HomeMy WebLinkAboutFMC 2022Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10137943 07-25-2022
Jaco #3367 Fastrip #640 (East)
8001 White Lane Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Ronald Clark
1073967
9482314 05-04-2024
Veeder-Root C27795 08-26-2022
07-25-2022 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder-Root TLS-350 336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 794380-420 UNL ANN
L2 794380-208 UNL STP
L3 794380-208 UNL FILL
L5 794380-208 UNL 2 STP
L6 794380-304 UNL 2 STP ANN
L7 794380-208 UNL 2 FILL
L8 794380-304 UNL 2 ANN FILL
L9 794380-303 UNL 2 ANN
L10 794380-420 PREM ANN
L11 794380-208 PREM STP
L12 794380-208 PREM FILL
L13 794380-420 DSL ANN
L14 794380-208 DSL STP
L15 794380-208 DSL FILL
L16 794280-208 DISP 13-14
L17 794380-208 DISP 15-16
L18 794380-208 DISP 17-18
L19 794380-208 DISP 19-20
L20 794380-208 DISP 21-22
L21 794380-208 DISP 23-24
L22 794380-208 VENTBOX
S1 330020-463 UNL 2 LINE
S2 330020-463 UNL 2 VENT
S3 330020-463 VAPOR
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 UNL FX1V Unleaded
T2 PREM FX1V Premium
T3 DSL FX1DV Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
NO
P
A
R
K
I
N
G
N
O
P
A
R
K
I
N
G
EXISTING BUILDING
L13
L14
L15L16
L17
L18
L12STP
L9STP
L6STP
L3STP
L10
L7
L4
L1
L11
L8
L5
L2
87-2 UNLEADED
12,000 GALLON87-1 UNLEADED
12,000 GALLON DIESEL12,000 GALLON
1/2
43
65
910
78
12/11
#3-366
#3-367
N
91 PREMIUM12,000 GALLON
V F
87-1 UNLEADED12,000 GALLON
87-2 UNLEADED12,000 GALLON91 PREMIUM12,000 GALLON
DIESEL12,000 GALLON
L5STP
L2STP
L11STP
L14STP
AL6
L1
L10
L13
L7/L8
L3
L12
L15
L9
L18
L17
L16L19
L20
L21
18/17
1516
1314
2122
1920
25/24
L22
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
H
W
W
H
PRICE SIGN
PR
I
C
E
S
I
G
N
DIESEL PRICE SIGN
#367
#366
NO P
A
R
K
I
N
G
ACCESS RAMPS ACCESSRAMP
D
U
M
P
S
T
E
R
G
A
A
A
V F
V F
F
A A
A
A
A
F
F
F
F
V
V
V
366 LEGEND
L1 87-1 ANNULAR
L2 87-1 FILL
L3 87-1 STP
L4 87-2 ANNULAR
L5 87-2 FILL
L6 87-2 STP
L7 91 ANNULAR
L8 91 FILL
L9 91 STP
L10 DSL ANNULAR
L11 DSL FILL
L12 DSL STP
L13 UDC 1 - 2
L14 UDC 3 - 4
L15 UDC 5 - 6
L16 UDC 7 - 8
L17 UDC 9 - 10
L18 UDC 11 -12
367 LEGEND
L1 87-1 ANNULAR
L2 87-1 STP ANNULAR AND SUMP SENSOR 2-TO-1
L3 87-1 FILL
L5 87-2 STP
L6 87- 2 STP ANNULAR
L7 87-2 FILL
L8 87-2 ANNULAR FILL
L9 87-2 ANNULAR
L10 91 ANNULAR
L11 91 STP
L12 91 FILL
L13 DSL ANNULAR
L14 DSL STP
L15 DSL FILL
L16 UDC 13 - 14
L17 UDC 15 - 16
L18 UDC 17 - 18
L19 UDC 19 -20
L20 UDC 21 -22
L21 UDC 23 - 24
L22 VENT BOX ANNULAR AND SUMP SENSOR 2-TO-1
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3/2 INCH DOUBLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
S1: 87-2 UNLEADED VENT LINE
S2: PRODUCT SIPHON LINE AND VACUUM CHASE
S3: VAPOR RETURN LINE
EMERGENCY SHUT-OFF
OVERFILL ALARM
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
FIRE EXTINGUISHER
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
WH
A
F
V
SITE MAP
DATE REVISIONS
DATE:
DRAWN BY:
CHECKED:
APPROVED:
RAC CADFILE:
SHEET NO.
A.P.N.:385-013-21-4
SCALE:
CONVENIENCE MARKET FOR:
3101 STATE RDBAKERSFIELD, CA 93308
PROJECT OWNER:
DRAWING:
CD
FASTRIPS - 3-366-3-367 3366-MSP
FASTRIP FOOD STORE
BAKERSFIELD, CALIFORNIA 933098001 WHITE LN.
JACO HILL
SITE PLAN
C1
TAB:CERS
1"=15'-0"
INCHES012
SHEET SIZE 22 X 34
01/07/2022
8001 WHITE LN.
BAKERSFIELD, CA 93309
G
O
S
F
O
R
D
R
D
.
WHITE LN.
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-097250
CERS ID 10137946
FASTRIPS 3-366 / 3-367
8001 WHITE LN.
BAKERSFIELD, CA 93309
02/12/2021 REV.
VICINITY MAP
PROJECT DATA
APPENDIX C-10
SH
E
A
R
V
A
L
V
E
O
P
E
R
A
T
I
O
N
I
N
S
P
E
C
T
I
O
N
)D
F
L
O
L
W
\
1
D
P
H
2Z
Q
H
U
$G
G
U
H
V
V
$G
G
U
H
V
V
&L
W
\
6
W
D
W
H
=
L
S
&
R
G
H
&L
W
\
6
W
D
W
H
=
L
S
&
R
G
H
)D
F
L
O
L
W
\
,
'
3K
R
Q
H
7H
V
W
L
Q
J
&
R
P
S
D
Q
\
3K
R
Q
H
7K
L
V
G
D
W
D
V
K
H
H
W
L
V
I
R
U
L
Q
V
S
H
F
W
L
Q
J
V
K
H
D
U
Y
D
O
Y
H
V
O
R
F
D
W
H
G
L
Q
V
L
G
H
G
LV
S
H
Q
V
H
U
V
6
H
H
3
(
,
5
3
6
H
F
W
L
R
Q
I
R
U
W
K
H
L
Q
V
S
H
F
W
L
R
Q
S
U
R
F
H
G
XU
H
3U
R
G
X
F
W
*
U
D
G
H
'L
V
S
H
Q
V
H
U
,
'
6K
H
D
U
9
D
O
Y
H
7
\
S
H
3
U
R
G
X
F
W
9
D
S
R
U
,
V
W
K
H
V
K
H
D
U
Y
D
O
Y
H
U
L
J
L
G
O
\
DQ
F
K
R
U
H
G
W
R
W
K
H
G
L
V
S
H
Q
V
H
U
E
R
[
IU
D
P
H
R
U
G
L
V
S
H
Q
V
H
U
L
V
O
D
Q
G
"
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<HV1R <HV1R
,
V
W
K
H
V
K
H
D
U
V
H
F
W
L
R
Q
S
R
V
L
WL
R
Q
H
G
E
H
W
Z
H
H
Q
ó
L
Q
F
K
D
E
R
Y
H
RU
E
H
O
R
Z
W
K
H
W
R
S
V
X
U
I
D
F
H
R
I
W
K
H
GL
V
S
H
Q
V
H
U
L
V
O
D
Q
G
"
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<HV1R <HV1R
,
V
W
K
H
O
H
Y
H
U
D
U
P
I
U
H
H
W
R
P
R
Y
H
"
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<HV1R 1$<HV1R 1$
'
R
H
V
W
K
H
O
H
Y
H
U
D
U
P
V
Q
D
S
V
K
X
W
WK
H
S
R
S
S
H
W
Y
D
O
Y
H
"
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<HV1R 1$<HV1R 1$
&
D
Q
D
Q
\
S
U
R
G
X
F
W
E
H
G
L
V
S
H
Q
V
H
G
ZK
H
Q
W
K
H
S
U
R
G
X
F
W
V
K
H
D
U
Y
D
O
Y
H
L
V
FO
R
V
H
G
"
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<HV1R 1$<HV1R 1$
$
´
1
R
µ
W
R
/
L
Q
H
V
R
U
D
´
<
H
V
µ
I
R
U
/
L
Q
H
L
Q
G
L
F
D
W
H
V
D
W
H
V
W
I
D
L
O
XU
H
Te
s
t
R
e
s
u
l
t
s
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3DVV)DLO3DVV)DLO
Co
m
m
e
n
t
s
:
7H
V
W
H
U
·
V
1
D PH
BB
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
7H
V
W
H
U
·
V
6
L
J
Q
D
W
X
U
H
BB
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
1Z
H
V
W
F
R
/
/
&
Ja
c
o
#
3
3
6
7
F
a
s
t
r
i
p
#
6
4
0
(
E
a
s
t
)
80
0
1
W
h
i
t
e
L
a
n
e
Ba
k
e
r
s
f
i
e
l
d
10
1
3
7
9
4
3
13
-
1
4
15
-
1
6
17
-
1
8
87
91
87
91
87
91
DS
L
87
91
13
-
1
4
15
-
1
6
17
-
1
8
17
-
1
8
19
-
2
0
19-20
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Product
Ro
n
a
l
d
C
l
a
r
k
APPENDIX C-10
7K
L
V
G
D
W
D
V
K
H
H
W
L
V
I
R
U
L
Q
V
S
H
F
W
L
Q
J
V
K
H
D
U
Y
D
O
Y
H
V
O
R
F
D
W
H
G
L
Q
V
L
G
H
G
LV
S
H
Q
V
H
U
V
6
H
H
3
(
,
5
3
6
H
F
W
L
R
Q
I
R
U
W
K
H
L
Q
V
S
H
F
W
L
R
Q
S
U
R
F
H
G
XU
H
3U
R
G
X
F
W
*
U
D
G
H
'L
V
S
H
Q
V
H
U
,
'
6K
H
D
U
9
D
O
Y
H
7
\
S
H
3
U
R
G
X
F
W
9
D
S
R
U
,
V
W
K
H
V
K
H
D
U
Y
D
O
Y
H
U
L
J
L
G
O
\
DQ
F
K
R
U
H
G
W
R
W
K
H
G
L
V
S
H
Q
V
H
U
E
R
[
IU
D
P
H
R
U
G
L
V
S
H
Q
V
H
U
L
V
O
D
Q
G
"
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<HV1R <HV1R
,
V
W
K
H
V
K
H
D
U
V
H
F
W
L
R
Q
S
R
V
L
WL
R
Q
H
G
E
H
W
Z
H
H
Q
ó
L
Q
F
K
D
E
R
Y
H
RU
E
H
O
R
Z
W
K
H
W
R
S
V
X
U
I
D
F
H
R
I
W
K
H
GL
V
S
H
Q
V
H
U
L
V
O
D
Q
G
"
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<HV1R <HV1R
,
V
W
K
H
O
H
Y
H
U
D
U
P
I
U
H
H
W
R
P
R
Y
H
"
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<HV1R 1$<HV1R 1$
'
R
H
V
W
K
H
O
H
Y
H
U
D
U
P
V
Q
D
S
V
K
X
W
WK
H
S
R
S
S
H
W
Y
D
O
Y
H
"
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<HV1R 1$<HV1R 1$
&
D
Q
D
Q
\
S
U
R
G
X
F
W
E
H
G
L
V
S
H
Q
V
H
G
ZK
H
Q
W
K
H
S
U
R
G
X
F
W
V
K
H
D
U
Y
D
O
Y
H
L
V
FO
R
V
H
G
"
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<HV1R 1$<HV1R 1$
$
´
1
R
µ
W
R
/
L
Q
H
V
R
U
D
´
<
H
V
µ
I
R
U
/
L
Q
H
L
Q
G
L
F
D
W
H
V
D
W
H
V
W
I
D
L
O
XU
H
Te
s
t
R
e
s
u
l
t
s
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3DVV)DLO3DVV)DLO
Co
m
m
e
n
t
s
:
7H
V
W
H
U
·
V
1
D PH
BB
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
7H
V
W
H
U
·
V
6
L
J
Q
D
W
X
U
H
BB
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
DS
L
23
-
2
4
Pr
o
d
u
c
t
Pr
o
d
u
c
t
23
-
2
4
91
87 23
-
2
4
Pr
o
d
u
c
t
Pr
o
d
u
c
t
21
-
2
2
2
91
87 21
-
2
2
Pr
o
d
u
c
t
Ro
n
a
l
d
C
l
a
r
k
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10137943 07-25-2022
Jaco #3367 Fastrip #640 (East)
8001 White Lane Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Ronald Clark
1073967
9482314 05-04-2024
OPW 0187329 08-28-2022
Hydrostatic Spill buckets
07-25-2022 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1 UNL
OPW
T2 PREM
OPW
T3 DSL
OPW
T4 UNL 2
OPW
Jaco 367 setup
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
JUL 25, 2022 11:06 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 7826 68.87 0.9 88.2 4242
2 UNLEADED 2 7178 54.32 0.9 88.5 4504
3 PREMIUM 6415 59.04 0.0 89.9 5585
4 DIESEL 3771 39.41 0.0 85.6 8229
I90500
JUL 25, 2022 11:06 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JUL 25, 2022 11:06 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUL 25, 2022 11:06 AM
SHIFT TIME 1 : 6:00 AM
I50202
JUL 25, 2022 11:06 AM
SHIFT TIME 2 : DISABLED
I50203
JUL 25, 2022 11:06 AM
SHIFT TIME 3 : DISABLED
I50204
JUL 25, 2022 11:06 AM
SHIFT TIME 4 : DISABLED
I54600
JUL 25, 2022 11:06 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUL 25, 2022 11:06 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUL 25, 2022 11:06 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUL 25, 2022 11:06 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUL 25, 2022 11:06 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUL 25, 2022 11:06 AM
PRINT TC VOLUMES
ENABLED
I50E00
JUL 25, 2022 11:06 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUL 25, 2022 11:06 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUL 25, 2022 11:06 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUL 25, 2022 11:06 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUL 25, 2022 11:06 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUL 25, 2022 11:06 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUL 25, 2022 11:06 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUL 25, 2022 11:06 AM
TANK CHART SECURITY
DISABLED
I5BD00
JUL 25, 2022 11:06 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JUL 25, 2022 11:06 AM
MASS/DENSITY
DISABLED
I88101
JUL 25, 2022 11:06 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JUL 25, 2022 11:06 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
JUL 25, 2022 11:06 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JUL 25, 2022 11:06 AM
I88105
JUL 25, 2022 11:06 AM
I88106
JUL 25, 2022 11:06 AM
I52000
JUL 25, 2022 11:06 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE SEP 8, 2011 DISABLED
2 ON DATE SEP 8, 2011 DISABLED
3 ON DATE SEP 8, 2011 DISABLED
4 ON DATE SEP 8, 2011 DISABLED
5 ON DATE SEP 8, 2011 DISABLED
6 ON DATE SEP 8, 2011 DISABLED
7 ON DATE SEP 8, 2011 DISABLED
8 ON DATE SEP 8, 2011 DISABLED
I60100
JUL 25, 2022 11:06 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 UNLEADED 2 ON
3 PREMIUM ON
4 DIESEL ON
I60200
JUL 25, 2022 11:06 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 UNLEADED 2
3 PREMIUM
4 DIESEL
I60300
JUL 25, 2022 11:06 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 UNLEADED 2 2
3 PREMIUM 3
4 DIESEL 4
I60900
JUL 25, 2022 11:06 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 UNLEADED 2 0.000700
3 PREMIUM 0.000700
4 DIESEL 0.000450
I60700
JUL 25, 2022 11:06 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 111.50
2 UNLEADED 2 92.00
3 PREMIUM 112.00
4 DIESEL 112.00
I60A00
JUL 25, 2022 11:06 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
1 PT 12068 2 UNLEADED 2 1 PT 11682 3 PREMIUM
1 PT 12000 4 DIESEL 1 PT 12000
I60400
JUL 25, 2022 11:06 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12068
2 UNLEADED 2 11682
3 PREMIUM 12000
4 DIESEL 12000
I60500
JUL 25, 2022 11:06 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12068 0 0 0
2 UNLEADED 2 11682 0 0 0
3 PREMIUM 12000 0 0 0
4 DIESEL 12000 0 0 0
I60600
JUL 25, 2022 11:06 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12068 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 UNLEADED 2 11682 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 PREMIUM 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 DIESEL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUL 25, 2022 11:06 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 UNLEADED 2 NO
3 PREMIUM NO
4 DIESEL NO
I62F00
JUL 25, 2022 11:06 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN.
2 UNLEADED 2 4.0 IN.
3 PREMIUM 3.0 IN.
4 DIESEL 4.0 IN.
I62700
JUL 25, 2022 11:06 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 UNLEADED 2 2.0
3 PREMIUM 2.0
4 DIESEL 2.0
I64200
JUL 25, 2022 11:06 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 UNLEADED 2 LOW
3 PREMIUM LOW
4 DIESEL LOW
I62400
JUL 25, 2022 11:07 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 UNLEADED 2 3.0
3 PREMIUM 3.0
4 DIESEL 3.0
I62800
JUL 25, 2022 11:07 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12068
2 UNLEADED 2 11682
3 PREMIUM 12000
4 DIESEL 12000
I62300
JUL 25, 2022 11:07 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10861
2 UNLEADED 2 10514
3 PREMIUM 10800
4 DIESEL 10800
I62200
JUL 25, 2022 11:07 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11465
2 UNLEADED 2 11098
3 PREMIUM 11400
4 DIESEL 11400
I62900
JUL 25, 2022 11:07 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1200
2 UNLEADED 2 1200
3 PREMIUM 1200
4 DIESEL 1200
I62100
JUL 25, 2022 11:07 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1200
2 UNLEADED 2 1200
3 PREMIUM 1200
4 DIESEL 1200
I62600
JUL 25, 2022 11:07 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 UNLEADED 2 99
3 PREMIUM 99
4 DIESEL 99
I62500
JUL 25, 2022 11:07 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 UNLEADED 2 99
3 PREMIUM 99
4 DIESEL 99
I60800
JUL 25, 2022 11:07 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED -3.25
2 UNLEADED 2 -4.50
3 PREMIUM 0.00
4 DIESEL 0.00
I60B00
JUL 25, 2022 11:07 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUL 25, 2022 11:07 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 UNLEADED 2 0.00
3 PREMIUM 0.00
4 DIESEL 0.00
I61200
JUL 25, 2022 11:07 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 UNLEADED 2 NONE NONE
3 PREMIUM NONE NONE
4 DIESEL NONE NONE
I63600
JUL 25, 2022 11:07 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 UNLEADED 2 120
3 PREMIUM 120
4 DIESEL 120
I62A00
JUL 25, 2022 11:07 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 UNLEADED 2 120
3 PREMIUM 120
4 DIESEL 120
I62C00
JUL 25, 2022 11:07 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 UNLEADED 2 STANDARD
3 PREMIUM STANDARD
4 DIESEL STANDARD
I62D00
JUL 25, 2022 11:07 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 UNLEADED 2 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUL 25, 2022 11:07 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 UNLEADED 2 OFF OFF
3 PREMIUM OFF OFF
4 DIESEL OFF OFF
I63000
JUL 25, 2022 11:07 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 UNLEADED 2 OFF
3 PREMIUM OFF
4 DIESEL OFF
I63200
JUL 25, 2022 11:07 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 UNLEADED 2 OFF
3 PREMIUM OFF
4 DIESEL OFF
I61000
JUL 25, 2022 11:07 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 UNLEADED 2 1
3 PREMIUM 1
4 DIESEL 1
I63A00
JUL 25, 2022 11:07 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 UNLEADED 2 10.00%
3 PREMIUM 10.00%
4 DIESEL 10.00%
I61100
JUL 25, 2022 11:07 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
OCT 9, 2008
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
JUL 25, 2022 11:07 AM
CSLD PROBABLITY OF DETECTION
I61400
JUL 25, 2022 11:07 AM
CSLD CLIMATE FACTOR
I61600
JUL 25, 2022 11:07 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 UNLEADED 2 IMMEDIATE
3 PREMIUM IMMEDIATE
4 DIESEL IMMEDIATE
I61A00
JUL 25, 2022 11:07 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED
2 UNLEADED 2 DISABLED
3 PREMIUM DISABLED
4 DIESEL DISABLED
I61B00
JUL 25, 2022 11:07 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JUL 25, 2022 11:07 AM
CSLD REPORT ONLY
I62B00
JUL 25, 2022 11:07 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 UNLEADED 2 ??? 0, 0
3 PREMIUM ??? 0, 0
4 DIESEL ??? 0, 0
I63300
JUL 25, 2022 11:07 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUL 25, 2022 11:07 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 UNLEADED 2 0
3 PREMIUM 0
4 DIESEL 0
I63500
JUL 25, 2022 11:07 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 UNLEADED 2 1
3 PREMIUM 1
4 DIESEL 1
I63900
JUL 25, 2022 11:07 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 UNLEADED 2
END FACTOR: NONE
3 PREMIUM
END FACTOR: NONE
4 DIESEL
END FACTOR: NONE
I78000
JUL 25, 2022 11:07 AM
I77700
JUL 25, 2022 11:07 AM
I77800
JUL 25, 2022 11:07 AM
I78C00
JUL 25, 2022 11:07 AM
I78300
JUL 25, 2022 11:07 AM
I78F00
JUL 25, 2022 11:07 AM
I78700
JUL 25, 2022 11:07 AM
I70200
JUL 25, 2022 11:07 AM
LIQUID LABEL
DEVICE LABEL
1 UNL ANN
2 UNL STP
3 UNL FILL
4 UNL 2 STP
5 UNL 2 STP
6 UNL 2 STP ANN
7 UNL 2 FILL
8 UNL 2 ANN FILL
9 UNL 2 ANN
10 PREM ANN
11 PREM STP
12 PREM FILL
13 DSL ANN
14 DSL STP
15 DSL FILL
16 DISP 13-14
17 DISP 15-16
18 DISP 17-18
19 DISP 19-20
20 DISP 21-22
21 DISP 23-24
22 VENTBOX
23
24
I70300
JUL 25, 2022 11:07 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL ANN TRI-STATE (SINGLE FLOAT)
2 UNL STP TRI-STATE (SINGLE FLOAT)
3 UNL FILL TRI-STATE (SINGLE FLOAT)
4 UNL 2 STP TRI-STATE (SINGLE FLOAT)
5 UNL 2 STP TRI-STATE (SINGLE FLOAT)
6 UNL 2 STP ANN TRI-STATE (SINGLE FLOAT)
7 UNL 2 FILL TRI-STATE (SINGLE FLOAT)
8 UNL 2 ANN FILL TRI-STATE (SINGLE FLOAT)
9 UNL 2 ANN DUAL POINT HYDROSTATIC
10 PREM ANN TRI-STATE (SINGLE FLOAT)
11 PREM STP TRI-STATE (SINGLE FLOAT)
12 PREM FILL TRI-STATE (SINGLE FLOAT)
13 DSL ANN TRI-STATE (SINGLE FLOAT)
14 DSL STP TRI-STATE (SINGLE FLOAT)
15 DSL FILL TRI-STATE (SINGLE FLOAT)
16 DISP 13-14 TRI-STATE (SINGLE FLOAT)
17 DISP 15-16 TRI-STATE (SINGLE FLOAT)
18 DISP 17-18 TRI-STATE (SINGLE FLOAT)
19 DISP 19-20 TRI-STATE (SINGLE FLOAT)
20 DISP 21-22 TRI-STATE (SINGLE FLOAT)
21 DISP 23-24 TRI-STATE (SINGLE FLOAT)
22 VENTBOX DW SUMP 2-1
23 TRI-STATE (SINGLE FLOAT)
24 TRI-STATE (SINGLE FLOAT)
I70400
JUL 25, 2022 11:07 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL ANN ANNULAR SPACE
2 UNL STP STP SUMP
3 UNL FILL PIPING SUMP
4 UNL 2 STP STP SUMP
5 UNL 2 STP STP SUMP
6 UNL 2 STP ANN ANNULAR SPACE
7 UNL 2 FILL PIPING SUMP
8 UNL 2 ANN FILL ANNULAR SPACE
9 UNL 2 ANN ANNULAR SPACE
10 PREM ANN ANNULAR SPACE
11 PREM STP STP SUMP
12 PREM FILL PIPING SUMP
13 DSL ANN ANNULAR SPACE
14 DSL STP STP SUMP
15 DSL FILL OTHER SENSORS
16 DISP 13-14 DISPENSER PAN
17 DISP 15-16 DISPENSER PAN
18 DISP 17-18 DISPENSER PAN
19 DISP 19-20 DISPENSER PAN
20 DISP 21-22 DISPENSER PAN
21 DISP 23-24 DISPENSER PAN
22 VENTBOX PIPING SUMP
23 OTHER SENSORS
24 OTHER SENSORS
I74200
JUL 25, 2022 11:07 AM
I74300
JUL 25, 2022 11:07 AM
I74400
JUL 25, 2022 11:07 AM
I74700
JUL 25, 2022 11:07 AM
I74800
JUL 25, 2022 11:07 AM
I74900
JUL 25, 2022 11:07 AM
I7BC00
JUL 25, 2022 11:07 AM
I80200
JUL 25, 2022 11:07 AM
I80300
JUL 25, 2022 11:07 AM
I80400
JUL 25, 2022 11:07 AM
I80700
JUL 25, 2022 11:07 AM
RELAY LABEL
DEVICE LABEL
1 POS SHUT OFF
2
3 UNLD 1
4 OVERFILL ALARM
5 INTERNAL ALARM
6
7
8 ANNUNCIATOR
I80900
JUL 25, 2022 11:07 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 POS SHUT OFF NORMALLY CLOSED
2 NORMALLY OPEN
3 UNLD 1 NORMALLY OPEN
4 OVERFILL ALARM NORMALLY OPEN
5 INTERNAL ALARM NORMALLY OPEN
6 NORMALLY OPEN
7 NORMALLY OPEN
8 ANNUNCIATOR NORMALLY CLOSED
I80B00
JUL 25, 2022 11:07 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 POS SHUT OFF 1
2 NONE
3 UNLD 1 1
4 OVERFILL ALARM NONE
5 INTERNAL ALARM NONE
6 NONE
7 NONE
8 ANNUNCIATOR NONE
I80A00
JUL 25, 2022 11:07 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 POS SHUT OFF STANDARD
2 STANDARD
3 UNLD 1 PUMP CONTROL OUTPUT
4 OVERFILL ALARM STANDARD
5 INTERNAL ALARM MOMENTARY
6 STANDARD
7 STANDARD
8 ANNUNCIATOR STANDARD
I80C00
JUL 25, 2022 11:07 AM
I80800
JUL 25, 2022 11:07 AM
RELAY SETUP REPORT
R 1:POS SHUT OFF
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 5:FUEL ALARM
L11:FUEL ALARM
L14:FUEL ALARM
L16:FUEL ALARM
L17:FUEL ALARM
L18:FUEL ALARM
L19:FUEL ALARM
L20:FUEL ALARM
L21:FUEL ALARM
L 2:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L16:SENSOR OUT ALARM
L17:SENSOR OUT ALARM
L18:SENSOR OUT ALARM
L19:SENSOR OUT ALARM
L20:SENSOR OUT ALARM
L21:SENSOR OUT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 5:SHORT ALARM
L 9:SHORT ALARM
L11:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
L16:SHORT ALARM
L17:SHORT ALARM
L18:SHORT ALARM
L19:SHORT ALARM
L20:SHORT ALARM
L21:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 3:UNLD 1
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 5:FUEL ALARM
L11:FUEL ALARM
L14:FUEL ALARM
L16:FUEL ALARM
L17:FUEL ALARM
L18:FUEL ALARM
L19:FUEL ALARM
L20:FUEL ALARM
L21:FUEL ALARM
L 2:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L16:SENSOR OUT ALARM
L17:SENSOR OUT ALARM
L18:SENSOR OUT ALARM
L19:SENSOR OUT ALARM
L20:SENSOR OUT ALARM
L21:SENSOR OUT ALARM
L 2:SHORT ALARM
L 5:SHORT ALARM
L11:SHORT ALARM
L16:SHORT ALARM
L17:SHORT ALARM
L18:SHORT ALARM
L19:SHORT ALARM
L20:SHORT ALARM
L21:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 5:INTERNAL ALARM
TYPE:
MOMENTARY
NORMALLY OPEN
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
SMARTSENSOR ALARMS
ALL:NO VACUUM ALARM
R 6:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 7:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 8:ANNUNCIATOR
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: NONE
IN-TANK ALARMS
ALL:LEAK ALARM
ALL:HIGH WATER ALARM
ALL:OVERFILL ALARM
ALL:LOW PRODUCT ALARM
ALL:SUDDEN LOSS ALARM
ALL:HIGH PRODUCT ALARM
ALL:INVALID FUEL LEVEL
ALL:PROBE OUT
ALL:HIGH WATER WARNING
ALL:DELIVERY NEEDED
ALL:MAX PRODUCT ALARM
ALL:GROSS TEST FAIL
ALL:PERIODIC TEST FAIL
ALL:ANNUAL TEST FAIL
ALL:PER TST NEEDED WRN
ALL:ANN TST NEEDED WRN
ALL:PER TST NEEDED ALM
ALL:ANN TST NEEDED ALM
ALL:TANK TEST ACTIVE
ALL:NO CSLD IDLE TIME
ALL:TANK SIPHON BREAK
ALL:CSLD INCR RATE WARN
ALL:ACCU_CHART CAL WARN
ALL:RECON WARNING
ALL:RECON ALARM
ALL:LOW TEMP WARNING
ALL:MISSING TICKET WARN
ALL:GROSS FAIL LINE TNK
ALL:DELIVY DENSITY WARN
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
ISD SITE ALARMS
ISD STAGE I WARN
ISD GROSS PRES WARN
ISD GROSS PRES FAIL
ISD DEGRD PRES WARN
ISD DEGRD PRES FAIL
ISD VAPOR LEAK WARN
ISD VAPOR LEAK FAIL
ISD VP PRES WARN
ISD VP PRES FAIL
ISD VP STATUS WARN
ISD VP STATUS FAIL
MISSING RELAY SETUP
MISSING HOSE SETUP
MISSING TANK SETUP
MISS VAPOR FLOW MTR
MISS VAPOR PRES SEN
MISSING VP INPUT
ISD SETUP WARN
ISD SETUP FAIL
ISD SENSOR OUT WARN
ISD SENSOR OUT FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT WARN
ALL:DEGRD COLLECT WARN
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT WARN
ALL:FLOW COLLECT FAIL
ALL:AIRFLOW MTR SETUP
I79000
JUL 25, 2022 11:08 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
JUL 25, 2022 11:08 AM
I72300
JUL 25, 2022 11:08 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 UNL 2 LINE VAC SENSOR
02 UNL 2 VENT VAC SENSOR
03 VAPOR VAC SENSOR
04 UNKNOWN
05 UNKNOWN
06 UNKNOWN
07 UNKNOWN
08 ATM ATM P SENSOR
09 PS 17-18 VAPOR PRESSURE
10 FM 13-14 AIR FLOW METER
11 FM 15-16 AIR FLOW METER
12 FM 17-18 AIR FLOW METER
13 FM 19-20 AIR FLOW METER
14 FM 21-22 AIR FLOW METER
15 FM 23-24 AIR FLOW METER
16 PS 17-18 VAPOR PRESSURE
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JUL 25, 2022 11:08 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
JUL 25, 2022 11:08 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JUL 25, 2022 11:08 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
VAPOR PROCESSOR TYPE
NONE
IV4700
JUL 25, 2022 11:08 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JUL 25, 2022 11:08 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
ACCEPT HIGH ORVR: NO
IV4A00
JUL 25, 2022 11:08 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 13 01 08 BLEND3
02 02 14 01 08 BLEND3
03 03 15 02 08 BLEND3
04 04 16 02 08 BLEND3
05 05 17 03 08 BLEND3
06 06 18 03 08 BLEND3
07 07 19 04 08 BLEND3
08 08 20 04 08 BLEND3
09 09 21 05 08 BLEND3
10 10 22 05 08 BLEND3
11 11 23 06 08 BLEND3
12 12 24 06 08 BLEND3
IV4B00
JUL 25, 2022 11:08 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 03/01 09/01 02/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
09 05 02/09 03/09 09/09 xx/xx
10 05 02/10 03/10 09/10 xx/xx
11 06 02/11 03/11 09/11 xx/xx
12 06 02/12 03/12 09/12 xx/xx
IV4900
JUL 25, 2022 11:08 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JUL 25, 2022 11:08 AM
ISD VERSION: 01.07
Jaco 367 alarm before
JUL 25, 2022 11:11 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 508187 507687
2 8SMARTSENSOR BD 39563 39572
3 4 PROBE / G.T. 164174 164301
4 INTERSTITIAL BD 201747 201972
5 INTERSTITIAL BD 202287 202327
6 INTERSTITIAL BD 202663 202611
7 UNUSED 4972927 4950998
8 UNUSED 4968243 4948729
9 RELAY BOARD 14927 14934
10 STP SENSE BOARD 33409 33419
11 RELAY BOARD 15145 15153
12 UNUSED 4969915 4950667
13 UNUSED 4967421 4949685
14 UNUSED 4967313 4946085
15 UNUSED 4965187 4948965
16 UNUSED 4968245 4950012
COMM 1 ELEC DISP INT. 101470 101587
COMM 2 RS232 SERIAL BD 15014 15022
COMM 3 RS232 SERIAL BD 14992 14978
COMM 4 UNUSED 4964884 4956427
COMM 5 UNUSED 4961392 4953416
COMM 6 UNUSED 4961739 4953111
I90200
JUL 25, 2022 11:11 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 25, 2022 11:11 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L15 OTHER DSL FILL FUEL ALARM CLEAR 7-25-22 11:11AM
L12 PIPE PREM FILL FUEL ALARM CLEAR 7-25-22 11:10AM
L15 OTHER DSL FILL FUEL ALARM ALARM 7-25-22 11:10AM
L12 PIPE PREM FILL FUEL ALARM ALARM 7-25-22 11:10AM
L 7 PIPE UNL 2 FILL FUEL ALARM CLEAR 7-25-22 11:09AM
L 3 PIPE UNL FILL FUEL ALARM CLEAR 7-25-22 11:08AM
L 7 PIPE UNL 2 FILL FUEL ALARM ALARM 7-25-22 11:08AM
L 3 PIPE UNL FILL FUEL ALARM ALARM 7-25-22 11:08AM
s 3 OTHER VAPOR NO VACUUM ALARM CLEAR 7-25-22 8:48AM
s 3 OTHER VAPOR NO VACUUM ALARM ALARM 7-23-22 12:28AM
s 3 OTHER VAPOR NO VACUUM ALARM CLEAR 7-22-22 4:00PM
s 3 OTHER VAPOR NO VACUUM ALARM ALARM 7-22-22 3:57PM
s 3 OTHER VAPOR NO VACUUM ALARM CLEAR 7-22-22 3:40PM
s 3 OTHER VAPOR NO VACUUM ALARM ALARM 7-21-22 4:25AM
s 1 OTHER UNL 2 LINE HIGH LIQUID ALARM CLEAR 7-20-22 12:16PM
s 3 OTHER VAPOR HIGH LIQUID ALARM CLEAR 7-20-22 12:16PM
s 3 OTHER VAPOR HIGH LIQUID ALARM ALARM 7-20-22 12:16PM
s 1 OTHER UNL 2 LINE HIGH LIQUID ALARM ALARM 7-20-22 12:16PM
s 3 OTHER VAPOR NO VACUUM ALARM CLEAR 7-20-22 12:15PM
s 2 OTHER UNL 2 VENT NO VACUUM ALARM CLEAR 7-20-22 12:15PM
s 1 OTHER UNL 2 LINE NO VACUUM ALARM CLEAR 7-20-22 12:15PM
s 3 OTHER VAPOR NO VACUUM ALARM ALARM 7-20-22 12:15PM
s 2 OTHER UNL 2 VENT NO VACUUM ALARM ALARM 7-20-22 12:15PM
s 1 OTHER UNL 2 LINE NO VACUUM ALARM ALARM 7-20-22 12:15PM
L 8 ANNULAR UNL 2 ANN FILL SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L 7 PIPE UNL 2 FILL SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L 6 ANNULAR UNL 2 STP ANN SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L 3 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L 2 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L 5 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L14 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L12 PIPE PREM FILL SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L11 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L10 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L16 DISP PAN DISP 13-14 SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L15 OTHER DSL FILL SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L22 PIPE VENTBOX SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L20 DISP PAN DISP 21-22 SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L19 DISP PAN DISP 19-20 SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L18 DISP PAN DISP 17-18 SENSOR OUT ALARM CLEAR 7-20-22 12:10PM
L13 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-20-22 12:09PM
L 9 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 7-20-22 12:09PM
L21 DISP PAN DISP 23-24 SENSOR OUT ALARM CLEAR 7-20-22 12:09PM
L17 DISP PAN DISP 15-16 SENSOR OUT ALARM CLEAR 7-20-22 12:09PM
L22 PIPE VENTBOX SENSOR OUT ALARM ALARM 7-20-22 12:09PM
L20 DISP PAN DISP 21-22 SENSOR OUT ALARM ALARM 7-20-22 12:09PM
L19 DISP PAN DISP 19-20 SENSOR OUT ALARM ALARM 7-20-22 12:09PM
L12 PIPE PREM FILL SENSOR OUT ALARM ALARM 7-20-22 12:09PM
L11 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-20-22 12:09PM
I11200
JUL 25, 2022 11:12 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 6-03-22 10:03PM
SYSTEM PAPER OUT CLEAR 6-03-22 10:03PM
SYSTEM PRINTER ERROR ALARM 6-03-22 9:39PM
SYSTEM PAPER OUT ALARM 6-03-22 9:39PM
h 1 OTHER FP13: BLEND3 GROSS COLLECT WARN CLEAR 4-14-22 9:29AM
h 1 OTHER FP13: BLEND3 GROSS COLLECT WARN ALARM 4-13-22 10:01AM
SYSTEM PRINTER ERROR CLEAR 4-01-22 4:11AM
SYSTEM PAPER OUT CLEAR 4-01-22 4:11AM
SYSTEM PRINTER ERROR ALARM 3-31-22 6:35PM
SYSTEM PAPER OUT ALARM 3-31-22 6:35PM
OTHER ISD GROSS PRES WARN CLEAR 3-21-22 4:06PM
OTHER ISD GROSS PRES WARN ALARM 3-20-22 10:01AM
s 3 OTHER VAPOR SETUP DATA WARNING CLEAR 2-13-21 8:06AM
s 2 OTHER UNL 2 VENT SETUP DATA WARNING CLEAR 2-13-21 8:06AM
s 3 OTHER VAPOR SETUP DATA WARNING ALARM 2-13-21 8:06AM
s 2 OTHER UNL 2 VENT SETUP DATA WARNING ALARM 2-13-21 8:06AM
I20600
JUL 25, 2022 11:12 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUN 29, 2022 1:19 AM
JUN 11, 2022 1:41 AM
MAY 21, 2022 11:34 AM
SUDDEN LOSS ALARM MAY 14, 2022 3:11 AM
MAY 1, 2022 12:45 AM
MAY 1, 2022 12:23 AM
TANK 2 UNLEADED 2
OVERFILL ALARM JUN 12, 2022 5:22 AM
MAY 25, 2022 2:44 AM
MAY 17, 2022 11:10 AM
TANK 3 PREMIUM
TANK 4 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 25, 2022 11:12 AM
I30200
JUL 25, 2022 11:12 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL ANN
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:27 AM FUEL ALARM
FEB 17, 2022 1:27 PM FUEL ALARM
2 UNL STP
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:00 AM FUEL ALARM
FEB 17, 2022 1:16 PM FUEL ALARM
3 UNL FILL
JUL 25, 2022 11:08 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:24 AM FUEL ALARM
5 UNL 2 STP
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:15 AM FUEL ALARM
FEB 17, 2022 1:17 PM FUEL ALARM
6 UNL 2 STP ANN
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:16 AM FUEL ALARM
FEB 17, 2022 1:01 PM FUEL ALARM
7 UNL 2 FILL
JUL 25, 2022 11:08 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:17 AM FUEL ALARM
8 UNL 2 ANN FILL
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:17 AM FUEL ALARM
FEB 17, 2022 1:24 PM FUEL ALARM
9 UNL 2 ANN
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:19 AM LOW LIQUID ALARM
JUL 20, 2022 11:19 AM HIGH LIQUID ALARM
10 PREM ANN
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:26 AM FUEL ALARM
FEB 17, 2022 1:29 PM FUEL ALARM
11 PREM STP
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:04 AM FUEL ALARM
FEB 17, 2022 12:59 PM FUEL ALARM
12 PREM FILL
JUL 25, 2022 11:10 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:25 AM FUEL ALARM
13 DSL ANN
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:26 AM FUEL ALARM
FEB 17, 2022 1:29 PM FUEL ALARM
14 DSL STP
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:09 AM FUEL ALARM
MAR 4, 2022 3:37 AM FUEL ALARM
15 DSL FILL
JUL 25, 2022 11:10 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:25 AM FUEL ALARM
16 DISP 13-14
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:34 AM FUEL ALARM
FEB 17, 2022 1:18 PM FUEL ALARM
17 DISP 15-16
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:28 AM FUEL ALARM
FEB 17, 2022 1:18 PM FUEL ALARM
18 DISP 17-18
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:22 AM FUEL ALARM
FEB 17, 2022 1:19 PM FUEL ALARM
19 DISP 19-20
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:40 AM FUEL ALARM
FEB 17, 2022 1:19 PM FUEL ALARM
20 DISP 21-22
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:53 AM FUEL ALARM
FEB 17, 2022 1:19 PM FUEL ALARM
21 DISP 23-24
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:59 AM FUEL ALARM
FEB 17, 2022 1:21 PM FUEL ALARM
22 VENTBOX
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:20 AM LOW LIQUID ALARM
JUL 20, 2022 11:20 AM FUEL ALARM
I31600
JUL 25, 2022 11:12 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL 2 LINE
JUL 20, 2022 12:16 PM HIGH LIQUID ALARM
JUL 20, 2022 12:15 PM NO VACUUM ALARM
FEB 17, 2022 1:44 PM HIGH LIQUID ALARM
2 UNL 2 VENT
JUL 20, 2022 12:15 PM NO VACUUM ALARM
FEB 17, 2022 1:44 PM NO VACUUM ALARM
FEB 17, 2022 1:02 PM NO VACUUM ALARM
3 VAPOR
JUL 23, 2022 12:28 AM NO VACUUM ALARM
JUL 22, 2022 3:57 PM NO VACUUM ALARM
JUL 21, 2022 4:25 AM NO VACUUM ALARM
8 ATM
10 FM 13-14
11 FM 15-16
12 FM 17-18
13 FM 19-20
14 FM 21-22
15 FM 23-24
16 PS 17-18
I40200
JUL 25, 2022 11:12 AM
I40300
JUL 25, 2022 11:12 AM
I34200
JUL 25, 2022 11:12 AM
I34700
JUL 25, 2022 11:12 AM
IV0100
JUL 25, 2022 11:12 AM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-04-13 10:01:18 A/L RATIO GROSS BLOCKAGE FP13 BLEND3 BLKD
22-03-21 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.00
22-03-20 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.00
22-02-14 10:02:32 A/L RATIO GROSS BLOCKAGE FP14 BLEND3 BLKD
22-02-13 10:02:30 A/L RATIO DEGRADATION FP14 BLEND3 BLKD
22-01-17 10:01:53 A/L RATIO DEGRADATION FP15 BLEND3 BLKD
22-01-17 10:01:53 A/L RATIO GROSS BLOCKAGE FP15 BLEND3 BLKD
22-01-16 10:01:58 A/L RATIO DEGRADATION FP14 BLEND3 BLKD
22-01-14 10:02:17 A/L RATIO DEGRADATION FP15 BLEND3 BLKD
21-12-12 10:02:12 A/L RATIO DEGRADATION FP23 BLEND3 0.81
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
21-10-27 10:03:09 A/L RATIO GROSS BLOCKAGE FP24 BLEND3 BLKD
20-12-02 10:02:55 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 56.91
19-05-17 08:31:19 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-05-16 08:31:33 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-05-15 08:31:32 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-05-14 08:31:21 SENSOR OUT SELFTEST T 1
19-05-14 08:31:21 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-05-14 08:31:20 SETUP SELFTEST
MISSING TANK(S)
19-05-13 08:31:17 SENSOR OUT SELFTEST T 1
19-05-13 08:31:16 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-07-23 10:02:35 READINESS ISD:PP EVR:PP ISD & EVR READY
22-07-22 10:02:21 READINESS ISD:PP EVR:NP EVR READINESS PENDING
22-07-21 10:02:20 READINESS ISD:PP EVR:NP EVR READINESS PENDING
22-07-20 12:08:02 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-07-20 12:08:02 ISD STARTUP
22-07-20 12:07:40 ISD SHUTDOWN
22-06-24 10:02:40 READINESS ISD:PP EVR:PP ISD & EVR READY
22-06-23 10:02:26 READINESS ISD:PP EVR:NP EVR READINESS PENDING
22-06-22 13:41:51 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-06-22 13:41:51 ISD STARTUP
Jaco 367 alarm after
JUL 25, 2022 1:27 PM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 508187 507343
2 8SMARTSENSOR BD 39563 39550
3 4 PROBE / G.T. 164174 164037
4 INTERSTITIAL BD 201747 201334
5 INTERSTITIAL BD 202287 202091
6 INTERSTITIAL BD 202663 202493
7 UNUSED 4972927 4940556
8 UNUSED 4968243 4942585
9 RELAY BOARD 14927 14934
10 STP SENSE BOARD 33409 33330
11 RELAY BOARD 15145 15109
12 UNUSED 4969915 4934444
13 UNUSED 4967421 4932676
14 UNUSED 4967313 4932240
15 UNUSED 4965187 4934793
16 UNUSED 4968245 4934073
COMM 1 ELEC DISP INT. 101470 101456
COMM 2 RS232 SERIAL BD 15014 15022
COMM 3 RS232 SERIAL BD 14992 14978
COMM 4 UNUSED 4964884 4937978
COMM 5 UNUSED 4961392 4938524
COMM 6 UNUSED 4961739 4937411
I90200
JUL 25, 2022 1:27 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 25, 2022 1:27 PM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L22 PIPE VENTBOX FUEL ALARM CLEAR 7-25-22 1:22PM
L22 PIPE VENTBOX FUEL ALARM ALARM 7-25-22 1:22PM
s 3 OTHER VAPOR NO VACUUM ALARM CLEAR 7-25-22 1:20PM
s 3 OTHER VAPOR NO VACUUM ALARM ALARM 7-25-22 12:48PM
L 2 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-25-22 11:47AM
L 6 ANNULAR UNL 2 STP ANN SENSOR OUT ALARM CLEAR 7-25-22 11:47AM
L 8 ANNULAR UNL 2 ANN FILL SENSOR OUT ALARM CLEAR 7-25-22 11:47AM
L 7 PIPE UNL 2 FILL SENSOR OUT ALARM CLEAR 7-25-22 11:47AM
L 3 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-25-22 11:47AM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-25-22 11:47AM
L 5 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L16 DISP PAN DISP 13-14 SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L20 DISP PAN DISP 21-22 SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L12 PIPE PREM FILL SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L11 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L10 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L15 OTHER DSL FILL SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L14 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L 9 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L19 DISP PAN DISP 19-20 SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L13 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L18 DISP PAN DISP 17-18 SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L17 DISP PAN DISP 15-16 SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L22 PIPE VENTBOX SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L21 DISP PAN DISP 23-24 SENSOR OUT ALARM CLEAR 7-25-22 11:46AM
L 2 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L18 DISP PAN DISP 17-18 SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L17 DISP PAN DISP 15-16 SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L12 PIPE PREM FILL SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L20 DISP PAN DISP 21-22 SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L22 PIPE VENTBOX SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L14 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L11 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L19 DISP PAN DISP 19-20 SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L21 DISP PAN DISP 23-24 SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L10 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L13 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L16 DISP PAN DISP 13-14 SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L 9 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L 8 ANNULAR UNL 2 ANN FILL SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L 7 PIPE UNL 2 FILL SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L15 OTHER DSL FILL SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L 6 ANNULAR UNL 2 STP ANN SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L 3 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L 5 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 7-25-22 11:46AM
L21 DISP PAN DISP 23-24 FUEL ALARM CLEAR 7-25-22 11:44AM
L21 DISP PAN DISP 23-24 FUEL ALARM ALARM 7-25-22 11:43AM
L21 DISP PAN DISP 23-24 FUEL ALARM CLEAR 7-25-22 11:43AM
L21 DISP PAN DISP 23-24 FUEL ALARM ALARM 7-25-22 11:43AM
I11200
JUL 25, 2022 1:27 PM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 7-25-22 1:26PM
SYSTEM PAPER OUT CLEAR 7-25-22 1:26PM
SYSTEM PRINTER ERROR ALARM 7-25-22 1:24PM
SYSTEM PAPER OUT ALARM 7-25-22 1:24PM
SYSTEM PRINTER ERROR CLEAR 6-03-22 10:03PM
SYSTEM PAPER OUT CLEAR 6-03-22 10:03PM
SYSTEM PRINTER ERROR ALARM 6-03-22 9:39PM
SYSTEM PAPER OUT ALARM 6-03-22 9:39PM
h 1 OTHER FP13: BLEND3 GROSS COLLECT WARN CLEAR 4-14-22 9:29AM
h 1 OTHER FP13: BLEND3 GROSS COLLECT WARN ALARM 4-13-22 10:01AM
SYSTEM PRINTER ERROR CLEAR 4-01-22 4:11AM
SYSTEM PAPER OUT CLEAR 4-01-22 4:11AM
SYSTEM PRINTER ERROR ALARM 3-31-22 6:35PM
SYSTEM PAPER OUT ALARM 3-31-22 6:35PM
OTHER ISD GROSS PRES WARN CLEAR 3-21-22 4:06PM
OTHER ISD GROSS PRES WARN ALARM 3-20-22 10:01AM
s 3 OTHER VAPOR SETUP DATA WARNING CLEAR 2-13-21 8:06AM
s 2 OTHER UNL 2 VENT SETUP DATA WARNING CLEAR 2-13-21 8:06AM
s 3 OTHER VAPOR SETUP DATA WARNING ALARM 2-13-21 8:06AM
s 2 OTHER UNL 2 VENT SETUP DATA WARNING ALARM 2-13-21 8:06AM
I20600
JUL 25, 2022 1:27 PM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUN 29, 2022 1:19 AM
JUN 11, 2022 1:41 AM
MAY 21, 2022 11:34 AM
SUDDEN LOSS ALARM MAY 14, 2022 3:11 AM
MAY 1, 2022 12:45 AM
MAY 1, 2022 12:23 AM
TANK 2 UNLEADED 2
OVERFILL ALARM JUN 12, 2022 5:22 AM
MAY 25, 2022 2:44 AM
MAY 17, 2022 11:10 AM
TANK 3 PREMIUM
TANK 4 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 25, 2022 1:27 PM
I30200
JUL 25, 2022 1:27 PM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL ANN
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:37 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
2 UNL STP
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:35 AM FUEL ALARM
JUL 25, 2022 11:34 AM FUEL ALARM
3 UNL FILL
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:08 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
5 UNL 2 STP
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:33 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
6 UNL 2 STP ANN
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:32 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
7 UNL 2 FILL
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:08 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
8 UNL 2 ANN FILL
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
JUL 20, 2022 11:17 AM FUEL ALARM
9 UNL 2 ANN
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:37 AM LOW LIQUID ALARM
JUL 25, 2022 11:37 AM HIGH LIQUID ALARM
10 PREM ANN
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:38 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
11 PREM STP
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:36 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
12 PREM FILL
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:10 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
13 DSL ANN
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:38 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
14 DSL STP
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:36 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
15 DSL FILL
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:10 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
16 DISP 13-14
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:41 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
17 DISP 15-16
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:40 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
18 DISP 17-18
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:39 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
19 DISP 19-20
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:42 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
20 DISP 21-22
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:42 AM FUEL ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
21 DISP 23-24
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 25, 2022 11:43 AM FUEL ALARM
JUL 25, 2022 11:43 AM FUEL ALARM
22 VENTBOX
JUL 25, 2022 1:22 PM FUEL ALARM
JUL 25, 2022 11:46 AM SENSOR OUT ALARM
JUL 20, 2022 12:09 PM SENSOR OUT ALARM
I31600
JUL 25, 2022 1:28 PM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL 2 LINE
JUL 25, 2022 11:32 AM HIGH LIQUID ALARM
JUL 25, 2022 11:31 AM NO VACUUM ALARM
JUL 20, 2022 12:16 PM HIGH LIQUID ALARM
2 UNL 2 VENT
JUL 25, 2022 11:31 AM NO VACUUM ALARM
JUL 20, 2022 12:15 PM NO VACUUM ALARM
FEB 17, 2022 1:44 PM NO VACUUM ALARM
3 VAPOR
JUL 25, 2022 12:48 PM NO VACUUM ALARM
JUL 25, 2022 11:32 AM HIGH LIQUID ALARM
JUL 25, 2022 11:31 AM NO VACUUM ALARM
8 ATM
10 FM 13-14
11 FM 15-16
12 FM 17-18
13 FM 19-20
14 FM 21-22
15 FM 23-24
16 PS 17-18
I40200
JUL 25, 2022 1:28 PM
I40300
JUL 25, 2022 1:28 PM
I34200
JUL 25, 2022 1:28 PM
I34700
JUL 25, 2022 1:28 PM
IV0100
JUL 25, 2022 1:28 PM
FASTRIP 367
8001 WHITE LANE
BAKERSFIELD CA,93309
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-04-13 10:01:18 A/L RATIO GROSS BLOCKAGE FP13 BLEND3 BLKD
22-03-21 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.00
22-03-20 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.00
22-02-14 10:02:32 A/L RATIO GROSS BLOCKAGE FP14 BLEND3 BLKD
22-02-13 10:02:30 A/L RATIO DEGRADATION FP14 BLEND3 BLKD
22-01-17 10:01:53 A/L RATIO DEGRADATION FP15 BLEND3 BLKD
22-01-17 10:01:53 A/L RATIO GROSS BLOCKAGE FP15 BLEND3 BLKD
22-01-16 10:01:58 A/L RATIO DEGRADATION FP14 BLEND3 BLKD
22-01-14 10:02:17 A/L RATIO DEGRADATION FP15 BLEND3 BLKD
21-12-12 10:02:12 A/L RATIO DEGRADATION FP23 BLEND3 0.81
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
21-10-27 10:03:09 A/L RATIO GROSS BLOCKAGE FP24 BLEND3 BLKD
20-12-02 10:02:55 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 56.91
19-05-17 08:31:19 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-05-16 08:31:33 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-05-15 08:31:32 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-05-14 08:31:21 SENSOR OUT SELFTEST T 1
19-05-14 08:31:21 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-05-14 08:31:20 SETUP SELFTEST
MISSING TANK(S)
19-05-13 08:31:17 SENSOR OUT SELFTEST T 1
19-05-13 08:31:16 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-07-25 11:51:57 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-07-25 11:51:57 ISD STARTUP
22-07-25 11:51:54 ISD SHUTDOWN
22-07-23 10:02:35 READINESS ISD:PP EVR:PP ISD & EVR READY
22-07-22 10:02:21 READINESS ISD:PP EVR:NP EVR READINESS PENDING
22-07-21 10:02:20 READINESS ISD:PP EVR:NP EVR READINESS PENDING
22-07-20 12:08:02 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-07-20 12:08:02 ISD STARTUP
22-07-20 12:07:40 ISD SHUTDOWN
22-06-24 10:02:40 READINESS ISD:PP EVR:PP ISD & EVR READY