HomeMy WebLinkAboutFMC 2022Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10120951 06/13/2022 Mesa Marin Chevron 11101 Highway 178 Bakersfield 93306 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Payton Phillips 1073967 9482312 01/15/2024 Veedor Root C27796 7-29-22 06/13/2022 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Gilbarco EMC 334.01 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208/420 Disp 1-2 L2 208/420 Disp 3-4 L3 208/420 Disp 5-6 L4 208/420 Disp 7-8 L5 208/420 Diso 9-10 L6 208/420 Disp 11-12 L7 208/420 UNL STP L8 208/420 UNL Fill L9 208/420 Supreme STP L10 208/420 Supreme Fill L11 208/420 Diesel STP L12 208/420 Diesel Fill L13 208/420 Vent Box S9 463 UNL Tank S10 463 UNL Product S11 463 Vapor Return S12 463 Supreme Tank S13 463 Supreme Product S14 463 UNL-SUP Vent S15 463 Diesel Tank S16 463 Diesel Product Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V Unleaded T2 FX1V Supreme T3 FX1DV Diesel Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ I had to remove water from all 3 Filll sumps. I had to replace the S14 (UNL SUP Vent) the Vac sensor was bad. I also had to change out the L10(Premium Fill sump) 208 sensor due to being bad also. The inspector wanted me to replace the 87 Fill and Vapor cap. Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. 03/13/2013 Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10120951 06/13/2022 Mesa Marin Chevron 11101 Highway 178 Bakersfield 93306 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Payton Phillips 1073967 9482312 01/15/2024 OPW 0187328 10/01/2022 Hydrostatic Lake Test OPW Spill buckets PEI 1200 06/13/2022 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1 Unleaded OPW T2 Supreme OPW T3 Diesel OPW 6/13/22 MESA MARIN CHEVRON MONITOR CERT TESTING SYSTEM SETUP 200 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 JUN 13, 2022 9:15 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 4458 38.07 0.0 81.1 7574 2 SUPREME 3116 29.27 0.0 79.4 8916 3 DIESEL 3667 32.86 0.0 80.2 8408 I90500 JUN 13, 2022 9:15 AM SOFTWARE REVISION LEVEL VERSION 334.01 SOFTWARE# 346334-100-B CREATED - 17.01.09.16.10 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JUN 13, 2022 9:15 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JUN 13, 2022 9:15 AM SHIFT TIME 1 : 1:00 AM I50202 JUN 13, 2022 9:15 AM SHIFT TIME 2 : DISABLED I50203 JUN 13, 2022 9:15 AM SHIFT TIME 3 : DISABLED I50204 JUN 13, 2022 9:15 AM SHIFT TIME 4 : DISABLED I54600 JUN 13, 2022 9:15 AM TANK PER TST NEEDED WRN: DISABLED I54900 JUN 13, 2022 9:15 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JUN 13, 2022 9:15 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JUN 13, 2022 9:15 AM LINE PER TST NEEDED WRN: DISABLED I55900 JUN 13, 2022 9:15 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JUN 13, 2022 9:15 AM PRINT TC VOLUMES ENABLED I50E00 JUN 13, 2022 9:15 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JUN 13, 2022 9:15 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JUN 13, 2022 9:15 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JUN 13, 2022 9:15 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 JUN 13, 2022 9:15 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 JUN 13, 2022 9:15 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JUN 13, 2022 9:15 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JUN 13, 2022 9:15 AM TANK CHART SECURITY DISABLED I5BD00 JUN 13, 2022 9:15 AM CUSTOM ALARM LABELS DISABLED I56000 JUN 13, 2022 9:15 AM MASS/DENSITY DISABLED I88101 JUN 13, 2022 9:15 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JUN 13, 2022 9:15 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JUN 13, 2022 9:15 AM PORT SETTINGS: COMM BOARD : 3 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88104 JUN 13, 2022 9:15 AM I88105 JUN 13, 2022 9:15 AM I88106 JUN 13, 2022 9:15 AM I52000 JUN 13, 2022 9:15 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 WEEKLY SUN 4:52 PM 2 WEEKLY SUN 4:52 PM 3 WEEKLY SUN 4:52 PM 4 WEEKLY SUN 4:52 PM 5 WEEKLY SUN 4:52 PM 6 WEEKLY SUN 4:52 PM 7 WEEKLY SUN 4:52 PM 8 VEEDER ROOT (FMS) WEEKLY SUN 4:52 PM I60100 JUN 13, 2022 9:15 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED ON 2 SUPREME ON 3 DIESEL ON 4 OFF I60200 JUN 13, 2022 9:15 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 2 SUPREME 3 DIESEL 4 I60300 JUN 13, 2022 9:15 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 2 SUPREME 2 3 DIESEL 3 4 4 I60900 JUN 13, 2022 9:15 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 0.000700 2 SUPREME 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 JUN 13, 2022 9:15 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 95.75 2 SUPREME 95.75 3 DIESEL 95.75 4 0.00 I60A00 JUN 13, 2022 9:15 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 PT 12032 2 SUPREME 1 PT 12032 3 DIESEL 1 PT 12075 4 1 PT 0 I60400 JUN 13, 2022 9:16 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 12032 2 SUPREME 12032 3 DIESEL 12075 4 0 I60500 JUN 13, 2022 9:16 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 12032 0 0 0 2 SUPREME 12032 0 0 0 3 DIESEL 12075 0 0 0 4 0 0 0 0 I60600 JUN 13, 2022 9:16 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 12032 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 SUPREME 12032 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 12075 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JUN 13, 2022 9:16 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED NO 2 SUPREME NO 3 DIESEL NO 4 NO I62F00 JUN 13, 2022 9:16 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 4.0 IN. PS 2 SUPREME 4.0 IN. PS 3 DIESEL 4.0 IN. I62700 JUN 13, 2022 9:16 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 2.0 2 SUPREME 2.0 3 DIESEL 2.0 I64200 JUN 13, 2022 9:16 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED LOW 2 SUPREME LOW 3 DIESEL LOW I62400 JUN 13, 2022 9:16 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 3.0 2 SUPREME 3.0 3 DIESEL 3.0 I62800 JUN 13, 2022 9:16 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 12032 2 SUPREME 12032 3 DIESEL 12075 4 0 I62300 JUN 13, 2022 9:16 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 10829 2 SUPREME 10829 3 DIESEL 10868 4 0 I62200 JUN 13, 2022 9:16 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 11430 2 SUPREME 11430 3 DIESEL 11471 4 0 I62900 JUN 13, 2022 9:16 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 SUPREME 120 3 DIESEL 121 4 0 I62100 JUN 13, 2022 9:16 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 500 2 SUPREME 500 3 DIESEL 500 4 0 I62600 JUN 13, 2022 9:16 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 SUPREME 99 3 DIESEL 99 4 99 I62500 JUN 13, 2022 9:16 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 SUPREME 99 3 DIESEL 99 4 99 I60800 JUN 13, 2022 9:16 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 SUPREME 0.00 3 DIESEL 0.00 4 0.00 I60B00 JUN 13, 2022 9:16 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JUN 13, 2022 9:16 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 SUPREME 0.00 3 DIESEL 0.00 4 0.00 I61200 JUN 13, 2022 9:16 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NONE NONE 2 SUPREME NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 JUN 13, 2022 9:16 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 SUPREME 120 3 DIESEL 120 4 0 I62A00 JUN 13, 2022 9:16 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 120 2 SUPREME 120 3 DIESEL 120 4 0 I62C00 JUN 13, 2022 9:16 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED STANDARD 2 SUPREME STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 JUN 13, 2022 9:16 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 SUPREME GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JUN 13, 2022 9:16 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED OFF OFF 2 SUPREME OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 JUN 13, 2022 9:16 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED OFF 2 SUPREME OFF 3 DIESEL OFF 4 OFF I63200 JUN 13, 2022 9:16 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED OFF 2 SUPREME OFF 3 DIESEL OFF 4 OFF I61000 JUN 13, 2022 9:16 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 2 SUPREME 1 3 DIESEL 1 4 1 I63A00 JUN 13, 2022 9:16 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 10.00% 2 SUPREME 10.00% 3 DIESEL 10.00% 4 10.00% I61100 JUN 13, 2022 9:16 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK JAN 2, 2019 START TIME : 2:00 AM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:ENABLED I61300 JUN 13, 2022 9:16 AM CSLD PROBABLITY OF DETECTION I61400 JUN 13, 2022 9:16 AM CSLD CLIMATE FACTOR I61600 JUN 13, 2022 9:16 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED IMMEDIATE 2 SUPREME IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 JUN 13, 2022 9:16 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED ENABLED 2 SUPREME ENABLED 3 DIESEL ENABLED 4 ENABLED I61B00 JUN 13, 2022 9:16 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JUN 13, 2022 9:16 AM CSLD REPORT ONLY I62B00 JUN 13, 2022 9:16 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED ??? 0, 0 2 SUPREME ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 JUN 13, 2022 9:16 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JUN 13, 2022 9:16 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 0 2 SUPREME 0 3 DIESEL 0 4 0 I63500 JUN 13, 2022 9:16 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 2 SUPREME 1 3 DIESEL 1 4 1 I63900 JUN 13, 2022 9:16 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED END FACTOR: NONE 2 SUPREME END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 JUN 13, 2022 9:16 AM I77700 JUN 13, 2022 9:16 AM I77800 JUN 13, 2022 9:16 AM I78C00 JUN 13, 2022 9:16 AM I78300 JUN 13, 2022 9:16 AM I78F00 JUN 13, 2022 9:16 AM I78700 JUN 13, 2022 9:16 AM I70200 JUN 13, 2022 9:16 AM LIQUID LABEL DEVICE LABEL 1 DISP 1-2 2 DISP 3-4 3 DISP 5-6 4 DISP 7-8 5 DISP 9-10 6 DISP 11-12 7 UNL STP 8 UNL FILL 9 SUPREME STP 10 SUPREME FILL 11 DIESEL STP 12 DIESEL FILL 13 VENT BOX 14 15 16 I70300 JUN 13, 2022 9:16 AM LIQUID TYPE SENSOR LOCATION TYPE 1 DISP 1-2 DW SUMP 2-1 2 DISP 3-4 DW SUMP 2-1 3 DISP 5-6 DW SUMP 2-1 4 DISP 7-8 DW SUMP 2-1 5 DISP 9-10 DW SUMP 2-1 6 DISP 11-12 DW SUMP 2-1 7 UNL STP DW SUMP 2-1 8 UNL FILL DW SUMP 2-1 9 SUPREME STP DW SUMP 2-1 10 SUPREME FILL DW SUMP 2-1 11 DIESEL STP DW SUMP 2-1 12 DIESEL FILL DW SUMP 2-1 13 VENT BOX DW SUMP 2-1 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JUN 13, 2022 9:16 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 DISP 1-2 DISPENSER PAN 2 DISP 3-4 DISPENSER PAN 3 DISP 5-6 DISPENSER PAN 4 DISP 7-8 DISPENSER PAN 5 DISP 9-10 DISPENSER PAN 6 DISP 11-12 DISPENSER PAN 7 UNL STP STP SUMP 8 UNL FILL OTHER SENSORS 9 SUPREME STP STP SUMP 10 SUPREME FILL OTHER SENSORS 11 DIESEL STP STP SUMP 12 DIESEL FILL OTHER SENSORS 13 VENT BOX OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 JUN 13, 2022 9:16 AM I74300 JUN 13, 2022 9:16 AM I74400 JUN 13, 2022 9:16 AM I74700 JUN 13, 2022 9:16 AM I74800 JUN 13, 2022 9:16 AM I74900 JUN 13, 2022 9:16 AM I7BC00 JUN 13, 2022 9:16 AM I80200 JUN 13, 2022 9:16 AM I80300 JUN 13, 2022 9:16 AM I80400 JUN 13, 2022 9:16 AM I80700 JUN 13, 2022 9:16 AM RELAY LABEL DEVICE LABEL 1 UNL 2 SUPREME 3 DIESEL 4 OVERFILL ALARM I80900 JUN 13, 2022 9:16 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL NORMALLY OPEN 2 SUPREME NORMALLY OPEN 3 DIESEL NORMALLY OPEN 4 OVERFILL ALARM NORMALLY OPEN I80B00 JUN 13, 2022 9:16 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNL 1 2 SUPREME 2 3 DIESEL 3 4 OVERFILL ALARM NONE I80A00 JUN 13, 2022 9:16 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNL PUMP CONTROL OUTPUT 2 SUPREME PUMP CONTROL OUTPUT 3 DIESEL PUMP CONTROL OUTPUT 4 OVERFILL ALARM STANDARD I80C00 JUN 13, 2022 9:16 AM I80800 JUN 13, 2022 9:16 AM RELAY SETUP REPORT R 1:UNL TYPE: PUMP CONTROL OUTPUT TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 9:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 9:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:SUPREME TYPE: PUMP CONTROL OUTPUT TANK #: 2 LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 9:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 9:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DIESEL TYPE: PUMP CONTROL OUTPUT TANK #: 3 LIQUID SENSOR ALMS L 2:FUEL ALARM L 6:FUEL ALARM L11:FUEL ALARM L 2:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 2:SHORT ALARM L 6:SHORT ALARM L11:SHORT ALARM R 4:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 JUN 13, 2022 9:17 AM EDIM:1 VR:349867-001-D TD:17.02.14.08.38 I79100 JUN 13, 2022 9:17 AM I72300 JUN 13, 2022 9:17 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 DISP 1-2 FM AIR FLOW METER 02 DISP 3-4 FM AIR FLOW METER 03 DISP 5-6 FM AIR FLOW METER 04 DISP 7-8 FM AIR FLOW METER 05 DISP 9-10 FM AIR FLOW METER 06 DISP 11-12 FM AIR FLOW METER 07 DISP 5-6 PS VAPOR PRESSURE 08 ATM ATM P SENSOR 09 UNL TANK VAC SENSOR 10 UNL PRODUCT VAC SENSOR 11 VAPOR RETURN VAC SENSOR 12 SUPREME TANK VAC SENSOR 13 SUPREME PRODUCT VAC SENSOR 14 UNL-SUP VENT VAC SENSOR 15 DIESEL TANK VAC SENSOR 16 DIESEL PRODUCT VAC SENSOR 17 DIESEL VENT VAC SENSOR 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JUN 13, 2022 9:17 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 EVR/ISD SETUP TYPE: BALANCE IV4F00 JUN 13, 2022 9:17 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JUN 13, 2022 9:17 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 VAPOR PROCESSOR TYPE NONE IV4700 JUN 13, 2022 9:17 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 JUN 13, 2022 9:17 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 ACCEPT HIGH ORVR: NO IV4A00 JUN 13, 2022 9:17 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 02 BLEND3 02 02 02 01 02 BLEND3 03 03 03 02 02 BLEND3 04 04 04 02 02 BLEND3 05 05 05 03 02 BLEND3 06 06 06 03 02 BLEND3 07 07 07 04 02 BLEND3 08 08 08 04 02 BLEND3 09 09 09 05 02 BLEND3 10 16 10 05 02 BLEND3 11 17 11 06 02 BLEND3 12 18 12 06 02 BLEND3 IV4B00 JUN 13, 2022 9:17 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 09/01 01/01 xx/xx 02 01 02/02 09/02 01/02 xx/xx 03 02 02/03 09/03 01/03 xx/xx 04 02 02/04 09/04 01/04 xx/xx 05 03 02/05 09/05 01/05 xx/xx 06 03 02/06 09/06 01/06 xx/xx 07 04 09/07 01/07 02/07 xx/xx 08 04 02/08 09/08 01/08 xx/xx 09 05 02/09 01/09 09/09 xx/xx 16 05 02/10 09/10 01/10 xx/xx 17 06 02/11 09/11 01/11 xx/xx 18 06 02/12 09/12 01/12 xx/xx IV4900 JUN 13, 2022 9:17 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JUN 13, 2022 9:17 AM ISD VERSION: 01.05 ALARM HISTORY (BEFORE) I10200 JUN 13, 2022 9:19 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 164673 164216 2 7SMARTSENSOR BD 507191 506060 3 8SMARTSENSOR BD 39377 39378 4 8SMARTSENSOR BD 39440 39443 5 INTERSTITIAL BD 201672 201918 6 INTERSTITIAL BD 200861 201381 7 UNUSED 4953456 4960547 8 UNUSED 4944083 4959793 9 RELAY BOARD 14972 14993 10 STP SENSE BOARD 33080 33102 11 UNUSED 4950675 4967361 12 UNUSED 4942529 4963442 13 UNUSED 4942944 4958124 14 UNUSED 4943339 4960708 15 UNUSED 4944711 4956057 16 UNUSED 4939848 4962602 COMM 1 ELEC DISP INT. 101264 101466 COMM 2 RS232 SERIAL BD 14930 14928 COMM 3 SERIAL SAT BD 481237 481385 COMM 4 UNUSED 4946373 4967619 COMM 5 UNUSED 4939474 4963937 COMM 6 UNUSED 4941947 4962258 I90200 JUN 13, 2022 9:19 AM SOFTWARE REVISION LEVEL VERSION 334.01 SOFTWARE# 346334-100-B CREATED - 17.01.09.16.10 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUN 13, 2022 9:19 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L12 OTHER DIESEL FILL FUEL ALARM ALARM 6-13-22 9:03AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 6-12-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 6-12-22 5:17PM h 7 OTHER FP7: BLEND3 FLOW COLLECT FAIL CLEAR 6-11-22 4:34PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 6-11-22 10:32AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 6-11-22 10:32AM h 7 OTHER FP7: BLEND3 FLOW COLLECT FAIL ALARM 6-11-22 10:07AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 6-10-22 10:32AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 6-10-22 10:32AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 6-05-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 6-05-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-29-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-29-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-23-22 10:32AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-23-22 10:32AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-22-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-22-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-19-22 10:32AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-19-22 10:32AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-15-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-15-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-10-22 11:30AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-10-22 11:30AM L10 OTHER SUPREME FILL LOW LIQUID ALARM ALARM 5-10-22 11:05AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-08-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-08-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-07-22 1:51AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-07-22 1:51AM E 1 OTHER COMMUNICATION ALARM CLEAR 5-05-22 1:25AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-05-22 1:15AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-05-22 1:15AM E 1 OTHER COMMUNICATION ALARM ALARM 5-05-22 12:50AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 5-01-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 5-01-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 4-28-22 1:29PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 4-28-22 1:29PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 4-26-22 10:30AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 4-26-22 10:30AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 4-25-22 10:30AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 4-25-22 10:30AM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 4-24-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 4-24-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 4-17-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 4-17-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 4-10-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 4-10-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 4-03-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 4-03-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 3-27-22 5:17PM D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 3-27-22 5:17PM I11200 JUN 13, 2022 9:19 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h10 OTHER FP10: BLEND3 FLOW COLLECT WARN CLEAR 6-11-22 4:34PM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 6-11-22 4:34PM SYSTEM PRINTER ERROR CLEAR 6-11-22 10:34AM SYSTEM PRINTER ERROR ALARM 6-11-22 10:33AM h 7 OTHER FP7: BLEND3 FLOW COLLECT WARN CLEAR 6-11-22 10:00AM h 7 OTHER FP7: BLEND3 FLOW COLLECT WARN ALARM 6-10-22 10:07AM SYSTEM PRINTER ERROR CLEAR 6-08-22 7:45AM SYSTEM PAPER OUT CLEAR 6-08-22 7:45AM SYSTEM PRINTER ERROR ALARM 6-08-22 7:45AM SYSTEM PAPER OUT ALARM 6-08-22 7:45AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 5-23-22 10:07AM h10 OTHER FP10: BLEND3 FLOW COLLECT WARN ALARM 5-19-22 10:07AM h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN CLEAR 4-26-22 1:03PM h 7 OTHER FP7: BLEND3 FLOW COLLECT WARN CLEAR 4-26-22 1:03PM h 7 OTHER FP7: BLEND3 FLOW COLLECT WARN ALARM 4-26-22 10:05AM h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN ALARM 4-25-22 10:05AM SYSTEM PRINTER ERROR CLEAR 3-25-22 11:39PM SYSTEM PAPER OUT CLEAR 3-25-22 11:39PM SYSTEM PAPER OUT ALARM 3-25-22 11:39PM SYSTEM PRINTER ERROR ALARM 3-25-22 11:39PM SYSTEM PAPER OUT CLEAR 3-25-22 11:39PM SYSTEM PRINTER ERROR CLEAR 3-25-22 11:39PM SYSTEM PRINTER ERROR ALARM 3-25-22 11:39PM SYSTEM PAPER OUT ALARM 3-25-22 11:39PM SYSTEM PAPER OUT CLEAR 3-25-22 11:39PM SYSTEM PAPER OUT ALARM 3-25-22 7:01AM SYSTEM PRINTER ERROR CLEAR 3-24-22 11:51PM SYSTEM PAPER OUT CLEAR 3-24-22 11:51PM SYSTEM PRINTER ERROR ALARM 3-24-22 11:51PM SYSTEM PRINTER ERROR CLEAR 3-24-22 11:51PM SYSTEM PRINTER ERROR ALARM 3-24-22 11:51PM SYSTEM PRINTER ERROR CLEAR 3-24-22 4:14PM SYSTEM PRINTER ERROR ALARM 3-24-22 4:14PM SYSTEM PAPER OUT ALARM 3-24-22 4:14PM SYSTEM PRINTER ERROR CLEAR 3-17-22 11:40PM SYSTEM PAPER OUT CLEAR 3-17-22 11:40PM SYSTEM PRINTER ERROR ALARM 3-17-22 11:39PM SYSTEM PAPER OUT ALARM 3-17-22 11:39PM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN CLEAR 3-05-22 10:00AM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN ALARM 3-04-22 10:07AM SYSTEM PRINTER ERROR CLEAR 3-02-22 5:22AM SYSTEM PRINTER ERROR ALARM 3-02-22 5:22AM SYSTEM PRINTER ERROR CLEAR 3-02-22 5:22AM SYSTEM PAPER OUT CLEAR 3-02-22 5:22AM SYSTEM PRINTER ERROR ALARM 3-02-22 5:22AM SYSTEM PAPER OUT ALARM 3-02-22 5:22AM SYSTEM PRINTER ERROR CLEAR 2-16-22 7:49AM SYSTEM PAPER OUT CLEAR 2-16-22 7:49AM SYSTEM PRINTER ERROR ALARM 2-16-22 7:48AM SYSTEM PAPER OUT ALARM 2-16-22 7:48AM I20600 JUN 13, 2022 9:19 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 TANK ALARM HISTORY TANK 1 UNLEADED SETUP DATA WARNING JUL 14, 2021 12:57 PM MAY 25, 2021 1:25 PM MAY 25, 2021 1:18 PM HIGH WATER ALARM JUL 14, 2021 1:06 PM MAY 25, 2021 12:49 PM MAY 25, 2021 12:33 PM OVERFILL ALARM MAY 25, 2021 12:22 PM HIGH PRODUCT ALARM MAY 25, 2021 12:28 PM MAY 25, 2021 12:22 PM MAY 20, 2019 2:49 PM INVALID FUEL LEVEL JUL 14, 2021 1:03 PM MAY 25, 2021 12:20 PM PROBE OUT JUL 14, 2021 12:57 PM MAY 25, 2021 1:25 PM MAY 25, 2021 1:18 PM HIGH WATER WARNING JUL 14, 2021 1:06 PM MAY 25, 2021 12:49 PM MAY 25, 2021 12:33 PM MAX PRODUCT ALARM MAY 20, 2019 2:49 PM LOW TEMP WARNING MAY 25, 2021 1:23 PM MAY 25, 2021 1:16 PM MAY 25, 2021 12:30 PM TANK 2 SUPREME SETUP DATA WARNING MAY 25, 2021 12:35 PM MAY 25, 2021 12:17 PM HIGH WATER ALARM MAY 25, 2021 12:21 PM OVERFILL ALARM MAY 25, 2021 12:30 PM LOW PRODUCT ALARM MAY 25, 2021 12:16 PM HIGH PRODUCT ALARM MAY 25, 2021 12:35 PM MAY 25, 2021 12:31 PM MAY 25, 2021 12:30 PM INVALID FUEL LEVEL MAY 25, 2021 12:16 PM PROBE OUT MAY 25, 2021 12:35 PM MAY 25, 2021 12:35 PM MAY 25, 2021 12:17 PM HIGH WATER WARNING MAY 25, 2021 12:21 PM MAX PRODUCT ALARM MAY 20, 2019 2:49 PM LOW TEMP WARNING MAY 25, 2021 12:35 PM TANK 3 DIESEL OVERFILL ALARM MAY 25, 2021 12:37 PM LOW PRODUCT ALARM MAY 25, 2021 12:14 PM SUDDEN LOSS ALARM MAY 20, 2019 3:20 PM HIGH PRODUCT ALARM MAY 25, 2021 12:37 PM MAY 25, 2021 12:37 PM MAY 20, 2019 2:49 PM PROBE OUT MAY 25, 2021 12:39 PM MAY 25, 2021 12:14 PM MAX PRODUCT ALARM MAY 20, 2019 2:49 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUN 13, 2022 9:19 AM I30200 JUN 13, 2022 9:19 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DISP 1-2 DEC 14, 2021 9:22 AM LOW LIQUID ALARM DEC 9, 2021 8:17 PM LOW LIQUID ALARM DEC 8, 2021 1:16 AM LOW LIQUID ALARM 2 DISP 3-4 NOV 15, 2021 6:28 AM LOW LIQUID ALARM NOV 14, 2021 6:25 AM LOW LIQUID ALARM NOV 13, 2021 7:00 AM LOW LIQUID ALARM 3 DISP 5-6 FEB 17, 2022 9:32 AM LOW LIQUID ALARM FEB 16, 2022 8:20 AM LOW LIQUID ALARM FEB 7, 2022 3:55 AM LOW LIQUID ALARM 4 DISP 7-8 NOV 10, 2021 8:45 PM LOW LIQUID ALARM NOV 10, 2021 2:57 AM LOW LIQUID ALARM NOV 8, 2021 10:22 PM LOW LIQUID ALARM 5 DISP 9-10 MAY 25, 2021 10:45 AM SENSOR OUT ALARM MAY 25, 2021 9:49 AM LOW LIQUID ALARM MAY 25, 2021 9:49 AM FUEL ALARM 6 DISP 11-12 MAY 25, 2021 10:45 AM SENSOR OUT ALARM MAY 25, 2021 9:48 AM LOW LIQUID ALARM MAY 25, 2021 9:48 AM LOW LIQUID ALARM 7 UNL STP MAY 25, 2021 10:44 AM SENSOR OUT ALARM MAY 25, 2021 9:34 AM LOW LIQUID ALARM MAY 25, 2021 9:34 AM FUEL ALARM 8 UNL FILL MAY 25, 2021 12:59 PM LOW LIQUID ALARM MAY 25, 2021 10:45 AM SENSOR OUT ALARM MAY 25, 2021 9:35 AM FUEL ALARM 9 SUPREME STP MAY 25, 2021 10:45 AM SENSOR OUT ALARM MAY 25, 2021 9:33 AM LOW LIQUID ALARM MAY 25, 2021 9:32 AM FUEL ALARM 10 SUPREME FILL MAY 10, 2022 11:05 AM LOW LIQUID ALARM SEP 7, 2021 1:00 PM LOW LIQUID ALARM SEP 7, 2021 12:59 PM LOW LIQUID ALARM 11 DIESEL STP MAY 25, 2021 10:45 AM SENSOR OUT ALARM MAY 25, 2021 9:31 AM LOW LIQUID ALARM MAY 25, 2021 9:31 AM LOW LIQUID ALARM 12 DIESEL FILL JUN 13, 2022 9:03 AM FUEL ALARM MAY 25, 2021 10:45 AM SENSOR OUT ALARM MAY 25, 2021 9:39 AM FUEL ALARM 13 VENT BOX SEP 14, 2021 9:27 PM LOW LIQUID ALARM SEP 13, 2021 10:48 PM LOW LIQUID ALARM SEP 13, 2021 12:34 AM LOW LIQUID ALARM I31600 JUN 13, 2022 9:19 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 DISP 1-2 FM 2 DISP 3-4 FM 3 DISP 5-6 FM 4 DISP 7-8 FM 5 DISP 9-10 FM 6 DISP 11-12 FM 7 DISP 5-6 PS 8 ATM 9 UNL TANK MAY 25, 2021 10:33 AM VACUUM WARNING MAY 25, 2021 10:15 AM HIGH LIQUID ALARM MAY 25, 2021 10:15 AM NO VACUUM ALARM 10 UNL PRODUCT MAY 25, 2021 12:02 PM NO VACUUM ALARM MAY 25, 2021 12:00 PM HIGH LIQUID ALARM MAY 21, 2020 10:56 AM HIGH LIQUID ALARM 11 VAPOR RETURN SEP 7, 2021 1:31 PM NO VACUUM ALARM JUL 21, 2021 1:50 PM NO VACUUM ALARM JUL 14, 2021 2:33 PM NO VACUUM ALARM 12 SUPREME TANK MAY 25, 2021 9:52 AM HIGH LIQUID ALARM MAY 21, 2020 10:18 AM HIGH LIQUID ALARM MAY 21, 2020 10:17 AM NO VACUUM ALARM 13 SUPREME PRODUCT MAY 25, 2021 12:06 PM NO VACUUM ALARM MAY 25, 2021 12:06 PM HIGH LIQUID ALARM MAY 21, 2020 11:30 AM HIGH LIQUID ALARM 14 UNL-SUP VENT JUL 24, 2021 11:31 PM NO VACUUM ALARM MAY 25, 2021 12:06 PM HIGH LIQUID ALARM MAY 25, 2021 12:06 PM NO VACUUM ALARM 15 DIESEL TANK MAY 25, 2021 10:24 AM HIGH LIQUID ALARM MAY 25, 2021 10:24 AM NO VACUUM ALARM MAY 25, 2021 9:35 AM NO VACUUM ALARM 16 DIESEL PRODUCT MAY 25, 2021 12:10 PM HIGH LIQUID ALARM MAY 25, 2021 12:10 PM NO VACUUM ALARM MAY 21, 2020 9:56 AM HIGH LIQUID ALARM 17 DIESEL VENT MAY 25, 2021 12:10 PM HIGH LIQUID ALARM MAY 25, 2021 12:10 PM NO VACUUM ALARM MAY 21, 2020 11:33 AM HIGH LIQUID ALARM I40200 JUN 13, 2022 9:19 AM I40300 JUN 13, 2022 9:19 AM I34200 JUN 13, 2022 9:19 AM I34700 JUN 13, 2022 9:19 AM IV0100 JUN 13, 2022 9:19 AM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :NOTEST EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-06-10 10:07:22 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3 0.59 22-05-23 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 0.58 22-05-19 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP10 BLEND3 0.58 22-04-26 10:05:48 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3 0.60 22-04-25 10:05:50 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 0.59 22-03-04 10:07:16 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3 0.60 21-12-27 10:02:59 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.91 21-12-26 10:04:07 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.91 21-12-25 10:03:55 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.71 21-12-05 10:05:07 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3 0.56 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-06-11 10:07:00 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3 22-03-05 10:07:15 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3 21-09-07 10:07:55 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 21-08-18 10:08:51 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 21-07-26 10:05:35 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-04-12 10:05:16 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 20-03-11 10:05:46 FLOW PERFORMANCE HOSE BLOCKAGE FP11 BLEND3 19-12-30 10:04:24 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 19-09-11 10:05:38 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 19-01-15 10:01:43 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.91 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-06-12 10:08:20 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-06-12 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-06-11 16:34:44 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED 22-06-11 16:34:38 COLLECTION TEST HH07 GRADE TEST MANUALLY CLEARED 22-06-11 16:34:19 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED 22-06-11 10:29:52 PUMPS MANUALLY RE-ENABLED 22-06-11 10:07:00 READINESS ISD:PP EVR:FP CHECK EVR SYSTEM 22-06-11 10:07:00 FLOW PERFORMANCE BLK DISABLED FP 07 BLEND3 22-06-11 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-06-10 10:07:22 READINESS ISD:PP EVR:FP CHECK EVR SYSTEM ALARM HISTORY (AFTER) I10200 JUN 13, 2022 6:31 PM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 164673 164096 2 7SMARTSENSOR BD 507191 506357 3 8SMARTSENSOR BD 39377 39385 4 8SMARTSENSOR BD 39440 39429 5 INTERSTITIAL BD 201672 201814 6 INTERSTITIAL BD 200861 201274 7 UNUSED 4953456 4910349 8 UNUSED 4944083 4914633 9 RELAY BOARD 14972 15007 10 STP SENSE BOARD 33080 33139 11 UNUSED 4950675 4913405 12 UNUSED 4942529 4912951 13 UNUSED 4942944 4908256 14 UNUSED 4943339 4916585 15 UNUSED 4944711 4915222 16 UNUSED 4939848 4912994 COMM 1 ELEC DISP INT. 101264 101312 COMM 2 RS232 SERIAL BD 14930 14942 COMM 3 SERIAL SAT BD 481237 481073 COMM 4 UNUSED 4946373 4917169 COMM 5 UNUSED 4939474 4906526 COMM 6 UNUSED 4941947 4911458 I90200 JUN 13, 2022 6:31 PM SOFTWARE REVISION LEVEL VERSION 334.01 SOFTWARE# 346334-100-B CREATED - 17.01.09.16.10 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUN 13, 2022 6:31 PM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME s15 OTHER DIESEL TANK NO VACUUM ALARM CLEAR 6-13-22 5:36PM s12 OTHER SUPREME TANK NO VACUUM ALARM CLEAR 6-13-22 5:32PM s 9 OTHER UNL TANK NO VACUUM ALARM CLEAR 6-13-22 5:25PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:30PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:30PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:29PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:29PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:27PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:27PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:26PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:26PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:25PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:25PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:24PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:24PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:23PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:23PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:23PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:23PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:21PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:21PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:20PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:20PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:19PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:19PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:18PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:18PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:17PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:17PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:17PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:17PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:16PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:16PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:14PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:14PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:14PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:13PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:13PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:13PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:10PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:10PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:09PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:09PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:09PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:09PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:09PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:09PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:08PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM CLEAR 6-13-22 4:08PM s14 OTHER UNL-SUP VENT NO VACUUM ALARM ALARM 6-13-22 4:08PM I11200 JUN 13, 2022 6:31 PM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:30PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:30PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:29PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:29PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:27PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:27PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:26PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:26PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:25PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:25PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:24PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:24PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:23PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:23PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:23PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:23PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:21PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:21PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:20PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:20PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:19PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:19PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:18PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:18PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:17PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:17PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:17PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:17PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:16PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:16PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:14PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:14PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:14PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:13PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:13PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:13PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:10PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:10PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:09PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:09PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:09PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:09PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:09PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:09PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:08PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:08PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:08PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:08PM s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:08PM s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:08PM I20600 JUN 13, 2022 6:31 PM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 TANK ALARM HISTORY TANK 1 UNLEADED SETUP DATA WARNING JUL 14, 2021 12:57 PM MAY 25, 2021 1:25 PM MAY 25, 2021 1:18 PM HIGH WATER ALARM JUL 14, 2021 1:06 PM MAY 25, 2021 12:49 PM MAY 25, 2021 12:33 PM OVERFILL ALARM MAY 25, 2021 12:22 PM HIGH PRODUCT ALARM MAY 25, 2021 12:28 PM MAY 25, 2021 12:22 PM MAY 20, 2019 2:49 PM INVALID FUEL LEVEL JUL 14, 2021 1:03 PM MAY 25, 2021 12:20 PM PROBE OUT JUL 14, 2021 12:57 PM MAY 25, 2021 1:25 PM MAY 25, 2021 1:18 PM HIGH WATER WARNING JUL 14, 2021 1:06 PM MAY 25, 2021 12:49 PM MAY 25, 2021 12:33 PM MAX PRODUCT ALARM MAY 20, 2019 2:49 PM LOW TEMP WARNING MAY 25, 2021 1:23 PM MAY 25, 2021 1:16 PM MAY 25, 2021 12:30 PM TANK 2 SUPREME SETUP DATA WARNING MAY 25, 2021 12:35 PM MAY 25, 2021 12:17 PM HIGH WATER ALARM MAY 25, 2021 12:21 PM OVERFILL ALARM MAY 25, 2021 12:30 PM LOW PRODUCT ALARM MAY 25, 2021 12:16 PM HIGH PRODUCT ALARM MAY 25, 2021 12:35 PM MAY 25, 2021 12:31 PM MAY 25, 2021 12:30 PM INVALID FUEL LEVEL MAY 25, 2021 12:16 PM PROBE OUT MAY 25, 2021 12:35 PM MAY 25, 2021 12:35 PM MAY 25, 2021 12:17 PM HIGH WATER WARNING MAY 25, 2021 12:21 PM MAX PRODUCT ALARM MAY 20, 2019 2:49 PM LOW TEMP WARNING MAY 25, 2021 12:35 PM TANK 3 DIESEL OVERFILL ALARM MAY 25, 2021 12:37 PM LOW PRODUCT ALARM MAY 25, 2021 12:14 PM SUDDEN LOSS ALARM MAY 20, 2019 3:20 PM HIGH PRODUCT ALARM MAY 25, 2021 12:37 PM MAY 25, 2021 12:37 PM MAY 20, 2019 2:49 PM PROBE OUT MAY 25, 2021 12:39 PM MAY 25, 2021 12:14 PM MAX PRODUCT ALARM MAY 20, 2019 2:49 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUN 13, 2022 6:31 PM I30200 JUN 13, 2022 6:31 PM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DISP 1-2 JUN 13, 2022 10:56 AM FUEL ALARM JUN 13, 2022 10:56 AM LOW LIQUID ALARM DEC 14, 2021 9:22 AM LOW LIQUID ALARM 2 DISP 3-4 JUN 13, 2022 10:55 AM FUEL ALARM JUN 13, 2022 10:54 AM LOW LIQUID ALARM NOV 15, 2021 6:28 AM LOW LIQUID ALARM 3 DISP 5-6 JUN 13, 2022 10:49 AM FUEL ALARM JUN 13, 2022 10:49 AM LOW LIQUID ALARM FEB 17, 2022 9:32 AM LOW LIQUID ALARM 4 DISP 7-8 JUN 13, 2022 11:14 AM LOW LIQUID ALARM JUN 13, 2022 10:47 AM FUEL ALARM NOV 10, 2021 8:45 PM LOW LIQUID ALARM 5 DISP 9-10 JUN 13, 2022 10:44 AM FUEL ALARM JUN 13, 2022 10:43 AM LOW LIQUID ALARM MAY 25, 2021 10:45 AM SENSOR OUT ALARM 6 DISP 11-12 JUN 13, 2022 10:41 AM FUEL ALARM JUN 13, 2022 10:41 AM LOW LIQUID ALARM MAY 25, 2021 10:45 AM SENSOR OUT ALARM 7 UNL STP JUN 13, 2022 10:26 AM LOW LIQUID ALARM JUN 13, 2022 10:26 AM FUEL ALARM MAY 25, 2021 10:44 AM SENSOR OUT ALARM 8 UNL FILL JUN 13, 2022 11:27 AM LOW LIQUID ALARM JUN 13, 2022 10:32 AM FUEL ALARM MAY 25, 2021 12:59 PM LOW LIQUID ALARM 9 SUPREME STP JUN 13, 2022 10:25 AM LOW LIQUID ALARM JUN 13, 2022 10:24 AM FUEL ALARM MAY 25, 2021 10:45 AM SENSOR OUT ALARM 10 SUPREME FILL JUN 13, 2022 10:29 AM FUEL ALARM JUN 13, 2022 10:01 AM LOW LIQUID ALARM JUN 13, 2022 10:01 AM FUEL ALARM 11 DIESEL STP JUN 13, 2022 10:23 AM LOW LIQUID ALARM JUN 13, 2022 10:23 AM LOW LIQUID ALARM JUN 13, 2022 10:23 AM FUEL ALARM 12 DIESEL FILL JUN 13, 2022 10:28 AM FUEL ALARM JUN 13, 2022 10:27 AM LOW LIQUID ALARM JUN 13, 2022 9:03 AM FUEL ALARM 13 VENT BOX JUN 13, 2022 10:57 AM FUEL ALARM JUN 13, 2022 10:57 AM LOW LIQUID ALARM SEP 14, 2021 9:27 PM LOW LIQUID ALARM I31600 JUN 13, 2022 6:31 PM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 DISP 1-2 FM 2 DISP 3-4 FM 3 DISP 5-6 FM 4 DISP 7-8 FM 5 DISP 9-10 FM 6 DISP 11-12 FM 7 DISP 5-6 PS 8 ATM 9 UNL TANK JUN 13, 2022 2:02 PM NO VACUUM ALARM JUN 13, 2022 1:15 PM HIGH LIQUID ALARM MAY 25, 2021 10:33 AM VACUUM WARNING 10 UNL PRODUCT JUN 13, 2022 1:06 PM HIGH LIQUID ALARM JUN 13, 2022 1:06 PM NO VACUUM ALARM JUN 13, 2022 12:37 PM NO VACUUM ALARM 11 VAPOR RETURN JUN 13, 2022 1:00 PM HIGH LIQUID ALARM JUN 13, 2022 12:59 PM NO VACUUM ALARM JUN 13, 2022 12:37 PM NO VACUUM ALARM 12 SUPREME TANK JUN 13, 2022 3:33 PM HIGH LIQUID ALARM JUN 13, 2022 1:21 PM NO VACUUM ALARM MAY 25, 2021 9:52 AM HIGH LIQUID ALARM 13 SUPREME PRODUCT JUN 13, 2022 12:47 PM HIGH LIQUID ALARM JUN 13, 2022 12:47 PM NO VACUUM ALARM MAY 25, 2021 12:06 PM NO VACUUM ALARM 14 UNL-SUP VENT JUN 13, 2022 4:30 PM NO VACUUM ALARM JUN 13, 2022 4:30 PM VACUUM WARNING JUN 13, 2022 4:29 PM NO VACUUM ALARM 15 DIESEL TANK JUN 13, 2022 2:33 PM NO VACUUM ALARM JUN 13, 2022 1:43 PM HIGH LIQUID ALARM MAY 25, 2021 10:24 AM HIGH LIQUID ALARM 16 DIESEL PRODUCT JUN 13, 2022 12:48 PM HIGH LIQUID ALARM JUN 13, 2022 12:48 PM NO VACUUM ALARM MAY 25, 2021 12:10 PM HIGH LIQUID ALARM 17 DIESEL VENT JUN 13, 2022 1:33 PM HIGH LIQUID ALARM JUN 13, 2022 12:48 PM HIGH LIQUID ALARM JUN 13, 2022 12:48 PM NO VACUUM ALARM I40200 JUN 13, 2022 6:32 PM I40300 JUN 13, 2022 6:32 PM I34200 JUN 13, 2022 6:32 PM I34700 JUN 13, 2022 6:32 PM IV0100 JUN 13, 2022 6:32 PM 175900 MESA MARIN CH PIT STOP MARKET 11101 HWY. 178 BAKERSFIELD,CA 93306 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :NOTEST EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-06-10 10:07:22 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3 0.59 22-05-23 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 0.58 22-05-19 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP10 BLEND3 0.58 22-04-26 10:05:48 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3 0.60 22-04-25 10:05:50 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 0.59 22-03-04 10:07:16 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3 0.60 21-12-27 10:02:59 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.91 21-12-26 10:04:07 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.91 21-12-25 10:03:55 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.71 21-12-05 10:05:07 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3 0.56 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-06-11 10:07:00 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3 22-03-05 10:07:15 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3 21-09-07 10:07:55 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 21-08-18 10:08:51 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 21-07-26 10:05:35 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-04-12 10:05:16 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 20-03-11 10:05:46 FLOW PERFORMANCE HOSE BLOCKAGE FP11 BLEND3 19-12-30 10:04:24 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 19-09-11 10:05:38 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 19-01-15 10:01:43 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.91 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-06-13 12:32:17 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-06-13 12:32:17 ISD STARTUP 22-06-13 12:32:14 ISD SHUTDOWN 22-06-13 10:08:03 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-06-13 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-06-12 10:08:20 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-06-12 10:00:10 ESTIMATED ORVRS >> EXPECTED 22-06-11 16:34:44 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED 22-06-11 16:34:38 COLLECTION TEST HH07 GRADE TEST MANUALLY CLEARED 22-06-11 16:34:19 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED