NOV 16, 2021 7:46 PM PROBE OUT APR 28, 2021 1:23 PM APR 28, 2021 1:18 PM DELIVERY NEEDED DEC 10, 2021 8:55 AM DEC 6, 2021 2:05 PM NOV 16, 2021 4:19 PM LOW TEMP WARNING APR 28, 2021 1:24 PM TANK 2 SUPER UNL TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JAN 25, 2022 9:01 AM I30200 JAN 25, 2022 9:01 AM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87-91 ANNULAR APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 1:01 PM FUEL ALARM 2 87 STP APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 12:59 PM FUEL ALARM 3 87 FILL APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 1:00 PM FUEL ALARM 4 91 STP APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 12:57 PM FUEL ALARM 5 91 FILL OCT 25, 2021 11:43 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 12:57 PM FUEL ALARM 6 DISP 1-2 APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 1:04 PM FUEL ALARM 7 DISP 3-4 APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 1:06 PM FUEL ALARM 8 DISP 5-6 APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 1:11 PM FUEL ALARM 10 DISP 9-10 APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 1:13 PM FUEL ALARM 11 DISP 11-12 APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 1:14 PM FUEL ALARM 12 DISP 7-8 APR 28, 2021 1:16 PM SENSOR OUT ALARM APR 28, 2021 1:12 PM FUEL ALARM I31600 JAN 25, 2022 9:01 AM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VAPOR PRESSUR 2 FM 1-2 3 FM 3-4 4 FM 5-6 5 FM 7-8 6 FM 9-10 7 FM 11-12 I40200 JAN 25, 2022 9:01 AM I40300 JAN 25, 2022 9:01 AM I34200 JAN 25, 2022 9:01 AM I34700 JAN 25, 2022 9:01 AM IV0100 JAN 25, 2022 9:01 AM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.06 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-01-24 13:18:02 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.84 22-01-23 13:18:02 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.91 22-01-16 13:17:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.64 22-01-15 13:17:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.62 22-01-14 13:18:01 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.67 22-01-13 13:18:04 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.02 22-01-12 13:18:08 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.05 22-01-05 13:18:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.68 22-01-04 13:18:13 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.66 22-01-03 13:18:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.81 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 21-11-28 13:17:27 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.59 21-11-27 13:17:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.59 21-11-13 13:17:34 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.54 21-02-26 13:18:01 A/L RATIO DEGRADATION FP 5 BLEND3 0.77 21-02-25 13:17:43 A/L RATIO DEGRADATION FP 5 BLEND3 0.77 21-01-06 13:17:48 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.06 21-01-05 13:17:41 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.03 21-01-04 13:17:42 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.11 20-12-23 13:18:06 A/L RATIO DEGRADATION FP 8 BLEND3 0.71 20-11-19 13:17:04 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.49 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-01-25 08:53:37 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 22-01-21 13:17:54 READINESS ISD:PP EVR:PP ISD & EVR READY 22-01-20 13:17:54 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-01-19 13:17:51 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-01-18 13:18:12 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-01-17 13:17:47 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-01-17 03:31:28 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 22-01-16 13:17:38 READINESS ISD:PP EVR:NF CHECK EVR SYSTEM 22-01-15 13:17:45 READINESS ISD:PP EVR:NF CHECK EVR SYSTEM 22-01-14 13:18:01 READINESS ISD:PP EVR:NF CHECK EVR SYSTEM alarm after flower st. I10200 JAN 25, 2022 12:24 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 10338915 10340706 2 UNUSED 10296801 10300223 3 UNUSED 10293976 10297194 4 8SMARTSENSOR BD 39519 39545 5 4 PROBE / G.T. 163516 163395 6 INTERSTITIAL BD 201358 201557 7 INTERSTITIAL BD 201563 201649 8 UNUSED 10302035 10309510 9 UNUSED 10288122 10287985 10 RELAY BOARD 14978 14985 11 UNUSED 10295874 10294067 12 UNUSED 10296334 10295208 13 UNUSED 10290465 10294945 14 UNUSED 10283523 10283529 15 UNUSED 10292523 10298194 16 UNUSED 10289195 10287832 COMM 1 ELEC DISP INT. 100618 100590 COMM 2 RS232 SERIAL BD 14912 14919 COMM 3 UNUSED 10299707 10295867 COMM 4 UNUSED 10287705 10290795 COMM 5 UNUSED 10286808 10284912 COMM 6 UNUSED 10284990 10295340 I90200 JAN 25, 2022 12:25 PM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JAN 25, 2022 12:25 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 6 DISP PAN DISP 1-2 FUEL ALARM CLEAR 1-25-22 10:20AM L 6 DISP PAN DISP 1-2 FUEL ALARM ALARM 1-25-22 10:14AM L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L 2 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L 4 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L 5 PIPE 91 FILL SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L 3 PIPE 87 FILL SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L 1 ANNULAR 87-91 ANNULAR SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L11 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L10 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 1-25-22 10:04AM L11 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 1-25-22 10:04AM L10 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 1-25-22 10:04AM L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 1-25-22 10:04AM L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 1-25-22 10:04AM L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 1-25-22 10:04AM L 4 STP SUMP 91 STP SENSOR OUT ALARM ALARM 1-25-22 10:04AM L 3 PIPE 87 FILL SENSOR OUT ALARM ALARM 1-25-22 10:04AM L 5 PIPE 91 FILL SENSOR OUT ALARM ALARM 1-25-22 10:04AM L 2 STP SUMP 87 STP SENSOR OUT ALARM ALARM 1-25-22 10:04AM L 1 ANNULAR 87-91 ANNULAR SENSOR OUT ALARM ALARM 1-25-22 10:04AM L11 DISP PAN DISP 11-12 FUEL ALARM CLEAR 1-25-22 9:56AM L11 DISP PAN DISP 11-12 FUEL ALARM ALARM 1-25-22 9:55AM L10 DISP PAN DISP 9-10 FUEL ALARM CLEAR 1-25-22 9:55AM L10 DISP PAN DISP 9-10 FUEL ALARM ALARM 1-25-22 9:55AM L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 1-25-22 9:54AM L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 1-25-22 9:54AM L 8 DISP PAN DISP 5-6 FUEL ALARM CLEAR 1-25-22 9:53AM L 8 DISP PAN DISP 5-6 FUEL ALARM ALARM 1-25-22 9:53AM L 7 DISP PAN DISP 3-4 FUEL ALARM CLEAR 1-25-22 9:52AM L 7 DISP PAN DISP 3-4 FUEL ALARM ALARM 1-25-22 9:52AM L 6 DISP PAN DISP 1-2 FUEL ALARM CLEAR 1-25-22 9:52AM L 6 DISP PAN DISP 1-2 FUEL ALARM ALARM 1-25-22 9:51AM L 4 STP SUMP 91 STP FUEL ALARM CLEAR 1-25-22 9:50AM L 4 STP SUMP 91 STP FUEL ALARM ALARM 1-25-22 9:50AM L 5 PIPE 91 FILL FUEL ALARM CLEAR 1-25-22 9:50AM L 5 PIPE 91 FILL FUEL ALARM ALARM 1-25-22 9:49AM L 2 STP SUMP 87 STP FUEL ALARM CLEAR 1-25-22 9:49AM L 2 STP SUMP 87 STP FUEL ALARM ALARM 1-25-22 9:49AM L 3 PIPE 87 FILL FUEL ALARM CLEAR 1-25-22 9:48AM L 3 PIPE 87 FILL FUEL ALARM ALARM 1-25-22 9:48AM L 1 ANNULAR 87-91 ANNULAR FUEL ALARM CLEAR 1-25-22 9:47AM L 1 ANNULAR 87-91 ANNULAR FUEL ALARM ALARM 1-25-22 9:47AM L 5 PIPE 91 FILL FUEL ALARM CLEAR 1-25-22 9:31AM OTHER ISD GROSS PRES FAIL CLEAR 11-28-21 1:30PM OTHER ISD GROSS PRES FAIL ALARM 11-28-21 1:17PM OTHER ISD GROSS PRES FAIL CLEAR 11-28-21 1:17PM I11200 JAN 25, 2022 12:25 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD GROSS PRES WARN CLEAR 1-25-22 8:53AM OTHER ISD GROSS PRES WARN ALARM 1-23-22 1:18PM OTHER ISD GROSS PRES WARN CLEAR 1-17-22 3:31AM SYSTEM PRINTER ERROR CLEAR 1-16-22 5:14PM SYSTEM PAPER OUT CLEAR 1-16-22 5:14PM SYSTEM PRINTER ERROR ALARM 1-16-22 5:14PM SYSTEM PAPER OUT ALARM 1-16-22 5:14PM OTHER ISD GROSS PRES WARN ALARM 1-12-22 1:18PM OTHER ISD GROSS PRES WARN CLEAR 1-06-22 11:48AM OTHER ISD GROSS PRES WARN ALARM 1-02-22 1:18PM OTHER ISD GROSS PRES WARN CLEAR 12-27-21 9:21AM OTHER ISD GROSS PRES WARN ALARM 12-24-21 1:18PM SYSTEM PRINTER ERROR CLEAR 12-20-21 1:25PM SYSTEM PAPER OUT CLEAR 12-20-21 1:25PM SYSTEM PRINTER ERROR ALARM 12-20-21 1:25PM SYSTEM PAPER OUT ALARM 12-20-21 1:25PM SYSTEM PRINTER ERROR CLEAR 12-20-21 1:25PM SYSTEM PAPER OUT CLEAR 12-20-21 1:25PM SYSTEM PAPER OUT ALARM 12-20-21 1:24PM SYSTEM PRINTER ERROR ALARM 12-20-21 1:24PM SYSTEM PRINTER ERROR CLEAR 12-20-21 1:24PM SYSTEM PAPER OUT CLEAR 12-20-21 1:24PM SYSTEM PRINTER ERROR ALARM 12-20-21 1:24PM SYSTEM PAPER OUT ALARM 12-20-21 1:24PM SYSTEM PRINTER ERROR CLEAR 12-20-21 1:24PM SYSTEM PAPER OUT CLEAR 12-20-21 1:24PM SYSTEM PRINTER ERROR ALARM 12-20-21 1:24PM SYSTEM PAPER OUT ALARM 12-20-21 1:24PM OTHER ISD GROSS PRES WARN CLEAR 12-17-21 1:49PM OTHER ISD GROSS PRES WARN ALARM 12-12-21 1:18PM T 1 TANK REGULAR UNL DELIVERY NEEDED CLEAR 12-10-21 4:07PM T 1 TANK REGULAR UNL INVALID FUEL LEVEL CLEAR 12-10-21 4:06PM T 1 TANK REGULAR UNL INVALID FUEL LEVEL ALARM 12-10-21 12:54PM T 1 TANK REGULAR UNL DELIVERY NEEDED ALARM 12-10-21 8:55AM T 1 TANK REGULAR UNL DELIVERY NEEDED CLEAR 12-06-21 5:06PM T 1 TANK REGULAR UNL INVALID FUEL LEVEL CLEAR 12-06-21 5:05PM T 1 TANK REGULAR UNL INVALID FUEL LEVEL ALARM 12-06-21 4:28PM T 1 TANK REGULAR UNL DELIVERY NEEDED ALARM 12-06-21 2:05PM OTHER ISD GROSS PRES WARN CLEAR 12-06-21 7:49AM OTHER ISD GROSS PRES WARN ALARM 12-05-21 1:17PM SYSTEM PRINTER ERROR CLEAR 11-29-21 8:12AM SYSTEM PAPER OUT CLEAR 11-29-21 8:12AM SYSTEM PRINTER ERROR ALARM 11-29-21 8:11AM SYSTEM PAPER OUT ALARM 11-29-21 8:11AM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 11-28-21 1:31PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 11-28-21 1:17PM OTHER ISD GROSS PRES WARN CLEAR 11-27-21 1:15PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 11-27-21 1:15PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 11-25-21 1:17PM OTHER ISD GROSS PRES WARN ALARM 11-20-21 1:17PM I20600 JAN 25, 2022 12:26 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 TANK ALARM HISTORY TANK 1 REGULAR UNL OVERFILL ALARM OCT 25, 2021 4:50 PM SEP 23, 2021 1:01 AM JUN 1, 2021 7:36 PM HIGH PRODUCT ALARM MAY 10, 2021 8:49 AM APR 28, 2021 1:23 PM INVALID FUEL LEVEL DEC 10, 2021 12:54 PM DEC 6, 2021 4:28 PM NOV 16, 2021 7:46 PM PROBE OUT APR 28, 2021 1:23 PM APR 28, 2021 1:18 PM DELIVERY NEEDED DEC 10, 2021 8:55 AM DEC 6, 2021 2:05 PM NOV 16, 2021 4:19 PM LOW TEMP WARNING APR 28, 2021 1:24 PM TANK 2 SUPER UNL TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JAN 25, 2022 12:26 PM I30200 JAN 25, 2022 12:26 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87-91 ANNULAR JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:47 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM 2 87 STP JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:49 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM 3 87 FILL JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:48 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM 4 91 STP JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:50 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM 5 91 FILL JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:49 AM FUEL ALARM OCT 25, 2021 11:43 AM FUEL ALARM 6 DISP 1-2 JAN 25, 2022 10:14 AM FUEL ALARM JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:51 AM FUEL ALARM 7 DISP 3-4 JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:52 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM 8 DISP 5-6 JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:53 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM 10 DISP 9-10 JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:55 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM 11 DISP 11-12 JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:55 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM 12 DISP 7-8 JAN 25, 2022 10:04 AM SENSOR OUT ALARM JAN 25, 2022 9:54 AM FUEL ALARM APR 28, 2021 1:16 PM SENSOR OUT ALARM I31600 JAN 25, 2022 12:27 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VAPOR PRESSUR 2 FM 1-2 3 FM 3-4 4 FM 5-6 5 FM 7-8 6 FM 9-10 7 FM 11-12 I40200 JAN 25, 2022 12:27 PM I40300 JAN 25, 2022 12:27 PM I34200 JAN 25, 2022 12:27 PM I34700 JAN 25, 2022 12:27 PM IV0100 JAN 25, 2022 12:27 PM FLOWER ST MINI MART 928 FLOWER ST BAKERSFIELD CA 93305 661-328-0673 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.06 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-01-24 13:18:02 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.84 22-01-23 13:18:02 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.91 22-01-16 13:17:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.64 22-01-15 13:17:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.62 22-01-14 13:18:01 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.67 22-01-13 13:18:04 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.02 22-01-12 13:18:08 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.05 22-01-05 13:18:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.68 22-01-04 13:18:13 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.66 22-01-03 13:18:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.81 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 21-11-28 13:17:27 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.59 21-11-27 13:17:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.59 21-11-13 13:17:34 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.54 21-02-26 13:18:01 A/L RATIO DEGRADATION FP 5 BLEND3 0.77 21-02-25 13:17:43 A/L RATIO DEGRADATION FP 5 BLEND3 0.77 21-01-06 13:17:48 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.06 21-01-05 13:17:41 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.03 21-01-04 13:17:42 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.11 20-12-23 13:18:06 A/L RATIO DEGRADATION FP 8 BLEND3 0.71 20-11-19 13:17:04 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.49 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-01-25 10:08:35 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-01-25 10:08:35 ISD STARTUP 22-01-25 10:06:29 ISD SHUTDOWN 22-01-25 08:53:37 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 22-01-21 13:17:54 READINESS ISD:PP EVR:PP ISD & EVR READY 22-01-20 13:17:54 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-01-19 13:17:51 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-01-18 13:18:12 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-01-17 13:17:47 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-01-17 03:31:28 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED