HomeMy WebLinkAboutCold Start Results 6/22Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10134223 06-02-2022
Jaco#2233D&G
2732 Brundage Lane Bakersfield 93301
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Frank Amestoy
1073967
8374998 10-22-2023
Veeder root 07-31-2022
06-02-2022 5
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder root TLS-350 327.04
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1: 794380-208 UDC 1/2
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
NOPARKING
N
EXISTING BUILDING
H
W
W
G
R
1
2
L1
S
T
P
F
1
2
,
0
0
0
G
A
L
L
O
N
D
I
E
S
E
L
1
2
,
0
0
0
G
A
L
L
O
N
8
7
U
N
L
E
A
D
E
D
1
2
,
0
0
0
G
A
L
L
O
N
P
R
E
M
I
U
M
V
F
V
F
S
T
P
S
T
P
A
N
O
D
E
DUMPSTER
PRICE SIGN
MYRTLE ST.
BR
U
N
D
A
G
E
L
N
.
PROPERTY LINE
PR
O
P
E
R
T
Y
L
I
N
E
141'
73
.
5
'
LEGEND
L1 UDC 1 - 2
87 GAS 2 INCH SINGLE WALLED PIPE
91 GAS 2 INCH SINGLE WALLED PIPE
DIESEL 2 INCH SINGLE WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
WATER SHUTOFF
EVACUATION MEETING POINT
RECTIFIER
AUTOMATIC TANK GAUGE
CIRCUIT BREAKER
AIR AND WATER DISPENSER
G
P
V
W
R
SITE MAP C1
VICINITY MAP
PROJECT DATA
1/8"=1'-0"
INCHES012
SHEET SIZE 22 X 34
SCALE:
2732 BRUNDAGE LN.
BAKERSFIELD, CA 93304
O
A
K
S
T
.
E BRUNDAGE LN.
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-002916
CERS ID 10134223
FASTRIP #2233
2732 BRUNDAGE LN.
BAKERSFIELD, CA 93304
12/21/16 REV.
D&G liquor after cold start setup
Responses Received:
200
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326-1083
JUN 2, 2022 11:29 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 8336 62.92 0.0 84.3 3664
2 PREMIUM 1350 16.30 0.8 89.8 10650
3 DIESEL 1402 16.73 0.0 84.7 10598
I90500
JUN 2, 2022 11:29 AM
SOFTWARE REVISION LEVEL
VERSION 327.04
SOFTWARE# 346327-100-E
CREATED - 07.02.06.10.28
S-MODULE# 330160-062-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I50500
JUN 2, 2022 11:29 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUN 2, 2022 11:29 AM
SHIFT TIME 1 : DISABLED
I50202
JUN 2, 2022 11:29 AM
SHIFT TIME 2 : DISABLED
I50203
JUN 2, 2022 11:29 AM
SHIFT TIME 3 : DISABLED
I50204
JUN 2, 2022 11:29 AM
SHIFT TIME 4 : DISABLED
I54600
JUN 2, 2022 11:29 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUN 2, 2022 11:29 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUN 2, 2022 11:29 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUN 2, 2022 11:29 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUN 2, 2022 11:29 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUN 2, 2022 11:29 AM
PRINT TC VOLUMES
ENABLED
I50E00
JUN 2, 2022 11:29 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUN 2, 2022 11:29 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUN 2, 2022 11:29 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUN 2, 2022 11:29 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUN 2, 2022 11:29 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUN 2, 2022 11:29 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUN 2, 2022 11:29 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUN 2, 2022 11:29 AM
TANK CHART SECURITY
DISABLED
I5BD00
JUN 2, 2022 11:29 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JUN 2, 2022 11:29 AM
MASS/DENSITY
DISABLED
I88101
JUN 2, 2022 11:29 AM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88102
JUN 2, 2022 11:29 AM
I88103
JUN 2, 2022 11:29 AM
I88104
JUN 2, 2022 11:29 AM
I88105
JUN 2, 2022 11:29 AM
I88106
JUN 2, 2022 11:29 AM
I52000
JUN 2, 2022 11:29 AM
I60100
JUN 2, 2022 11:29 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 PREMIUM ON
3 DIESEL ON
4 OFF
I60200
JUN 2, 2022 11:29 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4
I60300
JUN 2, 2022 11:29 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL 3
4 4
I60900
JUN 2, 2022 11:29 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 PREMIUM 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
JUN 2, 2022 11:29 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 96.00
2 PREMIUM 96.00
3 DIESEL 96.00
4 0.00
I60A00
JUN 2, 2022 11:29 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
1 PT 12000 2 PREMIUM 1 PT 12000 3 DIESEL
1 PT 12000 4 1 PT 0
I60400
JUN 2, 2022 11:29 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12000
2 PREMIUM 12000
3 DIESEL 12000
4 0
I60500
JUN 2, 2022 11:29 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12000 0 0 0
2 PREMIUM 12000 0 0 0
3 DIESEL 12000 0 0 0
4 0 0 0 0
I60600
JUN 2, 2022 11:29 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 PREMIUM 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DIESEL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUN 2, 2022 11:29 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 PREMIUM NO
3 DIESEL NO
4 NO
I62F00
JUN 2, 2022 11:29 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 INCHES
2 PREMIUM 4.0 INCHES
3 DIESEL 4.0 INCHES
I62700
JUN 2, 2022 11:29 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 PREMIUM 2.0
3 DIESEL 2.0
9999FF1B
I62400
JUN 2, 2022 11:29 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 PREMIUM 3.0
3 DIESEL 3.0
I62800
JUN 2, 2022 11:29 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12000
2 PREMIUM 12000
3 DIESEL 12000
4 0
I62300
JUN 2, 2022 11:29 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10800
2 PREMIUM 10800
3 DIESEL 10800
4 0
I62200
JUN 2, 2022 11:29 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11400
2 PREMIUM 11400
3 DIESEL 11400
4 0
I62900
JUN 2, 2022 11:29 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1800
2 PREMIUM 1800
3 DIESEL 1800
4 0
I62100
JUN 2, 2022 11:29 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 600
2 PREMIUM 600
3 DIESEL 600
4 0
I62600
JUN 2, 2022 11:29 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I62500
JUN 2, 2022 11:29 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I60800
JUN 2, 2022 11:30 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 0.00
3 DIESEL 0.00
4 0.00
I60B00
JUN 2, 2022 11:30 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUN 2, 2022 11:30 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 0.00
3 DIESEL 0.00
4 0.00
I61200
JUN 2, 2022 11:30 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 PREMIUM NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
JUN 2, 2022 11:30 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 PREMIUM 120
3 DIESEL 120
4 0
I62A00
JUN 2, 2022 11:30 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 PREMIUM 120
3 DIESEL 120
4 0
I62C00
JUN 2, 2022 11:30 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 PREMIUM STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
JUN 2, 2022 11:30 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUN 2, 2022 11:30 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 PREMIUM OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
JUN 2, 2022 11:30 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I63200
JUN 2, 2022 11:30 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I61000
JUN 2, 2022 11:30 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63A00
JUN 2, 2022 11:30 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 PREMIUM 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
JUN 2, 2022 11:30 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST CSLD : ALL TANK
Pd = 95%
CLIMATE FACTOR:MODERATE
GROSS TEST
AUTO-CONFIRM: DISABLED
REPORT ONLY:
DISABLED
TST EARLY STOP:DISABLED
I61300
JUN 2, 2022 11:30 AM
CSLD PROBABLITY OF DETECTION
T 1:UNLEADED : Pd = 95%
T 2:PREMIUM : Pd = 95%
T 3:DIESEL : Pd = 95%
I61400
JUN 2, 2022 11:30 AM
CSLD CLIMATE FACTOR
T 1:UNLEADED : MODERATE
T 2:PREMIUM : MODERATE
T 3:DIESEL : MODERATE
I61600
JUN 2, 2022 11:30 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 PREMIUM IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
JUN 2, 2022 11:30 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED
2 PREMIUM DISABLED
3 DIESEL DISABLED
4 DISABLED
I61B00
JUN 2, 2022 11:30 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
TANK PRODUCT LABEL AUTO-CONFIRM
1 UNLEADED DISABLED
2 PREMIUM DISABLED
3 DIESEL DISABLED
I61C00
JUN 2, 2022 11:30 AM
CSLD REPORT ONLY
TANK PRODUCT LABEL CSLD REPORT ONLY
1 UNLEADED DISABLED
2 PREMIUM DISABLED
3 DIESEL DISABLED
I62B00
JUN 2, 2022 11:30 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 PREMIUM ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
JUN 2, 2022 11:30 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUN 2, 2022 11:30 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 PREMIUM 0
3 DIESEL 0
4 0
I63500
JUN 2, 2022 11:30 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63900
JUN 2, 2022 11:30 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 PREMIUM
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
JUN 2, 2022 11:30 AM
I77700
JUN 2, 2022 11:30 AM
I77800
JUN 2, 2022 11:30 AM
I78C00
JUN 2, 2022 11:30 AM
I78300
JUN 2, 2022 11:30 AM
I78F00
JUN 2, 2022 11:30 AM
I78700
JUN 2, 2022 11:30 AM
I70200
JUN 2, 2022 11:30 AM
LIQUID LABEL
DEVICE LABEL
1 DISP 1
2
3
4
5
6
7
8
I70300
JUN 2, 2022 11:30 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 DISP 1 TRI-STATE (SINGLE FLOAT)
2 TRI-STATE (SINGLE FLOAT)
3 TRI-STATE (SINGLE FLOAT)
4 TRI-STATE (SINGLE FLOAT)
5 TRI-STATE (SINGLE FLOAT)
6 TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
I70400
JUN 2, 2022 11:30 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 DISP 1 DISPENSER PAN
2 OTHER SENSORS
3 OTHER SENSORS
4 OTHER SENSORS
5 OTHER SENSORS
6 OTHER SENSORS
7 OTHER SENSORS
8 OTHER SENSORS
I74200
JUN 2, 2022 11:30 AM
I74300
JUN 2, 2022 11:30 AM
I74400
JUN 2, 2022 11:30 AM
I74700
JUN 2, 2022 11:30 AM
I74800
JUN 2, 2022 11:30 AM
I74900
JUN 2, 2022 11:30 AM
I7BC00
JUN 2, 2022 11:30 AM
I80200
JUN 2, 2022 11:30 AM
I80300
JUN 2, 2022 11:30 AM
I80400
JUN 2, 2022 11:30 AM
I80700
JUN 2, 2022 11:30 AM
RELAY LABEL
DEVICE LABEL
1 OVERFILL ALARM
2
3
4
I80900
JUN 2, 2022 11:30 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 OVERFILL ALARM NORMALLY OPEN
2 NORMALLY OPEN
3 NORMALLY OPEN
4 NORMALLY OPEN
I80B00
JUN 2, 2022 11:30 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 OVERFILL ALARM NONE
2 NONE
3 NONE
4 NONE
I80A00
JUN 2, 2022 11:30 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 OVERFILL ALARM STANDARD
2 STANDARD
3 STANDARD
4 STANDARD
I80C00
JUN 2, 2022 11:30 AM
I80800
JUN 2, 2022 11:30 AM
RELAY SETUP REPORT
R 1:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 2:
TYPE:
STANDARD
NORMALLY OPEN
- NO ALARM ASSIGNMENTS -
R 3:
TYPE:
STANDARD
NORMALLY OPEN
- NO ALARM ASSIGNMENTS -
R 4:
TYPE:
STANDARD
NORMALLY OPEN
- NO ALARM ASSIGNMENTS -
I79000
JUN 2, 2022 11:30 AM
I79100
JUN 2, 2022 11:30 AM
I72300
JUN 2, 2022 11:30 AM
IV4E00
JUN 2, 2022 11:30 AM
IV4F00
JUN 2, 2022 11:30 AM
IV4000
JUN 2, 2022 11:30 AM
IV4700
JUN 2, 2022 11:30 AM
IV5200
JUN 2, 2022 11:30 AM
IV4A00
JUN 2, 2022 11:30 AM
IV4B00
JUN 2, 2022 11:30 AM
IV4900
JUN 2, 2022 11:30 AM
IV1000
JUN 2, 2022 11:30 AM
ISD VERSION: 01.01
D&G liquor after cold start alarm history
Responses Received:
I10200
JUN 2, 2022 11:33 AM
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326-1083
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 INTERSTITIAL BD 201162 201162
2 4 PROBE / G.T. 164019 164019
3 UNUSED 9810446 9810446
4 UNUSED 9790645 9790645
5 UNUSED 9792695 9792695
6 UNUSED 9786833 9786833
7 UNUSED 9785603 9785603
8 UNUSED 9783307 9783307
9 WPLLD POWER BD 202397 202397
10 AC INTERFACE BD 164236 164236
11 RELAY BOARD 15076 15076
12 UNUSED 9799395 9799395
13 UNUSED 9790089 9790089
14 UNUSED 9801301 9801301
15 UNUSED 9786707 9786707
16 UNUSED 9789372 9789372
COMM 1 RS232 SERIAL BD 14952 14952
COMM 2 WPLLD COMM BD 202440 202440
COMM 3 UNUSED 9797448 9797448
COMM 4 UNUSED 9779840 9779840
COMM 5 UNUSED 9792282 9792282
COMM 6 UNUSED 9788613 9788613
I90200
JUN 2, 2022 11:33 AM
SOFTWARE REVISION LEVEL
VERSION 327.04
SOFTWARE# 346327-100-E
CREATED - 07.02.06.10.28
S-MODULE# 330160-062-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I11100
JUN 2, 2022 11:33 AM
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326-1083
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK UNLEADED SUDDEN LOSS ALARM ALARM 6-02-22 11:22AM
W 3 OTHER PREMIUM WPLLD SHUTDOWN ALM CLEAR 6-02-22 11:19AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 6-02-22 11:19AM
W 1 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 6-02-22 11:19AM
L 1 DISP PAN DISP 1 FUEL ALARM CLEAR 6-02-22 11:19AM
T 2 TANK PREMIUM PROBE OUT CLEAR 6-02-22 11:18AM
T 1 TANK UNLEADED PROBE OUT CLEAR 6-02-22 11:18AM
T 3 TANK DIESEL PROBE OUT CLEAR 6-02-22 11:18AM
L 1 DISP PAN DISP 1 FUEL ALARM ALARM 6-02-22 11:18AM
W 3 OTHER PREMIUM WPLLD SHUTDOWN ALM ALARM 6-02-22 11:18AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 6-02-22 11:18AM
W 1 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 6-02-22 11:18AM
T 3 TANK DIESEL PROBE OUT ALARM 6-02-22 11:18AM
T 2 TANK PREMIUM PROBE OUT ALARM 6-02-22 11:18AM
T 1 TANK UNLEADED PROBE OUT ALARM 6-02-22 11:18AM
W 3 OTHER PREMIUM WPLLD SHUTDOWN ALM CLEAR 2-06-07 8:25AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 2-06-07 8:25AM
W 1 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 2-06-07 8:25AM
L 1 DISP PAN DISP 1 FUEL ALARM CLEAR 2-06-07 8:25AM
L 1 DISP PAN DISP 1 FUEL ALARM ALARM 2-06-07 8:25AM
W 3 OTHER PREMIUM WPLLD SHUTDOWN ALM ALARM 2-06-07 8:25AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 2-06-07 8:25AM
W 1 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 2-06-07 8:25AM
SYSTEM BATTERY IS OFF CLEAR 2-06-07 8:00AM
SYSTEM BATTERY IS OFF ALARM 2-06-07 8:00AM
I11200
JUN 2, 2022 11:33 AM
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326-1083
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 6-02-22 11:22AM
T 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 6-02-22 11:22AM
T 3 TANK DIESEL DELIVERY NEEDED ALARM 6-02-22 11:22AM
T 2 TANK PREMIUM HIGH PRODUCT ALARM CLEAR 6-02-22 11:22AM
T 2 TANK PREMIUM DELIVERY NEEDED ALARM 6-02-22 11:22AM
T 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 6-02-22 11:21AM
T 3 TANK DIESEL DELIVERY NEEDED CLEAR 6-02-22 11:21AM
T 2 TANK PREMIUM HIGH PRODUCT ALARM ALARM 6-02-22 11:21AM
T 2 TANK PREMIUM DELIVERY NEEDED CLEAR 6-02-22 11:21AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 6-02-22 11:21AM
W 3 OTHER PREMIUM SETUP DATA WARNING CLEAR 2-06-07 8:05AM
W 2 OTHER UNLEADED SETUP DATA WARNING CLEAR 2-06-07 8:05AM
W 1 OTHER DIESEL SETUP DATA WARNING CLEAR 2-06-07 8:05AM
W 3 OTHER PREMIUM SETUP DATA WARNING ALARM 2-06-07 8:05AM
W 2 OTHER UNLEADED SETUP DATA WARNING ALARM 2-06-07 8:05AM
W 1 OTHER DIESEL SETUP DATA WARNING ALARM 2-06-07 8:05AM
L 1 DISP PAN DISP 1 SETUP DATA WARNING CLEAR 2-06-07 8:05AM
T 3 TANK DIESEL DELIVERY NEEDED ALARM 2-06-07 8:05AM
T 2 TANK PREMIUM DELIVERY NEEDED ALARM 2-06-07 8:05AM
L 1 DISP PAN DISP 1 SETUP DATA WARNING ALARM 2-06-07 8:02AM
I20600
JUN 2, 2022 11:33 AM
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326-1083
TANK ALARM HISTORY
TANK 1 UNLEADED
SUDDEN LOSS ALARM JUN 2, 2022 11:22 AM
HIGH PRODUCT ALARM JUN 2, 2022 11:21 AM
PROBE OUT JUN 2, 2022 11:18 AM
TANK 2 PREMIUM
HIGH PRODUCT ALARM JUN 2, 2022 11:21 AM
PROBE OUT JUN 2, 2022 11:18 AM
DELIVERY NEEDED JUN 2, 2022 11:22 AM
FEB 6, 2007 8:05 AM
TANK 3 DIESEL
HIGH PRODUCT ALARM JUN 2, 2022 11:21 AM
PROBE OUT JUN 2, 2022 11:18 AM
DELIVERY NEEDED JUN 2, 2022 11:22 AM
FEB 6, 2007 8:05 AM
I38200
JUN 2, 2022 11:33 AM
I30200
JUN 2, 2022 11:33 AM
D AND G 233
2732 BRUNDAGE LN
BAKERSFFILD CA 9330
661-326-1083
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1
JUN 2, 2022 11:18 AM FUEL ALARM
FEB 6, 2007 8:25 AM FUEL ALARM
FEB 6, 2007 8:02 AM SETUP DATA WARNING
I31600
JUN 2, 2022 11:33 AM
I40200
JUN 2, 2022 11:33 AM
I40300
JUN 2, 2022 11:33 AM
I34200
JUN 2, 2022 11:33 AM
I34700
JUN 2, 2022 11:33 AM
IV0100
JUN 2, 2022 11:33 AM