HomeMy WebLinkAbout2023 EMC (Rejected)Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10134208 6-1-23
Jaco #3351 Howard's #4
3200 Panama Lane Bakersfield 93313
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Rockland Kirk
1073967
10241356 9-29-24
GVR ATG TECH C32654 9-28-24
6-1-23 5
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder-Root TLS-350
336.01
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 (2-1) 208/305 87-1 STP
L2 (2-1) 208/305 87-1 FILL
L3 (2-1) 208/305 87-2 STP
L4 (2-1) 208/305 87-2 FILL
L5 (2-1) 208/305 91 STP
L6 (2-1) 208/305 91 FILL
L7 (2-1) 208/305 DIESEL STP
L8 (2-1) 208/305 DIESEL FILL
L9 (2-1) 208/305 DISP 1-2
L10 (2-1) 208/305 DISP 3-4
L11 (2-1) 208/305 DISP 5-6
L12 (2-1) 208/305 DISP 7-8
L13 (2-1) 208/305 VENT BOX
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Performed EMC after 2-1's installed on sit, passed.
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
STP
PROPERTY LINE
NO PARKING
4 3
8 7
65 21
STP
STP
STP
F
F
F
FV
V
V
12,000 GALLON87-1 UNLEADED
12,000 GALLON87-2 UNLEADED
12,000 GALLONPREMIUM
12,000 GALLONDIESEL
H
PANAMA LN.WIBLE RD.EXISTING BUILDING
W
CATCHBASINPRICE SIGNDUMPSTER
GATED ENCLOSURE WITHA STAND ALONE ROOF
PROPERTY LINE
N
V-GUTTER
SWITCHGEAR
87 GAS 1.5" OMEGAFLEX PIPE
91 GAS 1.5" OMEGAFLEX PIPE
DIESEL 1.5" OMEGAFLEX PIPE
VAPOR RETURN 3/2 INCH DBL WALL PIPE
VAPOR RETURN 3/2 INCH MANIFOLDS
VAPOR RETURN 4/3 INCH DBL WALL PIPE
VAPOR VENT 3/2 INCH DBL WALL PIPE
VACUUM CROSSOVER 3/2 DBL WALL PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
WATER SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
AUTOMATIC TANK GAUGE
UST ELECTRICAL PANEL
CIRCUIT BREAKER
AIR AND WATER DISPENSER
HAZWASTE DRUM
H
F
V
W
S1 87-1 PRODUCT LINE SMART SENSOR
S2 87-1 VENT LINE SMART SENSOR
S3 87-1 TANK ANNULAR SMART SENSOR
S4 87-2 PRODUCT LINE SMART SENSOR
S5 87-2 VENT LINE SMART SENSOR
S6 87-2 TANK ANNULAR SMART SENSOR
S7 87-2 VAPOR LINE SMART SENSOR
S8 TEMPERATURE SENSOR METER
S9 PREMIUM PRODUCT SMART SENSOR
S10 PREMIUM VENT LINE SMART SENSOR
S11 PREMIUM TANK ANNULAR SMART SENSOR
S12 DIESEL PRODUCT SMART SENSOR
S13 DIESEL VENT LINE SMART SENSOR
S14 DIESEL TANK ANNULAR SMART SENSOR
LEGEND
L1 87-1 STP SUMP
L2 87-1 FILL SUMP
L3 87-2 STP SUMP
L4 87-2 FILL SUMP
L5 PREMIUM STP SUMP
L6 PREMIUM FILL SUMP
L7 DIESEL STP SUMP
L8 DIESEL FILL SUMP
L9 UDC 1-2
L10 UDC 3-4
L11 UDC 5-6
L12 UDC 7-8
L13 VENT BOX
DATE:
DRAWN BY:
CHECKED:
APPROVED:
RAC FASTRIP - 3351 CADFILE:
SHEET NO.3351-MSP
HOWARD'S MINI MARKETCONVENIENCE MARKET FOR:
BAKERSFIELD, CALIFORNIA 933133200 PANAMA LN.
DRAWING:
DATE REVISIONS
A.P.N.: 372-021-33
SCALE:
JACO HILL3101 STATE RDBAKERSFIELD, CA 93308
PROJECT OWNER:
CD
SITE MAP SITE PLAN
C1
VICINITY MAP
TAB:CERS
1/8"=1'-0"
0
SHEET SIZE 22 X 34
3200 PANAMA LN.BAKERSFIELD, CA 93313
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-46941
CERS ID 10134208
FASTRIP #3351
3200 PANAMA LN.
BAKERSFIELD, CA 93313
03/01/2021 REV.WIBLE RD.
PANAMA LN.
03/01/2021
PROJECT DATA
5'10'15' 20'
L1,S1,S2,S3 L2
L3,S4,S5,S6,S7 L4
L5,S9,S10,S11 L6
L7,S12,S13,S14 L8
L11 L9
L10
L12
VAPOR MANIFOLDCAPPED
L13