HomeMy WebLinkAboutFMC 2023Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10134244 07/19/2023
Jaco #7776 Howard's Market
3300 Planz Road Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
VeederRoot TLS-3XX Technician - C32655 10/11/2024
Vaporless Manufacturing Inc. 10/21/2024
FFS EVR Phase I Phil Tite - 1016703714 12/07/2024
07/19/2023 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS-350
333.05
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 Dispenser 1-2
L2 847970-001 Dispenser 3-4
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 848480-003 91 Premium
T2 848480-003 87 Unleaded
T3 848480-003 Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
07/19/2023
NOPARKING
EXISTING BUILDING
R
W
CATCHBASIN
H
DUMPSTER
P
R
I
C
E
S
I
G
N
CATCHBASIN
12,000 GALLONPREMIUM
F
V
43
F
21L1
STP
STP
STP
12,000 GALLON87 UNLEADED
12,000 GALLONDIESEL
VF
ANODE(3x)
UNATTACHED OUTDOOR AREA
FIELD WITH NO GRASS
PROPERTY LINE
PROPERTY LINE
205.51'125.5'124.37'165.91'
PLANZ RD.CHUMLEY ST.WIBLE RD.NWOOD FENCING SPANS ENTIRENORTHERN PROPERTY LINE
LEGEND
L1 UDC 1 - 2
87 GAS 2 INCH SINGLE WALLED PIPE
91 GAS 2 INCH SINGLE WALLED PIPE
DIESEL 2 INCH SINGLE WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
P
V
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
RECTIFIER
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
WH
R
SCALE:SITE MAP
C1
VICINITY MAP
PROJECT DATA
3/32"=1'-0"
INCHES012
SHEET SIZE 22 X 34
3300 PLANZ RD.
BAKERSFIELD, CA 93309
PROJECT OWNER:
JAMIESON HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-003735
CERS ID 10134244
FASTRIP #7776
3300 PLANZ RD.
BAKERSFIELD, CA 93309
03/13/17 REV.WIBLE RD.PLANZ RD.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #7776 Howard's Market3300 Planz RoadBakersfield101342441/23/4 3/48791Diesel 8791Diesel 1/21/23/4ProductProductProductProductProductProductBrandon Nunez
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10134244 07/19/2023
Jaco #7776 Howard's Market
3300 Planz Road Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
FFS EVR Phase I Phil Tite - 1016703714 12/07/2024
PEI 1200 1 Hour Hydrostatic All Spill Containers
07/19/2023 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1: 91 PNL
Phil-Tite
T2: 87 UNL
Phil-Tite
T3: DSL
Phil-Tite
Howard’s Market PLANZ System Setup
Responses Received:
200
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
JUL 19, 2023 8:39 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
2 UNLEADED 5347 43.89 0.8 86.6 6653
3 SUPER 5545 45.14 0.0 87.3 6455
4 DIESEL 1774 19.71 0.0 87.8 10226
I90500
JUL 19, 2023 8:39 AM
SOFTWARE REVISION LEVEL
VERSION 333.05
SOFTWARE# 346333-100-F
CREATED - 13.12.11.14.16
S-MODULE# 330160-016-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
ISD/APM
PLLD
0.10 REPETITIV
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I50500
JUL 19, 2023 8:40 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUL 19, 2023 8:40 AM
SHIFT TIME 1 : 6:00 AM
I50202
JUL 19, 2023 8:40 AM
SHIFT TIME 2 : DISABLED
I50203
JUL 19, 2023 8:40 AM
SHIFT TIME 3 : DISABLED
I50204
JUL 19, 2023 8:40 AM
SHIFT TIME 4 : DISABLED
I54600
JUL 19, 2023 8:40 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUL 19, 2023 8:40 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUL 19, 2023 8:40 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUL 19, 2023 8:40 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUL 19, 2023 8:40 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUL 19, 2023 8:40 AM
PRINT TC VOLUMES
ENABLED
I50E00
JUL 19, 2023 8:40 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUL 19, 2023 8:40 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUL 19, 2023 8:40 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUL 19, 2023 8:40 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUL 19, 2023 8:40 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 1 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUL 19, 2023 8:40 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUL 19, 2023 8:40 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUL 19, 2023 8:40 AM
TANK CHART SECURITY
DISABLED
I5BD00
JUL 19, 2023 8:40 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JUL 19, 2023 8:40 AM
MASS/DENSITY
DISABLED
I88101
JUL 19, 2023 8:40 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JUL 19, 2023 8:40 AM
I88103
JUL 19, 2023 8:40 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JUL 19, 2023 8:40 AM
I88105
JUL 19, 2023 8:40 AM
PORT SETTINGS:
COMM BOARD : 5 (RS-485)
BAUD RATE : 1200
PARITY : ODD
STOP BIT : 2 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88106
JUL 19, 2023 8:40 AM
PORT SETTINGS:
COMM BOARD : 6 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I52000
JUL 19, 2023 8:40 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE JUN 6, 2018 DISABLED
2 ON DATE JUN 6, 2018 DISABLED
3 ON DATE JUN 6, 2018 DISABLED
4 ON DATE JUN 6, 2018 DISABLED
5 ON DATE JUN 6, 2018 DISABLED
6 ON DATE JUN 6, 2018 DISABLED
7 ON DATE JUN 6, 2018 DISABLED
8 ON DATE JUN 6, 2018 DISABLED
I60100
JUL 19, 2023 8:40 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 OFF
2 UNLEADED ON
3 SUPER ON
4 DIESEL ON
I60200
JUL 19, 2023 8:40 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1
2 UNLEADED
3 SUPER
4 DIESEL
I60300
JUL 19, 2023 8:40 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 1
2 UNLEADED 2
3 SUPER 3
4 DIESEL 4
I60900
JUL 19, 2023 8:40 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 0.000000
2 UNLEADED 0.000700
3 SUPER 0.000700
4 DIESEL 0.000450
I60700
JUL 19, 2023 8:40 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 0.00
2 UNLEADED 96.00
3 SUPER 96.00
4 DIESEL 96.00
I60A00
JUL 19, 2023 8:40 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 4
PTS 0 2 UNLEADED 1 PT 12000 3 SUPER
1 PT 12000 4 DIESEL 1 PT 12000
I60400
JUL 19, 2023 8:40 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 12000
3 SUPER 12000
4 DIESEL 12000
I60500
JUL 19, 2023 8:40 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 0 0 0 101
2 UNLEADED 12000 0 0 0
3 SUPER 12000 0 0 0
4 DIESEL 12000 0 0 0
I60600
JUL 19, 2023 8:40 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 101
0 0 0 0
2 UNLEADED 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 SUPER 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 DIESEL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUL 19, 2023 8:40 AM
TANK PRODUCT LABEL METER DATA
1 NO
2 UNLEADED NO
3 SUPER NO
4 DIESEL NO
I62F00
JUL 19, 2023 8:40 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
2 UNLEADED 4.0 IN.
3 SUPER 4.0 IN.
4 DIESEL 4.0 IN.
I62700
JUL 19, 2023 8:40 AM
2 UNLEADED 2.0
3 SUPER 2.0
4 DIESEL 2.0
I64200
JUL 19, 2023 8:40 AM
2 UNLEADED LOW
3 SUPER LOW
4 DIESEL LOW
I62400
JUL 19, 2023 8:40 AM
2 UNLEADED 3.0
3 SUPER 3.0
4 DIESEL 3.0
I62800
JUL 19, 2023 8:40 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 12000
3 SUPER 12000
4 DIESEL 12000
I62300
JUL 19, 2023 8:40 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 10800
3 SUPER 10800
4 DIESEL 10800
I62200
JUL 19, 2023 8:40 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 11400
3 SUPER 11400
4 DIESEL 11400
I62900
JUL 19, 2023 8:40 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 1200
3 SUPER 1200
4 DIESEL 1200
I62100
JUL 19, 2023 8:40 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 1
2 UNLEADED 1200
3 SUPER 1200
4 DIESEL 1200
I62600
JUL 19, 2023 8:40 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 99
2 UNLEADED 99
3 SUPER 99
4 DIESEL 99
I62500
JUL 19, 2023 8:40 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 99
2 UNLEADED 99
3 SUPER 99
4 DIESEL 99
I60800
JUL 19, 2023 8:40 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 0.00
2 UNLEADED 1.00
3 SUPER 4.00
4 DIESEL 0.00
I60B00
JUL 19, 2023 8:40 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUL 19, 2023 8:40 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 0.00
2 UNLEADED 0.00
3 SUPER 0.00
4 DIESEL 0.00
I61200
JUL 19, 2023 8:40 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 NONE NONE
2 UNLEADED NONE NONE
3 SUPER NONE NONE
4 DIESEL NONE NONE
I63600
JUL 19, 2023 8:40 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 120
3 SUPER 120
4 DIESEL 120
I62A00
JUL 19, 2023 8:40 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 120
3 SUPER 120
4 DIESEL 120
I62C00
JUL 19, 2023 8:40 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 STANDARD
2 UNLEADED STANDARD
3 SUPER STANDARD
4 DIESEL STANDARD
I62D00
JUL 19, 2023 8:40 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 SUPER GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUL 19, 2023 8:40 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 OFF OFF
2 UNLEADED OFF OFF
3 SUPER OFF OFF
4 DIESEL OFF OFF
I63000
JUL 19, 2023 8:40 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 OFF
2 UNLEADED OFF
3 SUPER OFF
4 DIESEL OFF
I63200
JUL 19, 2023 8:40 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 OFF
2 UNLEADED OFF
3 SUPER OFF
4 DIESEL OFF
I61000
JUL 19, 2023 8:40 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 1
2 UNLEADED 1
3 SUPER 1
4 DIESEL 1
I63A00
JUL 19, 2023 8:40 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 10.00%
2 UNLEADED 10.00%
3 SUPER 10.00%
4 DIESEL 10.00%
I61100
JUL 19, 2023 8:40 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST CSLD : ALL TANK
Pd = 95%
CLIMATE FACTOR:MODERATE
GROSS TEST
AUTO-CONFIRM: DISABLED
REPORT ONLY:
DISABLED
TST EARLY STOP:DISABLED
I61300
JUL 19, 2023 8:40 AM
CSLD PROBABLITY OF DETECTION
T 2:UNLEADED : Pd = 95%
T 3:SUPER : Pd = 95%
T 4:DIESEL : Pd = 95%
I61400
JUL 19, 2023 8:40 AM
CSLD CLIMATE FACTOR
T 2:UNLEADED : MODERATE
T 3:SUPER : MODERATE
T 4:DIESEL : MODERATE
I61600
JUL 19, 2023 8:40 AM
TANK PRODUCT LABEL CAL UPDATE
1 IMMEDIATE
2 UNLEADED IMMEDIATE
3 SUPER IMMEDIATE
4 DIESEL IMMEDIATE
I61A00
JUL 19, 2023 8:40 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 DISABLED
2 UNLEADED DISABLED
3 SUPER DISABLED
4 DIESEL DISABLED
I61B00
JUL 19, 2023 8:40 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
2 UNLEADED DISABLED
3 SUPER DISABLED
4 DIESEL DISABLED
I61C00
JUL 19, 2023 8:40 AM
CSLD REPORT ONLY
2 UNLEADED DISABLED
3 SUPER DISABLED
4 DIESEL DISABLED
I62B00
JUL 19, 2023 8:40 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 ??? 0, 0
2 UNLEADED ??? 0, 0
3 SUPER ??? 0, 0
4 DIESEL ??? 0, 0
I63300
JUL 19, 2023 8:40 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUL 19, 2023 8:40 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 0
2 UNLEADED 0
3 SUPER 0
4 DIESEL 0
I63500
JUL 19, 2023 8:40 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 1
2 UNLEADED 1
3 SUPER 1
4 DIESEL 1
I63900
JUL 19, 2023 8:40 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1
END FACTOR: NONE
2 UNLEADED
END FACTOR: NONE
3 SUPER
END FACTOR: NONE
4 DIESEL
END FACTOR: NONE
I78000
JUL 19, 2023 8:40 AM
I77700
JUL 19, 2023 8:40 AM
I77800
JUL 19, 2023 8:40 AM
I78C00
JUL 19, 2023 8:40 AM
I78300
JUL 19, 2023 8:40 AM
I78F00
JUL 19, 2023 8:40 AM
I78700
JUL 19, 2023 8:40 AM
I70200
JUL 19, 2023 8:40 AM
LIQUID LABEL
DEVICE LABEL
1 UDC 1-2
2
3
4
5
6
7
8
I70300
JUL 19, 2023 8:40 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UDC 1-2 TRI-STATE (SINGLE FLOAT)
2 TRI-STATE (SINGLE FLOAT)
3 TRI-STATE (SINGLE FLOAT)
4 TRI-STATE (SINGLE FLOAT)
5 TRI-STATE (SINGLE FLOAT)
6 TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
I70400
JUL 19, 2023 8:40 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UDC 1-2 DISPENSER PAN
2 OTHER SENSORS
3 OTHER SENSORS
4 OTHER SENSORS
5 OTHER SENSORS
6 OTHER SENSORS
7 OTHER SENSORS
8 OTHER SENSORS
I74200
JUL 19, 2023 8:40 AM
I74300
JUL 19, 2023 8:40 AM
I74400
JUL 19, 2023 8:40 AM
I74700
JUL 19, 2023 8:40 AM
I74800
JUL 19, 2023 8:40 AM
I74900
JUL 19, 2023 8:40 AM
I7BC00
JUL 19, 2023 8:40 AM
I80200
JUL 19, 2023 8:40 AM
I80300
JUL 19, 2023 8:40 AM
I80400
JUL 19, 2023 8:40 AM
I80700
JUL 19, 2023 8:40 AM
RELAY LABEL
DEVICE LABEL
1 OVERFILL ALARM
2
3
4
I80900
JUL 19, 2023 8:40 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 OVERFILL ALARM NORMALLY OPEN
2 NORMALLY OPEN
3 NORMALLY OPEN
4 NORMALLY OPEN
I80B00
JUL 19, 2023 8:40 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 OVERFILL ALARM NONE
2 NONE
3 NONE
4 NONE
I80A00
JUL 19, 2023 8:40 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 OVERFILL ALARM STANDARD
2 STANDARD
3 STANDARD
4 STANDARD
I80C00
JUL 19, 2023 8:40 AM
I80800
JUL 19, 2023 8:40 AM
RELAY SETUP REPORT
R 1:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 2:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 3:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
JUL 19, 2023 8:41 AM
EDIM:1 VR:349634-003-E TD:09.05.18.15.18
I79100
JUL 19, 2023 8:41 AM
I72300
JUL 19, 2023 8:41 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VP SENSOR 3-4 VAPOR PRESSURE
02 VFM 1-2 AIR FLOW METER
03 VFM 3-4 AIR FLOW METER
04 UNKNOWN
05 UNKNOWN
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JUL 19, 2023 8:41 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
JUL 19, 2023 8:41 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JUL 19, 2023 8:41 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
VAPOR PROCESSOR TYPE
NONE
IV4700
JUL 19, 2023 8:41 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JUL 19, 2023 8:41 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ACCEPT HIGH ORVR: YES
IV4A00
JUL 19, 2023 8:41 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 UU BLEND3
02 02 02 01 UU BLEND3
03 03 03 02 UU BLEND3
04 04 04 02 UU BLEND3
IV4B00
JUL 19, 2023 8:41 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
IV4900
JUL 19, 2023 8:41 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JUL 19, 2023 8:41 AM
ISD VERSION: 01.05
Howard’s Market PLANZ Pre Alarm History
Responses Received:
I10200
JUL 19, 2023 8:42 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 163895 162691
2 INTERSTITIAL BD 201249 200242
3 7SMARTSENSOR BD 9865629 501754
4 UNUSED 9830660 4912646
5 UNUSED 9822698 4913540
6 UNUSED 9822698 4911709
7 UNUSED 9822174 4913583
8 UNUSED 9816831 4911186
9 WPLLD POWER BD 201158 200791
10 AC INTERFACE BD 163488 162992
11 RELAY BOARD 15049 15029
12 UNUSED 9832520 4905126
13 UNUSED 9813998 4905475
14 UNUSED 9818146 4904559
15 UNUSED 9810562 4906521
16 UNUSED 9815423 4905213
COMM 1 ELEC DISP INT. 100267 100115
COMM 2 WPLLD COMM BD 201900 201193
COMM 3 RS232 SERIAL BD 14902 14875
COMM 4 UNUSED 9825501 4916436
COMM 5 RS485 SERIAL BD 9815800 68149
COMM 6 RS232 SERIAL BD 9814270 14897
I90200
JUL 19, 2023 8:43 AM
SOFTWARE REVISION LEVEL
VERSION 333.05
SOFTWARE# 346333-100-F
CREATED - 13.12.11.14.16
S-MODULE# 330160-016-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
ISD/APM
PLLD
0.10 REPETITIV
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I11100
JUL 19, 2023 8:43 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-03-23 10:30AM
W 2 OTHER UNLEADED GROSS LINE FAIL CLEAR 7-03-23 10:30AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-03-23 10:25AM
W 2 OTHER UNLEADED GROSS LINE FAIL ALARM 7-03-23 10:25AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-03-23 10:08AM
W 1 OTHER SUPER GROSS LINE FAIL CLEAR 7-03-23 10:08AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-03-23 10:02AM
W 1 OTHER SUPER GROSS LINE FAIL ALARM 7-03-23 10:02AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:29AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:29AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:29AM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 7-03-23 9:29AM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 7-03-23 9:29AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-03-23 9:29AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-03-23 9:29AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-03-23 9:29AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:13AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:13AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:13AM
L 1 DISP PAN UDC 1-2 FUEL ALARM CLEAR 7-03-23 9:13AM
L 1 DISP PAN UDC 1-2 FUEL ALARM ALARM 7-03-23 9:12AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-03-23 9:12AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-03-23 9:12AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-03-23 9:12AM
T 2 TANK UNLEADED OVERFILL ALARM CLEAR 6-27-23 1:17AM
T 2 TANK UNLEADED OVERFILL ALARM ALARM 6-27-23 1:13AM
T 2 TANK UNLEADED OVERFILL ALARM CLEAR 6-27-23 1:09AM
T 2 TANK UNLEADED OVERFILL ALARM ALARM 6-27-23 1:06AM
T 2 TANK UNLEADED LOW PRODUCT ALARM CLEAR 5-07-23 7:48AM
T 2 TANK UNLEADED LOW PRODUCT ALARM ALARM 5-06-23 7:26PM
T 2 TANK UNLEADED LOW PRODUCT ALARM CLEAR 5-02-23 5:52AM
T 2 TANK UNLEADED LOW PRODUCT ALARM ALARM 5-01-23 10:26PM
T 3 TANK SUPER LOW PRODUCT ALARM CLEAR 4-18-23 2:57PM
T 4 TANK DIESEL LOW PRODUCT ALARM CLEAR 4-18-23 2:57PM
T 2 TANK UNLEADED LOW PRODUCT ALARM CLEAR 4-18-23 2:35PM
T 2 TANK UNLEADED LOW PRODUCT ALARM ALARM 4-17-23 2:48PM
T 3 TANK SUPER LOW PRODUCT ALARM ALARM 4-17-23 2:48PM
OTHER MISSING TANK SETUP CLEAR 4-17-23 2:48PM
OTHER MISSING TANK SETUP ALARM 4-17-23 2:47PM
T 3 TANK SUPER LOW PRODUCT ALARM CLEAR 4-17-23 2:47PM
T 2 TANK UNLEADED LOW PRODUCT ALARM CLEAR 4-17-23 2:47PM
T 1 TANK PROBE OUT CLEAR 4-17-23 2:39PM
T 1 TANK PROBE OUT ALARM 4-17-23 2:38PM
T 3 TANK SUPER LOW PRODUCT ALARM ALARM 4-16-23 1:29PM
T 4 TANK DIESEL LOW PRODUCT ALARM ALARM 4-16-23 1:29PM
T 2 TANK UNLEADED LOW PRODUCT ALARM ALARM 4-16-23 1:29PM
T 2 TANK UNLEADED LOW PRODUCT ALARM CLEAR 2-03-23 11:10PM
T 2 TANK UNLEADED LOW PRODUCT ALARM ALARM 2-03-23 5:54PM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 2-02-23 11:24AM
W 1 OTHER SUPER GROSS LINE FAIL CLEAR 2-02-23 11:24AM
I11200
JUL 19, 2023 8:43 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 7-14-23 1:32PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 7-14-23 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 7-03-23 9:30AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 7-02-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 6-26-23 8:02AM
SYSTEM PAPER OUT CLEAR 6-26-23 8:02AM
SYSTEM PRINTER ERROR ALARM 6-26-23 8:00AM
SYSTEM PAPER OUT ALARM 6-26-23 8:00AM
SYSTEM PRINTER ERROR CLEAR 5-09-23 6:20AM
SYSTEM PAPER OUT CLEAR 5-09-23 6:20AM
SYSTEM PRINTER ERROR ALARM 5-09-23 6:00AM
SYSTEM PAPER OUT ALARM 5-09-23 6:00AM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 5-07-23 7:48AM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 5-06-23 7:26PM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 5-02-23 5:52AM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 5-01-23 10:26PM
T 3 TANK SUPER DELIVERY NEEDED CLEAR 4-18-23 2:57PM
T 4 TANK DIESEL SETUP DATA WARNING CLEAR 4-18-23 2:57PM
T 3 TANK SUPER SETUP DATA WARNING CLEAR 4-18-23 2:57PM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 4-18-23 2:57PM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 4-18-23 2:35PM
T 2 TANK UNLEADED SETUP DATA WARNING CLEAR 4-18-23 2:35PM
T 3 TANK SUPER SETUP DATA WARNING ALARM 4-17-23 2:48PM
T 2 TANK UNLEADED SETUP DATA WARNING ALARM 4-17-23 2:48PM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 4-17-23 2:48PM
T 3 TANK SUPER DELIVERY NEEDED ALARM 4-17-23 2:48PM
T 3 TANK SUPER DELIVERY NEEDED CLEAR 4-17-23 2:47PM
T 3 TANK SUPER SETUP DATA WARNING CLEAR 4-17-23 2:47PM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 4-17-23 2:47PM
T 2 TANK UNLEADED SETUP DATA WARNING CLEAR 4-17-23 2:47PM
T 1 TANK SETUP DATA WARNING CLEAR 4-17-23 2:39PM
T 1 TANK SETUP DATA WARNING ALARM 4-17-23 2:38PM
T 3 TANK SUPER DELIVERY NEEDED ALARM 4-16-23 1:29PM
T 4 TANK DIESEL DELIVERY NEEDED ALARM 4-16-23 1:29PM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 4-16-23 1:29PM
T 4 TANK DIESEL SETUP DATA WARNING ALARM 4-16-23 1:29PM
T 3 TANK SUPER SETUP DATA WARNING ALARM 4-16-23 1:29PM
T 2 TANK UNLEADED SETUP DATA WARNING ALARM 4-16-23 1:29PM
SYSTEM PRINTER ERROR CLEAR 3-21-23 12:51PM
SYSTEM PAPER OUT CLEAR 3-21-23 12:51PM
SYSTEM PRINTER ERROR ALARM 3-11-23 6:00AM
SYSTEM PAPER OUT ALARM 3-11-23 6:00AM
OTHER ISD GROSS PRES WARN CLEAR 3-08-23 10:08AM
OTHER ISD GROSS PRES WARN ALARM 3-08-23 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 2-22-23 6:12PM
OTHER ISD GROSS PRES WARN ALARM 2-22-23 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 2-15-23 10:21AM
OTHER ISD GROSS PRES WARN ALARM 2-15-23 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 2-08-23 11:36AM
OTHER ISD GROSS PRES WARN ALARM 2-08-23 10:01AM
I20600
JUL 19, 2023 8:43 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
TANK ALARM HISTORY
TANK 2 UNLEADED
SETUP DATA WARNING APR 17, 2023 2:48 PM
APR 16, 2023 1:29 PM
HIGH WATER ALARM AUG 13, 2014 10:07 AM
OVERFILL ALARM JUN 27, 2023 1:13 AM
JUN 27, 2023 1:06 AM
JAN 15, 2023 12:41 AM
LOW PRODUCT ALARM MAY 6, 2023 7:26 PM
MAY 1, 2023 10:26 PM
APR 17, 2023 2:48 PM
SUDDEN LOSS ALARM FEB 1, 2020 4:26 AM
FEB 1, 2020 3:55 AM
FEB 1, 2020 3:49 AM
HIGH PRODUCT ALARM JUL 21, 2022 4:12 PM
AUG 18, 2020 11:26 AM
JUL 21, 2020 1:26 PM
INVALID FUEL LEVEL JUL 6, 2022 11:22 AM
JUL 5, 2022 9:15 AM
OCT 13, 2020 5:25 AM
PROBE OUT JUL 6, 2022 11:29 AM
JUL 5, 2022 10:26 AM
AUG 18, 2020 11:37 AM
HIGH WATER WARNING AUG 13, 2014 10:07 AM
DELIVERY NEEDED MAY 6, 2023 7:26 PM
MAY 1, 2023 10:26 PM
APR 17, 2023 2:48 PM
MAX PRODUCT ALARM JUL 21, 2022 4:12 PM
JUL 21, 2020 1:26 PM
AUG 4, 2017 9:14 AM
NO CSLD IDLE TIME JAN 27, 2021 6:53 AM
JAN 24, 2021 10:09 PM
DEC 10, 2020 11:15 PM
LOW TEMP WARNING JUL 31, 2018 3:15 PM
AUG 9, 2017 9:23 AM
AUG 11, 2016 9:48 AM
TANK 3 SUPER
SETUP DATA WARNING APR 17, 2023 2:48 PM
APR 16, 2023 1:29 PM
HIGH WATER ALARM JUL 15, 2022 2:19 PM
OVERFILL ALARM JUL 15, 2022 2:25 PM
AUG 18, 2020 11:25 AM
AUG 4, 2017 9:51 AM
LOW PRODUCT ALARM APR 17, 2023 2:48 PM
APR 16, 2023 1:29 PM
JUL 15, 2022 2:18 PM
SUDDEN LOSS ALARM JUL 15, 2022 2:20 PM
JUL 5, 2022 9:19 AM
JUL 5, 2022 8:48 AM
HIGH PRODUCT ALARM JUL 21, 2022 4:14 PM
JUL 15, 2022 2:24 PM
JUL 6, 2022 12:20 PM
INVALID FUEL LEVEL JUL 15, 2022 2:18 PM
JUL 5, 2022 8:51 AM
MAY 12, 2021 9:38 AM
PROBE OUT JUL 5, 2022 10:29 AM
MAY 12, 2021 10:07 AM
MAY 12, 2021 9:38 AM
HIGH WATER WARNING JUL 15, 2022 2:19 PM
AUG 18, 2020 11:19 AM
DELIVERY NEEDED APR 17, 2023 2:48 PM
APR 16, 2023 1:29 PM
JUL 15, 2022 2:18 PM
MAX PRODUCT ALARM JUL 21, 2022 4:14 PM
JUL 15, 2022 2:24 PM
JUL 6, 2022 12:20 PM
NO CSLD IDLE TIME JAN 24, 2021 10:18 PM
DEC 10, 2020 11:23 PM
LOW TEMP WARNING MAY 12, 2021 10:11 AM
AUG 18, 2020 11:41 AM
AUG 22, 2017 10:23 AM
TANK 4 DIESEL
SETUP DATA WARNING APR 16, 2023 1:29 PM
HIGH WATER ALARM AUG 18, 2020 11:32 AM
OVERFILL ALARM AUG 18, 2020 11:28 AM
AUG 7, 2018 9:41 AM
JUL 31, 2018 3:12 PM
LOW PRODUCT ALARM APR 16, 2023 1:29 PM
JUL 5, 2022 8:14 AM
SEP 16, 2021 10:14 AM
SUDDEN LOSS ALARM JUL 5, 2022 8:28 AM
JUL 5, 2022 8:03 AM
AUG 4, 2017 8:55 AM
HIGH PRODUCT ALARM JUL 21, 2022 4:16 PM
AUG 19, 2019 9:57 AM
JUL 31, 2018 3:12 PM
INVALID FUEL LEVEL JUL 5, 2022 8:19 AM
AUG 18, 2020 11:52 AM
AUG 18, 2020 11:44 AM
PROBE OUT JUL 5, 2022 10:54 AM
AUG 18, 2020 11:51 AM
AUG 18, 2020 11:47 AM
HIGH WATER WARNING AUG 18, 2020 11:32 AM
DELIVERY NEEDED APR 16, 2023 1:29 PM
JUL 5, 2022 8:14 AM
SEP 16, 2021 10:14 AM
LOW TEMP WARNING AUG 18, 2020 11:22 AM
AUG 11, 2016 9:44 AM
AUG 10, 2015 11:01 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 19, 2023 8:43 AM
I30200
JUL 19, 2023 8:43 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UDC 1-2
JUL 3, 2023 9:29 AM SENSOR OUT ALARM
JUL 3, 2023 9:12 AM FUEL ALARM
JUL 21, 2022 4:36 PM FUEL ALARM
I31600
JUL 19, 2023 8:43 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP SENSOR 3-4
SEP 1, 2020 2:01 PM COMMUNICATION ALARM
MAY 1, 2014 5:23 PM COMMUNICATION ALARM
2 VFM 1-2
3 VFM 3-4
I40200
JUL 19, 2023 8:43 AM
I40300
JUL 19, 2023 8:43 AM
I34200
JUL 19, 2023 8:43 AM
I34700
JUL 19, 2023 8:43 AM
IV0100
JUL 19, 2023 8:43 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-07-14 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.79
23-07-02 10:02:46 A/L RATIO DEGRADATION FP 4 BLEND3 0.79
23-03-08 10:02:08 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.42
23-02-22 10:02:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-02-15 10:01:28 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.56
23-02-08 10:01:55 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.77
23-01-29 10:01:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.67
23-01-28 10:01:50 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.82
23-01-27 10:01:50 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.82
23-01-26 10:01:57 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.82
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-01-30 10:02:18 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.89
22-10-28 10:02:26 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.43
22-09-23 10:02:01 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.48
22-09-09 10:03:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.94
22-09-08 10:03:19 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.91
22-09-07 10:04:24 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.91
22-03-16 10:02:55 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.29
22-03-02 10:02:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 4.35
20-08-29 10:03:17 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
20-08-28 10:04:01 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-07-14 13:32:19 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED
23-07-04 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-03 10:01:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING
23-07-03 09:30:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-03 09:30:30 ISD STARTUP
23-07-03 09:30:21 ISD SHUTDOWN
23-07-03 09:30:12 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED
23-05-30 10:03:49 READINESS ISD:PP EVR:PP ISD & EVR READY
23-05-30 08:43:15 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-05-30 08:43:15 ISD STARTUP
Post Alarm History
Responses Received:
I10200
JUL 19, 2023 10:14 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 163895 162917
2 INTERSTITIAL BD 201249 200601
3 7SMARTSENSOR BD 9865629 501987
4 UNUSED 9830660 4882134
5 UNUSED 9822698 4876985
6 UNUSED 9822698 4876505
7 UNUSED 9822174 4877967
8 UNUSED 9816831 4874542
9 WPLLD POWER BD 201158 200748
10 AC INTERFACE BD 163488 163171
11 RELAY BOARD 15049 15021
12 UNUSED 9832520 4886363
13 UNUSED 9813998 4885730
14 UNUSED 9818146 4886494
15 UNUSED 9810562 4885578
16 UNUSED 9815423 4882807
COMM 1 ELEC DISP INT. 100267 100108
COMM 2 WPLLD COMM BD 201900 201600
COMM 3 RS232 SERIAL BD 14902 14890
COMM 4 UNUSED 9825501 4886603
COMM 5 RS485 SERIAL BD 9815800 68165
COMM 6 RS232 SERIAL BD 9814270 14912
I90200
JUL 19, 2023 10:14 AM
SOFTWARE REVISION LEVEL
VERSION 333.05
SOFTWARE# 346333-100-F
CREATED - 13.12.11.14.16
S-MODULE# 330160-016-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
ISD/APM
PLLD
0.10 REPETITIV
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I11100
JUL 19, 2023 10:14 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-19-23 9:36AM
W 1 OTHER SUPER GROSS LINE FAIL CLEAR 7-19-23 9:36AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-19-23 9:34AM
W 1 OTHER SUPER GROSS LINE FAIL ALARM 7-19-23 9:34AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-19-23 9:19AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-19-23 9:19AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-19-23 9:19AM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 7-19-23 9:19AM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 7-19-23 9:19AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-19-23 9:19AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-19-23 9:19AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-19-23 9:19AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-19-23 9:06AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-19-23 9:06AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-19-23 9:06AM
L 1 DISP PAN UDC 1-2 FUEL ALARM CLEAR 7-19-23 9:06AM
L 1 DISP PAN UDC 1-2 FUEL ALARM ALARM 7-19-23 9:06AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-19-23 9:06AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-19-23 9:06AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-19-23 9:06AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-03-23 10:30AM
W 2 OTHER UNLEADED GROSS LINE FAIL CLEAR 7-03-23 10:30AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-03-23 10:25AM
W 2 OTHER UNLEADED GROSS LINE FAIL ALARM 7-03-23 10:25AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-03-23 10:08AM
W 1 OTHER SUPER GROSS LINE FAIL CLEAR 7-03-23 10:08AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-03-23 10:02AM
W 1 OTHER SUPER GROSS LINE FAIL ALARM 7-03-23 10:02AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:29AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:29AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:29AM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 7-03-23 9:29AM
L 1 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 7-03-23 9:29AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-03-23 9:29AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-03-23 9:29AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-03-23 9:29AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:13AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:13AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM CLEAR 7-03-23 9:13AM
L 1 DISP PAN UDC 1-2 FUEL ALARM CLEAR 7-03-23 9:13AM
L 1 DISP PAN UDC 1-2 FUEL ALARM ALARM 7-03-23 9:12AM
W 3 OTHER DIESEL WPLLD SHUTDOWN ALM ALARM 7-03-23 9:12AM
W 2 OTHER UNLEADED WPLLD SHUTDOWN ALM ALARM 7-03-23 9:12AM
W 1 OTHER SUPER WPLLD SHUTDOWN ALM ALARM 7-03-23 9:12AM
T 2 TANK UNLEADED OVERFILL ALARM CLEAR 6-27-23 1:17AM
T 2 TANK UNLEADED OVERFILL ALARM ALARM 6-27-23 1:13AM
T 2 TANK UNLEADED OVERFILL ALARM CLEAR 6-27-23 1:09AM
T 2 TANK UNLEADED OVERFILL ALARM ALARM 6-27-23 1:06AM
T 2 TANK UNLEADED LOW PRODUCT ALARM CLEAR 5-07-23 7:48AM
T 2 TANK UNLEADED LOW PRODUCT ALARM ALARM 5-06-23 7:26PM
I11200
JUL 19, 2023 10:14 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 7-14-23 1:32PM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 7-14-23 10:01AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN CLEAR 7-03-23 9:30AM
h 4 OTHER FP4: BLEND3 DEGRD COLLECT WARN ALARM 7-02-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 6-26-23 8:02AM
SYSTEM PAPER OUT CLEAR 6-26-23 8:02AM
SYSTEM PRINTER ERROR ALARM 6-26-23 8:00AM
SYSTEM PAPER OUT ALARM 6-26-23 8:00AM
SYSTEM PRINTER ERROR CLEAR 5-09-23 6:20AM
SYSTEM PAPER OUT CLEAR 5-09-23 6:20AM
SYSTEM PRINTER ERROR ALARM 5-09-23 6:00AM
SYSTEM PAPER OUT ALARM 5-09-23 6:00AM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 5-07-23 7:48AM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 5-06-23 7:26PM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 5-02-23 5:52AM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 5-01-23 10:26PM
T 3 TANK SUPER DELIVERY NEEDED CLEAR 4-18-23 2:57PM
T 4 TANK DIESEL SETUP DATA WARNING CLEAR 4-18-23 2:57PM
T 3 TANK SUPER SETUP DATA WARNING CLEAR 4-18-23 2:57PM
T 4 TANK DIESEL DELIVERY NEEDED CLEAR 4-18-23 2:57PM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 4-18-23 2:35PM
T 2 TANK UNLEADED SETUP DATA WARNING CLEAR 4-18-23 2:35PM
T 3 TANK SUPER SETUP DATA WARNING ALARM 4-17-23 2:48PM
T 2 TANK UNLEADED SETUP DATA WARNING ALARM 4-17-23 2:48PM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 4-17-23 2:48PM
T 3 TANK SUPER DELIVERY NEEDED ALARM 4-17-23 2:48PM
T 3 TANK SUPER DELIVERY NEEDED CLEAR 4-17-23 2:47PM
T 3 TANK SUPER SETUP DATA WARNING CLEAR 4-17-23 2:47PM
T 2 TANK UNLEADED DELIVERY NEEDED CLEAR 4-17-23 2:47PM
T 2 TANK UNLEADED SETUP DATA WARNING CLEAR 4-17-23 2:47PM
T 1 TANK SETUP DATA WARNING CLEAR 4-17-23 2:39PM
T 1 TANK SETUP DATA WARNING ALARM 4-17-23 2:38PM
T 3 TANK SUPER DELIVERY NEEDED ALARM 4-16-23 1:29PM
T 4 TANK DIESEL DELIVERY NEEDED ALARM 4-16-23 1:29PM
T 2 TANK UNLEADED DELIVERY NEEDED ALARM 4-16-23 1:29PM
T 4 TANK DIESEL SETUP DATA WARNING ALARM 4-16-23 1:29PM
T 3 TANK SUPER SETUP DATA WARNING ALARM 4-16-23 1:29PM
T 2 TANK UNLEADED SETUP DATA WARNING ALARM 4-16-23 1:29PM
SYSTEM PRINTER ERROR CLEAR 3-21-23 12:51PM
SYSTEM PAPER OUT CLEAR 3-21-23 12:51PM
SYSTEM PRINTER ERROR ALARM 3-11-23 6:00AM
SYSTEM PAPER OUT ALARM 3-11-23 6:00AM
OTHER ISD GROSS PRES WARN CLEAR 3-08-23 10:08AM
OTHER ISD GROSS PRES WARN ALARM 3-08-23 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 2-22-23 6:12PM
OTHER ISD GROSS PRES WARN ALARM 2-22-23 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 2-15-23 10:21AM
OTHER ISD GROSS PRES WARN ALARM 2-15-23 10:01AM
OTHER ISD GROSS PRES WARN CLEAR 2-08-23 11:36AM
OTHER ISD GROSS PRES WARN ALARM 2-08-23 10:01AM
I20600
JUL 19, 2023 10:14 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
TANK ALARM HISTORY
TANK 2 UNLEADED
SETUP DATA WARNING APR 17, 2023 2:48 PM
APR 16, 2023 1:29 PM
HIGH WATER ALARM AUG 13, 2014 10:07 AM
OVERFILL ALARM JUN 27, 2023 1:13 AM
JUN 27, 2023 1:06 AM
JAN 15, 2023 12:41 AM
LOW PRODUCT ALARM MAY 6, 2023 7:26 PM
MAY 1, 2023 10:26 PM
APR 17, 2023 2:48 PM
SUDDEN LOSS ALARM FEB 1, 2020 4:26 AM
FEB 1, 2020 3:55 AM
FEB 1, 2020 3:49 AM
HIGH PRODUCT ALARM JUL 21, 2022 4:12 PM
AUG 18, 2020 11:26 AM
JUL 21, 2020 1:26 PM
INVALID FUEL LEVEL JUL 6, 2022 11:22 AM
JUL 5, 2022 9:15 AM
OCT 13, 2020 5:25 AM
PROBE OUT JUL 6, 2022 11:29 AM
JUL 5, 2022 10:26 AM
AUG 18, 2020 11:37 AM
HIGH WATER WARNING AUG 13, 2014 10:07 AM
DELIVERY NEEDED MAY 6, 2023 7:26 PM
MAY 1, 2023 10:26 PM
APR 17, 2023 2:48 PM
MAX PRODUCT ALARM JUL 21, 2022 4:12 PM
JUL 21, 2020 1:26 PM
AUG 4, 2017 9:14 AM
NO CSLD IDLE TIME JAN 27, 2021 6:53 AM
JAN 24, 2021 10:09 PM
DEC 10, 2020 11:15 PM
LOW TEMP WARNING JUL 31, 2018 3:15 PM
AUG 9, 2017 9:23 AM
AUG 11, 2016 9:48 AM
TANK 3 SUPER
SETUP DATA WARNING APR 17, 2023 2:48 PM
APR 16, 2023 1:29 PM
HIGH WATER ALARM JUL 15, 2022 2:19 PM
OVERFILL ALARM JUL 15, 2022 2:25 PM
AUG 18, 2020 11:25 AM
AUG 4, 2017 9:51 AM
LOW PRODUCT ALARM APR 17, 2023 2:48 PM
APR 16, 2023 1:29 PM
JUL 15, 2022 2:18 PM
SUDDEN LOSS ALARM JUL 15, 2022 2:20 PM
JUL 5, 2022 9:19 AM
JUL 5, 2022 8:48 AM
HIGH PRODUCT ALARM JUL 21, 2022 4:14 PM
JUL 15, 2022 2:24 PM
JUL 6, 2022 12:20 PM
INVALID FUEL LEVEL JUL 15, 2022 2:18 PM
JUL 5, 2022 8:51 AM
MAY 12, 2021 9:38 AM
PROBE OUT JUL 5, 2022 10:29 AM
MAY 12, 2021 10:07 AM
MAY 12, 2021 9:38 AM
HIGH WATER WARNING JUL 15, 2022 2:19 PM
AUG 18, 2020 11:19 AM
DELIVERY NEEDED APR 17, 2023 2:48 PM
APR 16, 2023 1:29 PM
JUL 15, 2022 2:18 PM
MAX PRODUCT ALARM JUL 21, 2022 4:14 PM
JUL 15, 2022 2:24 PM
JUL 6, 2022 12:20 PM
NO CSLD IDLE TIME JAN 24, 2021 10:18 PM
DEC 10, 2020 11:23 PM
LOW TEMP WARNING MAY 12, 2021 10:11 AM
AUG 18, 2020 11:41 AM
AUG 22, 2017 10:23 AM
TANK 4 DIESEL
SETUP DATA WARNING APR 16, 2023 1:29 PM
HIGH WATER ALARM AUG 18, 2020 11:32 AM
OVERFILL ALARM AUG 18, 2020 11:28 AM
AUG 7, 2018 9:41 AM
JUL 31, 2018 3:12 PM
LOW PRODUCT ALARM APR 16, 2023 1:29 PM
JUL 5, 2022 8:14 AM
SEP 16, 2021 10:14 AM
SUDDEN LOSS ALARM JUL 5, 2022 8:28 AM
JUL 5, 2022 8:03 AM
AUG 4, 2017 8:55 AM
HIGH PRODUCT ALARM JUL 21, 2022 4:16 PM
AUG 19, 2019 9:57 AM
JUL 31, 2018 3:12 PM
INVALID FUEL LEVEL JUL 5, 2022 8:19 AM
AUG 18, 2020 11:52 AM
AUG 18, 2020 11:44 AM
PROBE OUT JUL 5, 2022 10:54 AM
AUG 18, 2020 11:51 AM
AUG 18, 2020 11:47 AM
HIGH WATER WARNING AUG 18, 2020 11:32 AM
DELIVERY NEEDED APR 16, 2023 1:29 PM
JUL 5, 2022 8:14 AM
SEP 16, 2021 10:14 AM
LOW TEMP WARNING AUG 18, 2020 11:22 AM
AUG 11, 2016 9:44 AM
AUG 10, 2015 11:01 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 19, 2023 10:14 AM
I30200
JUL 19, 2023 10:14 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UDC 1-2
JUL 19, 2023 9:19 AM SENSOR OUT ALARM
JUL 19, 2023 9:06 AM FUEL ALARM
JUL 3, 2023 9:29 AM SENSOR OUT ALARM
I31600
JUL 19, 2023 10:15 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP SENSOR 3-4
SEP 1, 2020 2:01 PM COMMUNICATION ALARM
MAY 1, 2014 5:23 PM COMMUNICATION ALARM
2 VFM 1-2
3 VFM 3-4
I40200
JUL 19, 2023 10:15 AM
I40300
JUL 19, 2023 10:15 AM
I34200
JUL 19, 2023 10:15 AM
I34700
JUL 19, 2023 10:15 AM
IV0100
JUL 19, 2023 10:15 AM
HOWARDS 7776
3300 PLANS RD
BAKERSFIELD 93309
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-07-14 10:01:09 A/L RATIO DEGRADATION FP 4 BLEND3 0.79
23-07-02 10:02:46 A/L RATIO DEGRADATION FP 4 BLEND3 0.79
23-03-08 10:02:08 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.42
23-02-22 10:02:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-02-15 10:01:28 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.56
23-02-08 10:01:55 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.77
23-01-29 10:01:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.67
23-01-28 10:01:50 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.82
23-01-27 10:01:50 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.82
23-01-26 10:01:57 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.82
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-01-30 10:02:18 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.89
22-10-28 10:02:26 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.43
22-09-23 10:02:01 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.48
22-09-09 10:03:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.94
22-09-08 10:03:19 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.91
22-09-07 10:04:24 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.91
22-03-16 10:02:55 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.29
22-03-02 10:02:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 4.35
20-08-29 10:03:17 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
20-08-28 10:04:01 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-07-19 10:06:36 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-19 09:24:46 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-19 09:24:46 ISD STARTUP
23-07-19 09:24:42 ISD SHUTDOWN
23-07-19 09:09:49 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-19 09:09:49 ISD STARTUP
23-07-19 09:09:47 ISD SHUTDOWN
23-07-14 13:32:19 COLLECTION TEST HH04 GRADE TEST MANUALLY CLEARED
23-07-04 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-03 10:01:09 READINESS ISD:PP EVR:NP EVR READINESS PENDING