HomeMy WebLinkAboutFMC 2022Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10026730 10/3/2022 White Lane Gas LLC 2601 White Lane Bakersfield 93304 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Aaron Perrigo 1073967 8485827 8/8/2024 Veeder Root B47853 7/31/2024 OPW 0148613 8/21/2024 10/3/2022 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder Root TLS-350 334.01 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 91 STP L2 208 91 Fill L3 208 87 STP L4 208 87 Fill L5 208 UDC 1-2 L6 208 UDC 3-4 L7 208 UDC 5-6 L8 208 UDC 7-8 L9 420 87/91 Ann Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V 87 T2 FX1V 91 Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  White Lane Gas LLC2601 White LaneBakersfield100267303-47-8MPD MPD MPD MPD 1-25-6ProductProductProductProductAaron Perrigo Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10026730 10/3/2022 White Lane Gas LLC 2601 White Lane Bakersfield 93304 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Aaron Perrigo 1073967 8485827 8/8/2024 OPW 0148613 8/21/2024 Lake Test Both fill spill buckets 10/3/2022 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. 87 OPW 91 OPW FJM Setup Responses Received: 200 MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 10-03-22 8:59 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 PREM 91 3224 48.28 0.0 85.1 4776 2 UNLEADED 87 6457 60.41 0.0 85.8 5543 I90500 10-03-22 8:59 AM SOFTWARE REVISION LEVEL VERSION 334.01 SOFTWARE# 346334-100-B CREATED - 17.01.09.16.10 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 10-03-22 8:59 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MM-DD-YY HH:MM:SS xM I50201 10-03-22 8:59 AM SHIFT TIME 1 : 12:00 AM I50202 10-03-22 8:59 AM SHIFT TIME 2 : 12:05 AM I50203 10-03-22 8:59 AM SHIFT TIME 3 : DISABLED I50204 10-03-22 8:59 AM SHIFT TIME 4 : DISABLED I54600 10-03-22 8:59 AM TANK PER TST NEEDED WRN: DISABLED I54900 10-03-22 8:59 AM TANK ANN TST NEEDED WRN: DISABLED I55300 10-03-22 8:59 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 10-03-22 8:59 AM LINE PER TST NEEDED WRN: DISABLED I55900 10-03-22 8:59 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 10-03-22 8:59 AM PRINT TC VOLUMES ENABLED I50E00 10-03-22 8:59 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 10-03-22 8:59 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 10-03-22 8:59 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 10-03-22 8:59 AM DAYLIGHT SAVING TIME DISABLED I51B00 10-03-22 8:59 AM I51600 10-03-22 8:59 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 10-03-22 8:59 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 10-03-22 8:59 AM TANK CHART SECURITY DISABLED I5BD00 10-03-22 8:59 AM CUSTOM ALARM LABELS DISABLED I56000 10-03-22 8:59 AM MASS/DENSITY DISABLED I88101 10-03-22 8:59 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88102 10-03-22 8:59 AM PORT SETTINGS: COMM BOARD : 2 (EDIM ) RS-232 SECURITY CODE : DISABLED I88103 10-03-22 8:59 AM I88104 10-03-22 8:59 AM I88105 10-03-22 8:59 AM I88106 10-03-22 8:59 AM I52000 10-03-22 8:59 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE AUG 21, 2017 DISABLED 2 ON DATE AUG 21, 2017 DISABLED 3 ON DATE AUG 21, 2017 DISABLED 4 ON DATE AUG 21, 2017 DISABLED 5 ON DATE AUG 21, 2017 DISABLED 6 ON DATE AUG 21, 2017 DISABLED 7 ON DATE AUG 21, 2017 DISABLED 8 ON DATE AUG 21, 2017 DISABLED I60100 10-03-22 8:59 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 PREM 91 ON 2 UNLEADED 87 ON 3 OFF 4 OFF I60200 10-03-22 8:59 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 PREM 91 2 UNLEADED 87 3 4 I60300 10-03-22 8:59 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 PREM 91 2 2 UNLEADED 87 1 3 3 4 4 I60900 10-03-22 8:59 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 PREM 91 0.000700 2 UNLEADED 87 0.000700 3 0.000000 4 0.000000 I60700 10-03-22 8:59 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 PREM 91 114.00 2 UNLEADED 87 114.00 3 0.00 4 0.00 I60A00 10-03-22 8:59 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 PREM 91 1 PT 8000 2 UNLEADED 87 1 PT 12000 3 1 PT 0 4 1 PT 0 I60400 10-03-22 8:59 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 PREM 91 8000 2 UNLEADED 87 12000 3 0 4 0 I60500 10-03-22 8:59 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 PREM 91 8000 0 0 0 2 UNLEADED 87 12000 0 0 0 3 0 0 0 0 4 0 0 0 0 I60600 10-03-22 8:59 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 PREM 91 8000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 UNLEADED 87 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 10-03-22 8:59 AM TANK PRODUCT LABEL METER DATA 1 PREM 91 NO 2 UNLEADED 87 NO 3 NO 4 NO I62F00 10-03-22 8:59 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 PREM 91 4.0 IN. 2 UNLEADED 87 4.0 IN. I62700 10-03-22 8:59 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 PREM 91 2.0 2 UNLEADED 87 2.0 I64200 10-03-22 8:59 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 PREM 91 LOW 2 UNLEADED 87 LOW I62400 10-03-22 8:59 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 PREM 91 2.5 2 UNLEADED 87 2.5 I62800 10-03-22 8:59 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 8000 2 UNLEADED 87 12000 3 0 4 0 I62300 10-03-22 8:59 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 7200 2 UNLEADED 87 10800 3 0 4 0 I62200 10-03-22 8:59 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 7600 2 UNLEADED 87 11400 3 0 4 0 I62900 10-03-22 8:59 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 2000 2 UNLEADED 87 2040 3 0 4 0 I62100 10-03-22 8:59 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 500 2 UNLEADED 87 600 3 0 4 0 I62600 10-03-22 8:59 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 99 2 UNLEADED 87 99 3 99 4 99 I62500 10-03-22 8:59 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 99 2 UNLEADED 87 99 3 99 4 99 I60800 10-03-22 8:59 AM TANK TILT TANK PRODUCT LABEL INCHES 1 PREM 91 0.00 2 UNLEADED 87 0.00 3 0.00 4 0.00 I60B00 10-03-22 8:59 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 10-03-22 8:59 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 PREM 91 0.00 2 UNLEADED 87 0.00 3 0.00 4 0.00 I61200 10-03-22 8:59 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 PREM 91 NONE NONE 2 UNLEADED 87 NONE NONE 3 NONE NONE 4 NONE NONE I63600 10-03-22 8:59 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 PREM 91 0 2 UNLEADED 87 0 3 0 4 0 I62A00 10-03-22 8:59 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 PREM 91 0 2 UNLEADED 87 0 3 0 4 0 I62C00 10-03-22 8:59 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 PREM 91 STANDARD 2 UNLEADED 87 STANDARD 3 STANDARD 4 STANDARD I62D00 10-03-22 8:59 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 PREM 91 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 UNLEADED 87 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 10-03-22 8:59 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 PREM 91 OFF OFF 2 UNLEADED 87 OFF OFF 3 OFF OFF 4 OFF OFF I63000 10-03-22 8:59 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 PREM 91 OFF 2 UNLEADED 87 OFF 3 OFF 4 OFF I63200 10-03-22 8:59 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 PREM 91 OFF 2 UNLEADED 87 OFF 3 OFF 4 OFF I61000 10-03-22 8:59 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 PREM 91 1 2 UNLEADED 87 1 3 1 4 1 I63A00 10-03-22 8:59 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 PREM 91 10.00% 2 UNLEADED 87 10.00% 3 10.00% 4 10.00% I61100 10-03-22 8:59 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK FEB 27, 2020 START TIME : 7:55 PM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 10-03-22 8:59 AM CSLD PROBABLITY OF DETECTION I61400 10-03-22 8:59 AM CSLD CLIMATE FACTOR I61600 10-03-22 8:59 AM TANK PRODUCT LABEL CAL UPDATE 1 PREM 91 IMMEDIATE 2 UNLEADED 87 IMMEDIATE 3 IMMEDIATE 4 IMMEDIATE I61A00 10-03-22 8:59 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 PREM 91 DISABLED 2 UNLEADED 87 DISABLED 3 DISABLED 4 DISABLED I61B00 10-03-22 8:59 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 10-03-22 8:59 AM CSLD REPORT ONLY I62B00 10-03-22 8:59 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 PREM 91 00-00-00 2 UNLEADED 87 00-00-00 3 00-00-00 4 00-00-00 I63300 10-03-22 8:59 AM LEAK TEST REPORT FORMAT: NORMAL I63400 10-03-22 8:59 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 0 2 UNLEADED 87 0 3 0 4 0 I63500 10-03-22 8:59 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 1 2 UNLEADED 87 1 3 1 4 1 I63900 10-03-22 8:59 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 PREM 91 END FACTOR: NONE 2 UNLEADED 87 END FACTOR: NONE 3 END FACTOR: NONE 4 END FACTOR: NONE I78000 10-03-22 8:59 AM I77700 10-03-22 8:59 AM I77800 10-03-22 8:59 AM I78C00 10-03-22 8:59 AM I78300 10-03-22 8:59 AM I78F00 10-03-22 8:59 AM I78700 10-03-22 8:59 AM I70200 10-03-22 9:00 AM LIQUID LABEL DEVICE LABEL 1 91 STP 2 91 FILL SUMP 3 87 STP 4 87 FILL SUMP 5 UDC 1-2 6 UDC 3-4 7 UDC 5-6 8 UDC 7-8 9 ANNULAR 87-91 10 11 12 13 14 15 16 I70300 10-03-22 9:00 AM LIQUID TYPE SENSOR LOCATION TYPE 1 91 STP TRI-STATE (SINGLE FLOAT) 2 91 FILL SUMP TRI-STATE (SINGLE FLOAT) 3 87 STP TRI-STATE (SINGLE FLOAT) 4 87 FILL SUMP TRI-STATE (SINGLE FLOAT) 5 UDC 1-2 TRI-STATE (SINGLE FLOAT) 6 UDC 3-4 TRI-STATE (SINGLE FLOAT) 7 UDC 5-6 TRI-STATE (SINGLE FLOAT) 8 UDC 7-8 TRI-STATE (SINGLE FLOAT) 9 ANNULAR 87-91 TRI-STATE (SINGLE FLOAT) 10 TRI-STATE (SINGLE FLOAT) 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 10-03-22 9:00 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 91 STP STP SUMP 2 91 FILL SUMP PIPING SUMP 3 87 STP STP SUMP 4 87 FILL SUMP PIPING SUMP 5 UDC 1-2 DISPENSER PAN 6 UDC 3-4 DISPENSER PAN 7 UDC 5-6 DISPENSER PAN 8 UDC 7-8 DISPENSER PAN 9 ANNULAR 87-91 ANNULAR SPACE 10 OTHER SENSORS 11 OTHER SENSORS 12 OTHER SENSORS 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 10-03-22 9:00 AM I74300 10-03-22 9:00 AM I74400 10-03-22 9:00 AM I74700 10-03-22 9:00 AM I74800 10-03-22 9:00 AM I74900 10-03-22 9:00 AM I7BC00 10-03-22 9:00 AM I80200 10-03-22 9:00 AM I80300 10-03-22 9:00 AM I80400 10-03-22 9:00 AM I80700 10-03-22 9:00 AM RELAY LABEL DEVICE LABEL 1 87 UNLEADED 2 PREM 91 3 4 I80900 10-03-22 9:00 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 87 UNLEADED NORMALLY CLOSED 2 PREM 91 NORMALLY CLOSED 3 NORMALLY OPEN 4 NORMALLY OPEN I80B00 10-03-22 9:00 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 87 UNLEADED 2 2 PREM 91 1 3 NONE 4 NONE I80A00 10-03-22 9:00 AM RELAY TYPE RELAY DESIGNATION TYPE 1 87 UNLEADED STANDARD 2 PREM 91 STANDARD 3 STANDARD 4 STANDARD I80C00 10-03-22 9:00 AM I80800 10-03-22 9:00 AM RELAY SETUP REPORT R 1:87 UNLEADED TYPE: STANDARD NORMALLY CLOSED TANK #: 2 IN-TANK ALARMS T 2:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 3:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PREM 91 TYPE: STANDARD NORMALLY CLOSED TANK #: 1 IN-TANK ALARMS T 1:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 1:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP EMISSIONS FAIL R 3: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 10-03-22 9:00 AM EDIM:1 VR:349867-001-D TD:17.02.14.08.38 I79100 10-03-22 9:00 AM I72300 10-03-22 9:00 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VAPOR PRESSURE VAPOR PRESSURE 02 FLOW METER 1-2 AIR FLOW METER 03 FLOW METER 3-4 AIR FLOW METER 04 FLOW METER 5-6 AIR FLOW METER 05 FLOW METER 7-8 AIR FLOW METER 06 VP UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 10-03-22 9:00 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 EVR/ISD SETUP TYPE: BALANCE IV4F00 10-03-22 9:00 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 10-03-22 9:00 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 VAPOR PROCESSOR TYPE NONE IV4700 10-03-22 9:00 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 10-03-22 9:00 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ACCEPT HIGH ORVR: YES IV4A00 10-03-22 9:00 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 02 BLEND3 02 02 02 01 02 BLEND3 03 03 03 02 02 BLEND3 04 04 04 02 02 BLEND3 05 05 05 03 02 BLEND3 06 06 06 03 02 BLEND3 07 07 07 04 02 BLEND3 08 08 08 04 02 BLEND3 IV4B00 10-03-22 9:00 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 01/01 09/01 xx/xx 02 01 02/02 01/02 09/02 xx/xx 03 02 02/03 01/03 09/03 xx/xx 04 02 02/04 01/04 09/04 xx/xx 05 03 02/05 01/05 09/05 xx/xx 06 03 02/06 01/06 09/06 xx/xx 07 04 02/07 01/07 09/07 xx/xx 08 04 02/08 01/08 09/08 xx/xx IV4900 10-03-22 9:00 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 10-03-22 9:00 AM ISD VERSION: 01.05 FJM Alarm History Responses Received: I10200 10-03-22 9:01 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 164738 163403 2 INTERSTITIAL BD 202007 200933 3 INTERSTITIAL BD 202007 201022 4 7SMARTSENSOR BD 507999 504932 5 UNUSED 9903073 9645492 6 UNUSED 9868832 9632843 7 UNUSED 9858988 9634774 8 UNUSED 9856420 9632567 9 RELAY BOARD 14987 14971 10 UNUSED 9859521 9641039 11 UNUSED 9850410 9635945 12 UNUSED 9848494 9631000 13 UNUSED 9844907 9633144 14 UNUSED 9838935 9632719 15 UNUSED 9845213 9631340 16 UNUSED 9841504 9633886 COMM 1 RS232 SERIAL BD 14946 14950 COMM 2 ELEC DISP INT. 101209 100996 COMM 3 UNUSED 9847618 9644095 COMM 4 UNUSED 9841748 9632040 COMM 5 UNUSED 9837448 9630575 COMM 6 UNUSED 9840158 9628262 I90200 10-03-22 9:01 AM SOFTWARE REVISION LEVEL VERSION 334.01 SOFTWARE# 346334-100-B CREATED - 17.01.09.16.10 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 10-03-22 9:01 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 8 OTHER FP8: BLEND3 FLOW COLLECT FAIL CLEAR 08-11-22 1:36 PM h 8 OTHER FP8: BLEND3 FLOW COLLECT FAIL ALARM 08-09-22 10:07 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT FAIL CLEAR 07-26-22 9:52 AM E 1 OTHER COMMUNICATION ALARM CLEAR 07-26-22 9:47 AM E 1 OTHER COMMUNICATION ALARM ALARM 07-26-22 9:47 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT FAIL ALARM 07-25-22 10:07 AM h 3 OTHER FP3: BLEND3 FLOW COLLECT FAIL CLEAR 05-07-22 10:00 AM h 3 OTHER FP3: BLEND3 FLOW COLLECT FAIL ALARM 05-06-22 10:06 AM T 2 TANK UNLEADED 87 OVERFILL ALARM CLEAR 04-07-22 5:54 AM T 2 TANK UNLEADED 87 OVERFILL ALARM ALARM 04-07-22 5:47 AM T 2 TANK UNLEADED 87 OVERFILL ALARM CLEAR 03-30-22 6:04 AM T 2 TANK UNLEADED 87 OVERFILL ALARM ALARM 03-30-22 6:00 AM T 2 TANK UNLEADED 87 OVERFILL ALARM CLEAR 01-13-22 11:32 PM T 2 TANK UNLEADED 87 OVERFILL ALARM ALARM 01-13-22 11:28 PM T 2 TANK UNLEADED 87 OVERFILL ALARM CLEAR 01-06-22 3:28 PM T 2 TANK UNLEADED 87 OVERFILL ALARM ALARM 01-06-22 3:26 PM T 2 TANK UNLEADED 87 OVERFILL ALARM CLEAR 11-28-21 11:55 AM T 2 TANK UNLEADED 87 OVERFILL ALARM ALARM 11-28-21 11:49 AM T 2 TANK UNLEADED 87 OVERFILL ALARM CLEAR 11-22-21 2:02 PM T 2 TANK UNLEADED 87 OVERFILL ALARM ALARM 11-22-21 1:59 PM E 1 OTHER COMMUNICATION ALARM CLEAR 10-19-21 10:32 AM E 1 OTHER COMMUNICATION ALARM ALARM 10-19-21 9:24 AM E 1 OTHER COMMUNICATION ALARM CLEAR 10-18-21 10:25 PM E 1 OTHER COMMUNICATION ALARM ALARM 10-18-21 10:23 PM E 1 OTHER COMMUNICATION ALARM CLEAR 10-18-21 8:08 AM E 1 OTHER COMMUNICATION ALARM ALARM 10-18-21 8:06 AM E 1 OTHER COMMUNICATION ALARM CLEAR 10-18-21 2:24 AM E 1 OTHER COMMUNICATION ALARM ALARM 10-18-21 2:22 AM E 1 OTHER COMMUNICATION ALARM CLEAR 10-14-21 9:09 AM E 1 OTHER COMMUNICATION ALARM ALARM 10-14-21 9:07 AM E 1 OTHER COMMUNICATION ALARM CLEAR 10-11-21 2:24 AM E 1 OTHER COMMUNICATION ALARM ALARM 10-11-21 2:22 AM E 1 OTHER COMMUNICATION ALARM CLEAR 10-04-21 2:38 AM E 1 OTHER COMMUNICATION ALARM ALARM 10-04-21 2:36 AM E 1 OTHER COMMUNICATION ALARM CLEAR 09-27-21 2:27 AM E 1 OTHER COMMUNICATION ALARM ALARM 09-27-21 2:25 AM E 1 OTHER COMMUNICATION ALARM CLEAR 09-20-21 2:12 AM E 1 OTHER COMMUNICATION ALARM ALARM 09-20-21 2:10 AM E 1 OTHER COMMUNICATION ALARM CLEAR 09-13-21 2:08 AM E 1 OTHER COMMUNICATION ALARM ALARM 09-13-21 2:06 AM T 2 TANK UNLEADED 87 OVERFILL ALARM CLEAR 09-10-21 2:42 PM T 2 TANK UNLEADED 87 OVERFILL ALARM ALARM 09-10-21 2:40 PM E 1 OTHER COMMUNICATION ALARM CLEAR 09-06-21 2:18 AM E 1 OTHER COMMUNICATION ALARM ALARM 09-06-21 2:16 AM E 1 OTHER COMMUNICATION ALARM CLEAR 09-05-21 8:31 AM E 1 OTHER COMMUNICATION ALARM ALARM 09-05-21 8:29 AM E 1 OTHER COMMUNICATION ALARM CLEAR 09-02-21 11:01 AM E 1 OTHER COMMUNICATION ALARM ALARM 09-02-21 10:58 AM E 1 OTHER COMMUNICATION ALARM CLEAR 08-30-21 2:14 AM E 1 OTHER COMMUNICATION ALARM ALARM 08-30-21 2:11 AM I11200 10-03-22 9:01 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 09-29-22 6:56 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 09-27-22 8:47 PM SYSTEM PRINTER ERROR CLEAR 09-12-22 12:24 PM SYSTEM PAPER OUT CLEAR 09-12-22 12:24 PM SYSTEM PRINTER ERROR ALARM 09-12-22 12:17 PM SYSTEM PAPER OUT ALARM 09-12-22 12:17 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 09-06-22 8:55 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 09-06-22 8:46 PM SYSTEM PRINTER ERROR CLEAR 09-06-22 4:43 PM SYSTEM PAPER OUT CLEAR 09-06-22 4:43 PM SYSTEM PRINTER ERROR ALARM 09-06-22 4:43 PM SYSTEM PAPER OUT ALARM 09-06-22 4:43 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 09-06-22 3:39 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 09-06-22 1:48 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-27-22 3:24 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-23-22 12:14 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-17-22 10:43 AM SYSTEM PRINTER ERROR CLEAR 08-15-22 12:03 PM SYSTEM PAPER OUT CLEAR 08-15-22 12:03 PM SYSTEM PAPER OUT ALARM 08-15-22 12:02 PM SYSTEM PRINTER ERROR ALARM 08-15-22 12:02 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-12-22 8:23 PM h 8 OTHER FP8: BLEND3 FLOW COLLECT WARN CLEAR 08-09-22 10:00 AM h 8 OTHER FP8: BLEND3 FLOW COLLECT WARN ALARM 08-08-22 10:07 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-06-22 11:10 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-05-22 7:49 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-29-22 6:30 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-27-22 3:21 PM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-25-22 10:00 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-24-22 10:04 AM OTHER ISD VAPOR LEAK WARN CLEAR 07-22-22 2:49 PM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 07-22-22 10:00 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-21-22 11:32 PM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 07-21-22 10:05 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-18-22 12:30 PM SYSTEM PRINTER ERROR CLEAR 07-18-22 12:05 PM SYSTEM PAPER OUT CLEAR 07-18-22 12:05 PM SYSTEM PRINTER ERROR ALARM 07-18-22 12:03 PM SYSTEM PAPER OUT ALARM 07-18-22 12:03 PM OTHER ISD VAPOR LEAK WARN ALARM 07-18-22 10:06 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-13-22 10:56 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-08-22 5:11 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-01-22 5:26 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-29-22 10:05 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-22-22 5:19 AM SYSTEM PRINTER ERROR CLEAR 06-20-22 12:28 PM SYSTEM PAPER OUT CLEAR 06-20-22 12:28 PM SYSTEM PRINTER ERROR ALARM 06-20-22 12:26 PM SYSTEM PAPER OUT ALARM 06-20-22 12:26 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-19-22 12:42 AM I20600 10-03-22 9:01 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 TANK ALARM HISTORY TANK 1 PREM 91 DELIVERY NEEDED 09-27-22 8:47 PM 09-06-22 1:48 AM 08-23-22 12:14 PM PER TST NEEDED ALM 12-23-19 12:00 AM ANN TST NEEDED ALM 12-23-19 12:00 AM TANK 2 UNLEADED 87 OVERFILL ALARM 04-07-22 5:47 AM 03-30-22 6:00 AM 01-13-22 11:28 PM LOW PRODUCT ALARM 07-11-20 12:04 PM 05-18-19 7:09 AM 01-14-19 5:41 PM HIGH PRODUCT ALARM 04-07-22 5:49 AM 06-09-20 5:58 AM 03-23-20 4:17 AM DELIVERY NEEDED 09-06-22 3:39 PM 05-18-22 7:33 PM 03-24-22 3:39 PM PER TST NEEDED ALM 12-23-19 12:00 AM ANN TST NEEDED ALM 12-23-19 12:00 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 10-03-22 9:01 AM I30200 10-03-22 9:01 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 91 STP 08-11-21 9:28 AM SENSOR OUT ALARM 08-11-21 9:17 AM FUEL ALARM 08-24-20 10:05 AM SENSOR OUT ALARM 2 91 FILL SUMP 08-11-21 11:15 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 12-26-20 1:36 AM FUEL ALARM 3 87 STP 08-11-21 9:28 AM SENSOR OUT ALARM 08-11-21 9:17 AM FUEL ALARM 08-24-20 10:05 AM SENSOR OUT ALARM 4 87 FILL SUMP 08-11-21 10:36 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 08-24-20 10:05 AM SENSOR OUT ALARM 5 UDC 1-2 08-11-21 9:28 AM SENSOR OUT ALARM 08-11-21 9:20 AM FUEL ALARM 08-24-20 10:05 AM SENSOR OUT ALARM 6 UDC 3-4 08-11-21 9:28 AM SENSOR OUT ALARM 08-11-21 9:18 AM FUEL ALARM 08-24-20 10:05 AM SENSOR OUT ALARM 7 UDC 5-6 08-11-21 9:28 AM SENSOR OUT ALARM 08-11-21 9:21 AM FUEL ALARM 08-24-20 10:05 AM SENSOR OUT ALARM 8 UDC 7-8 08-11-21 9:28 AM SENSOR OUT ALARM 08-11-21 9:19 AM FUEL ALARM 08-24-20 10:05 AM SENSOR OUT ALARM 9 ANNULAR 87-91 08-11-21 9:28 AM SENSOR OUT ALARM 08-11-21 9:22 AM FUEL ALARM 08-11-21 9:22 AM FUEL ALARM I31600 10-03-22 9:01 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VAPOR PRESSURE 01-29-20 12:19 PM COMMUNICATION ALARM 12-22-17 10:25 AM COMMUNICATION ALARM 12-22-17 9:52 AM COMMUNICATION ALARM 2 FLOW METER 1-2 12-22-17 10:00 AM COMMUNICATION ALARM 3 FLOW METER 3-4 12-22-17 10:00 AM COMMUNICATION ALARM 08-21-17 2:18 PM COMMUNICATION ALARM 4 FLOW METER 5-6 12-03-20 8:21 AM COMMUNICATION ALARM 12-22-17 10:00 AM COMMUNICATION ALARM 08-22-17 10:48 AM COMMUNICATION ALARM 5 FLOW METER 7-8 12-22-17 10:00 AM COMMUNICATION ALARM 08-21-17 2:18 PM COMMUNICATION ALARM I40200 10-03-22 9:01 AM I40300 10-03-22 9:01 AM I34200 10-03-22 9:01 AM I34700 10-03-22 9:01 AM IV0100 10-03-22 9:01 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-08-08 10:07:54 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 0.58 22-07-24 10:04:38 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 0.58 22-07-22 10:04:47 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 78.57 22-07-21 10:05:27 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 69.23 22-07-21 10:05:27 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.60 22-07-20 10:05:25 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 61.84 22-07-19 10:06:46 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 30.37 22-07-18 10:06:28 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.00 22-05-15 10:06:30 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 0.57 22-05-05 10:06:14 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.60 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-08-09 10:07:29 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 22-07-25 10:07:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 22-05-06 10:06:28 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 21-07-14 10:01:12 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-13 10:01:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-12 10:06:23 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-03 10:06:30 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 18-08-07 10:08:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 18-06-12 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 18-06-11 10:06:56 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-08-11 13:36:55 COLLECTION TEST HH08 GRADE TEST MANUALLY CLEARED 22-08-09 10:27:29 PUMPS MANUALLY RE-ENABLED 22-08-09 10:07:29 FLOW PERFORMANCE BLK DISABLED FP 08 BLEND3 22-08-05 10:07:02 READINESS ISD:PP EVR:PP ISD & EVR READY 22-08-04 20:32:42 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-08-04 20:32:42 ISD STARTUP 22-08-04 20:32:40 ISD SHUTDOWN 22-08-04 19:15:46 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-08-04 19:15:46 ISD STARTUP 22-08-04 15:32:10 ISD SHUTDOWN FJM Alarm History After Responses Received: I10200 10-03-22 10:37 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 164738 163313 2 INTERSTITIAL BD 202007 200699 3 INTERSTITIAL BD 202007 200963 4 7SMARTSENSOR BD 507999 504018 5 UNUSED 9903073 9737490 6 UNUSED 9868832 9708816 7 UNUSED 9858988 9702591 8 UNUSED 9856420 9713183 9 RELAY BOARD 14987 14965 10 UNUSED 9859521 9714712 11 UNUSED 9850410 9705491 12 UNUSED 9848494 9713678 13 UNUSED 9844907 9724059 14 UNUSED 9838935 9714374 15 UNUSED 9845213 9701082 16 UNUSED 9841504 9702875 COMM 1 RS232 SERIAL BD 14946 14944 COMM 2 ELEC DISP INT. 101209 100968 COMM 3 UNUSED 9847618 9717286 COMM 4 UNUSED 9841748 9715957 COMM 5 UNUSED 9837448 9723341 COMM 6 UNUSED 9840158 9712412 I90200 10-03-22 10:37 AM SOFTWARE REVISION LEVEL VERSION 334.01 SOFTWARE# 346334-100-B CREATED - 17.01.09.16.10 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 10-03-22 10:37 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 1 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM ALARM 10-03-22 9:46 AM L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 1 STP SUMP 91 STP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 6 DISP PAN UDC 3-4 FUEL ALARM CLEAR 10-03-22 9:40 AM L 6 DISP PAN UDC 3-4 FUEL ALARM ALARM 10-03-22 9:40 AM L 5 DISP PAN UDC 1-2 FUEL ALARM CLEAR 10-03-22 9:39 AM L 5 DISP PAN UDC 1-2 FUEL ALARM ALARM 10-03-22 9:39 AM L 7 DISP PAN UDC 5-6 FUEL ALARM CLEAR 10-03-22 9:39 AM L 7 DISP PAN UDC 5-6 FUEL ALARM ALARM 10-03-22 9:39 AM L 8 DISP PAN UDC 7-8 FUEL ALARM CLEAR 10-03-22 9:38 AM L 8 DISP PAN UDC 7-8 FUEL ALARM ALARM 10-03-22 9:38 AM L 9 ANNULAR ANNULAR 87-91 FUEL ALARM CLEAR 10-03-22 9:37 AM L 9 ANNULAR ANNULAR 87-91 FUEL ALARM ALARM 10-03-22 9:37 AM L 9 ANNULAR ANNULAR 87-91 FUEL ALARM CLEAR 10-03-22 9:37 AM L 9 ANNULAR ANNULAR 87-91 FUEL ALARM ALARM 10-03-22 9:37 AM L 9 ANNULAR ANNULAR 87-91 FUEL ALARM CLEAR 10-03-22 9:37 AM L 9 ANNULAR ANNULAR 87-91 FUEL ALARM ALARM 10-03-22 9:37 AM L 4 PIPE 87 FILL SUMP FUEL ALARM CLEAR 10-03-22 9:36 AM L 4 PIPE 87 FILL SUMP FUEL ALARM ALARM 10-03-22 9:36 AM L 2 PIPE 91 FILL SUMP FUEL ALARM CLEAR 10-03-22 9:35 AM L 2 PIPE 91 FILL SUMP FUEL ALARM ALARM 10-03-22 9:35 AM L 3 STP SUMP 87 STP FUEL ALARM CLEAR 10-03-22 9:34 AM L 3 STP SUMP 87 STP FUEL ALARM ALARM 10-03-22 9:34 AM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 10-03-22 9:34 AM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 10-03-22 9:31 AM L 3 STP SUMP 87 STP FUEL ALARM CLEAR 10-03-22 9:31 AM L 3 STP SUMP 87 STP FUEL ALARM ALARM 10-03-22 9:31 AM L 3 STP SUMP 87 STP FUEL ALARM CLEAR 10-03-22 9:31 AM L 3 STP SUMP 87 STP FUEL ALARM ALARM 10-03-22 9:31 AM L 1 STP SUMP 91 STP FUEL ALARM CLEAR 10-03-22 9:24 AM L 1 STP SUMP 91 STP FUEL ALARM ALARM 10-03-22 9:24 AM h 8 OTHER FP8: BLEND3 FLOW COLLECT FAIL CLEAR 08-11-22 1:36 PM h 8 OTHER FP8: BLEND3 FLOW COLLECT FAIL ALARM 08-09-22 10:07 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT FAIL CLEAR 07-26-22 9:52 AM E 1 OTHER COMMUNICATION ALARM CLEAR 07-26-22 9:47 AM I11200 10-03-22 10:37 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 09-29-22 6:56 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 09-27-22 8:47 PM SYSTEM PRINTER ERROR CLEAR 09-12-22 12:24 PM SYSTEM PAPER OUT CLEAR 09-12-22 12:24 PM SYSTEM PRINTER ERROR ALARM 09-12-22 12:17 PM SYSTEM PAPER OUT ALARM 09-12-22 12:17 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 09-06-22 8:55 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 09-06-22 8:46 PM SYSTEM PRINTER ERROR CLEAR 09-06-22 4:43 PM SYSTEM PAPER OUT CLEAR 09-06-22 4:43 PM SYSTEM PRINTER ERROR ALARM 09-06-22 4:43 PM SYSTEM PAPER OUT ALARM 09-06-22 4:43 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 09-06-22 3:39 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 09-06-22 1:48 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-27-22 3:24 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-23-22 12:14 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-17-22 10:43 AM SYSTEM PRINTER ERROR CLEAR 08-15-22 12:03 PM SYSTEM PAPER OUT CLEAR 08-15-22 12:03 PM SYSTEM PAPER OUT ALARM 08-15-22 12:02 PM SYSTEM PRINTER ERROR ALARM 08-15-22 12:02 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-12-22 8:23 PM h 8 OTHER FP8: BLEND3 FLOW COLLECT WARN CLEAR 08-09-22 10:00 AM h 8 OTHER FP8: BLEND3 FLOW COLLECT WARN ALARM 08-08-22 10:07 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-06-22 11:10 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-05-22 7:49 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-29-22 6:30 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-27-22 3:21 PM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-25-22 10:00 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-24-22 10:04 AM OTHER ISD VAPOR LEAK WARN CLEAR 07-22-22 2:49 PM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 07-22-22 10:00 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-21-22 11:32 PM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 07-21-22 10:05 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-18-22 12:30 PM SYSTEM PRINTER ERROR CLEAR 07-18-22 12:05 PM SYSTEM PAPER OUT CLEAR 07-18-22 12:05 PM SYSTEM PRINTER ERROR ALARM 07-18-22 12:03 PM SYSTEM PAPER OUT ALARM 07-18-22 12:03 PM OTHER ISD VAPOR LEAK WARN ALARM 07-18-22 10:06 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-13-22 10:56 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-08-22 5:11 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-01-22 5:26 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-29-22 10:05 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-22-22 5:19 AM SYSTEM PRINTER ERROR CLEAR 06-20-22 12:28 PM SYSTEM PAPER OUT CLEAR 06-20-22 12:28 PM SYSTEM PRINTER ERROR ALARM 06-20-22 12:26 PM SYSTEM PAPER OUT ALARM 06-20-22 12:26 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-19-22 12:42 AM I20600 10-03-22 10:37 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 TANK ALARM HISTORY TANK 1 PREM 91 DELIVERY NEEDED 09-27-22 8:47 PM 09-06-22 1:48 AM 08-23-22 12:14 PM PER TST NEEDED ALM 12-23-19 12:00 AM ANN TST NEEDED ALM 12-23-19 12:00 AM TANK 2 UNLEADED 87 OVERFILL ALARM 04-07-22 5:47 AM 03-30-22 6:00 AM 01-13-22 11:28 PM LOW PRODUCT ALARM 07-11-20 12:04 PM 05-18-19 7:09 AM 01-14-19 5:41 PM HIGH PRODUCT ALARM 04-07-22 5:49 AM 06-09-20 5:58 AM 03-23-20 4:17 AM DELIVERY NEEDED 09-06-22 3:39 PM 05-18-22 7:33 PM 03-24-22 3:39 PM PER TST NEEDED ALM 12-23-19 12:00 AM ANN TST NEEDED ALM 12-23-19 12:00 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 10-03-22 10:37 AM I30200 10-03-22 10:37 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 91 STP 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:24 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 2 91 FILL SUMP 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:35 AM FUEL ALARM 08-11-21 11:15 AM FUEL ALARM 3 87 STP 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:34 AM FUEL ALARM 10-03-22 9:31 AM SENSOR OUT ALARM 4 87 FILL SUMP 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:36 AM FUEL ALARM 08-11-21 10:36 AM FUEL ALARM 5 UDC 1-2 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:39 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 6 UDC 3-4 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:40 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 7 UDC 5-6 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:39 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 8 UDC 7-8 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:38 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 9 ANNULAR 87-91 10-03-22 9:46 AM SENSOR OUT ALARM 10-03-22 9:37 AM FUEL ALARM 10-03-22 9:37 AM FUEL ALARM I31600 10-03-22 10:37 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VAPOR PRESSURE 01-29-20 12:19 PM COMMUNICATION ALARM 12-22-17 10:25 AM COMMUNICATION ALARM 12-22-17 9:52 AM COMMUNICATION ALARM 2 FLOW METER 1-2 12-22-17 10:00 AM COMMUNICATION ALARM 3 FLOW METER 3-4 12-22-17 10:00 AM COMMUNICATION ALARM 08-21-17 2:18 PM COMMUNICATION ALARM 4 FLOW METER 5-6 12-03-20 8:21 AM COMMUNICATION ALARM 12-22-17 10:00 AM COMMUNICATION ALARM 08-22-17 10:48 AM COMMUNICATION ALARM 5 FLOW METER 7-8 12-22-17 10:00 AM COMMUNICATION ALARM 08-21-17 2:18 PM COMMUNICATION ALARM I40200 10-03-22 10:37 AM I40300 10-03-22 10:37 AM I34200 10-03-22 10:37 AM I34700 10-03-22 10:37 AM IV0100 10-03-22 10:37 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME : 99% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-08-08 10:07:54 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 0.58 22-07-24 10:04:38 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 0.58 22-07-22 10:04:47 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 78.57 22-07-21 10:05:27 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 69.23 22-07-21 10:05:27 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.60 22-07-20 10:05:25 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 61.84 22-07-19 10:06:46 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 30.37 22-07-18 10:06:28 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.00 22-05-15 10:06:30 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 0.57 22-05-05 10:06:14 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.60 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-08-09 10:07:29 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 22-07-25 10:07:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 22-05-06 10:06:28 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 21-07-14 10:01:12 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-13 10:01:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-12 10:06:23 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-03 10:06:30 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 18-08-07 10:08:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 18-06-12 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 18-06-11 10:06:56 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-10-03 10:08:00 READINESS ISD:PP EVR:PP ISD & EVR READY 22-10-03 09:44:49 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-10-03 09:44:49 ISD STARTUP 22-10-03 09:44:14 ISD SHUTDOWN 22-08-11 13:36:55 COLLECTION TEST HH08 GRADE TEST MANUALLY CLEARED 22-08-09 10:27:29 PUMPS MANUALLY RE-ENABLED 22-08-09 10:07:29 FLOW PERFORMANCE BLK DISABLED FP 08 BLEND3 22-08-05 10:07:02 READINESS ISD:PP EVR:PP ISD & EVR READY 22-08-04 20:32:42 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-08-04 20:32:42 ISD STARTUP