HomeMy WebLinkAbout2022 COLD START RESULTS (REJECTED - NO PERMIT TO PERFORM WORK)Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10120951 10/11/2022
Mesa Marin Chevron
11101 Highway 178 Bakersfeld 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Jason Woods
1073967
8492093 03/23/2023
Veeder Root C26937 07/26/2023
10/11/2022 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Gilbarco TLS 350 336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 794380-208/304 Dispenser 1/2
L2 794380-208/304 Dispenser 3/4
L3 794380-208/304 Dispenser 5/6
L4 794380-208/304 Dispenser 7/8
L5 794380-208/304 Dispenser 9/10
L6 794380-208/304 Dispenser 11/12
L7 794380-208/304 Unleaded STP
L8 794380-208/304 Unleaded Fill
L9 794380-208/304 Premium STP
L10 794380-208/304 Premium Fill
L11 794380-208/304 DSL STP
L12 794380-208/304 DSL Fill
L13 794380-208/304 Vent Box
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
S9 330020-464/ 794380-420 Unleaded Tank
S9 857280-100/Unleaded Tank
S10 330020-464 Unleaded product
S10 857280-100 Unleaded product
S11 330020-464 Vapor return
S11 857280-100 Vapor return
S12 330020-464 Premium Tank
S12 857280-100 Premium tank
S12 794380-420 Premium tank
S13 330020-464 Premium product
S13 857280-100 Premium product
S14 330020-464 Unleaded/ Premium Vent
S14 857280-100 Unleaded/ Premium Vent
S15 330020-464 DSL Tank
S15 857280-100 DSL Tank
S15 794380-420 DSL Tank
S16 330020-464 DSL Product
S16 857280-100 DSL Product
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V Unleaded
T2 FX1V Premium
T3 FX1DV DSL
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Performed electronic MC test due to system upgrade.
Mesa Marin Chevron Setup, Alarm History Before.
Responses Received:
200
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
OCT 11, 2022 8:28 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 6858 53.15 0.0 85.2 5174
2 SUPREME 3686 33.07 0.0 85.7 8346
3 DIESEL 3950 34.71 0.0 87.1 8125
I90500
OCT 11, 2022 8:28 AM
SOFTWARE REVISION LEVEL
VERSION 334.01
SOFTWARE# 346334-100-B
CREATED - 17.01.09.16.10
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
OCT 11, 2022 8:28 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
OCT 11, 2022 8:28 AM
SHIFT TIME 1 : 1:00 AM
I50202
OCT 11, 2022 8:28 AM
SHIFT TIME 2 : DISABLED
I50203
OCT 11, 2022 8:28 AM
SHIFT TIME 3 : DISABLED
I50204
OCT 11, 2022 8:28 AM
SHIFT TIME 4 : DISABLED
I54600
OCT 11, 2022 8:28 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
OCT 11, 2022 8:28 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
OCT 11, 2022 8:28 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
OCT 11, 2022 8:28 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
OCT 11, 2022 8:28 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
OCT 11, 2022 8:28 AM
PRINT TC VOLUMES
ENABLED
I50E00
OCT 11, 2022 8:28 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
OCT 11, 2022 8:28 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
OCT 11, 2022 8:28 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
OCT 11, 2022 8:28 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
OCT 11, 2022 8:28 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
OCT 11, 2022 8:28 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
OCT 11, 2022 8:28 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
OCT 11, 2022 8:28 AM
TANK CHART SECURITY
DISABLED
I5BD00
OCT 11, 2022 8:28 AM
CUSTOM ALARM LABELS
DISABLED
I56000
OCT 11, 2022 8:28 AM
MASS/DENSITY
DISABLED
I88101
OCT 11, 2022 8:28 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
OCT 11, 2022 8:28 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 2 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
OCT 11, 2022 8:28 AM
PORT SETTINGS:
COMM BOARD : 3 (S-SAT )
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 2 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
DTR NORMAL STATE: HIGH
I88104
OCT 11, 2022 8:28 AM
I88105
OCT 11, 2022 8:28 AM
I88106
OCT 11, 2022 8:28 AM
I52000
OCT 11, 2022 8:28 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 WEEKLY SUN 4:52 PM
2 WEEKLY SUN 4:52 PM
3 WEEKLY SUN 4:52 PM
4 WEEKLY SUN 4:52 PM
5 WEEKLY SUN 4:52 PM
6 WEEKLY SUN 4:52 PM
7 WEEKLY SUN 4:52 PM
8 VEEDER ROOT (FMS) WEEKLY MON 4:26 PM
I60100
OCT 11, 2022 8:28 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 SUPREME ON
3 DIESEL ON
4 OFF
I60200
OCT 11, 2022 8:28 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 SUPREME
3 DIESEL
4
I60300
OCT 11, 2022 8:28 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 SUPREME 2
3 DIESEL 3
4 4
I60900
OCT 11, 2022 8:28 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 SUPREME 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
OCT 11, 2022 8:28 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 95.75
2 SUPREME 95.75
3 DIESEL 95.75
4 0.00
I60A00
OCT 11, 2022 8:28 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
1 PT 12032 2 SUPREME 1 PT 12032 3 DIESEL
1 PT 12075 4 1 PT 0
I60400
OCT 11, 2022 8:28 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032
2 SUPREME 12032
3 DIESEL 12075
4 0
I60500
OCT 11, 2022 8:28 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032 0 0 0
2 SUPREME 12032 0 0 0
3 DIESEL 12075 0 0 0
4 0 0 0 0
I60600
OCT 11, 2022 8:28 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 SUPREME 12032 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DIESEL 12075 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
OCT 11, 2022 8:28 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 SUPREME NO
3 DIESEL NO
4 NO
I62F00
OCT 11, 2022 8:29 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN. PS
2 SUPREME 4.0 IN. PS
3 DIESEL 4.0 IN.
I62700
OCT 11, 2022 8:29 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 SUPREME 2.0
3 DIESEL 2.0
I64200
OCT 11, 2022 8:29 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 SUPREME LOW
3 DIESEL LOW
I62400
OCT 11, 2022 8:29 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 SUPREME 3.0
3 DIESEL 3.0
I62800
OCT 11, 2022 8:29 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032
2 SUPREME 12032
3 DIESEL 12075
4 0
I62300
OCT 11, 2022 8:29 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10829
2 SUPREME 10829
3 DIESEL 10868
4 0
I62200
OCT 11, 2022 8:29 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11430
2 SUPREME 11430
3 DIESEL 11471
4 0
I62900
OCT 11, 2022 8:29 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 SUPREME 120
3 DIESEL 121
4 0
I62100
OCT 11, 2022 8:29 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 500
2 SUPREME 500
3 DIESEL 500
4 0
I62600
OCT 11, 2022 8:29 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 SUPREME 99
3 DIESEL 99
4 99
I62500
OCT 11, 2022 8:29 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 SUPREME 99
3 DIESEL 99
4 99
I60800
OCT 11, 2022 8:29 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 SUPREME 0.00
3 DIESEL 0.00
4 0.00
I60B00
OCT 11, 2022 8:29 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
OCT 11, 2022 8:29 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 SUPREME 0.00
3 DIESEL 0.00
4 0.00
I61200
OCT 11, 2022 8:29 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 SUPREME NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
OCT 11, 2022 8:29 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 SUPREME 120
3 DIESEL 120
4 0
I62A00
OCT 11, 2022 8:29 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 SUPREME 120
3 DIESEL 120
4 0
I62C00
OCT 11, 2022 8:29 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 SUPREME STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
OCT 11, 2022 8:29 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 SUPREME GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
OCT 11, 2022 8:29 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 SUPREME OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
OCT 11, 2022 8:29 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 SUPREME OFF
3 DIESEL OFF
4 OFF
I63200
OCT 11, 2022 8:29 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 SUPREME OFF
3 DIESEL OFF
4 OFF
I61000
OCT 11, 2022 8:29 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 SUPREME 1
3 DIESEL 1
4 1
I63A00
OCT 11, 2022 8:29 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 SUPREME 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
OCT 11, 2022 8:29 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JAN 2, 2019
START TIME : 2:00 AM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:ENABLED
I61300
OCT 11, 2022 8:29 AM
CSLD PROBABLITY OF DETECTION
I61400
OCT 11, 2022 8:29 AM
CSLD CLIMATE FACTOR
I61600
OCT 11, 2022 8:29 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 SUPREME IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
OCT 11, 2022 8:29 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED ENABLED
2 SUPREME ENABLED
3 DIESEL ENABLED
4 ENABLED
I61B00
OCT 11, 2022 8:29 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
OCT 11, 2022 8:29 AM
CSLD REPORT ONLY
I62B00
OCT 11, 2022 8:29 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 SUPREME ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
OCT 11, 2022 8:29 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
OCT 11, 2022 8:29 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 SUPREME 0
3 DIESEL 0
4 0
I63500
OCT 11, 2022 8:29 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 SUPREME 1
3 DIESEL 1
4 1
I63900
OCT 11, 2022 8:29 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 SUPREME
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
OCT 11, 2022 8:29 AM
I77700
OCT 11, 2022 8:29 AM
I77800
OCT 11, 2022 8:29 AM
I78C00
OCT 11, 2022 8:29 AM
I78300
OCT 11, 2022 8:29 AM
I78F00
OCT 11, 2022 8:29 AM
I78700
OCT 11, 2022 8:29 AM
I70200
OCT 11, 2022 8:29 AM
LIQUID LABEL
DEVICE LABEL
1 DISP 1-2
2 DISP 3-4
3 DISP 5-6
4 DISP 7-8
5 DISP 9-10
6 DISP 11-12
7 UNL STP
8 UNL FILL
9 SUPREME STP
10 SUPREME FILL
11 DIESEL STP
12 DIESEL FILL
13 VENT BOX
14
15
16
I70300
OCT 11, 2022 8:29 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 DISP 1-2 DW SUMP 2-1
2 DISP 3-4 DW SUMP 2-1
3 DISP 5-6 DW SUMP 2-1
4 DISP 7-8 DW SUMP 2-1
5 DISP 9-10 DW SUMP 2-1
6 DISP 11-12 DW SUMP 2-1
7 UNL STP DW SUMP 2-1
8 UNL FILL DW SUMP 2-1
9 SUPREME STP DW SUMP 2-1
10 SUPREME FILL DW SUMP 2-1
11 DIESEL STP DW SUMP 2-1
12 DIESEL FILL DW SUMP 2-1
13 VENT BOX DW SUMP 2-1
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
OCT 11, 2022 8:29 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 DISP 1-2 DISPENSER PAN
2 DISP 3-4 DISPENSER PAN
3 DISP 5-6 DISPENSER PAN
4 DISP 7-8 DISPENSER PAN
5 DISP 9-10 DISPENSER PAN
6 DISP 11-12 DISPENSER PAN
7 UNL STP STP SUMP
8 UNL FILL OTHER SENSORS
9 SUPREME STP STP SUMP
10 SUPREME FILL OTHER SENSORS
11 DIESEL STP STP SUMP
12 DIESEL FILL OTHER SENSORS
13 VENT BOX OTHER SENSORS
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
OCT 11, 2022 8:29 AM
I74300
OCT 11, 2022 8:29 AM
I74400
OCT 11, 2022 8:29 AM
I74700
OCT 11, 2022 8:29 AM
I74800
OCT 11, 2022 8:29 AM
I74900
OCT 11, 2022 8:29 AM
I7BC00
OCT 11, 2022 8:29 AM
I80200
OCT 11, 2022 8:29 AM
I80300
OCT 11, 2022 8:29 AM
I80400
OCT 11, 2022 8:29 AM
I80700
OCT 11, 2022 8:29 AM
RELAY LABEL
DEVICE LABEL
1 UNL
2 SUPREME
3 DIESEL
4 OVERFILL ALARM
I80900
OCT 11, 2022 8:29 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNL NORMALLY OPEN
2 SUPREME NORMALLY OPEN
3 DIESEL NORMALLY OPEN
4 OVERFILL ALARM NORMALLY OPEN
I80B00
OCT 11, 2022 8:29 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNL 1
2 SUPREME 2
3 DIESEL 3
4 OVERFILL ALARM NONE
I80A00
OCT 11, 2022 8:29 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNL PUMP CONTROL OUTPUT
2 SUPREME PUMP CONTROL OUTPUT
3 DIESEL PUMP CONTROL OUTPUT
4 OVERFILL ALARM STANDARD
I80C00
OCT 11, 2022 8:29 AM
I80800
OCT 11, 2022 8:29 AM
RELAY SETUP REPORT
R 1:UNL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:SUPREME
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DIESEL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 3
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 6:FUEL ALARM
L11:FUEL ALARM
L 2:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L 2:SHORT ALARM
L 6:SHORT ALARM
L11:SHORT ALARM
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
I79000
OCT 11, 2022 8:30 AM
EDIM:1 VR:349867-001-D TD:17.02.14.08.38
I79100
OCT 11, 2022 8:30 AM
I72300
OCT 11, 2022 8:30 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 DISP 1-2 FM AIR FLOW METER
02 DISP 3-4 FM AIR FLOW METER
03 DISP 5-6 FM AIR FLOW METER
04 DISP 7-8 FM AIR FLOW METER
05 DISP 9-10 FM AIR FLOW METER
06 DISP 11-12 FM AIR FLOW METER
07 DISP 5-6 PS VAPOR PRESSURE
08 ATM ATM P SENSOR
09 UNL TANK VAC SENSOR
10 UNL PRODUCT VAC SENSOR
11 VAPOR RETURN VAC SENSOR
12 SUPREME TANK VAC SENSOR
13 SUPREME PRODUCT VAC SENSOR
14 UNL-SUP VENT VAC SENSOR
15 DIESEL TANK VAC SENSOR
16 DIESEL PRODUCT VAC SENSOR
17 DIESEL VENT VAC SENSOR
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
OCT 11, 2022 8:30 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
OCT 11, 2022 8:30 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
OCT 11, 2022 8:30 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
VAPOR PROCESSOR TYPE
NONE
IV4700
OCT 11, 2022 8:30 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
OCT 11, 2022 8:30 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ACCEPT HIGH ORVR: NO
IV4A00
OCT 11, 2022 8:30 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
09 09 09 05 02 BLEND3
10 16 10 05 02 BLEND3
11 17 11 06 02 BLEND3
12 18 12 06 02 BLEND3
IV4B00
OCT 11, 2022 8:30 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 09/01 01/01 xx/xx
02 01 02/02 09/02 01/02 xx/xx
03 02 02/03 09/03 01/03 xx/xx
04 02 02/04 09/04 01/04 xx/xx
05 03 02/05 09/05 01/05 xx/xx
06 03 02/06 09/06 01/06 xx/xx
07 04 09/07 01/07 02/07 xx/xx
08 04 02/08 09/08 01/08 xx/xx
09 05 02/09 01/09 09/09 xx/xx
16 05 02/10 09/10 01/10 xx/xx
17 06 02/11 09/11 01/11 xx/xx
18 06 02/12 09/12 01/12 xx/xx
IV4900
OCT 11, 2022 8:30 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
OCT 11, 2022 8:30 AM
ISD VERSION: 01.05
Alarm History Before.
Responses Received:
I10200
OCT 11, 2022 8:31 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164673 164096
2 7SMARTSENSOR BD 507191 506357
3 8SMARTSENSOR BD 39377 39385
4 8SMARTSENSOR BD 39440 39429
5 INTERSTITIAL BD 201672 201814
6 INTERSTITIAL BD 200861 201274
7 UNUSED 4953456 4910349
8 UNUSED 4944083 4914633
9 RELAY BOARD 14972 15007
10 STP SENSE BOARD 33080 33139
11 UNUSED 4950675 4913405
12 UNUSED 4942529 4912951
13 UNUSED 4942944 4908256
14 UNUSED 4943339 4916585
15 UNUSED 4944711 4915222
16 UNUSED 4939848 4912994
COMM 1 ELEC DISP INT. 101264 101312
COMM 2 RS232 SERIAL BD 14930 14942
COMM 3 SERIAL SAT BD 481237 481073
COMM 4 UNUSED 4946373 4917169
COMM 5 UNUSED 4939474 4906526
COMM 6 UNUSED 4941947 4911458
I90200
OCT 11, 2022 8:31 AM
SOFTWARE REVISION LEVEL
VERSION 334.01
SOFTWARE# 346334-100-B
CREATED - 17.01.09.16.10
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
OCT 11, 2022 8:31 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-10-22 4:51PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-10-22 4:51PM
L10 OTHER SUPREME FILL LOW LIQUID ALARM CLEAR 10-10-22 10:39AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-10-22 9:30AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-10-22 9:30AM
OTHER ISD VAPOR LEAK FAIL CLEAR 10-10-22 9:25AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM ALARM 10-10-22 9:23AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM CLEAR 10-10-22 9:22AM
L10 OTHER SUPREME FILL LOW LIQUID ALARM ALARM 10-10-22 9:10AM
L10 OTHER SUPREME FILL FUEL ALARM CLEAR 10-10-22 9:10AM
L 6 DISP PAN DISP 11-12 LOW LIQUID ALARM CLEAR 10-10-22 8:34AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-09-22 5:07PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-09-22 5:07PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-09-22 10:29AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-09-22 10:29AM
OTHER ISD VAPOR LEAK FAIL ALARM 10-09-22 10:03AM
OTHER ISD VAPOR LEAK FAIL CLEAR 10-09-22 10:03AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-08-22 4:51PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-08-22 4:51PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-08-22 10:28AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-08-22 10:28AM
OTHER ISD VAPOR LEAK FAIL ALARM 10-08-22 10:03AM
OTHER ISD VAPOR LEAK FAIL CLEAR 10-08-22 10:03AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-07-22 4:53PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-07-22 4:53PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-07-22 10:28AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-07-22 10:28AM
OTHER ISD VAPOR LEAK FAIL ALARM 10-07-22 10:03AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-06-22 5:19PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-06-22 5:19PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-05-22 4:51PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-05-22 4:51PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-04-22 5:15PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-04-22 5:15PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-03-22 5:17PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-03-22 5:17PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-02-22 4:51PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-02-22 4:51PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-01-22 5:23PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-01-22 5:23PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 9-30-22 5:17PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 9-30-22 5:17PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 9-30-22 10:28AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 9-30-22 10:28AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 9-29-22 5:03PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 9-29-22 5:03PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 9-28-22 4:31PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 9-28-22 4:31PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 9-27-22 5:01PM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 9-27-22 5:01PM
I11200
OCT 11, 2022 8:31 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 10-11-22 8:21AM
SYSTEM PAPER OUT CLEAR 10-11-22 8:21AM
SYSTEM PRINTER ERROR ALARM 10-11-22 8:18AM
SYSTEM PAPER OUT ALARM 10-11-22 8:18AM
OTHER ISD VAPOR LEAK WARN CLEAR 10-07-22 10:03AM
OTHER ISD VAPOR LEAK WARN ALARM 9-30-22 10:03AM
OTHER ISD VAPOR LEAK WARN CLEAR 9-24-22 7:27PM
SYSTEM PRINTER ERROR CLEAR 9-24-22 7:22PM
SYSTEM PAPER OUT CLEAR 9-24-22 7:22PM
SYSTEM PAPER OUT ALARM 9-24-22 7:22PM
SYSTEM PRINTER ERROR ALARM 9-24-22 7:22PM
SYSTEM PAPER OUT CLEAR 9-24-22 7:22PM
SYSTEM PAPER OUT ALARM 9-24-22 7:21PM
OTHER ISD VAPOR LEAK WARN ALARM 9-20-22 10:03AM
OTHER ISD VAPOR LEAK WARN CLEAR 9-14-22 1:23PM
OTHER ISD VAPOR LEAK WARN ALARM 9-08-22 10:06AM
SYSTEM PRINTER ERROR CLEAR 8-31-22 11:23AM
SYSTEM PAPER OUT CLEAR 8-31-22 11:23AM
SYSTEM PRINTER ERROR ALARM 8-31-22 11:23AM
SYSTEM PAPER OUT ALARM 8-31-22 11:21AM
SYSTEM PRINTER ERROR CLEAR 7-04-22 11:39PM
SYSTEM PRINTER ERROR ALARM 7-04-22 11:39PM
SYSTEM PAPER OUT CLEAR 7-04-22 11:39PM
SYSTEM PAPER OUT ALARM 7-04-22 11:39PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 7:29PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 7:29PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 6:41PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 6:41PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:30PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:30PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:29PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:29PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:27PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:27PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:26PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:26PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:25PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:25PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:24PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:24PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:23PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:23PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:23PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:23PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:21PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:21PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:20PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:20PM
s14 OTHER UNL-SUP VENT VACUUM WARNING CLEAR 6-13-22 4:19PM
s14 OTHER UNL-SUP VENT VACUUM WARNING ALARM 6-13-22 4:19PM
I20600
OCT 11, 2022 8:31 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
TANK ALARM HISTORY
TANK 1 UNLEADED
SETUP DATA WARNING JUL 14, 2021 12:57 PM
MAY 25, 2021 1:25 PM
MAY 25, 2021 1:18 PM
HIGH WATER ALARM JUL 14, 2021 1:06 PM
MAY 25, 2021 12:49 PM
MAY 25, 2021 12:33 PM
OVERFILL ALARM MAY 25, 2021 12:22 PM
HIGH PRODUCT ALARM MAY 25, 2021 12:28 PM
MAY 25, 2021 12:22 PM
MAY 20, 2019 2:49 PM
INVALID FUEL LEVEL JUL 14, 2021 1:03 PM
MAY 25, 2021 12:20 PM
PROBE OUT JUL 14, 2021 12:57 PM
MAY 25, 2021 1:25 PM
MAY 25, 2021 1:18 PM
HIGH WATER WARNING JUL 14, 2021 1:06 PM
MAY 25, 2021 12:49 PM
MAY 25, 2021 12:33 PM
MAX PRODUCT ALARM MAY 20, 2019 2:49 PM
LOW TEMP WARNING MAY 25, 2021 1:23 PM
MAY 25, 2021 1:16 PM
MAY 25, 2021 12:30 PM
TANK 2 SUPREME
SETUP DATA WARNING MAY 25, 2021 12:35 PM
MAY 25, 2021 12:17 PM
HIGH WATER ALARM MAY 25, 2021 12:21 PM
OVERFILL ALARM MAY 25, 2021 12:30 PM
LOW PRODUCT ALARM MAY 25, 2021 12:16 PM
HIGH PRODUCT ALARM MAY 25, 2021 12:35 PM
MAY 25, 2021 12:31 PM
MAY 25, 2021 12:30 PM
INVALID FUEL LEVEL MAY 25, 2021 12:16 PM
PROBE OUT MAY 25, 2021 12:35 PM
MAY 25, 2021 12:35 PM
MAY 25, 2021 12:17 PM
HIGH WATER WARNING MAY 25, 2021 12:21 PM
MAX PRODUCT ALARM MAY 20, 2019 2:49 PM
LOW TEMP WARNING MAY 25, 2021 12:35 PM
TANK 3 DIESEL
OVERFILL ALARM MAY 25, 2021 12:37 PM
LOW PRODUCT ALARM MAY 25, 2021 12:14 PM
SUDDEN LOSS ALARM MAY 20, 2019 3:20 PM
HIGH PRODUCT ALARM MAY 25, 2021 12:37 PM
MAY 25, 2021 12:37 PM
MAY 20, 2019 2:49 PM
PROBE OUT MAY 25, 2021 12:39 PM
MAY 25, 2021 12:14 PM
MAX PRODUCT ALARM MAY 20, 2019 2:49 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
OCT 11, 2022 8:31 AM
I30200
OCT 11, 2022 8:31 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 10:56 AM FUEL ALARM
JUN 13, 2022 10:56 AM LOW LIQUID ALARM
2 DISP 3-4
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 10:55 AM FUEL ALARM
JUN 13, 2022 10:54 AM LOW LIQUID ALARM
3 DISP 5-6
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 10:49 AM FUEL ALARM
JUN 13, 2022 10:49 AM LOW LIQUID ALARM
4 DISP 7-8
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 11:14 AM LOW LIQUID ALARM
JUN 13, 2022 10:47 AM FUEL ALARM
5 DISP 9-10
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 10:44 AM FUEL ALARM
JUN 13, 2022 10:43 AM LOW LIQUID ALARM
6 DISP 11-12
SEP 14, 2022 11:16 PM LOW LIQUID ALARM
SEP 14, 2022 5:24 AM LOW LIQUID ALARM
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
7 UNL STP
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 10:26 AM LOW LIQUID ALARM
JUN 13, 2022 10:26 AM FUEL ALARM
8 UNL FILL
JUL 28, 2022 7:27 AM LOW LIQUID ALARM
JUL 27, 2022 1:02 AM LOW LIQUID ALARM
JUL 26, 2022 9:31 PM LOW LIQUID ALARM
9 SUPREME STP
JUN 13, 2022 10:58 PM SENSOR OUT ALARM
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 10:25 AM LOW LIQUID ALARM
10 SUPREME FILL
OCT 10, 2022 9:23 AM LOW LIQUID ALARM
OCT 10, 2022 9:10 AM LOW LIQUID ALARM
JUL 28, 2022 12:19 PM FUEL ALARM
11 DIESEL STP
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 10:23 AM LOW LIQUID ALARM
JUN 13, 2022 10:23 AM LOW LIQUID ALARM
12 DIESEL FILL
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 8:30 PM SENSOR OUT ALARM
JUN 13, 2022 10:28 AM FUEL ALARM
13 VENT BOX
JUN 13, 2022 10:56 PM SENSOR OUT ALARM
JUN 13, 2022 10:57 AM FUEL ALARM
JUN 13, 2022 10:57 AM LOW LIQUID ALARM
I31600
OCT 11, 2022 8:31 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2 FM
2 DISP 3-4 FM
3 DISP 5-6 FM
4 DISP 7-8 FM
5 DISP 9-10 FM
6 DISP 11-12 FM
7 DISP 5-6 PS
8 ATM
9 UNL TANK
JUN 13, 2022 2:02 PM NO VACUUM ALARM
JUN 13, 2022 1:15 PM HIGH LIQUID ALARM
MAY 25, 2021 10:33 AM VACUUM WARNING
10 UNL PRODUCT
JUN 13, 2022 1:06 PM HIGH LIQUID ALARM
JUN 13, 2022 1:06 PM NO VACUUM ALARM
JUN 13, 2022 12:37 PM NO VACUUM ALARM
11 VAPOR RETURN
JUN 13, 2022 1:00 PM HIGH LIQUID ALARM
JUN 13, 2022 12:59 PM NO VACUUM ALARM
JUN 13, 2022 12:37 PM NO VACUUM ALARM
12 SUPREME TANK
JUN 13, 2022 3:33 PM HIGH LIQUID ALARM
JUN 13, 2022 1:21 PM NO VACUUM ALARM
MAY 25, 2021 9:52 AM HIGH LIQUID ALARM
13 SUPREME PRODUCT
JUN 13, 2022 8:18 PM HIGH LIQUID ALARM
JUN 13, 2022 12:47 PM HIGH LIQUID ALARM
JUN 13, 2022 12:47 PM NO VACUUM ALARM
14 UNL-SUP VENT
JUN 13, 2022 8:05 PM NO VACUUM ALARM
JUN 13, 2022 7:29 PM NO VACUUM ALARM
JUN 13, 2022 7:29 PM VACUUM WARNING
15 DIESEL TANK
JUN 13, 2022 2:33 PM NO VACUUM ALARM
JUN 13, 2022 1:43 PM HIGH LIQUID ALARM
MAY 25, 2021 10:24 AM HIGH LIQUID ALARM
16 DIESEL PRODUCT
JUN 13, 2022 12:48 PM HIGH LIQUID ALARM
JUN 13, 2022 12:48 PM NO VACUUM ALARM
MAY 25, 2021 12:10 PM HIGH LIQUID ALARM
17 DIESEL VENT
JUN 13, 2022 1:33 PM HIGH LIQUID ALARM
JUN 13, 2022 12:48 PM HIGH LIQUID ALARM
JUN 13, 2022 12:48 PM NO VACUUM ALARM
I40200
OCT 11, 2022 8:31 AM
I40300
OCT 11, 2022 8:31 AM
I34200
OCT 11, 2022 8:31 AM
I34700
OCT 11, 2022 8:31 AM
IV0100
OCT 11, 2022 8:31 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :NOTEST
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-10-06 10:03:52 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 38.55
22-10-05 10:03:48 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 37.45
22-10-04 10:03:56 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 33.33
22-10-03 10:03:55 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 32.76
22-10-02 10:03:59 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 31.98
22-10-01 10:03:39 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 31.95
22-09-30 10:03:11 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 30.32
22-09-24 10:04:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 24.92
22-09-23 10:03:58 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 24.91
22-09-22 10:03:47 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 25.16
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-10-09 10:03:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 43.37
22-10-08 10:03:42 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.44
22-10-07 10:03:44 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.38
22-06-11 10:07:00 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3
22-03-05 10:07:15 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3
21-09-07 10:07:55 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
21-08-18 10:08:51 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
21-07-26 10:05:35 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
21-04-12 10:05:16 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3
20-03-11 10:05:46 FLOW PERFORMANCE HOSE BLOCKAGE FP11 BLEND3
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-10-10 10:01:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING
22-10-10 09:25:43 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
22-10-09 10:17:40 PUMPS MANUALLY RE-ENABLED
22-10-09 10:03:50 READINESS ISD:PP EVR:NF CHECK EVR SYSTEM
22-10-09 10:03:50 VAPOR CONTAINMENT LEAKAGE DISABLED DISPENSERS
22-10-08 10:20:28 PUMPS MANUALLY RE-ENABLED
22-10-08 10:03:42 READINESS ISD:PP EVR:NF CHECK EVR SYSTEM
22-10-08 10:03:42 VAPOR CONTAINMENT LEAKAGE DISABLED DISPENSERS
22-10-07 10:37:19 PUMPS MANUALLY RE-ENABLED
22-10-07 10:03:44 READINESS ISD:PP EVR:NF CHECK EVR SYSTEM
ISD Setup
<
IV4200
OCT 11, 2022 8:33 AM
Sensor / Airflow Meter / Hose Table / Grade Table Relationship
SS AA F1 FL M1H1L1 M2H2L2 M3H3L3 M4H4L4 F2 L2 M1H1L1 M2H2L2 M3H3L3 M4H4L4
01 01 02 01 030102 100102 020102 000000 03 02 030202 100202 020202 000000
02 02 04 03 030302 100302 020302 040000 05 04 030402 100402 020402 040000
03 03 06 05 030502 100502 020502 000000 07 06 030602 100602 020602 000000
04 04 09 08 030802 100802 020802 000000 08 07 100702 020702 030702 000000
05 05 10 09 030902 020902 100902 000000 17 10 031002 101002 021002 000000
06 06 18 11 031102 101102 021102 040000 19 12 031202 101202 021202 040000
>
Mesa Marin Chevron Setup, alarm History After.
Setup
Responses Received:
200
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
OCT 11, 2022 10:09 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 6847 53.08 0.0 85.2 5185
2 SUPREME 3678 33.02 0.0 85.8 8354
3 DIESEL 3944 34.67 0.0 87.1 8131
I90500
OCT 11, 2022 10:09 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
OCT 11, 2022 10:09 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
OCT 11, 2022 10:09 AM
SHIFT TIME 1 : 1:00 AM
I50202
OCT 11, 2022 10:09 AM
SHIFT TIME 2 : DISABLED
I50203
OCT 11, 2022 10:09 AM
SHIFT TIME 3 : DISABLED
I50204
OCT 11, 2022 10:09 AM
SHIFT TIME 4 : DISABLED
I54600
OCT 11, 2022 10:09 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
OCT 11, 2022 10:09 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
OCT 11, 2022 10:09 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
OCT 11, 2022 10:09 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
OCT 11, 2022 10:09 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
OCT 11, 2022 10:09 AM
PRINT TC VOLUMES
ENABLED
I50E00
OCT 11, 2022 10:09 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
OCT 11, 2022 10:09 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
OCT 11, 2022 10:09 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
OCT 11, 2022 10:09 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
OCT 11, 2022 10:09 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
OCT 11, 2022 10:09 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
OCT 11, 2022 10:09 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
OCT 11, 2022 10:09 AM
TANK CHART SECURITY
DISABLED
I5BD00
OCT 11, 2022 10:09 AM
CUSTOM ALARM LABELS
DISABLED
I56000
OCT 11, 2022 10:09 AM
MASS/DENSITY
DISABLED
I88101
OCT 11, 2022 10:09 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
OCT 11, 2022 10:09 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 2 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
OCT 11, 2022 10:09 AM
PORT SETTINGS:
COMM BOARD : 3 (S-SAT )
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 2 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
DTR NORMAL STATE: HIGH
I88104
OCT 11, 2022 10:09 AM
I88105
OCT 11, 2022 10:09 AM
I88106
OCT 11, 2022 10:10 AM
I52000
OCT 11, 2022 10:10 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 WEEKLY SUN 4:52 PM
2 WEEKLY SUN 4:52 PM
3 WEEKLY SUN 4:52 PM
4 WEEKLY SUN 4:52 PM
5 WEEKLY SUN 4:52 PM
6 WEEKLY SUN 4:52 PM
7 WEEKLY SUN 4:52 PM
8 VEEDER ROOT (FMS) WEEKLY MON 4:26 PM
I60100
OCT 11, 2022 10:10 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 SUPREME ON
3 DIESEL ON
4 OFF
I60200
OCT 11, 2022 10:10 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 SUPREME
3 DIESEL
4
I60300
OCT 11, 2022 10:10 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 SUPREME 2
3 DIESEL 3
4 4
I60900
OCT 11, 2022 10:10 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 SUPREME 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
OCT 11, 2022 10:10 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 95.75
2 SUPREME 95.75
3 DIESEL 95.75
4 0.00
I60A00
OCT 11, 2022 10:10 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
1 PT 12032 2 SUPREME 1 PT 12032 3 DIESEL
1 PT 12075 4 1 PT 0
I60400
OCT 11, 2022 10:10 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032
2 SUPREME 12032
3 DIESEL 12075
4 0
I60500
OCT 11, 2022 10:10 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032 0 0 0
2 SUPREME 12032 0 0 0
3 DIESEL 12075 0 0 0
4 0 0 0 0
I60600
OCT 11, 2022 10:10 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 SUPREME 12032 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DIESEL 12075 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
OCT 11, 2022 10:10 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 SUPREME NO
3 DIESEL NO
4 NO
I62F00
OCT 11, 2022 10:10 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN. PS
2 SUPREME 4.0 IN. PS
3 DIESEL 4.0 IN.
I62700
OCT 11, 2022 10:10 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 SUPREME 2.0
3 DIESEL 2.0
I64200
OCT 11, 2022 10:10 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 SUPREME LOW
3 DIESEL LOW
I62400
OCT 11, 2022 10:10 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 SUPREME 3.0
3 DIESEL 3.0
I62800
OCT 11, 2022 10:10 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032
2 SUPREME 12032
3 DIESEL 12075
4 0
I62300
OCT 11, 2022 10:10 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10829
2 SUPREME 10829
3 DIESEL 10868
4 0
I62200
OCT 11, 2022 10:10 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11430
2 SUPREME 11430
3 DIESEL 11471
4 0
I62900
OCT 11, 2022 10:10 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 SUPREME 120
3 DIESEL 121
4 0
I62100
OCT 11, 2022 10:10 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 500
2 SUPREME 500
3 DIESEL 500
4 0
I62600
OCT 11, 2022 10:10 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 SUPREME 99
3 DIESEL 99
4 99
I62500
OCT 11, 2022 10:10 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 SUPREME 99
3 DIESEL 99
4 99
I60800
OCT 11, 2022 10:10 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 SUPREME 0.00
3 DIESEL 0.00
4 0.00
I60B00
OCT 11, 2022 10:10 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
OCT 11, 2022 10:10 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 SUPREME 0.00
3 DIESEL 0.00
4 0.00
I61200
OCT 11, 2022 10:10 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 SUPREME NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
OCT 11, 2022 10:10 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 SUPREME 120
3 DIESEL 120
4 0
I62A00
OCT 11, 2022 10:10 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 SUPREME 120
3 DIESEL 120
4 0
I62C00
OCT 11, 2022 10:10 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 SUPREME STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
OCT 11, 2022 10:10 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 SUPREME GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
OCT 11, 2022 10:10 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 SUPREME OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
OCT 11, 2022 10:10 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 SUPREME OFF
3 DIESEL OFF
4 OFF
I63200
OCT 11, 2022 10:10 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 SUPREME OFF
3 DIESEL OFF
4 OFF
I61000
OCT 11, 2022 10:10 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 SUPREME 1
3 DIESEL 1
4 1
I63A00
OCT 11, 2022 10:10 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 SUPREME 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
OCT 11, 2022 10:10 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JAN 2, 2019
START TIME : 2:00 AM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:ENABLED
I61300
OCT 11, 2022 10:10 AM
CSLD PROBABLITY OF DETECTION
I61400
OCT 11, 2022 10:10 AM
CSLD CLIMATE FACTOR
I61600
OCT 11, 2022 10:10 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 SUPREME IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
OCT 11, 2022 10:10 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED ENABLED
2 SUPREME ENABLED
3 DIESEL ENABLED
4 ENABLED
I61B00
OCT 11, 2022 10:10 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
OCT 11, 2022 10:10 AM
CSLD REPORT ONLY
I62B00
OCT 11, 2022 10:10 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 SUPREME ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
OCT 11, 2022 10:10 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
OCT 11, 2022 10:10 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 SUPREME 0
3 DIESEL 0
4 0
I63500
OCT 11, 2022 10:10 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 SUPREME 1
3 DIESEL 1
4 1
I63900
OCT 11, 2022 10:10 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 SUPREME
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
OCT 11, 2022 10:10 AM
I77700
OCT 11, 2022 10:10 AM
I77800
OCT 11, 2022 10:10 AM
I78C00
OCT 11, 2022 10:10 AM
I78300
OCT 11, 2022 10:10 AM
I78F00
OCT 11, 2022 10:10 AM
I78700
OCT 11, 2022 10:10 AM
I70200
OCT 11, 2022 10:10 AM
LIQUID LABEL
DEVICE LABEL
1 DISP 1-2
2 DISP 3-4
3 DISP 5-6
4 DISP 7-8
5 DISP 9-10
6 DISP 11-12
7 UNL STP
8 UNL FILL
9 SUPREME STP
10 SUPREME FILL
11 DIESEL STP
12 DIESEL FILL
13 VENT BOX
14
15
16
I70300
OCT 11, 2022 10:10 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 DISP 1-2 DW SUMP 2-1
2 DISP 3-4 DW SUMP 2-1
3 DISP 5-6 DW SUMP 2-1
4 DISP 7-8 DW SUMP 2-1
5 DISP 9-10 DW SUMP 2-1
6 DISP 11-12 DW SUMP 2-1
7 UNL STP DW SUMP 2-1
8 UNL FILL DW SUMP 2-1
9 SUPREME STP DW SUMP 2-1
10 SUPREME FILL DW SUMP 2-1
11 DIESEL STP DW SUMP 2-1
12 DIESEL FILL DW SUMP 2-1
13 VENT BOX DW SUMP 2-1
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
OCT 11, 2022 10:10 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 DISP 1-2 DISPENSER PAN
2 DISP 3-4 DISPENSER PAN
3 DISP 5-6 DISPENSER PAN
4 DISP 7-8 DISPENSER PAN
5 DISP 9-10 DISPENSER PAN
6 DISP 11-12 DISPENSER PAN
7 UNL STP STP SUMP
8 UNL FILL OTHER SENSORS
9 SUPREME STP STP SUMP
10 SUPREME FILL OTHER SENSORS
11 DIESEL STP STP SUMP
12 DIESEL FILL OTHER SENSORS
13 VENT BOX OTHER SENSORS
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
OCT 11, 2022 10:10 AM
I74300
OCT 11, 2022 10:10 AM
I74400
OCT 11, 2022 10:10 AM
I74700
OCT 11, 2022 10:10 AM
I74800
OCT 11, 2022 10:10 AM
I74900
OCT 11, 2022 10:10 AM
I7BC00
OCT 11, 2022 10:10 AM
I80200
OCT 11, 2022 10:10 AM
I80300
OCT 11, 2022 10:10 AM
I80400
OCT 11, 2022 10:10 AM
I80700
OCT 11, 2022 10:10 AM
RELAY LABEL
DEVICE LABEL
1 UNL
2 SUPREME
3 DIESEL
4 OVERFILL ALARM
I80900
OCT 11, 2022 10:10 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNL NORMALLY OPEN
2 SUPREME NORMALLY OPEN
3 DIESEL NORMALLY OPEN
4 OVERFILL ALARM NORMALLY OPEN
I80B00
OCT 11, 2022 10:10 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNL 1
2 SUPREME 2
3 DIESEL 3
4 OVERFILL ALARM NONE
I80A00
OCT 11, 2022 10:10 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNL PUMP CONTROL OUTPUT
2 SUPREME PUMP CONTROL OUTPUT
3 DIESEL PUMP CONTROL OUTPUT
4 OVERFILL ALARM STANDARD
I80C00
OCT 11, 2022 10:10 AM
I80800
OCT 11, 2022 10:10 AM
RELAY SETUP REPORT
R 1:UNL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:SUPREME
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DIESEL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 3
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 6:FUEL ALARM
L11:FUEL ALARM
L 2:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L 2:SHORT ALARM
L 6:SHORT ALARM
L11:SHORT ALARM
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
I79000
OCT 11, 2022 10:11 AM
EDIM:1 VR:349867-001-D TD:17.02.14.08.38
I79100
OCT 11, 2022 10:11 AM
I72300
OCT 11, 2022 10:11 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 DISP 1-2 FM AIR FLOW METER
02 DISP 3-4 FM AIR FLOW METER
03 DISP 5-6 FM AIR FLOW METER
04 DISP 7-8 FM AIR FLOW METER
05 DISP 9-10 FM AIR FLOW METER
06 DISP 11-12 FM AIR FLOW METER
07 DISP 5-6 PS VAPOR PRESSURE
08 ATM ATM P SENSOR
09 UNL TANK VAC SENSOR
10 UNL PRODUCT VAC SENSOR
11 VAPOR RETURN VAC SENSOR
12 SUPREME TANK VAC SENSOR
13 SUPREME PRODUCT VAC SENSOR
14 UNL-SUP VENT VAC SENSOR
15 DIESEL TANK VAC SENSOR
16 DIESEL PRODUCT VAC SENSOR
17 DIESEL VENT VAC SENSOR
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
OCT 11, 2022 10:11 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
OCT 11, 2022 10:11 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
OCT 11, 2022 10:11 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
VAPOR PROCESSOR TYPE
NONE
IV4700
OCT 11, 2022 10:11 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
OCT 11, 2022 10:11 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ACCEPT HIGH ORVR: NO
IV4A00
OCT 11, 2022 10:11 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
09 09 09 05 02 BLEND3
10 16 10 05 02 BLEND3
11 17 11 06 02 BLEND3
12 18 12 06 02 BLEND3
Alarm History after.
Responses Received:
I10200
OCT 11, 2022 10:13 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164210 164161
2 7SMARTSENSOR BD 505619 505458
3 8SMARTSENSOR BD 39372 39359
4 8SMARTSENSOR BD 39394 39447
5 INTERSTITIAL BD 201554 201616
6 INTERSTITIAL BD 201229 201148
7 UNUSED 4936496 4934901
8 UNUSED 4934375 4926700
9 RELAY BOARD 14978 14978
10 STP SENSE BOARD 33087 33131
11 UNUSED 4945617 4936592
12 UNUSED 4942939 4933657
13 UNUSED 4936532 4931822
14 UNUSED 4936382 4926902
15 UNUSED 4932718 4927506
16 UNUSED 4941032 4934045
COMM 1 ELEC DISP INT. 101260 101290
COMM 2 RS232 SERIAL BD 14914 14913
COMM 3 SERIAL SAT BD 480641 481171
COMM 4 UNUSED 4942232 4938793
COMM 5 UNUSED 4941139 4934175
COMM 6 UNUSED 4935461 4936657
I90200
OCT 11, 2022 10:13 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
OCT 11, 2022 10:13 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 8 OTHER UNL FILL LOW LIQUID ALARM CLEAR 10-11-22 10:06AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-11-22 10:01AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-11-22 10:01AM
L 8 OTHER UNL FILL LOW LIQUID ALARM ALARM 10-11-22 10:00AM
L 8 OTHER UNL FILL LOW LIQUID ALARM CLEAR 10-11-22 10:00AM
L 8 OTHER UNL FILL LOW LIQUID ALARM ALARM 10-11-22 9:57AM
L 4 DISP PAN DISP 7-8 LOW LIQUID ALARM CLEAR 10-11-22 9:45AM
L 4 DISP PAN DISP 7-8 LOW LIQUID ALARM ALARM 10-11-22 9:45AM
L12 OTHER DIESEL FILL SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L10 OTHER SUPREME FILL SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L13 OTHER VENT BOX SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L11 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 9 STP SUMP SUPREME STP SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 8 OTHER UNL FILL SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 2 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 4 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 7 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 1 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 6 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 3 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 5 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 10-11-22 9:43AM
L 3 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L 2 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L 1 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L 6 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L 5 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L 4 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L 8 OTHER UNL FILL SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L 7 STP SUMP UNL STP SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L12 OTHER DIESEL FILL SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L11 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L10 OTHER SUPREME FILL SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L 9 STP SUMP SUPREME STP SENSOR OUT ALARM ALARM 10-11-22 9:42AM
L13 OTHER VENT BOX SENSOR OUT ALARM ALARM 10-11-22 9:42AM
s10 OTHER UNL PRODUCT HIGH LIQUID ALARM CLEAR 10-11-22 9:36AM
s11 OTHER VAPOR RETURN HIGH LIQUID ALARM CLEAR 10-11-22 9:36AM
s11 OTHER VAPOR RETURN NO VACUUM ALARM CLEAR 10-11-22 9:36AM
s10 OTHER UNL PRODUCT NO VACUUM ALARM CLEAR 10-11-22 9:36AM
s11 OTHER VAPOR RETURN HIGH LIQUID ALARM ALARM 10-11-22 9:36AM
s11 OTHER VAPOR RETURN NO VACUUM ALARM ALARM 10-11-22 9:36AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE ALARM 10-11-22 9:36AM
D 8 OTHER VEEDER ROOT (FMS) AUTODIAL FAILURE CLEAR 10-11-22 9:36AM
s10 OTHER UNL PRODUCT HIGH LIQUID ALARM ALARM 10-11-22 9:36AM
s10 OTHER UNL PRODUCT NO VACUUM ALARM ALARM 10-11-22 9:36AM
L 7 STP SUMP UNL STP FUEL ALARM CLEAR 10-11-22 9:35AM
L 7 STP SUMP UNL STP FUEL ALARM ALARM 10-11-22 9:35AM
L 7 STP SUMP UNL STP LOW LIQUID ALARM CLEAR 10-11-22 9:35AM
L 7 STP SUMP UNL STP LOW LIQUID ALARM ALARM 10-11-22 9:35AM
s14 OTHER UNL-SUP VENT HIGH LIQUID ALARM CLEAR 10-11-22 9:34AM
s13 OTHER SUPREME PRODUCT HIGH LIQUID ALARM CLEAR 10-11-22 9:34AM
I11200
OCT 11, 2022 10:13 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
I20600
OCT 11, 2022 10:13 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
TANK ALARM HISTORY
TANK 1 UNLEADED
TANK 2 SUPREME
TANK 3 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
OCT 11, 2022 10:13 AM
I30200
OCT 11, 2022 10:13 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:17 AM FUEL ALARM
OCT 11, 2022 9:17 AM LOW LIQUID ALARM
2 DISP 3-4
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:17 AM FUEL ALARM
OCT 11, 2022 9:16 AM LOW LIQUID ALARM
3 DISP 5-6
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:18 AM FUEL ALARM
OCT 11, 2022 9:18 AM LOW LIQUID ALARM
4 DISP 7-8
OCT 11, 2022 9:45 AM LOW LIQUID ALARM
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:18 AM FUEL ALARM
5 DISP 9-10
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:20 AM FUEL ALARM
OCT 11, 2022 9:20 AM LOW LIQUID ALARM
6 DISP 11-12
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:19 AM FUEL ALARM
OCT 11, 2022 9:19 AM LOW LIQUID ALARM
7 UNL STP
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:35 AM FUEL ALARM
OCT 11, 2022 9:35 AM LOW LIQUID ALARM
8 UNL FILL
OCT 11, 2022 10:00 AM LOW LIQUID ALARM
OCT 11, 2022 9:57 AM LOW LIQUID ALARM
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
9 SUPREME STP
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:34 AM FUEL ALARM
OCT 11, 2022 9:33 AM LOW LIQUID ALARM
10 SUPREME FILL
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:26 AM LOW LIQUID ALARM
OCT 11, 2022 9:26 AM FUEL ALARM
11 DIESEL STP
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:31 AM FUEL ALARM
OCT 11, 2022 9:31 AM LOW LIQUID ALARM
12 DIESEL FILL
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:25 AM LOW LIQUID ALARM
OCT 11, 2022 9:25 AM FUEL ALARM
13 VENT BOX
OCT 11, 2022 9:42 AM SENSOR OUT ALARM
OCT 11, 2022 9:24 AM FUEL ALARM
OCT 11, 2022 9:24 AM LOW LIQUID ALARM
I31600
OCT 11, 2022 10:13 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2 FM
2 DISP 3-4 FM
3 DISP 5-6 FM
4 DISP 7-8 FM
5 DISP 9-10 FM
6 DISP 11-12 FM
7 DISP 5-6 PS
8 ATM
9 UNL TANK
10 UNL PRODUCT
OCT 11, 2022 9:36 AM HIGH LIQUID ALARM
OCT 11, 2022 9:36 AM NO VACUUM ALARM
11 VAPOR RETURN
OCT 11, 2022 9:36 AM HIGH LIQUID ALARM
OCT 11, 2022 9:36 AM NO VACUUM ALARM
12 SUPREME TANK
13 SUPREME PRODUCT
OCT 11, 2022 9:34 AM HIGH LIQUID ALARM
OCT 11, 2022 9:34 AM NO VACUUM ALARM
14 UNL-SUP VENT
OCT 11, 2022 9:34 AM HIGH LIQUID ALARM
OCT 11, 2022 9:34 AM NO VACUUM ALARM
15 DIESEL TANK
16 DIESEL PRODUCT
OCT 11, 2022 9:32 AM NO VACUUM ALARM
OCT 11, 2022 9:32 AM HIGH LIQUID ALARM
17 DIESEL VENT
OCT 11, 2022 9:32 AM NO VACUUM ALARM
OCT 11, 2022 9:32 AM HIGH LIQUID ALARM
I40200
OCT 11, 2022 10:13 AM
I40300
OCT 11, 2022 10:13 AM
I34200
OCT 11, 2022 10:13 AM
I34700
OCT 11, 2022 10:13 AM
IV0100
OCT 11, 2022 10:13 AM
175900 MESA MARIN CH
PIT STOP MARKET
11101 HWY. 178
BAKERSFIELD,CA 93306
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :NOTEST
EVR VAPOR CONTAINMENT :NOTEST
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-10-06 10:03:52 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 38.55
22-10-05 10:03:48 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 37.45
22-10-04 10:03:56 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 33.33
22-10-03 10:03:55 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 32.76
22-10-02 10:03:59 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 31.98
22-10-01 10:03:39 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 31.95
22-09-30 10:03:11 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 30.32
22-09-24 10:04:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 24.92
22-09-23 10:03:58 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 24.91
22-09-22 10:03:47 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 25.16
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-10-09 10:03:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 43.37
22-10-08 10:03:42 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.44
22-10-07 10:03:44 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 39.38
22-06-11 10:07:00 FLOW PERFORMANCE HOSE BLOCKAGE FP 7 BLEND3
22-03-05 10:07:15 FLOW PERFORMANCE HOSE BLOCKAGE FP 1 BLEND3
21-09-07 10:07:55 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
21-08-18 10:08:51 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
21-07-26 10:05:35 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
21-04-12 10:05:16 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3
20-03-11 10:05:46 FLOW PERFORMANCE HOSE BLOCKAGE FP11 BLEND3
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-10-11 10:01:09 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-10-11 09:44:11 READINESS ISD:PF EVR:NNN CHECK ISD SENSORS
22-10-11 09:44:11 ISD STARTUP
22-10-11 09:44:07 ISD SHUTDOWN
22-10-11 09:15:00 TIME CHANGE DETECTED AT: 22-10-11 08:16:58
22-10-11 08:16:45 TIME CHANGE DETECTED AT: 21-02-13 08:16:44
22-10-10 10:01:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING
22-10-10 09:25:43 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
22-10-09 10:17:40 PUMPS MANUALLY RE-ENABLED
22-10-09 10:03:50 READINESS ISD:PP EVR:NF CHECK EVR SYSTEM