HomeMy WebLinkAbout4013 S. H St EMC (North) 5-2-2023 (Rejected - no permit)Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10159161 5/2/2023
Jaco #7721 Fastrip #22
4013 South H St Bakersfield, Ca 93304
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Isaias Palacios
1073967
8391568 9/29/2024
Veeder root B46565 03/22/2024
5/2/2023 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS-350 336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 87 STP
L2 420 87 Annular
L3 208 91 STP
L4 420 91 Annular
L5 208 DSL STP
L6 420 DSL Annular
L7 NA
L8 NA
L9 208 Dispenser 9/10
L10 208 Dispenser 11/12
L11 208 Dispenser 13/14
L12 208 Dispenser 15/16
L13 208 Dispenser 17/18
L14 208 Dispenser 19/20
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V Unleaded
T2 FX1V Premium
T3 FX1DV DSL
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Performed EMC testing due to cold-start.
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
F
EXISTING BUILDING
NOPARKING
56L11
#7-781
78L10 34L12
12L9
12,000 GALLON87-1 UNLEADED
12,000 GALLON87-2 UNLEADED
12,000 GALLONPREMIUM
12,000 GALLONDIESEL
V AL2 STPL1
FV AL6 STPL5
FV AL8 STPL7
F AL4 STPL3 109L91413L121211L101615L122019L141817L1312,000 GALLON87 UNLEADED12,000 GALLONPREMIUM12,000 GALLONDIESELFAL6STPL5FVAL4STPL3FVAL2STPL1NOPARKING
G
W
7-721
7-781
#7-721DUMPSTER H
H
PRICE SIGN
PRICE SIGN
40' STORAGE CONTA
INER
S. H ST.WHITE LN.PROPERTY LINE
PROPERTY LINE
N
CAT
C
HBAS
I
N
721 LEGEND
L1 87 STP
L2 87 ANNULAR
L3 91 STP
L4 91 ANNULAR
L5 DSL STP
L6 DSL ANNULAR
L9 UDC 9 - 10
L10 UDC 11 -12
L11 UDC 13 - 14
L12 UDC 15 - 16
L13 UDC 17 - 18
L14 UDC 19 - 20
781 LEGEND
L1 87-1 STP
L2 87-1 ANNULAR
L3 DSL STP
L4 DSL ANNULAR
L5 87-2 STP
L6 87-2 ANNULAR
L7 91 STP
L8 91 ANNULAR
L9 UDC 1 -2
L10 UDC 7 - 8
L11 UDC 5 -6
L12 UDC 3 - 4
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 3/2 INCH DOUBLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
UST ELECTRICAL PANEL
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
W
G
A
H
P
V
SCALE:
SITE MAP
C1
VICINITY MAP
PROJECT DATA
3/32"=1'-0"
INCHES012
SHEET SIZE 22 X 34
4013 S. H ST.
BAKERSFIELD, CA 93304
PROJECT OWNER:
JAMIESON HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FASTRIP #7721
FACILITY ID 15-021-100296
CERS ID 10159161
FASTRIP #7781
FACILITY ID 15-021-003022
CERS ID 10159163
4013 S. H ST.
BAKERSFIELD, CA 93304
03/02/17 REV.S. H ST.WHITE LN.
Jaco#7721 Cold Start Alarm History After.
Responses Received:
I10200
MAY 2, 2023 5:14 PM
FASTRIP
4013 S H ST
BAKERSFIELD
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 507550 505805
2 INTERSTITIAL BD 202297 202007
3 4 PROBE / G.T. 163116 162771
4 INTERSTITIAL BD 201119 200726
5 UNUSED 4925158 4902879
6 UNUSED 4919506 4900889
7 UNUSED 4918637 4902070
8 UNUSED 4915441 4900146
9 STP SENSE BOARD 33132 33095
10 RELAY BOARD 15000 14963
11 UNUSED 4922919 4904339
12 UNUSED 4919289 4900140
13 UNUSED 4917137 4902545
14 UNUSED 4916680 4899877
15 UNUSED 4918050 4900643
16 UNUSED 4917224 4899221
COMM 1 ELEC DISP INT. 101140 101005
COMM 2 RS232 SERIAL BD 15000 15007
COMM 3 RS232 SERIAL BD 14956 14963
COMM 4 UNUSED 4920137 4902917
COMM 5 UNUSED 4916876 4901977
COMM 6 UNUSED 4916267 4903705
I90200
MAY 2, 2023 5:14 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
MAY 2, 2023 5:14 PM
FASTRIP
4013 S H ST
BAKERSFIELD
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L10 DISP PAN 11-12 SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L12 DISP PAN 15-16 SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L14 DISP PAN 19-20 SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L11 DISP PAN 13-14 SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L 9 DISP PAN 9-10 SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L13 DISP PAN 17-18 SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L 5 STP SUMP DEISE STP SENSOR OUT ALARM CLEAR 5-02-23 5:04PM
L12 DISP PAN 15-16 SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L14 DISP PAN 19-20 SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L11 DISP PAN 13-14 SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L13 DISP PAN 17-18 SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L10 DISP PAN 11-12 SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L 9 DISP PAN 9-10 SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L 1 STP SUMP 87 STP SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L 5 STP SUMP DEISE STP SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 5-02-23 5:03PM
L12 DISP PAN 15-16 FUEL ALARM CLEAR 5-02-23 5:01PM
L12 DISP PAN 15-16 FUEL ALARM ALARM 5-02-23 5:01PM
L11 DISP PAN 13-14 FUEL ALARM CLEAR 5-02-23 5:01PM
L11 DISP PAN 13-14 FUEL ALARM ALARM 5-02-23 5:01PM
L10 DISP PAN 11-12 FUEL ALARM CLEAR 5-02-23 5:01PM
L10 DISP PAN 11-12 FUEL ALARM ALARM 5-02-23 5:01PM
L 2 ANNULAR 87 ANN FUEL ALARM CLEAR 5-02-23 5:01PM
L 2 ANNULAR 87 ANN FUEL ALARM ALARM 5-02-23 5:01PM
L 3 STP SUMP 91 STP FUEL ALARM CLEAR 5-02-23 5:01PM
L 3 STP SUMP 91 STP FUEL ALARM ALARM 5-02-23 5:01PM
L 4 ANNULAR 91 ANN FUEL ALARM CLEAR 5-02-23 5:00PM
L 4 ANNULAR 91 ANN FUEL ALARM ALARM 5-02-23 5:00PM
L12 DISP PAN 15-16 FUEL ALARM CLEAR 5-02-23 5:00PM
L12 DISP PAN 15-16 FUEL ALARM ALARM 5-02-23 5:00PM
L 5 STP SUMP DEISE STP FUEL ALARM CLEAR 5-02-23 5:00PM
L 5 STP SUMP DEISE STP FUEL ALARM ALARM 5-02-23 5:00PM
L13 DISP PAN 17-18 FUEL ALARM CLEAR 5-02-23 5:00PM
L13 DISP PAN 17-18 FUEL ALARM ALARM 5-02-23 5:00PM
L 6 ANNULAR DSL ANN FUEL ALARM CLEAR 5-02-23 5:00PM
L 6 ANNULAR DSL ANN FUEL ALARM ALARM 5-02-23 5:00PM
L 9 DISP PAN 9-10 FUEL ALARM CLEAR 5-02-23 4:59PM
L 9 DISP PAN 9-10 FUEL ALARM ALARM 5-02-23 4:59PM
L 1 STP SUMP 87 STP FUEL ALARM CLEAR 5-02-23 4:59PM
L 1 STP SUMP 87 STP FUEL ALARM ALARM 5-02-23 4:59PM
L14 DISP PAN 19-20 FUEL ALARM CLEAR 5-02-23 4:59PM
L14 DISP PAN 19-20 FUEL ALARM ALARM 5-02-23 4:59PM
I11200
MAY 2, 2023 5:15 PM
FASTRIP
4013 S H ST
BAKERSFIELD
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
I20600
MAY 2, 2023 5:15 PM
FASTRIP
4013 S H ST
BAKERSFIELD
TANK ALARM HISTORY
TANK 1 87
TANK 2 91
TANK 3 DSL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
MAY 2, 2023 5:15 PM
I30200
MAY 2, 2023 5:15 PM
FASTRIP
4013 S H ST
BAKERSFIELD
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 STP
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 4:59 PM FUEL ALARM
2 87 ANN
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 5:01 PM FUEL ALARM
3 91 STP
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 5:01 PM FUEL ALARM
4 91 ANN
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 5:00 PM FUEL ALARM
5 DEISE STP
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 5:00 PM FUEL ALARM
6 DSL ANN
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 5:00 PM FUEL ALARM
9 9-10
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 4:59 PM FUEL ALARM
10 11-12
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 5:01 PM FUEL ALARM
11 13-14
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 5:01 PM FUEL ALARM
12 15-16
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 5:01 PM FUEL ALARM
MAY 2, 2023 5:00 PM FUEL ALARM
13 17-18
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 5:00 PM FUEL ALARM
14 19-20
MAY 2, 2023 5:03 PM SENSOR OUT ALARM
MAY 2, 2023 4:59 PM FUEL ALARM
I31600
MAY 2, 2023 5:15 PM
FASTRIP
4013 S H ST
BAKERSFIELD
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VPS
2 FM1
3 FM2
4 FM3
5 FM4
6 FM5
7 FM6
I40200
MAY 2, 2023 5:15 PM
I40300
MAY 2, 2023 5:15 PM
I34200
MAY 2, 2023 5:15 PM
I34700
MAY 2, 2023 5:15 PM
IV0100
MAY 2, 2023 5:15 PM
FASTRIP
4013 S H ST
BAKERSFIELD
ISD ALARM STATUS REPORT
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-04-17 00:00:45 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
23-04-16 00:00:32 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
23-04-14 00:00:28 A/L RATIO DEGRADATION FP 2 BLEND3 0.79
23-04-13 00:00:15 A/L RATIO DEGRADATION FP 3 BLEND3 0.55
23-04-12 00:01:12 A/L RATIO DEGRADATION FP 3 BLEND3 0.55
23-04-11 00:01:07 A/L RATIO DEGRADATION FP 3 BLEND3 0.55
23-04-03 10:01:33 A/L RATIO DEGRADATION FP 3 BLEND3 0.54
23-04-02 10:01:52 A/L RATIO DEGRADATION FP 3 BLEND3 0.76
23-04-01 10:01:38 A/L RATIO DEGRADATION FP 3 BLEND3 0.77
23-03-06 00:01:25 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.44
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-03-07 00:02:17 A/L RATIO DEGRADATION FP 4 BLEND3 0.79
23-01-24 00:01:42 A/L RATIO DEGRADATION FP 2 BLEND3 0.76
23-01-23 00:01:35 A/L RATIO DEGRADATION FP 2 BLEND3 0.76
23-01-22 00:01:37 A/L RATIO DEGRADATION FP 2 BLEND3 0.78
23-01-21 00:01:24 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-01-20 00:01:21 A/L RATIO DEGRADATION FP 2 BLEND3 0.79
23-01-18 00:01:01 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-01-06 00:00:49 A/L RATIO DEGRADATION FP 2 BLEND3 0.79
23-01-05 00:00:46 A/L RATIO DEGRADATION FP 2 BLEND3 0.78
23-01-04 00:00:49 A/L RATIO DEGRADATION FP 2 BLEND3 0.78
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-05-02 17:04:21 READINESS ISD:PF EVR:NNN CHECK ISD SENSORS
23-05-02 17:04:21 ISD STARTUP
23-05-02 17:04:15 ISD SHUTDOWN
23-05-02 15:15:00 TIME CHANGE DETECTED AT: 23-05-02 08:18:27
23-05-02 08:18:04 TIME CHANGE DETECTED AT: 21-02-13 08:18:03
23-04-29 00:00:28 READINESS ISD:PP EVR:NP EVR READINESS PENDING
23-04-28 00:00:45 READINESS ISD:PP EVR:NP EVR READINESS PENDING
23-04-27 00:00:59 READINESS ISD:PP EVR:NP EVR READINESS PENDING
23-04-26 00:00:48 READINESS ISD:PP EVR:NP EVR READINESS PENDING
23-04-25 00:00:50 READINESS ISD:PP EVR:NP EVR READINESS PENDING
Setup
Responses Received:
200
FASTRIP
4013 S H ST
BAKERSFIELD
MAY 2, 2023 5:15 PM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 87 8105 61.40 0.0 65.6 3895
2 91 10498 78.45 0.0 69.9 1502
3 DSL 1988 21.35 0.0 73.4 10012
I90500
MAY 2, 2023 5:16 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
MAY 2, 2023 5:16 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
MAY 2, 2023 5:16 PM
SHIFT TIME 1 : 6:00 AM
I50202
MAY 2, 2023 5:16 PM
SHIFT TIME 2 : DISABLED
I50203
MAY 2, 2023 5:16 PM
SHIFT TIME 3 : DISABLED
I50204
MAY 2, 2023 5:16 PM
SHIFT TIME 4 : DISABLED
I54600
MAY 2, 2023 5:16 PM
TANK PER TST NEEDED WRN: DISABLED
I54900
MAY 2, 2023 5:16 PM
TANK ANN TST NEEDED WRN: DISABLED
I55300
MAY 2, 2023 5:16 PM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
MAY 2, 2023 5:16 PM
LINE PER TST NEEDED WRN: DISABLED
I55900
MAY 2, 2023 5:16 PM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
MAY 2, 2023 5:16 PM
PRINT TC VOLUMES
ENABLED
I50E00
MAY 2, 2023 5:16 PM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
MAY 2, 2023 5:16 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
MAY 2, 2023 5:16 PM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
MAY 2, 2023 5:16 PM
DAYLIGHT SAVING TIME
DISABLED
I51B00
MAY 2, 2023 5:16 PM
I51600
MAY 2, 2023 5:16 PM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
MAY 2, 2023 5:16 PM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
MAY 2, 2023 5:16 PM
TANK CHART SECURITY
DISABLED
I5BD00
MAY 2, 2023 5:16 PM
CUSTOM ALARM LABELS
DISABLED
I56000
MAY 2, 2023 5:16 PM
MASS/DENSITY
DISABLED
I88101
MAY 2, 2023 5:16 PM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
MAY 2, 2023 5:16 PM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
MAY 2, 2023 5:16 PM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 2 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
MAY 2, 2023 5:16 PM
I88105
MAY 2, 2023 5:16 PM
I88106
MAY 2, 2023 5:16 PM
I52000
MAY 2, 2023 5:16 PM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE JUN 30, 2022 DISABLED
2 ON DATE JUN 30, 2022 DISABLED
3 ON DATE JUN 30, 2022 DISABLED
4 ON DATE JUN 30, 2022 DISABLED
5 ON DATE JUN 30, 2022 DISABLED
6 ON DATE JUN 30, 2022 DISABLED
7 ON DATE JUN 30, 2022 DISABLED
8 ON DATE JUN 30, 2022 DISABLED
I60100
MAY 2, 2023 5:16 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 87 ON
2 91 ON
3 DSL ON
4 OFF
I60200
MAY 2, 2023 5:16 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 87
2 91
3 DSL
4
I60300
MAY 2, 2023 5:16 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 87 1
2 91 2
3 DSL 3
4 4
I60900
MAY 2, 2023 5:16 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 87 0.000700
2 91 0.000700
3 DSL 0.000450
4 0.000000
I60700
MAY 2, 2023 5:16 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 87 96.00
2 91 96.00
3 DSL 96.00
4 0.00
I60A00
MAY 2, 2023 5:16 PM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 87
1 PT 12000 2 91 1 PT 12000 3 DSL
1 PT 12000 4 1 PT 0
I60400
MAY 2, 2023 5:16 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 87 12000
2 91 12000
3 DSL 12000
4 0
I60500
MAY 2, 2023 5:16 PM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 87 12000 0 0 0
2 91 12000 0 0 0
3 DSL 12000 0 0 0
4 0 0 0 0
I60600
MAY 2, 2023 5:16 PM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 87 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 91 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DSL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
MAY 2, 2023 5:16 PM
TANK PRODUCT LABEL METER DATA
1 87 NO
2 91 NO
3 DSL NO
4 NO
I62F00
MAY 2, 2023 5:16 PM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 87 4.0 IN.
2 91 4.0 IN.
3 DSL 4.0 IN.
I62700
MAY 2, 2023 5:16 PM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 87 2.0
2 91 2.0
3 DSL 2.0
I64200
MAY 2, 2023 5:16 PM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 87 LOW
2 91 LOW
3 DSL LOW
I62400
MAY 2, 2023 5:16 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 87 3.0
2 91 3.0
3 DSL 3.0
I62800
MAY 2, 2023 5:16 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 87 12000
2 91 12000
3 DSL 12000
4 0
I62300
MAY 2, 2023 5:16 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 87 10800
2 91 10800
3 DSL 10800
4 0
I62200
MAY 2, 2023 5:16 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 87 11400
2 91 11400
3 DSL 11400
4 0
I62900
MAY 2, 2023 5:16 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 87 1200
2 91 1200
3 DSL 1200
4 0
I62100
MAY 2, 2023 5:16 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 87 1200
2 91 1200
3 DSL 1200
4 0
I62600
MAY 2, 2023 5:16 PM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 87 99
2 91 99
3 DSL 99
4 99
I62500
MAY 2, 2023 5:16 PM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 87 99
2 91 99
3 DSL 99
4 99
I60800
MAY 2, 2023 5:16 PM
TANK TILT
TANK PRODUCT LABEL INCHES
1 87 0.00
2 91 0.00
3 DSL 0.00
4 0.00
I60B00
MAY 2, 2023 5:16 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
MAY 2, 2023 5:16 PM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 87 0.00
2 91 0.00
3 DSL 0.00
4 0.00
I61200
MAY 2, 2023 5:16 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 87 NONE NONE
2 91 NONE NONE
3 DSL NONE NONE
4 NONE NONE
I63600
MAY 2, 2023 5:16 PM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 87 120
2 91 120
3 DSL 120
4 0
I62A00
MAY 2, 2023 5:16 PM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 87 120
2 91 120
3 DSL 120
4 0
I62C00
MAY 2, 2023 5:16 PM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 87 STANDARD
2 91 STANDARD
3 DSL STANDARD
4 STANDARD
I62D00
MAY 2, 2023 5:16 PM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 87 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 91 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DSL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
MAY 2, 2023 5:16 PM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 87 OFF OFF
2 91 OFF OFF
3 DSL OFF OFF
4 OFF OFF
I63000
MAY 2, 2023 5:16 PM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 87 OFF
2 91 OFF
3 DSL OFF
4 OFF
I63200
MAY 2, 2023 5:16 PM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 87 OFF
2 91 OFF
3 DSL OFF
4 OFF
I61000
MAY 2, 2023 5:16 PM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 87 1
2 91 1
3 DSL 1
4 1
I63A00
MAY 2, 2023 5:16 PM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 87 10.00%
2 91 10.00%
3 DSL 10.00%
4 10.00%
I61100
MAY 2, 2023 5:16 PM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
FEB 13, 2021
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
MAY 2, 2023 5:16 PM
CSLD PROBABLITY OF DETECTION
I61400
MAY 2, 2023 5:16 PM
CSLD CLIMATE FACTOR
I61600
MAY 2, 2023 5:16 PM
TANK PRODUCT LABEL CAL UPDATE
1 87 IMMEDIATE
2 91 IMMEDIATE
3 DSL IMMEDIATE
4 IMMEDIATE
I61A00
MAY 2, 2023 5:16 PM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 87 DISABLED
2 91 DISABLED
3 DSL DISABLED
4 DISABLED
I61B00
MAY 2, 2023 5:16 PM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
MAY 2, 2023 5:16 PM
CSLD REPORT ONLY
I62B00
MAY 2, 2023 5:16 PM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 87 ??? 0, 0
2 91 ??? 0, 0
3 DSL ??? 0, 0
4 ??? 0, 0
I63300
MAY 2, 2023 5:16 PM
LEAK TEST REPORT FORMAT: NORMAL
I63400
MAY 2, 2023 5:16 PM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 87 0
2 91 0
3 DSL 0
4 0
I63500
MAY 2, 2023 5:16 PM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 87 1
2 91 1
3 DSL 1
4 1
I63900
MAY 2, 2023 5:16 PM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 87
END FACTOR: NONE
2 91
END FACTOR: NONE
3 DSL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
MAY 2, 2023 5:16 PM
I77700
MAY 2, 2023 5:16 PM
I77800
MAY 2, 2023 5:16 PM
I78C00
MAY 2, 2023 5:16 PM
I78300
MAY 2, 2023 5:16 PM
I78F00
MAY 2, 2023 5:16 PM
I78700
MAY 2, 2023 5:16 PM
I70200
MAY 2, 2023 5:16 PM
LIQUID LABEL
DEVICE LABEL
1 87 STP
2 87 ANN
3 91 STP
4 91 ANN
5 DEISE STP
6 DSL ANN
7
8
9 9-10
10 11-12
11 13-14
12 15-16
13 17-18
14 19-20
15
16
I70300
MAY 2, 2023 5:16 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87 STP TRI-STATE (SINGLE FLOAT)
2 87 ANN TRI-STATE (SINGLE FLOAT)
3 91 STP TRI-STATE (SINGLE FLOAT)
4 91 ANN TRI-STATE (SINGLE FLOAT)
5 DEISE STP TRI-STATE (SINGLE FLOAT)
6 DSL ANN TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
9 9-10 TRI-STATE (SINGLE FLOAT)
10 11-12 TRI-STATE (SINGLE FLOAT)
11 13-14 TRI-STATE (SINGLE FLOAT)
12 15-16 TRI-STATE (SINGLE FLOAT)
13 17-18 TRI-STATE (SINGLE FLOAT)
14 19-20 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
MAY 2, 2023 5:16 PM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 87 STP STP SUMP
2 87 ANN ANNULAR SPACE
3 91 STP STP SUMP
4 91 ANN ANNULAR SPACE
5 DEISE STP STP SUMP
6 DSL ANN ANNULAR SPACE
7 OTHER SENSORS
8 OTHER SENSORS
9 9-10 DISPENSER PAN
10 11-12 DISPENSER PAN
11 13-14 DISPENSER PAN
12 15-16 DISPENSER PAN
13 17-18 DISPENSER PAN
14 19-20 DISPENSER PAN
15 OTHER SENSORS
16 OTHER SENSORS
I74200
MAY 2, 2023 5:16 PM
I74300
MAY 2, 2023 5:16 PM
I74400
MAY 2, 2023 5:16 PM
I74700
MAY 2, 2023 5:16 PM
I74800
MAY 2, 2023 5:16 PM
I74900
MAY 2, 2023 5:16 PM
I7BC00
MAY 2, 2023 5:16 PM
I80200
MAY 2, 2023 5:16 PM
I80300
MAY 2, 2023 5:16 PM
I80400
MAY 2, 2023 5:17 PM
I80700
MAY 2, 2023 5:17 PM
RELAY LABEL
DEVICE LABEL
1 87
2 91
3 DSL
4 OVERFILL
I80900
MAY 2, 2023 5:17 PM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 87 NORMALLY OPEN
2 91 NORMALLY OPEN
3 DSL NORMALLY CLOSED
4 OVERFILL NORMALLY OPEN
I80B00
MAY 2, 2023 5:17 PM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 87 1
2 91 2
3 DSL NONE
4 OVERFILL 4
I80A00
MAY 2, 2023 5:17 PM
RELAY TYPE
RELAY DESIGNATION TYPE
1 87 PUMP CONTROL OUTPUT
2 91 PUMP CONTROL OUTPUT
3 DSL STANDARD
4 OVERFILL STANDARD
I80C00
MAY 2, 2023 5:17 PM
I80800
MAY 2, 2023 5:17 PM
RELAY SETUP REPORT
R 1:87
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 1:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 1:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L14:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 2:91
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 3:DSL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: NONE
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 5:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 5:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
R 4:OVERFILL
TYPE:
STANDARD
NORMALLY OPEN
TANK #: 4
IN-TANK ALARMS
ALL:LEAK ALARM
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
I79000
MAY 2, 2023 5:17 PM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
MAY 2, 2023 5:17 PM
I72300
MAY 2, 2023 5:17 PM
FASTRIP
4013 S H ST
BAKERSFIELD
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VPS VAPOR PRESSURE
02 FM1 AIR FLOW METER
03 FM2 AIR FLOW METER
04 FM3 AIR FLOW METER
05 FM4 AIR FLOW METER
06 FM5 AIR FLOW METER
07 FM6 AIR FLOW METER
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
MAY 2, 2023 5:17 PM
FASTRIP
4013 S H ST
BAKERSFIELD
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: VAPOR VAC
IV4F00
MAY 2, 2023 5:17 PM
FASTRIP
4013 S H ST
BAKERSFIELD
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
MAY 2, 2023 5:17 PM
FASTRIP
4013 S H ST
BAKERSFIELD
VAPOR PROCESSOR TYPE
NONE
IV4700
MAY 2, 2023 5:17 PM
FASTRIP
4013 S H ST
BAKERSFIELD
ASSESSMENT TIME
START TIME: 11:59 PM
TIME DELAY MINUTES: 1
IV5200
MAY 2, 2023 5:17 PM
FASTRIP
4013 S H ST
BAKERSFIELD
ACCEPT HIGH ORVR: NO
IV4A00
MAY 2, 2023 5:17 PM
FASTRIP
4013 S H ST
BAKERSFIELD
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 09 01 02 BLEND3
02 02 10 01 02 BLEND3
03 03 11 02 02 BLEND3
04 04 12 02 02 BLEND3
05 05 13 03 02 BLEND3
06 06 14 03 02 BLEND3
07 07 15 04 02 BLEND3
08 08 16 04 02 BLEND3
09 09 17 05 02 BLEND3
10 10 18 05 02 BLEND3
11 11 19 06 02 BLEND3
12 12 20 06 02 BLEND3
IV4B00
MAY 2, 2023 5:17 PM
FASTRIP
4013 S H ST
BAKERSFIELD
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
09 05 02/09 03/09 09/09 xx/xx
10 05 02/10 03/10 09/10 xx/xx
11 06 03/11 09/11 02/11 xx/xx
12 06 02/12 03/12 09/12 xx/xx
IV4900
MAY 2, 2023 5:17 PM
FASTRIP
4013 S H ST
BAKERSFIELD
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
MAY 2, 2023 5:17 PM
ISD VERSION: 01.07