HomeMy WebLinkAboutFMC 2022Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10134244 10/24/2022 Jaco #3360 Farrell's Fastrip 6401 White Lane Bakersfield 93309 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Matt Story 1073967 9118985 2/17/2023 GVR ATG Tech C26845 4/22/2023 10/24/2022 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder Root TLS-350 336.02 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 794380-208 87 STP Sump L3 794380-208 87 Fill Sump L4 794380-208 91STP Sump L5 794380-208 91 Fill Sump L6 794380-303 91 Annular L7 794380-208 Diesel STP Sump L9 794380-303 Diesel Annular L10 794380-208 UDC 1-2 L11 794380-208 UDC 3-4 L12 794380-208 UDC 5-6 L13 794380-208 UDC 7-8 L14 794380-303 87 Annular L15 794380-208 Diesel Fill Sump Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 87 FX1V 87 product line 91 FX1V 91 product line Diesel FX1DV Diesel product line Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. 10-24-2022 EXISTING BUILDING 78L13 12,000 GALLON87 UNLEADED 34L11 56L1212L10 STPL1 AL2 12,000 GALLONPREMIUM 12,000 GALLONDIESEL FV FV F AL5 AL16 STPL4 STPL7 L3 L6 L8 NOPARKING NOPARKING DUMPSTERDRAINAGE WAYDRAINAGE WAY DRAINAGE WAYDRAINAGE WAY DRAINAGE WAY DRAINAGE WAYDUMPSTER H W W G WHITE LN. PROPERTY LINE ASHE RD.PRICE SIGNPLAZA SIGNPRICE SIGN N PROPERTY LINE LEGEND L1 87 STP L2 87 ANNULAR L3 87 FILL L4 91 STP L5 91 ANNULAR L6 91 FILL L7 DSL STP L8 DSL FILL L10 UDC 1 - 2 L11 UDC 3 - 4 L12 UDC 5 - 6 L13 UDC 7 - 8 L16 DSL ANNULAR 87 GAS 3/2 INCH DBL WALLED PIPE 91 GAS 3/2 INCH DBL WALLED PIPE DIESEL 3/2 INCH DBL WALLED PIPE VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE VAPOR VENT 2 INCH SINGLE WALLED PIPE PRODUCT SPILL CONTAINER VAPOR SPILL CONTAINER ANNULAR EMERGENCY SHUT-OFF OVERFILL ALARM FIRE EXTINGUISHER GAS METER SHUT-OFF WATER SHUT OFF HEALY CAS EVACUATION MEETING POINT AUTOMATIC TANK GAUGE UST ELECTRICAL PANEL CIRCUIT BREAKER AIR AND WATER DISPENSER FIRE PREVENTION SYSTEM G A H P V W SCALE: SITE MAP C1 VICINITY MAP PROJECT DATA 1"=20'-0" INCHES012 SHEET SIZE 22 X 34 6401 WHITE LN. BAKERSFIELD, CA 93309 PROJECT OWNER: JACO HILL PO. BOX 82515 BAKERSFIELD, CA 93380 CONTACT: SITE PLOT PLAN FOR: FACITILY ID 15-021-003021 CERS ID 10134202 FASTRIP #3360 6401 WHITE LN. BAKERSFIELD, CA 93309 01/16/17 REV.ASHE RD.WHITE LN. APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Jaco #3360 Farrell's Fastrip6401 White LaneBakersfield101342441/23/45/68791Diesel 87918791Diesel 871/21/23/45/65/67/8ProductProductProductProductProductProductProductProductProductMatt Story APPENDIX C-10 7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB917/8Matt Story Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10134244 10/24/2022 Jaco #3360 Farrell's Fastrip 6401 White Lane Bakersfield 93309 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Matt Story 1073967 9118985 2/17/2023 FFS 1015653711 4/13/2023 Hydrostatic Lake Test 87 Phil-Tite fill spill bucket Hydrostatic Lake Test 91 Phil-Tite fill spill bucket Hydrostatic Lake Test Diesel Phil-Tite fill spill bucket 10/24/2022 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. 87 Phil-Tite 91 Phil-Tite Diesel Phil-Tite SETUP Responses Received: 200 FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 OCT 24, 2022 9:08 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNL 10238 75.32 0.0 68.3 1444 2 PNL 8021 59.69 0.8 80.1 3661 3 DIESEL 7163 54.22 0.0 84.4 4519 I90500 OCT 24, 2022 9:09 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 OCT 24, 2022 9:09 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 OCT 24, 2022 9:09 AM SHIFT TIME 1 : 7:00 AM I50202 OCT 24, 2022 9:09 AM SHIFT TIME 2 : DISABLED I50203 OCT 24, 2022 9:09 AM SHIFT TIME 3 : DISABLED I50204 OCT 24, 2022 9:09 AM SHIFT TIME 4 : DISABLED I54600 OCT 24, 2022 9:09 AM TANK PER TST NEEDED WRN: DISABLED I54900 OCT 24, 2022 9:09 AM TANK ANN TST NEEDED WRN: DISABLED I55300 OCT 24, 2022 9:09 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 OCT 24, 2022 9:09 AM LINE PER TST NEEDED WRN: DISABLED I55900 OCT 24, 2022 9:09 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 OCT 24, 2022 9:09 AM PRINT TC VOLUMES ENABLED I50E00 OCT 24, 2022 9:09 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 OCT 24, 2022 9:09 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 OCT 24, 2022 9:09 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 OCT 24, 2022 9:09 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 OCT 24, 2022 9:09 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 OCT 24, 2022 9:09 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 OCT 24, 2022 9:09 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 OCT 24, 2022 9:09 AM TANK CHART SECURITY DISABLED I5BD00 OCT 24, 2022 9:09 AM CUSTOM ALARM LABELS DISABLED I56000 OCT 24, 2022 9:09 AM MASS/DENSITY DISABLED I88101 OCT 24, 2022 9:09 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88102 OCT 24, 2022 9:09 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 OCT 24, 2022 9:09 AM PORT SETTINGS: COMM BOARD : 3 (EDIM ) RS-232 SECURITY CODE : DISABLED I88104 OCT 24, 2022 9:09 AM I88105 OCT 24, 2022 9:09 AM I88106 OCT 24, 2022 9:09 AM I52000 OCT 24, 2022 9:09 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE ??? 24, 2022 DISABLED 2 ON DATE ??? 24, 2022 DISABLED 3 ON DATE ??? 24, 2022 DISABLED 4 ON DATE ??? 24, 2022 DISABLED 5 ON DATE ??? 24, 2022 DISABLED 6 ON DATE ??? 24, 2022 DISABLED 7 ON DATE ??? 24, 2022 DISABLED 8 ON DATE ??? 24, 2022 DISABLED I60100 OCT 24, 2022 9:09 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNL ON 2 PNL ON 3 DIESEL ON 4 OFF I60200 OCT 24, 2022 9:09 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNL 2 PNL 3 DIESEL 4 I60300 OCT 24, 2022 9:09 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNL 1 2 PNL 2 3 DIESEL 3 4 4 I60900 OCT 24, 2022 9:09 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNL 0.000700 2 PNL 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 OCT 24, 2022 9:09 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNL 92.00 2 PNL 92.00 3 DIESEL 92.00 4 0.00 I60A00 OCT 24, 2022 9:09 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL 1 PT 11682 2 PNL 1 PT 11682 3 DIESEL 1 PT 11682 4 1 PT 0 I60400 OCT 24, 2022 9:09 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 11682 2 PNL 11682 3 DIESEL 11682 4 0 I60500 OCT 24, 2022 9:09 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 11682 0 0 0 2 PNL 11682 0 0 0 3 DIESEL 11682 0 0 0 4 0 0 0 0 I60600 OCT 24, 2022 9:09 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 11682 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PNL 11682 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 11682 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 OCT 24, 2022 9:09 AM TANK PRODUCT LABEL METER DATA 1 UNL NO 2 PNL NO 3 DIESEL NO 4 NO I62F00 OCT 24, 2022 9:09 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNL 4.0 IN. 2 PNL 4.0 IN. 3 DIESEL 4.0 IN. I62700 OCT 24, 2022 9:09 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNL 2.0 2 PNL 2.0 3 DIESEL 2.0 I64200 OCT 24, 2022 9:09 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNL LOW 2 PNL LOW 3 DIESEL LOW I62400 OCT 24, 2022 9:09 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNL 3.0 2 PNL 3.0 3 DIESEL 3.0 I62800 OCT 24, 2022 9:09 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 11682 2 PNL 11682 3 DIESEL 11682 4 0 I62300 OCT 24, 2022 9:09 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 10800 2 PNL 10800 3 DIESEL 10800 4 0 I62200 OCT 24, 2022 9:09 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 11400 2 PNL 11400 3 DIESEL 11400 4 0 I62900 OCT 24, 2022 9:09 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1800 2 PNL 1800 3 DIESEL 1800 4 0 I62100 OCT 24, 2022 9:09 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 500 2 PNL 500 3 DIESEL 500 4 0 I62600 OCT 24, 2022 9:09 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 PNL 99 3 DIESEL 99 4 99 I62500 OCT 24, 2022 9:09 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 PNL 99 3 DIESEL 99 4 99 I60800 OCT 24, 2022 9:09 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNL 8.00 2 PNL 6.00 3 DIESEL 10.00 4 0.00 I60B00 OCT 24, 2022 9:09 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 OCT 24, 2022 9:09 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNL 0.00 2 PNL 0.00 3 DIESEL 0.00 4 0.00 I61200 OCT 24, 2022 9:09 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNL NONE NONE 2 PNL NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 OCT 24, 2022 9:09 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 120 2 PNL 120 3 DIESEL 120 4 0 I62A00 OCT 24, 2022 9:09 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 120 2 PNL 120 3 DIESEL 120 4 0 I62C00 OCT 24, 2022 9:09 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNL STANDARD 2 PNL STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 OCT 24, 2022 9:09 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 OCT 24, 2022 9:09 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNL OFF OFF 2 PNL OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 OCT 24, 2022 9:09 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNL OFF 2 PNL OFF 3 DIESEL OFF 4 OFF I63200 OCT 24, 2022 9:09 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNL OFF 2 PNL OFF 3 DIESEL OFF 4 OFF I61000 OCT 24, 2022 9:09 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNL 1 2 PNL 1 3 DIESEL 1 4 1 I63A00 OCT 24, 2022 9:09 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNL 10.00% 2 PNL 10.00% 3 DIESEL 10.00% 4 10.00% I61100 OCT 24, 2022 9:09 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK MAR 22, 2011 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 OCT 24, 2022 9:09 AM CSLD PROBABLITY OF DETECTION I61400 OCT 24, 2022 9:09 AM CSLD CLIMATE FACTOR I61600 OCT 24, 2022 9:09 AM TANK PRODUCT LABEL CAL UPDATE 1 UNL IMMEDIATE 2 PNL IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 OCT 24, 2022 9:09 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNL DISABLED 2 PNL DISABLED 3 DIESEL DISABLED 4 DISABLED I61B00 OCT 24, 2022 9:09 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 OCT 24, 2022 9:09 AM CSLD REPORT ONLY I62B00 OCT 24, 2022 9:09 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNL ??? 0, 0 2 PNL ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 OCT 24, 2022 9:09 AM LEAK TEST REPORT FORMAT: NORMAL I63400 OCT 24, 2022 9:09 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 0 2 PNL 0 3 DIESEL 0 4 0 I63500 OCT 24, 2022 9:09 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 2 PNL 1 3 DIESEL 1 4 1 I63900 OCT 24, 2022 9:09 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNL END FACTOR: NONE 2 PNL END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 OCT 24, 2022 9:09 AM I77700 OCT 24, 2022 9:09 AM I77800 OCT 24, 2022 9:09 AM I78C00 OCT 24, 2022 9:09 AM I78300 OCT 24, 2022 9:09 AM I78F00 OCT 24, 2022 9:09 AM I78700 OCT 24, 2022 9:09 AM I70200 OCT 24, 2022 9:09 AM LIQUID LABEL DEVICE LABEL 1 UNL STP 2 UNL ANN 3 UNL FILL 4 PNL STP 5 PNL FILL 6 PNL ANN 7 DIE STP 8 DIE FILL 9 DIE ANN 10 DIS 1-2 11 DIS 3-4 12 DIS 5-6 13 DIS 7-8 14 UNL ANN 15 DSL FILL 16 DIE ANN I70300 OCT 24, 2022 9:09 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL STP TRI-STATE (SINGLE FLOAT) 2 UNL ANN DUAL POINT HYDROSTATIC 3 UNL FILL TRI-STATE (SINGLE FLOAT) 4 PNL STP TRI-STATE (SINGLE FLOAT) 5 PNL FILL TRI-STATE (SINGLE FLOAT) 6 PNL ANN DUAL POINT HYDROSTATIC 7 DIE STP TRI-STATE (SINGLE FLOAT) 8 DIE FILL TRI-STATE (SINGLE FLOAT) 9 DIE ANN DUAL POINT HYDROSTATIC 10 DIS 1-2 TRI-STATE (SINGLE FLOAT) 11 DIS 3-4 TRI-STATE (SINGLE FLOAT) 12 DIS 5-6 TRI-STATE (SINGLE FLOAT) 13 DIS 7-8 TRI-STATE (SINGLE FLOAT) 14 UNL ANN DUAL POINT HYDROSTATIC 15 DSL FILL TRI-STATE (SINGLE FLOAT) 16 DIE ANN DUAL POINT HYDROSTATIC I70400 OCT 24, 2022 9:09 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL STP STP SUMP 2 UNL ANN ANNULAR SPACE 3 UNL FILL OTHER SENSORS 4 PNL STP STP SUMP 5 PNL FILL OTHER SENSORS 6 PNL ANN ANNULAR SPACE 7 DIE STP STP SUMP 8 DIE FILL OTHER SENSORS 9 DIE ANN ANNULAR SPACE 10 DIS 1-2 DISPENSER PAN 11 DIS 3-4 DISPENSER PAN 12 DIS 5-6 DISPENSER PAN 13 DIS 7-8 DISPENSER PAN 14 UNL ANN ANNULAR SPACE 15 DSL FILL OTHER SENSORS 16 DIE ANN ANNULAR SPACE I74200 OCT 24, 2022 9:09 AM I74300 OCT 24, 2022 9:09 AM I74400 OCT 24, 2022 9:09 AM I74700 OCT 24, 2022 9:09 AM I74800 OCT 24, 2022 9:09 AM I74900 OCT 24, 2022 9:09 AM I7BC00 OCT 24, 2022 9:09 AM I80200 OCT 24, 2022 9:09 AM I80300 OCT 24, 2022 9:09 AM I80400 OCT 24, 2022 9:09 AM I80700 OCT 24, 2022 9:09 AM RELAY LABEL DEVICE LABEL 1 UNL 2 PNL 3 DSL 4 OVERFILL I80900 OCT 24, 2022 9:09 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL NORMALLY CLOSED 2 PNL NORMALLY CLOSED 3 DSL NORMALLY CLOSED 4 OVERFILL NORMALLY OPEN I80B00 OCT 24, 2022 9:09 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNL 1 2 PNL 2 3 DSL 3 4 OVERFILL 1 I80A00 OCT 24, 2022 9:09 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNL STANDARD 2 PNL STANDARD 3 DSL STANDARD 4 OVERFILL STANDARD I80C00 OCT 24, 2022 9:09 AM I80800 OCT 24, 2022 9:09 AM RELAY SETUP REPORT R 1:UNL TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L 1:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 1:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PNL TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 4:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L 4:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 4:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DSL TYPE: STANDARD NORMALLY CLOSED TANK #: 3 LIQUID SENSOR ALMS L 7:FUEL ALARM L10:FUEL ALARM L12:FUEL ALARM L 7:SENSOR OUT ALARM L10:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 7:SHORT ALARM L10:SHORT ALARM L12:SHORT ALARM R 4:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: 1 IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 OCT 24, 2022 9:10 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 OCT 24, 2022 9:10 AM I72300 OCT 24, 2022 9:10 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VP SENSOR DIS 3-4 VAPOR PRESSURE 02 FM DIS 1-2 AIR FLOW METER 03 FM DIS 3-4 AIR FLOW METER 04 FM DIS 5-6 AIR FLOW METER 05 FM DIS 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 OCT 24, 2022 9:10 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 OCT 24, 2022 9:10 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 OCT 24, 2022 9:10 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 VAPOR PROCESSOR TYPE NONE IV4700 OCT 24, 2022 9:10 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 ASSESSMENT TIME START TIME: 10:01 AM TIME DELAY MINUTES: 1 IV5200 OCT 24, 2022 9:10 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 ACCEPT HIGH ORVR: NO IV4A00 OCT 24, 2022 9:10 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 02 BLEND3 02 02 02 01 02 BLEND3 03 03 03 02 02 BLEND3 04 04 04 02 02 BLEND3 05 05 05 03 02 BLEND3 06 06 06 03 02 BLEND3 07 07 07 04 02 BLEND3 08 08 08 04 02 BLEND3 IV4B00 OCT 24, 2022 9:10 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 03/01 09/01 xx/xx 02 01 02/02 03/02 09/02 xx/xx 03 02 02/03 03/03 09/03 xx/xx 04 02 02/04 03/04 09/04 xx/xx 05 03 02/05 03/05 09/05 xx/xx 06 03 02/06 03/06 09/06 xx/xx 07 04 02/07 03/07 09/07 xx/xx 08 04 02/08 03/08 09/08 xx/xx IV4900 OCT 24, 2022 9:10 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 OCT 24, 2022 9:10 AM ISD VERSION: 01.07 ALARM HISTORY (BEFORE) Responses Received: I10200 OCT 24, 2022 9:11 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39576 39536 2 4 PROBE / G.T. 164189 163979 3 INTERSTITIAL BD 202921 202640 4 INTERSTITIAL BD 202609 202375 5 UNUSED 9839353 9690458 6 UNUSED 9834213 9680254 7 UNUSED 9832507 9679074 8 UNUSED 9831816 9674330 9 STP SENSE BOARD 33074 33074 10 RELAY BOARD 15053 15053 11 UNUSED 9835996 9686343 12 UNUSED 9830763 9679054 13 UNUSED 9836987 9681067 14 UNUSED 9826200 9680049 15 UNUSED 9830072 9681576 16 UNUSED 9824655 9678684 COMM 1 RS232 SERIAL BD 15030 15053 COMM 2 RS232 SERIAL BD 15099 15099 COMM 3 ELEC DISP INT. 101796 101770 COMM 4 UNUSED 9842657 9682340 COMM 5 UNUSED 9829519 9682756 COMM 6 UNUSED 9828274 9677041 I90200 OCT 24, 2022 9:11 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 OCT 24, 2022 9:11 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L10 DISP PAN DIS 1-2 FUEL ALARM CLEAR 8-15-22 10:35AM L10 DISP PAN DIS 1-2 FUEL ALARM ALARM 8-15-22 10:23AM L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 8-15-22 10:12AM L 7 STP SUMP DIE STP SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L 3 OTHER UNL FILL SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L15 OTHER DSL FILL SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L 5 OTHER PNL FILL SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L12 DISP PAN DIS 5-6 SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L11 DISP PAN DIS 3-4 SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L14 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L13 DISP PAN DIS 7-8 SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L10 DISP PAN DIS 1-2 SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L 9 ANNULAR DIE ANN SENSOR OUT ALARM CLEAR 8-15-22 10:11AM L15 OTHER DSL FILL SENSOR OUT ALARM ALARM 8-15-22 10:08AM L14 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 8-15-22 10:08AM L12 DISP PAN DIS 5-6 SENSOR OUT ALARM ALARM 8-15-22 10:08AM L11 DISP PAN DIS 3-4 SENSOR OUT ALARM ALARM 8-15-22 10:08AM L10 DISP PAN DIS 1-2 SENSOR OUT ALARM ALARM 8-15-22 10:08AM L 7 STP SUMP DIE STP SENSOR OUT ALARM ALARM 8-15-22 10:08AM L13 DISP PAN DIS 7-8 SENSOR OUT ALARM ALARM 8-15-22 10:08AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 8-15-22 10:08AM L 9 ANNULAR DIE ANN SENSOR OUT ALARM ALARM 8-15-22 10:08AM L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 8-15-22 10:08AM L 3 OTHER UNL FILL SENSOR OUT ALARM ALARM 8-15-22 10:08AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 8-15-22 10:08AM L 5 OTHER PNL FILL SENSOR OUT ALARM ALARM 8-15-22 10:08AM L14 ANNULAR UNL ANN LOW LIQUID ALARM CLEAR 8-15-22 10:06AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 8-15-22 10:05AM L 9 ANNULAR DIE ANN LOW LIQUID ALARM CLEAR 8-15-22 10:05AM L15 OTHER DSL FILL FUEL ALARM CLEAR 8-15-22 10:04AM L 5 OTHER PNL FILL FUEL ALARM CLEAR 8-15-22 10:04AM L 3 OTHER UNL FILL FUEL ALARM CLEAR 8-15-22 10:03AM L14 ANNULAR UNL ANN LOW LIQUID ALARM ALARM 8-15-22 10:03AM L14 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 8-15-22 10:03AM L14 ANNULAR UNL ANN LOW LIQUID ALARM CLEAR 8-15-22 10:03AM L14 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 8-15-22 10:03AM L14 ANNULAR UNL ANN LOW LIQUID ALARM ALARM 8-15-22 10:03AM L13 DISP PAN DIS 7-8 FUEL ALARM CLEAR 8-15-22 10:03AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM ALARM 8-15-22 10:02AM L 6 ANNULAR PNL ANN HIGH LIQUID ALARM CLEAR 8-15-22 10:02AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 8-15-22 10:02AM L 6 ANNULAR PNL ANN HIGH LIQUID ALARM ALARM 8-15-22 10:02AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM ALARM 8-15-22 10:02AM L 9 ANNULAR DIE ANN LOW LIQUID ALARM ALARM 8-15-22 10:02AM L 9 ANNULAR DIE ANN HIGH LIQUID ALARM CLEAR 8-15-22 10:02AM L 9 ANNULAR DIE ANN LOW LIQUID ALARM CLEAR 8-15-22 10:02AM L 9 ANNULAR DIE ANN HIGH LIQUID ALARM ALARM 8-15-22 10:02AM L 9 ANNULAR DIE ANN LOW LIQUID ALARM ALARM 8-15-22 10:02AM I11200 OCT 24, 2022 9:12 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD GROSS PRES WARN CLEAR 10-18-22 10:16AM OTHER ISD GROSS PRES WARN ALARM 10-18-22 10:02AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 10-16-22 1:53PM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 10-16-22 1:53PM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 10-16-22 12:32PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 10-16-22 5:48AM T 1 TANK UNL DELIVERY NEEDED CLEAR 10-04-22 2:18PM T 1 TANK UNL DELIVERY NEEDED ALARM 10-04-22 1:13PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 10-02-22 12:59PM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 10-02-22 12:59PM SYSTEM PRINTER ERROR CLEAR 10-02-22 7:08AM SYSTEM PAPER OUT CLEAR 10-02-22 7:08AM SYSTEM PRINTER ERROR ALARM 10-02-22 7:08AM SYSTEM PAPER OUT ALARM 10-02-22 7:08AM SYSTEM PRINTER ERROR CLEAR 10-02-22 7:08AM SYSTEM PAPER OUT CLEAR 10-02-22 7:08AM SYSTEM PRINTER ERROR ALARM 10-02-22 7:06AM SYSTEM PAPER OUT ALARM 10-02-22 7:06AM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 10-02-22 7:06AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 10-01-22 3:05PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 9-22-22 12:14AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 9-21-22 10:33PM SYSTEM PRINTER ERROR CLEAR 6-30-22 2:05PM SYSTEM PRINTER ERROR ALARM 6-30-22 2:05PM SYSTEM PRINTER ERROR CLEAR 6-30-22 2:03PM SYSTEM PAPER OUT CLEAR 6-30-22 2:03PM SYSTEM PRINTER ERROR ALARM 6-30-22 2:00PM SYSTEM PAPER OUT ALARM 6-30-22 2:00PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:59PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:59PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:59PM SYSTEM PAPER OUT CLEAR 6-30-22 1:59PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:58PM SYSTEM PAPER OUT ALARM 6-30-22 1:58PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:58PM SYSTEM PAPER OUT CLEAR 6-30-22 1:58PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:58PM SYSTEM PAPER OUT ALARM 6-30-22 1:58PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:58PM SYSTEM PAPER OUT CLEAR 6-30-22 1:58PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:58PM SYSTEM PAPER OUT ALARM 6-30-22 1:58PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:58PM SYSTEM PAPER OUT CLEAR 6-30-22 1:58PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:57PM SYSTEM PAPER OUT ALARM 6-30-22 1:57PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:57PM SYSTEM PAPER OUT CLEAR 6-30-22 1:57PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:57PM SYSTEM PAPER OUT ALARM 6-30-22 1:57PM I20600 OCT 24, 2022 9:12 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 TANK ALARM HISTORY TANK 1 UNL DELIVERY NEEDED OCT 4, 2022 1:13 PM APR 12, 2022 4:04 PM MAR 15, 2022 9:53 PM TANK 2 PNL TANK 3 DIESEL INVALID FUEL LEVEL OCT 16, 2022 12:32 PM OCT 2, 2022 7:06 AM DELIVERY NEEDED OCT 16, 2022 5:48 AM OCT 1, 2022 3:05 PM SEP 21, 2022 10:33 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 OCT 24, 2022 9:12 AM I30200 OCT 24, 2022 9:12 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 9:43 AM FUEL ALARM JUL 6, 2022 2:40 AM FUEL ALARM 3 UNL FILL AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 10:00 AM FUEL ALARM MAR 3, 2022 12:12 PM FUEL ALARM 4 PNL STP AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 9:43 AM FUEL ALARM MAR 3, 2022 12:00 PM FUEL ALARM 5 PNL FILL AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 10:01 AM FUEL ALARM MAR 3, 2022 12:20 PM FUEL ALARM 6 PNL ANN AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 10:02 AM LOW LIQUID ALARM AUG 15, 2022 10:02 AM HIGH LIQUID ALARM 7 DIE STP AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 9:42 AM FUEL ALARM MAR 3, 2022 11:58 AM FUEL ALARM 9 DIE ANN AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 10:02 AM LOW LIQUID ALARM AUG 15, 2022 10:02 AM HIGH LIQUID ALARM 10 DIS 1-2 AUG 15, 2022 10:23 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 9:51 AM FUEL ALARM 11 DIS 3-4 AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 9:56 AM FUEL ALARM MAR 3, 2022 11:49 AM FUEL ALARM 12 DIS 5-6 AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 9:47 AM FUEL ALARM MAR 3, 2022 11:50 AM FUEL ALARM 13 DIS 7-8 AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 9:59 AM FUEL ALARM MAR 3, 2022 11:51 AM FUEL ALARM 14 UNL ANN AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 10:03 AM LOW LIQUID ALARM AUG 15, 2022 10:03 AM HIGH LIQUID ALARM 15 DSL FILL AUG 15, 2022 10:08 AM SENSOR OUT ALARM AUG 15, 2022 10:01 AM FUEL ALARM MAR 4, 2022 3:41 AM FUEL ALARM I31600 OCT 24, 2022 9:12 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP SENSOR DIS 3-4 2 FM DIS 1-2 3 FM DIS 3-4 4 FM DIS 5-6 5 FM DIS 7-8 I40200 OCT 24, 2022 9:12 AM I40300 OCT 24, 2022 9:12 AM I34200 OCT 24, 2022 9:12 AM I34700 OCT 24, 2022 9:12 AM IV0100 OCT 24, 2022 9:12 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-10-18 10:02:18 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.40 22-05-09 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.81 22-05-08 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.81 21-07-25 10:01:25 21-07-22 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 21-07-21 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 21-04-16 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.45 21-04-15 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.75 21-04-09 10:02:09 A/L RATIO DEGRADATION FP 4 BLEND3 1.34 21-03-22 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.56 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 21-01-04 10:04:34 A/L RATIO DEGRADATION FP 2 BLEND3 0.68 21-01-03 10:04:02 A/L RATIO DEGRADATION FP 2 BLEND3 0.68 19-02-25 10:01:11 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 19-02-25 10:01:11 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 18-02-25 10:07:04 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 18-02-25 10:07:04 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 17-10-31 10:06:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 15-12-27 10:07:23 A/L RATIO DEGRADATION FP 5 BLEND3 0.76 11-10-02 10:02:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 11-10-02 10:02:09 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-10-18 10:16:33 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 22-08-20 10:02:09 READINESS ISD:PP EVR:PP ISD & EVR READY 22-08-19 10:02:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-08-19 10:00:41 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-08-19 10:00:41 ISD STARTUP 22-08-19 10:00:39 ISD SHUTDOWN 22-08-16 10:02:09 READINESS ISD:PP EVR:PP ISD & EVR READY 22-08-15 10:07:46 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-08-15 10:07:46 ISD STARTUP 22-08-15 10:07:29 ISD SHUTDOWN ALARM HISTORY (AFTER) Responses Received: I10200 OCT 24, 2022 10:02 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39576 39530 2 4 PROBE / G.T. 164189 164100 3 INTERSTITIAL BD 202921 202643 4 INTERSTITIAL BD 202609 202499 5 UNUSED 9839353 9814833 6 UNUSED 9834213 9806212 7 UNUSED 9832507 9811606 8 UNUSED 9831816 9802040 9 STP SENSE BOARD 33074 33074 10 RELAY BOARD 15053 15030 11 UNUSED 9835996 9807073 12 UNUSED 9830763 9809655 13 UNUSED 9836987 9803708 14 UNUSED 9826200 9807165 15 UNUSED 9830072 9807465 16 UNUSED 9824655 9803523 COMM 1 RS232 SERIAL BD 15030 15053 COMM 2 RS232 SERIAL BD 15099 15076 COMM 3 ELEC DISP INT. 101796 101869 COMM 4 UNUSED 9842657 9814172 COMM 5 UNUSED 9829519 9812075 COMM 6 UNUSED 9828274 9806151 I90200 OCT 24, 2022 10:02 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 OCT 24, 2022 10:02 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 7 STP SUMP DIE STP SENSOR OUT ALARM CLEAR 10-24-22 9:57AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 10-24-22 9:57AM L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L 5 OTHER PNL FILL SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L 3 OTHER UNL FILL SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L 9 ANNULAR DIE ANN SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L15 OTHER DSL FILL SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L10 DISP PAN DIS 1-2 SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L14 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L12 DISP PAN DIS 5-6 SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L13 DISP PAN DIS 7-8 SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L11 DISP PAN DIS 3-4 SENSOR OUT ALARM CLEAR 10-24-22 9:56AM L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 10-24-22 9:55AM L 3 OTHER UNL FILL SENSOR OUT ALARM ALARM 10-24-22 9:55AM L 7 STP SUMP DIE STP SENSOR OUT ALARM ALARM 10-24-22 9:55AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 10-24-22 9:55AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 10-24-22 9:55AM L12 DISP PAN DIS 5-6 SENSOR OUT ALARM ALARM 10-24-22 9:55AM L 5 OTHER PNL FILL SENSOR OUT ALARM ALARM 10-24-22 9:55AM L11 DISP PAN DIS 3-4 SENSOR OUT ALARM ALARM 10-24-22 9:55AM L10 DISP PAN DIS 1-2 SENSOR OUT ALARM ALARM 10-24-22 9:55AM L15 OTHER DSL FILL SENSOR OUT ALARM ALARM 10-24-22 9:55AM L14 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 10-24-22 9:55AM L 9 ANNULAR DIE ANN SENSOR OUT ALARM ALARM 10-24-22 9:55AM L13 DISP PAN DIS 7-8 SENSOR OUT ALARM ALARM 10-24-22 9:55AM L 1 STP SUMP UNL STP FUEL ALARM CLEAR 10-24-22 9:53AM L 1 STP SUMP UNL STP FUEL ALARM ALARM 10-24-22 9:53AM L 4 STP SUMP PNL STP FUEL ALARM CLEAR 10-24-22 9:52AM L 4 STP SUMP PNL STP FUEL ALARM ALARM 10-24-22 9:52AM L 7 STP SUMP DIE STP FUEL ALARM CLEAR 10-24-22 9:52AM L 7 STP SUMP DIE STP FUEL ALARM ALARM 10-24-22 9:52AM L13 DISP PAN DIS 7-8 FUEL ALARM CLEAR 10-24-22 9:50AM L13 DISP PAN DIS 7-8 FUEL ALARM ALARM 10-24-22 9:50AM L12 DISP PAN DIS 5-6 FUEL ALARM CLEAR 10-24-22 9:49AM L12 DISP PAN DIS 5-6 FUEL ALARM ALARM 10-24-22 9:49AM L10 DISP PAN DIS 1-2 FUEL ALARM CLEAR 10-24-22 9:49AM L10 DISP PAN DIS 1-2 FUEL ALARM ALARM 10-24-22 9:48AM L11 DISP PAN DIS 3-4 FUEL ALARM CLEAR 10-24-22 9:47AM L 9 ANNULAR DIE ANN LOW LIQUID ALARM CLEAR 10-24-22 9:45AM L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 10-24-22 9:45AM L11 DISP PAN DIS 3-4 FUEL ALARM ALARM 10-24-22 9:44AM L14 ANNULAR UNL ANN LOW LIQUID ALARM CLEAR 10-24-22 9:44AM L15 OTHER DSL FILL FUEL ALARM CLEAR 10-24-22 9:42AM L 9 ANNULAR DIE ANN LOW LIQUID ALARM ALARM 10-24-22 9:42AM L 9 ANNULAR DIE ANN HIGH LIQUID ALARM CLEAR 10-24-22 9:42AM L 9 ANNULAR DIE ANN LOW LIQUID ALARM CLEAR 10-24-22 9:42AM L 9 ANNULAR DIE ANN HIGH LIQUID ALARM ALARM 10-24-22 9:42AM L 5 OTHER PNL FILL FUEL ALARM CLEAR 10-24-22 9:42AM L 9 ANNULAR DIE ANN LOW LIQUID ALARM ALARM 10-24-22 9:42AM I11200 OCT 24, 2022 10:02 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD GROSS PRES WARN CLEAR 10-18-22 10:16AM OTHER ISD GROSS PRES WARN ALARM 10-18-22 10:02AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 10-16-22 1:53PM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 10-16-22 1:53PM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 10-16-22 12:32PM T 3 TANK DIESEL DELIVERY NEEDED ALARM 10-16-22 5:48AM T 1 TANK UNL DELIVERY NEEDED CLEAR 10-04-22 2:18PM T 1 TANK UNL DELIVERY NEEDED ALARM 10-04-22 1:13PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 10-02-22 12:59PM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 10-02-22 12:59PM SYSTEM PRINTER ERROR CLEAR 10-02-22 7:08AM SYSTEM PAPER OUT CLEAR 10-02-22 7:08AM SYSTEM PRINTER ERROR ALARM 10-02-22 7:08AM SYSTEM PAPER OUT ALARM 10-02-22 7:08AM SYSTEM PRINTER ERROR CLEAR 10-02-22 7:08AM SYSTEM PAPER OUT CLEAR 10-02-22 7:08AM SYSTEM PRINTER ERROR ALARM 10-02-22 7:06AM SYSTEM PAPER OUT ALARM 10-02-22 7:06AM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 10-02-22 7:06AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 10-01-22 3:05PM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 9-22-22 12:14AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 9-21-22 10:33PM SYSTEM PRINTER ERROR CLEAR 6-30-22 2:05PM SYSTEM PRINTER ERROR ALARM 6-30-22 2:05PM SYSTEM PRINTER ERROR CLEAR 6-30-22 2:03PM SYSTEM PAPER OUT CLEAR 6-30-22 2:03PM SYSTEM PRINTER ERROR ALARM 6-30-22 2:00PM SYSTEM PAPER OUT ALARM 6-30-22 2:00PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:59PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:59PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:59PM SYSTEM PAPER OUT CLEAR 6-30-22 1:59PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:58PM SYSTEM PAPER OUT ALARM 6-30-22 1:58PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:58PM SYSTEM PAPER OUT CLEAR 6-30-22 1:58PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:58PM SYSTEM PAPER OUT ALARM 6-30-22 1:58PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:58PM SYSTEM PAPER OUT CLEAR 6-30-22 1:58PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:58PM SYSTEM PAPER OUT ALARM 6-30-22 1:58PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:58PM SYSTEM PAPER OUT CLEAR 6-30-22 1:58PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:57PM SYSTEM PAPER OUT ALARM 6-30-22 1:57PM SYSTEM PRINTER ERROR CLEAR 6-30-22 1:57PM SYSTEM PAPER OUT CLEAR 6-30-22 1:57PM SYSTEM PRINTER ERROR ALARM 6-30-22 1:57PM SYSTEM PAPER OUT ALARM 6-30-22 1:57PM I20600 OCT 24, 2022 10:03 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 TANK ALARM HISTORY TANK 1 UNL DELIVERY NEEDED OCT 4, 2022 1:13 PM APR 12, 2022 4:04 PM MAR 15, 2022 9:53 PM TANK 2 PNL TANK 3 DIESEL INVALID FUEL LEVEL OCT 16, 2022 12:32 PM OCT 2, 2022 7:06 AM DELIVERY NEEDED OCT 16, 2022 5:48 AM OCT 1, 2022 3:05 PM SEP 21, 2022 10:33 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 OCT 24, 2022 10:03 AM I30200 OCT 24, 2022 10:03 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:53 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM 3 UNL FILL OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:38 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM 4 PNL STP OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:52 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM 5 PNL FILL OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:38 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM 6 PNL ANN OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:42 AM LOW LIQUID ALARM OCT 24, 2022 9:41 AM HIGH LIQUID ALARM 7 DIE STP OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:52 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM 9 DIE ANN OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:42 AM LOW LIQUID ALARM OCT 24, 2022 9:42 AM HIGH LIQUID ALARM 10 DIS 1-2 OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:48 AM FUEL ALARM AUG 15, 2022 10:23 AM FUEL ALARM 11 DIS 3-4 OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:44 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM 12 DIS 5-6 OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:49 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM 13 DIS 7-8 OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:50 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM 14 UNL ANN OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:41 AM LOW LIQUID ALARM OCT 24, 2022 9:40 AM HIGH LIQUID ALARM 15 DSL FILL OCT 24, 2022 9:55 AM SENSOR OUT ALARM OCT 24, 2022 9:39 AM FUEL ALARM AUG 15, 2022 10:08 AM SENSOR OUT ALARM I31600 OCT 24, 2022 10:03 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP SENSOR DIS 3-4 2 FM DIS 1-2 3 FM DIS 3-4 4 FM DIS 5-6 5 FM DIS 7-8 I40200 OCT 24, 2022 10:03 AM I40300 OCT 24, 2022 10:03 AM I34200 OCT 24, 2022 10:03 AM I34700 OCT 24, 2022 10:03 AM IV0100 OCT 24, 2022 10:03 AM FASTRIP 6401 WHITE LANE BAKERSFIELD,CA 93309 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME : 99% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 22-10-18 10:02:18 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.40 22-05-09 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.81 22-05-08 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 10.81 21-07-25 10:01:25 21-07-22 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 21-07-21 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.22 21-04-16 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.45 21-04-15 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.75 21-04-09 10:02:09 A/L RATIO DEGRADATION FP 4 BLEND3 1.34 21-03-22 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.56 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 21-01-04 10:04:34 A/L RATIO DEGRADATION FP 2 BLEND3 0.68 21-01-03 10:04:02 A/L RATIO DEGRADATION FP 2 BLEND3 0.68 19-02-25 10:01:11 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 19-02-25 10:01:11 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 18-02-25 10:07:04 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 18-02-25 10:07:04 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 17-10-31 10:06:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 15-12-27 10:07:23 A/L RATIO DEGRADATION FP 5 BLEND3 0.76 11-10-02 10:02:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 11-10-02 10:02:09 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 22-10-24 10:02:32 READINESS ISD:PP EVR:PP ISD & EVR READY 22-10-24 09:58:20 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-10-24 09:58:20 ISD STARTUP 22-10-24 09:57:59 ISD SHUTDOWN 22-10-18 10:16:33 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 22-08-20 10:02:09 READINESS ISD:PP EVR:PP ISD & EVR READY 22-08-19 10:02:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING 22-08-19 10:00:41 READINESS ISD:PP EVR:NN EVR READINESS PENDING 22-08-19 10:00:41 ISD STARTUP 22-08-19 10:00:39 ISD SHUTDOWN