BAKERSFIELD FIRE DEPARTMENT
2101 H STREET, BAKERSFIELD, CA 93301
Date:8/17/22 Inspector: M.Moore
Business Name: Cal Water BK-215
Business Address: 10460 Alfred Harrel
Aboveground Petroleum Storage Tank Program -Tier I Qualified Facility Inspection Report (v 3.0)
Violation
Viol
Number
Program Requirement
Citations
Y or N
Class
Comments
Requirement to Prepare and Implement
4010001
SPCC has been prepared
HSC 6.67 25270.4.5(a),
40 CFR 1 112.3 , 112.6
4010057
SPCC plan has been prepared that meets all
HSC 6.6725270.4.5(a);
applicable requirements
40 CFR 1 112.31 112.6
4030038
SPCC has been implemented
HSC 6.6725270.4.5(a);
40 CFR 1 112.3
4010008
SPCC onsite If facility staffed 4 hrs/day, or at the
HSC 6.67 25270.4.5(a);
nearest field office if not so attended
40 CFR 1 112.3(e)(1)
4010047
Qualified Facility's SPCC plan has been self or PE
HSC 6.6725270.4.5(a);
certified.
40 CFR 1 112.6(a)(1),
112.6(b)
4010035
Facility prepared appropriate SPCC when no
HSC 6.6725270.4.5(a);
longer meeting Tier 1/II requirements
40 CFR 1 112.3(g)
SPCC Amendments
4010010
Facility has amended SPCC as necessary
HSC 6.6725270.4.5(a);
40 CFR 1 112.5(a),
112.5(b)
jk
4030039
SPCC has been implemented within 6 months
HSC 6.6725270.4.5(a);
of amendment
40 CFR 1 112.5(a),
112.5(b)
4010048
Tier I Qualified Facility has certified tech
HSC 6.6725270.4.5(a);
amendments.
40 CFR 1 112.60)(2)
Five Year Review
4010009
5 year review performed on SPCC and
HSC 6.6725270.4.5(a);
documented
40 CFR 1 112.5(b)
General SPCC Requirements
4010012
SPCC in writing, follows code seq/cross ref,—
HSC 6.6725270.4.5(a);
good eng practice, mgt approval, items not in
40 CFR 1112.7
place
4010041
SPCC Plan addresses the type of oil and storage
HSC 6.6725270.4.5(a);
capacity for all fixed and portable containers
40 CFR 1 112.7(a)(3)(i)
4010042
SPCC Plan addressed countermeasures for
HSC 6.6725270.4.5(a);
discharge discovery, response and cleanup
40 CFR 1
112.7(a) (3) (i v)
4010017
SPCC contains procedures for reporting a
HSC 6.6725270.4.5(a);
discharge
40 CFR 1 112.7(a)(3)
(vi); 112.7(a) (4)
4010018
SPCC organized so discharge procedures are
HSC 6.6725270.4.5(a);
readily usable if the facility has no response
40 CFR 1 112.7(a)(5)
plan
1
Violation
Viol
Number
Program Requirement
Citations
Y or N
Class
Comments
4010054
SPCC contains a prediction of direction and total
HSC 6.6725270.4.5(a);
40 CFR 1 112.6(a)(3)(i)
quantity of oil potentially discharged
4010020
SPCC addresses the appropriate general
HSC 6.6725270.4.5(a);
containment/diversionary
40 CFR 1 112.7(c)
structures/equipment
4030037
Appropriate (general) containment/diversionary
HSC 6.6725270.4.5(a);
structures/equipment have been provided
40 CFR 1 112.7(c)
4010023
Employee training and spill prevention briefings
HSC 6.6725270.4.5(a);
discussed in SPCC plan
40 CFR 1 112.7(f)(1),
112.7(f)(3)
4020001
Training provided for op/maint of equip,
HSC 6.6725270.4.5(a);
discharge procedures, laws/regs, general fac
40 CFR 1 112.7(f)(1)
ops, and SPCC
4010022
Person has been designated as accountable for
HSC 6.6725270.4.5(a);
discharge prevention and reports to
40 CFR 1 112.7(f)(2)
management
4030040
Spill prevention briefings are conducted
HSC 6.6725270.4.5(a);
annually
40 CFR 1 112.7(f)(3)
4010024
SPCC addresses security measures -lighting,
HSC 6.6725270.4.5(a);
access to handling/storage,
40 CFR 1 112.7(g)
valves/pumps/transfer equip
4030001
Handling areas, valves, pumps/starter controls,
HSC 6.6725270.4.5(a);
load/unload connections secured, lighting
40 CFR 1 112.7(g)
adequate
4030034
Oil filled operational equipment containment
HSC 6.6725270.4.5(a);
standards are met
40 CFR 1 112.7 (k)
SPCC Requirements for Onshore Facilities
4010027
Facility drainage or drainage controls
HSC 6.6725270.4.5(a);
adequately discussed
40 CFR 1
112.7(a)(3)(iii);
112.8(b)
;J
i
4030035
Facility drainage adequately restrained unless
HSC 6.67 25270.4.5 (a);
conditions met
40 CFR 1 112.8(b)(1)
4030005
Valves used for drainage are manual (not
HSC 6.6725270.4.5(a);
flapper -type) to prevent a discharge
40 CFR 1 112.8(b)(2)
4010029
Adequate discussion of all bulk storage
HSC 6.6725270.4.5(a);
containers located at the facility
40 CFR 1 112.8(c)
4030012
Material and construction of all containers are
HSC 6.6725270.4.5(a);
compatible with the material stored
40 CFR 1 112.8(c)(1)
4030041
All bulk storage containers have secondary
HSC 6.6725270.4.5(a);
containment to prevent a discharge at Tier 1
40 CFR 1 112.6(a)(3)(ii)
facility
4030006
Rainwater in diked areas is inspected before
HSC 6.6725270.4.5(a);
draining
40 CFR 1 112.8(c)(3)(i-
iii)
Violation
Viol
Number
Program Requirement
Citations
Y or N
Class
Comments
4010026
Records maintained of drainage from diked
HSC 6.6725270.4.5(a);
areas
40 CFR 1
112.8(c)(3)(iv)
4030017
Buried section of partially buried or bunkered
HSC 6.6725270.4.5(a);
metallic tank has corrosion protection
40 CFR 1 112.8(c)(5)
'
4010028
SPCC discusses procedures to test/inspect
HSC 6.6725270.4.5(a);
storage containers for integrity per industry
40 CFR 1 112.8(c)(6)
standards
4030014
Tanks inspected and tested by qualified person
HSC 6.6725270.4.5(a);
in accordance with industry standards
40 CFR 1 112.8(c)(6)
4030015
Aboveground containers tested or inspected for
HSC 6.6725270.4.5(a);
integrity based on industry standards
40 CFR 1 112.8(c)(6)
4010021
Inspection/integrity testing records signed, kept
HSC 6.6725270.4.5(a);
for 3 years and written inspection procedures
40 CFR 1 112.7(e),
kept
112.8(c)(6)
4010055
SPCC plan adequately describes overfill
HSC 6.6725270.4.5(a);
prevention methods, including system or
40 CFR 1
procedures used
112.6(a)(3)(iii)
4030042
Overfill prevention sytems or procedures are
HSC 6.6725270.4.5(a);
used and tested routinely to ensure proper
40 CFR 1
operation
112.6(a)(3)(iii)
4030021
Visible discharges promptly corrected and any
HSC 6.6725270.4.5(a);
accumulation of oil in diked areas promptly
40 CFR 1 112.8(c)(10)
removed.
4030026
Aboveground valves, piping, and appurtenances
HSC 6.6725270.4.5(a);
are regularly inspected
40 CFR 1 112.8(d)(4)
4030030
Integrity/leak tested buried piping when
HSC 6.6725270.4.5(a);
installed, modified, constructed, relocated, or
40 CFR 1 112.8(d)(4)
i�
replaced
•�
Oil Filled Electrical Equipment
4010037
Oil filled electrical equipment exclusions have
HSC 6.67
been met, and where not met is included in
25270.2(a)(4)
}�
SPCC plan
General Facility Requirements
4010034
Valid permit maintained
HSC 6.11 25404.1
4010032
Tank Facility Statement or Business Plan has
HSC 6.67
been submitted
25270.6(a)(1),
25270.6(a)(2)
4040001
Spills/releases of 42 gallons or more of
HSC 6.67 25270.8
petroleum reported upon discovery to Cal OES
4010033
APSA program fee paid
HSC 6.67 25270.6(b)
4030036
All/any permanently closed tanks are properly
HSC 6.6725270.4.5(a);
closed under the definition in 40 CFR 112.2
40 CFR 1 112.1(b)(3),
112.2
4010044
Substantial Harm Criteria certification
HSC 6.6725270.4.5(a);
maintained at the facility as required
40 CFR 1 112.20(e)
4010
Administration/Documentation - General
HSC 6.67, 40 CFR 1
Violation
Viol
Number
Program Requirement
Citations
Y or N
Class
Comments
4015
Administration/Documentation - General Local
Ordinance
4020
Training - General
HSC 6.671 40 CFR 1
4025
Training - General Local Ordinance
4030
Operations/Maintenance - General
HSC 6.67, 40 CFR 1
4035
Operations/Maintenance - General Local
Ordinance
4040
Release/Leaks/Spills - General
HSC 6.67, 40 CFR 1
4045
Release/Leaks/Spills - General Local Ordinance
4050
Abandonment/Illegal Disposal/Unauthorized
HSC 6.67, 40 CFR 1
Treatment - General
112
4055
Abandonment/Illegal Disposal/Unauthorized
Treatment - General Local Ordinance
Comments:
f
There were no violations noted for this inspection
❑ This report shall serve as a "NOTICE TO COMPLY" for Minor Violations, and a "NOTICE OF VIOLATION" for Major violations.
You are, hereby, ordered to correct the above noted violations within 30 days, or according to correction summaries
provided. Formal enforcement and/or penalty assessment may be initiated for any violations noted, and for those not
corrected in a timely manner. (NOTE: If this is a preliminary report, a fin will follow.)
Operator's Name: Operator's Signature: Date:
Inspector's Signature: Date.-±::