HomeMy WebLinkAboutFMC 2023Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10137943 07/25/23
Jaco #3366 Fastrip (West)
8001 White Lane Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fisher
1073967
10278702 03/10/25
Vaporless Manufacturing LLC 03/14/25
OPW-1193585 04/14/25
07/25/23 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 420 87-1 ANNULAR
L2 208 87-1 FILL SUMP
L3 208 87-1 STP
L4 420 87-2 ANNULAR
L5 208 87-2 FILL SUMP
L6 208 87-2 STP
L7 420 91 ANNULAR
L8 208 91 FILL SUMP
L9 208 91 STP
L10 420 DIESEL ANNULAR
L11 208 DIESEL FILL SUMP
L12 208 DIESEL STP
L13 208 DISPENSER 1/2
L14 208 DISPENSER 3/4
L15 208 DISPENSER 5/6
L16 208 DISPENSER 7/8
L17 208 DISPENSER 9/10
L18 208 DISPENSER 11/12
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 UNLEADED
T2 FX1V 91 PREMIUM
T3 FX1DV DIESEL
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
07/25/23
NO PARKINGNO PAR
KING
EXISTING BUILDING
L13
L14
L15L16
L17
L18
L12STP
L9STP
L6STP
L3STP
L10
L7
L4
L1
L11
L8
L5
L2
87-2 UNLEADED
12,000 GALLON87-1 UNLEADED
12,000 GALLON DIESEL12,000 GALLON
1/2
43
65
910
78
12/11
#3-366
#3-367
N
91 PREMIUM12,000 GALLON
V F
87-1 UNLEADED12,000 GALLON
87-2 UNLEADED12,000 GALLON91 PREMIUM12,000 GALLON
DIESEL12,000 GALLON
L5STP
L2STP
L11STP
L14STP
AL6
L1
L10
L13
L7/L8
L3
L12
L15
L9
L18
L17
L16L19
L20
L21
18/17
1516
1314
2122
1920
25/24
L22
PROPERTY LINE
PROPERTY LINEH
W
W
H
PRICE SIGN
PRICE SIGNDIESEL PRICE SIGN
#367
#366
NO PARKINGACCESS RAMPS ACCESSRAMPDUMPSTER
G
A
A
A
V F
V F
F
A A
A
A
A
F
F
F
F
V
V
V
366 LEGEND
L1 87-1 ANNULAR
L2 87-1 FILL
L3 87-1 STP
L4 87-2 ANNULAR
L5 87-2 FILL
L6 87-2 STP
L7 91 ANNULAR
L8 91 FILL
L9 91 STP
L10 DSL ANNULAR
L11 DSL FILL
L12 DSL STP
L13 UDC 1 - 2
L14 UDC 3 - 4
L15 UDC 5 - 6
L16 UDC 7 - 8
L17 UDC 9 - 10
L18 UDC 11 -12
367 LEGEND
L1 87-1 ANNULAR
L2 87-1 STP ANNULAR AND SUMP SENSOR 2-TO-1
L3 87-1 FILL
L5 87-2 STP
L6 87- 2 STP ANNULAR
L7 87-2 FILL
L8 87-2 ANNULAR FILL
L9 87-2 ANNULAR
L10 91 ANNULAR
L11 91 STP
L12 91 FILL
L13 DSL ANNULAR
L14 DSL STP
L15 DSL FILL
L16 UDC 13 - 14
L17 UDC 15 - 16
L18 UDC 17 - 18
L19 UDC 19 -20
L20 UDC 21 -22
L21 UDC 23 - 24
L22 VENT BOX ANNULAR AND SUMP SENSOR 2-TO-1
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3/2 INCH DOUBLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
S1: 87-2 UNLEADED VENT LINE
S2: PRODUCT SIPHON LINE AND VACUUM CHASE
S3: VAPOR RETURN LINE
EMERGENCY SHUT-OFF
OVERFILL ALARM
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
FIRE EXTINGUISHER
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
WH
A
F
V
SITE MAP
DATE REVISIONS
DATE:
DRAWN BY:
CHECKED:
APPROVED:
RAC CADFILE:
SHEET NO.
A.P.N.:385-013-21-4
SCALE:
CONVENIENCE MARKET FOR:
3101 STATE RDBAKERSFIELD, CA 93308
PROJECT OWNER:
DRAWING:
CD
FASTRIPS - 3-366-3-367 3366-MSP
FASTRIP FOOD STORE
BAKERSFIELD, CALIFORNIA 933098001 WHITE LN.
JACO HILL
SITE PLAN
C1
TAB:CERS
1"=15'-0"
INCHES012
SHEET SIZE 22 X 34
01/07/2022
8001 WHITE LN.
BAKERSFIELD, CA 93309
GOSFORD RD.
WHITE LN.
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FACILITY ID 15-021-097250
CERS ID 10137946
FASTRIPS 3-366 / 3-367
8001 WHITE LN.
BAKERSFIELD, CA 93309
02/12/2021 REV.
VICINITY MAP
PROJECT DATA
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #3366 Fastrip (West)8001 White LaneBakersfield101379433/47/8 11/12MPDMPDMPDMPDMPDMPD1/25/69/10ProductProductProductProductProductProductMark Fisher
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10137943 07/25/23
Jaco #3366 Fastrip (West)
8001 White Lane Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fisher
1073967
10278702 03/10/25
OPW-1193585 04/14/25
PEI1200, 1 hour hydrostatic test All Spill Containers
07/25/23 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1: 87-1
OPW
T2: 87-2
OPW
T3: 91
OPW
T4: DIESEL
OPW
System Setup Fastrip West (8001 White Lane)
Responses Received:
200
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
JUL 25, 2023 9:12 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 7566 66.67 1.5 82.6 4496
2 UNLEADED 2 7737 67.94 1.0 82.6 4325
3 PREMIUM 7640 67.22 0.0 82.7 4422
4 DIESEL 2698 30.54 1.2 82.6 9364
I90500
JUL 25, 2023 9:12 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JUL 25, 2023 9:12 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUL 25, 2023 9:12 AM
SHIFT TIME 1 : DISABLED
I50202
JUL 25, 2023 9:12 AM
SHIFT TIME 2 : DISABLED
I50203
JUL 25, 2023 9:12 AM
SHIFT TIME 3 : DISABLED
I50204
JUL 25, 2023 9:12 AM
SHIFT TIME 4 : DISABLED
I54600
JUL 25, 2023 9:12 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUL 25, 2023 9:12 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUL 25, 2023 9:12 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUL 25, 2023 9:12 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUL 25, 2023 9:12 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUL 25, 2023 9:12 AM
PRINT TC VOLUMES
ENABLED
I50E00
JUL 25, 2023 9:12 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUL 25, 2023 9:12 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUL 25, 2023 9:12 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUL 25, 2023 9:12 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUL 25, 2023 9:12 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUL 25, 2023 9:12 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUL 25, 2023 9:12 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUL 25, 2023 9:12 AM
TANK CHART SECURITY
DISABLED
I5BD00
JUL 25, 2023 9:12 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JUL 25, 2023 9:12 AM
MASS/DENSITY
DISABLED
I88101
JUL 25, 2023 9:12 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JUL 25, 2023 9:12 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
JUL 25, 2023 9:12 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JUL 25, 2023 9:12 AM
I88105
JUL 25, 2023 9:12 AM
I88106
JUL 25, 2023 9:12 AM
I52000
JUL 25, 2023 9:12 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE FEB 23, 2012 DISABLED
2 ON DATE FEB 23, 2012 DISABLED
3 ON DATE FEB 23, 2012 DISABLED
4 ON DATE FEB 23, 2012 DISABLED
5 ON DATE FEB 23, 2012 DISABLED
6 ON DATE FEB 23, 2012 DISABLED
7 ON DATE FEB 23, 2012 DISABLED
8 ON DATE FEB 23, 2012 DISABLED
I60100
JUL 25, 2023 9:12 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 UNLEADED 2 ON
3 PREMIUM ON
4 DIESEL ON
I60200
JUL 25, 2023 9:13 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 UNLEADED 2
3 PREMIUM
4 DIESEL
I60300
JUL 25, 2023 9:13 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 UNLEADED 2 2
3 PREMIUM 3
4 DIESEL 4
I60900
JUL 25, 2023 9:13 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 UNLEADED 2 0.000700
3 PREMIUM 0.000700
4 DIESEL 0.000450
I60700
JUL 25, 2023 9:13 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 111.00
2 UNLEADED 2 111.00
3 PREMIUM 111.00
4 DIESEL 111.00
I60A00
JUL 25, 2023 9:13 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 PT
12062 2 UNLEADED 2 1 PT 12062 3 PREMIUM
1 PT 12062 4 DIESEL 1 PT 12062
I60400
JUL 25, 2023 9:13 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062
2 UNLEADED 2 12062
3 PREMIUM 12062
4 DIESEL 12062
I60500
JUL 25, 2023 9:13 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062 0 0 0
2 UNLEADED 2 12062 0 0 0
3 PREMIUM 12062 0 0 0
4 DIESEL 12062 0 0 0
I60600
JUL 25, 2023 9:13 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 UNLEADED 2 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 PREMIUM 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 DIESEL 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUL 25, 2023 9:13 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 UNLEADED 2 NO
3 PREMIUM NO
4 DIESEL NO
I62F00
JUL 25, 2023 9:13 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN.
2 UNLEADED 2 4.0 IN.
3 PREMIUM 4.0 IN.
4 DIESEL 4.0 IN.
I62700
JUL 25, 2023 9:13 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 UNLEADED 2 2.0
3 PREMIUM 2.0
4 DIESEL 2.0
I64200
JUL 25, 2023 9:13 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 UNLEADED 2 LOW
3 PREMIUM LOW
4 DIESEL LOW
I62400
JUL 25, 2023 9:13 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 UNLEADED 2 3.0
3 PREMIUM 3.0
4 DIESEL 4.0
I62800
JUL 25, 2023 9:13 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12062
2 UNLEADED 2 12062
3 PREMIUM 12062
4 DIESEL 12062
I62300
JUL 25, 2023 9:13 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10856
2 UNLEADED 2 10856
3 PREMIUM 10856
4 DIESEL 10856
I62200
JUL 25, 2023 9:13 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11459
2 UNLEADED 2 11459
3 PREMIUM 11459
4 DIESEL 11459
I62900
JUL 25, 2023 9:13 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 482
2 UNLEADED 2 1800
3 PREMIUM 1689
4 DIESEL 1800
I62100
JUL 25, 2023 9:13 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 500
2 UNLEADED 2 500
3 PREMIUM 500
4 DIESEL 500
I62600
JUL 25, 2023 9:13 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 UNLEADED 2 99
3 PREMIUM 99
4 DIESEL 99
I62500
JUL 25, 2023 9:13 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 UNLEADED 2 99
3 PREMIUM 99
4 DIESEL 99
I60800
JUL 25, 2023 9:13 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 UNLEADED 2 0.00
3 PREMIUM 0.00
4 DIESEL 0.00
I60B00
JUL 25, 2023 9:13 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUL 25, 2023 9:13 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 UNLEADED 2 0.00
3 PREMIUM 0.00
4 DIESEL 0.00
I61200
JUL 25, 2023 9:13 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED 2 NONE
2 UNLEADED 2 1 NONE
3 PREMIUM NONE NONE
4 DIESEL NONE NONE
I63600
JUL 25, 2023 9:13 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 UNLEADED 2 120
3 PREMIUM 120
4 DIESEL 120
I62A00
JUL 25, 2023 9:13 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 UNLEADED 2 120
3 PREMIUM 120
4 DIESEL 120
I62C00
JUL 25, 2023 9:13 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 UNLEADED 2 STANDARD
3 PREMIUM STANDARD
4 DIESEL STANDARD
I62D00
JUL 25, 2023 9:13 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 UNLEADED 2 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUL 25, 2023 9:13 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 UNLEADED 2 OFF OFF
3 PREMIUM OFF OFF
4 DIESEL OFF OFF
I63000
JUL 25, 2023 9:13 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 UNLEADED 2 OFF
3 PREMIUM OFF
4 DIESEL OFF
I63200
JUL 25, 2023 9:13 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 UNLEADED 2 OFF
3 PREMIUM OFF
4 DIESEL OFF
I61000
JUL 25, 2023 9:13 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 UNLEADED 2 1
3 PREMIUM 1
4 DIESEL 1
I63A00
JUL 25, 2023 9:13 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 UNLEADED 2 10.00%
3 PREMIUM 10.00%
4 DIESEL 10.00%
I61100
JUL 25, 2023 9:13 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JUL 23, 2010
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
JUL 25, 2023 9:13 AM
CSLD PROBABLITY OF DETECTION
I61400
JUL 25, 2023 9:13 AM
CSLD CLIMATE FACTOR
I61600
JUL 25, 2023 9:13 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 UNLEADED 2 IMMEDIATE
3 PREMIUM IMMEDIATE
4 DIESEL IMMEDIATE
I61A00
JUL 25, 2023 9:13 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED
2 UNLEADED 2 DISABLED
3 PREMIUM DISABLED
4 DIESEL DISABLED
I61B00
JUL 25, 2023 9:13 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JUL 25, 2023 9:13 AM
CSLD REPORT ONLY
I62B00
JUL 25, 2023 9:13 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 UNLEADED 2 ??? 0, 0
3 PREMIUM ??? 0, 0
4 DIESEL ??? 0, 0
I63300
JUL 25, 2023 9:13 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUL 25, 2023 9:13 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 UNLEADED 2 0
3 PREMIUM 0
4 DIESEL 0
I63500
JUL 25, 2023 9:13 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 UNLEADED 2 1
3 PREMIUM 1
4 DIESEL 1
I63900
JUL 25, 2023 9:13 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 UNLEADED 2
END FACTOR: NONE
3 PREMIUM
END FACTOR: NONE
4 DIESEL
END FACTOR: NONE
I78000
JUL 25, 2023 9:13 AM
I77700
JUL 25, 2023 9:13 AM
I77800
JUL 25, 2023 9:13 AM
I78C00
JUL 25, 2023 9:13 AM
I78300
JUL 25, 2023 9:13 AM
I78F00
JUL 25, 2023 9:13 AM
I78700
JUL 25, 2023 9:13 AM
I70200
JUL 25, 2023 9:13 AM
LIQUID LABEL
DEVICE LABEL
1 UNL ANN
2 UNL FILL
3 UNL STP
4 UNL 2 ANN
5 UNLD 2 FILL
6 UNL 2 STP
7 PREM ANN
8 PREM FILL
9 PREM STP
10 DSL ANN
11 DSL FILL
12 DSL STP
13 DISP 1-2
14 DISP 3 4
15 DISP 5-6
16 DISP 7-8
17 DISP 9-10
18 DISP 11-12
19
20
21
22
23
24
I70300
JUL 25, 2023 9:13 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL ANN TRI-STATE (SINGLE FLOAT)
2 UNL FILL TRI-STATE (SINGLE FLOAT)
3 UNL STP TRI-STATE (SINGLE FLOAT)
4 UNL 2 ANN TRI-STATE (SINGLE FLOAT)
5 UNLD 2 FILL TRI-STATE (SINGLE FLOAT)
6 UNL 2 STP TRI-STATE (SINGLE FLOAT)
7 PREM ANN TRI-STATE (SINGLE FLOAT)
8 PREM FILL TRI-STATE (SINGLE FLOAT)
9 PREM STP TRI-STATE (SINGLE FLOAT)
10 DSL ANN TRI-STATE (SINGLE FLOAT)
11 DSL FILL TRI-STATE (SINGLE FLOAT)
12 DSL STP TRI-STATE (SINGLE FLOAT)
13 DISP 1-2 TRI-STATE (SINGLE FLOAT)
14 DISP 3 4 TRI-STATE (SINGLE FLOAT)
15 DISP 5-6 TRI-STATE (SINGLE FLOAT)
16 DISP 7-8 TRI-STATE (SINGLE FLOAT)
17 DISP 9-10 TRI-STATE (SINGLE FLOAT)
18 DISP 11-12 TRI-STATE (SINGLE FLOAT)
19 TRI-STATE (SINGLE FLOAT)
20 TRI-STATE (SINGLE FLOAT)
21 TRI-STATE (SINGLE FLOAT)
22 TRI-STATE (SINGLE FLOAT)
23 TRI-STATE (SINGLE FLOAT)
24 TRI-STATE (SINGLE FLOAT)
I70400
JUL 25, 2023 9:13 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL ANN ANNULAR SPACE
2 UNL FILL PIPING SUMP
3 UNL STP STP SUMP
4 UNL 2 ANN ANNULAR SPACE
5 UNLD 2 FILL PIPING SUMP
6 UNL 2 STP STP SUMP
7 PREM ANN ANNULAR SPACE
8 PREM FILL PIPING SUMP
9 PREM STP STP SUMP
10 DSL ANN ANNULAR SPACE
11 DSL FILL PIPING SUMP
12 DSL STP STP SUMP
13 DISP 1-2 DISPENSER PAN
14 DISP 3 4 DISPENSER PAN
15 DISP 5-6 DISPENSER PAN
16 DISP 7-8 DISPENSER PAN
17 DISP 9-10 DISPENSER PAN
18 DISP 11-12 DISPENSER PAN
19 OTHER SENSORS
20 OTHER SENSORS
21 OTHER SENSORS
22 OTHER SENSORS
23 OTHER SENSORS
24 OTHER SENSORS
I74200
JUL 25, 2023 9:13 AM
I74300
JUL 25, 2023 9:13 AM
I74400
JUL 25, 2023 9:13 AM
I74700
JUL 25, 2023 9:13 AM
I74800
JUL 25, 2023 9:13 AM
I74900
JUL 25, 2023 9:13 AM
I7BC00
JUL 25, 2023 9:13 AM
I80200
JUL 25, 2023 9:13 AM
I80300
JUL 25, 2023 9:13 AM
I80400
JUL 25, 2023 9:13 AM
I80700
JUL 25, 2023 9:13 AM
RELAY LABEL
DEVICE LABEL
1 SHUTDOWN
2 OVERFILL ALARM
3 INTERNAL ALARM
4
I80900
JUL 25, 2023 9:13 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 SHUTDOWN NORMALLY CLOSED
2 OVERFILL ALARM NORMALLY OPEN
3 INTERNAL ALARM NORMALLY OPEN
4 NORMALLY OPEN
I80B00
JUL 25, 2023 9:13 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 SHUTDOWN 3
2 OVERFILL ALARM NONE
3 INTERNAL ALARM NONE
4 NONE
I80A00
JUL 25, 2023 9:13 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 SHUTDOWN STANDARD
2 OVERFILL ALARM STANDARD
3 INTERNAL ALARM MOMENTARY
4 STANDARD
I80C00
JUL 25, 2023 9:13 AM
I80800
JUL 25, 2023 9:13 AM
RELAY SETUP REPORT
R 1:SHUTDOWN
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 3
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 6:FUEL ALARM
L 9:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L15:FUEL ALARM
L16:FUEL ALARM
L17:FUEL ALARM
L18:FUEL ALARM
L 3:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L16:SENSOR OUT ALARM
L17:SENSOR OUT ALARM
L18:SENSOR OUT ALARM
L 3:SHORT ALARM
L 6:SHORT ALARM
L 9:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
L15:SHORT ALARM
L16:SHORT ALARM
L17:SHORT ALARM
L18:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 3:INTERNAL ALARM
TYPE:
MOMENTARY
NORMALLY OPEN
IN-TANK ALARMS
ALL:LEAK ALARM
ALL:HIGH WATER ALARM
ALL:OVERFILL ALARM
ALL:LOW PRODUCT ALARM
ALL:SUDDEN LOSS ALARM
ALL:HIGH PRODUCT ALARM
ALL:INVALID FUEL LEVEL
ALL:PROBE OUT
ALL:HIGH WATER WARNING
ALL:DELIVERY NEEDED
ALL:MAX PRODUCT ALARM
ALL:GROSS TEST FAIL
ALL:PERIODIC TEST FAIL
ALL:ANNUAL TEST FAIL
ALL:PER TST NEEDED WRN
ALL:ANN TST NEEDED WRN
ALL:PER TST NEEDED ALM
ALL:ANN TST NEEDED ALM
ALL:TANK TEST ACTIVE
ALL:NO CSLD IDLE TIME
ALL:TANK SIPHON BREAK
ALL:LOW TEMP WARNING
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
SMARTSENSOR ALARMS
ALL:SETUP DATA WARNING
ALL:COMMUNICATION ALARM
ALL:SENSOR FAULT ALARM
ALL:FUEL WARNING
ALL:FUEL ALARM
ALL:WATER WARNING
ALL:WATER ALARM
ALL:HIGH LIQUID WARNING
ALL:HIGH LIQUID ALARM
ALL:LOW LIQUID WARNING
ISD SITE ALARMS
ISD STAGE I WARN
ISD GROSS PRES WARN
ISD GROSS PRES FAIL
ISD DEGRD PRES WARN
ISD DEGRD PRES FAIL
ISD VAPOR LEAK WARN
ISD VAPOR LEAK FAIL
ISD VP PRES WARN
ISD VP PRES FAIL
ISD VP STATUS WARN
ISD VP STATUS FAIL
MISSING RELAY SETUP
MISSING HOSE SETUP
MISSING TANK SETUP
MISS VAPOR FLOW MTR
MISS VAPOR PRES SEN
MISSING VP INPUT
ISD SETUP WARN
ISD SETUP FAIL
ISD SENSOR OUT WARN
ISD SENSOR OUT FAIL
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
JUL 25, 2023 9:14 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
JUL 25, 2023 9:14 AM
I72300
JUL 25, 2023 9:14 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 PS 11-12 VAPOR PRESSURE
02 FM 1-2 AIR FLOW METER
03 FM 3-4 AIR FLOW METER
04 FM 5-6 AIR FLOW METER
05 FM 7-8 AIR FLOW METER
06 FM 9-10 AIR FLOW METER
07 FM 11-12 AIR FLOW METER
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JUL 25, 2023 9:14 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
JUL 25, 2023 9:14 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JUL 25, 2023 9:14 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
VAPOR PROCESSOR TYPE
NONE
IV4700
JUL 25, 2023 9:14 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JUL 25, 2023 9:14 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ACCEPT HIGH ORVR: NO
IV4A00
JUL 25, 2023 9:14 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 01 BLEND3
02 02 02 01 01 BLEND3
03 03 03 02 01 BLEND3
04 04 04 02 01 BLEND3
05 05 05 03 01 BLEND3
06 06 06 03 01 BLEND3
07 07 07 04 01 BLEND3
08 08 08 04 01 BLEND3
09 09 09 05 01 BLEND3
10 10 10 05 01 BLEND3
11 11 11 06 01 BLEND3
12 12 12 06 01 BLEND3
IV4B00
JUL 25, 2023 9:14 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
09 05 02/09 03/09 09/09 xx/xx
10 05 02/10 03/10 09/10 xx/xx
11 06 02/11 03/11 09/11 xx/xx
12 06 02/12 03/12 09/12 xx/xx
IV4900
JUL 25, 2023 9:14 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JUL 25, 2023 9:14 AM
ISD VERSION: 01.07
Fastrip West 8001 White Lane Alarm History (Before)
Responses Received:
I10200
JUL 25, 2023 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39395 39306
2 4 PROBE / G.T. 163529 163246
3 INTERSTITIAL BD 201924 201556
4 INTERSTITIAL BD 201901 201646
5 INTERSTITIAL BD 201060 200747
6 UNUSED 9661155 9539505
7 UNUSED 9644453 9537285
8 UNUSED 9643221 9534828
9 UNUSED 9638633 9528133
10 RELAY BOARD 14922 14899
11 UNUSED 9641842 9534557
12 UNUSED 9636678 9531798
13 UNUSED 9641927 9531367
14 UNUSED 9635913 9528996
15 UNUSED 9631239 9534341
16 UNUSED 9633619 9532250
COMM 1 ELEC DISP INT. 100982 101008
COMM 2 RS232 SERIAL BD 15007 14985
COMM 3 RS232 SERIAL BD 15007 14985
COMM 4 UNUSED 9648981 9540053
COMM 5 UNUSED 9632131 9531388
COMM 6 UNUSED 9631664 9535914
I90200
JUL 25, 2023 9:16 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 25, 2023 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK UNLEADED 2 OVERFILL ALARM CLEAR 7-21-23 11:11AM
T 2 TANK UNLEADED 2 OVERFILL ALARM ALARM 7-21-23 11:09AM
L13 DISP PAN DISP 1-2 FUEL ALARM CLEAR 7-18-23 10:41AM
L13 DISP PAN DISP 1-2 FUEL ALARM ALARM 7-18-23 10:41AM
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L10 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 8 PIPE PREM FILL SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L12 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L14 DISP PAN DISP 3 4 SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L11 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L13 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 3 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 9 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 7 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 6 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 5 PIPE UNLD 2 FILL SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 7-18-23 10:32AM
L 3 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L 8 PIPE PREM FILL SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L 7 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L 6 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L 5 PIPE UNLD 2 FILL SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L10 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L12 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L11 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L 9 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L14 DISP PAN DISP 3 4 SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L13 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-18-23 10:31AM
L10 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-18-23 10:24AM
L10 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-18-23 10:19AM
L10 ANNULAR DSL ANN FUEL ALARM CLEAR 7-18-23 10:19AM
L 5 PIPE UNLD 2 FILL FUEL ALARM CLEAR 7-18-23 10:05AM
L 5 PIPE UNLD 2 FILL FUEL ALARM ALARM 7-18-23 10:03AM
L18 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-18-23 9:58AM
L18 DISP PAN DISP 11-12 FUEL ALARM ALARM 7-18-23 9:58AM
L17 DISP PAN DISP 9-10 FUEL ALARM CLEAR 7-18-23 9:56AM
L17 DISP PAN DISP 9-10 FUEL ALARM ALARM 7-18-23 9:56AM
L16 DISP PAN DISP 7-8 FUEL ALARM CLEAR 7-18-23 9:56AM
I11200
JUL 25, 2023 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 7-25-23 9:11AM
SYSTEM PRINTER ERROR ALARM 7-25-23 9:11AM
SYSTEM PRINTER ERROR CLEAR 7-16-23 7:43PM
SYSTEM PAPER OUT CLEAR 7-16-23 7:43PM
SYSTEM PAPER OUT ALARM 7-16-23 7:43PM
SYSTEM PRINTER ERROR ALARM 7-16-23 7:43PM
SYSTEM PRINTER ERROR CLEAR 6-19-23 4:52AM
SYSTEM PRINTER ERROR ALARM 6-18-23 3:45AM
SYSTEM PRINTER ERROR CLEAR 6-18-23 3:45AM
SYSTEM PRINTER ERROR ALARM 6-18-23 3:45AM
SYSTEM PRINTER ERROR CLEAR 6-18-23 3:45AM
SYSTEM PRINTER ERROR ALARM 6-18-23 3:44AM
SYSTEM PRINTER ERROR CLEAR 6-18-23 3:44AM
SYSTEM PAPER OUT CLEAR 6-18-23 3:44AM
SYSTEM PRINTER ERROR ALARM 6-18-23 3:44AM
SYSTEM PAPER OUT ALARM 6-18-23 3:44AM
SYSTEM PRINTER ERROR CLEAR 6-18-23 3:44AM
SYSTEM PAPER OUT CLEAR 6-18-23 3:44AM
SYSTEM PRINTER ERROR ALARM 6-16-23 5:56PM
SYSTEM PAPER OUT ALARM 6-16-23 5:56PM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 5-05-23 10:11AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 5-02-23 10:02AM
OTHER ISD VAPOR LEAK WARN CLEAR 4-10-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 4-09-23 7:43PM
SYSTEM PAPER OUT CLEAR 4-09-23 7:43PM
SYSTEM PRINTER ERROR ALARM 4-09-23 7:38PM
SYSTEM PAPER OUT ALARM 4-09-23 7:38PM
OTHER ISD VAPOR LEAK WARN ALARM 4-09-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 4-09-23 8:01AM
SYSTEM PAPER OUT CLEAR 4-09-23 8:01AM
SYSTEM PRINTER ERROR ALARM 4-09-23 8:01AM
SYSTEM PAPER OUT ALARM 4-09-23 8:01AM
SYSTEM PRINTER ERROR CLEAR 4-09-23 8:00AM
SYSTEM PAPER OUT CLEAR 4-09-23 8:00AM
SYSTEM PRINTER ERROR ALARM 4-09-23 8:00AM
SYSTEM PAPER OUT ALARM 4-09-23 8:00AM
SYSTEM PRINTER ERROR CLEAR 4-09-23 8:00AM
SYSTEM PAPER OUT CLEAR 4-09-23 8:00AM
SYSTEM PRINTER ERROR ALARM 4-09-23 5:44AM
SYSTEM PAPER OUT ALARM 4-09-23 5:44AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 4-07-23 5:08PM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 4-07-23 10:02AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 4-05-23 10:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 4-04-23 10:02AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 3-31-23 10:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 3-24-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 3-11-23 11:23AM
SYSTEM PAPER OUT CLEAR 3-11-23 11:23AM
SYSTEM PRINTER ERROR ALARM 3-11-23 11:18AM
SYSTEM PAPER OUT ALARM 3-11-23 11:18AM
I20600
JUL 25, 2023 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUN 18, 2023 4:06 AM
JUN 12, 2023 9:17 AM
MAR 21, 2023 12:27 AM
TANK 2 UNLEADED 2
OVERFILL ALARM JUL 21, 2023 11:09 AM
JUL 16, 2023 10:00 AM
JUL 7, 2023 11:57 AM
TANK 3 PREMIUM
OVERFILL ALARM NOV 5, 2022 2:16 AM
TANK 4 DIESEL
LOW PRODUCT ALARM FEB 13, 2021 8:05 AM
DELIVERY NEEDED SEP 3, 2022 8:31 AM
MAY 24, 2022 9:25 AM
FEB 13, 2021 8:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 25, 2023 9:16 AM
I30200
JUL 25, 2023 9:16 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL ANN
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:53 AM FUEL ALARM
JUL 25, 2022 9:10 AM SENSOR OUT ALARM
2 UNL FILL
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:45 AM FUEL ALARM
JUN 16, 2023 6:34 AM FUEL ALARM
3 UNL STP
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:45 AM FUEL ALARM
JUL 25, 2022 9:10 AM SENSOR OUT ALARM
4 UNL 2 ANN
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:52 AM FUEL ALARM
JUL 25, 2022 9:10 AM SENSOR OUT ALARM
5 UNLD 2 FILL
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 10:03 AM FUEL ALARM
JUL 25, 2022 9:10 AM SENSOR OUT ALARM
6 UNL 2 STP
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:44 AM FUEL ALARM
JUL 25, 2022 9:10 AM SENSOR OUT ALARM
7 PREM ANN
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:50 AM FUEL ALARM
JUL 25, 2022 9:10 AM SENSOR OUT ALARM
8 PREM FILL
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:47 AM FUEL ALARM
JUL 25, 2022 9:10 AM SENSOR OUT ALARM
9 PREM STP
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:43 AM FUEL ALARM
JUL 25, 2022 9:10 AM FUEL ALARM
10 DSL ANN
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 10:19 AM SENSOR OUT ALARM
JUL 18, 2023 9:48 AM FUEL ALARM
11 DSL FILL
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:47 AM FUEL ALARM
JUN 21, 2023 6:13 AM FUEL ALARM
12 DSL STP
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:42 AM FUEL ALARM
JUL 16, 2023 6:46 PM FUEL ALARM
13 DISP 1-2
JUL 18, 2023 10:41 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:54 AM FUEL ALARM
14 DISP 3 4
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:54 AM FUEL ALARM
JUL 25, 2022 9:10 AM FUEL ALARM
15 DISP 5-6
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:55 AM FUEL ALARM
JUL 25, 2022 9:10 AM FUEL ALARM
16 DISP 7-8
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:56 AM FUEL ALARM
JUL 25, 2022 9:10 AM FUEL ALARM
17 DISP 9-10
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:56 AM FUEL ALARM
JUL 25, 2022 9:10 AM SENSOR OUT ALARM
18 DISP 11-12
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
JUL 18, 2023 9:58 AM FUEL ALARM
JUL 25, 2022 9:10 AM SENSOR OUT ALARM
I31600
JUL 25, 2023 9:17 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 11-12
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
6 FM 9-10
JUL 20, 2022 5:02 PM COMMUNICATION ALARM
JUL 20, 2022 3:11 PM COMMUNICATION ALARM
JUL 20, 2022 12:29 PM COMMUNICATION ALARM
7 FM 11-12
I40200
JUL 25, 2023 9:17 AM
I40300
JUL 25, 2023 9:17 AM
I34200
JUL 25, 2023 9:17 AM
I34700
JUL 25, 2023 9:17 AM
IV0100
JUL 25, 2023 9:17 AM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-05-05 10:02:01 A/L RATIO DEGRADATION FP10 BLEND3 0.79
23-05-04 10:02:12 A/L RATIO DEGRADATION FP10 BLEND3 0.78
23-05-03 10:02:05 A/L RATIO DEGRADATION FP10 BLEND3 0.78
23-05-02 10:02:06 A/L RATIO DEGRADATION FP10 BLEND3 0.79
23-04-09 10:02:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.61
23-04-07 10:02:09 A/L RATIO DEGRADATION FP 3 BLEND3 0.77
23-04-04 10:02:13 A/L RATIO DEGRADATION FP 3 BLEND3 0.80
23-03-30 10:02:14 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
23-03-29 10:02:15 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
23-03-28 10:02:26 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-03-31 10:02:22 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
22-08-06 10:01:53 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-08-03 10:01:09 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-02-13 10:01:35 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
21-04-19 10:02:18 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
20-10-23 10:01:58 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD
20-10-23 10:01:58 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD
20-10-17 10:02:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
20-06-14 10:01:09 A/L RATIO GROSS BLOCKAGE FP 9 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-07-19 10:02:31 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-18 10:33:36 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-18 10:33:36 ISD STARTUP
23-07-18 10:33:17 ISD SHUTDOWN
23-07-17 10:02:59 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-16 15:54:20 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-16 15:54:20 ISD STARTUP
23-07-16 15:53:51 ISD SHUTDOWN
23-05-05 10:11:01 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED
23-04-07 17:08:09 COLLECTION TEST HH03 GRADE TEST MANUALLY CLEARED
After:
Responses Received:
I10200
JUL 25, 2023 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39395 39303
2 4 PROBE / G.T. 163529 162963
3 INTERSTITIAL BD 201924 201470
4 INTERSTITIAL BD 201901 201448
5 INTERSTITIAL BD 201060 200551
6 UNUSED 9661155 9553595
7 UNUSED 9644453 9552498
8 UNUSED 9643221 9545940
9 UNUSED 9638633 9545973
10 RELAY BOARD 14922 14892
11 UNUSED 9641842 9550316
12 UNUSED 9636678 9547629
13 UNUSED 9641927 9542360
14 UNUSED 9635913 9545844
15 UNUSED 9631239 9549091
16 UNUSED 9633619 9548768
COMM 1 ELEC DISP INT. 100982 100902
COMM 2 RS232 SERIAL BD 15007 14978
COMM 3 RS232 SERIAL BD 15007 14978
COMM 4 UNUSED 9648981 9553735
COMM 5 UNUSED 9632131 9547199
COMM 6 UNUSED 9631664 9548575
I90200
JUL 25, 2023 12:04 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 25, 2023 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-25-23 9:55AM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-25-23 9:55AM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L12 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L14 DISP PAN DISP 3 4 SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 9 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L11 PIPE DSL FILL SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L13 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 3 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L10 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 8 PIPE PREM FILL SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 7 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 6 STP SUMP UNL 2 STP SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 2 PIPE UNL FILL SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 5 PIPE UNLD 2 FILL SENSOR OUT ALARM CLEAR 7-25-23 9:54AM
L 3 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L 8 PIPE PREM FILL SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L 7 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L 2 PIPE UNL FILL SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L 6 STP SUMP UNL 2 STP SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L 1 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L 5 PIPE UNLD 2 FILL SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L 4 ANNULAR UNL 2 ANN SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L13 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L12 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L16 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L14 DISP PAN DISP 3 4 SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L15 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L11 PIPE DSL FILL SENSOR OUT ALARM ALARM 7-25-23 9:53AM
L10 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-25-23 9:52AM
L 9 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-25-23 9:52AM
L18 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-25-23 9:52AM
L17 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-25-23 9:52AM
L13 DISP PAN DISP 1-2 FUEL ALARM CLEAR 7-25-23 9:47AM
L13 DISP PAN DISP 1-2 FUEL ALARM ALARM 7-25-23 9:46AM
L14 DISP PAN DISP 3 4 FUEL ALARM CLEAR 7-25-23 9:46AM
L14 DISP PAN DISP 3 4 FUEL ALARM ALARM 7-25-23 9:45AM
L15 DISP PAN DISP 5-6 FUEL ALARM CLEAR 7-25-23 9:45AM
L15 DISP PAN DISP 5-6 FUEL ALARM ALARM 7-25-23 9:45AM
L16 DISP PAN DISP 7-8 FUEL ALARM CLEAR 7-25-23 9:43AM
L16 DISP PAN DISP 7-8 FUEL ALARM ALARM 7-25-23 9:43AM
L17 DISP PAN DISP 9-10 FUEL ALARM CLEAR 7-25-23 9:42AM
L17 DISP PAN DISP 9-10 FUEL ALARM ALARM 7-25-23 9:42AM
L18 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-25-23 9:41AM
L18 DISP PAN DISP 11-12 FUEL ALARM ALARM 7-25-23 9:41AM
L 2 PIPE UNL FILL FUEL ALARM CLEAR 7-25-23 9:39AM
L 2 PIPE UNL FILL FUEL ALARM ALARM 7-25-23 9:39AM
I11200
JUL 25, 2023 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 7-25-23 9:11AM
SYSTEM PRINTER ERROR ALARM 7-25-23 9:11AM
SYSTEM PRINTER ERROR CLEAR 7-16-23 7:43PM
SYSTEM PAPER OUT CLEAR 7-16-23 7:43PM
SYSTEM PAPER OUT ALARM 7-16-23 7:43PM
SYSTEM PRINTER ERROR ALARM 7-16-23 7:43PM
SYSTEM PRINTER ERROR CLEAR 6-19-23 4:52AM
SYSTEM PRINTER ERROR ALARM 6-18-23 3:45AM
SYSTEM PRINTER ERROR CLEAR 6-18-23 3:45AM
SYSTEM PRINTER ERROR ALARM 6-18-23 3:45AM
SYSTEM PRINTER ERROR CLEAR 6-18-23 3:45AM
SYSTEM PRINTER ERROR ALARM 6-18-23 3:44AM
SYSTEM PRINTER ERROR CLEAR 6-18-23 3:44AM
SYSTEM PAPER OUT CLEAR 6-18-23 3:44AM
SYSTEM PRINTER ERROR ALARM 6-18-23 3:44AM
SYSTEM PAPER OUT ALARM 6-18-23 3:44AM
SYSTEM PRINTER ERROR CLEAR 6-18-23 3:44AM
SYSTEM PAPER OUT CLEAR 6-18-23 3:44AM
SYSTEM PRINTER ERROR ALARM 6-16-23 5:56PM
SYSTEM PAPER OUT ALARM 6-16-23 5:56PM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 5-05-23 10:11AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 5-02-23 10:02AM
OTHER ISD VAPOR LEAK WARN CLEAR 4-10-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 4-09-23 7:43PM
SYSTEM PAPER OUT CLEAR 4-09-23 7:43PM
SYSTEM PRINTER ERROR ALARM 4-09-23 7:38PM
SYSTEM PAPER OUT ALARM 4-09-23 7:38PM
OTHER ISD VAPOR LEAK WARN ALARM 4-09-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 4-09-23 8:01AM
SYSTEM PAPER OUT CLEAR 4-09-23 8:01AM
SYSTEM PRINTER ERROR ALARM 4-09-23 8:01AM
SYSTEM PAPER OUT ALARM 4-09-23 8:01AM
SYSTEM PRINTER ERROR CLEAR 4-09-23 8:00AM
SYSTEM PAPER OUT CLEAR 4-09-23 8:00AM
SYSTEM PRINTER ERROR ALARM 4-09-23 8:00AM
SYSTEM PAPER OUT ALARM 4-09-23 8:00AM
SYSTEM PRINTER ERROR CLEAR 4-09-23 8:00AM
SYSTEM PAPER OUT CLEAR 4-09-23 8:00AM
SYSTEM PRINTER ERROR ALARM 4-09-23 5:44AM
SYSTEM PAPER OUT ALARM 4-09-23 5:44AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 4-07-23 5:08PM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 4-07-23 10:02AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 4-05-23 10:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 4-04-23 10:02AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 3-31-23 10:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 3-24-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 3-11-23 11:23AM
SYSTEM PAPER OUT CLEAR 3-11-23 11:23AM
SYSTEM PRINTER ERROR ALARM 3-11-23 11:18AM
SYSTEM PAPER OUT ALARM 3-11-23 11:18AM
I20600
JUL 25, 2023 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUN 18, 2023 4:06 AM
JUN 12, 2023 9:17 AM
MAR 21, 2023 12:27 AM
TANK 2 UNLEADED 2
OVERFILL ALARM JUL 21, 2023 11:09 AM
JUL 16, 2023 10:00 AM
JUL 7, 2023 11:57 AM
TANK 3 PREMIUM
OVERFILL ALARM NOV 5, 2022 2:16 AM
TANK 4 DIESEL
LOW PRODUCT ALARM FEB 13, 2021 8:05 AM
DELIVERY NEEDED SEP 3, 2022 8:31 AM
MAY 24, 2022 9:25 AM
FEB 13, 2021 8:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 25, 2023 12:04 PM
I30200
JUL 25, 2023 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL ANN
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:38 AM FUEL ALARM
JUL 25, 2023 9:37 AM FUEL ALARM
2 UNL FILL
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:39 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
3 UNL STP
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:30 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
4 UNL 2 ANN
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:34 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
5 UNLD 2 FILL
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:37 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
6 UNL 2 STP
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:26 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
7 PREM ANN
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:32 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
8 PREM FILL
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:33 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
9 PREM STP
JUL 25, 2023 9:52 AM SENSOR OUT ALARM
JUL 25, 2023 9:27 AM FUEL ALARM
JUL 25, 2023 9:26 AM FUEL ALARM
10 DSL ANN
JUL 25, 2023 9:52 AM SENSOR OUT ALARM
JUL 25, 2023 9:29 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
11 DSL FILL
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:30 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
12 DSL STP
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:28 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
13 DISP 1-2
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:46 AM FUEL ALARM
JUL 18, 2023 10:41 AM FUEL ALARM
14 DISP 3 4
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:45 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
15 DISP 5-6
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:45 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
16 DISP 7-8
JUL 25, 2023 9:53 AM SENSOR OUT ALARM
JUL 25, 2023 9:43 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
17 DISP 9-10
JUL 25, 2023 9:52 AM SENSOR OUT ALARM
JUL 25, 2023 9:42 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
18 DISP 11-12
JUL 25, 2023 9:52 AM SENSOR OUT ALARM
JUL 25, 2023 9:41 AM FUEL ALARM
JUL 18, 2023 10:31 AM SENSOR OUT ALARM
I31600
JUL 25, 2023 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 PS 11-12
2 FM 1-2
3 FM 3-4
4 FM 5-6
5 FM 7-8
6 FM 9-10
JUL 20, 2022 5:02 PM COMMUNICATION ALARM
JUL 20, 2022 3:11 PM COMMUNICATION ALARM
JUL 20, 2022 12:29 PM COMMUNICATION ALARM
7 FM 11-12
I40200
JUL 25, 2023 12:04 PM
I40300
JUL 25, 2023 12:04 PM
I34200
JUL 25, 2023 12:04 PM
I34700
JUL 25, 2023 12:04 PM
IV0100
JUL 25, 2023 12:04 PM
FASTRIP 366
8001 WHITE LN
BAKERSFIELD CA
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-05-05 10:02:01 A/L RATIO DEGRADATION FP10 BLEND3 0.79
23-05-04 10:02:12 A/L RATIO DEGRADATION FP10 BLEND3 0.78
23-05-03 10:02:05 A/L RATIO DEGRADATION FP10 BLEND3 0.78
23-05-02 10:02:06 A/L RATIO DEGRADATION FP10 BLEND3 0.79
23-04-09 10:02:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.61
23-04-07 10:02:09 A/L RATIO DEGRADATION FP 3 BLEND3 0.77
23-04-04 10:02:13 A/L RATIO DEGRADATION FP 3 BLEND3 0.80
23-03-30 10:02:14 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
23-03-29 10:02:15 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
23-03-28 10:02:26 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-03-31 10:02:22 A/L RATIO DEGRADATION FP 3 BLEND3 0.72
22-08-06 10:01:53 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-08-03 10:01:09 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-02-13 10:01:35 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
21-04-19 10:02:18 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
20-10-23 10:01:58 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD
20-10-23 10:01:58 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD
20-10-17 10:02:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
20-06-14 10:01:09 A/L RATIO GROSS BLOCKAGE FP10 BLEND3 BLKD
20-06-14 10:01:09 A/L RATIO GROSS BLOCKAGE FP 9 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-07-25 10:02:50 READINESS ISD:PP EVR:NP EVR READINESS PENDING
23-07-25 09:55:34 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-25 09:55:34 ISD STARTUP
23-07-25 09:55:22 ISD SHUTDOWN
23-07-19 10:02:31 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-18 10:33:36 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-18 10:33:36 ISD STARTUP
23-07-18 10:33:17 ISD SHUTDOWN
23-07-17 10:02:59 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-16 15:54:20 READINESS ISD:PP EVR:NN EVR READINESS PENDING