HomeMy WebLinkAbout2022 FMCAppendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10134226 06-29-2022
Jaco #3346 Fastrip #621
805 34th Street Bakersfield 93301
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Ronald Clark
1073967
9482314 05-04-2024
Veeder-Root C27795 08-26-2022
06-29-2022 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Gilbarco EMC 336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 794380-208 UNL 1 STP
L2 794380-420 UNL 1 ANN
L3 794380-208 UNL 2 STP
L4 794380-420 UNL 2 ANN
L5 794380-208 PREM STP
L6 794380-420 PREM ANN
L7 794380-208 DSL STP
L8 794380-420 DSL ANN
L9 794380-208 DISP 1-2
L10 794380-208 DISP 3-4
L11 794380-208 DISP 5-6
L12 794380-208 DISP 7-8
L13 794380-208 E TRANS SUMP
L14 794380-208 W TRANS SUMP
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 UNL 1 FX1V Unleaded 1
T2 UNL 2 FX1V Unleaded 2
T3 PREM FX1V Premium
T4 DSL FX1DV DIESEL
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted. VFFN
PRIC
E
S
I
G
N
PROPERTY LINE
PROPERTY LINE141.50'125'EXISTING BUILDING
W
H
G
W
34TH ST.Q ST.VFSTPL112,000 GALLON87-1 UNLEADED12,000 GALLON87-2 UNLEADED12,000 GALLON91 PREMIUM12,000 GALLONDIESELVFSTPL3STPL5STPL7AL2AL4AL6AL8L9L11L12L10L13L1465874321L12L10DUMPSTER NOPARKINGLEGEND
L1 87-1 STP
L2 87-1 ANNULAR
L3 87-2 STP
L4 87-2 ANNULAR
L5 91 STP
L6 91 ANNULAR
L7 DSL STP
L8 DSL ANNULAR
L9 UDC 1 -2
L10 UDC 3 - 4
L11 UDC 5 - 6
L12 UDC 7 - 8
L13 E. TRANS SUMP
L14 W. TRANS SUMP
87 GAS 2 INCH SINGLE WALLED PIPE
91 GAS 2 INCH SINGLE WALLED PIPE
DIESEL 2 INCH SINGLE WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIP
VAPOR VENT 2 INCH SINGLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
EVACUATION MEETING POINT
AUTOMATIC TANK GAUGE
UST ELECTRICAL PANEL
AIR AND WATER DISPENSER
HAZ-WASTE DRUMS
G
A
P
V
SITE MAP SITE PLAN
C1
TAB:CERS
1"=10'-0"
INCHES012
SHEET SIZE 22 X 34
DATE REVISIONS
DATE:
DRAWN BY:
CHECKED:
APPROVED:
RAC FASTRIP - 3-346 CADFILE:
SHEET NO.3346-MSP
A.P.N.: 002-032-14-00-8
SCALE:
FASTRIP OIL COMPANYCONVENIENCE MARKET FOR:
BAKERSFIELD, CALIFORNIA 93301
JACO HILL
805 34TH ST.
3101 STATE RDBAKERSFIELD, CA 93308
PROJECT OWNER:
DRAWING:
CD
03/25/2021
805 34TH ST.
BAKERSFIELD, CA 93301
Q ST.
34TH ST.
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-03017
CERS ID 10134226
FASTRIP #3346
805 34TH ST.
BAKERSFIELD, CA 93301
03/05/2021 REV.
VICINITY MAP
PROJECT DATA
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10134226 06-29-2022
Jaco #3346 Fastrip #621
805 34th Street Bakersfield 93301
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Ronald Clark
1073967
9482314 05-04-2024
OPW 0187329 08-28-2022
Hydrostatic Spill buckets
06-29-2022 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1 UNL 1
OPW
T2 UNL 2
OPW
T3 PREM
OPW
T4 DIESEL
OPW
34th and Q setup
200
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
JUN 29, 2022 8:54 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 1 6387 49.97 0.0 86.3 5675
2 UNLEADEDED 2 6411 50.11 1.0 86.6 5651
3 PREMIUM 4825 40.22 0.0 84.6 7237
4 DIESEL 8076 60.62 0.8 83.7 3986
I90500
JUN 29, 2022 8:54 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JUN 29, 2022 8:54 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUN 29, 2022 8:54 AM
SHIFT TIME 1 : 6:00 AM
I50202
JUN 29, 2022 8:54 AM
SHIFT TIME 2 : DISABLED
I50203
JUN 29, 2022 8:54 AM
SHIFT TIME 3 : DISABLED
I50204
JUN 29, 2022 8:54 AM
SHIFT TIME 4 : DISABLED
I54600
JUN 29, 2022 8:54 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUN 29, 2022 8:54 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUN 29, 2022 8:54 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUN 29, 2022 8:54 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUN 29, 2022 8:54 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUN 29, 2022 8:54 AM
PRINT TC VOLUMES
ENABLED
I50E00
JUN 29, 2022 8:54 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUN 29, 2022 8:54 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUN 29, 2022 8:54 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUN 29, 2022 8:54 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUN 29, 2022 8:54 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUN 29, 2022 8:54 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUN 29, 2022 8:54 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUN 29, 2022 8:54 AM
TANK CHART SECURITY
DISABLED
I5BD00
JUN 29, 2022 8:54 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JUN 29, 2022 8:54 AM
MASS/DENSITY
DISABLED
I88101
JUN 29, 2022 8:54 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JUN 29, 2022 8:54 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
JUN 29, 2022 8:54 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JUN 29, 2022 8:54 AM
I88105
JUN 29, 2022 8:54 AM
I88106
JUN 29, 2022 8:54 AM
I52000
JUN 29, 2022 8:54 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE JAN 28, 2022 DISABLED
2 ON DATE JAN 28, 2022 DISABLED
3 ON DATE JAN 28, 2022 DISABLED
4 ON DATE JAN 28, 2022 DISABLED
5 ON DATE JAN 28, 2022 DISABLED
6 ON DATE JAN 28, 2022 DISABLED
7 ON DATE JAN 28, 2022 DISABLED
8 ON DATE JAN 28, 2022 DISABLED
I60100
JUN 29, 2022 8:54 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED 1 ON
2 UNLEADEDED 2 ON
3 PREMIUM ON
4 DIESEL ON
I60200
JUN 29, 2022 8:54 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED 1
2 UNLEADEDED 2
3 PREMIUM
4 DIESEL
I60300
JUN 29, 2022 8:54 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1 1
2 UNLEADEDED 2 2
3 PREMIUM 3
4 DIESEL 4
I60900
JUN 29, 2022 8:54 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 1 0.000700
2 UNLEADEDED 2 0.000700
3 PREMIUM 0.000700
4 DIESEL 0.000450
I60700
JUN 29, 2022 8:54 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 95.50
2 UNLEADEDED 2 95.50
3 PREMIUM 95.50
4 DIESEL 95.50
I60A00
JUN 29, 2022 8:54 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1
1 PT 12062 2 UNLEADEDED 2 1 PT 12062 3 PREMIUM
1 PT 12062 4 DIESEL 1 PT 12062
I60400
JUN 29, 2022 8:54 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 12062
2 UNLEADEDED 2 12062
3 PREMIUM 12062
4 DIESEL 12062
I60500
JUN 29, 2022 8:54 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 12062 0 0 0
2 UNLEADEDED 2 12062 0 0 0
3 PREMIUM 12062 0 0 0
4 DIESEL 12062 0 0 0
I60600
JUN 29, 2022 8:54 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 UNLEADEDED 2 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 PREMIUM 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 DIESEL 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUN 29, 2022 8:54 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED 1 NO
2 UNLEADEDED 2 NO
3 PREMIUM NO
4 DIESEL NO
I62F00
JUN 29, 2022 8:54 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 1 4.0 IN.
2 UNLEADEDED 2 4.0 IN.
3 PREMIUM 4.0 IN.
4 DIESEL 4.0 IN.
I62700
JUN 29, 2022 8:54 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 2.0
2 UNLEADEDED 2 2.0
3 PREMIUM 2.0
4 DIESEL 2.0
I64200
JUN 29, 2022 8:54 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED 1 LOW
2 UNLEADEDED 2 LOW
3 PREMIUM LOW
4 DIESEL LOW
I62400
JUN 29, 2022 8:54 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 3.0
2 UNLEADEDED 2 3.0
3 PREMIUM 3.0
4 DIESEL 3.0
I62800
JUN 29, 2022 8:54 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 12062
2 UNLEADEDED 2 12062
3 PREMIUM 12062
4 DIESEL 12062
I62300
JUN 29, 2022 8:54 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 10856
2 UNLEADEDED 2 10856
3 PREMIUM 10856
4 DIESEL 10856
I62200
JUN 29, 2022 8:54 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 11459
2 UNLEADEDED 2 11459
3 PREMIUM 11459
4 DIESEL 11459
I62900
JUN 29, 2022 8:54 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 1809
2 UNLEADEDED 2 1809
3 PREMIUM 1809
4 DIESEL 1809
I62100
JUN 29, 2022 8:54 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 500
2 UNLEADEDED 2 500
3 PREMIUM 500
4 DIESEL 500
I62600
JUN 29, 2022 8:54 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 99
2 UNLEADEDED 2 99
3 PREMIUM 99
4 DIESEL 99
I62500
JUN 29, 2022 8:54 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 99
2 UNLEADEDED 2 99
3 PREMIUM 99
4 DIESEL 99
I60800
JUN 29, 2022 8:54 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 2.50
2 UNLEADEDED 2 0.00
3 PREMIUM 1.40
4 DIESEL 0.20
I60B00
JUN 29, 2022 8:54 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUN 29, 2022 8:54 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 0.00
2 UNLEADEDED 2 0.00
3 PREMIUM 0.00
4 DIESEL 0.00
I61200
JUN 29, 2022 8:54 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED 1 NONE 2
2 UNLEADEDED 2 NONE 1
3 PREMIUM NONE NONE
4 DIESEL NONE NONE
I63600
JUN 29, 2022 8:54 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 120
2 UNLEADEDED 2 120
3 PREMIUM 120
4 DIESEL 120
I62A00
JUN 29, 2022 8:54 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 0
2 UNLEADEDED 2 0
3 PREMIUM 0
4 DIESEL 0
I62C00
JUN 29, 2022 8:54 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED 1 STANDARD
2 UNLEADEDED 2 STANDARD
3 PREMIUM STANDARD
4 DIESEL STANDARD
I62D00
JUN 29, 2022 8:54 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED 1 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
2 UNLEADEDED 2 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
3 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
4 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUN 29, 2022 8:54 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED 1 OFF OFF
2 UNLEADEDED 2 OFF OFF
3 PREMIUM OFF OFF
4 DIESEL OFF OFF
I63000
JUN 29, 2022 8:54 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED 1 OFF
2 UNLEADEDED 2 OFF
3 PREMIUM OFF
4 DIESEL OFF
I63200
JUN 29, 2022 8:54 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED 1 OFF
2 UNLEADEDED 2 OFF
3 PREMIUM OFF
4 DIESEL OFF
I61000
JUN 29, 2022 8:54 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1 1
2 UNLEADEDED 2 1
3 PREMIUM 1
4 DIESEL 1
I63A00
JUN 29, 2022 8:54 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 1 10.00%
2 UNLEADEDED 2 10.00%
3 PREMIUM 10.00%
4 DIESEL 10.00%
I61100
JUN 29, 2022 8:54 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JUL 1, 2009
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
JUN 29, 2022 8:54 AM
CSLD PROBABLITY OF DETECTION
I61400
JUN 29, 2022 8:54 AM
CSLD CLIMATE FACTOR
I61600
JUN 29, 2022 8:54 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED 1 IMMEDIATE
2 UNLEADEDED 2 IMMEDIATE
3 PREMIUM IMMEDIATE
4 DIESEL IMMEDIATE
I61A00
JUN 29, 2022 8:54 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED 1 DISABLED
2 UNLEADEDED 2 DISABLED
3 PREMIUM DISABLED
4 DIESEL DISABLED
I61B00
JUN 29, 2022 8:54 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JUN 29, 2022 8:54 AM
CSLD REPORT ONLY
I62B00
JUN 29, 2022 8:54 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED 1 ??? 0, 0
2 UNLEADEDED 2 ??? 0, 0
3 PREMIUM ??? 0, 0
4 DIESEL ??? 0, 0
I63300
JUN 29, 2022 8:54 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUN 29, 2022 8:54 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 0
2 UNLEADEDED 2 0
3 PREMIUM 0
4 DIESEL 0
I63500
JUN 29, 2022 8:54 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 1
2 UNLEADEDED 2 1
3 PREMIUM 1
4 DIESEL 1
I63900
JUN 29, 2022 8:54 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED 1
END FACTOR: NONE
2 UNLEADEDED 2
END FACTOR: NONE
3 PREMIUM
END FACTOR: NONE
4 DIESEL
END FACTOR: NONE
I78000
JUN 29, 2022 8:54 AM
I77700
JUN 29, 2022 8:54 AM
I77800
JUN 29, 2022 8:54 AM
I78C00
JUN 29, 2022 8:54 AM
I78300
JUN 29, 2022 8:54 AM
I78F00
JUN 29, 2022 8:54 AM
I78700
JUN 29, 2022 8:54 AM
I70200
JUN 29, 2022 8:54 AM
LIQUID LABEL
DEVICE LABEL
1 UNL 1 STP
2 UNL 1 ANN
3 UNL 2 STP
4 UNL 2 ANN
5 PREM STP
6 PREM ANN
7 DSL STP
8 DSL ANN
9 DISP 1-2
10 DISP 3-4
11 DISP 5-6
12 DISP 7-8
13 E TRANS SUMP
14 W TRANS SUMP
15
16
I70300
JUN 29, 2022 8:54 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL 1 STP TRI-STATE (SINGLE FLOAT)
2 UNL 1 ANN TRI-STATE (SINGLE FLOAT)
3 UNL 2 STP TRI-STATE (SINGLE FLOAT)
4 UNL 2 ANN TRI-STATE (SINGLE FLOAT)
5 PREM STP TRI-STATE (SINGLE FLOAT)
6 PREM ANN TRI-STATE (SINGLE FLOAT)
7 DSL STP TRI-STATE (SINGLE FLOAT)
8 DSL ANN TRI-STATE (SINGLE FLOAT)
9 DISP 1-2 TRI-STATE (SINGLE FLOAT)
10 DISP 3-4 TRI-STATE (SINGLE FLOAT)
11 DISP 5-6 TRI-STATE (SINGLE FLOAT)
12 DISP 7-8 TRI-STATE (SINGLE FLOAT)
13 E TRANS SUMP TRI-STATE (SINGLE FLOAT)
14 W TRANS SUMP TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
JUN 29, 2022 8:54 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL 1 STP STP SUMP
2 UNL 1 ANN ANNULAR SPACE
3 UNL 2 STP STP SUMP
4 UNL 2 ANN ANNULAR SPACE
5 PREM STP STP SUMP
6 PREM ANN ANNULAR SPACE
7 DSL STP STP SUMP
8 DSL ANN ANNULAR SPACE
9 DISP 1-2 DISPENSER PAN
10 DISP 3-4 DISPENSER PAN
11 DISP 5-6 DISPENSER PAN
12 DISP 7-8 DISPENSER PAN
13 E TRANS SUMP PIPING SUMP
14 W TRANS SUMP PIPING SUMP
15 OTHER SENSORS
16 OTHER SENSORS
I74200
JUN 29, 2022 8:54 AM
I74300
JUN 29, 2022 8:54 AM
I74400
JUN 29, 2022 8:55 AM
I74700
JUN 29, 2022 8:55 AM
I74800
JUN 29, 2022 8:55 AM
I74900
JUN 29, 2022 8:55 AM
I7BC00
JUN 29, 2022 8:55 AM
I80200
JUN 29, 2022 8:55 AM
I80300
JUN 29, 2022 8:55 AM
I80400
JUN 29, 2022 8:55 AM
I80700
JUN 29, 2022 8:55 AM
RELAY LABEL
DEVICE LABEL
1 UNL 1
2 UNLD 2
3 PREM
4 DIESEL
5 OVERFILL ALARMS
6
7
8
I80900
JUN 29, 2022 8:55 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNL 1 NORMALLY OPEN
2 UNLD 2 NORMALLY OPEN
3 PREM NORMALLY OPEN
4 DIESEL NORMALLY CLOSED
5 OVERFILL ALARMS NORMALLY OPEN
6 NORMALLY OPEN
7 NORMALLY OPEN
8 NORMALLY OPEN
I80B00
JUN 29, 2022 8:55 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNL 1 1
2 UNLD 2 2
3 PREM 3
4 DIESEL 4
5 OVERFILL ALARMS NONE
6 NONE
7 NONE
8 NONE
I80A00
JUN 29, 2022 8:55 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNL 1 PUMP CONTROL OUTPUT
2 UNLD 2 PUMP CONTROL OUTPUT
3 PREM PUMP CONTROL OUTPUT
4 DIESEL STANDARD
5 OVERFILL ALARMS STANDARD
6 STANDARD
7 STANDARD
8 STANDARD
I80C00
JUN 29, 2022 8:55 AM
I80800
JUN 29, 2022 8:55 AM
RELAY SETUP REPORT
R 1:UNL 1
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
IN-TANK ALARMS
T 1:HIGH WATER ALARM
T 1:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 2:UNLD 2
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
IN-TANK ALARMS
T 2:HIGH WATER ALARM
T 2:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 3:PREM
TYPE:
PUMP CONTROL OUTPUT
TANK #: 3
IN-TANK ALARMS
T 3:HIGH WATER ALARM
T 3:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 5:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 5:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 5:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 4:DIESEL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 4
IN-TANK ALARMS
T 3:HIGH WATER ALARM
T 3:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 7:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 7:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 7:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
R 5:OVERFILL ALARMS
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
R 6:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 7:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 8:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
JUN 29, 2022 8:55 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
JUN 29, 2022 8:55 AM
I72300
JUN 29, 2022 8:55 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VP 1-2 VAPOR PRESSURE
02 FM 1-2 AIR FLOW METER
03 FM 3-4 AIR FLOW METER
04 FM 5-6 AIR FLOW METER
05 FM 7-8 AIR FLOW METER
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JUN 29, 2022 8:55 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
JUN 29, 2022 8:55 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JUN 29, 2022 8:55 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
VAPOR PROCESSOR TYPE
NONE
IV4700
JUN 29, 2022 8:55 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
ASSESSMENT TIME
START TIME: 10:09 AM
TIME DELAY MINUTES: 1
IV5200
JUN 29, 2022 8:55 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
ACCEPT HIGH ORVR: YES
IV4A00
JUN 29, 2022 8:55 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 03 BLEND3
02 02 02 01 03 BLEND3
03 03 03 02 03 BLEND3
04 04 04 02 03 BLEND3
05 05 05 03 03 BLEND3
06 06 06 03 03 BLEND3
07 07 07 04 03 BLEND3
08 08 08 04 03 BLEND3
IV4B00
JUN 29, 2022 8:55 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
IV4900
JUN 29, 2022 8:55 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JUN 29, 2022 8:55 AM
ISD VERSION: 01.07
34th and Q alarm history before
I10200
JUN 29, 2022 8:59 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 503758 503817
2 4 PROBE / G.T. 161433 161417
3 INTERSTITIAL BD 201851 201891
4 INTERSTITIAL BD 200531 200607
5 UNUSED 4915838 4774605
6 UNUSED 4916524 4770809
7 UNUSED 4915594 4770855
8 UNUSED 4912981 4775241
9 STP SENSE BOARD 33065 33089
10 RELAY BOARD 15044 15045
11 RELAY BOARD 15089 15113
12 UNUSED 4917790 4773650
13 UNUSED 4914114 4775218
14 UNUSED 4913406 4773218
15 UNUSED 4914490 4772331
16 UNUSED 4912874 4770286
COMM 1 ELEC DISP INT. 101268 101358
COMM 2 RS232 SERIAL BD 15066 15067
COMM 3 RS232 SERIAL BD 14910 14953
COMM 4 UNUSED 4917081 4776195
COMM 5 UNUSED 4912298 4766331
COMM 6 UNUSED 4913937 4771604
I90200
JUN 29, 2022 8:59 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUN 29, 2022 8:59 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
E 1 OTHER COMMUNICATION ALARM CLEAR 6-28-22 9:58AM
E 1 OTHER COMMUNICATION ALARM ALARM 6-28-22 9:22AM
T 1 TANK UNLEADED 1 OVERFILL ALARM CLEAR 6-24-22 5:54AM
T 1 TANK UNLEADED 1 OVERFILL ALARM ALARM 6-24-22 5:46AM
T 1 TANK UNLEADED 1 OVERFILL ALARM CLEAR 6-24-22 5:46AM
T 1 TANK UNLEADED 1 OVERFILL ALARM ALARM 6-24-22 5:44AM
T 2 TANK UNLEADEDED 2 OVERFILL ALARM CLEAR 6-23-22 8:20AM
T 2 TANK UNLEADEDED 2 OVERFILL ALARM ALARM 6-23-22 8:13AM
L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L 6 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L 8 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L 5 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L14 PIPE W TRANS SUMP SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L13 PIPE E TRANS SUMP SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 6-15-22 2:51PM
L 8 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 6-15-22 2:51PM
L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L14 PIPE W TRANS SUMP SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L 6 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L13 PIPE E TRANS SUMP SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L 5 STP SUMP PREM STP SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 6-15-22 2:50PM
L 4 ANNULAR UNL 2 ANN FUEL ALARM CLEAR 6-15-22 2:50PM
L 4 ANNULAR UNL 2 ANN FUEL ALARM ALARM 6-15-22 2:41PM
L 7 STP SUMP DSL STP FUEL ALARM CLEAR 6-15-22 2:30PM
L 7 STP SUMP DSL STP FUEL ALARM ALARM 6-15-22 2:30PM
L 5 STP SUMP PREM STP FUEL ALARM CLEAR 6-15-22 2:30PM
L 5 STP SUMP PREM STP FUEL ALARM ALARM 6-15-22 2:30PM
L 3 STP SUMP UNL 2 STP FUEL ALARM CLEAR 6-15-22 2:29PM
L 3 STP SUMP UNL 2 STP FUEL ALARM ALARM 6-15-22 2:29PM
L 1 STP SUMP UNL 1 STP FUEL ALARM CLEAR 6-15-22 2:29PM
L 1 STP SUMP UNL 1 STP FUEL ALARM ALARM 6-15-22 2:29PM
L 8 ANNULAR DSL ANN FUEL ALARM CLEAR 6-15-22 1:44PM
L 8 ANNULAR DSL ANN FUEL ALARM ALARM 6-15-22 1:44PM
L 6 ANNULAR PREM ANN FUEL ALARM CLEAR 6-15-22 1:43PM
L 6 ANNULAR PREM ANN FUEL ALARM ALARM 6-15-22 1:43PM
I11200
JUN 29, 2022 8:59 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 6-29-22 8:51AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 6-27-22 10:10AM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 6-07-22 5:43PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:48PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:48PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:48PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:47PM
SYSTEM PAPER OUT ALARM 6-07-22 12:47PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:47PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:47PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:47PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:46PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:46PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:46PM
SYSTEM PAPER OUT ALARM 6-07-22 12:46PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:45PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:45PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:45PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:45PM
SYSTEM PAPER OUT ALARM 6-07-22 12:45PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:45PM
SYSTEM PAPER OUT ALARM 6-07-22 12:44PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:44PM
SYSTEM PAPER OUT ALARM 6-07-22 12:44PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:43PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:42PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:42PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:42PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:41PM
SYSTEM PAPER OUT ALARM 6-07-22 12:41PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:41PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:37PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:37PM
SYSTEM PAPER OUT ALARM 6-07-22 12:36PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:36PM
T 4 TANK DIESEL DELIVERY NEEDED ALARM 6-07-22 12:31PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 4:56AM
SYSTEM PAPER OUT CLEAR 6-07-22 4:56AM
SYSTEM PAPER OUT ALARM 6-07-22 4:56AM
SYSTEM PAPER OUT CLEAR 6-07-22 4:56AM
SYSTEM PRINTER ERROR ALARM 6-07-22 4:55AM
SYSTEM PAPER OUT ALARM 6-07-22 4:55AM
SYSTEM PRINTER ERROR CLEAR 6-07-22 3:33AM
SYSTEM PAPER OUT CLEAR 6-07-22 3:33AM
SYSTEM PAPER OUT ALARM 6-07-22 3:33AM
SYSTEM PAPER OUT CLEAR 6-07-22 3:33AM
SYSTEM PAPER OUT ALARM 6-07-22 3:33AM
SYSTEM PAPER OUT CLEAR 6-07-22 3:33AM
SYSTEM PAPER OUT ALARM 6-07-22 3:30AM
SYSTEM PRINTER ERROR ALARM 6-07-22 3:30AM
I20600
JUN 29, 2022 8:59 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
TANK ALARM HISTORY
TANK 1 UNLEADED 1
OVERFILL ALARM JUN 24, 2022 5:46 AM
JUN 24, 2022 5:44 AM
MAY 19, 2022 6:54 PM
HIGH PRODUCT ALARM MAY 16, 2022 6:30 AM
DELIVERY NEEDED FEB 23, 2022 5:16 PM
FEB 2, 2022 5:45 PM
TANK 2 UNLEADEDED 2
OVERFILL ALARM JUN 23, 2022 8:13 AM
JUN 3, 2022 12:20 PM
MAY 13, 2022 1:57 PM
DELIVERY NEEDED FEB 23, 2022 4:47 PM
FEB 2, 2022 5:23 PM
TANK 3 PREMIUM
TANK 4 DIESEL
DELIVERY NEEDED JUN 7, 2022 12:31 PM
JAN 31, 2022 4:51 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUN 29, 2022 8:59 AM
I30200
JUN 29, 2022 8:59 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL 1 STP
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 2:29 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
2 UNL 1 ANN
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 1:42 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
3 UNL 2 STP
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 2:29 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
4 UNL 2 ANN
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 2:41 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
5 PREM STP
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 2:30 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
6 PREM ANN
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 1:43 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
7 DSL STP
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 2:30 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
8 DSL ANN
JUN 15, 2022 2:51 PM SENSOR OUT ALARM
JUN 15, 2022 1:44 PM FUEL ALARM
JAN 28, 2022 5:08 PM SENSOR OUT ALARM
9 DISP 1-2
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 1:32 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
10 DISP 3-4
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 1:35 PM FUEL ALARM
JAN 28, 2022 5:08 PM SENSOR OUT ALARM
11 DISP 5-6
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 1:36 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
12 DISP 7-8
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 1:37 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
13 E TRANS SUMP
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 1:40 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
14 W TRANS SUMP
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
JUN 15, 2022 1:38 PM FUEL ALARM
JAN 28, 2022 5:07 PM SENSOR OUT ALARM
I31600
JUN 29, 2022 8:59 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP 1-2
2 FM 1-2
3 FM 3-4
JAN 28, 2022 12:38 PM COMMUNICATION ALARM
4 FM 5-6
JAN 28, 2022 12:38 PM COMMUNICATION ALARM
5 FM 7-8
JAN 28, 2022 12:38 PM COMMUNICATION ALARM
I40200
JUN 29, 2022 8:59 AM
I40300
JUN 29, 2022 8:59 AM
I34200
JUN 29, 2022 8:59 AM
I34700
JUN 29, 2022 8:59 AM
IV0100
JUN 29, 2022 8:59 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-06-28 10:10:16 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
22-06-27 10:10:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
22-05-24 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.14
22-05-23 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.59
22-05-22 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.59
22-05-21 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.59
22-05-20 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.46
22-05-05 10:10:09 A/L RATIO DEGRADATION FP 2 BLEND3 0.76
22-05-04 10:10:09 A/L RATIO DEGRADATION FP 2 BLEND3 0.76
22-05-03 10:10:12 A/L RATIO DEGRADATION FP 2 BLEND3 0.76
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-04-27 10:10:09 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
22-01-27 10:10:10 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
22-01-26 10:10:10 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-01-26 10:10:10 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-01-26 10:10:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-06-29 08:51:35 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED
22-06-16 10:11:27 READINESS ISD:PP EVR:PP ISD & EVR READY
22-06-15 14:56:35 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-06-15 14:56:35 ISD STARTUP
22-06-15 14:56:32 ISD SHUTDOWN
22-05-05 15:48:30 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
22-04-27 12:09:34 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
22-04-27 10:45:46 PUMPS MANUALLY RE-ENABLED
22-04-27 10:10:09 A/L RATIO GROSS DEGRADATION DISABLED FP 02 BLEND3
22-04-07 12:03:36 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
34th and Q alarm history after
JUN 29, 2022 10:48 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 503758 503342
2 4 PROBE / G.T. 161433 161312
3 INTERSTITIAL BD 201851 201739
4 INTERSTITIAL BD 200531 200361
5 UNUSED 4915838 4805826
6 UNUSED 4916524 4801473
7 UNUSED 4915594 4801813
8 UNUSED 4912981 4799229
9 STP SENSE BOARD 33065 33104
10 RELAY BOARD 15044 15037
11 RELAY BOARD 15089 15105
12 UNUSED 4917790 4804400
13 UNUSED 4914114 4798596
14 UNUSED 4913406 4799004
15 UNUSED 4914490 4802155
16 UNUSED 4912874 4797349
COMM 1 ELEC DISP INT. 101268 101212
COMM 2 RS232 SERIAL BD 15066 15060
COMM 3 RS232 SERIAL BD 14910 14923
COMM 4 UNUSED 4917081 4800749
COMM 5 UNUSED 4912298 4801747
COMM 6 UNUSED 4913937 4802586
I90200
JUN 29, 2022 10:48 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUN 29, 2022 10:48 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 8 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L 6 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L 5 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L14 PIPE W TRANS SUMP SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L13 PIPE E TRANS SUMP SENSOR OUT ALARM CLEAR 6-29-22 9:50AM
L 8 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L14 PIPE W TRANS SUMP SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L13 PIPE E TRANS SUMP SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L 3 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L 2 ANNULAR UNL 1 ANN SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L 6 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L 5 STP SUMP PREM STP SENSOR OUT ALARM ALARM 6-29-22 9:49AM
L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 6-29-22 9:45AM
L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 6-29-22 9:45AM
L14 PIPE W TRANS SUMP FUEL ALARM CLEAR 6-29-22 9:44AM
L14 PIPE W TRANS SUMP FUEL ALARM ALARM 6-29-22 9:44AM
L13 PIPE E TRANS SUMP FUEL ALARM CLEAR 6-29-22 9:43AM
L13 PIPE E TRANS SUMP FUEL ALARM ALARM 6-29-22 9:43AM
L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 6-29-22 9:43AM
L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 6-29-22 9:43AM
L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 6-29-22 9:42AM
L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 6-29-22 9:42AM
L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 6-29-22 9:41AM
L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 6-29-22 9:41AM
L 8 ANNULAR DSL ANN FUEL ALARM CLEAR 6-29-22 9:40AM
L 8 ANNULAR DSL ANN FUEL ALARM ALARM 6-29-22 9:40AM
L 6 ANNULAR PREM ANN FUEL ALARM CLEAR 6-29-22 9:39AM
L 6 ANNULAR PREM ANN FUEL ALARM ALARM 6-29-22 9:39AM
L 4 ANNULAR UNL 2 ANN FUEL ALARM CLEAR 6-29-22 9:38AM
L 4 ANNULAR UNL 2 ANN FUEL ALARM ALARM 6-29-22 9:38AM
L 2 ANNULAR UNL 1 ANN FUEL ALARM CLEAR 6-29-22 9:38AM
L 2 ANNULAR UNL 1 ANN FUEL ALARM ALARM 6-29-22 9:37AM
L 7 STP SUMP DSL STP FUEL ALARM CLEAR 6-29-22 9:37AM
L 7 STP SUMP DSL STP FUEL ALARM ALARM 6-29-22 9:36AM
I11200
JUN 29, 2022 10:48 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 6-29-22 8:51AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 6-27-22 10:10AM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 6-07-22 5:43PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:48PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:48PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:48PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:47PM
SYSTEM PAPER OUT ALARM 6-07-22 12:47PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:47PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:47PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:47PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:46PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:46PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:46PM
SYSTEM PAPER OUT ALARM 6-07-22 12:46PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:45PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:45PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:45PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:45PM
SYSTEM PAPER OUT ALARM 6-07-22 12:45PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:45PM
SYSTEM PAPER OUT ALARM 6-07-22 12:44PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:44PM
SYSTEM PAPER OUT ALARM 6-07-22 12:44PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:43PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:42PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:42PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:42PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:41PM
SYSTEM PAPER OUT ALARM 6-07-22 12:41PM
SYSTEM PAPER OUT CLEAR 6-07-22 12:41PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:37PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 12:37PM
SYSTEM PAPER OUT ALARM 6-07-22 12:36PM
SYSTEM PRINTER ERROR ALARM 6-07-22 12:36PM
T 4 TANK DIESEL DELIVERY NEEDED ALARM 6-07-22 12:31PM
SYSTEM PRINTER ERROR CLEAR 6-07-22 4:56AM
SYSTEM PAPER OUT CLEAR 6-07-22 4:56AM
SYSTEM PAPER OUT ALARM 6-07-22 4:56AM
SYSTEM PAPER OUT CLEAR 6-07-22 4:56AM
SYSTEM PRINTER ERROR ALARM 6-07-22 4:55AM
SYSTEM PAPER OUT ALARM 6-07-22 4:55AM
SYSTEM PRINTER ERROR CLEAR 6-07-22 3:33AM
SYSTEM PAPER OUT CLEAR 6-07-22 3:33AM
SYSTEM PAPER OUT ALARM 6-07-22 3:33AM
SYSTEM PAPER OUT CLEAR 6-07-22 3:33AM
SYSTEM PAPER OUT ALARM 6-07-22 3:33AM
SYSTEM PAPER OUT CLEAR 6-07-22 3:33AM
SYSTEM PAPER OUT ALARM 6-07-22 3:30AM
SYSTEM PRINTER ERROR ALARM 6-07-22 3:30AM
I20600
JUN 29, 2022 10:49 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
TANK ALARM HISTORY
TANK 1 UNLEADED 1
OVERFILL ALARM JUN 24, 2022 5:46 AM
JUN 24, 2022 5:44 AM
MAY 19, 2022 6:54 PM
HIGH PRODUCT ALARM MAY 16, 2022 6:30 AM
DELIVERY NEEDED FEB 23, 2022 5:16 PM
FEB 2, 2022 5:45 PM
TANK 2 UNLEADEDED 2
OVERFILL ALARM JUN 23, 2022 8:13 AM
JUN 3, 2022 12:20 PM
MAY 13, 2022 1:57 PM
DELIVERY NEEDED FEB 23, 2022 4:47 PM
FEB 2, 2022 5:23 PM
TANK 3 PREMIUM
TANK 4 DIESEL
DELIVERY NEEDED JUN 7, 2022 12:31 PM
JAN 31, 2022 4:51 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUN 29, 2022 10:49 AM
I30200
JUN 29, 2022 10:49 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL 1 STP
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:32 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
2 UNL 1 ANN
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:37 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
3 UNL 2 STP
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:35 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
4 UNL 2 ANN
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:38 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
5 PREM STP
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:36 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
6 PREM ANN
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:39 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
7 DSL STP
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:36 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
8 DSL ANN
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:40 AM FUEL ALARM
JUN 15, 2022 2:51 PM SENSOR OUT ALARM
9 DISP 1-2
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:41 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
10 DISP 3-4
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:42 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
11 DISP 5-6
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:45 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
12 DISP 7-8
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:43 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
13 E TRANS SUMP
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:43 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
14 W TRANS SUMP
JUN 29, 2022 9:49 AM SENSOR OUT ALARM
JUN 29, 2022 9:44 AM FUEL ALARM
JUN 15, 2022 2:50 PM SENSOR OUT ALARM
I31600
JUN 29, 2022 10:49 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP 1-2
2 FM 1-2
3 FM 3-4
JAN 28, 2022 12:38 PM COMMUNICATION ALARM
4 FM 5-6
JAN 28, 2022 12:38 PM COMMUNICATION ALARM
5 FM 7-8
JAN 28, 2022 12:38 PM COMMUNICATION ALARM
I40200
JUN 29, 2022 10:49 AM
I40300
JUN 29, 2022 10:49 AM
I34200
JUN 29, 2022 10:49 AM
I34700
JUN 29, 2022 10:49 AM
IV0100
JUN 29, 2022 10:49 AM
FASTRIP 346
805 34TH
BAKERSFIELD CA
661-325-0110
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-06-28 10:10:16 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
22-06-27 10:10:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
22-05-24 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.14
22-05-23 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.59
22-05-22 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.59
22-05-21 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.59
22-05-20 10:10:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.46
22-05-05 10:10:09 A/L RATIO DEGRADATION FP 2 BLEND3 0.76
22-05-04 10:10:09 A/L RATIO DEGRADATION FP 2 BLEND3 0.76
22-05-03 10:10:12 A/L RATIO DEGRADATION FP 2 BLEND3 0.76
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-04-27 10:10:09 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
22-01-27 10:10:10 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
22-01-27 10:10:09 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
22-01-26 10:10:10 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-01-26 10:10:10 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-01-26 10:10:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-06-29 10:10:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING
22-06-29 09:52:52 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-06-29 09:52:52 ISD STARTUP
22-06-29 09:52:46 ISD SHUTDOWN
22-06-29 08:51:35 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED
22-06-16 10:11:27 READINESS ISD:PP EVR:PP ISD & EVR READY
22-06-15 14:56:35 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-06-15 14:56:35 ISD STARTUP
22-06-15 14:56:32 ISD SHUTDOWN
22-05-05 15:48:30 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED