HomeMy WebLinkAboutFMC 2022Appendix VI Underground Storage Tank  Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION Installation Repair 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3.TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4.CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages Underground Storage Tank  Monitoring System Certification Form Page 2 of 6 5.MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; Monitoring System Set-up Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? Secondary containment systems are free of damage, debris, or liquid? Are the audible and visual alarms operational? All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? The monitoring system set-up was reviewed, and proper settings confirmed? Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) Sump UDC If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Underground Storage Tank  Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Underground Storage Tank  Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) 3 GPH 0.1 GPH 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? For electronic LLDs, does the turbine automatically shut off when a release is detected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? Were all items on the equipment manufacturer’s maintenance checklist completed? Were all LLDs confirmed operational within regulatory requirements? LLD ID LLD Model Lines Monitored Pass Fail Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Underground Storage Tank  Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING Check this box if tank gauging is used only for inventory control. Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? Was accuracy of system’s product level readings tested? Was accuracy of system’s water level readings tested? Were all probes reinstalled properly? Were all items on the equipment manufacturer’s maintenance checklist completed? Probe ID Probe Model Tanks Monitored Pass Fail 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ☐ Installation ☐ Repair ☐ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ☐ Manufacturer ☐ Industry Standard ☐ Professional Engineer Test Type ☐ Pressure ☐ Vacuum ☐ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other Is the spill container minimum capacity five gallons excluding riser volume? ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* Method to keep spill container empty ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other Spill Container Test Results ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other ☐ Nonmetallic ☐ Other Is the spill container minimum capacity five gallons excluding riser volume? ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* ☐ Yes ☐ No* Method to keep spill container empty ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other ☐ Drain ☐ Pump ☐ Other Spill Container Test Results ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail ☐ Pass ☐ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. SHEAR VALVE OPERATION INSPECTION Facility Name: Owner Address: Address City, State, Zip Code: City, State, Zip Code: Facility I.D. #:Owner Phone #: Testing Company: Phone #: This data sheet is for inspecting shear valves located inside dispensers. See PEI/RP1200 Section 10 for the inspection procedure. Product Grade Dispenser ID# Shear ValveType (Product/Vapor) 1. Is the shear valve rigidly anchored to the dispenser box frame or dispenser island? Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No 2. Is the shear section posi- tioned between ½ inch above or below the top surface of the dispenser island? Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No 3. Is the lever arm free to move?Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA 4.Does the lever arm snap the the poppet valve shut? Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA 5. Can any product be dispensed when the product shear valve is closed? Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA Yes No NA A “No” to Lines 1-4 or a “Yes” for Line 5 indicates a test failure. Test Results Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Pass Fail Comments: Tester’s Name (print) Tester’s Signature Reference PEI/RP1200-19 Appendix C-10 Date: Latest Version 3/14/2022 <I20100NOV 17, 2022 8:32 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 IN-TANK INVENTORY TANK PRODUCT VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP 1 87 UNLEADED 9710 9659 11857 55.16 0.64 67.51 2 91 PREMIUM 5789 5738 2742 76.77 0.00 72.51 3 DIESEL 4424 4420 15527 33.31 0.00 82.27 ><I90500NOV 17, 2022 8:32 AMSOFTWARE REVISION LEVELVERSION 335.00SOFTWARE# 346335-100-A CREATED - 18.08.27.10.22 S-MODULE# 330160-004-aSYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM ><I50201NOV 17, 2022 8:32 AM SHIFT TIME 1 : 1:00 AM ><I50202NOV 17, 2022 8:32 AM SHIFT TIME 2 : DISABLED ><I50203NOV 17, 2022 8:32 AM SHIFT TIME 3 : DISABLED > <I50204NOV 17, 2022 8:32 AM SHIFT TIME 4 : DISABLED ><I54600NOV 17, 2022 8:32 AM TANK PER TST NEEDED WRN: DISABLED ><I54900NOV 17, 2022 8:32 AM TANK ANN TST NEEDED WRN: DISABLED ><I55300NOV 17, 2022 8:32 AM LINE RE-ENABLE METHODALARM ACKNOWLEDGE ><I55600NOV 17, 2022 8:32 AM LINE PER TST NEEDED WRN: DISABLED ><I55900NOV 17, 2022 8:32 AM LINE ANN TST NEEDED WRN: DISABLED ><I51400NOV 17, 2022 8:32 AM H-PROTOCOL DATA FORMATHEIGHT ><I51A01NOV 17, 2022 8:32 AM DAYLIGHT SAVING TIMEENABLED OFF > <I51B00 NOV 17, 2022 8:32 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM >< I51600NOV 17, 2022 8:32 AM RE-DIRECT LOCAL PRINTOUT DISABLED >< I50400NOV 17, 2022 8:32 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED >< I21900NOV 17, 2022 8:33 AM TANK CHART SECURITY DISABLED >< I5BD00NOV 17, 2022 8:33 AM CUSTOM ALARM LABELS DISABLED ><I56000NOV 17, 2022 8:33 AM MASS/DENSITY DISABLED ><I88101NOV 17, 2022 8:33 AMPORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : ODD STOP BIT : 2 STOP DATA LENGTH: 7 DATARS-232 SECURITYCODE : DISABLED ><I88102NOV 17, 2022 8:33 AMPORT SETTINGS: COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATARS-232 SECURITYCODE : DISABLED DTR NORMAL STATE: HIGH ><I88103NOV 17, 2022 8:33 AMPORT SETTINGS: COMM BOARD : 3 (EDIM )RS-232 SECURITYCODE : DISABLED >< I60100 NOV 17, 2022 8:33 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 87 UNLEADED ON 2 91 PREMIUM ON 3 DIESEL ON 4 OFF >< I60200NOV 17, 2022 8:33 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 87 UNLEADED 2 91 PREMIUM 3 DIESEL 4 >< I60300NOV 17, 2022 8:33 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 87 UNLEADED 1 2 91 PREMIUM 2 3 DIESEL 3 4 4 >< I60900NOV 17, 2022 8:33 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 87 UNLEADED 0.000700 2 91 PREMIUM 0.000700 3 DIESEL 0.000045 4 0.000000 >< I60700NOV 17, 2022 8:33 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 87 UNLEADED 120.00 2 91 PREMIUM 120.00 3 DIESEL 120.00 4 0.00><I60A00NOV 17, 2022 8:33 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 87 UNLEADED 4 PTS 21567 2 91 PREMIUM 4 PTS 8531 3 DIESEL 4 PTS 19951 4 1 PT 0 ><I60400NOV 17, 2022 8:33 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 21567 2 91 PREMIUM 8531 3 DIESEL 19951 4 0><I60500NOV 17, 2022 8:33 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 21567 17567 10858 4125 2 91 PREMIUM 8531 6888 4294 1692 3 DIESEL 19951 16262 10044 3804 4 0 0 0 0 ><I60600NOV 17, 2022 8:33 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 21567 0 0 0 0 17567 0 0 0 0 10858 0 0 0 0 4125 0 0 0 0 2 91 PREMIUM 8531 0 0 0 0 6888 0 0 0 0 4294 0 0 0 0 1692 0 0 0 0 3 DIESEL 19951 0 0 0 0 16262 0 0 0 0 10044 0 0 0 0 3804 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 >< I61500NOV 17, 2022 8:33 AM TANK PRODUCT LABEL METER DATA 1 87 UNLEADED NO 2 91 PREMIUM NO 3 DIESEL NO 4 NO > <I62F00 NOV 17, 2022 8:33 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 87 UNLEADED 4.0 IN. 2 91 PREMIUM 2.0 IN. 3 DIESEL 4.0 IN. > <I62700 NOV 17, 2022 8:33 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 87 UNLEADED 1.5 2 91 PREMIUM 1.5 3 DIESEL 1.5><I64200NOV 17, 2022 8:34 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 87 UNLEADED LOW 2 91 PREMIUM LOW 3 DIESEL LOW ><I62400NOV 17, 2022 8:34 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 87 UNLEADED 2.0 2 91 PREMIUM 2.0 3 DIESEL 2.0><I62800NOV 17, 2022 8:34 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 21567 2 91 PREMIUM 8531 3 DIESEL 19951 4 0><I62300NOV 17, 2022 8:34 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 19410 2 91 PREMIUM 7678 3 DIESEL 17956 4 0><I62200NOV 17, 2022 8:34 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 20489 2 91 PREMIUM 8104 3 DIESEL 18953 4 0> <I62900 NOV 17, 2022 8:34 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 2157 2 91 PREMIUM 853 3 DIESEL 1995 4 0> <I62100 NOV 17, 2022 8:34 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 1000 2 91 PREMIUM 500 3 DIESEL 1000 4 0> <I62600 NOV 17, 2022 8:34 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 99 2 91 PREMIUM 99 3 DIESEL 99 4 99> <I62500 NOV 17, 2022 8:34 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 99 2 91 PREMIUM 99 3 DIESEL 99 4 99><I60800NOV 17, 2022 8:34 AM TANK TILT TANK PRODUCT LABEL INCHES 1 87 UNLEADED 0.00 2 91 PREMIUM 0.00 3 DIESEL 0.00 4 0.00><I60B00NOV 17, 2022 8:34 AM STICK HEIGHT OFFSET ENABLE STATUSDISABLED ><I60C00NOV 17, 2022 8:34 AM TANK STICK HEIGHT OFFSETTANK PRODUCT LABEL INCHES 1 87 UNLEADED 0.00 2 91 PREMIUM 0.00 3 DIESEL 0.00 4 0.00><I61200NOV 17, 2022 8:34 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 87 UNLEADED NONE NONE 2 91 PREMIUM NONE NONE 3 DIESEL NONE NONE 4 NONE NONE ><I63600NOV 17, 2022 8:34 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 0 2 91 PREMIUM 0 3 DIESEL 0 4 0 >< I62A00NOV 17, 2022 8:34 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 0 2 91 PREMIUM 0 3 DIESEL 0 4 0 >< I62C00NOV 17, 2022 8:34 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 87 UNLEADED STANDARD 2 91 PREMIUM STANDARD 3 DIESEL STANDARD 4 STANDARD > <I62D00 NOV 17, 2022 8:34 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 87 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 91 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED > <I63100NOV 17, 2022 8:34 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 87 UNLEADED OFF OFF 2 91 PREMIUM OFF OFF 3 DIESEL OFF OFF 4 OFF OFF ><I63000NOV 17, 2022 8:34 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 87 UNLEADED OFF 2 91 PREMIUM OFF 3 DIESEL OFF 4 OFF ><I63200NOV 17, 2022 8:35 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 87 UNLEADED OFF 2 91 PREMIUM OFF 3 DIESEL OFF 4 OFF ><I61000NOV 17, 2022 8:35 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 87 UNLEADED 5 2 91 PREMIUM 5 3 DIESEL 5 4 1><I63A00NOV 17, 2022 8:35 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 87 UNLEADED 10.00% 2 91 PREMIUM 10.00% 3 DIESEL 10.00% 4 10.00% >< I61100NOV 17, 2022 8:35 AM LEAK TEST METHOD - - - - - - - - - - - -TEST ON DATE : ALL TANK AUG 27, 2018START TIME : DISABLED TEST RATE :0.20 GAL/HRDURATION : 2 HOURS TST EARLY STOP:DISABLED > <I61300 NOV 17, 2022 8:35 AMCSLD PROBABLITY OF DETECTION >< I61400NOV 17, 2022 8:35 AM CSLD CLIMATE FACTOR > <I61600 NOV 17, 2022 8:35 AM TANK PRODUCT LABEL CAL UPDATE 1 87 UNLEADED IMMEDIATE 2 91 PREMIUM IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE >< I61A00NOV 17, 2022 8:35 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 87 UNLEADED DISABLED 2 91 PREMIUM DISABLED 3 DIESEL DISABLED 4 DISABLED><I61B00NOV 17, 2022 8:35 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM ><I61C00NOV 17, 2022 8:35 AM CSLD REPORT ONLY ><I63400NOV 17, 2022 8:35 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 0 2 91 PREMIUM 0 3 DIESEL 0 4 0><I63500NOV 17, 2022 8:35 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 87 UNLEADED 1 2 91 PREMIUM 1 3 DIESEL 1 4 1><I78700NOV 17, 2022 8:35 AM >< I70200 NOV 17, 2022 8:35 AM LIQUID LABEL DEVICE LABEL 1 87 STP 2 87 FILL 3 91 STP 4 91 FILL 5 DIESEL STP 6 DIESEL FILL 7 UNLEADED ANNULAR 8 DIESEL ANNULAR 9 1-2 UDC 10 3-4 UDC 11 5-6 UDC 12 7-8 UDC 13 VENT BOX 14 15 16 >< I70300NOV 17, 2022 8:35 AM LIQUID TYPE SENSOR LOCATION TYPE 1 87 STP DW SUMP 2-1 2 87 FILL DW SUMP 2-1 3 91 STP DW SUMP 2-1 4 91 FILL DW SUMP 2-1 5 DIESEL STP DW SUMP 2-1 6 DIESEL FILL DW SUMP 2-1 7 UNLEADED ANNULAR DUAL POINT HYDROSTATIC 8 DIESEL ANNULAR DUAL POINT HYDROSTATIC 9 1-2 UDC DW SUMP 2-1 10 3-4 UDC DW SUMP 2-1 11 5-6 UDC DW SUMP 2-1 12 7-8 UDC DW SUMP 2-1 13 VENT BOX DW SUMP 2-1 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) > <I70400 NOV 17, 2022 8:35 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 87 STP STP SUMP 2 87 FILL PIPING SUMP 3 91 STP STP SUMP 4 91 FILL PIPING SUMP 5 DIESEL STP STP SUMP 6 DIESEL FILL PIPING SUMP 7 UNLEADED ANNULAR ANNULAR SPACE 8 DIESEL ANNULAR ANNULAR SPACE 9 1-2 UDC DISPENSER PAN 10 3-4 UDC DISPENSER PAN 11 5-6 UDC DISPENSER PAN 12 7-8 UDC DISPENSER PAN 13 VENT BOX OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS ><I80700NOV 17, 2022 8:35 AM RELAY LABEL DEVICE LABEL 1 87 STP 2 91 STP 3 DIESEL STP 4 TEST 5 DISP 1-2 6 DISP 3-4 7 DISP 5-6 8 DISP 7-8 9 10 11 12 OVERFILL ><I80900NOV 17, 2022 8:35 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 87 STP NORMALLY OPEN 2 91 STP NORMALLY OPEN 3 DIESEL STP NORMALLY OPEN 4 TEST NORMALLY OPEN 5 DISP 1-2 NORMALLY OPEN 6 DISP 3-4 NORMALLY OPEN 7 DISP 5-6 NORMALLY OPEN 8 DISP 7-8 NORMALLY OPEN 9 NORMALLY OPEN 10 NORMALLY OPEN 11 NORMALLY OPEN 12 OVERFILL NORMALLY OPEN ><I80B00NOV 17, 2022 8:36 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 87 STP 1 2 91 STP 2 3 DIESEL STP 3 4 TEST NONE 5 DISP 1-2 NONE 6 DISP 3-4 NONE 7 DISP 5-6 NONE 8 DISP 7-8 NONE 9 NONE 10 NONE 11 NONE 12 OVERFILL NONE ><I80A00NOV 17, 2022 8:36 AM RELAY TYPE RELAY DESIGNATION TYPE 1 87 STP PUMP CONTROL OUTPUT 2 91 STP PUMP CONTROL OUTPUT 3 DIESEL STP PUMP CONTROL OUTPUT 4 TEST STANDARD 5 DISP 1-2 STANDARD 6 DISP 3-4 STANDARD 7 DISP 5-6 STANDARD 8 DISP 7-8 STANDARD 9 STANDARD 10 STANDARD 11 STANDARD 12 OVERFILL STANDARD ><I80800NOV 17, 2022 8:36 AM RELAY SETUP REPORT R 1:87 STP TYPE: PUMP CONTROL OUTPUT TANK #: 1 IN-TANK ALARMS T 1:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:FLOW COLLECT FAIL R 2:91 STP TYPE: PUMP CONTROL OUTPUTTANK #: 2 IN-TANK ALARMS T 2:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 3:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 3:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:FLOW COLLECT FAIL R 3:DIESEL STP TYPE: PUMP CONTROL OUTPUTTANK #: 3 IN-TANK ALARMS T 3:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 5:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM R 4:TEST TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 5:DISP 1-2 TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 6:DISP 3-4 TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 7:DISP 5-6 TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 8:DISP 7-8 TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 9: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R10: TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R11: TYPE: STANDARDNORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R12:OVERFILL TYPE: STANDARDNORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ><I79000NOV 17, 2022 8:36 AM EDIM:1 VR:349643-001-B TD:97.10.27.11.25 ><I72300NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY01 87 PRODUCT VAC SENSOR02 UNKNOWN03 VAPOR RETURN VAC SENSOR04 91 PRODUCT VAC SENSOR05 ALL VENTS VAC SENSOR06 DIESEL PRODUCT VAC SENSOR07 UNKNOWN08 ATM ATM P SENSOR09 1-2 FLOWMETER AIR FLOW METER10 3-4 FLOWMETER AIR FLOW METER 11 5-6 FLOWMETER AIR FLOW METER 12 7-8 FLOWMETER AIR FLOW METER13 UNKNOWN 14 UNKNOWN15 UNKNOWN 16 PRESSURE SENSOR VAPOR PRESSURE17 UNKNOWN 18 UNKNOWN19 UNKNOWN 20 UNKNOWN21 UNKNOWN 22 UNKNOWN23 UNKNOWN 24 UNKNOWN25 UNKNOWN 26 UNKNOWN27 UNKNOWN 28 UNKNOWN29 UNKNOWN 30 UNKNOWN31 UNKNOWN 32 UNKNOWN33 UNKNOWN 34 UNKNOWN35 UNKNOWN 36 UNKNOWN37 UNKNOWN 38 UNKNOWN39 UNKNOWN 40 UNKNOWN >< IV4F00NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 NOZZLE A/L RANGEA/L RATIO: 0.95 - 1.15 > <IV4000 NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 VAPOR PROCESSOR TYPENONE ><IV4700NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 ASSESSMENT TIMESTART TIME: 9:00 AMTIME DELAY MINUTES: 1 ><IV5200NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 ACCEPT HIGH ORVR: NO ><IV4A00NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 02 BLEND3 02 02 02 01 02 BLEND3 03 03 03 02 02 BLEND3 04 04 04 02 02 BLEND3 05 05 05 03 02 BLEND3 06 06 06 03 02 BLEND3 07 07 07 04 02 BLEND3 08 08 08 04 02 BLEND3 ><IV4B00 NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H401 01 xx/xx 02/01 01/01 xx/xx 02 01 02/02 xx/xx 09/02 01/0203 02 02/03 09/03 01/03 xx/xx 04 02 02/04 01/04 09/04 xx/xx05 03 02/05 01/05 09/05 xx/xx 06 03 02/06 09/06 01/06 xx/xx07 04 02/07 01/07 09/07 xx/xx 08 04 02/08 01/08 xx/xx 09/08 >< IV4900NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 LABEL TABLEID LABEL 01 UNASSIGNED02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 > <IV1000 NOV 17, 2022 8:37 AM ISD VERSION: 01.05 >< I90200NOV 17, 2022 8:37 AM SOFTWARE REVISION LEVEL VERSION 335.00SOFTWARE# 346335-100-A CREATED - 18.08.27.10.22 S-MODULE# 330160-004-aSYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM ><I11100NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 PRIORITY ALARM HISTORYID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIMEE 1 OTHER COMMUNICATION ALARM CLEAR 11-14-22 2:12AME 1 OTHER COMMUNICATION ALARM ALARM 11-14-22 2:11AME 1 OTHER COMMUNICATION ALARM CLEAR 11-07-22 2:06AME 1 OTHER COMMUNICATION ALARM ALARM 11-07-22 2:05AME 1 OTHER COMMUNICATION ALARM CLEAR 11-05-22 6:45AME 1 OTHER COMMUNICATION ALARM ALARM 11-05-22 6:44AME 1 OTHER COMMUNICATION ALARM CLEAR 10-31-22 2:08AME 1 OTHER COMMUNICATION ALARM ALARM 10-31-22 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 10-24-22 2:07AME 1 OTHER COMMUNICATION ALARM ALARM 10-24-22 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 10-17-22 2:08AME 1 OTHER COMMUNICATION ALARM ALARM 10-17-22 2:06AME 1 OTHER COMMUNICATION ALARM CLEAR 10-10-22 2:06AME 1 OTHER COMMUNICATION ALARM ALARM 10-10-22 2:04AME 1 OTHER COMMUNICATION ALARM CLEAR 10-03-22 2:11AME 1 OTHER COMMUNICATION ALARM ALARM 10-03-22 2:09AME 1 OTHER COMMUNICATION ALARM CLEAR 9-28-22 7:53AME 1 OTHER COMMUNICATION ALARM ALARM 9-28-22 7:52AME 1 OTHER COMMUNICATION ALARM CLEAR 9-26-22 2:11AME 1 OTHER COMMUNICATION ALARM ALARM 9-26-22 2:10AME 1 OTHER COMMUNICATION ALARM CLEAR 9-19-22 2:06AME 1 OTHER COMMUNICATION ALARM ALARM 9-19-22 2:05AME 1 OTHER COMMUNICATION ALARM CLEAR 9-12-22 2:08AME 1 OTHER COMMUNICATION ALARM ALARM 9-12-22 2:07AME 1 OTHER COMMUNICATION ALARM CLEAR 9-05-22 2:11AME 1 OTHER COMMUNICATION ALARM ALARM 9-05-22 2:10AME 1 OTHER COMMUNICATION ALARM CLEAR 8-29-22 2:11AME 1 OTHER COMMUNICATION ALARM ALARM 8-29-22 2:10AME 1 OTHER COMMUNICATION ALARM CLEAR 8-22-22 2:06AME 1 OTHER COMMUNICATION ALARM ALARM 8-22-22 2:04AML13 OTHER VENT BOX LOW LIQUID ALARM CLEAR 8-15-22 12:43PML13 OTHER VENT BOX LOW LIQUID ALARM ALARM 8-15-22 12:43PM L13 OTHER VENT BOX FUEL ALARM CLEAR 8-15-22 12:43PM E 1 OTHER COMMUNICATION ALARM CLEAR 8-15-22 2:11AME 1 OTHER COMMUNICATION ALARM ALARM 8-15-22 2:10AM L13 OTHER VENT BOX FUEL ALARM ALARM 8-14-22 2:45AML13 OTHER VENT BOX LOW LIQUID ALARM CLEAR 8-14-22 2:44AM L13 OTHER VENT BOX LOW LIQUID ALARM ALARM 8-14-22 2:44AME 1 OTHER COMMUNICATION ALARM CLEAR 8-08-22 2:10AM E 1 OTHER COMMUNICATION ALARM ALARM 8-08-22 2:09AME 1 OTHER COMMUNICATION ALARM CLEAR 8-01-22 2:10AM E 1 OTHER COMMUNICATION ALARM ALARM 8-01-22 2:09AME 1 OTHER COMMUNICATION ALARM CLEAR 7-25-22 2:12AM E 1 OTHER COMMUNICATION ALARM ALARM 7-25-22 2:10AME 1 OTHER COMMUNICATION ALARM CLEAR 7-18-22 2:11AM E 1 OTHER COMMUNICATION ALARM ALARM 7-18-22 2:09AME 1 OTHER COMMUNICATION ALARM CLEAR 7-12-22 8:32AM E 1 OTHER COMMUNICATION ALARM ALARM 7-12-22 8:31AME 1 OTHER COMMUNICATION ALARM CLEAR 7-12-22 8:28AM E 1 OTHER COMMUNICATION ALARM ALARM 7-12-22 8:25AM >< I11200NOV 17, 2022 8:37 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 NON-PRIORITY ALARM HISTORYID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD GROSS PRES WARN CLEAR 10-10-22 3:56PM OTHER ISD GROSS PRES WARN ALARM 10-10-22 9:05AM OTHER ISD VAPOR LEAK WARN CLEAR 9-21-22 2:40PM SYSTEM PRINTER ERROR CLEAR 9-20-22 10:08AM SYSTEM PAPER OUT CLEAR 9-20-22 10:08AM SYSTEM PRINTER ERROR ALARM 9-20-22 10:05AM SYSTEM PAPER OUT ALARM 9-20-22 10:05AM OTHER ISD VAPOR LEAK WARN ALARM 9-15-22 9:04AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 8-22-22 3:40PMT 3 TANK DIESEL DELIVERY NEEDED ALARM 8-22-22 7:55AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 7-09-22 1:32AMT 3 TANK DIESEL DELIVERY NEEDED ALARM 7-08-22 8:33AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 7-01-22 8:29AMT 3 TANK DIESEL DELIVERY NEEDED ALARM 7-01-22 7:04AM OTHER ISD VAPOR LEAK WARN CLEAR 6-23-22 9:03AM OTHER ISD VAPOR LEAK WARN ALARM 6-16-22 9:03AM OTHER ISD VAPOR LEAK WARN CLEAR 6-10-22 8:51AM OTHER ISD VAPOR LEAK WARN ALARM 6-04-22 9:04AM OTHER ISD VAPOR LEAK WARN CLEAR 5-29-22 9:03AM OTHER ISD VAPOR LEAK WARN ALARM 5-22-22 9:04AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 5-06-22 12:34AMT 3 TANK DIESEL DELIVERY NEEDED ALARM 5-05-22 1:10PM SYSTEM PRINTER ERROR CLEAR 4-23-22 7:41AM SYSTEM PAPER OUT CLEAR 4-23-22 7:41AM SYSTEM PAPER OUT ALARM 4-23-22 7:39AM SYSTEM PRINTER ERROR ALARM 4-23-22 7:39AMT 3 TANK DIESEL DELIVERY NEEDED CLEAR 3-26-22 12:48PMT 3 TANK DIESEL DELIVERY NEEDED ALARM 3-26-22 8:38AMT 3 TANK DIESEL DELIVERY NEEDED CLEAR 1-15-22 5:19PMT 3 TANK DIESEL DELIVERY NEEDED ALARM 1-15-22 9:12AMT 3 TANK DIESEL DELIVERY NEEDED CLEAR 12-23-21 1:30PMT 3 TANK DIESEL DELIVERY NEEDED ALARM 12-22-21 8:58AM OTHER ISD VAPOR LEAK WARN CLEAR 12-16-21 3:36PM OTHER ISD VAPOR LEAK WARN ALARM 12-15-21 9:01AMT 1 TANK 87 UNLEADED LOW TEMP WARNING CLEAR 12-06-21 10:51AMT 1 TANK 87 UNLEADED LOW TEMP WARNING ALARM 12-06-21 10:50AMT 3 TANK DIESEL HIGH PRODUCT ALARM CLEAR 12-06-21 10:48AMT 3 TANK DIESEL HIGH PRODUCT ALARM ALARM 12-06-21 10:48AMT 1 TANK 87 UNLEADED HIGH PRODUCT ALARM CLEAR 12-06-21 10:47AMT 1 TANK 87 UNLEADED HIGH PRODUCT ALARM ALARM 12-06-21 10:47AMT 2 TANK 91 PREMIUM HIGH PRODUCT ALARM CLEAR 12-06-21 10:45AMT 2 TANK 91 PREMIUM HIGH PRODUCT ALARM ALARM 12-06-21 10:45AMT 1 TANK 87 UNLEADED DELIVERY NEEDED CLEAR 12-06-21 10:41AMT 1 TANK 87 UNLEADED DELIVERY NEEDED ALARM 12-06-21 10:40AM SYSTEM PRINTER ERROR CLEAR 11-29-21 5:46AM SYSTEM PAPER OUT CLEAR 11-29-21 5:46AM SYSTEM PRINTER ERROR ALARM 11-29-21 5:40AM SYSTEM PAPER OUT ALARM 11-29-21 5:40AMT 3 TANK DIESEL DELIVERY NEEDED CLEAR 11-19-21 12:11PMT 3 TANK DIESEL DELIVERY NEEDED ALARM 11-19-21 8:05AM ><I20600NOV 17, 2022 8:38 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 TANK ALARM HISTORY TANK 1 87 UNLEADED SETUP DATA WARNING OCT 9, 2019 2:20 PM HIGH WATER ALARM OCT 10, 2019 7:39 AM OVERFILL ALARM NOV 17, 2020 11:29 AM OCT 10, 2019 11:45 AM LOW PRODUCT ALARM DEC 6, 2021 10:40 AM OCT 10, 2019 7:35 AM OCT 9, 2019 2:18 PM HIGH PRODUCT ALARM DEC 6, 2021 10:47 AM NOV 17, 2020 11:29 AM OCT 10, 2019 11:54 AM PROBE OUT DEC 6, 2021 10:49 AM DEC 6, 2021 10:40 AM NOV 17, 2020 11:57 AM HIGH WATER WARNING OCT 10, 2019 7:39 AM DELIVERY NEEDED DEC 6, 2021 10:40 AM OCT 10, 2019 7:35 AM OCT 9, 2019 2:18 PM MAX PRODUCT ALARM DEC 6, 2021 10:47 AM NOV 17, 2020 11:30 AM LOW TEMP WARNING DEC 6, 2021 10:50 AM NOV 17, 2020 11:58 AM OCT 10, 2019 12:22 PM TANK 2 91 PREMIUM SETUP DATA WARNING OCT 9, 2019 2:20 PM HIGH WATER ALARM NOV 17, 2020 11:52 AM OCT 9, 2019 3:09 PM OCT 9, 2019 2:24 PM OVERFILL ALARM AUG 18, 2021 9:23 AM AUG 16, 2021 8:24 AM MAR 30, 2021 10:32 AM LOW PRODUCT ALARM NOV 17, 2020 11:22 AM OCT 9, 2019 2:40 PM SUDDEN LOSS ALARM NOV 17, 2020 11:23 AM HIGH PRODUCT ALARM DEC 6, 2021 10:45 AM NOV 17, 2020 11:49 AM OCT 9, 2019 2:18 PM PROBE OUT DEC 6, 2021 10:50 AM DEC 6, 2021 10:40 AM NOV 17, 2020 11:57 AM HIGH WATER WARNING NOV 17, 2020 11:52 AM OCT 9, 2019 3:09 PM OCT 9, 2019 2:24 PM DELIVERY NEEDED NOV 17, 2020 11:22 AM OCT 9, 2019 2:40 PM MAX PRODUCT ALARM NOV 17, 2020 11:49 AM OCT 9, 2019 2:18 PM LOW TEMP WARNING NOV 17, 2020 12:12 PM TANK 3 DIESEL SETUP DATA WARNING AUG 27, 2018 8:19 AM HIGH WATER ALARM OCT 10, 2019 8:36 AM OCT 10, 2019 7:37 AM OVERFILL ALARM NOV 17, 2020 11:27 AM OCT 10, 2019 11:41 AM OCT 10, 2019 8:33 AM LOW PRODUCT ALARM OCT 7, 2021 6:38 PM OCT 10, 2019 7:33 AM AUG 27, 2018 8:05 AM HIGH PRODUCT ALARM DEC 6, 2021 10:48 AM OCT 10, 2019 11:41 AM OCT 10, 2019 7:52 AM INVALID FUEL LEVEL AUG 27, 2018 8:05 AM PROBE OUT DEC 6, 2021 10:49 AM DEC 6, 2021 10:39 AM NOV 17, 2020 11:56 AM HIGH WATER WARNING OCT 10, 2019 7:56 AM OCT 10, 2019 7:37 AM DELIVERY NEEDED AUG 22, 2022 7:55 AM JUL 8, 2022 8:33 AM JUL 1, 2022 7:04 AM LOW TEMP WARNING OCT 10, 2019 12:21 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 >< I38200NOV 17, 2022 8:38 AM > <I30200 NOV 17, 2022 8:38 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 STP DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 9:48 AM LOW LIQUID ALARM DEC 6, 2021 9:48 AM FUEL ALARM 2 87 FILL DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 9:51 AM LOW LIQUID ALARM DEC 6, 2021 9:50 AM FUEL ALARM 3 91 STP DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 9:53 AM LOW LIQUID ALARM DEC 6, 2021 9:52 AM FUEL ALARM 4 91 FILL DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 9:54 AM LOW LIQUID ALARM DEC 6, 2021 9:53 AM FUEL ALARM 5 DIESEL STP DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 9:57 AM LOW LIQUID ALARM DEC 6, 2021 9:56 AM FUEL ALARM 6 DIESEL FILL DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 9:55 AM LOW LIQUID ALARM DEC 6, 2021 9:55 AM FUEL ALARM 7 UNLEADED ANNULAR DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 9:59 AM LOW LIQUID ALARM DEC 6, 2021 9:58 AM HIGH LIQUID ALARM 8 DIESEL ANNULAR DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 10:00 AM LOW LIQUID ALARM DEC 6, 2021 10:00 AM HIGH LIQUID ALARM 9 1-2 UDC DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 10:02 AM LOW LIQUID ALARM DEC 6, 2021 10:01 AM FUEL ALARM 10 3-4 UDC DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 10:04 AM LOW LIQUID ALARM DEC 6, 2021 10:03 AM FUEL ALARM 11 5-6 UDC DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 10:05 AM LOW LIQUID ALARM DEC 6, 2021 10:04 AM FUEL ALARM 12 7-8 UDC DEC 6, 2021 10:18 AM SENSOR OUT ALARM DEC 6, 2021 10:05 AM LOW LIQUID ALARM DEC 6, 2021 10:05 AM FUEL ALARM 13 VENT BOX AUG 15, 2022 12:43 PM LOW LIQUID ALARM AUG 14, 2022 2:45 AM FUEL ALARM AUG 14, 2022 2:44 AM LOW LIQUID ALARM ><I31600NOV 17, 2022 8:38 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308661-588-1338 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 87 PRODUCT DEC 6, 2021 10:08 AM HIGH LIQUID ALARM DEC 6, 2021 10:08 AM NO VACUUM ALARM NOV 17, 2020 11:11 AM HIGH LIQUID ALARM 3 VAPOR RETURN DEC 6, 2021 10:08 AM HIGH LIQUID ALARM DEC 6, 2021 10:08 AM NO VACUUM ALARM MAR 10, 2021 3:31 PM SENSOR FAULT ALARM 4 91 PRODUCT DEC 6, 2021 10:10 AM HIGH LIQUID ALARM DEC 6, 2021 10:10 AM NO VACUUM ALARM FEB 10, 2021 11:28 AM NO VACUUM ALARM 5 ALL VENTS DEC 6, 2021 10:10 AM HIGH LIQUID ALARM DEC 6, 2021 10:10 AM NO VACUUM ALARM MAR 2, 2021 8:46 AM HIGH LIQUID ALARM 6 DIESEL PRODUCT DEC 6, 2021 10:12 AM HIGH LIQUID ALARM DEC 6, 2021 10:12 AM NO VACUUM ALARM NOV 17, 2020 11:19 AM HIGH LIQUID ALARM 8 ATM 9 1-2 FLOWMETER AUG 27, 2018 9:34 AM COMMUNICATION ALARM 10 3-4 FLOWMETER AUG 27, 2018 9:34 AM COMMUNICATION ALARM 11 5-6 FLOWMETER AUG 27, 2018 9:34 AM COMMUNICATION ALARM 12 7-8 FLOWMETER AUG 27, 2018 9:34 AM COMMUNICATION ALARM 16 PRESSURE SENSOR AUG 27, 2018 9:34 AM COMMUNICATION ALARM >< I10200NOV 17, 2022 8:38 AM BROOKSIDE MARKET 4700 COFFEE RD BAKERSFIELD CA 93308 661-588-1338 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 4952047 5198370 2 UNUSED 4939418 5105679 3 4 PROBE / G.T. 165562 165951 4 INTERSTITIAL BD 204254 204616 5 INTERSTITIAL BD 204109 204521 6 7SMARTSENSOR BD 516304 517555 7 8SMARTSENSOR BD 39981 39998 8 UNUSED 4932980 5089715 9 RELAY BOARD 15141 15125 10 RELAY BOARD 15141 15147 11 RELAY BOARD 15163 15147 12 STP SENSE BOARD 33612 33589 13 UNUSED 4942637 5083194 14 UNUSED 4938220 5076988 15 UNUSED 4936444 5075475 16 UNUSED 4938753 5074160 COMM 1 RS232 SERIAL BD 15186 15125 COMM 2 SERIAL SAT BD 488306 488180 COMM 3 ELEC DISP INT. 102294 102195 COMM 4 UNUSED 4940528 5074949 COMM 5 UNUSED 84872 5070037 COMM 6 RS232 SERIAL BD 15208 15169 > <I90200NOV 17, 2022 8:38 AMSOFTWARE REVISION LEVELVERSION 335.00SOFTWARE# 346335-100-A CREATED - 18.08.27.10.22 S-MODULE# 330160-004-aSYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM > UDC-1UDC-2 UDC-3UDC-4123456 78Diesel91 Premium87 Unleaded22,000 GALLONSUST-18,000 GALLONSUST-220,000 GALLONSUST-3TS-3TS-1TS-2FS-1FS-2FS-3AAVVVVDISPENSER UDC 1-2536 SENSORDISPENSER UDC 3-4536 SENSORDISPENSER UDC 5-6536 SENSORDISPENSER UDC 7-8536 SENSOR87 TURBINE SUMP536 SENSOR480 SENSOR99LD LINE LEAK DETECTORVACUUM SENSOR KIT #11-2-3-4-5-6-7-8 PRODUCT LINEDIESEL TURBINE SUMP536 SENSOR480 SENSOR99LD LINE LEAK DETECTORVACUUM SENSOR KIT #31-2-7-8 PRODUCT LINE91 TURBINE SUMP536 SENSOR480 SENSOR99LD LINE LEAK DETECTORVACUUM SENSOR KIT #21-2-3-4-5-6-7-8 PRODUCT LINE87 FILL SUMP536 SENSORDIESEL FILL SUMP536 SENSORPREMIUM FILL SUMP536 SENSORDIESEL ANNULAR303 SENSOR8791 ANNULAR303 SENSORHEALY CLEAN AIR SEPERATORVENTSUMPTRANSITION SUMP536 SENSORZONE # 1-87 REGULARZONE#4- 91 PREMIUMZONE #2- 87 VAPOR LINEZONE #3- 87 VENT LINEZONE #7- DIESEL VENT LINEZONE #5-91 VENT LINESLOPE 18" PER FOOT MIN. TO TANKSSTOREELECTRICAL TIE INFIRE HYDRANTE STOPTLSHAGEMAN RDCOFFEE RD30K SPLIT TANKLEGENDVACUUM SENSOR KIT # 1- 87 TURBINEZONE 187BRUGGPRODUCTZONE 287VAPOR LINEZONE 387VENT LINEVACUUM SENSOR KIT # 2- 91 TURBINEZONE 491BRUGGPRODUCTZONE 591VENT LINEVACUUM SENSOR KIT # 3- DIESEL TURBINEZONE 6DIESELBRUGGPRODUCTZONE 7DIESELVENT LINEVEEDER ROOT SENSOR,PROBES,LEAK DETECTORS4 DISPENSER +UDCUDC 1,2,3,4330020-536HYDROSTATICDISPENSER PANSENSOR2 ANNULARS30K SPLIT + 20K330020-536HYDROSTATICDISPENSER PANSENSOR794380-303BRINE SENSOR3 TURBINESUMPS87 , 91, DIESELPRODUCTS330020-536HYDROSTATICDISPENSER PANSENSOR330020-480VACUUMSENSOR116-057-5 LINELEAK DETECTOR3 FILL SUMPS87,91,DIESEL330020-536HYDROSTATICDISPENSER PANSENSOR1 VENT SUMPHEALY TANK330020-536HYDROSTATICDISPENSER PANSENSOR3 TANK PROBES87,91,DIESEL846390-110 MAGPROBE 3 LEAKDETECTORS87,91,DIESEL99LD-2000 VMILINE LEAKDETECTOR6" X 7 FOOT BOLLARDSHB PROPANETANKSITE MAP= Penetrations BRAVO F-75-PE-BRG-D (65) FOR PRODUCT= Penetrations BRAVO F-32-TS-D BRAVO FB (51) FOR VAPOR/VENTNORTHZONE# 6- DIESELPRICE SIGNAIR /WATERSITE HAZMAT INVENTORYCARBON DIOXIDE LIQUIDABSORBANT PADSCIM-TEK FILTERSLIQUEFIED PETROLEUM GAS (LPG)GASOLINE ALL GRADESDIESEL FUEL NO. 2CO2CO2FIRE SUPRESSIONCIRCUIT BREAKERWATER METER SHUTOFFOVER FILL ALARMCIM-TEKFILTERSOUTSIDEABSORBANT PADSOUTSIDE