Loading...
HomeMy WebLinkAboutORD NO 3302ORDINANCE NO. 3302 AN ORDINANCE OF THE CITY OF BAKERSFIELD ADDING CHAPTER 15.40 TO THE BAKERSFIELD MUNICIPAL CODE RELATING TO UNREINFORCED MASONRY BUILDINGS. BE IT ORDAINED by the Council of the City of Bakersfield as follows: SECTION 1. Chapter 15.40 is hereby added to the Bakersfield Municipal Code to read as follows: CHAPTER 15.40 EARTHQUAKE HAZARD REDUCTION IN EXISTING UNREINFORCED MASONRY BEARING WALL BUILDINGS Sections: 15.40.005 15.40.010 15.40.020 15.40.030 15.40.040 15.40.050 15.40.060 15.40.070 15.40.080 15.40.090 15.40.100 15.40.110 Purpose. Scope. Definitions and notations. Materials of construction. Quality control. Allowable design values. Analysis and design. Detailed systems design requirements. Tables. Pointing. Acceptable span for diaphrams (Pigure A-l). Analysis of URM wall for in-plan shear force (Figure A-2). 15.40.005 Purpose. The purpose of this chapter is to promote public safety, health and welfare by reducing the risk of death or injury that may result from the effects of earthquakes on unreinforced masonry buildings. The provisions of this chapter establish minimum standards for structural seismic resistance primarily to reduce the risk of death or injury, but cannot prevent loss of life or injury or pre- vent earthquake damage to an existing building even though it com- plies with these standards. ORIGINAL 15.40.010 Scope. The provisions of these requirements shall apply to all buildings constructed prior to 1946 and having unreinforced masonry bearing walls as defined herein. It is recognized that strengthen- ing was done to many unreinforced masonry buildings following thee 1952 Kern County earthquake. The engineer or architect retained by the building owner and the city building official shall give full consideration to any strengthening done when analyzing the existing condition of the building as required by this chapter. Where strengthening was done which may not fully comply with the provi- sions of this chapter, approval may be granted by the building official if the building's condition complies with the intent of this chapter. Nothing in this chapter shall prevent the building owner, his architect or engineer from employing accepted alternative meth- ods to prove the minimum seismic safety of a building. In the event an alternative method is employed by the building owner, his architect or engineer which is not accepted by the city building official, the building owner shall have the right to appeal that decision to the Board of Building Appeals. This chapter provides for strengthening standards for unre- inforced buildings as defined in this chapter. This chapter shall not require existing electrical, plumbing, mechanical, fire safety systems, parking, disabled access or other existing non-conforming uses to be altered as a result of seismic strengthening unless they constitute a hazard to life. Exceptions: This chapter shall not apply to detached one or two family dwellings and detached multi-unit dwellings contain-- ing less than five (5) dwelling units and used solely for residen-- tial purposes, nor shall it apply to single story warehouse buildings used solely for storage purposes and occupied less than three (3) hours per day. 15.40.020 Definitions and notations. A. Definitions. For purposes of this chapter, the defini- tions set forth herein shall have the following meanings: 1. "Collar joint" is the vertical joint between wythes of the multi-wythe walls. 2. "Continuous inspection" means that an inspector has observed the work to the extent that he certifies the work has been done according to applicable plans and specifications without reservation. 3. "Crosswall" is a wood-framed wall sheathed with any of the materials described in Tables A1-D and A1-E. Other systems such as ductile moment resisting frames may be used as crosswalls provided that the yield deflection does not exceed one inch in each story height. A crosswall is not a shear wall. 4. "Diaphragm edge" is the intersection of the hori- zontal diaphragm and a shear wall. 5. "Moment-resisting frame" is a planar moment- resisting frame complying with the requirements of Section 2625 for reinforced concrete or Section 2722 (f) for structural steel of the Building Code. 6. "Open front" is an exterior building wall plane without a shear wall capable of resisting the required lateral forces. 7. "Shear wall" is a wall utilized to resist the required seismic forces parallel to the wall (not including crosswalls). All reinforced or unreinforced masonry or concrete walls shall be considered shear walls. Braced frames shall be con- sidered as shear walls. Moment-resisting frames may be designed as crosswalls or shear walls. 8. "Unreinforced masonry bearing wall" or "URM". A masonry wall having all of the following characteristics: a. Provides the vertical support for a floor or roof. b. The total superimposed load is over 100 pounds per linear foot. c. The masonry wall does not have vertical reinforcement. 9. "Yield deflection" is the deflection at which yield stress is first developed in a frame member. B. Notations. The applicable Code and the following sym- bols and notations apply to the provisions of this section. A = Area of unreinforced masonry pier in square inches. Cd = Numerical coefficient for the calculation of DCR. Cp Numerical coefficient as specified in Section 2312(g)2 and as set forth in Table No. 23-P of the Building Code and Table No. A1-B. of these requirements. ORIGINAL Fi, D DCR Fn, Fx Fp H h/t L LC L1 P V VA VC Vca VR va vc In-plane dimension of pier in inches, or depth of diaphragm in feet. Demand-Capacity Ratio. Lateral force applied to level i, n, or x, respectively. Lateral forces on a part of a structure in the direction under consideration. Least clear height of opening on either side of pier, in inches. Height/thickness ratio of URM wall. Height is measured between wall anchorage levels. Span from shear wall to open front or span of dia- phragm between shear walls. Length of crosswall in feet. Effective span of an open front building = 2[(Ww/Wd)-L + L]. Axial dead load on pier in pounds. The total lateral force or shear at the building or shear wall base. Va-A, the allowable shear in pounds in any URM pier, based on the allowable in-plane shear value. Total shear capacity of crosswalls in the direction of analysis immediately below the diaphragm level being investigated. Total shear capacity of crosswalls in the direction of analysis immediately above the diaphragm level being investigated. 0.5 P (D/H), the restoring shear in pounds of any URM pier, based on the cracked pier analysis. Allowable shear stress in pounds per square inch for unreinforced masonry. Maximum shear strength in pounds per foot for a crosswall sheathed with any of the materials given in Tables No. A1-D or A1-E. ORIGINAL vu W Wd = ~ Wd = Wp = Ww = Maximum shear strength in pounds per foot for a diaphragm sheathed with any of the materials given in Tables No. A1-D or A1-E. The total dead load as defined in Section 2302 of the Building Code, including the partition loading specified in Section 2304(d) of the Building Code where applicable. Total of the dead load that is tributary to a diaphragm level. Total of the dead load that is tributary to all of the diaphragms. The weight of a portion of a structure or non- structural component. Total dead load of an unreinforced masonry shear wall above the level under consideration or above an open front of a building. Seismic zone factor as defined in Chapter 23 of the Building Code. 15.40.030 Materials of construction. A. General. All materials permitted by the Building Code, including their appropriate allowable stresses and those existing configurations of materials specified herein, may be utilized to meet the requirements of this chapter. B. Existing unreinforced masonry walls. Unreinforced masonry walls analyzed in accordance with this section may provide vertical support for roof and floor construction and resistance to lateral loads. The facing and backing shall be bonded so that not less than 4 percent of the exposed face area is composed of solid headers extending not less than 4 inches into the backing. The distance between adjacent full-length headers shall not exceed 24 inches vertically or horizontally. Where the backing consists of two or more wythes, the headers shall extend not less than 4 inches into the most distant wythe or the backing wythes shall be bonded together with separate headers whose area and spacing conform to the foregoing. Wythes of walls not bonded as described above shall be considered as veneer. The veneer wythe shall not be included in the effective thickness used in calculating the height to thickness ratio and the shear capacity of the wall. C. Minimum acceptable quality of existing unreinforced masonry walls. 1. General provisions. All unreinforced masonry wallis utilized to carry vertical loads and seismic forces parallel and perpendicular to the wall plane shall be tested as specified in this subsection. All masonry quality shall equal or exceed the minimum standards established herein or shall be removed and replaced by new materials. The quality of mortar in all masonry walls shall be determined by performing in-place shear tests. All testing shall meet approved testing method parameters (including rate of load application) and shall be performed in accordance with the requirements specified in this subsection by a testing agency approved by the building official. Alternative methods of testing may be approved by the building official. Nothing shall prevent pointing with mortar of all the masonry wall joints before the tests are first made. Prior to any pointing, the mortar joints must be raked and cleaned to remove loose and deteriorated mortar. Mortar for pointing shall be Type S or N except masonry cements shal~ not be used. All preparation and mortar pointing shall be done under a permit and under the continuous inspection of a spe- cial inspector. At the conclusion of the inspection, the inspector shall submit a written report to the licensed engineer or architect responsible for the seismic analysis of the building, setting forth the result of the work inspected. The vertical wall joint between wythes (collar joint) shall be inspected at the test location, and an estimate of the percentage of wythe to wythe mortar coverage shall be reported along with the results of the in-place shear tests. Where the exterior face is veneer, the type of veneer, its thickness and its bonding and/or ties to the structural wall masonry shall also be reported. An accurate record of all such tests and their location in the building shall be recorded and these results shall be submitted to the building official for approval as part of the structural analysis. 2. Number and location of tests. The minimum number of tests shall be as follows: a. At each of both the first and top stories, not less than two per wall or line of wall elements providing a common line of resistance to lateral forces. b. At each of all other stories, not less than one per wall or line of wall elements providing a common line of resis- tance to lateral forces. c. In any case, not less than one per 1500 square feet of wall surface and a total of eight. The shear tests shall be taken at locations repre- sentative of the mortar conditions throughout the entire building, taking into account variations in workmanship at different building height levels, variations in weathering of the exterior surfaces, and variations in the condition of the interior surfaces due to deterioration caused by leaks and condensation of water and/or by the deleterious effects of other substances contained within the building. The exact test location shall be determined at the building site by the licensed engineer or architect responsible for the seismic analysis of the subject building. 3. In-place shear tests. The bed joints of the outer wythe of the masonry shall be tested in shear by laterally displac- ing a single brick relative to the adjacent bricks in that wythe. The mortar in the opposite head joint of the brick to be tested shall be removed and the head joint shall be cleaned prior to testing. The brick to be tested shall be a minimum of one course away from a header course. The minimum quality mortar in 80 per- cent of the shear tests shall not be less than the total of 30 psi plus the axial stress in the wall at the point of the test. The shear stress shall be based on the gross area of both bed joints and shall be that at which first movement of the brick or flaking of the mortar is observed. Walls with mortar values which are con- sistently low and do not meet the minimum quality values specified in this subsection shall be entirely repointed. 15.40.040 Quality control. A. Inspections: Except as modified in this section, inspections shall comply with Section 306 of the Building Code. B. Special inspection: Inspection specified herein shall be performed by a special inspector in accordance with Section 306 of the Building Code. C. Continuous inspection for pointing: Continuous inspec- tion shall be provided during all preparation and joint pointing. Exception: At the discretion of the building official, incidental. pointing may be performed without special inspection. D. Testing of Shear Bolts. One-fourth of all new shear bolts and dowels embedded in unreinforced masonry walls shall be tested by a special inspector using a torque calibrated wrench to the following minimum torques: 1/2-inch-diameter bolts or dowels--40 foot lbs. 5/8-inch-diameter bolts or dowels--50 foot lbs. 3/4-inch-diameter bolts or dowels--60 foot lbs. ORIGINAL Exception: Special inspection may be provided during installation in lieu of testing. E. Determination of allowable values for existing anchors. Five percent of the existing rod anchors utilized as all or part of the required wall anchors shall be tested in pullout by an approw~d testing laboratory. The minimum number tested shall be four per floor, with two tests at walls with joists framing into the wall and two tests at walls with joists parallel to the wall. The test apparatus shall be supported on the masonry wall at a minimum dis- tance of the wall thickness from the anchor tested. The rod anchor shall be given a preload of 300 pounds prior to establishing a datum for recording elongation. The tension test load reported shall be recorded at 1/8-inch relative movement of the anchor and the adjacent masonry surface. Results of all tests shall be reported. The report shall include the test results as related to the wall thickness and joist orientation. The allowable resistance value of the existing anchors shall be 40 percent of the average of those anchors tested in the same wall thickness and with the same joist orientation. The allowable resistance shall not exceed the values given in Table A1-E for tension bolts. F. Determination of allowable values for wall anchorage devices. Qualification tests for devices used for wall anchorage shall be performed with the entire tension load carried on the enlarged head at the exterior face of the wall. Bona on the part of the device between the enlarged head and the interior wall face shall be eliminated for the qualification tests. The resistance value assigned the device shall be twenty percent of the average of the ultimate loads. 15.40.050 Allowable design values. A. General. Stresses in materials and existing construc- tion utilized to resist seismic forces shall conform to those spec- ified in the Building Code and those materials and types of construction specified in this section: B. Determination of allowable shear stress in existing unreinforced masonry: 1. Design shear values. Design seismic in-plane shear stresses shall be substantiated by tests performed as specified in Section 15.40.030(C). The allowable shear Va, shall be 10 percent. of a test value that is determined by the in-plane shear tests. The test value, in psi, is that value that is exceeded by 80 per- cent of the test values. The tested shear values are calculated by reducing the test results, in psi, by the axial stress, in psi, in the masonry at the point of testing. The maximum value of va is 10 psi. The allowable shear stress, Va, may be increased by addition of 15 percent of the axial stress due to the weight of the wall directly above. (~ 2. Design compression and tension values. Compression stresses for unreinforced masonry having a minimum design shear value of 3 psi shall not exceed 100 psi. Design tension values for unreinforced masonry shall not be permitted. C. Combination of vertical and seismic forces. 1. New materials. All new materials introduced into the structure to meet the requirements of this chapter which are subjected to combined vertical and horizontal forces shall comply with Chapter 23 of the Building Code. 2. Existing materials. When stresses in existing lateral force-resisting elements are due to a combination of dead loads plus floor live loads plus seismic loads, the allowable work- ing stress specified in the Building Code may be increased 100 percent. However, no increase will be permitted in the allowable values given in Section 15.40.080, Tables No. A1-D (except as noted in footnote 4) and A1-E, and the stresses in the members due only to seismic and dead loads shall not exceed the values permit-- ted by Section 2303(d) of the Building Code. 15.40.060 Analysis and design. A. General. Every structure within the scope of this chapter shall be analyzed and constructed to resist stress produced by lateral forces as provided in this section. Stresses shall be calculated as the effect of a force applied horizontally at each floor or roof level above the base. The force shall be assumed to come from any horizontal direction. However, structural concepts other than those set forth in this section may be approved by the building official when evidence is submitted showing that equiva- lent ductility, strength, and energy absorption are provided. The structure shall be analyzed by the general procedures of the Earthquake Regulations of the Building Code or, when applicable, may be analyzed by Section 15.40.060(I). B. Analysis and design. Every structure within the scope of this chapter shall be analyzed and constructed to resist minimum lateral seismic forces assumed to act nonconcurrently in the direc- tion of each of the main axes of the structure in accordance with the following equation: V = ZW 3 .................................... (Ai-1) The total base shear shall be distributed over the height of the structure including level n according to the follow- ing formula. Fx -- Wxhx n ~ wihi i=l V ............................. (A2-2) At each level designated as x1 the force Fx shall be distributed over the area of the building in accordance with the mass distribution on that level. C. Lateral forces on elements of structures. 1. General. Parts or portions of structures shall be analyzed and designed for lateral loads in accordance with this subsection. The lateral forces shall be determined by the follow- ing formula. Fp = ZICpWp ....................................... (A1-3) Exception: Unreinforced masonry walls in buildings not required to be designed as an essential facility may be analyzed for out-of-plane stability in accordance with Section 15.40.060(I). D. Regulated elements of buildings. The elements of buildings required to be analyzed by this chapter shall be as spec- ified in Section 15.40.080, Table No. A1-A. E. Anchorage and interconnection. Anchorage and interconnection of all parts, portions and elements of the struc- ture shall be analyzed and designed for lateral forces in accor- dance with the Building Code and subsection C. of this section. F. Analysis procedure. 1. General. Stresses in materials and existing con- struction utilized to transfer seismic forces from the ground to parts or portions of the structure shall conform to those permitted by the Building Code and those materials and types of construction specified in Section 15.40.080, Tables No. A1-D and A1-E. 2. Connections. Materials and connectors used for interconnection of parts and portions of the structure shall conform to the Building Code. Anchorage of masonry walls to each floor or roof shall resist a minimum force determined by Formula A1-3 or 200 pounds per linear foot, whichever is greater, acting normal to the wall at the level of the floor or roof. Existing anchors, installed under previous permits, must meet or must be upgraded to meet the requirements of this chapter. Substantial changes in wall thickness shall be restrained by anchorage and bracing to the floor or roof diaphragm in accordance with Section 15.40.060(C). G. Unreinforced masonry walls, in-plane shear. 1. General. Except as modified herein, unreinforced masonry walls shall be analyzed as specified in Chapter 24 to with- stand all vertical loads as specified in Chapter 23 of the Building Code in addition to the seismic forces required by this chapter. The 50 percent increase in the seismic force factor for shear walls as specified in Section 2407(h)4.F. of the Building Code may be omitted in the computation of seismic loads to existing shear walls. 2. Allowable shear value. The allowable shear shall be as specified in Section 15.40.050(B). 3. Allowable reduction of bending stress by vertical load. In calculating tensile fiber stress due to seismic forces required by this section, the maximum tensile fiber stress may be reduced by the full direct stress due to vertical dead loads. Exception: In lieu of calculating flexural fiber stress in unreinforced masonry piers, the in-plane flexural capacity of the pier may be taken as: VR = 0.5 P (D/H) ....................................... (A1-4]~ 4. In-plane loads. Shear strength of a URM pier shall be calculated utilizing Section 15.40.110, Figure No. A-2 and the following equations: (i) VA = Va'A ..................................... (A1-5]~ (ii) VR = 0.5P-D/H ................................. (A1-6]~ When the shear strength of an unreinforced masonry pier, analyzed in accordance with Figure A-2 requires strengthening, said pier shall be strengthened in accordance with this chapter. 5. Shear resisting elements constructed of new materials. Moment resisting frames, braced frames, and reinforced{ masonry or concrete shear walls shall comply with all requirements of the Building Code. The relative rigidity of the added shear walls and the existing shear walls shall be considered. H. Unreinforced masonry walls, out-of-plane forces. Flexural stresses due to seismic forces normal to the wall need not be analyzed if the wall does not exceed the height-to-thickness ratio as set forth in Section 15.40.080, Table No. Ai-C for "all other buildings". If the wall height-thickness ratio exceeds the speci- fied limits, the wall may be supported by vertical bracing members designed in accordance with Chapter 23 of the Building Code. The deflection of such bracing members at design loads shall not exceed one-tenth of the wall thickness. Exception: The wall may be supported by flexible vertical bracing members designed for two-thirds of the forces specified by Chapter 23 of the Building Code if their deflection at design loads is not less than one-quarter nor more than one-third of the wall thickness. All vertical bracing members shall be attached to floor and roof construction for their design loads independently of required wall anchors. Horizontal spacing of vertical bracing mem- bers shall not exceed one-half the unsupported height of the wall nor 10 feet. The wall height may be measured vertically to bracing elements other than a floor or roof. Spacing of the bracing ele- ments and wall anchors shall not exceed 6 feet. Bracing elements shall be detailed to minimize the horizontal displacement of the wall by components of vertical displacements of the floor or roof.. I. Analysis procedure: Buildings with wood diaphragms: 1. General. Except as modified herein, the analysis shall be in accordance with Chapter 23 of the Building Code and Section 15.40.060(B) through (H). Buildings that have horizontal diaphragms of wood construction conforming to the criteria of this section may be analyzed by this section. The in-plane seismic force in each shear wall shall be calculated in accordance with Section 15.40.0604(I) in lieu of calculation and distribution of a base shear as prescribed in the Building Code. For determination of the capacity of anchorages of masonry walls out-of-plane, the value of ZICp = 0.3 shall be used. a. Criteria: The diaphragm sheathing shall be boards, finish flooring, plywood or similar wood material, single or in combination, nailed to joists or rafters. Nailing of exist-- ing wood sheathing need not be verified. Nailing of supplemental sheathing or plywood shall be equal to that specified in the Building Code for the specified shear values. 2. Modification of Base Shear: Buildings with hori- zontal wood diaphragms and complying with the following limitations shall be analyzed to resist minimum lateral forces in accordance with the following formula: V = ZW 4 .................................... (A1-7) a. Limitations: The building shall have crosswalls in each level on each axis of the building. All crosswalls need not be continuous below a wood diaphragm at/or near grade provided: (1) Shear connections and anchorage require- ments of Section 15.40.060(E) are satisfied at all edges of the diaphragm. (2) Crosswalls with total capacity of~.07 Wd interconnect the diaphragm to the foundation. (3) The demand/capacity ratio of the diaphragm between the crosswalls that are continuous to their foundations shall be calculated as [0.33Wd + Vca] /2VuD and shall not exceed 2.5. b. Spacing of crosswalls shall not exceed 40'-0" O.C. in the direction of consideration. c. Crosswalls shall have a minimum strength of 30 percent of the diaphragm strength in the direction of consideration. If several crosswalls exist at a spacing of less than 40 feet O.C., the total capacity of the crosswalls in any 40 feet measured along the span of the diaphragm shall exceed 30 per-- cent of the diaphragm strength. 3. Distribution of lateral forces. 1. The total lateral force shall be distributed over the height of the structure in accordance with Formulas A1-8 and A1-9. V =~Fi ................................................... (A1-8) i=l A portion of the total base shear V shall be distributed over the height of the structure including level according to the following formula: n Fx = Z 3 __Wx .............................................. (A1-9) Exception: Building with crosswalls conforming to Section 15.40.060(I)(2)(C) shall use the following formula: Z Wx ................................................ (Al-10) 4 4. Unreinforced masonry walls.. a. In-plane shear. The provisions of Section 15.40.060(G) are applicable except the ~eismic force distributed to the shear wall at any diaphragm level shall be the lesser value calculated as: (i) For buildings without crosswalls: Z Wd/2 .............................................. (Al-ll) 3 (ii) For buildings with crosswalls in all levels: Z vu · D -~Wd/[ (2Vu'D) + Vc] ...................... (Al-12) 4 where: Vc = the capacity of the crosswalls in the story below the level of consideration. (iii) Vu.D. b. The strength of a shear wall at any level need not exceed the value of Z/K Ww plus the sum of the diaphragms' shear strength. where: K = divisor of Z in equations (Ai-1 and (A1-7). 5. Unreinforced masonry walls - out-of-plane forces. a. The provision of Section 15.40.060(H) are applicable except that the allowable h/t ratio for buildings com- plying with the limitations for crosswalls may be used. 6. Existing roof, floors and walls. a. Existing materials, including wood framed dia-- phragms utilized in a described configuration, may be used as part of the lateral load-resisting system, provided that the demand/capacity ratio of these materials does not exceed the values shown in Section 15.40.100, Figure No. A-1. Wood diaphragms at or near grade shall comply with the requirements of Section 15.40.060(I). Values of diaphragm capacity, Vu, and crosswall capacity, Vc, for existing materials are given in Section 15.40.080, Table A1-D. b. Strengthening of existing materials. New materials, including wood shear walls, may be utilized to strengthen portions of the existing seismic resisting system in a described configuration, provided that the stresses do not exceed the values shown in Section 15.40.080, Table No. A1-E. c. Alternate materials. Alternate materials, designs and methods of construction may be approved by the Building Official. d. Diaphragm displacement control. The displace- ment of a diaphragm relative to the shear walls is acceptable if the values of DCR and span in feet lies within the boundaries of the curve shown in Section 15.40.100, Figure A-1. e. Use of wood diaphragms to control displacement of an open front. Wood framed crosswalls and diaphragms con- structed of materials described in Section 15.40.080, Tables A1-D and A1-E shall be analyzed by the following procedures: Calculate L1, diaphragm span in feet, for use in Section 15.40.100, Figure No. A-1 as: L1 = Effective span = 2 [(Ww/Wd) · L + L] .............. (Al-13 Ww = Total dead load of URM wall above the open front. L = Span from shear wall to open front or span of diaphragm beyond crosswall. Calculate demand/capacity ratio as: 0.33 (Wd + Ww)/(vu · D) ................................. (Al-14 If crosswalls are used to limit displacement at open front, calcu-- late demand/capacity ratio as: 0.33 (Wd + Ww) / [(vu D) + Vc] ...................... (Al-15 A supplemental support system in conformance to Section 15.40.070(C) shall be provided at lintels bearing on unreinforced masonry piers at the open front. Horizontal diaphragms shall not be considered to trans- mit lateral forces by rotation. A minimum of one (1) shear wall and one (1) crosswall shall be parallel to each axis of the building. 7. Shear connection of wood diaphragms. For determi- nation of the capacity of the shear connections at the edges of wood diaphragms, the values of ZIC~ as set forth in Section 15.40.080, Table A1-B shall be use~. However, the strength of the shear connections need not exceed the strength of the diaphragm as given in Section 15.40.080, Table A1-D and A1-E. 15.40.070 Detailed systems design requirements. A. General. In addition to the seismic analysis required elsewhere in this chapter, the licensed engineer or architect responsible for the seismic analysis of the building shall deter- mine and record the information required by this section on the approved plans. B. Wall anchorage. 1. Locations. All unreinforced masonry walls shall be anchored at the roof, floor and ceiling levels by tension bolts through the wall as specified in Section 15.40.080, Table No. A1-E, or by approved equivalent at a maximum anchor spacing of 6 feet. All existing rod anchors shall be secured to the joists to develop the required forces. The building official may require testing to verify the adequacy of the embedded ends of existing rod anchors. Tests when required shall conform to Section 15.40.040(E). Exception: Walls need not be anchored to ceiling systems, if due to their low mass and/or relative location with respect to the floor or roof systems, the ceiling does not impose significant normal forces on the wall. At the roof and all floor levels, the anchors near- est the building corners shall be combination shear and tension anchors located not more than two feet horizontally from the inside of the corners of the walls. 2. Access for anchorage. When access to the exterior face of the masonry wall is prevented by proximity of an existing building, wall anchors conforming to Item 5a and b in Section 15.40.080, Table No. A1-E may be used. Alternative devices to bolts for masonry wall anchorage shall Section 15.40.040(F). be used in lieu of tension be tested as specified in C. Truss and beam supports. Where trusses and beams other than rafters or joists are supported on masonry, independent secon- dary columns shall be installed to support vertical loads of the roof or floor members. D. Parapets. Parapets and exterior wall appendages not capable of resisting the forces specified in this section shall be removed, stabilized or braced to insure that the parapets and appendages remain in their original position. The maximum height of an unbraced unreinforced masonry parapet above the lower of either the level of tension anchors or roof sheathing, shall not exceed one and one-half (1-1/2) times the thickness of the parapet wall. If the required parapet height exceeds this maximum height, a bracing system designed for the force factors specified in Table No. 23-P of the Building Code for walls shall support the top of the parapet. Parapet corrective work must be performed in conjunction with the installation of ten- sion roof anchors. The minimum height of a parapet above the wall anchor shall be twelve (12) inches. Exception: at the top of the wall, may be six (6) inches. If a reinforced concrete beam is provided the minimum height above the wall anchor All deteriorated mortar joints in unreinforced masonry walls shall be pointed in accordance with Section 15.40.090. E. Existing damage. Repair details of any cracked or dam- aged unreinforced masonry wall required to resist forces specified in this chapter shall be provided in the approved construction documents. Repair details to restore the original strength of other structural elements shall also be provided. F. Veneer. Veneer shall be anchored with approved anchor ties, conforming to the required design horizontal force specified in tlhe Building Code and placed at a maximum spacing of 24 inches with a maximum supported area of four (4) square feet. Exception: Existing veneer anchor ties may be accepted by the building official provided the ties are in good condition and conform to the following minimum size, maximum spacing and material requirements. Existing veneer anchor ties shall be corru- gated galvanized iron strips not less than one inch in width, eight inches in length and one-sixteenth of an inch in thickness (1' X 8" X 1/16") or equal and shall be located and laid in every alternate course in the vertical height of the wall at a spacing not to exceed 17 inches on centers horizontally. As an alternate, such ties may be laid in every fourth course vertically at a spacing not to exceed nine (9) inches on centers horizontally. The existence and condition of existing veneer anchor ties shall be verified as follows: 1. An approved testing laboratory shall verify the location and spacing of the ties and shall submit a report to the building as a part of the structural analysis. 2. The veneer in a selected area shall be removed to expose a representative sample of ties (not less than four) for inspection by the building official. 15.40.080 Tables. BUILDING ELEMENTS REQUIRING ANALYSIS 1. 2. 3. 4. 5. TABLE NO. A1-A REGULATED ELEMENTS Walls, h/t ratio Walls, In-plane Shear Wall Anchorage Parapets Floors and Roofs: Connections at edge Diaphragm Displacement Control TABLE NO. A1-B VALUES OF ZICp CONFIGURATION OF MATERIALS Roofs with straight or diagonal sheathing and roofing applied directly to tlhe sheathing, or floors with straight tongue and grove sheathing. Double or multiple layers of boards with edges offset and blocked plywood systems. 0.2 0.3 TABLE NO. A1-C ALLOWABLE VALUE OF HEIGHT-THICKNESS RATIO OF UNREINFORCED MASONRY WALLS WITH MINIMUM QUALITY MORTAR1 ALL OTHER BUILDINGS BUILDINGS WITH CROSSWALLS Walls of one-story Buildings 13 162 First-story wall of multi-story buildings 15 16 Walls in top story of multi-story buildings 9 142 All other walls 13 16 1Minimum quality mortar shall be determined by laboratory testing in accordance with Section 15.40.030(c). 2Values shown are for mortar shear test values of 60 psi or greater and with filled collar joints. Filled collar joints are defined as over 50 percent mortar coverage of the area exposed in the in-place shear tests. TABLE NO A1-D VALUES FOR EXISTING MATERIALS EXISTING MATERIALS OR CONFIGURATIONS OF MATERIALS1 ALLOWABLE VALUES 1. HORIZONTAL DIAPHRAGMS a. Roofs with straight :sheathing and roofing ,applied directly to the sheathing. 4 190 lbs. per foot for seismic shear ORIGINAL ee Roofs with diagonal sheathing and roofing applied directly to the sheathing. 4 Floors with straight tongue-and-groove sheathing. Floors with straight sheathing and finished wood flooring with board edges offset or perpendicular. Floors with diagonal sheathing and finished wood flooring. 250 lbs. per foot for seismic shear 100 lbs. per foot for seismic shear 500 lbs. per foot for seismic shear 600 lbs. per foot for seismic shear CROSSWALLS2 a. Plaster on wood or metal lath. b. Plaster on gypsum lath. c. Gypsum wall board, un- blocked edges. d. Gypsum wall board, blocked edges. Per side: 200 ~Lbs. per foot for seismic shear 175 lbs. per foot for seismic shear 75 lbs. per foot for seismic shear 125 lbs. per foot for seismic shear EXISTING FOOTINGS, WOOD FRAMING, STRUCTURAL STEEL, AND REINFORCED STEEL a. Plain concrete footings. b. Douglas fir wood. c. Reinforcing steel. d. Structural steel. f'c = 1500 psi unless otherwise shown by tests. Allowable stress same as No. 1 D.F.3 ft = 18,000 lbs.~ per square inch maximum.3 ft = 20,000 lbs.. per square inch maximum.3 Material must be sound and in good condition. Shear values of these materials may be combined, except the total combined value shall not exceed 300 lbs. per foot. Stresses given may be increased for combinations of loads as specified in Section 15.40.050(C). Shear values may be increased to 150 lbs. per linear foot for items (a) and (c), and to 300 lbs. per linear foot for item (b). Such increase shall be substantiated by the engineer and approved by the building official. TABLE NO. A1-E ALLOWABLE VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION NEW MATERIALS OR CONFIGURATION OF MATERIALS1 1. HORIZONTAL DIAPHRAGMS Plywood sheathing applied directly over existing straight sheathing with ends of plywood sheets bearing on joists or rafters and edges of plywood located on center of individual sheathing boards. 2. CROSSWALLS Plywood sheathing applied directly over existing wood studs. No value shall be given to plywood applied over existing plaster or wood sheathing. Drywall or plaster applied directly over existing wood studs. Drywall or plaster applied to plywood sheathing over existing woods studs. ALLOWABLE VALUES 225 lbs. per foot 1.33 times the values specified in Table No. 25-K-1 of the Building Code for shear walls. 100 percent of the values specified Table No. 47-I of the Building Code. 50 percent of the values specified in Table No. 47-I of the Building Code.. 3. SHEAR BOLTS Shear bolts embedded a minimum of 8 inches into unreinforced masonry walls. Bolt centered in a 2-1/2-inch diameter hole with dry-pack or non-shrink grout around circum- ference of bolt. 1 3 4. 'PENSION BOLTS Tension bolts and tension dowels extending entirely through unrein- forced masonry walls secured with bearing plates on far side of a 3 wythe minimum wall with at least 30 square inches of area. 2 3 Bolts extending to 1 inch from the exterior face of the wall with a 2 1/2-inch round plate under the head. Install as specified for shear bolts. Spaced not closer than 12 inches on centers.I 2 3 Bolts extending to 1 inch from the exterior face of the wall with a 2 1/2-inch round plate under the head and drilled at an angle of 22-1/2 degrees to the horizontal. Installed as specified for shear bolts. 1 2 3 5. INFILLED WALLS Reinforced masonry infilled openings in existing unrein- forced masonry walls. Provide keys or dowels to match rein- forcing. 6. REINFORCED MASONRY Masonry piers and walls rein- forced per Section 2407(h) 4. 133 percent of the values specified for solid masonry in Table No. 24-J of the Building Code. No values larger than those given for 3/4 inch bolts shall be used. 1800 lbs. per bolt, tension. 900 lbs. for 2 wythe walls. 600 lbs. per bolt, tension for 3 wythe walls. 1200 lbs. per bolts, tension for 3 wythe walls. Same as values specified for unreinforced masonry walls. Same as values spec- ified in Section 2406 of the Building Code. 7. REINFORCED CONCRETE Concrete footings, walls and piers reinforced as specified in Chapter 26 of the Building Code and designed for tributary loads. 8. EXISTING FOUNDATION LOADS Foundation loads for structures exhibiting no evidence of ~settlement. Same as values spec- ified in Chapter 26 of the Building Code. Calculated existinq foundation load may be increased 25 per- cent for dead loads, and may be increased 50 percent for dead load plus seismic load required by this chapter. 1Bolts to be tested as specified in Section 15.40.040(D). 2Bolts to be 1/2-inch minimum in diameter. 3Drilling for bolts and dowels shall be done with an electric rotary drill. Impact tools shall not be used for drilling holes or tightening anchors and shear bolt nuts. 15.40.090 Pointing and relaying of brick. A. Pointing. The Uniform Building Code Standard No. 24-42 for the Pointing of unreinforced masonry walls is adopted. 1. The old mortar should be cut out, by means of a toothing chisel or a special painter's grinder, to a uniform depth of 3/4", or until sound mortar is reached. Care must be taken not to damage the brick edges. All dust and debris must be removed from the joint by brushing, blowing air or rinsing with water. 2. Mortar mix shall be Type "S" or "N" proportions as called for in the construction specifications. The tuck-pointing mortar should be pre-hydrated to reduce excessive shrinkage. The proper pre-hydration process is as follows: a. All dry ingredients should be thoroughly mixed. Only enough clean water should be added to the dry mix to produce a damp, workable consistency which will retain its shape when formed into a ball. The mortar should stand in this dampened condition for one to one and one-half hours. - 23 ~ ORIGINAL b. The joints to be tuck-pointed should be dampened, but to ensure a good bond, the brickwork must absorb al~L surface water. Water should be added to the pre-hydrated mortar to bring it to a workable consistency (somewhat drier than conven- tional mortar). The mortar should be packed tightly into the joints in thin layers (1/4" maximum). Each layer should become "thumbprint hard" before applying the next layer. The joints should be tooled to match the original profile after the last layer of mortar is "thumbprint hard." B. Relaying of brick. Replacement bricks must match the originals with respect to size, color, and texture where exposed. A tuck-pointing toothing chisel should be used to cut out the mor- tar which surrounds the affected units. Power driven impact tools are not allowed. Once the units are removed, all of the old mortar shall be carefully chiseled out and all dust and debris shall be swept out with a brush. If used brick is to be relayed, it shall be cleaned of all old mortar. The brick surfaces in the wall shall be dampened before new units are placed, but the masonry should absorb all sur- face moisture to ensure a good bond. The appropriate surfaces of the surrounding brickwork and the replacement brick should be but- tered with mortar. The replacement brick should be centered in the opening and pressed into position. The excess mortar should be removed with a trowel. Pointing around the replacement brick wil~L help to ensure full head and bed joints. When the mortar becomes "thumbprint hard," the joints shall be tooled to match the original profile. ORIGINAL 15.40.100 Acceptable Span for Diaphrams (Figure A-i). 540 .... 48O 360 ...... 300 240 ' !B0 ........ 120 _ _ _ 60___ 0 0 DEMAND-CAPACITY RATIO FIGURE A-1 ACCEPTABLE SPAN FOR DIAPHRAGMS ORIGINAL 15.40.110 Analysis of URM wall for in-plane shear force (Figure A-2). COMPARE VR AND VA IN EACH PIER RESTORING SHEAR IS ADEQUATE; ROCKING OF PIER SYSFFEM IS SAFE Vt > ~' VR ( STRENGTHEN WALL) IS IN PROPORTION TO PD/H; ~IV~UAL P~S RESTORING SHEAR OF PIER CAN ROCK SAFELY SYSTEM IF NOT ADEQUATE VR > VA RELATIVE RIGIDITY IN AT LEAST ANALYSIS ONE PIER VR -- Restoring sheor of a pier ~VR -- Rest~ring sheor of eli piers in the w~li VA -- Shear strength OF a pier Vt - Total sheor force applied t~ the wall Vx -- Shear fome assigned ~ o pier on the baeie OF a relative sheor rigidity anolyeie Vx > Va IN ANY PIER tVR<Vx I 1N AT LEASTI ONE PIER I DISTRIBUTION OF SHEAR FORCES IN PIERS CANNOT BE DETERMINED OMIT FROM ANALYSIS ANY PIER W/VR < Vx VR > Vx IN ALL PIERS SHEAR FORCE IN AN INDIVIDUAL PIER IS PROPORTIONAL TO D?H SHEAR 5"]'R_FSS If OK STRENGTHEN WAll)~ SHEAR FORCE IN AN INDIVIDUAL PER tS PROPORTIONAL TO D/H. PER IS OVERSTRESSED IN SHEAR FIGURE A-2 - ANALYSIS OF URM WALL FOR IN-PLANE SHEAR FORCE - 26 - 109005 SECTION 2. This ordinance shall be posted in accordance with the City Charter provisions and shall become effective thirty (30) days from and after the date of its passage. .......... o0o .......... I HEREBY CERTIFY that the foregoing Ordinance was passed and adopted by the Council of the City of Bakersfield at a regular meeting thereof held on JUL 2 5 1990 , by the following vote: AYES; COUNCILMEMBERS: EDWARDS, DeMaND, SMITH, RRUNNI, PETERSON, MCDERMo'Tr, SALVABGIO NOES; COUNCILMEMBERS: ABSENT COUNCILMEMBERS: ,/V ~' ~ ,~ ABSTAIN: COUNCILMEMRER$' ASSISTANT CITY CLERK and Ex Officio Clerk of the Council of the City of Bakersfield APPROVED JUL 2 5 1990 MAYOR of the City of Bakersfield APPROVED as to form: ARTI{UR J. SAALFIELD CITY ATTORNEY of the City of Bakersfield LCM/meg O ORD 5 URM.1-27 7/2/90 - 27 ORI(}INAL AFFIDAVIT OF POSTING DOCUMENTS STATE OF CALIFORNIA) ) County of Kern) CAROL WILLIAMS, That she is the of Bakersfield; Being duly sworn, deposes and says: duly appointed, acting and qualified City Clerk of and that on the 30th day of July posted on the Bulletin Board at City Hall, a the following: Ord±nance No. City Council at a meeting held on the 25th and entitled: the City 1990 she full, true and correct copy of passed by the Bakersfield day of July , 1990 NSAOPD /s/ CAROL WILLIAMS CITY CLERK of the City of Bakersfield DEPUTY City Clerk