HomeMy WebLinkAboutFMC 2022Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10022950 8/19/2022
Grand Avenue Coast, Inc. (ARCO)
4203 Ming Avenue Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Aaron Perrigo
1073967
8485827 8/8/2024
Veeder Root B47853 7/31/2024
OPW 0148613 8/19/2022
8/19/2022 5
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS-350 336.01
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 409 Unl Ann
L2 208 Unl STP
L3 208 Unl Fill S
L4 409 Unl 2 Ann
L5 208 Unl 2 Sy
L6 208 Unl M Fill
L7 409 Unl 3 Ann
L8 208 Unl 3 Sy
L9 208 Unl N Fill
L10 409 Prem Ann
L11 208 Prem Fill
L12 208 Prem STP
L13 208 Disp-2
L14 208 Disp 3-4
L15 208 Disp 5-6
L16 208 Disp 7-8
L17 208 Disp 9-10
L18 208 Disp 11-12
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Q1 848480-001 Unl
Q2 848480-001 Prem
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
APPENDIX C-10
SH
E
A
R
V
A
L
V
E
O
P
E
R
A
T
I
O
N
I
N
S
P
E
C
T
I
O
N
)D
F
L
O
L
W
\
1
D
P
H
2Z
Q
H
U
$G
G
U
H
V
V
$G
G
U
H
V
V
&L
W
\
6
W
D
W
H
=
L
S
&
R
G
H
&L
W
\
6
W
D
W
H
=
L
S
&
R
G
H
)D
F
L
O
L
W
\
,
'
3K
R
Q
H
7H
V
W
L
Q
J
&
R
P
S
D
Q
\
3K
R
Q
H
7K
L
V
G
D
W
D
V
K
H
H
W
L
V
I
R
U
L
Q
V
S
H
F
W
L
Q
J
V
K
H
D
U
Y
D
O
Y
H
V
O
R
F
D
W
H
G
L
Q
V
L
G
H
G
LV
S
H
Q
V
H
U
V
6
H
H
3
(
,
5
3
6
H
F
W
L
R
Q
I
R
U
W
K
H
L
Q
V
S
H
F
W
L
R
Q
S
U
R
F
H
G
XU
H
3U
R
G
X
F
W
*
U
D
G
H
'L
V
S
H
Q
V
H
U
,
'
6K
H
D
U
9
D
O
Y
H
7
\
S
H
3
U
R
G
X
F
W
9
D
S
R
U
,
V
W
K
H
V
K
H
D
U
Y
D
O
Y
H
U
L
J
L
G
O
\
DQ
F
K
R
U
H
G
W
R
W
K
H
G
L
V
S
H
Q
V
H
U
E
R
[
IU
D
P
H
R
U
G
L
V
S
H
Q
V
H
U
L
V
O
D
Q
G
"
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<HV1R <HV1R
,
V
W
K
H
V
K
H
D
U
V
H
F
W
L
R
Q
S
R
V
L
WL
R
Q
H
G
E
H
W
Z
H
H
Q
ó
L
Q
F
K
D
E
R
Y
H
RU
E
H
O
R
Z
W
K
H
W
R
S
V
X
U
I
D
F
H
R
I
W
K
H
GL
V
S
H
Q
V
H
U
L
V
O
D
Q
G
"
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<
H
V
1
R
<HV1R <HV1R
,
V
W
K
H
O
H
Y
H
U
D
U
P
I
U
H
H
W
R
P
R
Y
H
"
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<HV1R 1$<HV1R 1$
'
R
H
V
W
K
H
O
H
Y
H
U
D
U
P
V
Q
D
S
V
K
X
W
WK
H
S
R
S
S
H
W
Y
D
O
Y
H
"
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<HV1R 1$<HV1R 1$
&
D
Q
D
Q
\
S
U
R
G
X
F
W
E
H
G
L
V
S
H
Q
V
H
G
ZK
H
Q
W
K
H
S
U
R
G
X
F
W
V
K
H
D
U
Y
D
O
Y
H
L
V
FO
R
V
H
G
"
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<
H
V
1
R
1
$
<HV1R 1$<HV1R 1$
$
´
1
R
µ
W
R
/
L
Q
H
V
R
U
D
´
<
H
V
µ
I
R
U
/
L
Q
H
L
Q
G
L
F
D
W
H
V
D
W
H
V
W
I
D
L
O
XU
H
Te
s
t
R
e
s
u
l
t
s
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3
D
V
V
)
D
L
O
3DVV)DLO3DVV)DLO
Co
m
m
e
n
t
s
:
7H
V
W
H
U
·
V
1
D PH
BB
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
7H
V
W
H
U
·
V
6
L
J
Q
D
W
X
U
H
BB
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
1Z
H
V
W
F
R
/
/
&
Gr
a
n
d
A
v
e
n
u
e
C
o
a
s
t
,
I
n
c
.
(
A
R
C
O
)
42
0
3
M
i
n
g
A
v
e
n
u
e
Ba
k
e
r
s
f
i
e
l
d
10
0
2
2
9
5
0
3-
4
7-
8
1
1
-
1
2
MP
D
MP
D
MP
D
MP
D
MP
D
MP
D
1-
2
5-
6
9-
1
0
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Pr
o
d
u
c
t
Aa
r
o
n
P
e
r
r
i
g
o
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10022950 8/19/2022
Grand Avenue Coast, Inc. (ARCO)
4203 Ming Avenue Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Aaron Perrigo
1073967
8485827 8/8/2024
OPW 0148613 7/10/2024
Lake Test Al 4 fill spill buckets
8/19/2022 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
Unl 1
OPW
Unl 2
OPW
Unl 3
OPW
Prem
OPW
Grand Ave Setup
Responses Received:
200
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
AUG 19, 2022 8:53 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 1 1668 21.29 0.1 89.9 8332
2 UNLEADED 2 TURBN 1976 24.02 0.8 91.0 8024
3 UNLEADED 3 2289 26.70 0.0 88.5 7711
4 PREMIUM 1714 21.71 0.0 88.8 8286
I90500
AUG 19, 2022 8:53 AM
SOFTWARE REVISION LEVEL
VERSION 336.01
SOFTWARE# 346336-100-B
CREATED - 20.04.26.20.30
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
AUG 19, 2022 8:53 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
AUG 19, 2022 8:53 AM
SHIFT TIME 1 : DISABLED
I50202
AUG 19, 2022 8:53 AM
SHIFT TIME 2 : DISABLED
I50203
AUG 19, 2022 8:53 AM
SHIFT TIME 3 : DISABLED
I50204
AUG 19, 2022 8:53 AM
SHIFT TIME 4 : DISABLED
I54600
AUG 19, 2022 8:53 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
AUG 19, 2022 8:53 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
AUG 19, 2022 8:53 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
AUG 19, 2022 8:53 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
AUG 19, 2022 8:53 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
AUG 19, 2022 8:53 AM
PRINT TC VOLUMES
ENABLED
I50E00
AUG 19, 2022 8:53 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
AUG 19, 2022 8:53 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
AUG 19, 2022 8:53 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
AUG 19, 2022 8:53 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
AUG 19, 2022 8:53 AM
DAYLIGHT SAVING TIME
START DATE APR WEEK 1 SUN 2:00 AM
END DATE OCT WEEK 6 SUN 2:00 AM
I51600
AUG 19, 2022 8:53 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
AUG 19, 2022 8:53 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
AUG 19, 2022 8:53 AM
TANK CHART SECURITY
DISABLED
I5BD00
AUG 19, 2022 8:53 AM
CUSTOM ALARM LABELS
DISABLED
I56000
AUG 19, 2022 8:53 AM
MASS/DENSITY
DISABLED
I88101
AUG 19, 2022 8:53 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
AUG 19, 2022 8:53 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
AUG 19, 2022 8:53 AM
PORT SETTINGS:
COMM BOARD : 3 (S-SAT )
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
DTR NORMAL STATE: HIGH
I88104
AUG 19, 2022 8:53 AM
I88105
AUG 19, 2022 8:53 AM
PORT SETTINGS:
COMM BOARD : 5 (RS-485)
BAUD RATE : 1200
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88106
AUG 19, 2022 8:53 AM
PORT SETTINGS:
COMM BOARD : 6 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I52000
AUG 19, 2022 8:53 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE JUL 17, 2006 DISABLED
2 ON DATE JUL 17, 2006 DISABLED
3 ON DATE JUL 17, 2006 DISABLED
4 ON DATE JUL 17, 2006 DISABLED
5 ON DATE JUL 17, 2006 DISABLED
6 ON DATE JUL 17, 2006 DISABLED
7 ON DATE JUL 17, 2006 DISABLED
8 VEEDER ROOT (FMS) ON DATE JUN 13, 2006 11:46 AM
I60100
AUG 19, 2022 8:53 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED 1 ON
2 UNLEADED 2 TURBN ON
3 UNLEADED 3 ON
4 PREMIUM ON
I60200
AUG 19, 2022 8:53 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED 1
2 UNLEADED 2 TURBN
3 UNLEADED 3
4 PREMIUM
I60300
AUG 19, 2022 8:54 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1 1
2 UNLEADED 2 TURBN 1
3 UNLEADED 3 1
4 PREMIUM 2
I60900
AUG 19, 2022 8:54 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 1 0.000700
2 UNLEADED 2 TURBN 0.000700
3 UNLEADED 3 0.000700
4 PREMIUM 0.000700
I60700
AUG 19, 2022 8:54 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 96.00
2 UNLEADED 2 TURBN 96.00
3 UNLEADED 3 96.00
4 PREMIUM 96.00
I60A00
AUG 19, 2022 8:54 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1
4 PTS 10000 2 UNLEADED 2 TURBN 4 PTS 10000 3 UNLEADED 3
4 PTS 10000 4 PREMIUM 4 PTS 10000
I60400
AUG 19, 2022 8:54 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 10000
2 UNLEADED 2 TURBN 10000
3 UNLEADED 3 10000
4 PREMIUM 10000
I60500
AUG 19, 2022 8:54 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 10000 8079 5061 1973
2 UNLEADED 2 TURBN 10000 8079 5061 1973
3 UNLEADED 3 10000 8079 5061 1973
4 PREMIUM 10000 8079 5061 1973
I60600
AUG 19, 2022 8:54 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 10000 0 0 0
0 8079 0 0
0 0 5061 0
0 0 0 1973
0 0 0 0
2 UNLEADED 2 TURBN 10000 0 0 0
0 8079 0 0
0 0 5061 0
0 0 0 1973
0 0 0 0
3 UNLEADED 3 10000 0 0 0
0 8079 0 0
0 0 5061 0
0 0 0 1973
0 0 0 0
4 PREMIUM 10000 0 0 0
0 8079 0 0
0 0 5061 0
0 0 0 1973
0 0 0 0
I61500
AUG 19, 2022 8:54 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED 1 NO
2 UNLEADED 2 TURBN NO
3 UNLEADED 3 NO
4 PREMIUM NO
I62F00
AUG 19, 2022 8:54 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 1 4.0 IN.
2 UNLEADED 2 TURBN 4.0 IN.
3 UNLEADED 3 4.0 IN.
4 PREMIUM 4.0 IN.
I62700
AUG 19, 2022 8:54 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 2.5
2 UNLEADED 2 TURBN 2.5
3 UNLEADED 3 2.5
4 PREMIUM 2.5
I64200
AUG 19, 2022 8:54 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED 1 LOW
2 UNLEADED 2 TURBN LOW
3 UNLEADED 3 LOW
4 PREMIUM LOW
I62400
AUG 19, 2022 8:54 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 3.0
2 UNLEADED 2 TURBN 3.0
3 UNLEADED 3 3.0
4 PREMIUM 3.0
I62800
AUG 19, 2022 8:54 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 10000
2 UNLEADED 2 TURBN 10000
3 UNLEADED 3 10000
4 PREMIUM 10000
I62300
AUG 19, 2022 8:54 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 9000
2 UNLEADED 2 TURBN 9000
3 UNLEADED 3 9000
4 PREMIUM 9000
I62200
AUG 19, 2022 8:54 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 9500
2 UNLEADED 2 TURBN 9500
3 UNLEADED 3 9500
4 PREMIUM 9500
I62900
AUG 19, 2022 8:54 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 2000
2 UNLEADED 2 TURBN 2000
3 UNLEADED 3 2000
4 PREMIUM 2000
I62100
AUG 19, 2022 8:54 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 1000
2 UNLEADED 2 TURBN 1000
3 UNLEADED 3 1000
4 PREMIUM 1000
I62600
AUG 19, 2022 8:54 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 99
2 UNLEADED 2 TURBN 99
3 UNLEADED 3 99
4 PREMIUM 99
I62500
AUG 19, 2022 8:54 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 99
2 UNLEADED 2 TURBN 99
3 UNLEADED 3 99
4 PREMIUM 99
I60800
AUG 19, 2022 8:54 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 0.00
2 UNLEADED 2 TURBN 0.00
3 UNLEADED 3 0.00
4 PREMIUM 0.00
I60B00
AUG 19, 2022 8:54 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
AUG 19, 2022 8:54 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 1 0.00
2 UNLEADED 2 TURBN 0.00
3 UNLEADED 3 0.00
4 PREMIUM 0.00
I61200
AUG 19, 2022 8:54 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED 1 NONE NONE
2 UNLEADED 2 TURBN NONE NONE
3 UNLEADED 3 NONE NONE
4 PREMIUM NONE NONE
I63600
AUG 19, 2022 8:54 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 0
2 UNLEADED 2 TURBN 0
3 UNLEADED 3 0
4 PREMIUM 0
I62A00
AUG 19, 2022 8:54 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 0
2 UNLEADED 2 TURBN 0
3 UNLEADED 3 0
4 PREMIUM 0
I62C00
AUG 19, 2022 8:54 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED 1 STANDARD
2 UNLEADED 2 TURBN STANDARD
3 UNLEADED 3 STANDARD
4 PREMIUM STANDARD
I62D00
AUG 19, 2022 8:54 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED 1 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 UNLEADED 2 TURBN GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 UNLEADED 3 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
AUG 19, 2022 8:54 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED 1 OFF OFF
2 UNLEADED 2 TURBN OFF OFF
3 UNLEADED 3 OFF OFF
4 PREMIUM OFF OFF
I63000
AUG 19, 2022 8:54 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED 1 OFF
2 UNLEADED 2 TURBN OFF
3 UNLEADED 3 OFF
4 PREMIUM OFF
I63200
AUG 19, 2022 8:54 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED 1 OFF
2 UNLEADED 2 TURBN OFF
3 UNLEADED 3 OFF
4 PREMIUM OFF
I61000
AUG 19, 2022 8:54 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1 2
2 UNLEADED 2 TURBN 2
3 UNLEADED 3 2
4 PREMIUM 2
I63A00
AUG 19, 2022 8:54 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 1 10.00%
2 UNLEADED 2 TURBN 10.00%
3 UNLEADED 3 10.00%
4 PREMIUM 3.00%
I61100
AUG 19, 2022 8:54 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
NOV 10, 2003
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
AUG 19, 2022 8:54 AM
CSLD PROBABLITY OF DETECTION
I61400
AUG 19, 2022 8:54 AM
CSLD CLIMATE FACTOR
I61600
AUG 19, 2022 8:54 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED 1 IMMEDIATE
2 UNLEADED 2 TURBN IMMEDIATE
3 UNLEADED 3 IMMEDIATE
4 PREMIUM IMMEDIATE
I61A00
AUG 19, 2022 8:54 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED 1 DISABLED
2 UNLEADED 2 TURBN DISABLED
3 UNLEADED 3 DISABLED
4 PREMIUM DISABLED
I61B00
AUG 19, 2022 8:54 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
AUG 19, 2022 8:54 AM
CSLD REPORT ONLY
I62B00
AUG 19, 2022 8:54 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED 1 ??? 0, 0
2 UNLEADED 2 TURBN ??? 0, 0
3 UNLEADED 3 ??? 0, 0
4 PREMIUM ??? 0, 0
I63300
AUG 19, 2022 8:54 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
AUG 19, 2022 8:54 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 0
2 UNLEADED 2 TURBN 0
3 UNLEADED 3 0
4 PREMIUM 0
I63500
AUG 19, 2022 8:54 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1 1
2 UNLEADED 2 TURBN 1
3 UNLEADED 3 1
4 PREMIUM 1
I63900
AUG 19, 2022 8:54 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED 1
END FACTOR: NONE
2 UNLEADED 2 TURBN
END FACTOR: NONE
3 UNLEADED 3
END FACTOR: NONE
4 PREMIUM
END FACTOR: NONE
I78000
AUG 19, 2022 8:54 AM
PRESSURE LINE LEAK SETUP
Q 1:87 REG UNL
TYP:2.0/3.0IN FIBERGLASS
2.0IN DIA LEN: 320 FEET
3.0IN DIA LEN: 0 FEET
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE : 0 PSI
T 1:UNLEADED 1
DISPENSE MODE:
STANDARD
SENSOR: NON-VENTED
PRESSURE OFFSET: 0.0PSI
MECHANICAL BLENDER: NO
Q 2:92 PREM UNL
TYP:2.0/3.0IN FIBERGLASS
2.0IN DIA LEN: 300 FEET
3.0IN DIA LEN: 0 FEET
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE : 0 PSI
T 4:PREMIUM
DISPENSE MODE:
STANDARD
SENSOR: NON-VENTED
PRESSURE OFFSET: 0.0PSI
MECHANICAL BLENDER: NO
I77700
AUG 19, 2022 8:54 AM
I77800
AUG 19, 2022 8:54 AM
I78C00
AUG 19, 2022 8:54 AM
I78300
AUG 19, 2022 8:54 AM
I78F00
AUG 19, 2022 8:54 AM
PRESSURE LINE LEAK DISPENSE THRESHOLD
LINE LOW PRESSURE
Q 1:87 REG UNL 0 PSI
Q 2:92 PREM UNL 0 PSI
Q 3: 0 PSI
I78700
AUG 19, 2022 8:54 AM
PRESSURE LLD SETUP REPORT
Q 1:87 REG UNL
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 5:FUEL ALARM
L 8:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L15:FUEL ALARM
L16:FUEL ALARM
L17:FUEL ALARM
L18:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
PRESSURE LINE LEAK
ALL:PLLD OPEN ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
Q 2:92 PREM UNL
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 5:FUEL ALARM
L 8:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L15:FUEL ALARM
L16:FUEL ALARM
L17:FUEL ALARM
L18:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
PRESSURE LINE LEAK
ALL:PLLD OPEN ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD SETUP WARN
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
Q 3:
- NO ALARM ASSIGNMENTS -
I70200
AUG 19, 2022 8:54 AM
LIQUID LABEL
DEVICE LABEL
1 87 REG UNL ANNULAR
2 87 REG UNL STP
3 87 REG UNL FILL S
4 87 REG UNL 2 ANNULAR
5 87 REG UNL 2 SYPHON
6 87 REG UNL M FILL
7 87 REG UNL 3 ANNULAR
8 87 REG UNL 3 SYPHON
9 87 REG UNL N FILL
10 91 PREM UNL ANNULAR
11 91 PEM UNL FILL
12 91 PREM UNL STP
13 DIRP 1-2
14 DISP 3-4
15 DISP 5-6
16 DISP 7-8
17 DISP 9-10
18 DISP 11-12
19
20
21
22
23
24
I70300
AUG 19, 2022 8:54 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87 REG UNL ANNULAR TRI-STATE (SINGLE FLOAT)
2 87 REG UNL STP TRI-STATE (SINGLE FLOAT)
3 87 REG UNL FILL S TRI-STATE (SINGLE FLOAT)
4 87 REG UNL 2 ANNULAR TRI-STATE (SINGLE FLOAT)
5 87 REG UNL 2 SYPHON TRI-STATE (SINGLE FLOAT)
6 87 REG UNL M FILL TRI-STATE (SINGLE FLOAT)
7 87 REG UNL 3 ANNULAR TRI-STATE (SINGLE FLOAT)
8 87 REG UNL 3 SYPHON TRI-STATE (SINGLE FLOAT)
9 87 REG UNL N FILL TRI-STATE (SINGLE FLOAT)
10 91 PREM UNL ANNULAR TRI-STATE (SINGLE FLOAT)
11 91 PEM UNL FILL TRI-STATE (SINGLE FLOAT)
12 91 PREM UNL STP TRI-STATE (SINGLE FLOAT)
13 DIRP 1-2 TRI-STATE (SINGLE FLOAT)
14 DISP 3-4 TRI-STATE (SINGLE FLOAT)
15 DISP 5-6 TRI-STATE (SINGLE FLOAT)
16 DISP 7-8 TRI-STATE (SINGLE FLOAT)
17 DISP 9-10 TRI-STATE (SINGLE FLOAT)
18 DISP 11-12 TRI-STATE (SINGLE FLOAT)
19 TRI-STATE (SINGLE FLOAT)
20 TRI-STATE (SINGLE FLOAT)
21 TRI-STATE (SINGLE FLOAT)
22 TRI-STATE (SINGLE FLOAT)
23 TRI-STATE (SINGLE FLOAT)
24 TRI-STATE (SINGLE FLOAT)
I70400
AUG 19, 2022 8:54 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 87 REG UNL ANNULAR ANNULAR SPACE
2 87 REG UNL STP STP SUMP
3 87 REG UNL FILL S PIPING SUMP
4 87 REG UNL 2 ANNULAR ANNULAR SPACE
5 87 REG UNL 2 SYPHON STP SUMP
6 87 REG UNL M FILL PIPING SUMP
7 87 REG UNL 3 ANNULAR ANNULAR SPACE
8 87 REG UNL 3 SYPHON PIPING SUMP
9 87 REG UNL N FILL PIPING SUMP
10 91 PREM UNL ANNULAR ANNULAR SPACE
11 91 PEM UNL FILL STP SUMP
12 91 PREM UNL STP PIPING SUMP
13 DIRP 1-2 DISPENSER PAN
14 DISP 3-4 DISPENSER PAN
15 DISP 5-6 DISPENSER PAN
16 DISP 7-8 DISPENSER PAN
17 DISP 9-10 DISPENSER PAN
18 DISP 11-12 DISPENSER PAN
19 OTHER SENSORS
20 OTHER SENSORS
21 OTHER SENSORS
22 OTHER SENSORS
23 OTHER SENSORS
24 OTHER SENSORS
I74200
AUG 19, 2022 8:54 AM
I74300
AUG 19, 2022 8:54 AM
I74400
AUG 19, 2022 8:54 AM
I74700
AUG 19, 2022 8:54 AM
I74800
AUG 19, 2022 8:54 AM
I74900
AUG 19, 2022 8:54 AM
I7BC00
AUG 19, 2022 8:54 AM
I80200
AUG 19, 2022 8:54 AM
I80300
AUG 19, 2022 8:54 AM
I80400
AUG 19, 2022 8:54 AM
I80700
AUG 19, 2022 8:54 AM
RELAY LABEL
DEVICE LABEL
1
2
3 ALARM
4
I80900
AUG 19, 2022 8:54 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 NORMALLY OPEN
2 NORMALLY OPEN
3 ALARM NORMALLY OPEN
4 NORMALLY OPEN
I80B00
AUG 19, 2022 8:54 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 NONE
2 NONE
3 ALARM NONE
4 NONE
I80A00
AUG 19, 2022 8:54 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 STANDARD
2 STANDARD
3 ALARM STANDARD
4 STANDARD
I80C00
AUG 19, 2022 8:54 AM
I80800
AUG 19, 2022 8:54 AM
RELAY SETUP REPORT
R 1:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 2:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 3:ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
AUG 19, 2022 8:55 AM
EDIM:1 VR:349866-001-E TD:19.10.30.16.33
I79100
AUG 19, 2022 8:55 AM
I72300
AUG 19, 2022 8:55 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 DIS 1-2 AIR FLOW METER
02 DIS 3-4 AIR FLOW METER
03 DIS 5-6 AIR FLOW METER
04 DIS 7-8 AIR FLOW METER
05 DIS 9-10 AIR FLOW METER
06 DIS 11-12 AIR FLOW METER
07 VAPOR PRESS SENSOR VAPOR PRESSURE
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
AUG 19, 2022 8:55 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
AUG 19, 2022 8:55 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
AUG 19, 2022 8:55 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
VAPOR PROCESSOR TYPE
NONE
IV4700
AUG 19, 2022 8:55 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
ASSESSMENT TIME
START TIME: 11:59 PM
TIME DELAY MINUTES: 1
IV5200
AUG 19, 2022 8:55 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
ACCEPT HIGH ORVR: NO
IV4A00
AUG 19, 2022 8:55 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 00 01 01 UU BLEND3
02 01 02 01 UU BLEND3
03 02 03 02 UU BLEND3
04 03 04 02 UU BLEND3
05 04 05 03 UU BLEND3
06 05 06 03 UU BLEND3
07 06 07 04 UU BLEND3
08 07 08 04 UU BLEND3
09 08 09 05 UU BLEND3
10 09 10 05 UU BLEND3
11 10 11 06 UU BLEND3
12 11 12 06 UU BLEND3
IV4B00
AUG 19, 2022 8:55 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
00 01 00/01 03/01 09/01 xx/xx
01 01 00/02 03/02 09/02 xx/xx
02 02 00/03 03/03 09/03 xx/xx
03 02 00/04 03/04 09/04 xx/xx
04 03 00/05 03/05 09/05 xx/xx
05 03 00/06 03/06 09/06 xx/xx
06 04 00/07 03/07 09/07 xx/xx
07 04 00/08 03/08 09/08 xx/xx
08 05 00/09 03/09 09/09 xx/xx
09 05 00/10 03/10 09/10 xx/xx
10 06 00/11 03/11 09/11 xx/xx
11 06 00/12 03/12 09/12 xx/xx
IV4900
AUG 19, 2022 8:55 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
AUG 19, 2022 8:55 AM
ISD VERSION: 01.05
Grand Ave Alarm History
Responses Received:
I10200
AUG 19, 2022 8:56 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 INTERSTITIAL BD 203872 204303
2 INTERSTITIAL BD 203464 203819
3 INTERSTITIAL BD 203153 203310
4 PLLD SENSOR BD 3932 3952
5 4 PROBE / G.T. 165488 165770
6 8SMARTSENSOR BD 40245 40268
7 UNUSED 9801818 9704645
8 UNUSED 9790023 9690081
9 RELAY BOARD 15068 15100
10 PLLD POWER BD 101943 102061
11 UNUSED 9799782 9700603
12 UNUSED 9788700 9683577
13 UNUSED 9786792 9694332
14 UNUSED 9794241 9709175
15 UNUSED 9788884 9686411
16 UNUSED 9778883 9685017
COMM 1 ELEC DISP INT. 102717 102915
COMM 2 RS232 SERIAL BD 15091 15123
COMM 3 SERIAL SAT BD 488929 489474
COMM 4 UNUSED 9790264 9704366
COMM 5 RS485 SERIAL BD 69401 69554
COMM 6 RS232 SERIAL BD 15114 15146
I90200
AUG 19, 2022 8:57 AM
SOFTWARE REVISION LEVEL
VERSION 336.01
SOFTWARE# 346336-100-B
CREATED - 20.04.26.20.30
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 19, 2022 8:57 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 7-19-22 3:29AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 7-19-22 3:05AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 7-16-22 2:16AM
E 1 OTHER G COMMUNICATION ALARM ALARM 7-16-22 2:15AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 7-14-22 5:29AM
E 1 OTHER G COMMUNICATION ALARM ALARM 7-14-22 5:22AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 7-14-22 2:58AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 7-14-22 1:09AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 7-14-22 12:46AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 7-14-22 12:35AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 7-09-22 5:54AM
E 1 OTHER G COMMUNICATION ALARM ALARM 7-09-22 5:42AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 7-03-22 6:13AM
E 1 OTHER G COMMUNICATION ALARM ALARM 7-03-22 6:13AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 7-02-22 3:11AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 7-02-22 3:06AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 6-30-22 3:00AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 6-30-22 1:55AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 6-30-22 1:33AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 6-30-22 1:08AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 6-27-22 11:32PM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 6-27-22 11:30PM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 6-16-22 12:13AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 6-15-22 11:52PM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 6-10-22 12:43AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 6-10-22 12:35AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 6-09-22 11:51PM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 6-09-22 11:27PM
L 6 PIPE 87 REG UNL M FILL FUEL ALARM CLEAR 5-23-22 8:56AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 5-21-22 11:21PM
E 1 OTHER G COMMUNICATION ALARM ALARM 5-21-22 11:16PM
L 3 PIPE 87 REG UNL FILL S FUEL ALARM CLEAR 5-12-22 7:36PM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 5-12-22 4:07AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 5-12-22 4:03AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 5-07-22 3:34AM
E 1 OTHER G COMMUNICATION ALARM ALARM 5-07-22 3:33AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 5-07-22 3:29AM
E 1 OTHER G COMMUNICATION ALARM ALARM 5-07-22 3:27AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM CLEAR 5-03-22 2:18AM
T 1 TANK UNLEADED 1 SUDDEN LOSS ALARM ALARM 5-03-22 1:34AM
T 1 TANK UNLEADED 1 LOW PRODUCT ALARM CLEAR 5-03-22 12:49AM
T 1 TANK UNLEADED 1 LOW PRODUCT ALARM ALARM 5-02-22 6:19PM
E 1 OTHER G COMMUNICATION ALARM CLEAR 4-28-22 5:28AM
E 1 OTHER G COMMUNICATION ALARM ALARM 4-28-22 5:27AM
L 3 PIPE 87 REG UNL FILL S FUEL ALARM ALARM 4-22-22 10:00PM
L 6 PIPE 87 REG UNL M FILL FUEL ALARM ALARM 4-22-22 1:09PM
Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 4-22-22 6:28AM
Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 4-22-22 6:28AM
L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM CLEAR 4-22-22 6:28AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 4-22-22 4:59AM
I11200
AUG 19, 2022 8:57 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED ALARM 8-19-22 8:15AM
T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 8-18-22 8:10PM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-18-22 3:31PM
T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 8-16-22 12:02PM
T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 8-16-22 9:38AM
SYSTEM PRINTER ERROR CLEAR 8-15-22 1:24PM
SYSTEM PAPER OUT CLEAR 8-15-22 1:24PM
SYSTEM PRINTER ERROR ALARM 8-15-22 1:22PM
SYSTEM PAPER OUT ALARM 8-15-22 1:22PM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-12-22 4:45PM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-10-22 7:37PM
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED CLEAR 8-08-22 1:46PM
T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 8-08-22 1:38PM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-08-22 1:37PM
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED ALARM 8-08-22 11:39AM
T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 8-08-22 6:41AM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-06-22 11:37PM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-05-22 10:55AM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-04-22 10:04AM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-02-22 11:49PM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-01-22 12:01PM
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED CLEAR 8-01-22 11:59AM
T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 8-01-22 11:54AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:46AM
SYSTEM PAPER OUT CLEAR 8-01-22 11:46AM
SYSTEM PAPER OUT ALARM 8-01-22 11:45AM
SYSTEM PRINTER ERROR ALARM 8-01-22 11:45AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:44AM
SYSTEM PAPER OUT CLEAR 8-01-22 11:44AM
SYSTEM PRINTER ERROR ALARM 8-01-22 11:44AM
SYSTEM PAPER OUT ALARM 8-01-22 11:44AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:44AM
SYSTEM PAPER OUT CLEAR 8-01-22 11:44AM
SYSTEM PRINTER ERROR ALARM 8-01-22 11:44AM
SYSTEM PAPER OUT ALARM 8-01-22 11:44AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:44AM
SYSTEM PAPER OUT CLEAR 8-01-22 11:44AM
SYSTEM PAPER OUT ALARM 8-01-22 11:44AM
SYSTEM PRINTER ERROR ALARM 8-01-22 11:43AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:43AM
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED ALARM 8-01-22 10:00AM
T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 7-31-22 10:02PM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 7-31-22 1:51AM
SYSTEM PRINTER ERROR ALARM 7-31-22 1:45AM
SYSTEM PRINTER ERROR CLEAR 7-31-22 1:45AM
SYSTEM PRINTER ERROR ALARM 7-31-22 1:45AM
SYSTEM PRINTER ERROR CLEAR 7-31-22 1:44AM
SYSTEM PAPER OUT CLEAR 7-31-22 1:44AM
SYSTEM PAPER OUT ALARM 7-31-22 1:44AM
SYSTEM PRINTER ERROR ALARM 7-31-22 1:44AM
I20600
AUG 19, 2022 8:57 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
TANK ALARM HISTORY
TANK 1 UNLEADED 1
SETUP DATA WARNING MAR 24, 2021 9:18 AM
LOW PRODUCT ALARM MAY 2, 2022 6:19 PM
SUDDEN LOSS ALARM JUL 19, 2022 3:05 AM
JUL 14, 2022 1:09 AM
JUL 14, 2022 12:35 AM
HIGH PRODUCT ALARM MAR 24, 2021 9:18 AM
DELIVERY NEEDED AUG 18, 2022 8:10 PM
AUG 16, 2022 9:38 AM
AUG 8, 2022 6:41 AM
TANK 2 UNLEADED 2 TURBN
SETUP DATA WARNING MAR 24, 2021 9:20 AM
HIGH PRODUCT ALARM MAR 24, 2021 9:20 AM
DELIVERY NEEDED AUG 19, 2022 8:15 AM
AUG 8, 2022 11:39 AM
AUG 1, 2022 10:00 AM
TANK 3 UNLEADED 3
SETUP DATA WARNING MAR 24, 2021 9:22 AM
HIGH PRODUCT ALARM MAR 24, 2021 9:22 AM
DELIVERY NEEDED JUL 16, 2022 8:06 PM
MAY 2, 2022 11:46 AM
JAN 24, 2022 1:02 PM
TANK 4 PREMIUM
SETUP DATA WARNING MAR 24, 2021 9:24 AM
HIGH PRODUCT ALARM MAR 24, 2021 9:24 AM
DELIVERY NEEDED AUG 18, 2022 3:31 PM
AUG 10, 2022 7:37 PM
AUG 6, 2022 11:37 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
AUG 19, 2022 8:57 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1:87 REG UNL
APR 22, 2022 2:00 AM PLLD SHUTDOWN ALARM
MAR 20, 2022 6:52 AM PLLD SHUTDOWN ALARM
MAR 13, 2022 3:56 AM PLLD SHUTDOWN ALARM
MAR 4, 2022 3:21 AM PLLD SHUTDOWN ALARM
FEB 9, 2022 11:53 PM PLLD SHUTDOWN ALARM
DEC 27, 2021 1:57 PM PLLD SHUTDOWN ALARM
DEC 24, 2021 2:26 AM PLLD SHUTDOWN ALARM
DEC 23, 2021 6:15 PM PLLD SHUTDOWN ALARM
DEC 22, 2021 8:29 PM PLLD SHUTDOWN ALARM
AUG 24, 2021 10:44 AM PLLD SHUTDOWN ALARM
Q 2:92 PREM UNL
APR 22, 2022 2:00 AM PLLD SHUTDOWN ALARM
MAR 20, 2022 6:52 AM PLLD SHUTDOWN ALARM
MAR 13, 2022 3:56 AM PLLD SHUTDOWN ALARM
MAR 4, 2022 3:21 AM PLLD SHUTDOWN ALARM
FEB 9, 2022 11:53 PM PLLD SHUTDOWN ALARM
DEC 27, 2021 1:57 PM PLLD SHUTDOWN ALARM
DEC 24, 2021 2:26 AM PLLD SHUTDOWN ALARM
DEC 23, 2021 6:15 PM PLLD SHUTDOWN ALARM
DEC 22, 2021 8:29 PM PLLD SHUTDOWN ALARM
AUG 24, 2021 11:13 AM PLLD SHUTDOWN ALARM
I30200
AUG 19, 2022 8:57 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 REG UNL ANNULAR
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
AUG 24, 2021 10:02 AM FUEL ALARM
AUG 24, 2021 9:47 AM FUEL ALARM
2 87 REG UNL STP
MAR 13, 2022 3:56 AM SENSOR OUT ALARM
DEC 23, 2021 7:00 PM SENSOR OUT ALARM
DEC 23, 2021 6:34 PM SENSOR OUT ALARM
3 87 REG UNL FILL S
APR 22, 2022 10:00 PM FUEL ALARM
MAR 28, 2022 9:38 AM FUEL ALARM
MAR 4, 2022 3:24 AM FUEL ALARM
4 87 REG UNL 2 ANNULAR
DEC 23, 2021 6:35 PM SENSOR OUT ALARM
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
AUG 24, 2021 9:45 AM FUEL ALARM
5 87 REG UNL 2 SYPHON
APR 22, 2022 2:00 AM FUEL ALARM
MAR 20, 2022 6:52 AM FUEL ALARM
MAR 4, 2022 3:21 AM FUEL ALARM
6 87 REG UNL M FILL
APR 22, 2022 1:09 PM FUEL ALARM
MAR 20, 2022 2:12 PM FUEL ALARM
DEC 15, 2021 10:32 AM FUEL ALARM
7 87 REG UNL 3 ANNULAR
DEC 22, 2021 8:58 PM SENSOR OUT ALARM
AUG 24, 2021 10:08 AM SENSOR OUT ALARM
AUG 24, 2021 9:43 AM FUEL ALARM
8 87 REG UNL 3 SYPHON
DEC 23, 2021 6:20 PM SENSOR OUT ALARM
AUG 24, 2021 10:08 AM SENSOR OUT ALARM
AUG 24, 2021 9:40 AM FUEL ALARM
9 87 REG UNL N FILL
DEC 14, 2021 12:03 PM FUEL ALARM
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
AUG 24, 2021 9:48 AM FUEL ALARM
10 91 PREM UNL ANNULAR
DEC 23, 2021 6:32 PM SENSOR OUT ALARM
DEC 22, 2021 8:58 PM SENSOR OUT ALARM
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
11 91 PEM UNL FILL
JAN 19, 2022 3:54 PM FUEL ALARM
JAN 8, 2022 2:24 AM FUEL ALARM
JAN 8, 2022 1:53 AM FUEL ALARM
12 91 PREM UNL STP
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
AUG 24, 2021 9:41 AM FUEL ALARM
MAR 24, 2021 9:15 AM FUEL ALARM
13 DIRP 1-2
AUG 24, 2021 10:08 AM SENSOR OUT ALARM
AUG 24, 2021 9:50 AM FUEL ALARM
MAR 24, 2021 9:16 AM FUEL ALARM
14 DISP 3-4
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
AUG 24, 2021 9:50 AM FUEL ALARM
MAR 24, 2021 9:16 AM FUEL ALARM
15 DISP 5-6
DEC 23, 2021 6:39 PM SENSOR OUT ALARM
DEC 23, 2021 6:36 PM SENSOR OUT ALARM
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
16 DISP 7-8
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
AUG 24, 2021 9:52 AM FUEL ALARM
MAR 24, 2021 9:16 AM FUEL ALARM
17 DISP 9-10
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
AUG 24, 2021 9:53 AM FUEL ALARM
MAR 24, 2021 9:16 AM FUEL ALARM
18 DISP 11-12
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
AUG 24, 2021 9:54 AM FUEL ALARM
MAR 24, 2021 9:16 AM FUEL ALARM
I31600
AUG 19, 2022 8:57 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DIS 1-2
2 DIS 3-4
3 DIS 5-6
4 DIS 7-8
5 DIS 9-10
6 DIS 11-12
7 VAPOR PRESS SENSOR
I40200
AUG 19, 2022 8:57 AM
I40300
AUG 19, 2022 8:57 AM
I34200
AUG 19, 2022 8:57 AM
I34700
AUG 19, 2022 8:57 AM
IV0100
AUG 19, 2022 8:57 AM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-01-30 00:02:58 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.08
21-11-10 00:03:07 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.83
21-11-09 00:03:13 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.86
21-09-04 00:02:55 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 1:DIS 1-2
21-05-14 00:01:53 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.94
21-05-13 00:01:52 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.81
21-05-12 00:02:00 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.94
21-05-11 00:01:57 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.81
21-05-10 00:02:07 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.64
21-05-09 00:02:07 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.66
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-06-17 00:02:08 READINESS ISD:PP EVR:PP ISD & EVR READY
22-06-16 10:46:28 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-06-16 10:46:28 ISD STARTUP
22-06-16 10:46:11 ISD SHUTDOWN
22-04-25 13:16:00 TIME CHANGE DETECTED AT: 22-04-25 14:16:15
22-04-03 03:00:00 TIME CHANGE DETECTED AT: 22-04-03 02:00:13
22-03-28 13:35:00 TIME CHANGE DETECTED AT: 22-03-28 12:33:32
22-02-05 00:02:13 READINESS ISD:PP EVR:PP ISD & EVR READY
22-02-04 00:02:10 READINESS ISD:PP EVR:NP EVR READINESS PENDING
22-02-03 00:02:11 READINESS ISD:PP EVR:NP EVR READINESS PENDING
Grand Ave Alarm History After
Responses Received:
I10200
AUG 19, 2022 12:49 PM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 INTERSTITIAL BD 203872 203302
2 INTERSTITIAL BD 203464 203302
3 INTERSTITIAL BD 203153 202771
4 PLLD SENSOR BD 3932 3947
5 4 PROBE / G.T. 165488 164990
6 8SMARTSENSOR BD 40245 40146
7 UNUSED 9801818 9674786
8 UNUSED 9790023 9655765
9 RELAY BOARD 15068 15045
10 PLLD POWER BD 101943 101759
11 UNUSED 9799782 9641473
12 UNUSED 9788700 9648748
13 UNUSED 9786792 9648979
14 UNUSED 9794241 9647404
15 UNUSED 9788884 9647566
16 UNUSED 9778883 9645967
COMM 1 ELEC DISP INT. 102717 102516
COMM 2 RS232 SERIAL BD 15091 15092
COMM 3 SERIAL SAT BD 488929 487992
COMM 4 UNUSED 9790264 9638137
COMM 5 RS485 SERIAL BD 69401 69242
COMM 6 RS232 SERIAL BD 15114 15092
I90200
AUG 19, 2022 12:49 PM
SOFTWARE REVISION LEVEL
VERSION 336.01
SOFTWARE# 346336-100-B
CREATED - 20.04.26.20.30
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 19, 2022 12:49 PM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 3 PIPE 87 REG UNL FILL S FUEL ALARM CLEAR 8-19-22 12:47PM
L 3 PIPE 87 REG UNL FILL S FUEL ALARM ALARM 8-19-22 12:37PM
Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-19-22 11:52AM
Q 2 OTHER 92 PREM UNL GROSS LINE FAIL CLEAR 8-19-22 11:52AM
Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-19-22 11:52AM
Q 1 OTHER 87 REG UNL GROSS LINE FAIL CLEAR 8-19-22 11:52AM
Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-19-22 11:29AM
Q 1 OTHER 87 REG UNL GROSS LINE FAIL ALARM 8-19-22 11:29AM
Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-19-22 10:20AM
Q 2 OTHER 92 PREM UNL GROSS LINE FAIL ALARM 8-19-22 10:20AM
Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-19-22 10:12AM
Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-19-22 10:12AM
L16 DISP PAN DISP 7-8 FUEL ALARM CLEAR 8-19-22 10:12AM
L16 DISP PAN DISP 7-8 FUEL ALARM ALARM 8-19-22 9:59AM
Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-19-22 9:59AM
Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-19-22 9:59AM
Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-19-22 9:56AM
Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-19-22 9:56AM
L 4 ANNULAR 87 REG UNL 2 ANNULAR SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L 3 PIPE 87 REG UNL FILL S SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L 2 STP SUMP 87 REG UNL STP SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L 1 ANNULAR 87 REG UNL ANNULAR SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L 8 PIPE 87 REG UNL 3 SYPHON SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L 7 ANNULAR 87 REG UNL 3 ANNULAR SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L 6 PIPE 87 REG UNL M FILL SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L 5 STP SUMP 87 REG UNL 2 SYPHON SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L12 PIPE 91 PREM UNL STP SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L11 STP SUMP 91 PEM UNL FILL SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L10 ANNULAR 91 PREM UNL ANNULAR SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L14 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L 9 PIPE 87 REG UNL N FILL SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L13 DISP PAN DIRP 1-2 SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 8-19-22 9:56AM
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L12 PIPE 91 PREM UNL STP SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L11 STP SUMP 91 PEM UNL FILL SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L10 ANNULAR 91 PREM UNL ANNULAR SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L14 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L13 DISP PAN DIRP 1-2 SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L 9 PIPE 87 REG UNL N FILL SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L 4 ANNULAR 87 REG UNL 2 ANNULAR SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L 3 PIPE 87 REG UNL FILL S SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L 2 STP SUMP 87 REG UNL STP SENSOR OUT ALARM ALARM 8-19-22 9:55AM
L 8 PIPE 87 REG UNL 3 SYPHON SENSOR OUT ALARM ALARM 8-19-22 9:55AM
I11200
AUG 19, 2022 12:50 PM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 8-19-22 9:00AM
SYSTEM PAPER OUT CLEAR 8-19-22 9:00AM
SYSTEM PRINTER ERROR ALARM 8-19-22 8:59AM
SYSTEM PAPER OUT ALARM 8-19-22 8:59AM
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED ALARM 8-19-22 8:15AM
T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 8-18-22 8:10PM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-18-22 3:31PM
T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 8-16-22 12:02PM
T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 8-16-22 9:38AM
SYSTEM PRINTER ERROR CLEAR 8-15-22 1:24PM
SYSTEM PAPER OUT CLEAR 8-15-22 1:24PM
SYSTEM PRINTER ERROR ALARM 8-15-22 1:22PM
SYSTEM PAPER OUT ALARM 8-15-22 1:22PM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-12-22 4:45PM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-10-22 7:37PM
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED CLEAR 8-08-22 1:46PM
T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 8-08-22 1:38PM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-08-22 1:37PM
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED ALARM 8-08-22 11:39AM
T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 8-08-22 6:41AM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-06-22 11:37PM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-05-22 10:55AM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-04-22 10:04AM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-02-22 11:49PM
T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-01-22 12:01PM
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED CLEAR 8-01-22 11:59AM
T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 8-01-22 11:54AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:46AM
SYSTEM PAPER OUT CLEAR 8-01-22 11:46AM
SYSTEM PAPER OUT ALARM 8-01-22 11:45AM
SYSTEM PRINTER ERROR ALARM 8-01-22 11:45AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:44AM
SYSTEM PAPER OUT CLEAR 8-01-22 11:44AM
SYSTEM PRINTER ERROR ALARM 8-01-22 11:44AM
SYSTEM PAPER OUT ALARM 8-01-22 11:44AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:44AM
SYSTEM PAPER OUT CLEAR 8-01-22 11:44AM
SYSTEM PRINTER ERROR ALARM 8-01-22 11:44AM
SYSTEM PAPER OUT ALARM 8-01-22 11:44AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:44AM
SYSTEM PAPER OUT CLEAR 8-01-22 11:44AM
SYSTEM PAPER OUT ALARM 8-01-22 11:44AM
SYSTEM PRINTER ERROR ALARM 8-01-22 11:43AM
SYSTEM PRINTER ERROR CLEAR 8-01-22 11:43AM
T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED ALARM 8-01-22 10:00AM
T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 7-31-22 10:02PM
T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 7-31-22 1:51AM
SYSTEM PRINTER ERROR ALARM 7-31-22 1:45AM
SYSTEM PRINTER ERROR CLEAR 7-31-22 1:45AM
SYSTEM PRINTER ERROR ALARM 7-31-22 1:45AM
I20600
AUG 19, 2022 12:50 PM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
TANK ALARM HISTORY
TANK 1 UNLEADED 1
SETUP DATA WARNING MAR 24, 2021 9:18 AM
LOW PRODUCT ALARM MAY 2, 2022 6:19 PM
SUDDEN LOSS ALARM JUL 19, 2022 3:05 AM
JUL 14, 2022 1:09 AM
JUL 14, 2022 12:35 AM
HIGH PRODUCT ALARM MAR 24, 2021 9:18 AM
DELIVERY NEEDED AUG 18, 2022 8:10 PM
AUG 16, 2022 9:38 AM
AUG 8, 2022 6:41 AM
TANK 2 UNLEADED 2 TURBN
SETUP DATA WARNING MAR 24, 2021 9:20 AM
HIGH PRODUCT ALARM MAR 24, 2021 9:20 AM
DELIVERY NEEDED AUG 19, 2022 8:15 AM
AUG 8, 2022 11:39 AM
AUG 1, 2022 10:00 AM
TANK 3 UNLEADED 3
SETUP DATA WARNING MAR 24, 2021 9:22 AM
HIGH PRODUCT ALARM MAR 24, 2021 9:22 AM
DELIVERY NEEDED JUL 16, 2022 8:06 PM
MAY 2, 2022 11:46 AM
JAN 24, 2022 1:02 PM
TANK 4 PREMIUM
SETUP DATA WARNING MAR 24, 2021 9:24 AM
HIGH PRODUCT ALARM MAR 24, 2021 9:24 AM
DELIVERY NEEDED AUG 18, 2022 3:31 PM
AUG 10, 2022 7:37 PM
AUG 6, 2022 11:37 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
AUG 19, 2022 12:50 PM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1:87 REG UNL
AUG 19, 2022 11:29 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 11:29 AM GROSS LINE FAIL
AUG 19, 2022 9:59 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:55 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:52 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:52 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:51 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:50 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:49 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:49 AM PLLD SHUTDOWN ALARM
Q 2:92 PREM UNL
AUG 19, 2022 10:20 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 10:20 AM GROSS LINE FAIL
AUG 19, 2022 9:59 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:55 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:52 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:52 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:51 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:50 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:49 AM PLLD SHUTDOWN ALARM
AUG 19, 2022 9:49 AM PLLD SHUTDOWN ALARM
I30200
AUG 19, 2022 12:50 PM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 REG UNL ANNULAR
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:35 AM FUEL ALARM
AUG 19, 2022 9:35 AM FUEL ALARM
2 87 REG UNL STP
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:29 AM FUEL ALARM
MAR 13, 2022 3:56 AM SENSOR OUT ALARM
3 87 REG UNL FILL S
AUG 19, 2022 12:37 PM FUEL ALARM
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:33 AM FUEL ALARM
4 87 REG UNL 2 ANNULAR
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:47 AM FUEL ALARM
AUG 19, 2022 9:40 AM FUEL ALARM
5 87 REG UNL 2 SYPHON
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:30 AM FUEL ALARM
APR 22, 2022 2:00 AM FUEL ALARM
6 87 REG UNL M FILL
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:32 AM FUEL ALARM
APR 22, 2022 1:09 PM FUEL ALARM
7 87 REG UNL 3 ANNULAR
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:40 AM FUEL ALARM
AUG 19, 2022 9:37 AM FUEL ALARM
8 87 REG UNL 3 SYPHON
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:30 AM FUEL ALARM
DEC 23, 2021 6:20 PM SENSOR OUT ALARM
9 87 REG UNL N FILL
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:32 AM FUEL ALARM
DEC 14, 2021 12:03 PM FUEL ALARM
10 91 PREM UNL ANNULAR
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:46 AM FUEL ALARM
AUG 19, 2022 9:43 AM FUEL ALARM
11 91 PEM UNL FILL
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:31 AM FUEL ALARM
JAN 19, 2022 3:54 PM FUEL ALARM
12 91 PREM UNL STP
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:30 AM FUEL ALARM
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
13 DIRP 1-2
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:52 AM FUEL ALARM
AUG 24, 2021 10:08 AM SENSOR OUT ALARM
14 DISP 3-4
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:52 AM FUEL ALARM
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
15 DISP 5-6
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:50 AM FUEL ALARM
DEC 23, 2021 6:39 PM SENSOR OUT ALARM
16 DISP 7-8
AUG 19, 2022 9:59 AM FUEL ALARM
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:51 AM FUEL ALARM
17 DISP 9-10
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:49 AM FUEL ALARM
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
18 DISP 11-12
AUG 19, 2022 9:55 AM SENSOR OUT ALARM
AUG 19, 2022 9:49 AM FUEL ALARM
AUG 24, 2021 10:09 AM SENSOR OUT ALARM
I31600
AUG 19, 2022 12:50 PM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DIS 1-2
2 DIS 3-4
3 DIS 5-6
4 DIS 7-8
5 DIS 9-10
6 DIS 11-12
7 VAPOR PRESS SENSOR
I40200
AUG 19, 2022 12:50 PM
I40300
AUG 19, 2022 12:50 PM
I34200
AUG 19, 2022 12:50 PM
I34700
AUG 19, 2022 12:50 PM
IV0100
AUG 19, 2022 12:50 PM
243508 ARCO AM-PM
4203 MING AVE
BAKERSFIELD CA.
661-834-1076
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-01-30 00:02:58 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.08
21-11-10 00:03:07 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.83
21-11-09 00:03:13 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.86
21-09-04 00:02:55 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 1:DIS 1-2
21-05-14 00:01:53 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.94
21-05-13 00:01:52 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.81
21-05-12 00:02:00 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.94
21-05-11 00:01:57 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.81
21-05-10 00:02:07 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.64
21-05-09 00:02:07 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.66
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-08-19 09:54:16 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-08-19 09:54:16 ISD STARTUP
22-08-19 09:54:04 ISD SHUTDOWN
22-06-17 00:02:08 READINESS ISD:PP EVR:PP ISD & EVR READY
22-06-16 10:46:28 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-06-16 10:46:28 ISD STARTUP
22-06-16 10:46:11 ISD SHUTDOWN
22-04-25 13:16:00 TIME CHANGE DETECTED AT: 22-04-25 14:16:15
22-04-03 03:00:00 TIME CHANGE DETECTED AT: 22-04-03 02:00:13
22-03-28 13:35:00 TIME CHANGE DETECTED AT: 22-03-28 12:33:32