HomeMy WebLinkAboutFMC 2023Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10155793 7/26/2023
Jaco #7705 Fastrip #641
1200 Coffee Road Bakersfield 93308
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Aaron Perrigo
1073967
8485827 8/8/2024
VMI 3924 10/24/2024
GVR ATG B47853 7/30/2024
7/26/2023 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder-Root TLS 350R
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 UNL STP
L2 420 UNL ANN
L3 208 UNL FILL
L4 208 PREM STP
C1 208 PREM ANN
L6 208 PREM FILL
L7 208 DSL STP
L8 420 DSL ANN
L9 208 DSL FILL
L10 208 DISP 1-2
L11 208 DISP 3-4
L12 208 DISP 5-6
L13 208 DISP 7-8
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V UNL
T2 FX1V PREM
T3 FX1DV DIESEL
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
V F L9
L6
L3
STP L1
STP L4
STP L7
L10
L11 L13
L12 1 2
3 4
5 6
7 8
COFFEE RD BRIMHALL RDPROPERTY LINE
PROPERTY LINEW
G
V F
V F12,000 GALLON87 UNLEADED
12,000 GALLON91 PREMIUM
12,000 GALLONDIESEL L8
L5
L2
A
A
A
EXISTING BUILDING
DUMPSTER
NOPARKING
PRICE SIGNCATCHBASIN
N
W
H
LEGEND
L1 87 STP
L2 87 ANNULAR
L3 87 FILL
L4 91 STP
L5 91 ANNULAR
L6 91 FILL
L7 DSL STP
L8 DSL ANNULAR
L9 DSL FILL
L10 UDC 1 - 2
L11 UDC 3 - 4
L12 UDC 5 - 6
L13 UDC 7 - 8
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 3/2 INCH DOUBLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
UST ELECTRICAL PANEL
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
W
G
A
H
P
V
SITE MAP
PROJECT OWNER:
JAMIESON HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FASTRIP #7705
FACILITY ID 15-021-003504
CERS ID 10133029
1200 COFFEE RD.
BAKERSFIELD, CA 93308
09/14/16 REV.
1200 COFFEE RD.
BAKERSFIELD, CA 93308
SCALE:
C1
VICINITY MAP
PROJECT DATA
1"=10'-0"
INCHES012
SHEET SIZE 22 X 34
BRIMHALL RD.COFFEE RD.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #7705 Fastrip #6411200 Coffee RoadBakersfield101557931/23/4 5/68791Diesel 87918791Diesel 871/21/23/45/65/67/8ProductProductProductProductProductProductProductProductProductAaron Perrigo
APPENDIX C-10
7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB917/8ProductAaron Perrigo
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10155793 7/26/2023
Jaco #7705 Fastrip #641
1200 Coffee Road Bakersfield 93308
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Aaron Perrigo
1073967
8485827 8/8/2024
FFS 1010993708 7/10/2024
PEI 1200 Lake Test SPILL BUCKETS x3
7/26/2023 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1
PHILTITE
T2
PHILTITE
T3
PHILTITE
Jaco 7705 Setup
Responses Received:
200
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
AUG 2, 2023 12:19 PM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 2484 28.84 1.1 85.4 9548
2 PREMIUM 7816 68.66 0.0 86.9 4216
3 DIESEL 6589 59.65 1.0 90.0 5443
I90500
AUG 2, 2023 12:19 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
AUG 2, 2023 12:19 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
AUG 2, 2023 12:19 PM
SHIFT TIME 1 : 11:00 PM
I50202
AUG 2, 2023 12:19 PM
SHIFT TIME 2 : DISABLED
I50203
AUG 2, 2023 12:19 PM
SHIFT TIME 3 : DISABLED
I50204
AUG 2, 2023 12:19 PM
SHIFT TIME 4 : DISABLED
I54600
AUG 2, 2023 12:19 PM
TANK PER TST NEEDED WRN: DISABLED
I54900
AUG 2, 2023 12:19 PM
TANK ANN TST NEEDED WRN: DISABLED
I55300
AUG 2, 2023 12:19 PM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
AUG 2, 2023 12:19 PM
LINE PER TST NEEDED WRN: DISABLED
I55900
AUG 2, 2023 12:19 PM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
AUG 2, 2023 12:19 PM
PRINT TC VOLUMES
ENABLED
I50E00
AUG 2, 2023 12:19 PM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
AUG 2, 2023 12:19 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
AUG 2, 2023 12:19 PM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
AUG 2, 2023 12:19 PM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
AUG 2, 2023 12:19 PM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE OCT WEEK 6 SUN 2:00 AM
I51600
AUG 2, 2023 12:19 PM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
AUG 2, 2023 12:19 PM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
AUG 2, 2023 12:19 PM
TANK CHART SECURITY
DISABLED
I5BD00
AUG 2, 2023 12:19 PM
CUSTOM ALARM LABELS
DISABLED
I56000
AUG 2, 2023 12:19 PM
MASS/DENSITY
DISABLED
I88101
AUG 2, 2023 12:19 PM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88102
AUG 2, 2023 12:19 PM
PORT SETTINGS:
COMM BOARD : 2 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88103
AUG 2, 2023 12:19 PM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
AUG 2, 2023 12:19 PM
I88105
AUG 2, 2023 12:19 PM
I88106
AUG 2, 2023 12:19 PM
I52000
AUG 2, 2023 12:19 PM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE DEC 7, 2010 DISABLED
2 ON DATE DEC 7, 2010 DISABLED
3 ON DATE DEC 7, 2010 DISABLED
4 ON DATE DEC 7, 2010 DISABLED
5 ON DATE DEC 7, 2010 DISABLED
6 ON DATE DEC 7, 2010 DISABLED
7 ON DATE DEC 7, 2010 DISABLED
8 ON DATE DEC 7, 2010 DISABLED
I60100
AUG 2, 2023 12:19 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 PREMIUM ON
3 DIESEL ON
4 OFF
I60200
AUG 2, 2023 12:19 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4
I60300
AUG 2, 2023 12:19 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL 3
4 4
I60900
AUG 2, 2023 12:19 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 PREMIUM 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
AUG 2, 2023 12:19 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 111.00
2 PREMIUM 111.00
3 DIESEL 111.00
4 0.00
I60A00
AUG 2, 2023 12:19 PM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
1 PT 12032 2 PREMIUM 1 PT 12032 3 DIESEL
1 PT 12032 4 1 PT 0
I60400
AUG 2, 2023 12:19 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032
2 PREMIUM 12032
3 DIESEL 12032
4 0
I60500
AUG 2, 2023 12:19 PM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032 0 0 0
2 PREMIUM 12032 0 0 0
3 DIESEL 12032 0 0 0
4 0 0 0 0
I60600
AUG 2, 2023 12:19 PM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 PREMIUM 12032 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DIESEL 12032 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
AUG 2, 2023 12:19 PM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 PREMIUM NO
3 DIESEL NO
4 NO
I62F00
AUG 2, 2023 12:19 PM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN.
2 PREMIUM 4.0 IN.
3 DIESEL 4.0 IN.
I62700
AUG 2, 2023 12:19 PM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 2.0
2 PREMIUM 2.0
3 DIESEL 2.0
I64200
AUG 2, 2023 12:19 PM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 PREMIUM LOW
3 DIESEL LOW
I62400
AUG 2, 2023 12:19 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 PREMIUM 3.0
3 DIESEL 3.0
I62800
AUG 2, 2023 12:19 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 12032
2 PREMIUM 12032
3 DIESEL 12032
4 0
I62300
AUG 2, 2023 12:19 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 10829
2 PREMIUM 10829
3 DIESEL 10829
4 0
I62200
AUG 2, 2023 12:19 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 11431
2 PREMIUM 11431
3 DIESEL 11431
4 0
I62900
AUG 2, 2023 12:19 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1805
2 PREMIUM 1805
3 DIESEL 1805
4 0
I62100
AUG 2, 2023 12:19 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 500
2 PREMIUM 500
3 DIESEL 500
4 0
I62600
AUG 2, 2023 12:19 PM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I62500
AUG 2, 2023 12:19 PM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I60800
AUG 2, 2023 12:19 PM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 5.40
2 PREMIUM 5.00
3 DIESEL 1.00
4 0.00
I60B00
AUG 2, 2023 12:20 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
AUG 2, 2023 12:20 PM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 0.00
3 DIESEL 0.00
4 0.00
I61200
AUG 2, 2023 12:20 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 PREMIUM NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
AUG 2, 2023 12:20 PM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 PREMIUM 120
3 DIESEL 120
4 0
I62A00
AUG 2, 2023 12:20 PM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 120
2 PREMIUM 120
3 DIESEL 120
4 0
I62C00
AUG 2, 2023 12:20 PM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 PREMIUM STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
AUG 2, 2023 12:20 PM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
AUG 2, 2023 12:20 PM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 PREMIUM OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
AUG 2, 2023 12:20 PM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I63200
AUG 2, 2023 12:20 PM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I61000
AUG 2, 2023 12:20 PM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63A00
AUG 2, 2023 12:20 PM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 PREMIUM 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
AUG 2, 2023 12:20 PM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JAN 15, 2008
START TIME : 2:00 AM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
AUG 2, 2023 12:20 PM
CSLD PROBABLITY OF DETECTION
I61400
AUG 2, 2023 12:20 PM
CSLD CLIMATE FACTOR
I61600
AUG 2, 2023 12:20 PM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 PREMIUM IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
AUG 2, 2023 12:20 PM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED DISABLED
2 PREMIUM DISABLED
3 DIESEL DISABLED
4 DISABLED
I61B00
AUG 2, 2023 12:20 PM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
AUG 2, 2023 12:20 PM
CSLD REPORT ONLY
I62B00
AUG 2, 2023 12:20 PM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 PREMIUM ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
AUG 2, 2023 12:20 PM
LEAK TEST REPORT FORMAT: NORMAL
I63400
AUG 2, 2023 12:20 PM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 PREMIUM 0
3 DIESEL 0
4 0
I63500
AUG 2, 2023 12:20 PM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63900
AUG 2, 2023 12:20 PM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 PREMIUM
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
AUG 2, 2023 12:20 PM
I77700
AUG 2, 2023 12:20 PM
I77800
AUG 2, 2023 12:20 PM
I78C00
AUG 2, 2023 12:20 PM
I78300
AUG 2, 2023 12:20 PM
I78F00
AUG 2, 2023 12:20 PM
I78700
AUG 2, 2023 12:20 PM
I70200
AUG 2, 2023 12:20 PM
LIQUID LABEL
DEVICE LABEL
1 UNL STP
2 UNL ANN
3 UNL FILL
4 PREM STP
5 PREM ANN
6 PREM FILL
7 DIESEL STP
8 DIESEL ANN
9 DIESEL FILL
10 DISP 1-2
11 DISP 3-4
12 DISP 5-6
13 DISP 7-8
14
15
16
I70300
AUG 2, 2023 12:20 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL STP TRI-STATE (SINGLE FLOAT)
2 UNL ANN TRI-STATE (SINGLE FLOAT)
3 UNL FILL TRI-STATE (SINGLE FLOAT)
4 PREM STP TRI-STATE (SINGLE FLOAT)
5 PREM ANN TRI-STATE (SINGLE FLOAT)
6 PREM FILL TRI-STATE (SINGLE FLOAT)
7 DIESEL STP TRI-STATE (SINGLE FLOAT)
8 DIESEL ANN TRI-STATE (SINGLE FLOAT)
9 DIESEL FILL TRI-STATE (SINGLE FLOAT)
10 DISP 1-2 TRI-STATE (SINGLE FLOAT)
11 DISP 3-4 TRI-STATE (SINGLE FLOAT)
12 DISP 5-6 TRI-STATE (SINGLE FLOAT)
13 DISP 7-8 TRI-STATE (SINGLE FLOAT)
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
AUG 2, 2023 12:20 PM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL STP STP SUMP
2 UNL ANN ANNULAR SPACE
3 UNL FILL OTHER SENSORS
4 PREM STP STP SUMP
5 PREM ANN ANNULAR SPACE
6 PREM FILL OTHER SENSORS
7 DIESEL STP STP SUMP
8 DIESEL ANN ANNULAR SPACE
9 DIESEL FILL OTHER SENSORS
10 DISP 1-2 DISPENSER PAN
11 DISP 3-4 DISPENSER PAN
12 DISP 5-6 DISPENSER PAN
13 DISP 7-8 DISPENSER PAN
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
AUG 2, 2023 12:20 PM
2 WIRE CL LABEL
DEVICE LABEL
1 PREM ANN
2
3
4
5
6
7
8
I74300
AUG 2, 2023 12:20 PM
2 WIRE CL TYPE
SENSOR LOCATION TYPE
1 PREM ANN ULTRA 2
2 ULTRA 2
3 ULTRA 2
4 ULTRA 2
5 ULTRA 2
6 ULTRA 2
7 ULTRA 2
8 ULTRA 2
I74400
AUG 2, 2023 12:20 PM
2 WIRE CL CATEGORY
SENSOR LOCATION CATEGORY
1 PREM ANN ANNULAR SPACE
2 OTHER SENSORS
3 OTHER SENSORS
4 OTHER SENSORS
5 OTHER SENSORS
6 OTHER SENSORS
7 OTHER SENSORS
8 OTHER SENSORS
I74700
AUG 2, 2023 12:20 PM
I74800
AUG 2, 2023 12:20 PM
I74900
AUG 2, 2023 12:20 PM
I7BC00
AUG 2, 2023 12:20 PM
I80200
AUG 2, 2023 12:20 PM
I80300
AUG 2, 2023 12:20 PM
I80400
AUG 2, 2023 12:20 PM
I80700
AUG 2, 2023 12:20 PM
RELAY LABEL
DEVICE LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4 OVERFILL ALARM
I80900
AUG 2, 2023 12:20 PM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNLEADED NORMALLY OPEN
2 PREMIUM NORMALLY OPEN
3 DIESEL NORMALLY CLOSED
4 OVERFILL ALARM NORMALLY OPEN
I80B00
AUG 2, 2023 12:20 PM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL 3
4 OVERFILL ALARM NONE
I80A00
AUG 2, 2023 12:20 PM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNLEADED PUMP CONTROL OUTPUT
2 PREMIUM PUMP CONTROL OUTPUT
3 DIESEL STANDARD
4 OVERFILL ALARM STANDARD
I80C00
AUG 2, 2023 12:20 PM
I80800
AUG 2, 2023 12:20 PM
RELAY SETUP REPORT
R 1:UNLEADED
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L 1:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 1:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD SETUP FAIL
ISD SENSOR OUT FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:PREMIUM
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
LIQUID SENSOR ALMS
L 4:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L 4:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 4:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD SETUP FAIL
ISD SENSOR OUT FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DIESEL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 3
LIQUID SENSOR ALMS
L 7:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L 7:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 7:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
I79000
AUG 2, 2023 12:21 PM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
AUG 2, 2023 12:21 PM
I72300
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 P.S.DISP 3-4 VAPOR PRESSURE
02 F.M. DISP 1-2 AIR FLOW METER
03 F.M. DISP 3-4 AIR FLOW METER
04 F.M. DISP 5-6 AIR FLOW METER
05 F.M. DISP 7-8 AIR FLOW METER
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
VAPOR PROCESSOR TYPE
NONE
IV4700
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
ACCEPT HIGH ORVR: YES
IV4A00
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
IV4B00
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
IV4900
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
AUG 2, 2023 12:21 PM
ISD VERSION: 01.07
Jaco Alarm History
Responses Received:
I10200
AUG 2, 2023 12:21 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 505479 504728
2 4 PROBE / G.T. 163020 162750
3 INTERSTITIAL BD 201109 200909
4 INTERSTITIAL BD 200615 200393
5 2 WIRE CL 68258 68106
6 UNUSED 9895331 9858119
7 UNUSED 9894485 9846279
8 UNUSED 9884372 9838283
9 STP SENSE BOARD 33099 33072
10 RELAY BOARD 14869 14883
11 UNUSED 9899057 9844615
12 UNUSED 9887313 9836102
13 UNUSED 9880998 9835751
14 UNUSED 9882607 9841826
15 UNUSED 9882938 9832692
16 UNUSED 9882153 9844202
COMM 1 RS232 SERIAL BD 14931 14924
COMM 2 ELEC DISP INT. 100900 100828
COMM 3 RS232 SERIAL BD 14994 14966
COMM 4 UNUSED 9892618 9851682
COMM 5 UNUSED 9888077 9847219
COMM 6 UNUSED 9889006 9842652
I90200
AUG 2, 2023 12:22 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
AUG 2, 2023 12:22 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 6 OTHER PREM FILL FUEL ALARM CLEAR 7-26-23 11:00AM
L 6 OTHER PREM FILL FUEL ALARM ALARM 7-26-23 10:57AM
L 6 OTHER PREM FILL SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L 4 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L 3 OTHER UNL FILL SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L 8 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L 7 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L12 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L11 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L10 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L 9 OTHER DIESEL FILL SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L13 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
C 1 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-26-23 9:51AM
L 6 OTHER PREM FILL SENSOR OUT ALARM ALARM 7-26-23 9:51AM
L12 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L11 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L 4 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L 3 OTHER UNL FILL SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L10 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-26-23 9:50AM
C 1 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L13 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L 8 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L 7 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L 9 OTHER DIESEL FILL SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-26-23 9:50AM
L 8 ANNULAR DIESEL ANN FUEL ALARM CLEAR 7-26-23 9:43AM
L 8 ANNULAR DIESEL ANN FUEL ALARM ALARM 7-26-23 9:43AM
C 1 ANNULAR PREM ANN FUEL ALARM CLEAR 7-26-23 9:42AM
C 1 ANNULAR PREM ANN FUEL ALARM ALARM 7-26-23 9:42AM
L 2 ANNULAR UNL ANN FUEL ALARM CLEAR 7-26-23 9:41AM
L 2 ANNULAR UNL ANN FUEL ALARM ALARM 7-26-23 9:41AM
L 3 OTHER UNL FILL FUEL ALARM CLEAR 7-26-23 9:41AM
L 3 OTHER UNL FILL FUEL ALARM ALARM 7-26-23 9:40AM
L 6 OTHER PREM FILL FUEL ALARM CLEAR 7-26-23 9:40AM
L 6 OTHER PREM FILL FUEL ALARM ALARM 7-26-23 9:40AM
L 9 OTHER DIESEL FILL FUEL ALARM CLEAR 7-26-23 9:39AM
L 9 OTHER DIESEL FILL FUEL ALARM ALARM 7-26-23 9:39AM
L 7 STP SUMP DIESEL STP FUEL ALARM CLEAR 7-26-23 9:39AM
L 7 STP SUMP DIESEL STP FUEL ALARM ALARM 7-26-23 9:39AM
L 4 STP SUMP PREM STP FUEL ALARM CLEAR 7-26-23 9:38AM
L 4 STP SUMP PREM STP FUEL ALARM ALARM 7-26-23 9:38AM
L 1 STP SUMP UNL STP FUEL ALARM CLEAR 7-26-23 9:38AM
L 1 STP SUMP UNL STP FUEL ALARM ALARM 7-26-23 9:38AM
L11 DISP PAN DISP 3-4 FUEL ALARM CLEAR 7-26-23 9:37AM
L11 DISP PAN DISP 3-4 FUEL ALARM ALARM 7-26-23 9:37AM
L13 DISP PAN DISP 7-8 FUEL ALARM CLEAR 7-26-23 9:36AM
L13 DISP PAN DISP 7-8 FUEL ALARM ALARM 7-26-23 9:36AM
I11200
AUG 2, 2023 12:22 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-29-23 6:43PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-29-23 4:27PM
SYSTEM PRINTER ERROR CLEAR 7-27-23 11:51AM
SYSTEM PAPER OUT CLEAR 7-27-23 11:51AM
SYSTEM PRINTER ERROR ALARM 7-27-23 11:51AM
SYSTEM PAPER OUT ALARM 7-27-23 11:51AM
SYSTEM PRINTER ERROR CLEAR 7-27-23 11:50AM
SYSTEM PAPER OUT CLEAR 7-27-23 11:50AM
SYSTEM PRINTER ERROR ALARM 7-27-23 11:50AM
SYSTEM PAPER OUT ALARM 7-27-23 11:50AM
SYSTEM PRINTER ERROR CLEAR 7-27-23 11:43AM
SYSTEM PAPER OUT CLEAR 7-27-23 11:43AM
SYSTEM PRINTER ERROR ALARM 7-27-23 11:43AM
SYSTEM PAPER OUT ALARM 7-27-23 11:43AM
SYSTEM PRINTER ERROR CLEAR 7-27-23 11:42AM
SYSTEM PAPER OUT CLEAR 7-27-23 11:42AM
SYSTEM PRINTER ERROR ALARM 7-27-23 11:41AM
SYSTEM PAPER OUT ALARM 7-27-23 11:41AM
SYSTEM PRINTER ERROR CLEAR 7-27-23 11:36AM
SYSTEM PAPER OUT CLEAR 7-27-23 11:36AM
SYSTEM PRINTER ERROR ALARM 7-27-23 11:36AM
SYSTEM PAPER OUT ALARM 7-27-23 11:36AM
SYSTEM PRINTER ERROR CLEAR 7-27-23 11:36AM
SYSTEM PAPER OUT CLEAR 7-27-23 11:36AM
SYSTEM PRINTER ERROR ALARM 7-27-23 11:35AM
SYSTEM PAPER OUT ALARM 7-27-23 11:35AM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-17-23 2:00PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-17-23 1:03PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-14-23 4:09PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-14-23 3:48PM
T 1 TANK UNLEADED DELIVERY NEEDED CLEAR 7-12-23 1:22PM
T 1 TANK UNLEADED DELIVERY NEEDED ALARM 7-12-23 1:08PM
SYSTEM PRINTER ERROR CLEAR 7-11-23 6:52AM
SYSTEM PAPER OUT CLEAR 7-11-23 6:52AM
SYSTEM PRINTER ERROR ALARM 7-11-23 6:52AM
SYSTEM PAPER OUT ALARM 7-11-23 6:52AM
SYSTEM PRINTER ERROR CLEAR 7-11-23 6:51AM
SYSTEM PAPER OUT CLEAR 7-11-23 6:51AM
SYSTEM PRINTER ERROR ALARM 7-11-23 2:51AM
SYSTEM PAPER OUT ALARM 7-11-23 2:51AM
SYSTEM PRINTER ERROR CLEAR 7-11-23 2:51AM
SYSTEM PAPER OUT CLEAR 7-11-23 2:51AM
SYSTEM PRINTER ERROR ALARM 7-11-23 2:50AM
SYSTEM PAPER OUT ALARM 7-11-23 2:50AM
SYSTEM PRINTER ERROR CLEAR 7-11-23 2:50AM
SYSTEM PAPER OUT CLEAR 7-11-23 2:50AM
SYSTEM PRINTER ERROR ALARM 7-11-23 1:43AM
SYSTEM PAPER OUT ALARM 7-11-23 1:43AM
SYSTEM PRINTER ERROR CLEAR 7-11-23 1:43AM
SYSTEM PAPER OUT CLEAR 7-11-23 1:43AM
I20600
AUG 2, 2023 12:22 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JUN 9, 2023 12:36 AM
MAR 31, 2023 1:43 AM
MAR 25, 2023 11:29 AM
INVALID FUEL LEVEL APR 26, 2023 6:39 PM
MAR 9, 2023 5:18 PM
JAN 12, 2023 1:52 PM
DELIVERY NEEDED JUL 29, 2023 4:27 PM
JUL 17, 2023 1:03 PM
JUL 14, 2023 3:48 PM
TANK 2 PREMIUM
OVERFILL ALARM FEB 22, 2023 5:14 AM
DEC 27, 2022 8:16 PM
JUN 26, 2022 1:25 PM
SUDDEN LOSS ALARM MAY 1, 2023 3:19 PM
TANK 3 DIESEL
DELIVERY NEEDED JUL 26, 2022 3:21 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
AUG 2, 2023 12:22 PM
I30200
AUG 2, 2023 12:22 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL STP
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:38 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
2 UNL ANN
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:41 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
3 UNL FILL
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:40 AM FUEL ALARM
JUL 3, 2023 2:00 PM FUEL ALARM
4 PREM STP
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:38 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
6 PREM FILL
JUL 26, 2023 10:57 AM FUEL ALARM
JUL 26, 2023 9:51 AM SENSOR OUT ALARM
JUL 26, 2023 9:40 AM FUEL ALARM
7 DIESEL STP
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:39 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
8 DIESEL ANN
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:43 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
9 DIESEL FILL
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:39 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
10 DISP 1-2
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:35 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
11 DISP 3-4
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:37 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
12 DISP 5-6
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:36 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
13 DISP 7-8
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:36 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
I31600
AUG 2, 2023 12:22 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 P.S.DISP 3-4
2 F.M. DISP 1-2
3 F.M. DISP 3-4
4 F.M. DISP 5-6
5 F.M. DISP 7-8
I40200
AUG 2, 2023 12:22 PM
I40300
AUG 2, 2023 12:22 PM
I34200
AUG 2, 2023 12:22 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
2 WIRE CL ALARM HISTORY REPORT
SENSOR LOCATION
1 PREM ANN
JUL 26, 2023 9:50 AM SENSOR OUT ALARM
JUL 26, 2023 9:42 AM FUEL ALARM
JUL 3, 2023 2:00 PM SENSOR OUT ALARM
I34700
AUG 2, 2023 12:22 PM
IV0100
AUG 2, 2023 12:22 PM
FASTRIP 705
1200 COFFEE RD.
BAKERSFIELD CB 93308
661-589-6305
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-06-26 10:02:38 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
23-06-16 10:02:34 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
23-05-25 10:01:36 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-05-24 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-05-23 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-05-22 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-05-21 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-05-20 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-05-19 10:01:09 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-05-12 10:01:09 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-05-26 10:02:21 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-05-01 10:02:06 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
23-04-30 10:02:10 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
23-04-29 10:01:57 VAPOR CONTAINMENT LEAKAGE GROSS FAIL
23-04-08 10:02:18 A/L RATIO DEGRADATION FP 8 BLEND3 0.78
23-03-08 10:02:05 A/L RATIO DEGRADATION FP 4 BLEND3 0.80
23-03-07 10:01:49 A/L RATIO DEGRADATION FP 4 BLEND3 0.79
22-10-23 10:02:24 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-10-23 10:02:24 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
20-11-02 10:03:20 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-07-26 10:03:07 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-26 09:50:01 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-26 09:50:01 ISD STARTUP
23-07-26 09:49:32 ISD SHUTDOWN
23-07-16 10:02:54 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-16 09:50:04 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-16 09:50:04 ISD STARTUP
23-07-16 09:49:53 ISD SHUTDOWN
23-07-06 10:03:46 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-05 10:03:44 READINESS ISD:PP EVR:NP EVR READINESS PENDING