HomeMy WebLinkAbout6901 Mcduvitt dr_tmobile astI
INSPECTION RECORD �-°� � BAKERSFIELD FIRE DEPART
Prevention Services
2101 H Street
UST JOB CARD Bakersfield, CA 93301
- Tel.: (661) 326-3979
Fes: (6611852-2171
Post this Card at the Job Site and DO NOT Remove for Duration of Work
DESCRIPTION DATE SIGNATURE
TANK INSTALL
PRIMARY PIPE-50PS1-1HR
SECONDARY PIPE-5PS1-1 HR
PRF_FI f1
TANK TES N
DESCRIPTION DATE SIGNATURE
UST =11M AL
DESCRIPTION DATE SIGNATURE
AS Al I
DESCRIPTION
DATE
SIGNATURE
MODIFICATIONS MINOR I MAJOR
DESCRIPTION
DATE
SIGNATURE
DESCRIPTION
DATE
SIGNATURE
PRIOR TO OCCUPANCY OF ANY BUILDING,
ALL UST AND/OR AST SYSTEMS SHALL BE
INTALLED, COMPLETED, AND ACCEPTED BY
THE BAKERSFIELD CITY FIRE DEPARTMENT.
BUILDING ADDRESS: ?40/ t"( ,�
EJOBDESCRIPTION:ER: %`� �► g) fj /'� PERMIT NO.: '�� _ �� )TRACTOR: j /-- P %z ie A e, 6','0-0 v'40,
If - I
.j
FD 2165 (Rev. 3/2018)
rbruinQdernagrp.com
From: Malcolm W. Moore <
Sent: mwmoore@bakersfieldfire.us>
Tuesday, May 18, 2021 8:16 AM
To: rbruin@derna r .c g p om
Subject: RE: Bakersfield Am Twr Sites 8653, 277456 & 300975
Rachel,
Thank you, one set of plans for each site will suffice. Just have the changes clouded around (in a bubble). Remember a
minimum of 10 feet from the property line is required for those volumes
of diesel fuel per California Fire Code..
Regards,
Jta&01M itoou
Fire Prevention Environmental Officer
Bakersfield FIRE Department
Office: 661-326-3684
Fax: 661-852-2171
2101 H Street, Bakersfield, CA 93301
mwmoore@bakersfieldfire.us
From: rbruin@,de.rnagrp:com <rlruin@dernagrp.com>
Sent: Mondar -
May 17, ?Q213:25 PM
To: Malcolm W. Moore <mwmoore@bakersfieldfire. us>
Subject: RE: Bakersfield Am Twr Sites 8653, 277456 & 300975
Warning: This email originated from outside the City of Bakersfield. T r
� Think before you click.
Hi Malcolm,
This email should suffice. I will let you know if not. When I am read to resubmit will 3 . Y � }sets of the revised plans be
required or just (1) set? Please let me know.
Thanks,
Rachel Bruin I The Derna Group
22431 Antonio Parkway
Suite B160-234
Rancho Santa Margarita, CA 92688
(805) 215-9444
From: Malcolm W. Moore <mwmoore bakersfieldfire.us>
Sent: Friday, May 14, 2021 12:38 PM
To: rbruin dernaRro.com
Cc: Shane Gardner <s ardner bakersfieldfire.us>
Subject: Bakersfield Am Twr Sites 8653, 277456 & 300975
Rachel,
Site #8653--Resubmit actual distance from lot line for emergent generator. Per
001 is showing 6+/-
'
Y g your overall site plan, sheet number C-
CFC Table 5705.3.4(2) for tank capacity 466 gal requires 10' min. list. From lot line.
Site #277456--same sized diesel tank, showing 8' +/- distance from lot line.
Site #300975—same sized diesel tank showing 5' +/- distance from lot line.
Do you require a deficiency letter or will this email suffice?
Rega rds,
Ata&Wm Atoow
Fire Prevention Environmental Officer
Bakersfield FIRE Department
Office: 661-326-3684
Fax: 661-852-2171.
2101 H Street, Bakersfield, CA 93301
mwmoore@bakersfieldfire.us
10
r A9.�
2
THE
DERNA
June 1, 2422
Bakersfield Fire Department
Prevention Services
2101 H Street
Bakersfield, CA 93301
RE: Resubmittal for Aboveground Storage Tank — Site # 300975 - 6901 McDivitt Drive, Bakersfield, CA
93313; APN: 385-412-28-00-1
Dear Malcolm Moore,
Regarding your comments:
1. Comment: CFC Table 5705.3.4(2) for lank capacity 466 gal requires 10) rain. list. From lot line.
Response: The generator has been moved and is now 10' from the lot lines. Please see sheet C-001
of the revised plans.
Please feel free to contact me should you have any further questions or concerns,
Sincerely,
Rachel Bruin I The Derna Group
22431 Antonio Parkway
Suite B160-234
Rancho $ants Margorita.,A 92688
_ Finail: rbruin@dernag_ .co