Loading...
HomeMy WebLinkAboutLINE TEST 2022 - DIESEL1ZHVWFR//& =HXV&RXUW%DNHUVILHOG&$ 800-339-9930 or 661-631-3870 FINAL TEST RESULTS ALERT 1000 / ALERT 1050 / TEI LT-3 / VMI LDT-890 CUSTOMER ADDRESS: WORK ORDER: SITE ADDRESS: TEST DATE: SITE CONTACT: PHONE: TECHNICIAN: PHONE: LICENSE: WATER IN BACKFILL: DATE & TIME OF LAST FUEL DELIVERY: ____________________________________________________________________________ TANK INFORMATION: (WETTED)TANK 1 TANK 2 TANK 3 TANK 4 PRODUCT TYPE: TOTAL GALLONS: PRODUCT LEVEL: PERCENT FULL: TEST METHOD: WATER IN TANK: TANK MATERIAL: P.S.I. @ BOTTOM: TEST DURATION: FINAL LEAK RATE: TEST RESULT: TANK INFORMATION (ULLAGE) U/F ONLY ALERT 1050X ALERT 1050X ALERT 1050X ALERT 1050X ULLAGE GALLONS: START PRESSURE: END PRESSURE: TEST RESULT: PRODUCT LINES: TEI LT-3 TEI LT-3 TEI LT-3 TEI LT-3 LINE TYPE: START TIME: END TIME: TEST PRESSURE: FINAL LEAK RATE: TEST RESULT: MECHNICAL LINE LEAK DETECTORS:VMI LDT-890 VMI LDT-890 VMI LDT-890 VMI LDT-890 MODEL: SERIAL NUMBER: CHECK VALVE PSI: BLEED OFF ml: LEAK RATE TESTED: TEST RESULT: A) These systems and methods meet or exceed the criteria in USEPA 40CFR parts 280, NFPA 329-87 and all applicable state codes. B) Any failure listed above may require further action, check with all regulatory agencies. TECHNICIAN SIGNATURE: DATE: MANUFACTURER CERTIFICATION NO: Jaco Oil P.O. Box 82515 Bakersfield, CA 93380-2515 128515 11/09/2022 Jaco #7776 Howard's Market 3300 Planz Road Bakersfield, CA 93309 Omero Garcia (661)393-7000 Bryan Self (800)339-9930 11-1756 0.00"24 Hours + Diesel Pressuer 2:00 PM 2:15 PM 65 PSI 0.002 Pass 11/09/2022 TMI-146