HomeMy WebLinkAboutFMC 2022Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION Installation Repair 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3.TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4.CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5.MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; Monitoring System Set-up Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications?
Secondary containment systems are free of damage, debris, or liquid?
Are the audible and visual alarms operational?
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational?
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment?
The monitoring system set-up was reviewed, and proper settings confirmed?
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational?
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment?
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected?
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) Sump UDC
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational?
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
3 GPH 0.1 GPH 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated?
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected?
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected?
For electronic LLDs, does the turbine automatically shut off when a release is
detected?
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected?
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test?
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks?
Were all items on the equipment manufacturer’s maintenance checklist completed?
Were all LLDs confirmed operational within regulatory requirements?
LLD ID LLD Model Lines Monitored Pass Fail
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
Check this box if tank gauging is used only for inventory control.
Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults?
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational?
Was accuracy of system’s product level readings tested?
Was accuracy of system’s water level readings tested?
Were all probes reinstalled properly?
Were all items on the equipment manufacturer’s maintenance checklist completed?
Probe ID Probe Model Tanks Monitored Pass Fail
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
lllonitoring System Certifi cation
UST Monitoring Site Plan
site Address: 8803 Camino Media, Bakersfield, CA. 93311
,,,'l:'.
',,,,1.,,.,r.s ?I? .
at
v,1
. . 1ltai)! ? +L.t .
. .Ax?:t" z,rg.
' 'sf unEq@
,m"si- oi. . .. .'*45.)r.
./(v........
-.LTD ,
o'"*t,
..... ..
Lro . . .
,4.'^t"tJ. ..
-:-, 7<ltl1tlo -:4:2i ie.A5:.(
>tt/(.
-:
..
{
::
Date map was draw l l_.
Instructlons
If you already have a diagram that shows all required information, you may include it, rather thar this page, with your Molritoring
System Certification- On your site plan, show the general layout of tatrks and piping. Ctearly identifu locations of the following
equipment, if installed: monitoring system control parels; sensors monitoring tank annular spacesr sumps, dispenser pans, spill
containers, or other secondary containment areas; mechaaical or electronic line leak detectors; and in+ank liquid level probes (ifused
for leak detection). In the space provided, note the date this Site Plan lyas prepared.
Page 4 of 4
rrr"_w.unidocs.orguN-035 - 4/.1 Rev.0l/17l0E
. r;4r\,a
03 17 22
CVE
Cal- Valley Equipment
3500 Gilmore Ave.
Bakersfield CA 93308
661 -327-9341 FAX# 661 -325-2529
VAPORLESS MANUFACTURING, INC.
LDT-890 Leak Detector Test Record
Technician Date
Pass / Fail
Product
Manufacturer
Leak rate
Operating pressure
Line pressure (pump off)
Facility Address
Bleed back (pump off)
Step through time to full flow
Stays in leak search position
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
<
I20100MAR 17, 2022 8:25 AM
BROOKSIDE MARKET
8803 CAMINO MEDIA BAKERSFIELD CA 93311
IN-TANK INVENTORY
TANK PRODUCT VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP 1 UNLEADED 10471 10441 9611 65.89 1.12 63.93
2 PREMIUM 4863 4844 7178 54.09 0.00 65.48 3 DIESEL 4311 4298 3716 67.46 0.00 66.10
>
<I90500
MAR 17, 2022 8:26 AMSOFTWARE REVISION LEVEL
VERSION 336.02SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-aSYSTEM FEATURES:
PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS
ISD/APM
><
I50201MAR 17, 2022 8:26 AM
SHIFT TIME 1 : 11:00 PM
>
<I50202
MAR 17, 2022 8:26 AM
SHIFT TIME 2 : DISABLED
><
I50203MAR 17, 2022 8:26 AM
SHIFT TIME 3 : DISABLED
>
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
<
I50204MAR 17, 2022 8:26 AM
SHIFT TIME 4 : DISABLED
>
<I54600
MAR 17, 2022 8:26 AM
TANK PER TST NEEDED WRN: DISABLED
><
I54900MAR 17, 2022 8:26 AM
TANK ANN TST NEEDED WRN: DISABLED
>
<I55300
MAR 17, 2022 8:26 AM
LINE RE-ENABLE METHODPASS LINE TEST
>
<I55600
MAR 17, 2022 8:26 AM
LINE PER TST NEEDED WRN: DISABLED
><
I55900MAR 17, 2022 8:26 AM
LINE ANN TST NEEDED WRN: DISABLED
>
<I51400
MAR 17, 2022 8:26 AM
H-PROTOCOL DATA FORMATHEIGHT
>
<I51A01
MAR 17, 2022 8:27 AM
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
DAYLIGHT SAVING TIMEENABLED OFF
>
<I51B00
MAR 17, 2022 8:27 AM
DAYLIGHT SAVING TIME
START DATE APR WEEK 1 SUN 2:00 AM
END DATE OCT WEEK 6 SUN 2:00 AM
><
I51600MAR 17, 2022 8:27 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
><
I50400MAR 17, 2022 8:27 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED 3 000000 DISABLED
4 000000 DISABLED 5 000000 DISABLED
6 000000 DISABLED
><
I21900MAR 17, 2022 8:27 AM
TANK CHART SECURITY
ENABLED
><
I5BD00MAR 17, 2022 8:27 AM
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
CUSTOM ALARM LABELS
DISABLED
>
<I56000
MAR 17, 2022 8:27 AM
MASS/DENSITY
DISABLED
><
I88101MAR 17, 2022 8:27 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )RS-232 SECURITY
CODE : ******
><
I88102MAR 17, 2022 8:27 AM
PORT SETTINGS:
COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600
PARITY : NONE STOP BIT : 1 STOP
DATA LENGTH: 8 DATARS-232 SECURITY
CODE : ****** DTR NORMAL STATE: HIGH
>
<I88103
MAR 17, 2022 8:27 AMPORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600 PARITY : NONE
STOP BIT : 1 STOP DATA LENGTH: 8 DATA
RS-232 SECURITYCODE : ******
>
<
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
I60100
MAR 17, 2022 8:27 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED 1 UNLEADED ON
2 PREMIUM ON 3 DIESEL ON
4 HACKED OFF
><
I60200MAR 17, 2022 8:27 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED 2 PREMIUM
3 DIESEL 4 HACKED
><
I60300MAR 17, 2022 8:27 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1 2 PREMIUM 2
3 DIESEL 3 4 HACKED 4
><
I60900MAR 17, 2022 8:27 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700 2 PREMIUM 0.000700
3 DIESEL 0.000450 4 HACKED 0.000000
><
I60700MAR 17, 2022 8:27 AM
TANK DIAMETER
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
TANK PRODUCT LABEL INCHES
1 UNLEADED 127.50 2 PREMIUM 127.50
3 DIESEL 127.50 4 HACKED 0.00
><
I60A00MAR 17, 2022 8:27 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS
1 UNLEADED 1 PT 20082
2 PREMIUM 1 PT 12041
3 DIESEL 1 PT 8027
4 HACKED 1 PT 111111
><
I60400MAR 17, 2022 8:27 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 20082 2 PREMIUM 12041
3 DIESEL 8027 4 HACKED 111111
><
I60500MAR 17, 2022 8:27 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 20082 0 0 0 2 PREMIUM 12041 0 0 0
3 DIESEL 8027 0 0 0 4 HACKED 111111 0 0 0
>
<I60600
MAR 17, 2022 8:27 AM
TANK 20 POINT VOLUMES
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
TANK PRODUCT LABEL GALLONS 1 UNLEADED 20082 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
2 PREMIUM 12041 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 3 DIESEL 8027 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
4 HACKED 111111 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
0 0 0 0
><
I61500MAR 17, 2022 8:27 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO 2 PREMIUM NO
3 DIESEL NO 4 HACKED NO
>
<I62F00
MAR 17, 2022 8:27 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 4.0 IN.
2 PREMIUM 4.0 IN. 3 DIESEL 4.0 IN.
>
<I62700
MAR 17, 2022 8:28 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
1 UNLEADED 2.0
2 PREMIUM 2.0 3 DIESEL 2.0
><
I64200MAR 17, 2022 8:28 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW 2 PREMIUM LOW
3 DIESEL LOW
><
I62400MAR 17, 2022 8:28 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0 2 PREMIUM 3.0
3 DIESEL 3.0>
<I62800
MAR 17, 2022 8:28 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS 1 UNLEADED 20082
2 PREMIUM 12041 3 DIESEL 8027
4 HACKED 111111>
<I62300
MAR 17, 2022 8:28 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS 1 UNLEADED 18074
2 PREMIUM 10837 3 DIESEL 7224
4 HACKED 0>
<I62200
MAR 17, 2022 8:28 AM
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS 1 UNLEADED 19078
2 PREMIUM 11439 3 DIESEL 7626
4 HACKED 0>
<I62900
MAR 17, 2022 8:28 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS 1 UNLEADED 2008
2 PREMIUM 1204 3 DIESEL 803
4 HACKED 0>
<I62100
MAR 17, 2022 8:28 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS 1 UNLEADED 500
2 PREMIUM 500 3 DIESEL 500
4 HACKED 0>
<I62600
MAR 17, 2022 8:28 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS 1 UNLEADED 99
2 PREMIUM 99 3 DIESEL 99
4 HACKED 99>
<I62500
MAR 17, 2022 8:28 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS 1 UNLEADED 50
2 PREMIUM 50
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
3 DIESEL 50
4 HACKED 99>
<I60800
MAR 17, 2022 8:28 AM
TANK TILT
TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00
2 PREMIUM 0.00 3 DIESEL 0.00
4 HACKED 0.00>
<I60B00
MAR 17, 2022 8:28 AM
STICK HEIGHT OFFSET ENABLE STATUSDISABLED
>
<I60C00
MAR 17, 2022 8:28 AM
TANK STICK HEIGHT OFFSETTANK PRODUCT LABEL INCHES
1 UNLEADED 0.00 2 PREMIUM 0.00
3 DIESEL 0.00 4 HACKED 0.00
><
I61200MAR 17, 2022 8:28 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE 2 PREMIUM NONE NONE
3 DIESEL NONE NONE 4 HACKED NONE NONE
><
I63600MAR 17, 2022 8:28 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 2008
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
2 PREMIUM 1204
3 DIESEL 802 4 HACKED 0
><
I62A00MAR 17, 2022 8:28 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 2008 2 PREMIUM 1204
3 DIESEL 802 4 HACKED 0
><
I62C00MAR 17, 2022 8:28 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD 2 PREMIUM STANDARD
3 DIESEL STANDARD 4 HACKED STANDARD
>
<I62D00
MAR 17, 2022 8:28 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL 1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED
2 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED
4 HACKED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED
>
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
<
I63100MAR 17, 2022 8:29 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF 2 PREMIUM OFF OFF
3 DIESEL OFF OFF 4 HACKED OFF OFF
>
<I63000
MAR 17, 2022 8:29 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED OFF
2 PREMIUM OFF 3 DIESEL OFF
4 HACKED OFF
><
I63200MAR 17, 2022 8:29 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF 2 PREMIUM OFF
3 DIESEL OFF 4 HACKED OFF
>
<I61000
MAR 17, 2022 8:29 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL 1 UNLEADED 15
2 PREMIUM 15 3 DIESEL 15
4 HACKED 1>
<I63A00
MAR 17, 2022 8:29 AM
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 10.00%
2 PREMIUM 10.00% 3 DIESEL 10.00%
4 HACKED 10.00%
><
I61100MAR 17, 2022 8:29 AM
LEAK TEST METHOD
- - - - - - - - - - - -TEST ANNUALLY: ALL TANK
DEC WEEK 2 WEDSTART TIME : 2:30 AM
TEST RATE :0.20 GAL/HRDURATION : 2 HOURS
TST EARLY STOP:DISABLED
>
<I61300
MAR 17, 2022 8:29 AMCSLD PROBABLITY OF DETECTION
><
I61400MAR 17, 2022 8:29 AM
CSLD CLIMATE FACTOR
>
<I61600
MAR 17, 2022 8:29 AM
TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED IMMEDIATE
2 PREMIUM IMMEDIATE 3 DIESEL IMMEDIATE
4 HACKED IMMEDIATE
><
I61A00MAR 17, 2022 8:29 AM
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED 2 PREMIUM DISABLED
3 DIESEL DISABLED 4 HACKED DISABLED
><
I61B00MAR 17, 2022 8:29 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
><
I61C00MAR 17, 2022 8:29 AM
CSLD REPORT ONLY
><
I63400MAR 17, 2022 8:29 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0 2 PREMIUM 0
3 DIESEL 0 4 HACKED 0
><
I63500MAR 17, 2022 8:29 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 2 PREMIUM 1
3 DIESEL 1 4 HACKED 1
><
I78700MAR 17, 2022 8:29 AM
>
<
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
I70200
MAR 17, 2022 8:29 AM
LIQUID LABEL
DEVICE LABEL 1 87 ANNULAR
2 87 STP 3 87 FILL
4 91-DIESEL ANNULAR 5 91 STP
6 91 FILL 7 DIESEL STP
8 DIESEL FILL 9 DISP 1-2
10 DISP 3-4 11 DISP 5-6
12 DISP 7-8 13
14 15
16
><
I70300MAR 17, 2022 8:29 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87 ANNULAR TRI-STATE (SINGLE FLOAT) 2 87 STP TRI-STATE (SINGLE FLOAT)
3 87 FILL TRI-STATE (SINGLE FLOAT) 4 91-DIESEL ANNULAR TRI-STATE (SINGLE FLOAT)
5 91 STP TRI-STATE (SINGLE FLOAT) 6 91 FILL TRI-STATE (SINGLE FLOAT)
7 DIESEL STP TRI-STATE (SINGLE FLOAT) 8 DIESEL FILL TRI-STATE (SINGLE FLOAT)
9 DISP 1-2 TRI-STATE (SINGLE FLOAT) 10 DISP 3-4 TRI-STATE (SINGLE FLOAT)
11 DISP 5-6 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT)
13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT)
>
<I70400
MAR 17, 2022 8:30 AM
LIQUID CATEGORY
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
SENSOR LOCATION CATEGORY
1 87 ANNULAR ANNULAR SPACE 2 87 STP STP SUMP
3 87 FILL OTHER SENSORS 4 91-DIESEL ANNULAR ANNULAR SPACE
5 91 STP STP SUMP 6 91 FILL OTHER SENSORS
7 DIESEL STP STP SUMP 8 DIESEL FILL OTHER SENSORS
9 DISP 1-2 DISPENSER PAN 10 DISP 3-4 DISPENSER PAN
11 DISP 5-6 DISPENSER PAN 12 DISP 7-8 DISPENSER PAN
13 OTHER SENSORS 14 OTHER SENSORS
15 OTHER SENSORS 16 OTHER SENSORS
>
<I80700
MAR 17, 2022 8:30 AM
RELAY LABEL
DEVICE LABEL 1 87 STP
2 91 STP 3 DIESEL STP
4
><
I80900MAR 17, 2022 8:30 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 87 STP NORMALLY CLOSED 2 91 STP NORMALLY CLOSED
3 DIESEL STP NORMALLY CLOSED 4 NORMALLY OPEN
>
<I80B00
MAR 17, 2022 8:30 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK 1 87 STP 1
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
2 91 STP 2
3 DIESEL STP 3 4 NONE
>
<I80A00
MAR 17, 2022 8:30 AM
RELAY TYPE
RELAY DESIGNATION TYPE 1 87 STP STANDARD
2 91 STP STANDARD 3 DIESEL STP STANDARD
4 STANDARD
><
I80800MAR 17, 2022 8:30 AM
RELAY SETUP REPORT
R 1:87 STP
TYPE: STANDARD
NORMALLY CLOSED
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM L 2:FUEL ALARM
L 9:FUEL ALARM L10:FUEL ALARM
L11:FUEL ALARM L12:FUEL ALARM
L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS ALL:FLOW COLLECT FAIL
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
R 2:91 STP TYPE:
STANDARDNORMALLY CLOSED
TANK #: 2
LIQUID SENSOR ALMS L 4:FUEL ALARM
L 5:FUEL ALARM L 9:FUEL ALARM
L10:FUEL ALARM L11:FUEL ALARM
L12:FUEL ALARM L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
ISD SITE ALARMS ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:FLOW COLLECT FAIL
R 3:DIESEL STP
TYPE: STANDARD
NORMALLY CLOSED
TANK #: 3
LIQUID SENSOR ALMS
L 4:FUEL ALARM L 7:FUEL ALARM
L12:FUEL ALARM L 4:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM L12:SENSOR OUT ALARM
R 4: TYPE:
STANDARDNORMALLY OPEN
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
TANK #: NONE
- NO ALARM ASSIGNMENTS -
><
I79000MAR 17, 2022 8:30 AM
EDIM:1 VR:349643-001-B TD:97.10.27.11.25
>
<I72300
MAR 17, 2022 8:30 AM
BROOKSIDE MARKET 8803 CAMINO MEDIA
BAKERSFIELD CA 93311
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY01 DISP 1-2 FM AIR FLOW METER
02 DISP 3-4 FM AIR FLOW METER03 DISP 5-6 FM AIR FLOW METER
04 DISP 7-8 FM AIR FLOW METER05 PRESS SENSOR VAPOR PRESSURE
06 UNKNOWN07 UNKNOWN
08 UNKNOWN09 UNKNOWN
10 UNKNOWN11 UNKNOWN
12 UNKNOWN13 UNKNOWN
14 UNKNOWN15 UNKNOWN
16 UNKNOWN17 UNKNOWN
18 UNKNOWN19 UNKNOWN
20 UNKNOWN21 UNKNOWN
22 UNKNOWN23 UNKNOWN
24 UNKNOWN25 UNKNOWN
26 UNKNOWN27 UNKNOWN
28 UNKNOWN
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
29 UNKNOWN
30 UNKNOWN31 UNKNOWN
32 UNKNOWN33 UNKNOWN
34 UNKNOWN35 UNKNOWN
36 UNKNOWN37 UNKNOWN
38 UNKNOWN39 UNKNOWN
40 UNKNOWN
><
IV4F00MAR 17, 2022 8:30 AM
BROOKSIDE MARKET
8803 CAMINO MEDIA BAKERSFIELD CA 93311
NOZZLE A/L RANGEA/L RATIO: 0.95 - 1.15
>
<IV4000
MAR 17, 2022 8:30 AM
BROOKSIDE MARKET 8803 CAMINO MEDIA
BAKERSFIELD CA 93311
VAPOR PROCESSOR TYPE
NONE
><
IV4700MAR 17, 2022 8:31 AM
BROOKSIDE MARKET
8803 CAMINO MEDIA BAKERSFIELD CA 93311
ASSESSMENT TIMESTART TIME: 9:00 AM
TIME DELAY MINUTES: 1
>
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
<
IV5200MAR 17, 2022 8:31 AM
BROOKSIDE MARKET
8803 CAMINO MEDIA BAKERSFIELD CA 93311
ACCEPT HIGH ORVR: NO >
<IV4A00
MAR 17, 2022 8:31 AM
BROOKSIDE MARKET 8803 CAMINO MEDIA
BAKERSFIELD CA 93311
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL 01 01 01 01 UU BLEND3
02 02 02 01 UU BLEND3 03 03 03 02 UU BLEND3
04 04 04 02 UU BLEND3 05 05 05 03 UU BLEND3
06 06 06 03 UU BLEND3 07 07 07 04 UU BLEND3
08 08 08 04 UU BLEND3
><
IV4B00MAR 17, 2022 8:31 AM
BROOKSIDE MARKET
8803 CAMINO MEDIA BAKERSFIELD CA 93311
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H401 01 02/01 09/01 01/01 xx/xx
02 01 02/02 09/02 01/02 xx/xx03 02 02/03 09/03 01/03 xx/xx
04 02 02/04 09/04 01/04 xx/xx05 03 02/05 09/05 01/05 xx/xx
06 03 02/06 09/06 01/06 xx/xx07 04 02/07 09/07 01/07 xx/xx
08 04 02/08 09/08 01/08 xx/xx
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
><
IV4900MAR 17, 2022 8:31 AM
BROOKSIDE MARKET
8803 CAMINO MEDIA BAKERSFIELD CA 93311
LABEL TABLEID LABEL
01 UNASSIGNED02 BLEND3
03 REGULAR 04 MID GRADE
05 PREMIUM 06 GOLD
07 BRONZE 08 SILVER
09 BLEND2 10 BLEND4
>
<IV1000
MAR 17, 2022 8:31 AM
ISD VERSION: 01.06
><
I90200MAR 17, 2022 8:31 AM
SOFTWARE REVISION LEVELVERSION 336.02
SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES: PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS ISD/APM
>
<I11100
MAR 17, 2022 8:31 AM
BROOKSIDE MARKET 8803 CAMINO MEDIA
BAKERSFIELD CA 93311
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER MISS VAPOR FLOW MTR CLEAR 3-11-22 3:21PM
OTHER MISSING HOSE SETUP CLEAR 3-11-22 3:21PM OTHER MISS VAPOR FLOW MTR ALARM 2-13-21 8:27AM
OTHER MISSING HOSE SETUP ALARM 2-13-21 8:27AM OTHER MISSING HOSE SETUP CLEAR 2-13-21 8:20AM
OTHER MISS VAPOR PRES SEN CLEAR 2-13-21 8:09AM OTHER MISS VAPOR FLOW MTR CLEAR 2-13-21 8:09AM
OTHER MISS VAPOR PRES SEN ALARM 2-13-21 8:05AM OTHER MISS VAPOR FLOW MTR ALARM 2-13-21 8:05AM
OTHER MISSING HOSE SETUP ALARM 2-13-21 8:05AM SYSTEM BATTERY IS OFF CLEAR 2-13-21 8:00AM
SYSTEM BATTERY IS OFF ALARM 2-13-21 8:00AM
><
I11200MAR 17, 2022 8:31 AM
BROOKSIDE MARKET
8803 CAMINO MEDIA BAKERSFIELD CA 93311
NON-PRIORITY ALARM HISTORYID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 3-14-22 9:29AM SYSTEM PAPER OUT CLEAR 3-14-22 9:29AM
SYSTEM PRINTER ERROR ALARM 3-14-22 9:29AM SYSTEM PAPER OUT ALARM 3-14-22 9:29AM
>
<I20600
MAR 17, 2022 8:31 AM
BROOKSIDE MARKET 8803 CAMINO MEDIA
BAKERSFIELD CA 93311
TANK ALARM HISTORY
TANK 1 UNLEADED
TANK 2 PREMIUM
TANK 3 DIESEL
TANK 5
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
>
<I38200
MAR 17, 2022 8:31 AM
><
I30200MAR 17, 2022 8:32 AM
BROOKSIDE MARKET
8803 CAMINO MEDIA BAKERSFIELD CA 93311
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION 1 87 ANNULAR
2 87 STP 3 87 FILL
4 91-DIESEL ANNULAR 5 91 STP
6 91 FILL 7 DIESEL STP
8 DIESEL FILL 9 DISP 1-2
10 DISP 3-4 11 DISP 5-6
12 DISP 7-8
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
>
<I31600
MAR 17, 2022 8:32 AM
BROOKSIDE MARKET 8803 CAMINO MEDIA
BAKERSFIELD CA 93311
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2 FM 2 DISP 3-4 FM
3 DISP 5-6 FM 4 DISP 7-8 FM
5 PRESS SENSOR
><
I10200MAR 17, 2022 8:32 AM
BROOKSIDE MARKET
8803 CAMINO MEDIA BAKERSFIELD CA 93311
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 10340846 10340846
2 UNUSED 10264550 10264550 3 UNUSED 10253776 10253776
4 UNUSED 10256495 10256495 5 4 PROBE / G.T. 164181 164181
6 INTERSTITIAL BD 202863 202863 7 INTERSTITIAL BD 203964 203964
8 8SMARTSENSOR BD 39611 39611 9 UNUSED 10274437 10274437
10 RELAY BOARD 14980 14980 11 UNUSED 10267565 10267565
12 UNUSED 10251061 10251061 13 UNUSED 10247075 10247075
14 UNUSED 10248507 10248507 15 UNUSED 10252618 10252618
16 UNUSED 10257164 10257164 COMM 1 ELEC DISP INT. 101655 101655
COMM 2 SERIAL SAT BD 487411 487411 COMM 3 RS232 SERIAL BD 15042 15042
COMM 4 UNUSED 10258784 10258784 COMM 5 UNUSED 10246203 10246203
file:///C/Users/jerryr/Desktop/03-17-22%20Oaks%20-%20Monitor/Cougar%20monitor.txt[3/17/2022 11:44:19 AM]
COMM 6 UNUSED 10240265 10240265
>
<I90200
MAR 17, 2022 8:32 AMSOFTWARE REVISION LEVEL
VERSION 336.02SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-aSYSTEM FEATURES:
PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS
ISD/APM
>