HomeMy WebLinkAboutFMC 2022Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10134244 7/21/2022
Jaco #7776 Howard's Market
3300 Planz Road Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Matt Story
1073967
9118985 2/17/2023
GVR ATG Tech C26845 4/22/2023
7/21/2022 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS-350 333.05
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 794380-208 UDC 1/2
Stand Alone 847990-001 UDC 3/4
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
W1 849490-001 91 product line
W2 849490-001 87 product line
W3 849490-001 Diesel product line
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
T1 87 847390-107 87 tank
T2 91 847390-107 91 tank
T3 Diesel 847390-107 Diesel tank
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #7776 Howard's Market3300 Planz RoadBakersfield101342441/23/4 3/48791Diesel 8791Diesel 1/21/23/4ProductProductProductProductProductProductMatt Story
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10134244 7/21/2022
Jaco #7776 Howard's Market
3300 Planz Road Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Matt Story
1073967
9118985 2/17/2023
FFS 1015653711 4/13/2023
Hydrostatic Lake Test 87 Phil-Tite Fill Spill Bucket
Hydrostatic Lake Test 91 Phil-Tite Fill Spill Bucket
Hydrostatic Lake Test Diesel Phil-Tite Fill Spill Bucket
7/21/2022 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1 87
Phil-Tite
T2 91
Phil-Tite
T3 Diesel
Phil-Tite
SETUP
Responses Received:
200
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
JUL 21, 2022 1:47 PM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
2 UNLEADED 4649 39.47 0.0 89.3 7351
3 SUPER 3628 32.84 0.0 87.0 8372
4 DIESEL 1799 19.91 0.0 89.9 10201
I90500
JUL 21, 2022 1:47 PM
SOFTWARE REVISION LEVEL
VERSION 333.05
SOFTWARE# 346333-100-F
CREATED - 13.12.11.14.16
S-MODULE# 330160-016-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
ISD/APM
PLLD
0.10 REPETITIV
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I50500
JUL 21, 2022 1:47 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUL 21, 2022 1:47 PM
SHIFT TIME 1 : 6:00 AM
I50202
JUL 21, 2022 1:47 PM
SHIFT TIME 2 : DISABLED
I50203
JUL 21, 2022 1:47 PM
SHIFT TIME 3 : DISABLED
I50204
JUL 21, 2022 1:47 PM
SHIFT TIME 4 : DISABLED
I54600
JUL 21, 2022 1:47 PM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUL 21, 2022 1:47 PM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUL 21, 2022 1:47 PM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUL 21, 2022 1:47 PM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUL 21, 2022 1:47 PM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUL 21, 2022 1:47 PM
PRINT TC VOLUMES
ENABLED
I50E00
JUL 21, 2022 1:47 PM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUL 21, 2022 1:47 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUL 21, 2022 1:47 PM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUL 21, 2022 1:47 PM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUL 21, 2022 1:47 PM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 1 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUL 21, 2022 1:47 PM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUL 21, 2022 1:47 PM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUL 21, 2022 1:47 PM
TANK CHART SECURITY
DISABLED
I5BD00
JUL 21, 2022 1:47 PM
CUSTOM ALARM LABELS
DISABLED
I56000
JUL 21, 2022 1:47 PM
MASS/DENSITY
DISABLED
I88101
JUL 21, 2022 1:47 PM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JUL 21, 2022 1:47 PM
I88103
JUL 21, 2022 1:47 PM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JUL 21, 2022 1:47 PM
I88105
JUL 21, 2022 1:47 PM
PORT SETTINGS:
COMM BOARD : 5 (RS-485)
BAUD RATE : 1200
PARITY : ODD
STOP BIT : 2 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88106
JUL 21, 2022 1:47 PM
PORT SETTINGS:
COMM BOARD : 6 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I52000
JUL 21, 2022 1:47 PM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE JUN 6, 2018 DISABLED
2 ON DATE JUN 6, 2018 DISABLED
3 ON DATE JUN 6, 2018 DISABLED
4 ON DATE JUN 6, 2018 DISABLED
5 ON DATE JUN 6, 2018 DISABLED
6 ON DATE JUN 6, 2018 DISABLED
7 ON DATE JUN 6, 2018 DISABLED
8 ON DATE JUN 6, 2018 DISABLED
I60100
JUL 21, 2022 1:47 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 OFF
2 UNLEADED ON
3 SUPER ON
4 DIESEL ON
I60200
JUL 21, 2022 1:47 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1
2 UNLEADED
3 SUPER
4 DIESEL
I60300
JUL 21, 2022 1:47 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 1
2 UNLEADED 2
3 SUPER 3
4 DIESEL 4
I60900
JUL 21, 2022 1:47 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 0.000000
2 UNLEADED 0.000700
3 SUPER 0.000700
4 DIESEL 0.000450
I60700
JUL 21, 2022 1:47 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 0.00
2 UNLEADED 96.00
3 SUPER 96.00
4 DIESEL 96.00
I60A00
JUL 21, 2022 1:47 PM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1
1 PT 0 2 UNLEADED 1 PT 12000 3 SUPER
1 PT 12000 4 DIESEL 1 PT 12000
I60400
JUL 21, 2022 1:47 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 12000
3 SUPER 12000
4 DIESEL 12000
I60500
JUL 21, 2022 1:47 PM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 0 0 0 0
2 UNLEADED 12000 0 0 0
3 SUPER 12000 0 0 0
4 DIESEL 12000 0 0 0
I60600
JUL 21, 2022 1:47 PM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 UNLEADED 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 SUPER 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 DIESEL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUL 21, 2022 1:47 PM
TANK PRODUCT LABEL METER DATA
1 NO
2 UNLEADED NO
3 SUPER NO
4 DIESEL NO
I62F00
JUL 21, 2022 1:47 PM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
2 UNLEADED 4.0 IN.
3 SUPER 4.0 IN.
4 DIESEL 4.0 IN.
I62700
JUL 21, 2022 1:47 PM
2 UNLEADED 2.0
3 SUPER 2.0
4 DIESEL 2.0
I64200
JUL 21, 2022 1:48 PM
2 UNLEADED LOW
3 SUPER LOW
4 DIESEL LOW
I62400
JUL 21, 2022 1:48 PM
2 UNLEADED 3.0
3 SUPER 3.0
4 DIESEL 3.0
I62800
JUL 21, 2022 1:48 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 12000
3 SUPER 12000
4 DIESEL 12000
I62300
JUL 21, 2022 1:48 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 10800
3 SUPER 10800
4 DIESEL 10800
I62200
JUL 21, 2022 1:48 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 11400
3 SUPER 11400
4 DIESEL 11400
I62900
JUL 21, 2022 1:48 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 1200
3 SUPER 1200
4 DIESEL 1200
I62100
JUL 21, 2022 1:48 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 1200
3 SUPER 1200
4 DIESEL 1200
I62600
JUL 21, 2022 1:48 PM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 99
2 UNLEADED 99
3 SUPER 99
4 DIESEL 99
I62500
JUL 21, 2022 1:48 PM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 99
2 UNLEADED 99
3 SUPER 99
4 DIESEL 99
I60800
JUL 21, 2022 1:48 PM
TANK TILT
TANK PRODUCT LABEL INCHES
1 0.00
2 UNLEADED 1.00
3 SUPER 4.00
4 DIESEL 0.00
I60B00
JUL 21, 2022 1:48 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUL 21, 2022 1:48 PM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 0.00
2 UNLEADED 0.00
3 SUPER 0.00
4 DIESEL 0.00
I61200
JUL 21, 2022 1:48 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 NONE NONE
2 UNLEADED NONE NONE
3 SUPER NONE NONE
4 DIESEL NONE NONE
I63600
JUL 21, 2022 1:48 PM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 120
3 SUPER 120
4 DIESEL 120
I62A00
JUL 21, 2022 1:48 PM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 120
3 SUPER 120
4 DIESEL 120
I62C00
JUL 21, 2022 1:48 PM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 STANDARD
2 UNLEADED STANDARD
3 SUPER STANDARD
4 DIESEL STANDARD
I62D00
JUL 21, 2022 1:48 PM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 SUPER GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUL 21, 2022 1:48 PM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 OFF OFF
2 UNLEADED OFF OFF
3 SUPER OFF OFF
4 DIESEL OFF OFF
I63000
JUL 21, 2022 1:48 PM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 OFF
2 UNLEADED OFF
3 SUPER OFF
4 DIESEL OFF
I63200
JUL 21, 2022 1:48 PM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 OFF
2 UNLEADED OFF
3 SUPER OFF
4 DIESEL OFF
I61000
JUL 21, 2022 1:48 PM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 1
2 UNLEADED 1
3 SUPER 1
4 DIESEL 1
I63A00
JUL 21, 2022 1:48 PM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 10.00%
2 UNLEADED 10.00%
3 SUPER 10.00%
4 DIESEL 10.00%
I61100
JUL 21, 2022 1:48 PM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST CSLD : ALL TANK
Pd = 95%
CLIMATE FACTOR:MODERATE
GROSS TEST
AUTO-CONFIRM: DISABLED
REPORT ONLY:
DISABLED
TST EARLY STOP:DISABLED
I61300
JUL 21, 2022 1:48 PM
CSLD PROBABLITY OF DETECTION
T 2:UNLEADED : Pd = 95%
T 3:SUPER : Pd = 95%
T 4:DIESEL : Pd = 95%
I61400
JUL 21, 2022 1:48 PM
CSLD CLIMATE FACTOR
T 2:UNLEADED : MODERATE
T 3:SUPER : MODERATE
T 4:DIESEL : MODERATE
I61600
JUL 21, 2022 1:48 PM
TANK PRODUCT LABEL CAL UPDATE
1 IMMEDIATE
2 UNLEADED IMMEDIATE
3 SUPER IMMEDIATE
4 DIESEL IMMEDIATE
I61A00
JUL 21, 2022 1:48 PM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 DISABLED
2 UNLEADED DISABLED
3 SUPER DISABLED
4 DIESEL DISABLED
I61B00
JUL 21, 2022 1:48 PM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
2 UNLEADED DISABLED
3 SUPER DISABLED
4 DIESEL DISABLED
I61C00
JUL 21, 2022 1:48 PM
CSLD REPORT ONLY
2 UNLEADED DISABLED
3 SUPER DISABLED
4 DIESEL DISABLED
I62B00
JUL 21, 2022 1:48 PM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 ??? 0, 0
2 UNLEADED ??? 0, 0
3 SUPER ??? 0, 0
4 DIESEL ??? 0, 0
I63300
JUL 21, 2022 1:48 PM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUL 21, 2022 1:48 PM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 0
3 SUPER 0
4 DIESEL 0
I63500
JUL 21, 2022 1:48 PM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 1
2 UNLEADED 1
3 SUPER 1
4 DIESEL 1
I63900
JUL 21, 2022 1:48 PM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1
END FACTOR: NONE
2 UNLEADED
END FACTOR: NONE
3 SUPER
END FACTOR: NONE
4 DIESEL
END FACTOR: NONE
I78000
JUL 21, 2022 1:48 PM
I77700
JUL 21, 2022 1:48 PM
I77800
JUL 21, 2022 1:48 PM
I78C00
JUL 21, 2022 1:48 PM
I78300
JUL 21, 2022 1:48 PM
I78F00
JUL 21, 2022 1:48 PM
I78700
JUL 21, 2022 1:48 PM
I70200
JUL 21, 2022 1:48 PM
LIQUID LABEL
DEVICE LABEL
1 UDC 1-2
2
3
4
5
6
7
8
I70300
JUL 21, 2022 1:48 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UDC 1-2 TRI-STATE (SINGLE FLOAT)
2 TRI-STATE (SINGLE FLOAT)
3 TRI-STATE (SINGLE FLOAT)
4 TRI-STATE (SINGLE FLOAT)
5 TRI-STATE (SINGLE FLOAT)
6 TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
I70400
JUL 21, 2022 1:48 PM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UDC 1-2 DISPENSER PAN
2 OTHER SENSORS
3 OTHER SENSORS
4 OTHER SENSORS
5 OTHER SENSORS
6 OTHER SENSORS
7 OTHER SENSORS
8 OTHER SENSORS
I74200
JUL 21, 2022 1:48 PM
I74300
JUL 21, 2022 1:48 PM
I74400
JUL 21, 2022 1:48 PM
I74700
JUL 21, 2022 1:48 PM
I74800
JUL 21, 2022 1:48 PM
I74900
JUL 21, 2022 1:48 PM
I7BC00
JUL 21, 2022 1:48 PM
I80200
JUL 21, 2022 1:48 PM
I80300
JUL 21, 2022 1:48 PM
I80400
JUL 21, 2022 1:48 PM
I80700
JUL 21, 2022 1:48 PM
RELAY LABEL
DEVICE LABEL
1 OVERFILL ALARM
2
3
4
I80900
JUL 21, 2022 1:48 PM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 OVERFILL ALARM NORMALLY OPEN
2 NORMALLY OPEN
3 NORMALLY OPEN
4 NORMALLY OPEN
I80B00
JUL 21, 2022 1:48 PM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 OVERFILL ALARM NONE
2 NONE
3 NONE
4 NONE
I80A00
JUL 21, 2022 1:48 PM
RELAY TYPE
RELAY DESIGNATION TYPE
1 OVERFILL ALARM STANDARD
2 STANDARD
3 STANDARD
4 STANDARD
I80C00
JUL 21, 2022 1:48 PM
I80800
JUL 21, 2022 1:48 PM
RELAY SETUP REPORT
R 1:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 2:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 3:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
JUL 21, 2022 1:48 PM
EDIM:1 VR:349634-003-E TD:09.05.18.15.18
I79100
JUL 21, 2022 1:48 PM
I72300
JUL 21, 2022 1:48 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VP SENSOR 3-4 VAPOR PRESSURE
02 VFM 1-2 AIR FLOW METER
03 VFM 3-4 AIR FLOW METER
04 UNKNOWN
05 UNKNOWN
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JUL 21, 2022 1:48 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
JUL 21, 2022 1:48 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JUL 21, 2022 1:48 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
VAPOR PROCESSOR TYPE
NONE
IV4700
JUL 21, 2022 1:48 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JUL 21, 2022 1:48 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ACCEPT HIGH ORVR: YES
IV4A00
JUL 21, 2022 1:48 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 UU BLEND3
02 02 02 01 UU BLEND3
03 03 03 02 UU BLEND3
04 04 04 02 UU BLEND3
IV4B00
JUL 21, 2022 1:48 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
IV4900
JUL 21, 2022 1:48 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JUL 21, 2022 1:49 PM
ISD VERSION: 01.05
ALARM HISTORY (BEFORE)
Responses Received:
I10200
JUL 21, 2022 1:51 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 163895 163083
2 INTERSTITIAL BD 201249 200703
3 7SMARTSENSOR BD 9865629 503585
4 UNUSED 9830660 4929622
5 UNUSED 9822698 4924883
6 UNUSED 9822698 4926274
7 UNUSED 9822174 4927318
8 UNUSED 9816831 4925144
9 WPLLD POWER BD 201158 201042
10 AC INTERFACE BD 163488 163177
11 RELAY BOARD 15049 15043
12 UNUSED 9832520 4929470
13 UNUSED 9813998 4929883
14 UNUSED 9818146 4928992
15 UNUSED 9810562 4929188
16 UNUSED 9815423 4929035
COMM 1 ELEC DISP INT. 100267 100118
COMM 2 WPLLD COMM BD 201900 201701
COMM 3 RS232 SERIAL BD 14902 14890
COMM 4 UNUSED 9825501 4931079
COMM 5 RS485 SERIAL BD 9815800 68187
COMM 6 RS232 SERIAL BD 9814270 14912
I90200
JUL 21, 2022 1:51 PM
SOFTWARE REVISION LEVEL
VERSION 333.05
SOFTWARE# 346333-100-F
CREATED - 13.12.11.14.16
S-MODULE# 330160-016-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
ISD/APM
PLLD
0.10 REPETITIV
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I11100
JUL 21, 2022 1:51 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-21-22 8:37AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-21-22 8:37AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-21-22 8:37AM
L 1 DISP PAN UDC 1-2 FUEL ALARM CLEAR 7-21-22 8:37AM
L 1 DISP PAN UDC 1-2 FUEL ALARM ALARM 7-21-22 8:37AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-21-22 8:37AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-21-22 8:37AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-21-22 8:37AM
T 3 TANK SUPER HIGH WATER ALARM CLEAR 7-15-22 2:28PM
T 3 TANK SUPER MAX PRODUCT ALARM CLEAR 7-15-22 2:28PM
T 3 TANK SUPER OVERFILL ALARM CLEAR 7-15-22 2:26PM
T 3 TANK SUPER OVERFILL ALARM ALARM 7-15-22 2:25PM
T 3 TANK SUPER MAX PRODUCT ALARM ALARM 7-15-22 2:24PM
T 3 TANK SUPER SUDDEN LOSS ALARM CLEAR 7-15-22 2:24PM
T 3 TANK SUPER LOW PRODUCT ALARM CLEAR 7-15-22 2:24PM
T 3 TANK SUPER SUDDEN LOSS ALARM ALARM 7-15-22 2:20PM
T 3 TANK SUPER HIGH WATER ALARM ALARM 7-15-22 2:19PM
T 3 TANK SUPER LOW PRODUCT ALARM ALARM 7-15-22 2:18PM
T 3 TANK SUPER MAX PRODUCT ALARM CLEAR 7-15-22 2:15PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-14-22 10:22AM
W 2 OTHER UNLEADED GROSS LINE FAIL CLEAR 7-14-22 10:22AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-14-22 10:22AM
W 1 OTHER SUPER GROSS LINE FAIL CLEAR 7-14-22 10:22AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-14-22 9:50AM
W 2 OTHER UNLEADED GROSS LINE FAIL ALARM 7-14-22 9:50AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-14-22 9:38AM
W 1 OTHER SUPER GROSS LINE FAIL ALARM 7-14-22 9:38AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-14-22 8:51AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-14-22 8:51AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-14-22 8:51AM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 7-14-22 8:51AM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 7-14-22 8:51AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-14-22 8:51AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-14-22 8:51AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-14-22 8:51AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-14-22 8:47AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-14-22 8:47AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-14-22 8:47AM
L 1 DISP PAN UDC 1-2 FUEL ALARM CLEAR 7-14-22 8:47AM
L 1 DISP PAN UDC 1-2 FUEL ALARM ALARM 7-14-22 8:47AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-14-22 8:47AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-14-22 8:47AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-14-22 8:47AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-12-22 1:39PM
W 2 OTHER UNLEADED GROSS LINE FAIL CLEAR 7-12-22 1:39PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-12-22 12:50PM
W 2 OTHER UNLEADED GROSS LINE FAIL ALARM 7-12-22 12:50PM
T 2 TANK UNLEADED LOW PRODUCT ALARM CLEAR 7-07-22 2:21PM
T 4 TANK DIESEL LOW PRODUCT ALARM CLEAR 7-07-22 2:16PM
OTHER MISSING TANK SETUP CLEAR 7-07-22 10:00AM
I11200
JUL 21, 2022 1:51 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 7-21-22 1:44PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 7-21-22 10:02AM
SYSTEM PRINTER ERROR CLEAR 7-20-22 8:05AM
SYSTEM PAPER OUT CLEAR 7-20-22 8:05AM
SYSTEM PRINTER ERROR ALARM 7-20-22 8:05AM
SYSTEM PAPER OUT ALARM 7-20-22 8:05AM
SYSTEM PRINTER ERROR CLEAR 7-20-22 8:05AM
SYSTEM PAPER OUT CLEAR 7-20-22 8:05AM
SYSTEM PRINTER ERROR ALARM 7-20-22 8:00AM
SYSTEM PAPER OUT ALARM 7-20-22 8:00AM
T 3 TANK SUPER HIGH WATER WARNING CLEAR 7-15-22 2:28PM
T 3 TANK SUPER HIGH PRODUCT ALARM CLEAR 7-15-22 2:28PM
T 3 TANK SUPER INVALID FUEL LEVEL CLEAR 7-15-22 2:24PM
T 3 TANK SUPER HIGH PRODUCT ALARM ALARM 7-15-22 2:24PM
T 3 TANK SUPER DELIVERY NEEDED CLEAR 7-15-22 2:24PM
T 3 TANK SUPER HIGH WATER WARNING ALARM 7-15-22 2:19PM
T 3 TANK SUPER DELIVERY NEEDED ALARM 7-15-22 2:18PM
T 3 TANK SUPER INVALID FUEL LEVEL ALARM 7-15-22 2:18PM
T 3 TANK SUPER HIGH PRODUCT ALARM CLEAR 7-15-22 2:15PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 7-14-22 10:25AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 7-14-22 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 7-12-22 5:34PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 7-11-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 7-10-22 10:01AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 7-10-22 10:00AM
OTHER ISD GROSS PRES WARN ALARM 7-08-22 10:01AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 7-08-22 10:01AM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 7-07-22 2:21PM
T 2 TANK UNLEADED INVALID FUEL LEVEL CLEAR 7-07-22 2:20PM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 7-07-22 2:16PM
T 4 TANK DIESEL INVALID FUEL LEVEL CLEAR 7-07-22 2:14PM
OTHER ISD SENSOR OUT WARN CLEAR 7-07-22 10:01AM
OTHER ISD SETUP WARN CLEAR 7-07-22 10:00AM
T 3 TANK SUPER HIGH PRODUCT ALARM ALARM 7-06-22 12:20PM
T 3 TANK SUPER DELIVERY NEEDED CLEAR 7-06-22 12:20PM
T 3 TANK SUPER INVALID FUEL LEVEL CLEAR 7-06-22 12:20PM
T 2 TANK UNLEADED INVALID FUEL LEVEL ALARM 7-06-22 11:22AM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 7-06-22 11:21AM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 7-06-22 11:21AM
T 2 TANK UNLEADED INVALID FUEL LEVEL CLEAR 7-06-22 11:21AM
OTHER ISD SENSOR OUT WARN ALARM 7-06-22 10:01AM
OTHER ISD SETUP WARN ALARM 7-06-22 10:01AM
T 2 TANK UNLEADED INVALID FUEL LEVEL ALARM 7-05-22 9:15AM
T 3 TANK SUPER INVALID FUEL LEVEL ALARM 7-05-22 8:51AM
T 3 TANK SUPER DELIVERY NEEDED ALARM 7-05-22 8:49AM
T 4 TANK DIESEL INVALID FUEL LEVEL ALARM 7-05-22 8:19AM
T 4 TANK DIESEL DELIVERY NEEDED ALARM 7-05-22 8:14AM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 7-04-22 5:35PM
SYSTEM PRINTER ERROR CLEAR 6-26-22 8:01AM
SYSTEM PAPER OUT CLEAR 6-26-22 8:01AM
I20600
JUL 21, 2022 1:51 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
TANK ALARM HISTORY
TANK 2 UNLEADED
HIGH WATER ALARM AUG 13, 2014 10:07 AM
OVERFILL ALARM MAY 7, 2022 1:10 AM
DEC 7, 2021 11:15 PM
OCT 10, 2021 5:56 AM
LOW PRODUCT ALARM JUL 6, 2022 11:21 AM
JUL 4, 2022 5:35 PM
JUN 12, 2022 11:32 PM
SUDDEN LOSS ALARM FEB 1, 2020 4:26 AM
FEB 1, 2020 3:55 AM
FEB 1, 2020 3:49 AM
HIGH PRODUCT ALARM AUG 18, 2020 11:26 AM
JUL 21, 2020 1:26 PM
AUG 19, 2019 10:00 AM
INVALID FUEL LEVEL JUL 6, 2022 11:22 AM
JUL 5, 2022 9:15 AM
OCT 13, 2020 5:25 AM
PROBE OUT JUL 6, 2022 11:29 AM
JUL 5, 2022 10:26 AM
AUG 18, 2020 11:37 AM
HIGH WATER WARNING AUG 13, 2014 10:07 AM
DELIVERY NEEDED JUL 6, 2022 11:21 AM
JUL 4, 2022 5:35 PM
JUN 12, 2022 11:32 PM
MAX PRODUCT ALARM JUL 21, 2020 1:26 PM
AUG 4, 2017 9:14 AM
NO CSLD IDLE TIME JAN 27, 2021 6:53 AM
JAN 24, 2021 10:09 PM
DEC 10, 2020 11:15 PM
LOW TEMP WARNING JUL 31, 2018 3:15 PM
AUG 9, 2017 9:23 AM
AUG 11, 2016 9:48 AM
TANK 3 SUPER
HIGH WATER ALARM JUL 15, 2022 2:19 PM
OVERFILL ALARM JUL 15, 2022 2:25 PM
AUG 18, 2020 11:25 AM
AUG 4, 2017 9:51 AM
LOW PRODUCT ALARM JUL 15, 2022 2:18 PM
JUL 5, 2022 8:49 AM
MAY 12, 2020 1:11 PM
SUDDEN LOSS ALARM JUL 15, 2022 2:20 PM
JUL 5, 2022 9:19 AM
JUL 5, 2022 8:48 AM
HIGH PRODUCT ALARM JUL 15, 2022 2:24 PM
JUL 6, 2022 12:20 PM
MAY 12, 2021 10:11 AM
INVALID FUEL LEVEL JUL 15, 2022 2:18 PM
JUL 5, 2022 8:51 AM
MAY 12, 2021 9:38 AM
PROBE OUT JUL 5, 2022 10:29 AM
MAY 12, 2021 10:07 AM
MAY 12, 2021 9:38 AM
HIGH WATER WARNING JUL 15, 2022 2:19 PM
AUG 18, 2020 11:19 AM
DELIVERY NEEDED JUL 15, 2022 2:18 PM
JUL 5, 2022 8:49 AM
MAY 12, 2020 1:11 PM
MAX PRODUCT ALARM JUL 15, 2022 2:24 PM
JUL 6, 2022 12:20 PM
MAY 12, 2021 10:11 AM
NO CSLD IDLE TIME JAN 24, 2021 10:18 PM
DEC 10, 2020 11:23 PM
LOW TEMP WARNING MAY 12, 2021 10:11 AM
AUG 18, 2020 11:41 AM
AUG 22, 2017 10:23 AM
TANK 4 DIESEL
HIGH WATER ALARM AUG 18, 2020 11:32 AM
OVERFILL ALARM AUG 18, 2020 11:28 AM
AUG 7, 2018 9:41 AM
JUL 31, 2018 3:12 PM
LOW PRODUCT ALARM JUL 5, 2022 8:14 AM
SEP 16, 2021 10:14 AM
AUG 31, 2021 6:51 PM
SUDDEN LOSS ALARM JUL 5, 2022 8:28 AM
JUL 5, 2022 8:03 AM
AUG 4, 2017 8:55 AM
HIGH PRODUCT ALARM AUG 19, 2019 9:57 AM
JUL 31, 2018 3:12 PM
AUG 9, 2017 9:17 AM
INVALID FUEL LEVEL JUL 5, 2022 8:19 AM
AUG 18, 2020 11:52 AM
AUG 18, 2020 11:44 AM
PROBE OUT JUL 5, 2022 10:54 AM
AUG 18, 2020 11:51 AM
AUG 18, 2020 11:47 AM
HIGH WATER WARNING AUG 18, 2020 11:32 AM
DELIVERY NEEDED JUL 5, 2022 8:14 AM
SEP 16, 2021 10:14 AM
AUG 31, 2021 6:51 PM
LOW TEMP WARNING AUG 18, 2020 11:22 AM
AUG 11, 2016 9:44 AM
AUG 10, 2015 11:01 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 21, 2022 1:52 PM
I30200
JUL 21, 2022 1:52 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UDC 1-2
JUL 21, 2022 8:37 AM FUEL ALARM
JUL 14, 2022 8:51 AM SENSOR OUT ALARM
JUL 14, 2022 8:47 AM FUEL ALARM
I31600
JUL 21, 2022 1:52 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP SENSOR 3-4
SEP 1, 2020 2:01 PM COMMUNICATION ALARM
MAY 1, 2014 5:23 PM COMMUNICATION ALARM
2 VFM 1-2
3 VFM 3-4
I40200
JUL 21, 2022 1:52 PM
I40300
JUL 21, 2022 1:52 PM
I34200
JUL 21, 2022 1:52 PM
I34700
JUL 21, 2022 1:52 PM
IV0100
JUL 21, 2022 1:52 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-07-21 10:02:03 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
22-07-14 10:03:01 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
22-07-12 10:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-11 10:02:42 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-10 10:01:46 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-10 10:01:46 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
22-07-09 10:01:23 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-09 10:01:23 A/L RATIO DEGRADATION FP 1 BLEND3 0.80
22-07-08 10:01:31 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-08 10:01:31 A/L RATIO DEGRADATION FP 1 BLEND3 0.80
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-03-16 10:02:55 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.29
22-03-02 10:02:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 4.35
20-08-29 10:03:17 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
20-08-28 10:04:01 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
19-09-16 10:03:08 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.63
19-07-26 10:02:56 A/L RATIO DEGRADATION FP 1 BLEND3 0.76
19-07-10 10:02:21 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.83
19-06-23 10:01:59 A/L RATIO DEGRADATION FP 3 BLEND3 0.75
18-07-17 10:03:06 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.87
18-03-18 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.32
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-07-21 13:44:50 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
22-07-21 10:26:46 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-07-21 10:26:46 ISD STARTUP
22-07-21 10:25:00 ISD SHUTDOWN
22-07-14 10:25:47 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
22-07-14 10:03:01 READINESS ISD:PP EVR:PP ISD & EVR READY
22-07-14 08:52:48 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-07-14 08:52:48 ISD STARTUP
22-07-14 08:52:04 ISD SHUTDOWN
22-07-12 17:34:39 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
ALARM HISTORY (AFTER)
Responses Received:
I10200
JUL 21, 2022 5:07 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 163895 163083
2 INTERSTITIAL BD 201249 200703
3 7SMARTSENSOR BD 9865629 503585
4 UNUSED 9830660 4929622
5 UNUSED 9822698 4924883
6 UNUSED 9822698 4926274
7 UNUSED 9822174 4927318
8 UNUSED 9816831 4925144
9 WPLLD POWER BD 201158 201042
10 AC INTERFACE BD 163488 163177
11 RELAY BOARD 15049 15043
12 UNUSED 9832520 4929470
13 UNUSED 9813998 4929883
14 UNUSED 9818146 4928992
15 UNUSED 9810562 4929188
16 UNUSED 9815423 4929035
COMM 1 ELEC DISP INT. 100267 100118
COMM 2 WPLLD COMM BD 201900 201701
COMM 3 RS232 SERIAL BD 14902 14890
COMM 4 UNUSED 9825501 4931079
COMM 5 RS485 SERIAL BD 9815800 68187
COMM 6 RS232 SERIAL BD 9814270 14912
I90200
JUL 21, 2022 5:07 PM
SOFTWARE REVISION LEVEL
VERSION 333.05
SOFTWARE# 346333-100-F
CREATED - 13.12.11.14.16
S-MODULE# 330160-016-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
ISD/APM
PLLD
0.10 REPETITIV
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I11100
JUL 21, 2022 5:08 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-21-22 4:41PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-21-22 4:41PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-21-22 4:41PM
L 1 DISP PAN UDC 1-2 FUEL ALARM CLEAR 7-21-22 4:41PM
L 1 DISP PAN UDC 1-2 FUEL ALARM ALARM 7-21-22 4:36PM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-21-22 4:36PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-21-22 4:36PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-21-22 4:36PM
T 3 TANK SUPER MAX PRODUCT ALARM CLEAR 7-21-22 4:16PM
T 2 TANK UNLEADED MAX PRODUCT ALARM CLEAR 7-21-22 4:14PM
T 3 TANK SUPER MAX PRODUCT ALARM ALARM 7-21-22 4:14PM
T 2 TANK UNLEADED MAX PRODUCT ALARM ALARM 7-21-22 4:12PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-21-22 3:45PM
W 1 OTHER SUPER GROSS LINE FAIL CLEAR 7-21-22 3:45PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-21-22 3:43PM
W 1 OTHER SUPER GROSS LINE FAIL ALARM 7-21-22 3:43PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-21-22 3:31PM
W 2 OTHER UNLEADED GROSS LINE FAIL CLEAR 7-21-22 3:31PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-21-22 3:29PM
W 2 OTHER UNLEADED GROSS LINE FAIL ALARM 7-21-22 3:29PM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-21-22 2:36PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-21-22 2:36PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-21-22 2:36PM
L 1 DISP PAN UDC 1-2 FUEL ALARM CLEAR 7-21-22 2:36PM
L 1 DISP PAN UDC 1-2 FUEL ALARM ALARM 7-21-22 2:22PM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-21-22 2:22PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-21-22 2:22PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-21-22 2:22PM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-21-22 2:11PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-21-22 2:11PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-21-22 2:11PM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 7-21-22 2:11PM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 7-21-22 2:10PM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-21-22 2:10PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-21-22 2:10PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-21-22 2:10PM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-21-22 2:09PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-21-22 2:09PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-21-22 2:09PM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 7-21-22 2:09PM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 7-21-22 2:08PM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-21-22 2:08PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-21-22 2:08PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-21-22 2:08PM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-21-22 1:57PM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-21-22 1:57PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-21-22 1:57PM
L 1 DISP PAN UDC 1-2 FUEL ALARM CLEAR 7-21-22 1:57PM
L 1 DISP PAN UDC 1-2 FUEL ALARM ALARM 7-21-22 1:57PM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-21-22 1:57PM
I11200
JUL 21, 2022 5:08 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 4 TANK DIESEL HIGH PRODUCT ALARM CLEAR 7-21-22 4:16PM
T 3 TANK SUPER HIGH PRODUCT ALARM CLEAR 7-21-22 4:16PM
T 4 TANK DIESEL HIGH PRODUCT ALARM ALARM 7-21-22 4:16PM
T 2 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 7-21-22 4:14PM
T 3 TANK SUPER HIGH PRODUCT ALARM ALARM 7-21-22 4:14PM
T 2 TANK UNLEADED HIGH PRODUCT ALARM ALARM 7-21-22 4:12PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 7-21-22 1:44PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 7-21-22 10:02AM
SYSTEM PRINTER ERROR CLEAR 7-20-22 8:05AM
SYSTEM PAPER OUT CLEAR 7-20-22 8:05AM
SYSTEM PRINTER ERROR ALARM 7-20-22 8:05AM
SYSTEM PAPER OUT ALARM 7-20-22 8:05AM
SYSTEM PRINTER ERROR CLEAR 7-20-22 8:05AM
SYSTEM PAPER OUT CLEAR 7-20-22 8:05AM
SYSTEM PRINTER ERROR ALARM 7-20-22 8:00AM
SYSTEM PAPER OUT ALARM 7-20-22 8:00AM
T 3 TANK SUPER HIGH WATER WARNING CLEAR 7-15-22 2:28PM
T 3 TANK SUPER HIGH PRODUCT ALARM CLEAR 7-15-22 2:28PM
T 3 TANK SUPER INVALID FUEL LEVEL CLEAR 7-15-22 2:24PM
T 3 TANK SUPER HIGH PRODUCT ALARM ALARM 7-15-22 2:24PM
T 3 TANK SUPER DELIVERY NEEDED CLEAR 7-15-22 2:24PM
T 3 TANK SUPER HIGH WATER WARNING ALARM 7-15-22 2:19PM
T 3 TANK SUPER DELIVERY NEEDED ALARM 7-15-22 2:18PM
T 3 TANK SUPER INVALID FUEL LEVEL ALARM 7-15-22 2:18PM
T 3 TANK SUPER HIGH PRODUCT ALARM CLEAR 7-15-22 2:15PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 7-14-22 10:25AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 7-14-22 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 7-12-22 5:34PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 7-11-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 7-10-22 10:01AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 7-10-22 10:00AM
OTHER ISD GROSS PRES WARN ALARM 7-08-22 10:01AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 7-08-22 10:01AM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 7-07-22 2:21PM
T 2 TANK UNLEADED INVALID FUEL LEVEL CLEAR 7-07-22 2:20PM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 7-07-22 2:16PM
T 4 TANK DIESEL INVALID FUEL LEVEL CLEAR 7-07-22 2:14PM
OTHER ISD SENSOR OUT WARN CLEAR 7-07-22 10:01AM
OTHER ISD SETUP WARN CLEAR 7-07-22 10:00AM
T 3 TANK SUPER HIGH PRODUCT ALARM ALARM 7-06-22 12:20PM
T 3 TANK SUPER DELIVERY NEEDED CLEAR 7-06-22 12:20PM
T 3 TANK SUPER INVALID FUEL LEVEL CLEAR 7-06-22 12:20PM
T 2 TANK UNLEADED INVALID FUEL LEVEL ALARM 7-06-22 11:22AM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 7-06-22 11:21AM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 7-06-22 11:21AM
T 2 TANK UNLEADED INVALID FUEL LEVEL CLEAR 7-06-22 11:21AM
OTHER ISD SENSOR OUT WARN ALARM 7-06-22 10:01AM
OTHER ISD SETUP WARN ALARM 7-06-22 10:01AM
T 2 TANK UNLEADED INVALID FUEL LEVEL ALARM 7-05-22 9:15AM
T 3 TANK SUPER INVALID FUEL LEVEL ALARM 7-05-22 8:51AM
I20600
JUL 21, 2022 5:08 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
TANK ALARM HISTORY
TANK 2 UNLEADED
HIGH WATER ALARM AUG 13, 2014 10:07 AM
OVERFILL ALARM MAY 7, 2022 1:10 AM
DEC 7, 2021 11:15 PM
OCT 10, 2021 5:56 AM
LOW PRODUCT ALARM JUL 6, 2022 11:21 AM
JUL 4, 2022 5:35 PM
JUN 12, 2022 11:32 PM
SUDDEN LOSS ALARM FEB 1, 2020 4:26 AM
FEB 1, 2020 3:55 AM
FEB 1, 2020 3:49 AM
HIGH PRODUCT ALARM JUL 21, 2022 4:12 PM
AUG 18, 2020 11:26 AM
JUL 21, 2020 1:26 PM
INVALID FUEL LEVEL JUL 6, 2022 11:22 AM
JUL 5, 2022 9:15 AM
OCT 13, 2020 5:25 AM
PROBE OUT JUL 6, 2022 11:29 AM
JUL 5, 2022 10:26 AM
AUG 18, 2020 11:37 AM
HIGH WATER WARNING AUG 13, 2014 10:07 AM
DELIVERY NEEDED JUL 6, 2022 11:21 AM
JUL 4, 2022 5:35 PM
JUN 12, 2022 11:32 PM
MAX PRODUCT ALARM JUL 21, 2022 4:12 PM
JUL 21, 2020 1:26 PM
AUG 4, 2017 9:14 AM
NO CSLD IDLE TIME JAN 27, 2021 6:53 AM
JAN 24, 2021 10:09 PM
DEC 10, 2020 11:15 PM
LOW TEMP WARNING JUL 31, 2018 3:15 PM
AUG 9, 2017 9:23 AM
AUG 11, 2016 9:48 AM
TANK 3 SUPER
HIGH WATER ALARM JUL 15, 2022 2:19 PM
OVERFILL ALARM JUL 15, 2022 2:25 PM
AUG 18, 2020 11:25 AM
AUG 4, 2017 9:51 AM
LOW PRODUCT ALARM JUL 15, 2022 2:18 PM
JUL 5, 2022 8:49 AM
MAY 12, 2020 1:11 PM
SUDDEN LOSS ALARM JUL 15, 2022 2:20 PM
JUL 5, 2022 9:19 AM
JUL 5, 2022 8:48 AM
HIGH PRODUCT ALARM JUL 21, 2022 4:14 PM
JUL 15, 2022 2:24 PM
JUL 6, 2022 12:20 PM
INVALID FUEL LEVEL JUL 15, 2022 2:18 PM
JUL 5, 2022 8:51 AM
MAY 12, 2021 9:38 AM
PROBE OUT JUL 5, 2022 10:29 AM
MAY 12, 2021 10:07 AM
MAY 12, 2021 9:38 AM
HIGH WATER WARNING JUL 15, 2022 2:19 PM
AUG 18, 2020 11:19 AM
DELIVERY NEEDED JUL 15, 2022 2:18 PM
JUL 5, 2022 8:49 AM
MAY 12, 2020 1:11 PM
MAX PRODUCT ALARM JUL 21, 2022 4:14 PM
JUL 15, 2022 2:24 PM
JUL 6, 2022 12:20 PM
NO CSLD IDLE TIME JAN 24, 2021 10:18 PM
DEC 10, 2020 11:23 PM
LOW TEMP WARNING MAY 12, 2021 10:11 AM
AUG 18, 2020 11:41 AM
AUG 22, 2017 10:23 AM
TANK 4 DIESEL
HIGH WATER ALARM AUG 18, 2020 11:32 AM
OVERFILL ALARM AUG 18, 2020 11:28 AM
AUG 7, 2018 9:41 AM
JUL 31, 2018 3:12 PM
LOW PRODUCT ALARM JUL 5, 2022 8:14 AM
SEP 16, 2021 10:14 AM
AUG 31, 2021 6:51 PM
SUDDEN LOSS ALARM JUL 5, 2022 8:28 AM
JUL 5, 2022 8:03 AM
AUG 4, 2017 8:55 AM
HIGH PRODUCT ALARM JUL 21, 2022 4:16 PM
AUG 19, 2019 9:57 AM
JUL 31, 2018 3:12 PM
INVALID FUEL LEVEL JUL 5, 2022 8:19 AM
AUG 18, 2020 11:52 AM
AUG 18, 2020 11:44 AM
PROBE OUT JUL 5, 2022 10:54 AM
AUG 18, 2020 11:51 AM
AUG 18, 2020 11:47 AM
HIGH WATER WARNING AUG 18, 2020 11:32 AM
DELIVERY NEEDED JUL 5, 2022 8:14 AM
SEP 16, 2021 10:14 AM
AUG 31, 2021 6:51 PM
LOW TEMP WARNING AUG 18, 2020 11:22 AM
AUG 11, 2016 9:44 AM
AUG 10, 2015 11:01 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 21, 2022 5:08 PM
I30200
JUL 21, 2022 5:08 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UDC 1-2
JUL 21, 2022 4:36 PM FUEL ALARM
JUL 21, 2022 2:22 PM FUEL ALARM
JUL 21, 2022 2:10 PM SENSOR OUT ALARM
I31600
JUL 21, 2022 5:08 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP SENSOR 3-4
SEP 1, 2020 2:01 PM COMMUNICATION ALARM
MAY 1, 2014 5:23 PM COMMUNICATION ALARM
2 VFM 1-2
3 VFM 3-4
I40200
JUL 21, 2022 5:08 PM
I40300
JUL 21, 2022 5:08 PM
I34200
JUL 21, 2022 5:08 PM
I34700
JUL 21, 2022 5:08 PM
IV0100
JUL 21, 2022 5:08 PM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-07-21 10:02:03 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
22-07-14 10:03:01 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
22-07-12 10:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-11 10:02:42 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-10 10:01:46 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-10 10:01:46 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
22-07-09 10:01:23 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-09 10:01:23 A/L RATIO DEGRADATION FP 1 BLEND3 0.80
22-07-08 10:01:31 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.67
22-07-08 10:01:31 A/L RATIO DEGRADATION FP 1 BLEND3 0.80
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-03-16 10:02:55 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.29
22-03-02 10:02:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 4.35
20-08-29 10:03:17 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
20-08-28 10:04:01 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
19-09-16 10:03:08 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.63
19-07-26 10:02:56 A/L RATIO DEGRADATION FP 1 BLEND3 0.76
19-07-10 10:02:21 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.83
19-06-23 10:01:59 A/L RATIO DEGRADATION FP 3 BLEND3 0.75
18-07-17 10:03:06 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.87
18-03-18 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.32
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-07-21 13:44:50 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
22-07-21 10:26:46 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-07-21 10:26:46 ISD STARTUP
22-07-21 10:25:00 ISD SHUTDOWN
22-07-14 10:25:47 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
22-07-14 10:03:01 READINESS ISD:PP EVR:PP ISD & EVR READY
22-07-14 08:52:48 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-07-14 08:52:48 ISD STARTUP
22-07-14 08:52:04 ISD SHUTDOWN
22-07-12 17:34:39 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED