HomeMy WebLinkAbout2023 FMC and OPI Repair1
Jennifer Pruitt
Subject:SA002, AT&T Probe Certification - PO-28045493 w/Overfill Test (BKFDCA01), Bakersfield
Location:1520 20TH ST, BAKERSFIELD, CA 93301-4406
Start:Mon 4/3/2023 9:00 AM
End:Mon 4/3/2023 11:00 AM
Recurrence:(none)
Meeting Status:Meeting organizer
Organizer:Simplex Communication
Required Attendees:AGUILAR, ADOLFO; MEDINA, ELOISA; 'FLORES, CECILIA'; AT&T CA Testing; 'HAYN, CINDY H (ATTSI)'
(ch1921@att.com) ; Carlos Cardenas; Jennifer Pruitt; Maria Figueroa; Krystine Gossett; Alan
Throckmorton; Randy Novak; Kristin Reynolds; Erin Langford; Jon Larsen
Categories:Probe Certification, Overfill Alarm Testing, Legacy T Site
There is an AT&T Probe Certification scheduled for this location on the date and time indicated.
NOTE: -PO- 28045493 (Tait) will be addressed at this time.
-Recertify the new probe
-Testing will include the Overfill Test of the Overfill alarm
-Permit Required for repairs made
-Permit # TBD
SA002 1520 20TH ST BAKERSFIELD 93301-4406
Please contact the Compliance Manager with any questions and/or comments at:
simplexcommunication@tait.com
714.560.8200
Environmental Health/CUPA Contact Information:
Bakersfield City Fire Department
2101 H Street
Bakersfield, CA 93301
Method of Notification: Email
Contact (Once Permit is Approved):
https://www.bakersfieldcity.us/1048/Inspection‐Request
Test Results Submittal: USTResults@bakersfieldfire.us
1
Jennifer Pruitt
From:Luke Preece <lpreece@bakersfieldfire.us>
Sent:Friday, March 17, 2023 4:13 PM
To:Carlos Cardenas
Subject:RE: New Fire Inspection Request (SA002 - Bakersfield)
External Email.
Carlos,
You are confirmed for 4/3 @ 9am.
Thank you,
From: WebMaster <WebMaster@bakersfieldcity.us>
Sent: Friday, March 10, 2023 5:24 PM
To: InspectionRequest <InspectionRequest@bakersfieldfire.us>
Subject: New Fire Inspection Request
Importance: Low
There is a new Fire Inspection Request.
Carlos Cardenas
(909) 230‐8256
ccardenas@tait.com
1520 20th St, Bakersfield, CA, 93301, USA
1520
Underground_Storage_Tank
We will be recertifying the new probe and also performing the overfill prevention test of the overfill alarm.
Luke Preece
Fire Prevention/Environmental Officer
Bakersfield Fire Department
email: lpreece@bakersfieldfire.us
web: www.bakersfieldfire.us
phone: 661-326-3659
Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
SA002
✔
10029370 04/03/2023
Pacific Bell Telephone Co. dba AT&T California
1520 20th St.Bakersfield 93301
TAIT Environmental Services, Inc. (714) 560-8222
701 N. Parkcenter Dr., Santa Ana, CA 92705
Jon Larsen
588098
8144945 05/03/2024
VeederRoot B41757 03/04/2025
04/03/2023
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either;܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications?܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid?܆܆܆܆
Are the audible and visual alarms operational?܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational?܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment?܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed?܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational?܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment?܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected?܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply)܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational?܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS 350 Plus 120.00
✔✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated?܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected?܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected?܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected?܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected?܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test?܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks?܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed?܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements?܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
✔
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults?܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational?܆܆ ܆܆ ܆܆
Was accuracy of system’s product level readings tested?܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested?܆܆ ܆܆ ܆܆
Were all probes reinstalled properly?܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed?܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
✔
✔
✔
✔
✔
✔
T-1 846397-105 / 590391 SA002U001 ATG Probe
✔
Certify ATG Probe only.
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
03/29/2023
Appendix IX
Underground Storage Tank
Overfill Prevention Equipment Inspection Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council, OPE = Overfill Prevention Equipment
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 36 Month
1. FACILITY INFORMATION
CERS ID Inspection Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Inspection Phone
Mailing Address
Service Technician Performing Inspection
Contractor/Tank Tester License Number
ICC Number Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. INSPECTION PROCEDURES INFORMATION
Inspection Procedures Used Components Inspected
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING INSPECTION
I hereby certify that the OPE was inspected in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.2; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date Total # of Pages
SA002
✔
10029370 4/3/2023
Pacific Bell Telephone Co. dba AT&T California
1520 20th St. Bakersfield 93301
TAIT Environmental Services, Inc. (714) 560-8222
701 N. Parkcenter Dr., Santa Ana, CA 92705
Jon Larsen
588098
8144945 05/03/2024
VeederRoot B41757 03/04/2025
Manufacture Guidelines SA002U001 ATG Probe
4/3/2023
Underground Storage Tank
Overfill Prevention Equipment Inspection Report
Additional copies of this page may be attached.
Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s)
Page 2 of 2
6. OVERFILL PREVENTION EQUIPMENT DETAILS
Tank ID (one OPE per column)
Are both vent and tank riser piping
secondarily contained?
܆܆ Yes
܆܆ No
܆܆ Yes
܆܆ No
܆܆ Yes
܆܆ No
܆܆ Yes
܆܆ No
OPE Model
What is the OPE response when activated?
(Check all that apply.)
܆܆ Shut off
Flow
܆܆Restricts
Flow
܆܆ Audible
Alarm
܆܆ Visual
Alarm
܆܆ Shut off
Flow
܆܆Restricts
Flow
܆܆ Audible
Alarm
܆܆ Visual
Alarm
܆܆ Shut off
Flow
܆܆Restricts
Flow
܆܆ Audible
Alarm
܆܆ Visual
Alarm
܆܆ Shut off
Flow
܆܆Restricts
Flow
܆܆ Audible
Alarm
܆܆ Visual
Alarm
Are flow restrictors installed on vent piping
that may interfere with the OPE operation?
܆܆ Yes
܆܆ No
܆܆ Yes
܆܆ No
܆܆ Yes
܆܆ No
܆܆ Yes
܆܆ No
At what level in the tank is the OPE set to
activate? (Inches from bottom of tank)
What is the percent capacity of the tank at
which the OPE activates?
Is the OPE in proper operating condition to
respond when the stored substance
reaches the designated regulatory level?
܆܆ Yes
܆܆ No
܆܆ Yes
܆܆ No
܆܆ Yes
܆܆ No
܆܆ Yes
܆܆ No
7. SUMMARY OF TESTING RESULTS
OPE Inspection Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all results marked “Fail” and each proposed remedy.
* Mark here if:
܆܆ Flow restrictors interfere with overfill prevention and equipment repairs required.
SA002U001
790091-001
✔
✔
✔
69.2"
90%
✔
✔
I50301
APR 4, 2023 6:49 AM
# 1:BKFDCA01 SA002 T-S
I50302
APR 4, 2023 6:49 AM
# 2:1520 20TH ST
I50303
APR 4, 2023 6:49 AM
# 3:BAKERSFIELD,CA 93301
I50304
APR 4, 2023 6:49 AM
# 4:661-869-1846
I51700
APR 4, 2023 6:49 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50F00
APR 4, 2023 6:49 AM
MON DD YYYY HH:MM:SS xM
I10200
APR 4, 2023 6:49 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 162295 162126
2 INTERSTITIAL BD 201439 200914
3 UNUSED 15000000 15000000
4 UNUSED 15000000 15000000
5 UNUSED 15000000 15000000
6 UNUSED 15000000 15000000
7 UNUSED 15000000 15000000
8 UNUSED 15000000 15000000
9 RELAY BOARD 14933 14932
10 COMBO I/O BOARD 9929 9936
11 UNUSED 15000000 15000000
12 UNUSED 15000000 15000000
13 UNUSED 15000000 15000000
14 UNUSED 15000000 15000000
15 UNUSED 15000000 15000000
16 UNUSED 15000000 15000000
COMM 1 FAXMODEM BOARD 40571 40561
COMM 2 UNUSED 15000000 15000000
COMM 3 UNUSED 15000000 15000000
COMM 4 UNUSED 15000000 15000000
COMM 5 UNUSED 15000000 15000000
COMM 6 UNUSED 15000000 15000000
I60100
APR 4, 2023 6:49 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK#SA002U001 ON
2 DIESEL TK#SA002A002 ON
3 OFF
4 OFF
I60200
APR 4, 2023 6:49 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK#SA002U001
2 DIESEL TK#SA002A002
3
4
I60300
APR 4, 2023 6:49 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK#SA002U001 1
2 DIESEL TK#SA002A002 1
3 3
4 4
I60400
APR 4, 2023 6:49 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 8002
2 DIESEL TK#SA002A002 250
3 0
4 0
I60700
APR 4, 2023 6:49 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA002U001 82.00
2 DIESEL TK#SA002A002 30.00
3 0.00
4 0.00
I60900
APR 4, 2023 6:50 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK#SA002U001 0.000450
2 DIESEL TK#SA002A002 0.000450
3 0.000000
4 0.000000
I61200
APR 4, 2023 6:50 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL MANIFOLDED TANKS
1 DIESEL TK#SA002U001 NONE
2 DIESEL TK#SA002A002 NONE
3 NONE
4 NONE
I62100
APR 4, 2023 6:50 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 4000
2 DIESEL TK#SA002A002 105
3 0
4 0
I62200
APR 4, 2023 6:50 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 7601
2 DIESEL TK#SA002A002 237
3 0
4 0
I62300
APR 4, 2023 6:50 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 7201
2 DIESEL TK#SA002A002 225
3 0
4 0
I62400
APR 4, 2023 6:50 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA002U001 2.0
2 DIESEL TK#SA002A002 2.0
I62800
APR 4, 2023 6:50 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 8002
2 DIESEL TK#SA002A002 250
3 0
4 0
I62900
APR 4, 2023 6:50 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 4000
2 DIESEL TK#SA002A002 125
3 0
4 0
I70300
APR 4, 2023 6:50 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 FILL SUMP TRI-STATE (SINGLE FLOAT)
2 PIPING SUMP TRI-STATE (SINGLE FLOAT)
3 DAYTANK RUPTURE BASN TRI-STATE (SINGLE FLOAT)
4 DAY TANK ANNULAR TRI-STATE (SINGLE FLOAT)
5 ANNULAR UST TRI-STATE (SINGLE FLOAT)
6 TRANSITION SUMP TRI-STATE (SINGLE FLOAT)
7 REMOTE PUMP CABINET TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
I90200
APR 4, 2023 6:50 AM
SOFTWARE REVISION LEVEL
VERSION 120.00
SOFTWARE# 346120-100-A
CREATED - 00.07.28.15.33
S-MODULE# 330160-002-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
I11100
APR 4, 2023 6:50 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK#SA002U001 HIGH WATER ALARM CLEAR 4-03-23 9:10AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 4-03-23 9:10AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 4-03-23 9:09AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER ALARM ALARM 4-03-23 9:06AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM CLEAR 4-03-23 9:03AM
T 1 TANK DIESEL TK#SA002U001 MAX PRODUCT ALARM CLEAR 4-03-23 9:02AM
T 1 TANK DIESEL TK#SA002U001 MAX PRODUCT ALARM ALARM 4-03-23 9:01AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM ALARM 4-03-23 9:01AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM CLEAR 4-03-23 9:01AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM ALARM 4-03-23 8:59AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM CLEAR 4-03-23 8:59AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 4-03-23 8:58AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 4-03-23 8:57AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM ALARM 4-03-23 8:57AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 3-15-23 9:58AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 3-15-23 9:54AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM CLEAR 3-15-23 9:50AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM ALARM 3-15-23 9:49AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER ALARM CLEAR 3-15-23 9:45AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 3-15-23 9:45AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 3-15-23 9:44AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER ALARM ALARM 3-15-23 9:41AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM CLEAR 3-15-23 9:34AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM ALARM 3-15-23 9:32AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM CLEAR 3-15-23 9:20AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 3-15-23 9:19AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 3-15-23 9:03AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM CLEAR 1-09-23 10:04AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM ALARM 1-09-23 10:04AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM CLEAR 1-09-23 9:33AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM ALARM 1-09-23 9:33AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM CLEAR 1-09-23 9:32AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM ALARM 1-09-23 9:32AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 1-09-23 9:22AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 1-09-23 9:14AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 1-09-23 9:13AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 1-09-23 9:13AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 1-09-23 9:13AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 1-09-23 9:09AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 1-09-23 9:09AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 1-09-23 9:08AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 1-09-23 9:03AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 1-09-23 9:02AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM ALARM 12-23-22 4:19AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM CLEAR 12-23-22 3:45AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM ALARM 12-23-22 3:41AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM CLEAR 12-23-22 3:39AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM ALARM 12-23-22 2:24AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM CLEAR 12-23-22 2:08AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM ALARM 12-23-22 2:08AM
I11200
APR 4, 2023 6:51 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK#SA002U001 LOW TEMP WARNING CLEAR 4-03-23 9:11AM
T 1 TANK DIESEL TK#SA002U001 LOW TEMP WARNING ALARM 4-03-23 9:10AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING CLEAR 4-03-23 9:10AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING ALARM 4-03-23 9:06AM
T 1 TANK DIESEL TK#SA002U001 HIGH PRODUCT ALARM CLEAR 4-03-23 9:02AM
T 1 TANK DIESEL TK#SA002U001 HIGH PRODUCT ALARM ALARM 4-03-23 9:01AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 4-03-23 8:59AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 4-03-23 8:57AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 3-15-23 9:50AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 3-15-23 9:49AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING CLEAR 3-15-23 9:45AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING ALARM 3-15-23 9:41AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 3-15-23 9:20AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL CLEAR 3-15-23 9:19AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL ALARM 12-23-22 4:19AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 12-23-22 4:19AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL CLEAR 12-23-22 3:45AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 12-23-22 3:45AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL ALARM 12-23-22 3:42AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 12-23-22 3:41AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL CLEAR 12-23-22 3:39AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 12-23-22 3:39AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL ALARM 12-23-22 2:25AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 12-23-22 2:24AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 12-23-22 2:08AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 12-23-22 2:08AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 12-22-22 5:50PM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 12-22-22 5:50PM
SYSTEM PRINTER ERROR CLEAR 12-02-22 5:58PM
SYSTEM PAPER OUT CLEAR 12-02-22 5:58PM
SYSTEM PAPER OUT ALARM 12-02-22 5:58PM
SYSTEM PAPER OUT CLEAR 12-02-22 5:58PM
SYSTEM PAPER OUT ALARM 12-02-22 5:58PM
SYSTEM PAPER OUT CLEAR 12-02-22 5:58PM
SYSTEM PAPER OUT ALARM 12-02-22 5:58PM
SYSTEM PAPER OUT CLEAR 12-02-22 5:58PM
SYSTEM PAPER OUT ALARM 12-02-22 5:58PM
SYSTEM PRINTER ERROR ALARM 12-02-22 5:58PM
SYSTEM PRINTER ERROR CLEAR 11-14-22 7:56PM
SYSTEM PRINTER ERROR ALARM 11-14-22 7:56PM
T 2 TANK DIESEL TK#SA002A002 HIGH WATER WARNING CLEAR 10-28-22 10:33AM
T 2 TANK DIESEL TK#SA002A002 HIGH WATER WARNING ALARM 10-28-22 10:13AM
T 2 TANK DIESEL TK#SA002A002 HIGH PRODUCT ALARM CLEAR 10-28-22 10:10AM
T 2 TANK DIESEL TK#SA002A002 HIGH PRODUCT ALARM ALARM 10-28-22 10:03AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING CLEAR 10-28-22 9:34AM
T 1 TANK DIESEL TK#SA002U001 LOW TEMP WARNING CLEAR 10-28-22 9:33AM
T 1 TANK DIESEL TK#SA002U001 LOW TEMP WARNING ALARM 10-28-22 9:32AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING ALARM 10-28-22 9:25AM
T 1 TANK DIESEL TK#SA002U001 LOW TEMP WARNING CLEAR 1-27-22 12:13PM
T 1 TANK DIESEL TK#SA002U001 LOW TEMP WARNING ALARM 1-27-22 12:12PM
I20600
APR 4, 2023 6:52 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
TANK ALARM HISTORY
TANK 1 DIESEL TK#SA002U001
LEAK ALARM OCT 11, 2011 6:08 AM
OCT 14, 2010 2:44 PM
OCT 13, 2010 11:06 AM
HIGH WATER ALARM APR 3, 2023 9:06 AM
MAR 15, 2023 9:41 AM
OCT 28, 2022 9:25 AM
OVERFILL ALARM APR 3, 2023 9:01 AM
APR 3, 2023 8:59 AM
MAR 15, 2023 9:32 AM
LOW PRODUCT ALARM APR 3, 2023 8:57 AM
MAR 15, 2023 9:49 AM
DEC 23, 2022 4:19 AM
SUDDEN LOSS ALARM APR 4, 2010 3:43 PM
FEB 19, 2010 10:08 AM
FEB 19, 2010 10:05 AM
HIGH PRODUCT ALARM APR 3, 2023 9:01 AM
OCT 29, 2021 9:12 AM
OCT 15, 2020 9:12 AM
INVALID FUEL LEVEL DEC 23, 2022 4:19 AM
DEC 23, 2022 3:42 AM
DEC 23, 2022 2:25 AM
PROBE OUT APR 3, 2023 9:09 AM
APR 3, 2023 8:57 AM
MAR 15, 2023 9:54 AM
HIGH WATER WARNING APR 3, 2023 9:06 AM
MAR 15, 2023 9:41 AM
OCT 28, 2022 9:25 AM
DELIVERY NEEDED APR 3, 2023 8:57 AM
MAR 15, 2023 9:49 AM
DEC 23, 2022 4:19 AM
MAX PRODUCT ALARM APR 3, 2023 9:01 AM
OCT 15, 2020 9:12 AM
OCT 23, 2019 9:13 AM
CSLD INCR RATE WARN DEC 10, 2008 9:38 AM
SEP 18, 2008 10:06 AM
SEP 18, 2008 6:58 AM
LOW TEMP WARNING APR 3, 2023 9:10 AM
OCT 28, 2022 9:32 AM
JAN 27, 2022 12:12 PM
TANK 2 DIESEL TK#SA002A002
SETUP DATA WARNING JAN 27, 2012 11:49 AM
HIGH WATER ALARM OCT 28, 2022 10:13 AM
OCT 29, 2021 9:40 AM
NOV 21, 2016 10:37 AM
OVERFILL ALARM OCT 23, 2019 10:26 AM
NOV 2, 2018 10:38 AM
NOV 21, 2016 11:18 AM
LOW PRODUCT ALARM OCT 23, 2019 10:24 AM
NOV 21, 2016 10:31 AM
JAN 7, 2014 9:54 AM
SUDDEN LOSS ALARM OCT 12, 2010 8:39 PM
FEB 19, 2010 9:55 AM
APR 28, 2009 11:13 AM
HIGH PRODUCT ALARM OCT 28, 2022 10:03 AM
OCT 29, 2021 9:35 AM
OCT 29, 2021 9:33 AM
INVALID FUEL LEVEL OCT 29, 2021 9:33 AM
OCT 23, 2019 10:24 AM
NOV 21, 2016 10:31 AM
PROBE OUT OCT 28, 2022 10:32 AM
OCT 28, 2022 10:01 AM
OCT 29, 2021 9:42 AM
HIGH WATER WARNING OCT 28, 2022 10:13 AM
OCT 29, 2021 9:40 AM
NOV 21, 2016 10:37 AM
DELIVERY NEEDED OCT 23, 2019 10:24 AM
NOV 2, 2018 10:37 AM
NOV 7, 2017 1:37 PM
MAX PRODUCT ALARM OCT 28, 2022 10:03 AM
OCT 29, 2021 9:35 AM
OCT 29, 2021 9:33 AM
LOW TEMP WARNING DEC 17, 2014 11:26 AM
JAN 22, 2013 10:14 AM
I30200
APR 4, 2023 6:53 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 FILL SUMP
OCT 28, 2022 9:09 AM FUEL ALARM
JAN 27, 2022 12:07 PM FUEL ALARM
JAN 1, 2022 8:19 AM SETUP DATA WARNING
2 PIPING SUMP
OCT 28, 2022 9:15 AM FUEL ALARM
OCT 29, 2021 8:37 AM FUEL ALARM
OCT 25, 2021 5:05 PM FUEL ALARM
3 DAYTANK RUPTURE BASN
JAN 9, 2023 10:04 AM FUEL ALARM
JAN 9, 2023 9:33 AM FUEL ALARM
OCT 28, 2022 9:57 AM FUEL ALARM
4 DAY TANK ANNULAR
JAN 9, 2023 9:32 AM FUEL ALARM
OCT 28, 2022 9:59 AM FUEL ALARM
OCT 28, 2022 9:58 AM FUEL ALARM
5 ANNULAR UST
OCT 28, 2022 9:05 AM FUEL ALARM
OCT 29, 2021 8:40 AM FUEL ALARM
OCT 15, 2020 9:00 AM FUEL ALARM
6 TRANSITION SUMP
OCT 28, 2022 9:37 AM FUEL ALARM
OCT 16, 2022 4:47 PM FUEL ALARM
OCT 29, 2021 9:01 AM FUEL ALARM
7 REMOTE PUMP CABINET
OCT 28, 2022 9:41 AM FUEL ALARM
OCT 25, 2022 8:40 AM SENSOR OUT ALARM
OCT 25, 2022 8:36 AM SENSOR OUT ALARM
Identification of Inspection Procedures for Overfill Prevention Equipment
To Whom It May Concern:
Tait Environmental Services, Inc., utilizes the following procedures when conducting Overfill Prevention
Equipment Inspections:
1) Drop Tubes with Overfill Prevention Valves
a) Verify information based upon Manufacturer installation instructions and follow their
inspection procedures.
b) If manufacturer information is not available, we conduct the inspection per PEI-RP1200-17,
Section 7.1
2) Audible/Visual Alarms
a) Verify programming or installation per manufacturer guidelines and test the system per
manufacturer specifications.
b) If manufacturer information is not available, we conduct the inspection per PEI-1200-17,
Section 7.3.
3) Ballfloat Inspections are conducted following the procedures in PEI-RP1200-17, Section 7.2