Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10134205 11/2/2022
Jaco #3362 Fastrip #633
6401 South H Street Bakersfield 93304
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Aaron Perrigo
1073967
8485827 8/8/2022
Veeder Root B47853 7/30/2024
OPW 0148613 8/21/2024
11/2/2022 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS-350 336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 Unl STP
L2 208 Unl Fill
L3 303 Unl Ann
L4 208 Prem STP
L5 208 Prem Fill
L6 303 Prem Ann
L7 208 Dsl STP
L8 208 Dsl Fill
L9 303 Dsl Ann
L10 208 Disp 1-2
L11 208 Disp 3-4
L12 208 Disp 5-6
L13 208 Disp 7-8
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V Unl
T2 FX1V Prem
T3 FX1DV Dsl
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
FVAL3 STPL1L212,000 GALLON87 UNLEADED
AL6 STPL4L5
AL9 STPL7L8
V
F
F
12L1056L12
34L1178L13
NOPARKING
EXISTING BUILDING
12,000 GALLONPREMIUM
12,000 GALLONDIESEL
PRICE SIGNDUMPSTERCATCHBASIN
W
G
H
W
SOUTH H ST.PANAMA LN.PROPERTY LINE
STORAGE CONTAINER130'130'109.98'110.11'
N
LEGEND
L1 87 STP
L2 87 FILL
L3 87 ANNULAR
L4 91 STP
L5 91 FILL
L6 91 ANNULAR
L7 DSL STP
L8 DSL FILL
L9 DSL ANNULAR
L10 UDC 1 - 2
L11 UDC 3 - 4
L12 UDC 5 - 6
L13 UDC 7 - 8
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
AUTOMATIC TANK GAUGE
CIRCUIT BREAKER
UST ELECTRICAL PANEL
AIR AND WATER
HAZWASTE DRUM
W
G
A
H
P
V
SCALE:
SITE MAP C1
VICINITY MAP
PROJECT DATA
1"=10'-0"
INCHES012
SHEET SIZE 22 X 34
6401 S H ST.
BAKERSFIELD, CA 93304
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-003024
CERS ID 10134205
FASTRIP #3362
6401 S H ST.
BAKERSFIELD, CA 93304
01/23/17 REV.S H ST.PANAMA LN.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #3362 Fastrip #6336401 South H StreetBakersfield101342053-47-8MPD MPD MPD MPD 1-25-6ProductProductProductProductAaron Perrigo
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10134205 11/2/2022
Jaco #3362 Fastrip #633
6401 South H Street Bakersfield 93304
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Aaron Perrigo
1073967
8485827 8/8/2022
FFS 1010993708 7/10/2024
Lake Test All 3 fill spill buckets
11/2/2022 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
Unl
PhilTite
Prem
PhilTite
Dsl
PhilTite
Jaco 3362 Setup
Responses Received:
200
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
NOV 2, 2022 9:02 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 4802 39.55 0.8 73.3 6880
2 PREMIUM 6618 50.81 0.0 75.8 5064
3 DIESEL 3184 29.18 0.0 81.5 8498
I90500
NOV 2, 2022 9:02 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
NOV 2, 2022 9:02 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
NOV 2, 2022 9:02 AM
SHIFT TIME 1 : 6:00 AM
I50202
NOV 2, 2022 9:02 AM
SHIFT TIME 2 : DISABLED
I50203
NOV 2, 2022 9:02 AM
SHIFT TIME 3 : DISABLED
I50204
NOV 2, 2022 9:02 AM
SHIFT TIME 4 : DISABLED
I54600
NOV 2, 2022 9:02 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
NOV 2, 2022 9:02 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
NOV 2, 2022 9:02 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
NOV 2, 2022 9:02 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
NOV 2, 2022 9:02 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
NOV 2, 2022 9:02 AM
PRINT TC VOLUMES
ENABLED
I50E00
NOV 2, 2022 9:02 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
NOV 2, 2022 9:02 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
NOV 2, 2022 9:02 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
NOV 2, 2022 9:03 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
NOV 2, 2022 9:03 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 1 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
NOV 2, 2022 9:03 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
NOV 2, 2022 9:03 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
NOV 2, 2022 9:03 AM
TANK CHART SECURITY
DISABLED
I5BD00
NOV 2, 2022 9:03 AM
CUSTOM ALARM LABELS
DISABLED
I56000
NOV 2, 2022 9:03 AM
MASS/DENSITY
DISABLED
I88101
NOV 2, 2022 9:03 AM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88102
NOV 2, 2022 9:03 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
NOV 2, 2022 9:03 AM
PORT SETTINGS:
COMM BOARD : 3 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88104
NOV 2, 2022 9:03 AM
I88105
NOV 2, 2022 9:03 AM
I88106
NOV 2, 2022 9:03 AM
I52000
NOV 2, 2022 9:03 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE JUN 24, 2019 DISABLED
2 ON DATE JUN 24, 2019 DISABLED
3 ON DATE JUN 24, 2019 DISABLED
4 ON DATE JUN 24, 2019 DISABLED
5 ON DATE JUN 24, 2019 DISABLED
6 ON DATE JUN 24, 2019 DISABLED
7 ON DATE JUN 24, 2019 DISABLED
8 ON DATE JUN 24, 2019 DISABLED
I60100
NOV 2, 2022 9:03 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 PREMIUM ON
3 DIESEL ON
4 OFF
I60200
NOV 2, 2022 9:03 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4
I60300
NOV 2, 2022 9:03 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL 3
4 4
I60900
NOV 2, 2022 9:03 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 PREMIUM 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
NOV 2, 2022 9:03 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 92.00
2 PREMIUM 92.00
3 DIESEL 92.00
4 0.00
I60A00
NOV 2, 2022 9:03 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
1 PT 11682 2 PREMIUM 1 PT 11682 3 DIESEL
1 PT 11682 4 1 PT 0
I60400
NOV 2, 2022 9:03 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11682
2 PREMIUM 11682
3 DIESEL 11682
4 0
I60500
NOV 2, 2022 9:03 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11682 0 0 0
2 PREMIUM 11682 0 0 0
3 DIESEL 11682 0 0 0
4 0 0 0 0
I60600
NOV 2, 2022 9:03 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11682 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 PREMIUM 11682 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DIESEL 11682 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
NOV 2, 2022 9:03 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 PREMIUM NO
3 DIESEL NO
4 NO
I62F00
NOV 2, 2022 9:03 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN.
2 PREMIUM 4.0 IN.
3 DIESEL 4.0 IN.
I62700
NOV 2, 2022 9:03 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 PREMIUM 2.0
3 DIESEL 2.0
I64200
NOV 2, 2022 9:03 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 PREMIUM LOW
3 DIESEL LOW
I62400
NOV 2, 2022 9:03 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 PREMIUM 3.0
3 DIESEL 3.0
I62800
NOV 2, 2022 9:03 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11682
2 PREMIUM 11682
3 DIESEL 11682
4 0
I62300
NOV 2, 2022 9:03 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10514
2 PREMIUM 10514
3 DIESEL 10514
4 0
I62200
NOV 2, 2022 9:03 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11098
2 PREMIUM 11098
3 DIESEL 11098
4 0
I62900
NOV 2, 2022 9:03 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1168
2 PREMIUM 1168
3 DIESEL 1168
4 0
I62100
NOV 2, 2022 9:03 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1200
2 PREMIUM 1200
3 DIESEL 1200
4 0
I62600
NOV 2, 2022 9:03 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I62500
NOV 2, 2022 9:03 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I60800
NOV 2, 2022 9:03 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 9.00
2 PREMIUM 8.00
3 DIESEL 0.00
4 0.00
I60B00
NOV 2, 2022 9:03 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
NOV 2, 2022 9:03 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 0.00
3 DIESEL 0.00
4 0.00
I61200
NOV 2, 2022 9:03 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 PREMIUM NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
NOV 2, 2022 9:03 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 PREMIUM 120
3 DIESEL 120
4 0
I62A00
NOV 2, 2022 9:03 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 PREMIUM 120
3 DIESEL 120
4 0
I62C00
NOV 2, 2022 9:03 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 PREMIUM STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
NOV 2, 2022 9:03 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
NOV 2, 2022 9:03 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 PREMIUM OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
NOV 2, 2022 9:03 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I63200
NOV 2, 2022 9:03 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I61000
NOV 2, 2022 9:03 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63A00
NOV 2, 2022 9:03 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 PREMIUM 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
NOV 2, 2022 9:03 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
FEB 6, 2007
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
NOV 2, 2022 9:03 AM
CSLD PROBABLITY OF DETECTION
I61400
NOV 2, 2022 9:03 AM
CSLD CLIMATE FACTOR
I61600
NOV 2, 2022 9:03 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 PREMIUM IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
NOV 2, 2022 9:03 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED
2 PREMIUM DISABLED
3 DIESEL DISABLED
4 DISABLED
I61B00
NOV 2, 2022 9:03 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
NOV 2, 2022 9:03 AM
CSLD REPORT ONLY
I62B00
NOV 2, 2022 9:03 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 PREMIUM ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
NOV 2, 2022 9:03 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
NOV 2, 2022 9:03 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 PREMIUM 0
3 DIESEL 0
4 0
I63500
NOV 2, 2022 9:03 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63900
NOV 2, 2022 9:03 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 PREMIUM
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
NOV 2, 2022 9:03 AM
I77700
NOV 2, 2022 9:03 AM
I77800
NOV 2, 2022 9:03 AM
I78C00
NOV 2, 2022 9:03 AM
I78300
NOV 2, 2022 9:03 AM
I78F00
NOV 2, 2022 9:03 AM
I78700
NOV 2, 2022 9:03 AM
I70200
NOV 2, 2022 9:03 AM
LIQUID LABEL
DEVICE LABEL
1 UNL STP
2 UNL FILL
3 UNL ANN
4 PNL STP
5 PNL FILL
6 PNL ANN
7 DSL STP
8 DSL FILL
9 DSL ANN
10 DISP 1-2
11 DISP 3-4
12 DISP 5-6
13 DISP 7-8
14
15
16
I70300
NOV 2, 2022 9:03 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL STP TRI-STATE (SINGLE FLOAT)
2 UNL FILL TRI-STATE (SINGLE FLOAT)
3 UNL ANN DUAL POINT HYDROSTATIC
4 PNL STP TRI-STATE (SINGLE FLOAT)
5 PNL FILL TRI-STATE (SINGLE FLOAT)
6 PNL ANN DUAL POINT HYDROSTATIC
7 DSL STP TRI-STATE (SINGLE FLOAT)
8 DSL FILL TRI-STATE (SINGLE FLOAT)
9 DSL ANN DUAL POINT HYDROSTATIC
10 DISP 1-2 TRI-STATE (SINGLE FLOAT)
11 DISP 3-4 TRI-STATE (SINGLE FLOAT)
12 DISP 5-6 TRI-STATE (SINGLE FLOAT)
13 DISP 7-8 TRI-STATE (SINGLE FLOAT)
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
NOV 2, 2022 9:03 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL STP STP SUMP
2 UNL FILL PIPING SUMP
3 UNL ANN ANNULAR SPACE
4 PNL STP STP SUMP
5 PNL FILL PIPING SUMP
6 PNL ANN ANNULAR SPACE
7 DSL STP STP SUMP
8 DSL FILL PIPING SUMP
9 DSL ANN ANNULAR SPACE
10 DISP 1-2 DISPENSER PAN
11 DISP 3-4 DISPENSER PAN
12 DISP 5-6 DISPENSER PAN
13 DISP 7-8 DISPENSER PAN
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
NOV 2, 2022 9:03 AM
I74300
NOV 2, 2022 9:03 AM
I74400
NOV 2, 2022 9:03 AM
I74700
NOV 2, 2022 9:03 AM
I74800
NOV 2, 2022 9:03 AM
I74900
NOV 2, 2022 9:03 AM
I7BC00
NOV 2, 2022 9:03 AM
I80200
NOV 2, 2022 9:03 AM
I80300
NOV 2, 2022 9:03 AM
I80400
NOV 2, 2022 9:03 AM
I80700
NOV 2, 2022 9:03 AM
RELAY LABEL
DEVICE LABEL
1 POS SHUT DOWN
2 OVERFILL ALARM
3
4
I80900
NOV 2, 2022 9:03 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 POS SHUT DOWN NORMALLY CLOSED
2 OVERFILL ALARM NORMALLY OPEN
3 NORMALLY OPEN
4 NORMALLY OPEN
I80B00
NOV 2, 2022 9:03 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 POS SHUT DOWN 1
2 OVERFILL ALARM NONE
3 NONE
4 NONE
I80A00
NOV 2, 2022 9:03 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 POS SHUT DOWN STANDARD
2 OVERFILL ALARM STANDARD
3 STANDARD
4 STANDARD
I80C00
NOV 2, 2022 9:03 AM
I80800
NOV 2, 2022 9:03 AM
RELAY SETUP REPORT
R 1:POS SHUT DOWN
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 4:FUEL ALARM
L 7:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L 1:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 1:SHORT ALARM
L 4:SHORT ALARM
L 7:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 3:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
NOV 2, 2022 9:04 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
NOV 2, 2022 9:04 AM
I72300
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 PS 1-2 VAPOR PRESSURE
02 FM 1-2 AIR FLOW METER
03 FM 3-4 AIR FLOW METER
04 F-M 5-6 AIR FLOW METER
05 FM 7-8 AIR FLOW METER
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
VAPOR PROCESSOR TYPE
NONE
IV4700
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
ACCEPT HIGH ORVR: YES
IV4A00
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 33 01 01 01 BLEND3
02 34 02 01 01 BLEND3
03 35 03 02 01 BLEND3
04 00 04 02 01 BLEND3
05 01 05 03 01 BLEND3
06 02 06 03 01 BLEND3
07 03 07 04 01 BLEND3
08 04 08 04 01 BLEND3
IV4B00
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
00 02 02/04 03/04 09/04 xx/xx
01 03 02/05 03/05 09/05 xx/xx
02 03 02/06 03/06 09/06 xx/xx
03 04 02/07 03/07 09/07 xx/xx
04 04 02/08 03/08 09/08 xx/xx
33 01 02/01 03/01 09/01 xx/xx
34 01 02/02 03/02 09/02 xx/xx
35 02 02/03 03/03 09/03 xx/xx
IV4900
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
NOV 2, 2022 9:04 AM
ISD VERSION: 01.07
Jaco 3362 Alarm History
Responses Received:
I10200
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39650 39484
2 4 PROBE / G.T. 164808 164532
3 INTERSTITIAL BD 202695 202450
4 INTERSTITIAL BD 202877 202473
5 UNUSED 10023974 9975248
6 UNUSED 10003811 9955156
7 UNUSED 9999355 9956455
8 UNUSED 10000403 9954694
9 UNUSED 9995811 9946386
10 RELAY BOARD 14992 14992
11 UNUSED 10000180 9954792
12 UNUSED 9998170 9958643
13 UNUSED 9999372 9947794
14 UNUSED 9991508 9950853
15 UNUSED 9998345 9954858
16 UNUSED 9995178 9952459
COMM 1 RS232 SERIAL BD 14992 15014
COMM 2 RS232 SERIAL BD 15102 15103
COMM 3 ELEC DISP INT. 101715 101687
COMM 4 UNUSED 10002059 9959831
COMM 5 UNUSED 9996204 9953824
COMM 6 UNUSED 9995483 9952041
I90200
NOV 2, 2022 9:04 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 2 PIPE UNL FILL FUEL ALARM CLEAR 10-12-22 9:41AM
L 2 PIPE UNL FILL FUEL ALARM ALARM 10-09-22 5:46PM
T 2 TANK PREMIUM OVERFILL ALARM CLEAR 10-03-22 4:35PM
T 2 TANK PREMIUM OVERFILL ALARM ALARM 10-03-22 4:31PM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 8-31-22 4:43PM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 8-31-22 4:39PM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 8-31-22 4:39PM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 8-31-22 4:38PM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-31-22 11:36AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-31-22 11:22AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-31-22 11:20AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-31-22 11:20AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-31-22 10:31AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-31-22 10:31AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-31-22 9:34AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-30-22 11:33PM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-30-22 9:27PM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-30-22 9:26PM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-30-22 8:49PM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-30-22 8:38PM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-30-22 9:54AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-30-22 5:59AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-30-22 5:47AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-30-22 5:47AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-29-22 9:22AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-29-22 9:22AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-29-22 9:22AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-29-22 9:21AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-29-22 9:17AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-29-22 9:17AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-29-22 9:17AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-29-22 9:17AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-29-22 8:40AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-29-22 8:40AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-29-22 8:31AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-29-22 8:31AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-29-22 6:42AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-29-22 6:42AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-28-22 2:39AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-28-22 2:39AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-27-22 6:20AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-27-22 6:20AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-26-22 8:21AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-26-22 8:21AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-26-22 8:16AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-26-22 8:14AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-26-22 8:13AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-26-22 8:11AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM CLEAR 8-26-22 8:09AM
L 9 ANNULAR DSL ANN HIGH LIQUID ALARM ALARM 8-26-22 8:09AM
I11200
NOV 2, 2022 9:04 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 10-31-22 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 10-28-22 4:07PM
OTHER ISD GROSS PRES WARN ALARM 10-28-22 10:01AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 10-28-22 10:00AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 10-27-22 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 10-27-22 10:00AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 10-26-22 11:17AM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 10-26-22 10:21AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 10-26-22 10:01AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 10-26-22 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 10-26-22 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 10-25-22 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 10-25-22 10:01AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 10-23-22 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 10-21-22 10:42AM
OTHER ISD GROSS PRES WARN ALARM 10-21-22 10:02AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 10-17-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 10-16-22 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 10-14-22 2:47PM
OTHER ISD GROSS PRES WARN ALARM 10-14-22 10:01AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 10-05-22 12:16PM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 10-05-22 10:45AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 10-03-22 10:00AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 9-30-22 10:01AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 9-28-22 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 9-27-22 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 9-26-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 9-25-22 10:01AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 9-22-22 12:10PM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 9-22-22 12:04PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 9-17-22 10:00AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 9-16-22 10:10PM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 9-16-22 6:45PM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 9-15-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 9-14-22 10:01AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 9-13-22 4:29PM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 9-13-22 3:48PM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 9-11-22 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 9-11-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 9-09-22 10:01AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 9-03-22 10:34AM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 9-03-22 9:51AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 8-31-22 4:45PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 8-29-22 10:01AM
SYSTEM PRINTER ERROR CLEAR 8-27-22 5:48PM
SYSTEM PAPER OUT CLEAR 8-27-22 5:48PM
SYSTEM PRINTER ERROR ALARM 8-27-22 5:48PM
SYSTEM PAPER OUT ALARM 8-27-22 5:48PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 8-24-22 11:51AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 8-24-22 10:01AM
I20600
NOV 2, 2022 9:05 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUL 5, 2022 5:17 PM
INVALID FUEL LEVEL OCT 26, 2022 10:21 AM
OCT 5, 2022 10:45 AM
SEP 22, 2022 12:04 PM
TANK 2 PREMIUM
OVERFILL ALARM OCT 3, 2022 4:31 PM
TANK 3 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
NOV 2, 2022 9:05 AM
I30200
NOV 2, 2022 9:05 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL STP
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 1:01 PM FUEL ALARM
JUL 23, 2022 4:48 AM FUEL ALARM
2 UNL FILL
OCT 9, 2022 5:46 PM FUEL ALARM
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 12:54 PM FUEL ALARM
3 UNL ANN
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 12:51 PM HIGH LIQUID ALARM
AUG 3, 2022 12:50 PM LOW LIQUID ALARM
4 PNL STP
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 1:02 PM FUEL ALARM
JUN 21, 2022 9:41 AM FUEL ALARM
5 PNL FILL
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 12:56 PM FUEL ALARM
JUN 21, 2022 9:38 AM SENSOR OUT ALARM
6 PNL ANN
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
JUN 21, 2022 9:38 AM SENSOR OUT ALARM
JUN 21, 2022 9:13 AM LOW LIQUID ALARM
7 DSL STP
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 12:58 PM FUEL ALARM
JUL 13, 2022 10:09 PM FUEL ALARM
8 DSL FILL
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 12:56 PM FUEL ALARM
JUN 21, 2022 9:38 AM SENSOR OUT ALARM
9 DSL ANN
AUG 31, 2022 4:39 PM LOW LIQUID ALARM
AUG 31, 2022 4:38 PM LOW LIQUID ALARM
AUG 31, 2022 11:22 AM HIGH LIQUID ALARM
10 DISP 1-2
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 1:05 PM FUEL ALARM
JUN 21, 2022 9:38 AM SENSOR OUT ALARM
11 DISP 3-4
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 1:03 PM FUEL ALARM
JUN 21, 2022 9:38 AM SENSOR OUT ALARM
12 DISP 5-6
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 1:04 PM FUEL ALARM
AUG 3, 2022 1:04 PM FUEL ALARM
13 DISP 7-8
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
AUG 3, 2022 1:04 PM FUEL ALARM
JUN 21, 2022 9:38 AM SENSOR OUT ALARM
I31600
NOV 2, 2022 9:05 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 1-2
2 FM 1-2
3 FM 3-4
4 F-M 5-6
5 FM 7-8
I40200
NOV 2, 2022 9:05 AM
I40300
NOV 2, 2022 9:05 AM
I34200
NOV 2, 2022 9:05 AM
I34700
NOV 2, 2022 9:05 AM
IV0100
NOV 2, 2022 9:05 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-11-01 10:01:10 A/L RATIO DEGRADATION FP 8 BLEND3 0.76
22-11-01 10:01:10 A/L RATIO DEGRADATION FP 2 BLEND3 1.42
22-10-31 10:01:18 A/L RATIO DEGRADATION FP 8 BLEND3 0.77
22-10-31 10:01:18 A/L RATIO DEGRADATION FP 2 BLEND3 1.44
22-10-30 10:01:24 A/L RATIO DEGRADATION FP 2 BLEND3 1.43
22-10-29 10:01:29 A/L RATIO DEGRADATION FP 2 BLEND3 1.46
22-10-28 10:01:29 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.59
22-10-28 10:01:29 A/L RATIO DEGRADATION FP 2 BLEND3 1.43
22-10-27 10:01:32 A/L RATIO DEGRADATION FP 8 BLEND3 0.77
22-10-27 10:01:32 A/L RATIO DEGRADATION FP 2 BLEND3 1.39
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
21-06-20 10:01:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
21-05-31 10:01:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
21-05-31 10:01:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
21-03-31 10:01:34 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.75
19-09-26 10:01:23 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-09-05 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
19-07-13 09:22:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
19-03-06 09:54:16 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
19-03-06 09:54:16 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
19-01-12 09:24:35 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-10-29 10:01:29 READINESS ISD:PP EVR:PP ISD & EVR READY
22-10-28 16:07:22 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-10-28 10:01:29 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
22-10-28 07:18:46 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-10-28 07:18:46 ISD STARTUP
22-10-28 07:17:55 ISD SHUTDOWN
22-10-21 10:42:03 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-10-14 14:47:01 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-09-26 10:01:11 READINESS ISD:PP EVR:PP ISD & EVR READY
22-09-25 10:58:24 READINESS ISD:PP EVR:NN EVR READINESS PENDING
Jaco 3362 Alarm History After
Responses Received:
I10200
NOV 2, 2022 11:16 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39650 39540
2 4 PROBE / G.T. 164808 164591
3 INTERSTITIAL BD 202695 202447
4 INTERSTITIAL BD 202877 202724
5 UNUSED 10023974 9948728
6 UNUSED 10003811 9944316
7 UNUSED 9999355 9939949
8 UNUSED 10000403 9942654
9 UNUSED 9995811 9935828
10 RELAY BOARD 14992 14992
11 UNUSED 10000180 9947134
12 UNUSED 9998170 9937402
13 UNUSED 9999372 9940239
14 UNUSED 9991508 9937734
15 UNUSED 9998345 9942456
16 UNUSED 9995178 9939752
COMM 1 RS232 SERIAL BD 14992 15014
COMM 2 RS232 SERIAL BD 15102 15125
COMM 3 ELEC DISP INT. 101715 101793
COMM 4 UNUSED 10002059 9946934
COMM 5 UNUSED 9996204 9940328
COMM 6 UNUSED 9995483 9944917
I90200
NOV 2, 2022 11:16 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
NOV 2, 2022 11:16 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 8 PIPE DSL FILL FUEL ALARM CLEAR 11-02-22 10:50AM
L 8 PIPE DSL FILL FUEL ALARM ALARM 11-02-22 10:50AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT FAIL CLEAR 11-02-22 10:04AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT FAIL ALARM 11-02-22 10:01AM
L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L 8 PIPE DSL FILL SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L 7 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L 4 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L 3 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L 5 PIPE PNL FILL SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L12 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L11 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L10 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L13 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L 9 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 11-02-22 9:43AM
L10 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 11-02-22 9:43AM
L12 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 11-02-22 9:43AM
L11 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 11-02-22 9:43AM
L 9 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 11-02-22 9:43AM
L 8 PIPE DSL FILL SENSOR OUT ALARM ALARM 11-02-22 9:43AM
L 7 STP SUMP DSL STP SENSOR OUT ALARM ALARM 11-02-22 9:43AM
L13 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 11-02-22 9:43AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 11-02-22 9:42AM
L 4 STP SUMP PNL STP SENSOR OUT ALARM ALARM 11-02-22 9:42AM
L 3 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 11-02-22 9:42AM
L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 11-02-22 9:42AM
L 5 PIPE PNL FILL SENSOR OUT ALARM ALARM 11-02-22 9:42AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 11-02-22 9:42AM
L13 DISP PAN DISP 7-8 FUEL ALARM CLEAR 11-02-22 9:38AM
L13 DISP PAN DISP 7-8 FUEL ALARM ALARM 11-02-22 9:38AM
L11 DISP PAN DISP 3-4 FUEL ALARM CLEAR 11-02-22 9:37AM
L11 DISP PAN DISP 3-4 FUEL ALARM ALARM 11-02-22 9:37AM
L10 DISP PAN DISP 1-2 FUEL ALARM CLEAR 11-02-22 9:37AM
L10 DISP PAN DISP 1-2 FUEL ALARM ALARM 11-02-22 9:36AM
L12 DISP PAN DISP 5-6 FUEL ALARM CLEAR 11-02-22 9:36AM
L12 DISP PAN DISP 5-6 FUEL ALARM ALARM 11-02-22 9:35AM
L 3 ANNULAR UNL ANN LOW LIQUID ALARM CLEAR 11-02-22 9:35AM
L 3 ANNULAR UNL ANN LOW LIQUID ALARM ALARM 11-02-22 9:35AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM CLEAR 11-02-22 9:35AM
L 3 ANNULAR UNL ANN LOW LIQUID ALARM CLEAR 11-02-22 9:34AM
L 3 ANNULAR UNL ANN HIGH LIQUID ALARM ALARM 11-02-22 9:34AM
L 3 ANNULAR UNL ANN LOW LIQUID ALARM ALARM 11-02-22 9:34AM
L 6 ANNULAR PNL ANN HIGH LIQUID ALARM CLEAR 11-02-22 9:34AM
L 6 ANNULAR PNL ANN LOW LIQUID ALARM CLEAR 11-02-22 9:34AM
L 6 ANNULAR PNL ANN HIGH LIQUID ALARM ALARM 11-02-22 9:34AM
L 6 ANNULAR PNL ANN LOW LIQUID ALARM ALARM 11-02-22 9:34AM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM CLEAR 11-02-22 9:33AM
L 9 ANNULAR DSL ANN LOW LIQUID ALARM ALARM 11-02-22 9:33AM
I11200
NOV 2, 2022 11:16 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 11-02-22 10:04AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-02-22 10:00AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 10-31-22 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 10-28-22 4:07PM
OTHER ISD GROSS PRES WARN ALARM 10-28-22 10:01AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 10-28-22 10:00AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 10-27-22 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 10-27-22 10:00AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 10-26-22 11:17AM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 10-26-22 10:21AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 10-26-22 10:01AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 10-26-22 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 10-26-22 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 10-25-22 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 10-25-22 10:01AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 10-23-22 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 10-21-22 10:42AM
OTHER ISD GROSS PRES WARN ALARM 10-21-22 10:02AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 10-17-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 10-16-22 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 10-14-22 2:47PM
OTHER ISD GROSS PRES WARN ALARM 10-14-22 10:01AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 10-05-22 12:16PM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 10-05-22 10:45AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 10-03-22 10:00AM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 9-30-22 10:01AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN CLEAR 9-28-22 10:00AM
h 7 OTHER FP7: BLEND3 DEGRD COLLECT WARN ALARM 9-27-22 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 9-26-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 9-25-22 10:01AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 9-22-22 12:10PM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 9-22-22 12:04PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 9-17-22 10:00AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 9-16-22 10:10PM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 9-16-22 6:45PM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 9-15-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 9-14-22 10:01AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 9-13-22 4:29PM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 9-13-22 3:48PM
h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 9-11-22 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 9-11-22 10:00AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 9-09-22 10:01AM
T 1 TANK UNLEADED INVALID FUEL LEVEL CLEAR 9-03-22 10:34AM
T 1 TANK UNLEADED INVALID FUEL LEVEL ALARM 9-03-22 9:51AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 8-31-22 4:45PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 8-29-22 10:01AM
SYSTEM PRINTER ERROR CLEAR 8-27-22 5:48PM
SYSTEM PAPER OUT CLEAR 8-27-22 5:48PM
SYSTEM PRINTER ERROR ALARM 8-27-22 5:48PM
SYSTEM PAPER OUT ALARM 8-27-22 5:48PM
I20600
NOV 2, 2022 11:16 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUL 5, 2022 5:17 PM
INVALID FUEL LEVEL OCT 26, 2022 10:21 AM
OCT 5, 2022 10:45 AM
SEP 22, 2022 12:04 PM
TANK 2 PREMIUM
OVERFILL ALARM OCT 3, 2022 4:31 PM
TANK 3 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
NOV 2, 2022 11:16 AM
I30200
NOV 2, 2022 11:16 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL STP
NOV 2, 2022 9:42 AM SENSOR OUT ALARM
NOV 2, 2022 9:30 AM FUEL ALARM
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
2 UNL FILL
NOV 2, 2022 9:42 AM SENSOR OUT ALARM
NOV 2, 2022 9:31 AM FUEL ALARM
OCT 9, 2022 5:46 PM FUEL ALARM
3 UNL ANN
NOV 2, 2022 9:42 AM SENSOR OUT ALARM
NOV 2, 2022 9:35 AM LOW LIQUID ALARM
NOV 2, 2022 9:34 AM HIGH LIQUID ALARM
4 PNL STP
NOV 2, 2022 9:42 AM SENSOR OUT ALARM
NOV 2, 2022 9:30 AM FUEL ALARM
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
5 PNL FILL
NOV 2, 2022 9:42 AM SENSOR OUT ALARM
NOV 2, 2022 9:31 AM FUEL ALARM
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
6 PNL ANN
NOV 2, 2022 9:42 AM SENSOR OUT ALARM
NOV 2, 2022 9:34 AM HIGH LIQUID ALARM
NOV 2, 2022 9:34 AM LOW LIQUID ALARM
7 DSL STP
NOV 2, 2022 9:43 AM SENSOR OUT ALARM
NOV 2, 2022 9:28 AM FUEL ALARM
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
8 DSL FILL
NOV 2, 2022 10:50 AM FUEL ALARM
NOV 2, 2022 9:43 AM SENSOR OUT ALARM
NOV 2, 2022 9:32 AM FUEL ALARM
9 DSL ANN
NOV 2, 2022 9:43 AM SENSOR OUT ALARM
NOV 2, 2022 9:33 AM LOW LIQUID ALARM
NOV 2, 2022 9:33 AM HIGH LIQUID ALARM
10 DISP 1-2
NOV 2, 2022 9:43 AM SENSOR OUT ALARM
NOV 2, 2022 9:36 AM FUEL ALARM
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
11 DISP 3-4
NOV 2, 2022 9:43 AM SENSOR OUT ALARM
NOV 2, 2022 9:37 AM FUEL ALARM
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
12 DISP 5-6
NOV 2, 2022 9:43 AM SENSOR OUT ALARM
NOV 2, 2022 9:35 AM FUEL ALARM
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
13 DISP 7-8
NOV 2, 2022 9:43 AM SENSOR OUT ALARM
NOV 2, 2022 9:38 AM FUEL ALARM
AUG 3, 2022 1:10 PM SENSOR OUT ALARM
I31600
NOV 2, 2022 11:16 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 1-2
2 FM 1-2
3 FM 3-4
4 F-M 5-6
5 FM 7-8
I40200
NOV 2, 2022 11:16 AM
I40300
NOV 2, 2022 11:16 AM
I34200
NOV 2, 2022 11:16 AM
I34700
NOV 2, 2022 11:16 AM
IV0100
NOV 2, 2022 11:16 AM
FASTRIP 3362
6401 S H ST
BAKERSFIELD,CA93304
661-831-4709
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :FAIL EVR VAPOR COLLECTION :FAIL
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-11-02 10:01:09 A/L RATIO DEGRADATION FP 8 BLEND3 0.78
22-11-01 10:01:10 A/L RATIO DEGRADATION FP 8 BLEND3 0.76
22-11-01 10:01:10 A/L RATIO DEGRADATION FP 2 BLEND3 1.42
22-10-31 10:01:18 A/L RATIO DEGRADATION FP 8 BLEND3 0.77
22-10-31 10:01:18 A/L RATIO DEGRADATION FP 2 BLEND3 1.44
22-10-30 10:01:24 A/L RATIO DEGRADATION FP 2 BLEND3 1.43
22-10-29 10:01:29 A/L RATIO DEGRADATION FP 2 BLEND3 1.46
22-10-28 10:01:29 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.59
22-10-28 10:01:29 A/L RATIO DEGRADATION FP 2 BLEND3 1.43
22-10-27 10:01:32 A/L RATIO DEGRADATION FP 8 BLEND3 0.77
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-11-02 10:01:09 A/L RATIO DEGRADATION FP 2 BLEND3 1.43
21-06-20 10:01:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
21-05-31 10:01:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
21-05-31 10:01:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
21-03-31 10:01:34 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.75
19-09-26 10:01:23 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
19-09-05 10:01:09 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
19-07-13 09:22:09 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
19-03-06 09:54:16 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
19-03-06 09:54:16 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-11-02 10:04:59 COLLECTION TEST HH08 GRADE TEST MANUALLY CLEARED
22-11-02 10:04:52 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
22-11-02 10:04:18 PUMPS MANUALLY RE-ENABLED
22-11-02 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY
22-11-02 10:01:09 A/L RATIO GROSS DEGRADATION DISABLED FP 02 BLEND3
22-11-02 09:42:01 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-11-02 09:42:01 ISD STARTUP
22-11-02 09:41:22 ISD SHUTDOWN
22-10-29 10:01:29 READINESS ISD:PP EVR:PP ISD & EVR READY
22-10-28 16:07:22 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED