HomeMy WebLinkAboutFMC 2022Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10125616 11/22/2022
Xpress Gas
928 Flower Street Bakersfield 93305
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Aaron Perrigo
1073967
8485827 8/8/2024
Veeder Root B47853 7/30/2024
FFS 1010993708 7/10/2024
VMI 3924 10/24/2024
11/22/2022 7
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS-350 336.01
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 420 87-91 Ann
L2 208 87 STP
L3 208 87 Fill
L4 208 91 STP
L5 208 91 Fill
L6 208 Disp 1-2
L7 208 Disp 3-4
L8 208 Disp 5-6
L9 Not used
L10 208 Disp 9-10
L11 208 Disp 11-12
L12 208 Disp 7-8
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87
T2 FX1V 91
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Xpress Gas928 Flower StreetBakersfield101256163-47-8 11-12MPD MPD MPD MPD MPD MPD 1-25-69-10ProductProductProductProductProductProductAaron Perrigo
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10125616 11/22/2022
Xpress Gas
928 Flower Street Bakersfield 93305
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Aaron Perrigo
1073967
8485827 8/8/2024
FFS 1010993708 7/10/2024
Lake test Both fill spill buckets
11/22/2022 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
87
PhilTite
91
PhilTite
Flower St Setup
Responses Received:
200
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
NOV 22, 2022 8:46 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 REGULAR UNL 5141 43.71 0.0 69.9 6886
2 SUPER UNL 2225 33.26 0.0 73.2 5964
I90500
NOV 22, 2022 8:46 AM
SOFTWARE REVISION LEVEL
VERSION 336.01
SOFTWARE# 346336-100-B
CREATED - 20.04.26.20.30
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
NOV 22, 2022 8:46 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
NOV 22, 2022 8:46 AM
SHIFT TIME 1 : 2:00 AM
I50202
NOV 22, 2022 8:46 AM
SHIFT TIME 2 : DISABLED
I50203
NOV 22, 2022 8:46 AM
SHIFT TIME 3 : DISABLED
I50204
NOV 22, 2022 8:46 AM
SHIFT TIME 4 : DISABLED
I54600
NOV 22, 2022 8:46 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
NOV 22, 2022 8:46 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
NOV 22, 2022 8:46 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
NOV 22, 2022 8:47 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
NOV 22, 2022 8:47 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
NOV 22, 2022 8:47 AM
PRINT TC VOLUMES
ENABLED
I50E00
NOV 22, 2022 8:47 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
NOV 22, 2022 8:47 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
NOV 22, 2022 8:47 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
NOV 22, 2022 8:47 AM
DAYLIGHT SAVING TIME
DISABLED
I51B00
NOV 22, 2022 8:47 AM
I51600
NOV 22, 2022 8:47 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
NOV 22, 2022 8:47 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
NOV 22, 2022 8:47 AM
TANK CHART SECURITY
DISABLED
I5BD00
NOV 22, 2022 8:47 AM
CUSTOM ALARM LABELS
DISABLED
I56000
NOV 22, 2022 8:47 AM
MASS/DENSITY
DISABLED
I88101
NOV 22, 2022 8:47 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
NOV 22, 2022 8:47 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 1200
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
NOV 22, 2022 8:47 AM
I88104
NOV 22, 2022 8:47 AM
I88105
NOV 22, 2022 8:47 AM
I88106
NOV 22, 2022 8:47 AM
I52000
NOV 22, 2022 8:47 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE JUN 26, 2015 DISABLED
2 ON DATE JUN 26, 2015 DISABLED
3 ON DATE JUN 26, 2015 DISABLED
4 ON DATE JUN 26, 2015 DISABLED
5 ON DATE JUN 26, 2015 DISABLED
6 ON DATE JUN 26, 2015 DISABLED
7 ON DATE JUN 26, 2015 DISABLED
8 ON DATE JUN 26, 2015 DISABLED
I60100
NOV 22, 2022 8:47 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 REGULAR UNL ON
2 SUPER UNL ON
3 OFF
4 OFF
I60200
NOV 22, 2022 8:47 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 REGULAR UNL
2 SUPER UNL
3
4
I60300
NOV 22, 2022 8:47 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 REGULAR UNL 1
2 SUPER UNL 2
3 3
4 4
I60900
NOV 22, 2022 8:47 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 REGULAR UNL 0.000700
2 SUPER UNL 0.000700
3 0.000000
4 0.000000
I60700
NOV 22, 2022 8:47 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 REGULAR UNL 109.00
2 SUPER UNL 109.00
3 0.00
4 0.00
I60A00
NOV 22, 2022 8:47 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 REGULAR UNL
20 PTS 12027 2 SUPER UNL 20 PTS 8189 3
1 PT 0 4 1 PT 0
I60400
NOV 22, 2022 8:47 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 12027
2 SUPER UNL 8189
3 0
4 0
I60500
NOV 22, 2022 8:47 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 12027 10372 6531 2759
2 SUPER UNL 8189 6711 4229 1698
3 0 0 0 0
4 0 0 0 0
I60600
NOV 22, 2022 8:47 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 12027 11916 11547 11066
10511 10372 9655 9356
8538 7693 6531 5965
5124 4321 3532 2759
2032 1372 795 485
2 SUPER UNL 8189 8089 7850 7520
7141 6711 6259 5770
5269 4751 4229 3699
3180 2667 2175 1698
1258 847 490 198
3 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
NOV 22, 2022 8:48 AM
TANK PRODUCT LABEL METER DATA
1 REGULAR UNL NO
2 SUPER UNL NO
3 NO
4 NO
I62F00
NOV 22, 2022 8:48 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 REGULAR UNL 4.0 IN.
2 SUPER UNL 4.0 IN.
I62700
NOV 22, 2022 8:48 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 REGULAR UNL 3.0
2 SUPER UNL 3.0
I64200
NOV 22, 2022 8:48 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 REGULAR UNL LOW
2 SUPER UNL LOW
I62400
NOV 22, 2022 8:48 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 REGULAR UNL 2.0
2 SUPER UNL 2.0
I62800
NOV 22, 2022 8:48 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 12027
2 SUPER UNL 8189
3 0
4 0
I62300
NOV 22, 2022 8:48 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 10824
2 SUPER UNL 7370
3 0
4 0
I62200
NOV 22, 2022 8:48 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 11426
2 SUPER UNL 7780
3 0
4 0
I62900
NOV 22, 2022 8:48 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 1203
2 SUPER UNL 819
3 0
4 0
I62100
NOV 22, 2022 8:48 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 222
2 SUPER UNL 400
3 0
4 0
I62600
NOV 22, 2022 8:48 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 99
2 SUPER UNL 99
3 99
4 99
I62500
NOV 22, 2022 8:48 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 99
2 SUPER UNL 99
3 99
4 99
I60800
NOV 22, 2022 8:48 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 REGULAR UNL 0.00
2 SUPER UNL 0.00
3 0.00
4 0.00
I60B00
NOV 22, 2022 8:48 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
NOV 22, 2022 8:48 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 REGULAR UNL 0.00
2 SUPER UNL 0.00
3 0.00
4 0.00
I61200
NOV 22, 2022 8:48 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 REGULAR UNL NONE NONE
2 SUPER UNL NONE NONE
3 NONE NONE
4 NONE NONE
I63600
NOV 22, 2022 8:48 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 1202
2 SUPER UNL 818
3 0
4 0
I62A00
NOV 22, 2022 8:48 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 1202
2 SUPER UNL 818
3 0
4 0
I62C00
NOV 22, 2022 8:48 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 REGULAR UNL STANDARD
2 SUPER UNL STANDARD
3 STANDARD
4 STANDARD
I62D00
NOV 22, 2022 8:48 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 REGULAR UNL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 SUPER UNL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
NOV 22, 2022 8:48 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 REGULAR UNL OFF OFF
2 SUPER UNL OFF OFF
3 OFF OFF
4 OFF OFF
I63000
NOV 22, 2022 8:48 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 REGULAR UNL OFF
2 SUPER UNL OFF
3 OFF
4 OFF
I63200
NOV 22, 2022 8:49 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 REGULAR UNL OFF
2 SUPER UNL OFF
3 OFF
4 OFF
I61000
NOV 22, 2022 8:49 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 REGULAR UNL 1
2 SUPER UNL 1
3 1
4 1
I63A00
NOV 22, 2022 8:49 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 REGULAR UNL 10.00%
2 SUPER UNL 10.00%
3 10.00%
4 10.00%
I61100
NOV 22, 2022 8:49 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
OCT 1, 2014
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
NOV 22, 2022 8:49 AM
CSLD PROBABLITY OF DETECTION
I61400
NOV 22, 2022 8:49 AM
CSLD CLIMATE FACTOR
I61600
NOV 22, 2022 8:49 AM
TANK PRODUCT LABEL CAL UPDATE
1 REGULAR UNL IMMEDIATE
2 SUPER UNL IMMEDIATE
3 IMMEDIATE
4 IMMEDIATE
I61A00
NOV 22, 2022 8:49 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 REGULAR UNL DISABLED
2 SUPER UNL DISABLED
3 DISABLED
4 DISABLED
I61B00
NOV 22, 2022 8:49 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
NOV 22, 2022 8:49 AM
CSLD REPORT ONLY
I62B00
NOV 22, 2022 8:49 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 REGULAR UNL ??? 0, 0
2 SUPER UNL ??? 0, 0
3 ??? 0, 0
4 ??? 0, 0
I63300
NOV 22, 2022 8:49 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
NOV 22, 2022 8:49 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 0
2 SUPER UNL 0
3 0
4 0
I63500
NOV 22, 2022 8:49 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR UNL 1
2 SUPER UNL 1
3 1
4 1
I63900
NOV 22, 2022 8:49 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 REGULAR UNL
END FACTOR: NONE
2 SUPER UNL
END FACTOR: NONE
3
END FACTOR: NONE
4
END FACTOR: NONE
I78000
NOV 22, 2022 8:49 AM
I77700
NOV 22, 2022 8:49 AM
I77800
NOV 22, 2022 8:49 AM
I78C00
NOV 22, 2022 8:49 AM
I78300
NOV 22, 2022 8:49 AM
I78F00
NOV 22, 2022 8:49 AM
I78700
NOV 22, 2022 8:49 AM
I70200
NOV 22, 2022 8:49 AM
LIQUID LABEL
DEVICE LABEL
1 87-91 ANNULAR
2 87 STP
3 87 FILL
4 91 STP
5 91 FILL
6 DISP 1-2
7 DISP 3-4
8 DISP 5-6
9 DISP 7-8
10 DISP 9-10
11 DISP 11-12
12 DISP 7-8
13
14
15
16
I70300
NOV 22, 2022 8:49 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87-91 ANNULAR TRI-STATE (SINGLE FLOAT)
2 87 STP TRI-STATE (SINGLE FLOAT)
3 87 FILL TRI-STATE (SINGLE FLOAT)
4 91 STP TRI-STATE (SINGLE FLOAT)
5 91 FILL TRI-STATE (SINGLE FLOAT)
6 DISP 1-2 TRI-STATE (SINGLE FLOAT)
7 DISP 3-4 TRI-STATE (SINGLE FLOAT)
8 DISP 5-6 TRI-STATE (SINGLE FLOAT)
9 DISP 7-8 TRI-STATE (SINGLE FLOAT)
10 DISP 9-10 TRI-STATE (SINGLE FLOAT)
11 DISP 11-12 TRI-STATE (SINGLE FLOAT)
12 DISP 7-8 TRI-STATE (SINGLE FLOAT)
13 TRI-STATE (SINGLE FLOAT)
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
NOV 22, 2022 8:49 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 87-91 ANNULAR ANNULAR SPACE
2 87 STP STP SUMP
3 87 FILL PIPING SUMP
4 91 STP STP SUMP
5 91 FILL PIPING SUMP
6 DISP 1-2 DISPENSER PAN
7 DISP 3-4 DISPENSER PAN
8 DISP 5-6 DISPENSER PAN
9 DISP 7-8 DISPENSER PAN
10 DISP 9-10 DISPENSER PAN
11 DISP 11-12 DISPENSER PAN
12 DISP 7-8 DISPENSER PAN
13 OTHER SENSORS
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
NOV 22, 2022 8:49 AM
I74300
NOV 22, 2022 8:50 AM
I74400
NOV 22, 2022 8:50 AM
I74700
NOV 22, 2022 8:50 AM
I74800
NOV 22, 2022 8:50 AM
I74900
NOV 22, 2022 8:50 AM
I7BC00
NOV 22, 2022 8:50 AM
I80200
NOV 22, 2022 8:50 AM
I80300
NOV 22, 2022 8:50 AM
I80400
NOV 22, 2022 8:50 AM
I80700
NOV 22, 2022 8:50 AM
RELAY LABEL
DEVICE LABEL
1 REGULAR UNL
2 SUPER UNL
3 OVERFILL
4
I80900
NOV 22, 2022 8:50 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 REGULAR UNL NORMALLY CLOSED
2 SUPER UNL NORMALLY CLOSED
3 OVERFILL NORMALLY OPEN
4 NORMALLY OPEN
I80B00
NOV 22, 2022 8:50 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 REGULAR UNL 1
2 SUPER UNL 2
3 OVERFILL NONE
4 NONE
I80A00
NOV 22, 2022 8:50 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 REGULAR UNL STANDARD
2 SUPER UNL STANDARD
3 OVERFILL STANDARD
4 STANDARD
I80C00
NOV 22, 2022 8:50 AM
I80800
NOV 22, 2022 8:50 AM
RELAY SETUP REPORT
R 1:REGULAR UNL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
IN-TANK ALARMS
T 1:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 2:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 2:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
PMC ALARMS
VP EMISSIONS FAIL
VP PRESSURE FAIL
VP DUTY CYCLE FAIL
PMC SETUP FAIL
R 2:SUPER UNL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
IN-TANK ALARMS
T 2:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 4:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 4:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
PMC ALARMS
VP EMISSIONS FAIL
VP PRESSURE FAIL
VP DUTY CYCLE FAIL
R 3:OVERFILL
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
NOV 22, 2022 8:50 AM
EDIM:1 VR:349643-001-B TD:97.10.27.11.25
I79100
NOV 22, 2022 8:50 AM
I72300
NOV 22, 2022 8:50 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VAPOR PRESSUR VAPOR PRESSURE
02 FM 1-2 AIR FLOW METER
03 FM 3-4 AIR FLOW METER
04 FM 5-6 AIR FLOW METER
05 FM 7-8 AIR FLOW METER
06 FM 9-10 AIR FLOW METER
07 FM 11-12 AIR FLOW METER
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
NOV 22, 2022 8:51 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
NOV 22, 2022 8:51 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
NOV 22, 2022 8:51 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
VAPOR PROCESSOR TYPE
NONE
IV4700
NOV 22, 2022 8:51 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
NOV 22, 2022 8:51 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
ACCEPT HIGH ORVR: NO
IV4A00
NOV 22, 2022 8:51 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
09 09 09 05 02 BLEND3
10 16 10 05 02 BLEND3
11 17 11 06 02 BLEND3
12 18 12 06 02 BLEND3
IV4B00
NOV 22, 2022 8:51 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 09/01 01/01 xx/xx
02 01 02/02 09/02 01/02 xx/xx
03 02 02/03 09/03 01/03 xx/xx
04 02 02/04 09/04 01/04 xx/xx
05 03 02/05 09/05 01/05 xx/xx
06 03 02/06 09/06 01/06 xx/xx
07 04 02/07 09/07 01/07 xx/xx
08 04 09/08 02/08 01/08 xx/xx
09 05 02/09 09/09 01/09 xx/xx
16 05 02/10 09/10 01/10 xx/xx
17 06 02/11 09/11 01/11 xx/xx
18 06 02/12 09/12 01/12 xx/xx
IV4900
NOV 22, 2022 8:51 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
NOV 22, 2022 8:51 AM
ISD VERSION: 01.06
Flower St Alarm History
Responses Received:
I10200
NOV 22, 2022 8:52 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 UNUSED 10338915 10318255
2 UNUSED 10296801 10282144
3 UNUSED 10293976 10282663
4 8SMARTSENSOR BD 39519 39565
5 4 PROBE / G.T. 163516 163733
6 INTERSTITIAL BD 201358 201638
7 INTERSTITIAL BD 201563 201840
8 UNUSED 10302035 10288217
9 UNUSED 10288122 10271065
10 RELAY BOARD 14978 14993
11 UNUSED 10295874 10280573
12 UNUSED 10296334 10263328
13 UNUSED 10290465 10275084
14 UNUSED 10283523 10273377
15 UNUSED 10292523 10272837
16 UNUSED 10289195 10272124
COMM 1 ELEC DISP INT. 100618 100680
COMM 2 RS232 SERIAL BD 14912 14928
COMM 3 UNUSED 10299707 10276597
COMM 4 UNUSED 10287705 10274069
COMM 5 UNUSED 10286808 10274933
COMM 6 UNUSED 10284990 10266959
I90200
NOV 22, 2022 8:52 AM
SOFTWARE REVISION LEVEL
VERSION 336.01
SOFTWARE# 346336-100-B
CREATED - 20.04.26.20.30
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
NOV 22, 2022 8:52 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 5 PIPE 91 FILL FUEL ALARM CLEAR 11-10-22 8:50AM
L 5 PIPE 91 FILL FUEL ALARM ALARM 11-08-22 2:23PM
L 3 PIPE 87 FILL FUEL ALARM CLEAR 10-19-22 2:56AM
L 3 PIPE 87 FILL FUEL ALARM ALARM 10-17-22 2:35PM
OTHER ISD VAPOR LEAK FAIL CLEAR 10-01-22 10:41AM
OTHER ISD VAPOR LEAK FAIL ALARM 10-01-22 10:04AM
OTHER ISD VAPOR LEAK FAIL CLEAR 10-01-22 10:04AM
OTHER ISD VAPOR LEAK FAIL ALARM 9-30-22 10:03AM
T 1 TANK REGULAR UNL OVERFILL ALARM CLEAR 6-05-22 6:20PM
T 1 TANK REGULAR UNL OVERFILL ALARM ALARM 6-05-22 6:16PM
OTHER ISD VAPOR LEAK FAIL CLEAR 4-15-22 1:47PM
OTHER ISD VAPOR LEAK FAIL ALARM 4-15-22 10:02AM
OTHER ISD VAPOR LEAK FAIL CLEAR 4-15-22 10:02AM
f 4 OTHER FM 7-8 CHK VAPOR FLOW MTR CLEAR 4-15-22 10:00AM
OTHER ISD SENSOR OUT FAIL CLEAR 4-14-22 4:57PM
OTHER ISD SENSOR OUT FAIL ALARM 4-14-22 1:17PM
OTHER ISD SENSOR OUT FAIL CLEAR 4-14-22 1:17PM
OTHER ISD VAPOR LEAK FAIL ALARM 4-14-22 1:17PM
OTHER ISD SENSOR OUT FAIL ALARM 4-13-22 1:17PM
OTHER ISD SENSOR OUT FAIL CLEAR 4-13-22 1:17PM
OTHER ISD SENSOR OUT FAIL ALARM 4-12-22 1:17PM
OTHER ISD SENSOR OUT FAIL CLEAR 4-12-22 1:17PM
OTHER ISD SENSOR OUT FAIL ALARM 4-11-22 1:17PM
OTHER ISD SENSOR OUT FAIL CLEAR 4-11-22 1:17PM
OTHER ISD SENSOR OUT FAIL ALARM 4-10-22 1:17PM
f 4 OTHER FM 7-8 CHK VAPOR FLOW MTR ALARM 4-03-22 1:18PM
L 5 PIPE 91 FILL FUEL ALARM CLEAR 3-31-22 8:32AM
T 1 TANK REGULAR UNL OVERFILL ALARM CLEAR 3-28-22 10:40PM
T 1 TANK REGULAR UNL OVERFILL ALARM ALARM 3-28-22 10:37PM
L 5 PIPE 91 FILL FUEL ALARM ALARM 3-28-22 8:45AM
OTHER ISD VAPOR LEAK FAIL CLEAR 3-16-22 9:00AM
L 5 PIPE 91 FILL FUEL ALARM CLEAR 3-16-22 7:06AM
OTHER ISD VAPOR LEAK FAIL ALARM 3-15-22 1:17PM
L 5 PIPE 91 FILL FUEL ALARM ALARM 3-04-22 3:49AM
L 2 STP SUMP 87 STP FUEL ALARM CLEAR 3-01-22 2:47PM
L 2 STP SUMP 87 STP FUEL ALARM ALARM 3-01-22 11:43AM
L 6 DISP PAN DISP 1-2 FUEL ALARM CLEAR 1-25-22 10:20AM
L 6 DISP PAN DISP 1-2 FUEL ALARM ALARM 1-25-22 10:14AM
L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L 2 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L 4 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L 5 PIPE 91 FILL SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L 3 PIPE 87 FILL SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L 1 ANNULAR 87-91 ANNULAR SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L11 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L10 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 1-25-22 10:05AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 1-25-22 10:04AM
I11200
NOV 22, 2022 8:52 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
OTHER ISD GROSS PRES WARN CLEAR 11-19-22 5:58AM
OTHER ISD GROSS PRES WARN ALARM 11-17-22 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 11-10-22 2:04PM
OTHER ISD GROSS PRES WARN ALARM 11-07-22 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 10-31-22 3:31PM
OTHER ISD GROSS PRES WARN ALARM 10-31-22 10:02AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 10-25-22 5:26PM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 10-25-22 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 10-25-22 6:32AM
OTHER ISD GROSS PRES WARN ALARM 10-24-22 10:03AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 10-23-22 10:00AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 10-23-22 10:00AM
SYSTEM PRINTER ERROR CLEAR 10-23-22 2:02AM
SYSTEM PAPER OUT CLEAR 10-23-22 2:02AM
SYSTEM PRINTER ERROR ALARM 10-23-22 2:01AM
SYSTEM PAPER OUT ALARM 10-23-22 2:01AM
SYSTEM PRINTER ERROR CLEAR 10-23-22 2:01AM
SYSTEM PAPER OUT CLEAR 10-23-22 2:01AM
SYSTEM PRINTER ERROR ALARM 10-23-22 2:00AM
SYSTEM PAPER OUT ALARM 10-23-22 2:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 10-21-22 10:03AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 10-19-22 10:03AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 10-17-22 4:17PM
OTHER ISD GROSS PRES WARN CLEAR 10-17-22 4:16PM
T 1 TANK REGULAR UNL DELIVERY NEEDED CLEAR 10-17-22 11:34AM
T 1 TANK REGULAR UNL INVALID FUEL LEVEL CLEAR 10-17-22 11:32AM
T 1 TANK REGULAR UNL INVALID FUEL LEVEL ALARM 10-17-22 11:06AM
T 1 TANK REGULAR UNL DELIVERY NEEDED ALARM 10-17-22 6:22AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 10-15-22 10:02AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 10-14-22 10:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 10-12-22 10:01AM
OTHER ISD GROSS PRES WARN ALARM 10-11-22 10:01AM
T 1 TANK REGULAR UNL DELIVERY NEEDED CLEAR 10-11-22 2:27AM
T 1 TANK REGULAR UNL DELIVERY NEEDED ALARM 10-10-22 9:12PM
OTHER ISD VAPOR LEAK WARN CLEAR 10-10-22 4:45PM
OTHER ISD VAPOR LEAK WARN ALARM 10-07-22 10:04AM
OTHER ISD VAPOR LEAK WARN CLEAR 9-30-22 10:03AM
SYSTEM PRINTER ERROR CLEAR 9-29-22 12:39PM
SYSTEM PAPER OUT CLEAR 9-29-22 12:39PM
SYSTEM PRINTER ERROR ALARM 9-29-22 12:31PM
SYSTEM PAPER OUT ALARM 9-29-22 12:31PM
OTHER ISD VAPOR LEAK WARN ALARM 9-23-22 10:03AM
OTHER ISD VAPOR LEAK WARN CLEAR 9-19-22 10:03AM
OTHER ISD VAPOR LEAK WARN ALARM 9-18-22 10:03AM
OTHER ISD VAPOR LEAK WARN CLEAR 9-15-22 10:03AM
SYSTEM PRINTER ERROR CLEAR 9-09-22 3:47PM
SYSTEM PRINTER ERROR ALARM 9-09-22 3:47PM
SYSTEM PRINTER ERROR CLEAR 9-09-22 3:47PM
SYSTEM PRINTER ERROR ALARM 9-09-22 3:47PM
SYSTEM PRINTER ERROR CLEAR 9-09-22 3:47PM
I20600
NOV 22, 2022 8:53 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
TANK ALARM HISTORY
TANK 1 REGULAR UNL
OVERFILL ALARM JUN 5, 2022 6:16 PM
MAR 28, 2022 10:37 PM
OCT 25, 2021 4:50 PM
HIGH PRODUCT ALARM MAY 10, 2021 8:49 AM
APR 28, 2021 1:23 PM
INVALID FUEL LEVEL OCT 17, 2022 11:06 AM
JUN 30, 2022 11:11 PM
DEC 10, 2021 12:54 PM
PROBE OUT APR 28, 2021 1:23 PM
APR 28, 2021 1:18 PM
DELIVERY NEEDED OCT 17, 2022 6:22 AM
OCT 10, 2022 9:12 PM
JUL 18, 2022 8:21 PM
LOW TEMP WARNING APR 28, 2021 1:24 PM
TANK 2 SUPER UNL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
NOV 22, 2022 8:53 AM
I30200
NOV 22, 2022 8:53 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87-91 ANNULAR
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:47 AM FUEL ALARM
APR 28, 2021 1:16 PM SENSOR OUT ALARM
2 87 STP
MAR 1, 2022 11:43 AM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:49 AM FUEL ALARM
3 87 FILL
OCT 17, 2022 2:35 PM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:48 AM FUEL ALARM
4 91 STP
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:50 AM FUEL ALARM
APR 28, 2021 1:16 PM SENSOR OUT ALARM
5 91 FILL
NOV 8, 2022 2:23 PM FUEL ALARM
MAR 28, 2022 8:45 AM FUEL ALARM
MAR 4, 2022 3:49 AM FUEL ALARM
6 DISP 1-2
JAN 25, 2022 10:14 AM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:51 AM FUEL ALARM
7 DISP 3-4
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:52 AM FUEL ALARM
APR 28, 2021 1:16 PM SENSOR OUT ALARM
8 DISP 5-6
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:53 AM FUEL ALARM
APR 28, 2021 1:16 PM SENSOR OUT ALARM
10 DISP 9-10
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:55 AM FUEL ALARM
APR 28, 2021 1:16 PM SENSOR OUT ALARM
11 DISP 11-12
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:55 AM FUEL ALARM
APR 28, 2021 1:16 PM SENSOR OUT ALARM
12 DISP 7-8
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
JAN 25, 2022 9:54 AM FUEL ALARM
APR 28, 2021 1:16 PM SENSOR OUT ALARM
I31600
NOV 22, 2022 8:54 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VAPOR PRESSUR
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
6 FM 9-10
7 FM 11-12
I40200
NOV 22, 2022 8:54 AM
I40300
NOV 22, 2022 8:54 AM
I34200
NOV 22, 2022 8:54 AM
I34700
NOV 22, 2022 8:54 AM
IV0100
NOV 22, 2022 8:54 AM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-11-18 10:03:23 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.74
22-11-17 10:03:53 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.86
22-11-10 10:03:40 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
22-11-09 10:03:32 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
22-11-08 10:03:27 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.83
22-11-07 10:03:20 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.12
22-10-31 10:02:17 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.71
22-10-25 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.81
22-10-24 10:03:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55
22-10-22 10:03:25 A/L RATIO DEGRADATION FP 3 BLEND3 0.79
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-10-01 10:04:05 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
22-09-30 10:03:57 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
22-04-15 10:02:40 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.49
22-04-14 13:17:52 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-04-14 13:17:51 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.63
22-04-13 13:17:44 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-04-12 13:17:52 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-04-11 13:17:48 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-04-10 13:17:48 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-03-15 13:17:40 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 63.14
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-11-19 05:58:45 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-11-10 14:04:08 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-11-10 08:03:00 TIME CHANGE DETECTED AT: 22-11-10 08:58:43
22-10-31 15:31:26 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-10-25 17:26:03 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED
22-10-25 06:32:21 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-10-17 16:17:54 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED
22-10-17 16:16:56 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-10-10 16:45:57 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
22-10-02 10:01:34 READINESS ISD:PP EVR:PP ISD & EVR READY
Flower St Alarm History After
Responses Received:
I10200
NOV 22, 2022 12:08 PM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 UNUSED 10338915 10362315
2 UNUSED 10296801 10341375
3 UNUSED 10293976 10350321
4 8SMARTSENSOR BD 39519 39498
5 4 PROBE / G.T. 163516 163207
6 INTERSTITIAL BD 201358 201155
7 INTERSTITIAL BD 201563 201452
8 UNUSED 10302035 10355277
9 UNUSED 10288122 10335687
10 RELAY BOARD 14978 14971
11 UNUSED 10295874 10347659
12 UNUSED 10296334 10342594
13 UNUSED 10290465 10342945
14 UNUSED 10283523 10331083
15 UNUSED 10292523 10337441
16 UNUSED 10289195 10336170
COMM 1 ELEC DISP INT. 100618 100466
COMM 2 RS232 SERIAL BD 14912 14905
COMM 3 UNUSED 10299707 10346410
COMM 4 UNUSED 10287705 10346519
COMM 5 UNUSED 10286808 10330359
COMM 6 UNUSED 10284990 10346432
I90200
NOV 22, 2022 12:08 PM
SOFTWARE REVISION LEVEL
VERSION 336.01
SOFTWARE# 346336-100-B
CREATED - 20.04.26.20.30
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
NOV 22, 2022 12:09 PM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L 4 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L 3 PIPE 87 FILL SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L10 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L 2 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L 5 PIPE 91 FILL SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L11 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L 1 ANNULAR 87-91 ANNULAR SENSOR OUT ALARM CLEAR 11-22-22 9:48AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L11 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L10 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L 2 STP SUMP 87 STP SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L 8 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L 7 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L 6 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L 4 STP SUMP 91 STP SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L 3 PIPE 87 FILL SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L 1 ANNULAR 87-91 ANNULAR SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L 5 PIPE 91 FILL SENSOR OUT ALARM ALARM 11-22-22 9:47AM
L11 DISP PAN DISP 11-12 FUEL ALARM CLEAR 11-22-22 9:45AM
L11 DISP PAN DISP 11-12 FUEL ALARM ALARM 11-22-22 9:44AM
L10 DISP PAN DISP 9-10 FUEL ALARM CLEAR 11-22-22 9:44AM
L10 DISP PAN DISP 9-10 FUEL ALARM ALARM 11-22-22 9:44AM
L 8 DISP PAN DISP 5-6 FUEL ALARM CLEAR 11-22-22 9:43AM
L 8 DISP PAN DISP 5-6 FUEL ALARM ALARM 11-22-22 9:43AM
L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 11-22-22 9:42AM
L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 11-22-22 9:42AM
L 7 DISP PAN DISP 3-4 FUEL ALARM CLEAR 11-22-22 9:42AM
L 7 DISP PAN DISP 3-4 FUEL ALARM ALARM 11-22-22 9:41AM
L 6 DISP PAN DISP 1-2 FUEL ALARM CLEAR 11-22-22 9:41AM
L 6 DISP PAN DISP 1-2 FUEL ALARM ALARM 11-22-22 9:41AM
L 1 ANNULAR 87-91 ANNULAR FUEL ALARM CLEAR 11-22-22 9:40AM
L 1 ANNULAR 87-91 ANNULAR FUEL ALARM ALARM 11-22-22 9:40AM
L 3 PIPE 87 FILL FUEL ALARM CLEAR 11-22-22 9:39AM
L 3 PIPE 87 FILL FUEL ALARM ALARM 11-22-22 9:39AM
L 5 PIPE 91 FILL FUEL ALARM CLEAR 11-22-22 9:39AM
L 5 PIPE 91 FILL FUEL ALARM ALARM 11-22-22 9:38AM
L 4 STP SUMP 91 STP FUEL ALARM CLEAR 11-22-22 9:38AM
L 4 STP SUMP 91 STP FUEL ALARM ALARM 11-22-22 9:38AM
L 2 STP SUMP 87 STP FUEL ALARM CLEAR 11-22-22 9:37AM
L 2 STP SUMP 87 STP FUEL ALARM ALARM 11-22-22 9:37AM
L 5 PIPE 91 FILL FUEL ALARM CLEAR 11-10-22 8:50AM
L 5 PIPE 91 FILL FUEL ALARM ALARM 11-08-22 2:23PM
L 3 PIPE 87 FILL FUEL ALARM CLEAR 10-19-22 2:56AM
L 3 PIPE 87 FILL FUEL ALARM ALARM 10-17-22 2:35PM
OTHER ISD VAPOR LEAK FAIL CLEAR 10-01-22 10:41AM
OTHER ISD VAPOR LEAK FAIL ALARM 10-01-22 10:04AM
I11200
NOV 22, 2022 12:09 PM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 11-22-22 9:49AM
SYSTEM PAPER OUT CLEAR 11-22-22 9:49AM
SYSTEM PRINTER ERROR ALARM 11-22-22 9:47AM
SYSTEM PAPER OUT ALARM 11-22-22 9:47AM
OTHER ISD GROSS PRES WARN CLEAR 11-19-22 5:58AM
OTHER ISD GROSS PRES WARN ALARM 11-17-22 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 11-10-22 2:04PM
OTHER ISD GROSS PRES WARN ALARM 11-07-22 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 10-31-22 3:31PM
OTHER ISD GROSS PRES WARN ALARM 10-31-22 10:02AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 10-25-22 5:26PM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 10-25-22 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 10-25-22 6:32AM
OTHER ISD GROSS PRES WARN ALARM 10-24-22 10:03AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 10-23-22 10:00AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN CLEAR 10-23-22 10:00AM
SYSTEM PRINTER ERROR CLEAR 10-23-22 2:02AM
SYSTEM PAPER OUT CLEAR 10-23-22 2:02AM
SYSTEM PRINTER ERROR ALARM 10-23-22 2:01AM
SYSTEM PAPER OUT ALARM 10-23-22 2:01AM
SYSTEM PRINTER ERROR CLEAR 10-23-22 2:01AM
SYSTEM PAPER OUT CLEAR 10-23-22 2:01AM
SYSTEM PRINTER ERROR ALARM 10-23-22 2:00AM
SYSTEM PAPER OUT ALARM 10-23-22 2:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 10-21-22 10:03AM
h 1 OTHER FP1: BLEND3 DEGRD COLLECT WARN ALARM 10-19-22 10:03AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 10-17-22 4:17PM
OTHER ISD GROSS PRES WARN CLEAR 10-17-22 4:16PM
T 1 TANK REGULAR UNL DELIVERY NEEDED CLEAR 10-17-22 11:34AM
T 1 TANK REGULAR UNL INVALID FUEL LEVEL CLEAR 10-17-22 11:32AM
T 1 TANK REGULAR UNL INVALID FUEL LEVEL ALARM 10-17-22 11:06AM
T 1 TANK REGULAR UNL DELIVERY NEEDED ALARM 10-17-22 6:22AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 10-15-22 10:02AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 10-14-22 10:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 10-12-22 10:01AM
OTHER ISD GROSS PRES WARN ALARM 10-11-22 10:01AM
T 1 TANK REGULAR UNL DELIVERY NEEDED CLEAR 10-11-22 2:27AM
T 1 TANK REGULAR UNL DELIVERY NEEDED ALARM 10-10-22 9:12PM
OTHER ISD VAPOR LEAK WARN CLEAR 10-10-22 4:45PM
OTHER ISD VAPOR LEAK WARN ALARM 10-07-22 10:04AM
OTHER ISD VAPOR LEAK WARN CLEAR 9-30-22 10:03AM
SYSTEM PRINTER ERROR CLEAR 9-29-22 12:39PM
SYSTEM PAPER OUT CLEAR 9-29-22 12:39PM
SYSTEM PRINTER ERROR ALARM 9-29-22 12:31PM
SYSTEM PAPER OUT ALARM 9-29-22 12:31PM
OTHER ISD VAPOR LEAK WARN ALARM 9-23-22 10:03AM
OTHER ISD VAPOR LEAK WARN CLEAR 9-19-22 10:03AM
OTHER ISD VAPOR LEAK WARN ALARM 9-18-22 10:03AM
OTHER ISD VAPOR LEAK WARN CLEAR 9-15-22 10:03AM
SYSTEM PRINTER ERROR CLEAR 9-09-22 3:47PM
I20600
NOV 22, 2022 12:10 PM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
TANK ALARM HISTORY
TANK 1 REGULAR UNL
OVERFILL ALARM JUN 5, 2022 6:16 PM
MAR 28, 2022 10:37 PM
OCT 25, 2021 4:50 PM
HIGH PRODUCT ALARM MAY 10, 2021 8:49 AM
APR 28, 2021 1:23 PM
INVALID FUEL LEVEL OCT 17, 2022 11:06 AM
JUN 30, 2022 11:11 PM
DEC 10, 2021 12:54 PM
PROBE OUT APR 28, 2021 1:23 PM
APR 28, 2021 1:18 PM
DELIVERY NEEDED OCT 17, 2022 6:22 AM
OCT 10, 2022 9:12 PM
JUL 18, 2022 8:21 PM
LOW TEMP WARNING APR 28, 2021 1:24 PM
TANK 2 SUPER UNL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
NOV 22, 2022 12:10 PM
I30200
NOV 22, 2022 12:10 PM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87-91 ANNULAR
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:40 AM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
2 87 STP
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:37 AM FUEL ALARM
MAR 1, 2022 11:43 AM FUEL ALARM
3 87 FILL
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:39 AM FUEL ALARM
OCT 17, 2022 2:35 PM FUEL ALARM
4 91 STP
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:38 AM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
5 91 FILL
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:38 AM FUEL ALARM
NOV 8, 2022 2:23 PM FUEL ALARM
6 DISP 1-2
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:41 AM FUEL ALARM
JAN 25, 2022 10:14 AM FUEL ALARM
7 DISP 3-4
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:41 AM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
8 DISP 5-6
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:43 AM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
10 DISP 9-10
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:44 AM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
11 DISP 11-12
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:44 AM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
12 DISP 7-8
NOV 22, 2022 9:47 AM SENSOR OUT ALARM
NOV 22, 2022 9:42 AM FUEL ALARM
JAN 25, 2022 10:04 AM SENSOR OUT ALARM
I31600
NOV 22, 2022 12:10 PM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VAPOR PRESSUR
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
6 FM 9-10
7 FM 11-12
I40200
NOV 22, 2022 12:11 PM
I40300
NOV 22, 2022 12:11 PM
I34200
NOV 22, 2022 12:11 PM
I34700
NOV 22, 2022 12:11 PM
IV0100
NOV 22, 2022 12:11 PM
FLOWER ST MINI MART
928 FLOWER ST
BAKERSFIELD CA 93305
661-328-0673
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
22-11-18 10:03:23 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.74
22-11-17 10:03:53 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.86
22-11-10 10:03:40 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
22-11-09 10:03:32 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.79
22-11-08 10:03:27 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.83
22-11-07 10:03:20 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.12
22-10-31 10:02:17 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.71
22-10-25 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.81
22-10-24 10:03:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55
22-10-22 10:03:25 A/L RATIO DEGRADATION FP 3 BLEND3 0.79
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-10-01 10:04:05 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
22-09-30 10:03:57 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
22-04-15 10:02:40 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.49
22-04-14 13:17:52 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-04-14 13:17:51 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.63
22-04-13 13:17:44 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-04-12 13:17:52 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-04-11 13:17:48 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-04-10 13:17:48 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 4:FM 7-8
22-03-15 13:17:40 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 63.14
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
22-11-22 10:03:28 READINESS ISD:PP EVR:PP ISD & EVR READY
22-11-22 09:46:54 READINESS ISD:PP EVR:NN EVR READINESS PENDING
22-11-22 09:46:54 ISD STARTUP
22-11-22 09:46:40 ISD SHUTDOWN
22-11-19 05:58:45 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-11-10 14:04:08 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-11-10 08:03:00 TIME CHANGE DETECTED AT: 22-11-10 08:58:43
22-10-31 15:31:26 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
22-10-25 17:26:03 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED
22-10-25 06:32:21 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED