HomeMy WebLinkAboutARCO White Ln. Bakersfield 91 UL Pass 11-1-2021 Leak Detector Test RecordAdvanced Compliance 4007 Brae Burn Drive Bakersfield, Ca. 93306 661-706-4321 VAPORLESS MANUFACTURING, INC. LDT-890 Leak Detector Test Record Contractor: Advanced Compliance Customer: ARCO AMPM Date: 11/1/2021 Location: 6450 White Ln. Bakersfield, Ca. Product: 91 UL Technician: Bruce W. Hinsley Submersible Pump Identification Manufacturer: Redjacket Model No.: Serial No.: Notes: Leak Detector Identification Manufacturer: Veeder-Root Description: PLLD Diaphragm-type: Piston-type: Tamper-proof seal installed: Other Style Leak Detector: Notes: Leak Detector in Submersible Pump Test at Dispenser Operating Pump Pressure (psi): 27 (para. 15) Gallons per hour rate: 3.0 (para. 22) Line pressure with pump shut off (psi): 18 (para. 23) Bleed-back Test with pump off (ml): 75 (para. 26) Step-through time to full flow (secs): N/A (para. 30) Leak detector stays in leak search position (Yes/No): N/A (para. 42) Leak Detector Test Pass / Fail Notes: Pass *Complete thermal expansion test before failing leak detector