LDT-890 Leak Detector Test Record
Contractor: Advanced Compliance Customer: ARCO AMPM
Date: 11/1/2021 Location: 6450 White Ln. Bakersfield, Ca.
Product: 91 UL Technician: Bruce W. Hinsley
Submersible Pump Identification
Manufacturer: Redjacket Model No.:
Serial No.: Notes:
Leak Detector Identification
Manufacturer: Veeder-Root Description: PLLD
Diaphragm-type: Piston-type:
Tamper-proof seal installed: Other Style Leak Detector:
Notes:
Leak Detector in Submersible Pump Test at Dispenser
Operating Pump Pressure (psi): 27 (para. 15)
Gallons per hour rate: 3.0 (para. 22)
Line pressure with pump shut off (psi): 18 (para. 23)
Bleed-back Test with pump off (ml): 75 (para. 26)
Step-through time to full flow (secs): N/A (para. 30)
Leak detector stays in leak search position (Yes/No): N/A (para. 42)
Leak Detector Test
Pass / Fail Notes:
Pass
*Complete thermal expansion test before failing leak detector