HomeMy WebLinkAboutFMC 2022IMPACT VALVE LEAK DETECTOR MONITOR CERTIFICATION SPILL BUCKET TEST 11000 N. MoPac Expressway, Suite 500 Austin, Texas 78759 Phone: (512) 451-6334 Fax: (512) 459-1459 Date Printed and Mailed: 4/18/2022 BAKERSFIELD FIRE DEPARTMENT OFFICE OF ENVIRONMENTAL SERVICES INSPECTOR KRIS KARNS 1501 TRUXTUN AVE. BAKERSFIELD, CA 93301 Test Date: 4/13/2022 Order Number: 3457903 Dear Regulator, Enclosed are the results of recent testing performed at the following facility: 7-ELEVEN 37942 (37942/59987) 3225 BUCK OWENS BLVD., HWY 99/HWY 58 BAKERSFIELD, CA 93301 In an effort to keep all our record keeping and reporting requirements as current as possible, Tanknology kindly requests you notify Dawn Kohlmeyer in writing at dkohlmeyer@tanknology.com when your CUPA requires all records to be submitted electronically via the CERS database. Your assistance in this endeavor is greatly appreciated. Testing performed: Sincerely, Dawn Kohlmeyer Manager, Field Reporting LDT 5000 Field Test Apparatus Line Leak Detector Test Page 1 of 1 Work Order:3457903 Date:4/13/2022 Site Name / ID:7-ELEVEN 37942 / 37942/59987 Address:3225 BUCK OWENS BLVD., HWY 99/HWY 58 City:BAKERSFIELD State:CA Zip:93301 Tank ID Product Product Line Tested From Existing/New Mechanical/Electronic Manufacturer/Model Serial No. Pump Operating Pressure (psi) Calibrated Leak (ml/min) Calibrated Leak (gph) Holding PSI *N/A for Electronic LD's Resiliency (ml) *N/A for Electronic LD's Metering PSI *N/A for Electronic LD's Opening Time (sec) *N/A for Electronic LD's Test Results T-1 REGULAR 1 6 Existing Mechanical Veeder Root FX1V 20508-3195 29.00 189.0 3.00 26.00 150.00 10 5 Pass T-2 PREMIUM 1 6 Existing Mechanical Veeder Root FX1V 30208-9410 28.00 189.0 3.00 26.00 125.00 10 7 Pass T-4 Diesel 1 9 Existing Mechanical Veeder Root FX1DV 412209911 31.00 189.0 3.00 28.00 200.00 11 9 Pass Technician Comments: Technician Name:Luis Navarro Certification #:147337 Technician Signature:Expire Date:11/29/2024 Environmental Compliance for Petroleum Systems © 2022 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Impact Valve Inspection Impact Valve Operational Inspection Work Order:3457903 Date:4/13/2022 Site Name/ID:7-ELEVEN 37942 Address:3225 BUCK OWENS BLVD., HWY 99/HWY 58 City:BAKERSFIELD State:CA Zip:93301 How Inspected: Line Test NFPA 30A PEI RP1200 Other Dispenser Number Grade Secure Mount? Valve Lock?Pass/ Fail Comments 1/2 87 Pass Fail Not Tested 1/2 91 Pass Fail Not Tested 3/4 87 Pass Fail Not Tested 3/4 91 Pass Fail Not Tested 5/6 87 Pass Fail Not Tested 5/6 91 Pass Fail Not Tested 7/8 87 Pass Fail Not Tested 7/8 91 Pass Fail Not Tested 9/ 40 Pass Fail Not Tested none/ 40 Pass Fail Not Tested 9 Sat/10 40 Pass Fail Not Tested 10 Sat/11 40 Pass Fail Not Tested 11 Sat/12 40 Pass Fail Not Tested 12 Sat/13 40 Pass Fail Not Tested 13 Sat/ 40 Pass Fail Not Tested Technician Comments: Technician Name:Luis Navarro Signature: Environmental Compliance for Petroleum Systems ©2022 Tanknology Inc., Austin, TX. All rights reserved. tanknology.com Tanknology, Inc.800-964-1250 11000 N Mopac Expy #500 Austin, Tx 78759 Luis Navarro 10134880 04/13/2022 7-ELEVEN 37942 3225 BUCK OWENS BLVD., HWY 99/HWY 58 BAKERSFIELD 93301 Class A General Engineering 743160 8171123 12/31/2022 05/28/2022 07/13/2022 04/03/2024 04/13/2022 6 Veeder Root:VR TLS-3XX VMI:TLDT-5000 Tester Franklin Fueling:Phil-Tite EVR Ph 1 Systems Gilbarco EMC 334.00 L1 91 STP SUMP L2 L3 87 INT L4 L5 L6 L7 FILTER SUMP L8 L9 91 FVR SUMP L10 UDC UDC UDC 3/4 UDC UDC 5/6 UDC UDC 7/8 UDC UDC 9 DIESEL UDC UDC 9 SAT/10 DIESEL UDC UDC 10- SAT/11 DIESEL UDC UDC 11 SAT/ 12 DIESEL UDC UDC UDC 13 SAT DIESEL 794380-205 87 STP SUMP 91 INT DSL STP SUMP DSL INT 87 FVR SUMP DSL FVR SUMP UDC 1/2 UDC 12 SAT/ 13 DIESEL 794380-208 794390-420 794390-420 794380-208 794390-420 794380-208 794380-208 794380-208 794380-208 330212-001 330212-001 330212-001 330212-001 330212-001 330212-001 330212-001 330212-001 330212-001 330212-001 T1 RUL T1 RUL T2 PUL T4 DSL T4 DSL Red Jacket FX1V T2 PULRed Jacket FX1V Red Jacket FX1DV The fueling point #1/2 and sat 12/13 main does not shut down dispensers, note :(stand-alone sensors in UDC's) , will require repairs. The rest of the testing with passing results. 04/13/2022 10134880 04/13/2022 7-ELEVEN 37942 3225 BUCK OWENS BLVD., HWY 99/HWY 58 BAKERSFIELD 93301 Tanknology, Inc.800-964-1250 11000 N Mopac Expy #500 Austin, TX 78759 Luis Navarro 743160 8171123 12/31/2022 04/03/2024 PEI RP1200 / Hydrostatic Franklin Fueling Spill Bucket 04/13/2022 2 Franklin Fueling:Phil-Tite EVR Ph 1 Systems T1 RUL T2 PUL T3 DSL Frankin Fueling Frankin Fueling Frankin Fueling SWRCB, January 2006 Spill Bucket Testing Report Form This form is intended for use by contractors performing annual testing of UST spill containment structures. The completed form and printouts from tests (if applicable), should be provided to the facility owner/operator for submittal to the local regulatory agency. 1. FACILITY INFORMATION Facility Name: 7-ELEVEN 37942 Date of Testing: 4/13/2022 Facility Address: 3225 BUCK OWENS BLVD., HWY 99/HWY 58 , BAKERSFIELD, CA 93301 Facility Contact: Joel Phone: 661-229-9416 Date Local Agency Was Notified of Testing: 3/23/2022 Name of Local Agency Inspector (if present during testing): Marty Brownfield, Bakersfield Fire 2. TESTING CONTRACTOR INFORMATION Company Name: TANKNOLOGY INC. Technician Conducting Test: Luis Navarro Credentials1: CSLB Contractor ICC Service Tech. SWRCB Tank Tester Other (Specify) License Number(s): 743160 / 8171123 3. SPILL BUCKET TESTING INFORMATION Test Method Used By: Hydrostatic Vacuum Other Test Equipment Used: LAKE TEST Equipment Resolution: 0.0625 in. Identify Spill Bucket (By Tank Number, Stored Product, etc.) Bucket Installation Type: Bucket Diameter: Bucket Depth: Wait time between applying vacuum/water and start of test Test Start Time (TI): Initial Reading (RI): Test End Time(TF): Final Reading (RF): Test Duration(TF–TI): Change in Reading (RF–RI) : Pass/Fail Threshold or Criteria: Test Result: Spill Box # Tank T-1 REGULAR - Fill 1 - Direct - Grade level in containment sump Direct Bury Contained in Sump 11.00 13.00 15 min 09:00:00 12.00 in. H20 10:00:00 12.00 in. H20 1 hr 0.00 in. H20 +/- 0.00 Pass Spill Box # Tank T-2 PREMIUM - Fill 1 - Direct - Below Grade in containment sump Direct Bury Contained in Sump 11.00 13.00 15 min 09:00:00 12.00 in. H20 10:00:00 12.00 in. H20 1 hr 0.00 in. H20 +/- 0.00 Pass Spill Box # Tank T-4 Diesel - Fill 1 - Direct - Grade level in containment sump Direct Bury Contained in Sump 11.00 13.00 15 min 10:30:00 12.00 in. H20 11:30:00 12.00 in. H20 1 hr 0.00 in. H20 +/- 0.00 Pass Spill Box # Direct Bury Contained in Sump min +/- Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) CERTIFICATION OF TECHNICIAN RESPONSIBLE FOR CONDUCTING THIS TESTING I hereby certify that all the information contained in this report is true, accurate, and in full compliance with legal requirements. Technician's Signature:Date:4/13/2022 1State laws and regulations do not currently require testing to be performed by a qualified contractor. However, local requirements may be more stringent. WO: 3457903 Site Diagram (This site diagram is for reference only and is not drawn to scale) Work Order:3457903 Site ID / Name:37942/59987 / 7-ELEVEN 37942 Address:3225 BUCK OWENS BLVD., HWY 99/HWY 58 City:BAKERSFIELD State:CA Zip:93301 W.O.# SC1-3457903 Responses Received: I10200 APR 13, 2022 11:38 AM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 162747 161298 2 INTERSTITIAL BD 201721 200948 3 INTERSTITIAL BD 202553 202164 4 UNUSED 9318278 9065903 5 UNUSED 9281574 9049028 6 UNUSED 9284007 9053727 7 UNUSED 9280400 9048059 8 UNUSED 9270269 9054653 9 RELAY BOARD 14937 14920 10 RELAY BOARD 14979 14963 11 UNUSED 9285281 9058736 12 UNUSED 9276640 9050654 13 UNUSED 9273829 9054145 14 UNUSED 9268711 9050352 15 UNUSED 9268942 9053412 16 UNUSED 9268837 9046796 COMM 1 ELEC DISP INT. 100470 100479 COMM 2 SERIAL SAT BD 480366 480086 COMM 3 RS232 SERIAL BD 15000 14985 COMM 4 UNUSED 9278947 9062680 COMM 5 RS485 SERIAL BD 68350 68337 COMM 6 MT COMM BOARD 406574 406320 I90200 APR 13, 2022 11:38 AM SOFTWARE REVISION LEVEL VERSION 334.00 SOFTWARE+ACM- 346334-100-A CREATED - 15.05.29.10.36 NO SOFTWARE MODULE SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS I11100 APR 13, 2022 11:38 AM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 7 PIPE FILTER SUMP FUEL ALARM CLEAR 4-13-22 11:28AM L 7 PIPE FILTER SUMP FUEL ALARM ALARM 4-13-22 11:27AM L 6 ANNULAR DSL INT FUEL ALARM CLEAR 4-13-22 10:22AM L 6 ANNULAR DSL INT FUEL ALARM ALARM 4-13-22 10:22AM L10 OTHER DSL FVR SUMP FUEL ALARM CLEAR 4-13-22 10:22AM L10 OTHER DSL FVR SUMP FUEL ALARM ALARM 4-13-22 10:22AM L 5 STP SUMP DSL STP SUMP FUEL ALARM CLEAR 4-13-22 10:21AM L 5 STP SUMP DSL STP SUMP FUEL ALARM ALARM 4-13-22 10:21AM L 4 ANNULAR 91 INT SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L 3 ANNULAR 87 INT SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L 8 OTHER 87 FVR SUMP SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L 2 STP SUMP 87 STP SUMP SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L 7 PIPE FILTER SUMP SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L 1 STP SUMP 91 STP SUMP SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L 6 ANNULAR DSL INT SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L 5 STP SUMP DSL STP SUMP SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L10 OTHER DSL FVR SUMP SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L 9 OTHER 91 FVR SUMP SENSOR OUT ALARM CLEAR 4-13-22 9:04AM L10 OTHER DSL FVR SUMP SENSOR OUT ALARM ALARM 4-13-22 9:03AM L 9 OTHER 91 FVR SUMP SENSOR OUT ALARM ALARM 4-13-22 9:03AM L 4 ANNULAR 91 INT SENSOR OUT ALARM ALARM 4-13-22 9:03AM L 3 ANNULAR 87 INT SENSOR OUT ALARM ALARM 4-13-22 9:03AM L 8 OTHER 87 FVR SUMP SENSOR OUT ALARM ALARM 4-13-22 9:03AM L 7 PIPE FILTER SUMP SENSOR OUT ALARM ALARM 4-13-22 9:03AM L 2 STP SUMP 87 STP SUMP SENSOR OUT ALARM ALARM 4-13-22 9:03AM L 1 STP SUMP 91 STP SUMP SENSOR OUT ALARM ALARM 4-13-22 9:03AM L 6 ANNULAR DSL INT SENSOR OUT ALARM ALARM 4-13-22 9:03AM L 5 STP SUMP DSL STP SUMP SENSOR OUT ALARM ALARM 4-13-22 9:03AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 4-13-22 8:57AM L 2 STP SUMP 87 STP SUMP FUEL ALARM CLEAR 4-13-22 8:48AM L 2 STP SUMP 87 STP SUMP FUEL ALARM ALARM 4-13-22 8:47AM L 8 OTHER 87 FVR SUMP FUEL ALARM CLEAR 4-13-22 8:47AM L 8 OTHER 87 FVR SUMP FUEL ALARM ALARM 4-13-22 8:47AM L 3 ANNULAR 87 INT FUEL ALARM CLEAR 4-13-22 8:47AM L 3 ANNULAR 87 INT FUEL ALARM ALARM 4-13-22 8:47AM L 4 ANNULAR 91 INT FUEL ALARM CLEAR 4-13-22 8:47AM L 4 ANNULAR 91 INT FUEL ALARM ALARM 4-13-22 8:47AM L 1 STP SUMP 91 STP SUMP FUEL ALARM CLEAR 4-13-22 8:46AM L 1 STP SUMP 91 STP SUMP FUEL ALARM ALARM 4-13-22 8:46AM L 9 OTHER 91 FVR SUMP FUEL ALARM CLEAR 4-13-22 8:46AM L 9 OTHER 91 FVR SUMP FUEL ALARM ALARM 4-13-22 8:46AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 4-06-22 4:43PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 4-06-22 4:43PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 3-30-22 4:43PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 3-30-22 4:43PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 3-23-22 4:43PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 3-23-22 4:43PM T 4 TANK DSL OVERFILL ALARM CLEAR 3-20-22 11:20PM T 4 TANK DSL OVERFILL ALARM ALARM 3-20-22 11:15PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 3-16-22 4:43PM I11200 APR 13, 2022 11:38 AM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PAPER OUT CLEAR 2-14-22 10:09AM SYSTEM PAPER OUT ALARM 2-14-22 6:00AM SYSTEM PRINTER ERROR CLEAR 11-26-21 8:54AM SYSTEM PAPER OUT CLEAR 11-26-21 8:53AM SYSTEM PAPER OUT ALARM 11-26-21 8:53AM SYSTEM PRINTER ERROR ALARM 11-26-21 8:53AM SYSTEM PRINTER ERROR CLEAR 11-26-21 8:53AM SYSTEM PAPER OUT CLEAR 11-26-21 8:52AM SYSTEM PAPER OUT ALARM 11-26-21 8:52AM SYSTEM PRINTER ERROR ALARM 11-26-21 8:52AM SYSTEM PRINTER ERROR CLEAR 11-26-21 8:51AM SYSTEM PRINTER ERROR ALARM 11-26-21 8:51AM SYSTEM PAPER OUT CLEAR 11-26-21 8:51AM SYSTEM PAPER OUT ALARM 11-26-21 6:00AM SYSTEM PRINTER ERROR CLEAR 11-12-21 9:51AM SYSTEM PRINTER ERROR ALARM 11-12-21 9:51AM SYSTEM PRINTER ERROR CLEAR 7-20-21 3:04PM SYSTEM PRINTER ERROR ALARM 7-20-21 3:04PM SYSTEM PAPER OUT CLEAR 7-20-21 3:04PM SYSTEM PAPER OUT ALARM 7-20-21 3:03PM SYSTEM PRINTER ERROR CLEAR 5-31-21 3:05AM SYSTEM PRINTER ERROR ALARM 5-31-21 3:05AM SYSTEM PAPER OUT CLEAR 5-31-21 3:05AM SYSTEM PRINTER ERROR CLEAR 5-31-21 3:05AM SYSTEM PAPER OUT ALARM 5-31-21 3:05AM SYSTEM PRINTER ERROR ALARM 5-31-21 3:05AM SYSTEM PRINTER ERROR CLEAR 5-31-21 3:04AM SYSTEM PRINTER ERROR ALARM 5-31-21 3:04AM SYSTEM PAPER OUT CLEAR 5-31-21 3:04AM SYSTEM PAPER OUT ALARM 5-31-21 3:01AM T 4 TANK DSL LOW TEMP WARNING CLEAR 4-19-21 12:22PM T 4 TANK DSL HIGH WATER WARNING CLEAR 4-19-21 12:21PM T 4 TANK DSL LOW TEMP WARNING ALARM 4-19-21 12:18PM T 4 TANK DSL HIGH PRODUCT ALARM CLEAR 4-19-21 12:18PM T 4 TANK DSL HIGH PRODUCT ALARM ALARM 4-19-21 12:14PM T 4 TANK DSL INVALID FUEL LEVEL CLEAR 4-19-21 12:12PM T 4 TANK DSL HIGH WATER WARNING ALARM 4-19-21 12:04PM T 4 TANK DSL DELIVERY NEEDED CLEAR 4-19-21 12:01PM T 4 TANK DSL DELIVERY NEEDED ALARM 4-19-21 11:47AM T 4 TANK DSL INVALID FUEL LEVEL ALARM 4-19-21 11:47AM T 1 TANK RUL LOW TEMP WARNING CLEAR 4-19-21 10:00AM T 1 TANK RUL LOW TEMP WARNING ALARM 4-19-21 9:58AM T 2 TANK PUL HIGH WATER WARNING CLEAR 4-19-21 9:58AM T 1 TANK RUL HIGH PRODUCT ALARM CLEAR 4-19-21 9:57AM T 1 TANK RUL HIGH PRODUCT ALARM ALARM 4-19-21 9:57AM T 2 TANK PUL LOW TEMP WARNING CLEAR 4-19-21 9:55AM T 2 TANK PUL LOW TEMP WARNING ALARM 4-19-21 9:55AM T 2 TANK PUL HIGH PRODUCT ALARM CLEAR 4-19-21 9:55AM T 2 TANK PUL HIGH PRODUCT ALARM ALARM 4-19-21 9:53AM T 1 TANK RUL HIGH WATER WARNING CLEAR 4-19-21 9:53AM I20600 APR 13, 2022 11:38 AM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 TANK ALARM HISTORY TANK 1 RUL HIGH WATER ALARM APR 19, 2021 9:39 AM APR 6, 2020 9:55 AM APR 15, 2019 10:12 AM OVERFILL ALARM APR 19, 2021 9:56 AM APR 6, 2020 9:53 AM APR 15, 2019 10:27 AM HIGH PRODUCT ALARM APR 19, 2021 9:57 AM APR 6, 2020 9:53 AM APR 15, 2019 10:27 AM INVALID FUEL LEVEL APR 19, 2021 9:35 AM APR 6, 2020 9:50 AM APR 15, 2019 10:09 AM PROBE OUT APR 19, 2021 9:57 AM APR 19, 2021 9:35 AM APR 6, 2020 9:57 AM HIGH WATER WARNING APR 19, 2021 9:39 AM APR 6, 2020 9:55 AM APR 15, 2019 10:12 AM MAX PRODUCT ALARM APR 19, 2021 9:57 AM APR 6, 2020 9:54 AM APR 15, 2019 10:27 AM LOW TEMP WARNING APR 19, 2021 9:58 AM APR 6, 2020 9:58 AM APR 15, 2019 10:30 AM TANK 2 PUL SETUP DATA WARNING OCT 27, 2016 1:06 PM HIGH WATER ALARM APR 19, 2021 9:42 AM APR 6, 2020 9:54 AM APR 15, 2019 10:12 AM OVERFILL ALARM APR 19, 2021 9:53 AM APR 6, 2020 10:00 AM APR 15, 2019 10:19 AM HIGH PRODUCT ALARM APR 19, 2021 9:53 AM APR 6, 2020 10:01 AM APR 15, 2019 10:20 AM INVALID FUEL LEVEL APR 19, 2021 9:37 AM APR 6, 2020 10:03 AM APR 6, 2020 9:51 AM PROBE OUT APR 19, 2021 9:54 AM APR 19, 2021 9:36 AM APR 6, 2020 10:03 AM HIGH WATER WARNING APR 19, 2021 9:42 AM APR 6, 2020 9:54 AM APR 15, 2019 10:12 AM MAX PRODUCT ALARM APR 19, 2021 9:53 AM APR 6, 2020 10:01 AM APR 15, 2019 10:20 AM LOW TEMP WARNING APR 19, 2021 9:55 AM APR 15, 2019 10:22 AM TANK 4 DSL SETUP DATA WARNING OCT 27, 2016 1:06 PM HIGH WATER ALARM APR 19, 2021 12:04 PM APR 6, 2020 11:36 AM APR 15, 2019 11:37 AM OVERFILL ALARM MAR 20, 2022 11:15 PM JUL 20, 2021 2:56 PM APR 19, 2021 12:14 PM HIGH PRODUCT ALARM APR 19, 2021 12:14 PM APR 6, 2020 11:33 AM APR 15, 2019 11:53 AM INVALID FUEL LEVEL APR 19, 2021 11:47 AM APR 6, 2020 11:59 AM APR 6, 2020 11:32 AM PROBE OUT APR 19, 2021 12:17 PM APR 19, 2021 11:46 AM APR 6, 2020 11:58 AM HIGH WATER WARNING APR 19, 2021 12:04 PM APR 6, 2020 11:36 AM APR 15, 2019 11:37 AM DELIVERY NEEDED APR 19, 2021 11:47 AM NOV 14, 2017 11:13 PM NOV 3, 2017 6:59 AM MAX PRODUCT ALARM APR 19, 2021 12:15 PM APR 6, 2020 11:34 AM APR 15, 2019 11:55 AM LOW TEMP WARNING APR 19, 2021 12:18 PM APR 15, 2019 11:58 AM MAY 9, 2018 12:03 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 APR 13, 2022 11:38 AM I30200 APR 13, 2022 11:38 AM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 91 STP SUMP APR 13, 2022 9:03 AM SENSOR OUT ALARM APR 13, 2022 8:46 AM FUEL ALARM APR 19, 2021 9:42 AM SENSOR OUT ALARM 2 87 STP SUMP APR 13, 2022 9:03 AM SENSOR OUT ALARM APR 13, 2022 8:47 AM FUEL ALARM APR 19, 2021 9:42 AM SENSOR OUT ALARM 3 87 INT APR 13, 2022 9:03 AM SENSOR OUT ALARM APR 13, 2022 8:47 AM FUEL ALARM APR 19, 2021 9:42 AM SENSOR OUT ALARM 4 91 INT APR 13, 2022 9:03 AM SENSOR OUT ALARM APR 13, 2022 8:47 AM FUEL ALARM APR 19, 2021 9:42 AM SENSOR OUT ALARM 5 DSL STP SUMP APR 13, 2022 10:21 AM FUEL ALARM APR 13, 2022 9:03 AM SENSOR OUT ALARM APR 19, 2021 11:44 AM FUEL ALARM 6 DSL INT APR 13, 2022 10:22 AM FUEL ALARM APR 13, 2022 9:03 AM SENSOR OUT ALARM APR 19, 2021 11:45 AM FUEL ALARM 7 FILTER SUMP APR 13, 2022 11:27 AM FUEL ALARM APR 13, 2022 9:03 AM SENSOR OUT ALARM DEC 16, 2021 9:06 AM FUEL ALARM 8 87 FVR SUMP APR 13, 2022 9:03 AM SENSOR OUT ALARM APR 13, 2022 8:47 AM FUEL ALARM APR 19, 2021 9:42 AM SENSOR OUT ALARM 9 91 FVR SUMP APR 13, 2022 9:03 AM SENSOR OUT ALARM APR 13, 2022 8:46 AM FUEL ALARM APR 19, 2021 9:42 AM SENSOR OUT ALARM 10 DSL FVR SUMP APR 13, 2022 10:22 AM FUEL ALARM APR 13, 2022 9:03 AM SENSOR OUT ALARM DEC 24, 2021 5:42 AM FUEL ALARM I31600 APR 13, 2022 11:39 AM I40200 APR 13, 2022 11:39 AM I40300 APR 13, 2022 11:39 AM I34200 APR 13, 2022 11:39 AM I34700 APR 13, 2022 11:39 AM IV0100 APR 13, 2022 11:39 AM W.O.# SC1-3457903 Responses Received: 200 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 APR 13, 2022 11:40 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 RUL 7011 47.47 0.0 71.8 7119 2 PUL 2565 28.70 0.0 73.3 7575 4 DSL 9936 63.26 0.0 71.7 10132 I90500 APR 13, 2022 11:40 AM SOFTWARE REVISION LEVEL VERSION 334.00 SOFTWARE+ACM- 346334-100-A CREATED - 15.05.29.10.36 NO SOFTWARE MODULE SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS I50500 APR 13, 2022 11:40 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 APR 13, 2022 11:40 AM SHIFT TIME 1 : 6:00 AM I50202 APR 13, 2022 11:40 AM SHIFT TIME 2 : 6:15 AM I50203 APR 13, 2022 11:40 AM SHIFT TIME 3 : DISABLED I50204 APR 13, 2022 11:40 AM SHIFT TIME 4 : DISABLED I54600 APR 13, 2022 11:40 AM TANK PER TST NEEDED WRN: DISABLED I54900 APR 13, 2022 11:40 AM TANK ANN TST NEEDED WRN: DISABLED I55300 APR 13, 2022 11:40 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 APR 13, 2022 11:40 AM LINE PER TST NEEDED WRN: DISABLED I55900 APR 13, 2022 11:40 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 APR 13, 2022 11:40 AM PRINT TC VOLUMES ENABLED I50E00 APR 13, 2022 11:40 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 APR 13, 2022 11:40 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 APR 13, 2022 11:40 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 APR 13, 2022 11:40 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 APR 13, 2022 11:40 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 APR 13, 2022 11:40 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 APR 13, 2022 11:40 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 APR 13, 2022 11:40 AM TANK CHART SECURITY DISABLED I5BD00 APR 13, 2022 11:40 AM CUSTOM ALARM LABELS DISABLED I56000 APR 13, 2022 11:40 AM MASS/DENSITY DISABLED I88101 APR 13, 2022 11:40 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 APR 13, 2022 11:40 AM PORT SETTINGS: COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88103 APR 13, 2022 11:40 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88104 APR 13, 2022 11:40 AM I88105 APR 13, 2022 11:40 AM PORT SETTINGS: COMM BOARD : 5 (RS-485) BAUD RATE : 2400 PARITY : EVEN STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88106 APR 13, 2022 11:40 AM PORT SETTINGS: COMM BOARD : 6 (MTCOMM) BAUD RATE : 9600 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I52000 APR 13, 2022 11:40 AM RECEIVER AUTO DIAL TYPE +ACY- START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE APR 15, 2019 DISABLED 2 ON DATE APR 15, 2019 DISABLED 3 ON DATE APR 15, 2019 DISABLED 4 ON DATE APR 15, 2019 DISABLED 5 ON DATE APR 15, 2019 DISABLED 6 ON DATE APR 15, 2019 DISABLED 7 ON DATE APR 15, 2019 DISABLED 8 VEEDER ROOT (FMS) WEEKLY WED 4:18 PM I60100 APR 13, 2022 11:40 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 RUL ON 2 PUL ON 3 OFF 4 DSL ON I60200 APR 13, 2022 11:40 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 RUL 2 PUL 3 4 DSL I60300 APR 13, 2022 11:40 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 RUL 1 2 PUL 2 3 3 4 DSL 4 I60900 APR 13, 2022 11:40 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 RUL 0.000700 2 PUL 0.000700 3 0.000000 4 DSL 0.000450 I60700 APR 13, 2022 11:40 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 RUL 95.50 2 PUL 95.50 3 0.00 4 DSL 127.50 I60A00 APR 13, 2022 11:40 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 RUL 1 PT 14130 2 PUL 1 PT 10140 3 1 PT 0 4 DSL 1 PT 20068 I60400 APR 13, 2022 11:40 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 RUL 14130 2 PUL 10140 3 0 4 DSL 20068 I60500 APR 13, 2022 11:40 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 RUL 14130 0 0 0 2 PUL 10140 0 0 0 3 0 0 0 0 4 DSL 20068 0 0 0 I60600 APR 13, 2022 11:40 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 RUL 14130 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PUL 10140 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 DSL 20068 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 APR 13, 2022 11:40 AM TANK PRODUCT LABEL METER DATA 1 RUL NO 2 PUL NO 3 NO 4 DSL NO I62F00 APR 13, 2022 11:40 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 RUL 4.0 IN. 2 PUL 4.0 IN. 4 DSL 4.0 IN. I62700 APR 13, 2022 11:40 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 RUL 1.0 2 PUL 1.0 4 DSL 1.5 I64200 APR 13, 2022 11:40 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 RUL LOW 2 PUL LOW 4 DSL LOW I62400 APR 13, 2022 11:40 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 RUL 1.5 2 PUL 1.5 4 DSL 2.0 I62800 APR 13, 2022 11:40 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 14130 2 PUL 10140 3 0 4 DSL 20068 I62300 APR 13, 2022 11:40 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 12717 2 PUL 9126 3 0 4 DSL 18061 I62200 APR 13, 2022 11:40 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 13424 2 PUL 9633 3 0 4 DSL 19065 I62900 APR 13, 2022 11:40 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 141 2 PUL 101 3 0 4 DSL 201 I62100 APR 13, 2022 11:40 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 0 2 PUL 0 3 0 4 DSL 0 I62600 APR 13, 2022 11:40 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 99 2 PUL 99 3 99 4 DSL 99 I62500 APR 13, 2022 11:40 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 99 2 PUL 99 3 99 4 DSL 99 I60800 APR 13, 2022 11:40 AM TANK TILT TANK PRODUCT LABEL INCHES 1 RUL 0.00 2 PUL 0.00 3 0.00 4 DSL 0.00 I60B00 APR 13, 2022 11:40 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 APR 13, 2022 11:40 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 RUL 0.00 2 PUL 0.00 3 0.00 4 DSL 0.00 I61200 APR 13, 2022 11:40 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 RUL NONE NONE 2 PUL NONE NONE 3 NONE NONE 4 DSL NONE NONE I63600 APR 13, 2022 11:40 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 RUL 7065 2 PUL 5070 3 0 4 DSL 10034 I62A00 APR 13, 2022 11:40 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 RUL 7065 2 PUL 5070 3 0 4 DSL 10034 I62C00 APR 13, 2022 11:40 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 RUL STANDARD 2 PUL STANDARD 3 STANDARD 4 DSL STANDARD I62D00 APR 13, 2022 11:40 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 RUL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PUL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 DSL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 APR 13, 2022 11:40 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 RUL OFF OFF 2 PUL OFF OFF 3 OFF OFF 4 DSL OFF OFF I63000 APR 13, 2022 11:40 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 RUL OFF 2 PUL OFF 3 OFF 4 DSL OFF I63200 APR 13, 2022 11:40 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 RUL OFF 2 PUL OFF 3 OFF 4 DSL OFF I61000 APR 13, 2022 11:40 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 RUL 3 2 PUL 3 3 1 4 DSL 3 I63A00 APR 13, 2022 11:40 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 RUL 10.00+ACU- 2 PUL 10.00+ACU- 3 10.00+ACU- 4 DSL 10.00+ACU- I61100 APR 13, 2022 11:40 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK MAY 29, 2015 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 APR 13, 2022 11:40 AM CSLD PROBABLITY OF DETECTION I61400 APR 13, 2022 11:40 AM CSLD CLIMATE FACTOR I61600 APR 13, 2022 11:40 AM TANK PRODUCT LABEL CAL UPDATE 1 RUL IMMEDIATE 2 PUL IMMEDIATE 3 IMMEDIATE 4 DSL IMMEDIATE I61A00 APR 13, 2022 11:40 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 RUL DISABLED 2 PUL DISABLED 3 DISABLED 4 DSL DISABLED I61B00 APR 13, 2022 11:40 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 APR 13, 2022 11:40 AM CSLD REPORT ONLY I62B00 APR 13, 2022 11:40 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 RUL ??? 0, 0 2 PUL ??? 0, 0 3 ??? 0, 0 4 DSL ??? 0, 0 I63300 APR 13, 2022 11:40 AM LEAK TEST REPORT FORMAT: NORMAL I63400 APR 13, 2022 11:40 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 0 2 PUL 0 3 0 4 DSL 0 I63500 APR 13, 2022 11:40 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 RUL 1 2 PUL 1 3 1 4 DSL 1 I63900 APR 13, 2022 11:40 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 RUL END FACTOR: NONE 2 PUL END FACTOR: NONE 3 END FACTOR: NONE 4 DSL END FACTOR: NONE I78000 APR 13, 2022 11:40 AM I77700 APR 13, 2022 11:40 AM I77800 APR 13, 2022 11:40 AM I78C00 APR 13, 2022 11:40 AM I78300 APR 13, 2022 11:40 AM I78F00 APR 13, 2022 11:40 AM I78700 APR 13, 2022 11:40 AM I70200 APR 13, 2022 11:40 AM LIQUID LABEL DEVICE LABEL 1 91 STP SUMP 2 87 STP SUMP 3 87 INT 4 91 INT 5 DSL STP SUMP 6 DSL INT 7 FILTER SUMP 8 87 FVR SUMP 9 91 FVR SUMP 10 DSL FVR SUMP 11 12 13 14 15 16 I70300 APR 13, 2022 11:40 AM LIQUID TYPE SENSOR LOCATION TYPE 1 91 STP SUMP TRI-STATE (SINGLE FLOAT) 2 87 STP SUMP TRI-STATE (SINGLE FLOAT) 3 87 INT TRI-STATE (SINGLE FLOAT) 4 91 INT TRI-STATE (SINGLE FLOAT) 5 DSL STP SUMP TRI-STATE (SINGLE FLOAT) 6 DSL INT TRI-STATE (SINGLE FLOAT) 7 FILTER SUMP TRI-STATE (SINGLE FLOAT) 8 87 FVR SUMP TRI-STATE (SINGLE FLOAT) 9 91 FVR SUMP TRI-STATE (SINGLE FLOAT) 10 DSL FVR SUMP TRI-STATE (SINGLE FLOAT) 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 APR 13, 2022 11:40 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 91 STP SUMP STP SUMP 2 87 STP SUMP STP SUMP 3 87 INT ANNULAR SPACE 4 91 INT ANNULAR SPACE 5 DSL STP SUMP STP SUMP 6 DSL INT ANNULAR SPACE 7 FILTER SUMP PIPING SUMP 8 87 FVR SUMP OTHER SENSORS 9 91 FVR SUMP OTHER SENSORS 10 DSL FVR SUMP OTHER SENSORS 11 OTHER SENSORS 12 OTHER SENSORS 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 APR 13, 2022 11:40 AM I74300 APR 13, 2022 11:40 AM I74400 APR 13, 2022 11:40 AM I74700 APR 13, 2022 11:40 AM I74800 APR 13, 2022 11:40 AM I74900 APR 13, 2022 11:40 AM I7BC00 APR 13, 2022 11:41 AM I80200 APR 13, 2022 11:41 AM I80300 APR 13, 2022 11:41 AM I80400 APR 13, 2022 11:41 AM I80700 APR 13, 2022 11:41 AM RELAY LABEL DEVICE LABEL 1 87 STP 2 89 STP 3 DSL 1,2,3 4 DSL STP 4,5 5 DSL OVERFILL 6 GAS OVERFILL 7 8 I80900 APR 13, 2022 11:41 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 87 STP NORMALLY CLOSED 2 89 STP NORMALLY CLOSED 3 DSL 1,2,3 NORMALLY CLOSED 4 DSL STP 4,5 NORMALLY CLOSED 5 DSL OVERFILL NORMALLY OPEN 6 GAS OVERFILL NORMALLY OPEN 7 NORMALLY OPEN 8 NORMALLY OPEN I80B00 APR 13, 2022 11:41 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 87 STP NONE 2 89 STP NONE 3 DSL 1,2,3 NONE 4 DSL STP 4,5 NONE 5 DSL OVERFILL NONE 6 GAS OVERFILL NONE 7 NONE 8 NONE I80A00 APR 13, 2022 11:41 AM RELAY TYPE RELAY DESIGNATION TYPE 1 87 STP STANDARD 2 89 STP STANDARD 3 DSL 1,2,3 STANDARD 4 DSL STP 4,5 STANDARD 5 DSL OVERFILL STANDARD 6 GAS OVERFILL STANDARD 7 STANDARD 8 STANDARD I80C00 APR 13, 2022 11:41 AM I80800 APR 13, 2022 11:41 AM RELAY SETUP REPORT R 1:87 STP TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS L 2:FUEL ALARM L 2:SENSOR OUT ALARM L 2:SHORT ALARM R 2:89 STP TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS L 1:FUEL ALARM L 1:SENSOR OUT ALARM L 1:SHORT ALARM R 3:DSL 1,2,3 TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM R 4:DSL STP 4,5 TYPE: STANDARD NORMALLY CLOSED LIQUID SENSOR ALMS L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM R 5:DSL OVERFILL TYPE: STANDARD NORMALLY OPEN IN-TANK ALARMS T 1:OVERFILL ALARM T 4:HIGH PRODUCT ALARM T 4:MAX PRODUCT ALARM LIQUID SENSOR ALMS ALL:FUEL ALARM R 6:GAS OVERFILL TYPE: STANDARD NORMALLY OPEN IN-TANK ALARMS T 1:OVERFILL ALARM T 2:OVERFILL ALARM T 1:HIGH PRODUCT ALARM T 2:HIGH PRODUCT ALARM T 1:MAX PRODUCT ALARM T 2:MAX PRODUCT ALARM R 7: TYPE: STANDARD NORMALLY OPEN - NO ALARM ASSIGNMENTS - R 8: TYPE: STANDARD NORMALLY OPEN - NO ALARM ASSIGNMENTS - I79000 APR 13, 2022 11:41 AM EDIM:1 VR:349781-001-D TD:01.08.15.07.12 I79100 APR 13, 2022 11:41 AM I72300 APR 13, 2022 11:41 AM I72A00 APR 13, 2022 11:41 AM IV4E00 APR 13, 2022 11:41 AM IV4F00 APR 13, 2022 11:41 AM IV4000 APR 13, 2022 11:41 AM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 VAPOR PROCESSOR TYPE NONE IV4700 APR 13, 2022 11:41 AM 860169 7-11 37942 3225 BUCK OWENS BAKERSFIELD,CA 933O8 41031663305001 ASSESSMENT TIME START TIME: 11:59 PM TIME DELAY MINUTES: 1 IV5200 APR 13, 2022 11:41 AM IV4A00 APR 13, 2022 11:41 AM IV4B00 APR 13, 2022 11:41 AM IV4900 APR 13, 2022 11:41 AM IV1000 APR 13, 2022 11:41 AM ISD VERSION: 01.05 Test Duration Test Pressure P/F Threshold Tank Annular - Vacuum 1 hr, 20k or less tank 10" hg 0 loss, int dry before and after test Tank Annular - Vacuum 2 hr, >20k tank 10" hg 0 loss, int dry before and after test Line Annular - Pressure 1 hr 5 psi 0 loss STP Sump - Hydro 1 hr 4" above highest penetration or sidewall seam less than 1/8" over hour, settle time of 15 minutes minimum prior to starting the test UDC Sump - Hydro 1 hr 4" above highest penetration or sidewall seam less than 1/8" over hour, settle time of 15 minutes minimum prior to starting the test Spill Bucket - SW Vac 1 min 30" wc no greater than 4" wc vaccum decay - bucket must be dry Spill Bucket - SW Hydro 1 hr within 1.5" of top of the bucket less than 1/8" over hour, settle time of 5 minutest minimum prior to starting the test Spill Bucket - DW Vac 1 min 15" wc no greater than 3" wc vaccum decay - int must be dry