Loading...
HomeMy WebLinkAboutCold Start 2-21-22Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 02/21/2022 Jaco#7708 12851 Rosedale Hwy Bakersfield, Ca 93312 Confidence UST Services, Inc.(800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Jason Woods 1073967 8492093 03/23/2023 Veeder Root C26937 07/26/2023 02/21/2022 5 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder Root TLS-350 327.04 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 794380–208 87 STP L2 794380-420 87 Annular L3 794380-208 91 STP L4 794380-420 91 Annular L5 794380–208 Diesel STP L6 794380-420 Diesel Annular L7 794380-208 UDC 9-10 L8 794380-208 UDC 11-12 L9 794380-208 UDC 13-14 L10 794380-208 UDC 15-16 Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Performed Electronic MC after software upgrade. Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. 708 LEGEND L1 87 STP L2 87 ANNULAR L3 91 STP L4 91 ANNULAR L5 DSL STP L6 DSL ANNULAR L7 UDC 9 - 10 L8 UDC 11- 12 L9 UDC 13 - 14 L10 UDC 15 - 16 707 LEGEND L1 87-1 STP L2 87-1 ANNULAR L3 87-1 FILL L4 87-2 STP L5 87-2 ANNULAR L6 87-2 FILL L7 91 STP L8 91 ANNULAR L9 91 FILL L10 DSL STP L11 DSL ANNULAR L12 DSL FILL L13 UDC 3 - 4 L14 UDC 1 - 2 L15 UDC 5 - 6 L16 UDC 7 - 8 EXISTING BUILDING A L 4 S T P L 4 L 3 V F 1 2 , 0 0 0 G A L L O N P R E M I U M A L 6 S T P L 4 L 5 V F A L 2 S T P L 4 L 1 F 1 2 , 0 0 0 G A L L O N 8 7 U N L E A D E D 1 2 , 0 0 0 G A L L O N D I E S E L 1 1 1 2 L 8 1 5 1 6 L 1 0 9 1 0 L 7 1 3 1 4 L 9 H VF VF F VF 12,000 GALLONDIESEL 12,000 GALLONPREMIUM 12,000 GALLON87-2 UNLEADED 12,000 GALLON87-1 UNLEADED AL11 AL8 AL5 AL2 STPL10L12 STPL7L9 STPL4L6 STPL1L3 78L16 34L13 56L15 12L14 H NO PARKING G W D U M P S T E R CATCHBASIN DRAIN WITH METAL COVER 2 PROPANE TANK CAGES #7-707 #7-708 4 0 ' S T O R A G E C O N T A I N E R ROSEDALE HWY. AL L E N R D . P R O P E R T Y L I N E PROPERTY LINE ALLEY N 7-708 7-707 87 GAS 3/2 INCH DBL WALLED PIPE 91 GAS 3/2 INCH DBL WALLED PIPE DIESEL 3/2 INCH DBL WALLED PIPE VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE VAPOR VENT 2 INCH SINGLE WALLED PIPE PRODUCT SPILL CONTAINER VAPOR SPILL CONTAINER ANNULAR EMERGENCY SHUT-OFF OVERFILL ALARM FIRE EXTINGUISHER GAS METER SHUT-OFF WATER METER SHUT-SHUT OFF HEALY CAS EVACUATION MEETING POINT AUTOMATIC TANK GAUGE ELECTRICAL PANEL AIR AND WATER HAZWASTE DRUM W G A H P V SCALE:SITE MAP C1 VICINITY MAP PROJECT DATA 1"=15'-0" INCHES012 SHEET SIZE 22 X 34 12851 ROSEDALE HWY. BAKERSFIELD, CA 93312 PROJECT OWNER: JAMIESON HILL PO. BOX 82515 BAKERSFIELD, CA 93380 CONTACT: SITE PLOT PLAN FOR: FA0003958 CERS ID 10175661 FASTRIPS #7707 / #7708 12851 ROSEDALE HWY. BAKERSFIELD, CA 93312 01/25/17 REV. A L L E N R D . ROSEDALE HWY. Jaco 708 East side Setup Alarm History Responses Received: 200 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 FEB 21, 2022 8:32 TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNL 5946 47.41 0.8 63.3 6054 2 PNL 10370 77.02 0.0 63.1 1630 3 DIESEL 5372 43.82 1.0 64.3 6628 I90500 FEB 21, 2022 8:32 SOFTWARE REVISION LEVEL VERSION 327.04 SOFTWARE# 346327-100-E CREATED - 07.02.06.10.28 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD PMC I50500 FEB 21, 2022 8:32 SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS I50201 FEB 21, 2022 8:32 SHIFT TIME 1 : 12:00 AM I50202 FEB 21, 2022 8:32 SHIFT TIME 2 : DISABLED I50203 FEB 21, 2022 8:32 SHIFT TIME 3 : DISABLED I50204 FEB 21, 2022 8:32 SHIFT TIME 4 : DISABLED I54600 FEB 21, 2022 8:32 TANK PER TST NEEDED WRN: DISABLED I54900 FEB 21, 2022 8:32 TANK ANN TST NEEDED WRN: DISABLED I55300 FEB 21, 2022 8:32 LINE RE-ENABLE METHOD PASS LINE TEST I55600 FEB 21, 2022 8:32 LINE PER TST NEEDED WRN: DISABLED I55900 FEB 21, 2022 8:32 LINE ANN TST NEEDED WRN: DISABLED I50D00 FEB 21, 2022 8:32 PRINT TC VOLUMES ENABLED I50E00 FEB 21, 2022 8:32 TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 FEB 21, 2022 8:32 STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 FEB 21, 2022 8:32 H-PROTOCOL DATA FORMAT HEIGHT I51A01 FEB 21, 2022 8:32 DAYLIGHT SAVING TIME ENABLED OFF I51B00 FEB 21, 2022 8:32 DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE OCT WEEK 6 SUN 2:00 AM I51600 FEB 21, 2022 8:32 RE-DIRECT LOCAL PRINTOUT DISABLED I50400 FEB 21, 2022 8:32 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 FEB 21, 2022 8:32 TANK CHART SECURITY DISABLED I5BD00 FEB 21, 2022 8:32 CUSTOM ALARM LABELS DISABLED I56000 FEB 21, 2022 8:32 MASS/DENSITY DISABLED I88101 FEB 21, 2022 8:32 PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 FEB 21, 2022 8:32 PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 FEB 21, 2022 8:32 PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 FEB 21, 2022 8:32 I88105 FEB 21, 2022 8:32 I88106 FEB 21, 2022 8:32 I52000 FEB 21, 2022 8:32 RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE MAR 9, 2014 DISABLED 2 ON DATE MAR 9, 2014 DISABLED 3 ON DATE MAR 9, 2014 DISABLED 4 ON DATE MAR 9, 2014 DISABLED 5 ON DATE MAR 9, 2014 DISABLED 6 ON DATE MAR 9, 2014 DISABLED 7 ON DATE MAR 9, 2014 DISABLED 8 ON DATE MAR 9, 2014 DISABLED I60100 FEB 21, 2022 8:32 TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNL ON 2 PNL ON 3 DIESEL ON 4 OFF I60200 FEB 21, 2022 8:32 TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNL 2 PNL 3 DIESEL 4 I60300 FEB 21, 2022 8:32 TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNL 1 2 PNL 2 3 DIESEL 3 4 4 I60900 FEB 21, 2022 8:32 TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNL 0.000700 2 PNL 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 FEB 21, 2022 8:32 TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNL 95.50 2 PNL 95.50 3 DIESEL 95.50 4 0.00 I60A00 FEB 21, 2022 8:32 TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL 1 PT 12000 2 PNL 1 PT 12000 3 DIESEL 1 PT 12000 4 1 PT 0 I60400 FEB 21, 2022 8:32 TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 12000 2 PNL 12000 3 DIESEL 12000 4 0 I60500 FEB 21, 2022 8:32 TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12000 0 0 0 2 PNL 12000 0 0 0 3 DIESEL 12000 0 0 0 4 0 0 0 0 I60600 FEB 21, 2022 8:32 TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PNL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 FEB 21, 2022 8:32 TANK PRODUCT LABEL METER DATA 1 UNL NO 2 PNL NO 3 DIESEL NO 4 NO I62F00 FEB 21, 2022 8:32 MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNL 4.0 INCHES 2 PNL 4.0 INCHES 3 DIESEL 4.0 INCHES I62700 FEB 21, 2022 8:32 TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNL 2.0 2 PNL 2.0 3 DIESEL 2.0 9999FF1B I62400 FEB 21, 2022 8:32 TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNL 3.0 2 PNL 3.0 3 DIESEL 3.0 I62800 FEB 21, 2022 8:32 TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 12000 2 PNL 12000 3 DIESEL 12000 4 0 I62300 FEB 21, 2022 8:32 TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 10800 2 PNL 10800 3 DIESEL 10800 4 0 I62200 FEB 21, 2022 8:32 TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 11400 2 PNL 11400 3 DIESEL 11400 4 0 I62900 FEB 21, 2022 8:32 TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1800 2 PNL 1800 3 DIESEL 1800 4 0 I62100 FEB 21, 2022 8:32 TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 500 2 PNL 500 3 DIESEL 500 4 0 I62600 FEB 21, 2022 8:32 TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 PNL 99 3 DIESEL 99 4 99 I62500 FEB 21, 2022 8:32 TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 PNL 99 3 DIESEL 99 4 99 I60800 FEB 21, 2022 8:32 TANK TILT TANK PRODUCT LABEL INCHES 1 UNL -3.50 2 PNL -1.50 3 DIESEL -6.00 4 0.00 I60B00 FEB 21, 2022 8:32 STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 FEB 21, 2022 8:32 TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNL 0.00 2 PNL 0.00 3 DIESEL 0.00 4 0.00 I61200 FEB 21, 2022 8:32 TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNL NONE NONE 2 PNL NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 FEB 21, 2022 8:32 PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 120 2 PNL 120 3 DIESEL 120 4 0 I62A00 FEB 21, 2022 8:32 ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 0 2 PNL 120 3 DIESEL 120 4 0 I62C00 FEB 21, 2022 8:32 TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNL STANDARD 2 PNL STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 FEB 21, 2022 8:32 TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 2 PNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 FEB 21, 2022 8:32 TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNL OFF OFF 2 PNL OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 FEB 21, 2022 8:32 IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNL OFF 2 PNL OFF 3 DIESEL OFF 4 OFF I63200 FEB 21, 2022 8:32 TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNL OFF 2 PNL OFF 3 DIESEL OFF 4 OFF I61000 FEB 21, 2022 8:32 TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNL 1 2 PNL 1 3 DIESEL 1 4 1 I63A00 FEB 21, 2022 8:32 LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNL 10.00% 2 PNL 10.00% 3 DIESEL 10.00% 4 10.00% I61100 FEB 21, 2022 8:32 LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK FEB 6, 2007 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 FEB 21, 2022 8:32 CSLD PROBABLITY OF DETECTION I61400 FEB 21, 2022 8:32 CSLD CLIMATE FACTOR I61600 FEB 21, 2022 8:32 TANK PRODUCT LABEL CAL UPDATE 1 UNL IMMEDIATE 2 PNL IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 FEB 21, 2022 8:32 IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNL DISABLED 2 PNL DISABLED 3 DIESEL DISABLED 4 DISABLED I61B00 FEB 21, 2022 8:32 IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 FEB 21, 2022 8:32 CSLD REPORT ONLY I62B00 FEB 21, 2022 8:32 TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNL ??? 0, 0 2 PNL ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 FEB 21, 2022 8:33 LEAK TEST REPORT FORMAT: NORMAL I63400 FEB 21, 2022 8:33 RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 0 2 PNL 0 3 DIESEL 0 4 0 I63500 FEB 21, 2022 8:33 RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 2 PNL 1 3 DIESEL 1 4 1 I63900 FEB 21, 2022 8:33 ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNL END FACTOR: NONE 2 PNL END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 FEB 21, 2022 8:33 I77700 FEB 21, 2022 8:33 I77800 FEB 21, 2022 8:33 I78C00 FEB 21, 2022 8:33 I78300 FEB 21, 2022 8:33 I78F00 FEB 21, 2022 8:33 I78700 FEB 21, 2022 8:33 I70200 FEB 21, 2022 8:33 LIQUID LABEL DEVICE LABEL 1 UNL STP 2 UNL ANN 3 PNL STP 4 PNL ANN 5 DIESEL STP 6 DIESEL ANN 7 DISP 9-10 8 DISP 11-12 9 DISP 13-14 10 DISP 15-16 11 12 13 14 15 16 I70300 FEB 21, 2022 8:33 LIQUID TYPE SENSOR LOCATION TYPE 1 UNL STP TRI-STATE (SINGLE FLOAT) 2 UNL ANN TRI-STATE (SINGLE FLOAT) 3 PNL STP TRI-STATE (SINGLE FLOAT) 4 PNL ANN TRI-STATE (SINGLE FLOAT) 5 DIESEL STP TRI-STATE (SINGLE FLOAT) 6 DIESEL ANN TRI-STATE (SINGLE FLOAT) 7 DISP 9-10 TRI-STATE (SINGLE FLOAT) 8 DISP 11-12 TRI-STATE (SINGLE FLOAT) 9 DISP 13-14 TRI-STATE (SINGLE FLOAT) 10 DISP 15-16 TRI-STATE (SINGLE FLOAT) 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 FEB 21, 2022 8:33 LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL STP STP SUMP 2 UNL ANN ANNULAR SPACE 3 PNL STP STP SUMP 4 PNL ANN ANNULAR SPACE 5 DIESEL STP STP SUMP 6 DIESEL ANN ANNULAR SPACE 7 DISP 9-10 DISPENSER PAN 8 DISP 11-12 DISPENSER PAN 9 DISP 13-14 DISPENSER PAN 10 DISP 15-16 DISPENSER PAN 11 OTHER SENSORS 12 OTHER SENSORS 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 FEB 21, 2022 8:33 I74300 FEB 21, 2022 8:33 I74400 FEB 21, 2022 8:33 I74700 FEB 21, 2022 8:33 I74800 FEB 21, 2022 8:33 I74900 FEB 21, 2022 8:33 I7BC00 FEB 21, 2022 8:33 I80200 FEB 21, 2022 8:33 I80300 FEB 21, 2022 8:33 I80400 FEB 21, 2022 8:33 I80700 FEB 21, 2022 8:33 RELAY LABEL DEVICE LABEL 1 UNL 2 PNL 3 DIESEL 4 OVERFILL ALARM I80900 FEB 21, 2022 8:33 RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL NORMALLY CLOSED 2 PNL NORMALLY CLOSED 3 DIESEL NORMALLY CLOSED 4 OVERFILL ALARM NORMALLY OPEN I80B00 FEB 21, 2022 8:33 RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNL 1 2 PNL 2 3 DIESEL 3 4 OVERFILL ALARM NONE I80A00 FEB 21, 2022 8:33 RELAY TYPE RELAY DESIGNATION TYPE 1 UNL STANDARD 2 PNL STANDARD 3 DIESEL STANDARD 4 OVERFILL ALARM STANDARD I80C00 FEB 21, 2022 8:33 I80800 FEB 21, 2022 8:33 RELAY SETUP REPORT R 1:UNL TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L 1:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 1:SHORT ALARM L 7:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PNL TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 3:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L 3:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 3:SHORT ALARM L 7:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DIESEL TYPE: STANDARD NORMALLY CLOSED TANK #: 3 LIQUID SENSOR ALMS L 5:FUEL ALARM L10:FUEL ALARM L 5:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 5:SHORT ALARM L10:SHORT ALARM R 4:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 FEB 21, 2022 8:33 EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 FEB 21, 2022 8:33 I72300 FEB 21, 2022 8:33 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 P.S 11-12 VAPOR PRESSURE 02 F.M 9-10 AIR FLOW METER 03 F.M 11-12 AIR FLOW METER 04 F.M 13-14 AIR FLOW METER 05 F.M 15-16 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 FEB 21, 2022 8:33 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 FEB 21, 2022 8:33 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 FEB 21, 2022 8:33 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 VAPOR PROCESSOR TYPE NO VAPOR PROCESSOR IV4700 FEB 21, 2022 8:33 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 ASSESSMENT TIME START TIME: 10:00 TIME DELAY MINUTES: 1 IV5200 FEB 21, 2022 8:33 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 ACCEPT HIGH ORVR: NO IV4A00 FEB 21, 2022 8:33 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 ISD HOSE TABLE HOSE FP FP AFM HOSE ID ID LABEL ID LABEL 01 25 09 01 BLEND3 02 26 10 01 BLEND3 03 27 11 02 BLEND3 04 28 12 02 BLEND3 05 01 13 03 BLEND3 06 02 14 03 BLEND3 07 03 15 04 BLEND3 08 04 16 04 BLEND3 IV4B00 FEB 21, 2022 8:33 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 03 02/05 03/05 09/05 xx/xx 02 03 02/06 03/06 09/06 xx/xx 03 04 02/07 03/07 09/07 xx/xx 04 04 02/08 03/08 09/08 xx/xx 25 01 02/01 03/01 09/01 xx/xx 26 01 02/02 03/02 09/02 xx/xx 27 02 02/03 03/03 09/03 xx/xx 28 02 02/04 03/04 09/04 xx/xx IV4900 FEB 21, 2022 8:33 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 FEB 21, 2022 8:33 ISD VERSION: 01.01 Alarm History Before Responses Received: I10200 FEB 21, 2022 8:34 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39349 39309 2 4 PROBE / G.T. 163759 163674 3 INTERSTITIAL BD 202674 202283 4 INTERSTITIAL BD 201965 201792 5 UNUSED 9803608 9736737 6 UNUSED 9795157 9728129 7 UNUSED 9787584 9742521 8 UNUSED 9798186 9722929 9 RELAY BOARD 14963 14947 10 UNUSED 9796223 9725408 11 UNUSED 9791306 9732043 12 UNUSED 9784062 9743184 13 UNUSED 9797188 9720073 14 UNUSED 9781471 9752509 15 UNUSED 9791723 9718279 16 UNUSED 9789308 9739866 COMM 1 ELEC DISP INT. 101323 101285 COMM 2 RS232 SERIAL BD 15029 15014 COMM 3 RS232 SERIAL BD 15051 15059 COMM 4 UNUSED 9799888 9723144 COMM 5 UNUSED 9786476 9742153 COMM 6 UNUSED 9784698 9738768 I90200 FEB 21, 2022 8:34 SOFTWARE REVISION LEVEL VERSION 327.04 SOFTWARE# 346327-100-E CREATED - 07.02.06.10.28 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD PMC I11100 FEB 21, 2022 8:34 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 4 OTHER FP12: BLEND3 GROSS COLLECT FAIL CLEAR FEB 4 2022 12:19 h 3 OTHER FP11: BLEND3 GROSS COLLECT FAIL CLEAR FEB 4 2022 12:19 L 6 ANNULAR DIESEL ANN FUEL ALARM CLEAR FEB 4 2022 11:12 L 6 ANNULAR DIESEL ANN FUEL ALARM ALARM FEB 4 2022 11:12 L 6 ANNULAR DIESEL ANN FUEL ALARM CLEAR FEB 4 2022 11:07 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR FEB 4 2022 10:56 L 2 ANNULAR UNL ANN FUEL ALARM ALARM FEB 4 2022 10:56 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR FEB 4 2022 10:54 h 4 OTHER FP12: BLEND3 GROSS COLLECT FAIL ALARM FEB 4 2022 10:02 h 3 OTHER FP11: BLEND3 GROSS COLLECT FAIL ALARM FEB 4 2022 10:02 L 6 ANNULAR DIESEL ANN FUEL ALARM ALARM FEB 3 2022 15:40 f 2 OTHER F.M 11-12 CHK VAPOR FLOW MTR CLEAR FEB 3 2022 15:00 f 2 OTHER F.M 11-12 CHK VAPOR FLOW MTR ALARM FEB 3 2022 10:02 L 2 ANNULAR UNL ANN FUEL ALARM ALARM FEB 2 2022 9:18 T 3 TANK DIESEL OVERFILL ALARM CLEAR JAN 17 2022 1:33 T 3 TANK DIESEL OVERFILL ALARM ALARM JAN 17 2022 1:30 T 1 TANK UNL OVERFILL ALARM CLEAR JAN 16 2022 15:07 T 1 TANK UNL OVERFILL ALARM ALARM JAN 16 2022 15:01 T 2 TANK PNL OVERFILL ALARM CLEAR JAN 15 2022 5:01 T 2 TANK PNL OVERFILL ALARM ALARM JAN 15 2022 4:57 L 6 ANNULAR DIESEL ANN FUEL ALARM CLEAR JAN 5 2022 8:43 L 6 ANNULAR DIESEL ANN FUEL ALARM ALARM JAN 5 2022 8:43 L 6 ANNULAR DIESEL ANN FUEL ALARM CLEAR JAN 5 2022 8:41 L 6 ANNULAR DIESEL ANN FUEL ALARM ALARM JAN 1 2022 2:28 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 30 2021 18:19 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 30 2021 0:32 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 12 2021 12:20 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 12 2021 8:17 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 12 2021 2:02 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 11 2021 21:28 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 11 2021 20:21 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 11 2021 18:11 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 11 2021 18:09 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 10 2021 14:40 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 10 2021 14:32 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 10 2021 14:32 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 10 2021 14:31 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 10 2021 14:31 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 10 2021 14:30 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 10 2021 14:29 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 10 2021 11:46 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 10 2021 9:13 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 10 2021 9:11 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 10 2021 9:11 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR DEC 10 2021 8:58 L 2 ANNULAR UNL ANN FUEL ALARM ALARM DEC 9 2021 10:26 T 1 TANK UNL OVERFILL ALARM CLEAR DEC 4 2021 7:16 T 1 TANK UNL OVERFILL ALARM ALARM DEC 4 2021 7:12 T 3 TANK DIESEL OVERFILL ALARM CLEAR NOV 21 2021 2:23 T 3 TANK DIESEL OVERFILL ALARM ALARM NOV 21 2021 2:07 I11200 FEB 21, 2022 8:34 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 3 TANK DIESEL DELIVERY NEEDED CLEAR FEB 18 2022 15:22 T 3 TANK DIESEL DELIVERY NEEDED ALARM FEB 18 2022 13:54 T 1 TANK UNL DELIVERY NEEDED CLEAR FEB 12 2022 15:18 T 1 TANK UNL DELIVERY NEEDED ALARM FEB 12 2022 13:06 OTHER ISD VAPOR LEAK WARN CLEAR FEB 6 2022 10:02 OTHER ISD VAPOR LEAK WARN ALARM FEB 5 2022 10:02 OTHER ISD SENSOR OUT WARN CLEAR FEB 3 2022 15:00 h 4 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR FEB 3 2022 14:58 h 4 OTHER FP12: BLEND3 GROSS COLLECT WARN CLEAR FEB 3 2022 14:58 h 3 OTHER FP11: BLEND3 DEGRD COLLECT WARN CLEAR FEB 3 2022 14:58 h 3 OTHER FP11: BLEND3 GROSS COLLECT WARN CLEAR FEB 3 2022 14:58 OTHER ISD SENSOR OUT WARN ALARM FEB 3 2022 10:02 h 4 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM FEB 3 2022 10:02 h 4 OTHER FP12: BLEND3 GROSS COLLECT WARN ALARM FEB 3 2022 10:02 h 3 OTHER FP11: BLEND3 DEGRD COLLECT WARN ALARM FEB 3 2022 10:02 h 3 OTHER FP11: BLEND3 GROSS COLLECT WARN ALARM FEB 3 2022 10:02 h 5 OTHER FP13: BLEND3 DEGRD COLLECT WARN CLEAR JAN 17 2022 10:48 h 5 OTHER FP13: BLEND3 DEGRD COLLECT WARN ALARM JAN 14 2022 10:01 T 1 TANK UNL DELIVERY NEEDED CLEAR JAN 10 2022 19:06 T 1 TANK UNL DELIVERY NEEDED ALARM JAN 10 2022 17:59 T 1 TANK UNL DELIVERY NEEDED CLEAR JAN 2 2022 23:30 SYSTEM PRINTER ERROR CLEAR JAN 2 2022 20:28 SYSTEM PAPER OUT CLEAR JAN 2 2022 20:28 SYSTEM PRINTER ERROR ALARM JAN 2 2022 20:28 SYSTEM PAPER OUT ALARM JAN 2 2022 20:28 SYSTEM PRINTER ERROR CLEAR JAN 2 2022 20:27 SYSTEM PRINTER ERROR ALARM JAN 2 2022 20:27 SYSTEM PRINTER ERROR CLEAR JAN 2 2022 20:27 SYSTEM PAPER OUT CLEAR JAN 2 2022 20:27 SYSTEM PRINTER ERROR ALARM JAN 2 2022 20:25 SYSTEM PAPER OUT ALARM JAN 2 2022 20:25 SYSTEM PRINTER ERROR CLEAR JAN 2 2022 20:25 SYSTEM PAPER OUT CLEAR JAN 2 2022 20:25 SYSTEM PRINTER ERROR ALARM JAN 2 2022 20:24 SYSTEM PAPER OUT ALARM JAN 2 2022 20:24 T 1 TANK UNL DELIVERY NEEDED ALARM JAN 2 2022 20:22 OTHER ISD VAPOR LEAK WARN CLEAR DEC 23 2021 10:01 OTHER ISD VAPOR LEAK WARN ALARM DEC 21 2021 10:02 OTHER ISD GROSS PRES WARN CLEAR DEC 14 2021 10:16 OTHER ISD GROSS PRES WARN ALARM DEC 14 2021 10:02 T 1 TANK UNL DELIVERY NEEDED CLEAR NOV 24 2021 13:05 T 1 TANK UNL DELIVERY NEEDED ALARM NOV 24 2021 11:21 T 1 TANK UNL DELIVERY NEEDED CLEAR NOV 22 2021 23:59 T 1 TANK UNL DELIVERY NEEDED ALARM NOV 22 2021 19:20 T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR NOV 21 2021 6:24 T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM NOV 21 2021 2:21 T 1 TANK UNL DELIVERY NEEDED CLEAR NOV 17 2021 2:02 T 1 TANK UNL DELIVERY NEEDED ALARM NOV 16 2021 20:32 T 1 TANK UNL DELIVERY NEEDED CLEAR NOV 16 2021 0:26 T 1 TANK UNL DELIVERY NEEDED ALARM NOV 15 2021 17:20 I20600 FEB 21, 2022 8:34 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 TANK ALARM HISTORY TANK 1 UNL OVERFILL ALARM JAN 16, 2022 15:01 DEC 4, 2021 7:12 NOV 13, 2021 6:42 LOW PRODUCT ALARM MAY 28, 2021 15:16 MAR 25, 2019 19:05 DEC 21, 2018 11:28 HIGH PRODUCT ALARM DEC 11, 2018 3:17 OCT 23, 2018 0:38 SEP 14, 2018 2:59 INVALID FUEL LEVEL AUG 18, 2018 14:00 SEP 7, 2017 12:09 OCT 3, 2015 16:37 PROBE OUT SEP 13, 2018 12:36 SEP 13, 2018 12:25 SEP 6, 2018 11:17 HIGH WATER WARNING SEP 13, 2016 12:23 SEP 21, 2015 9:21 DELIVERY NEEDED FEB 12, 2022 13:06 JAN 10, 2022 17:59 JAN 2, 2022 20:22 LOW TEMP WARNING SEP 13, 2018 12:37 SEP 6, 2018 11:18 SEP 13, 2017 12:58 TANK 2 PNL OVERFILL ALARM JAN 15, 2022 4:57 FEB 24, 2021 6:13 FEB 24, 2021 6:06 HIGH PRODUCT ALARM SEP 6, 2018 11:19 SEP 13, 2017 12:34 SEP 7, 2017 12:16 INVALID FUEL LEVEL SEP 7, 2017 12:07 SEP 18, 2013 15:02 SEP 22, 2011 10:50 PROBE OUT SEP 13, 2018 12:38 SEP 13, 2018 12:23 SEP 6, 2018 11:19 DELIVERY NEEDED AUG 24, 2018 19:14 AUG 19, 2018 12:25 AUG 18, 2018 10:55 LOW TEMP WARNING SEP 6, 2018 11:20 SEP 29, 2016 13:13 SEP 13, 2016 13:13 TANK 3 DIESEL OVERFILL ALARM JAN 17, 2022 1:30 NOV 21, 2021 2:07 JUL 7, 2021 2:33 LOW PRODUCT ALARM SEP 13, 2018 12:21 MAY 6, 2016 11:49 SEP 21, 2015 9:54 HIGH PRODUCT ALARM NOV 21, 2021 2:21 SEP 6, 2018 11:20 SEP 13, 2017 12:56 INVALID FUEL LEVEL SEP 21, 2015 9:54 SEP 11, 2015 19:42 APR 14, 2012 22:05 PROBE OUT SEP 13, 2018 12:42 SEP 13, 2018 12:21 SEP 6, 2018 11:21 HIGH WATER WARNING SEP 21, 2015 9:22 DELIVERY NEEDED FEB 18, 2022 13:54 AUG 22, 2021 21:17 AUG 9, 2021 14:18 LOW TEMP WARNING SEP 13, 2018 12:43 SEP 6, 2018 11:21 SEP 7, 2017 12:26 I38200 FEB 21, 2022 8:34 I30200 FEB 21, 2022 8:34 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP SEP 22, 2021 9:41 SENSOR OUT ALARM SEP 22, 2021 9:15 FUEL ALARM SEP 14, 2021 13:38 SENSOR OUT ALARM 2 UNL ANN FEB 4, 2022 10:56 FUEL ALARM FEB 2, 2022 9:18 FUEL ALARM DEC 30, 2021 0:32 FUEL ALARM 3 PNL STP SEP 22, 2021 9:41 SENSOR OUT ALARM SEP 22, 2021 9:16 FUEL ALARM SEP 14, 2021 13:37 SENSOR OUT ALARM 4 PNL ANN SEP 22, 2021 15:24 SENSOR OUT ALARM SEP 22, 2021 13:45 SENSOR OUT ALARM SEP 22, 2021 9:41 SENSOR OUT ALARM 5 DIESEL STP SEP 22, 2021 9:41 SENSOR OUT ALARM SEP 22, 2021 9:17 FUEL ALARM SEP 14, 2021 13:38 SENSOR OUT ALARM 6 DIESEL ANN FEB 4, 2022 11:12 FUEL ALARM FEB 3, 2022 15:40 FUEL ALARM JAN 5, 2022 8:43 FUEL ALARM 7 DISP 9-10 SEP 22, 2021 9:41 SENSOR OUT ALARM SEP 22, 2021 9:23 FUEL ALARM SEP 14, 2021 13:38 SENSOR OUT ALARM 8 DISP 11-12 SEP 22, 2021 9:41 SENSOR OUT ALARM SEP 22, 2021 9:23 FUEL ALARM SEP 14, 2021 13:38 SENSOR OUT ALARM 9 DISP 13-14 SEP 22, 2021 9:41 SENSOR OUT ALARM SEP 22, 2021 9:24 FUEL ALARM SEP 14, 2021 13:37 SENSOR OUT ALARM 10 DISP 15-16 SEP 22, 2021 9:41 SENSOR OUT ALARM SEP 22, 2021 9:24 FUEL ALARM SEP 14, 2021 13:38 SENSOR OUT ALARM I31600 FEB 21, 2022 8:34 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 P.S 11-12 APR 22, 2014 11:18 COMMUNICATION ALARM APR 22, 2014 9:34 COMMUNICATION ALARM 2 F.M 9-10 JUN 7, 2010 7:57 COMMUNICATION ALARM JUN 7, 2010 7:18 COMMUNICATION ALARM JUN 7, 2010 6:11 COMMUNICATION ALARM 3 F.M 11-12 4 F.M 13-14 5 F.M 15-16 I40200 FEB 21, 2022 8:34 I40300 FEB 21, 2022 8:34 I34200 FEB 21, 2022 8:34 I34700 FEB 21, 2022 8:34 IV0100 FEB 21, 2022 8:34 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.01 VAPOR PROCESSOR TYPE: NO VAPOR PROCESSOR OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% STAGE I TRANSFERS: 0 of 0 NOTEST EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-02-05 10:02:52 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.60 22-02-03 10:02:05 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 2:F.M 11-12 22-02-03 10:02:05 A/L RATIO DEGRADATION FP12 BLEND3 0.00 22-02-03 10:02:05 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD 22-02-03 10:02:05 A/L RATIO DEGRADATION FP11 BLEND3 0.00 22-02-03 10:02:04 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 22-01-14 10:01:54 A/L RATIO DEGRADATION FP13 BLEND3 0.00 21-12-22 10:02:08 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.44 21-12-21 10:02:42 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.89 21-12-14 10:02:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.52 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-02-04 10:02:34 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD 22-02-04 10:02:33 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 20-07-04 10:02:49 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 19-11-23 10:02:05 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 19-01-15 10:01:38 A/L RATIO GROSS BLOCKAGE FP16 BLEND3 BLKD 19-01-15 10:01:38 A/L RATIO GROSS BLOCKAGE FP15 BLEND3 BLKD 19-01-13 10:01:37 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD 19-01-13 10:01:37 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 18-08-17 10:02:21 A/L RATIO GROSS BLOCKAGE FP15 BLEND3 BLKD 18-04-15 10:01:51 A/L RATIO GROSS BLOCKAGE FP10 BLEND3 2.71 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-02-20 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-02-19 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-02-18 10:00:09 ESTIMATED ORVRS >> EXPECTED 22-02-17 10:00:09 ESTIMATED ORVRS >> EXPECTED 22-02-16 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-02-15 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-02-14 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-02-13 10:00:09 ESTIMATED ORVRS >> EXPECTED 22-02-12 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-02-11 10:00:10 ESTIMATED ORVRS >> EXPECTED ISD Setup IV4200 FEB 21, 2022 8:36 Sensor / Airflow Meter / Hose Table / Grade Table Relationship SS AA F1 FL M1H1L1 M2H2L2 M3H3L3 M4H4L4 F2 L2 M1H1L1 M2H2L2 M3H3L3 M4H4L4 02 01 26 09 030102 040102 100102 000000 27 10 030202 040202 100202 000000 03 02 28 11 030302 040302 100302 06UU01 29 12 030402 040402 100402 06UU01 04 03 02 13 030502 040502 100502 000000 03 14 030602 040602 100602 000000 05 04 04 15 030702 040702 100702 06UU01 05 16 030802 040802 100802 06UU01 > Jaco 7708 Alarm History After. Responses Received: I10200 FEB 21, 2022 11:46 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39324 39359 2 4 PROBE / G.T. 163678 163682 3 INTERSTITIAL BD 202225 202669 4 INTERSTITIAL BD 201807 202012 5 UNUSED 9779221 9745232 6 UNUSED 9783833 9739652 7 UNUSED 9771268 9733464 8 UNUSED 9773362 9741182 9 RELAY BOARD 14962 14969 10 UNUSED 9769617 9744206 11 UNUSED 9780644 9740044 12 UNUSED 9767946 9727893 13 UNUSED 9773716 9738041 14 UNUSED 9778929 9734419 15 UNUSED 9764782 9743959 16 UNUSED 9780577 9738829 COMM 1 ELEC DISP INT. 101142 101335 COMM 2 RS232 SERIAL BD 15007 15014 COMM 3 RS232 SERIAL BD 15051 15059 COMM 4 UNUSED 9785033 9746479 COMM 5 UNUSED 9772624 9733474 COMM 6 UNUSED 9763914 9739706 I90200 FEB 21, 2022 11:46 SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 FEB 21, 2022 11:46 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 6 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L 4 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L 5 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L 3 STP SUMP PNL STP SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L10 DISP PAN DISP 15-16 SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM CLEAR FEB 21 2022 11:45 L 6 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM FEB 21 2022 11:45 L 5 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM FEB 21 2022 11:45 L 4 ANNULAR PNL ANN SENSOR OUT ALARM ALARM FEB 21 2022 11:45 L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM FEB 21 2022 11:45 L10 DISP PAN DISP 15-16 SENSOR OUT ALARM ALARM FEB 21 2022 11:45 L 3 STP SUMP PNL STP SENSOR OUT ALARM ALARM FEB 21 2022 11:45 L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM ALARM FEB 21 2022 11:45 L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM FEB 21 2022 11:45 L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM FEB 21 2022 11:45 L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM FEB 21 2022 11:44 L 2 ANNULAR UNL ANN FUEL ALARM CLEAR FEB 21 2022 11:39 L10 DISP PAN DISP 15-16 FUEL ALARM CLEAR FEB 21 2022 11:39 L10 DISP PAN DISP 15-16 FUEL ALARM ALARM FEB 21 2022 11:39 L 2 ANNULAR UNL ANN FUEL ALARM ALARM FEB 21 2022 11:39 L 4 ANNULAR PNL ANN FUEL ALARM CLEAR FEB 21 2022 11:38 L 9 DISP PAN DISP 13-14 FUEL ALARM CLEAR FEB 21 2022 11:38 L 9 DISP PAN DISP 13-14 FUEL ALARM ALARM FEB 21 2022 11:38 L 7 DISP PAN DISP 9-10 FUEL ALARM CLEAR FEB 21 2022 11:37 L 7 DISP PAN DISP 9-10 FUEL ALARM ALARM FEB 21 2022 11:37 L 1 STP SUMP UNL STP FUEL ALARM CLEAR FEB 21 2022 11:36 L 1 STP SUMP UNL STP FUEL ALARM ALARM FEB 21 2022 11:36 L 1 STP SUMP UNL STP FUEL ALARM CLEAR FEB 21 2022 11:36 L 4 ANNULAR PNL ANN FUEL ALARM ALARM FEB 21 2022 11:33 L 3 STP SUMP PNL STP FUEL ALARM CLEAR FEB 21 2022 11:31 L 8 DISP PAN DISP 11-12 FUEL ALARM CLEAR FEB 21 2022 11:31 L 6 ANNULAR DIESEL ANN FUEL ALARM CLEAR FEB 21 2022 11:31 L 5 STP SUMP DIESEL STP FUEL ALARM CLEAR FEB 21 2022 11:31 L 6 ANNULAR DIESEL ANN FUEL ALARM ALARM FEB 21 2022 11:31 L 1 STP SUMP UNL STP FUEL ALARM ALARM FEB 21 2022 11:30 L 8 DISP PAN DISP 11-12 FUEL ALARM ALARM FEB 21 2022 11:30 L 3 STP SUMP PNL STP FUEL ALARM ALARM FEB 21 2022 11:29 L 5 STP SUMP DIESEL STP FUEL ALARM ALARM FEB 21 2022 11:28 SYSTEM BATTERY IS OFF CLEAR FEB 21 2022 10:00 SYSTEM BATTERY IS OFF ALARM FEB 13 2021 8:00 I11200 FEB 21, 2022 11:46 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME I20600 FEB 21, 2022 11:46 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 TANK ALARM HISTORY TANK 1 UNL TANK 2 PNL TANK 3 DIESEL TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 FEB 21, 2022 11:46 I30200 FEB 21, 2022 11:46 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP FEB 21, 2022 11:45 SENSOR OUT ALARM FEB 21, 2022 11:36 FUEL ALARM FEB 21, 2022 11:30 FUEL ALARM 2 UNL ANN FEB 21, 2022 11:45 SENSOR OUT ALARM FEB 21, 2022 11:39 FUEL ALARM 3 PNL STP FEB 21, 2022 11:45 SENSOR OUT ALARM FEB 21, 2022 11:29 FUEL ALARM 4 PNL ANN FEB 21, 2022 11:45 SENSOR OUT ALARM FEB 21, 2022 11:33 FUEL ALARM 5 DIESEL STP FEB 21, 2022 11:45 SENSOR OUT ALARM FEB 21, 2022 11:28 FUEL ALARM 6 DIESEL ANN FEB 21, 2022 11:45 SENSOR OUT ALARM FEB 21, 2022 11:31 FUEL ALARM 7 DISP 9-10 FEB 21, 2022 11:44 SENSOR OUT ALARM FEB 21, 2022 11:37 FUEL ALARM 8 DISP 11-12 FEB 21, 2022 11:45 SENSOR OUT ALARM FEB 21, 2022 11:30 FUEL ALARM 9 DISP 13-14 FEB 21, 2022 11:45 SENSOR OUT ALARM FEB 21, 2022 11:38 FUEL ALARM 10 DISP 15-16 FEB 21, 2022 11:45 SENSOR OUT ALARM FEB 21, 2022 11:39 FUEL ALARM I31600 FEB 21, 2022 11:46 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 P.S 11-12 2 F.M 9-10 3 F.M 11-12 4 F.M 13-14 5 F.M 15-16 I40200 FEB 21, 2022 11:46 I40300 FEB 21, 2022 11:46 I34200 FEB 21, 2022 11:46 I34700 FEB 21, 2022 11:46 IV0100 FEB 21, 2022 11:46 FASTRIP 708 12851 ROSEDALE HWY BAKERSFIELD CA,93312 661-588-2799 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :NOTEST ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-02-05 10:02:52 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.60 22-02-03 10:02:05 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 2:F.M 11-12 22-02-03 10:02:05 A/L RATIO DEGRADATION FP12 BLEND3 BLKD 22-02-03 10:02:05 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD 22-02-03 10:02:05 A/L RATIO DEGRADATION FP11 BLEND3 BLKD 22-02-03 10:02:04 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 22-01-14 10:01:54 A/L RATIO DEGRADATION FP13 BLEND3 BLKD 21-12-22 10:02:08 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.44 21-12-21 10:02:42 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.89 21-12-14 10:02:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.52 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-02-04 10:02:34 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD 22-02-04 10:02:33 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 20-07-04 10:02:49 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 19-11-23 10:02:05 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 19-01-15 10:01:38 A/L RATIO GROSS BLOCKAGE FP16 BLEND3 BLKD 19-01-15 10:01:38 A/L RATIO GROSS BLOCKAGE FP15 BLEND3 BLKD 19-01-13 10:01:37 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD 19-01-13 10:01:37 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD 18-08-17 10:02:21 A/L RATIO GROSS BLOCKAGE FP15 BLEND3 BLKD 18-04-15 10:01:51 A/L RATIO GROSS BLOCKAGE FP10 BLEND3 2.71 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-02-21 11:45:36 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-02-21 11:45:36 ISD STARTUP 22-02-21 11:45:30 ISD SHUTDOWN 22-02-21 10:01:09 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-02-21 10:00:00 TIME CHANGE DETECTED AT: 22-02-21 08:23:46 22-02-21 08:23:36 TIME CHANGE DETECTED AT: 21-02-13 08:23:35 22-02-20 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-02-19 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-02-18 10:00:09 ESTIMATED ORVRS >> EXPECTED 22-02-17 10:00:09 ESTIMATED ORVRS >> EXPECTED