HomeMy WebLinkAboutMcCutchen Outflow Installation2022.05 McCutchen Outflow
East of Mc Cutchen Rd & Gosford Rd
MH on north shoulder of road, north of
lift station
X Install Date: 5/27/2022
Access:System Type:
StormSanitary
Map
Technology
Flow Meter
Meter Depth: 66"
MH Coordinates: 35.281693, -119.090229
Moderate open channel hydraulics
Avg Velocity Avg Measured Level Multiplier
O2 H2S CO LEL
20.9 0 0 0
Notes
No laterals; monitored upstream line as it
provided best hydraulics during inspection.
Traffic Safety
Used cones to delineate work zone.
Land Use
Residential Commercial Industrial Trunk
X
East
Manhole Depth
60"
141"
Round
60"/60"
Good
Concrete
None observed
Passed
0.4 2-D
74.5"
14.5"
Upstream
Flow Heading
Sensor Direction
Sensor Dist. to Crown
Sensor Offset
Velocity Profile Data
Velocity Profile Taken
Silt
Manhole Material
Pipe Condition
Pipe Shape
Inner Pipe Size (In/Out)
Monitored Pipe Size
McIntosh & Associates
Bakersfield, CA 93313
MH # unknown
Site Report
Confidential Proprietary Information
6/26/2022
Sewer Plan
2.5 fps 15.5" 1.0
Gas
2022.05 McCutchen Outflow
East of Mc Cutchen Rd & Gosford
Rd
Bakersfield, CA 93313
Meter Site Document
Manhole Before Install
Installed
Site
Installation Process
Monitored Manhole
Temporary Flow Study
McIntosh & Associates
2022.05 McCutchen Outflow
Utility Systems, Science and Software
Santa Ana, CA 92705
601 N. Parkcenter Dr, Suite 209
Meter Start Date From 5/27/2022
Meter Stop Date To 6/21/2022
El Cajon, CA 92021
9314 Bond Av, Suite A
Velocity (fps) Level (in) Flow (mgd)
Average 2.538 15.507 6.343
Maximum 4.670 64.940 17.392
Minimum 0.330 8.140 2.501
Pipe Size 60.000
Estimated Capacity (mgd) Not Calculated
Capacity Used Not Calculated
Sensor Type Hach - Flodar