Loading...
HomeMy WebLinkAboutFMC 2023Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10159083 7/24/23 Jaco #7725 Fastrip #19 (South) 4901 South Union Avenue Bakersfield 93307 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Payton Phillips 1073967 9482312 0/15/20024 Veeder Root C27796 08/01/2024 7/24/23 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder Root TLS-350 336.02 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 UNL STP L2 420 UNL Ann L3 208 PREM STP L4 420 PREM Ann L5 208 DSL STP L6 420 DSL Ann L7 208 Disp 9-10 L8 208 Disp 11-12 L9 208 Disp 13-14 L10 208 Disp 15-16 Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V UNLEADED T2 FX1V PREM T3 FX1DV Diesel Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Fill sumps have water. Upon arrival the tank pad was covered in water causing the DSL annular to get wet. I removed water from Annular riser. Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. N/A 12,000 GALLON12,000 GALLONEXISTING BUILDING NOPAR KI NG G W PRICE SIGNPRICE SIGN12,000 GALLON87-1 UNLEADEDFV STPL5H HDUMPSTER FFVSTPL3STPL1AL6AL4AL212,000 GALLONDIESEL87 UNLEADEDPREMIUM1112L81516L10910L71314L9#7-725FSTPL1V AL8 AL6 AL4 AL2 FSTPL3V FSTPL5V FSTPL7 12,000 GALLON87-2 UNLEADED 12,000 GALLONPREMIUM 12,000 GALLONDIESEL 21L9 43L10 L14 65L11 87L12 L13 40' STORAGE CONTAINER 40' STORAGE CONTAINER S. UNION AVE.PACHECO RD.N #7-775 7-775 7-725 SLOPE PROPERTY LINE PROPERTY LINE ADJACENT JACO PORPERTY TO THE SOUTH NOT SHOWN, FOR CLARITY PROPANE TANK CAGE 167.17' 148.17' 315.86'108.70'63.50'172.22' EMERGENCY SHUT-OFF OVERFILL ALARM FIRE EXTINGUISHER GAS METER SHUT-OFF WATER METER SHUT-SHUT OFF HEALY CAS EVACUATION MEETING POINT CIRCUIT BREAKER UST ELECTRICAL PANEL AUTOMATIC TANK GAUGE AIR AND WATER DISPENSER HAZWASTE DRUM W G H 725 LEGEND L1 87 STP L2 87 ANNULAR L3 91 STP L4 91 ANNULAR L5 DSL STP L6 DSL ANNULAR L7 UDC 9 -10 L8 UDC 11 - 12 L9 UDC 13 - 14 L10 UDC 15 - 16 775 LEGEND L1 87-1 STP L2 87-1 ANNULAR L3 87-2 STP L4 87-2 ANNULAR L5 91 STP L6 91 ANNULAR L7 DSL STP L8 DSL ANNULAR L9 UDC 1 -2 L10 UDC 3 - 4 L11 UDC 5 -6 L12 UDC 7 - 8 L13 N TRANS SUMP L14 S TRANS SUMP 87 GAS 3/2 INCH DBL WALLED PIPE 91 GAS 3/2 INCH DBL WALLED PIPE DIESEL 3/2 INCH DBL WALLED PIPE VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE VAPOR VENT 3/2 INCH DOUBLE WALLED PIPE PRODUCT SPILL CONTAINER VAPOR SPILL CONTAINER ANNULARA P V SITE MAP SCALE: C1 VICINITY MAP PROJECT DATA 1"=15'-0" INCHES012 SHEET SIZE 22 X 34 4901 S. UNION AVE. BAKERSFIELD, CA 93307 PROJECT OWNER: JAMIESON HILL PO. BOX 82515 BAKERSFIELD, CA 93380 CONTACT: SITE PLOT PLAN FOR: FASTRIPS #7725 / #7775 #7725 CERS ID 10159083 FACILITY ID 15-021-100269 #7775 CERS ID 10159109 FACILITY ID 15-021-003076 4901 S. UNION AVE. BAKERSFIELD, CA 93307 03/06/17 REV.S. UNION AVE.E. PACHECO RD. APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Jaco #7725 Fastrip #19 (South)4901 South Union AvenueBakersfield1015908311-1215-16 Tested ESO also and it passed.MPDMPDMPDMPD9-1013-14ProductProductProductProductPayton Phillips Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10159083 7/24/23 Jaco #7725 Fastrip #19 (South) 4901 South Union Avenue Bakersfield 93307 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Payton Phillips 1073967 9482312 0/15/20024 OPW 0187328 08/14/24 PEI 1200 Hydrostatic Lake Test (OPW Spill buckets) 7/24/23 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1 UNL OPW T2 PREM OPW T3 DIESEL OPW 07-24-23 Monitor Cert Printouts FASTRIP 7725 4901 S UNION BAKERSFIELD CA SYSTEM SETUP 200 FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 JUL 24, 2023 9:00 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNL 4074 35.76 0.0 81.8 7926 2 PREM 4318 37.34 0.8 82.2 7682 3 DSL 538 8.67 1.1 86.9 11462 I90500 JUL 24, 2023 9:00 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JUL 24, 2023 9:00 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JUL 24, 2023 9:00 AM SHIFT TIME 1 : 12:00 AM I50202 JUL 24, 2023 9:00 AM SHIFT TIME 2 : DISABLED I50203 JUL 24, 2023 9:00 AM SHIFT TIME 3 : DISABLED I50204 JUL 24, 2023 9:00 AM SHIFT TIME 4 : DISABLED I54600 JUL 24, 2023 9:00 AM TANK PER TST NEEDED WRN: DISABLED I54900 JUL 24, 2023 9:00 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JUL 24, 2023 9:00 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JUL 24, 2023 9:00 AM LINE PER TST NEEDED WRN: DISABLED I55900 JUL 24, 2023 9:00 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JUL 24, 2023 9:00 AM PRINT TC VOLUMES ENABLED I50E00 JUL 24, 2023 9:00 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JUL 24, 2023 9:00 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JUL 24, 2023 9:00 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JUL 24, 2023 9:00 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 JUL 24, 2023 9:00 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 JUL 24, 2023 9:00 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JUL 24, 2023 9:00 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JUL 24, 2023 9:00 AM TANK CHART SECURITY DISABLED I5BD00 JUL 24, 2023 9:00 AM CUSTOM ALARM LABELS DISABLED I56000 JUL 24, 2023 9:00 AM MASS/DENSITY DISABLED I88101 JUL 24, 2023 9:00 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JUL 24, 2023 9:00 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88103 JUL 24, 2023 9:00 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 JUL 24, 2023 9:00 AM I88105 JUL 24, 2023 9:00 AM I88106 JUL 24, 2023 9:00 AM I52000 JUL 24, 2023 9:00 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE ??? 24, 2023 DISABLED 2 ON DATE ??? 24, 2023 DISABLED 3 ON DATE ??? 24, 2023 DISABLED 4 ON DATE ??? 24, 2023 DISABLED 5 ON DATE ??? 24, 2023 DISABLED 6 ON DATE ??? 24, 2023 DISABLED 7 ON DATE ??? 24, 2023 DISABLED 8 ON DATE ??? 24, 2023 DISABLED I60100 JUL 24, 2023 9:00 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNL ON 2 PREM ON 3 DSL ON 4 OFF I60200 JUL 24, 2023 9:00 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNL 2 PREM 3 DSL 4 I60300 JUL 24, 2023 9:00 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNL 1 2 PREM 2 3 DSL 3 4 4 I60900 JUL 24, 2023 9:00 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNL 0.000700 2 PREM 0.000700 3 DSL 0.000450 4 0.000000 I60700 JUL 24, 2023 9:00 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNL 96.00 2 PREM 96.00 3 DSL 96.00 4 0.00 I60A00 JUL 24, 2023 9:00 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL 1 PT 12000 2 PREM 1 PT 12000 3 DSL 1 PT 12000 4 1 PT 0 I60400 JUL 24, 2023 9:00 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 12000 2 PREM 12000 3 DSL 12000 4 0 I60500 JUL 24, 2023 9:01 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12000 0 0 0 2 PREM 12000 0 0 0 3 DSL 12000 0 0 0 4 0 0 0 0 I60600 JUL 24, 2023 9:01 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PREM 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DSL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JUL 24, 2023 9:01 AM TANK PRODUCT LABEL METER DATA 1 UNL NO 2 PREM NO 3 DSL NO 4 NO I62F00 JUL 24, 2023 9:01 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNL 4.0 IN. 2 PREM 4.0 IN. 3 DSL 3.0 IN. I62700 JUL 24, 2023 9:01 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNL 2.0 2 PREM 2.0 3 DSL 2.0 I64200 JUL 24, 2023 9:01 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNL LOW 2 PREM LOW 3 DSL LOW I62400 JUL 24, 2023 9:01 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNL 3.0 2 PREM 3.0 3 DSL 3.0 I62800 JUL 24, 2023 9:01 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 12000 2 PREM 12000 3 DSL 12000 4 0 I62300 JUL 24, 2023 9:01 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 10800 2 PREM 10800 3 DSL 10800 4 0 I62200 JUL 24, 2023 9:01 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 11400 2 PREM 11400 3 DSL 11400 4 0 I62900 JUL 24, 2023 9:01 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1200 2 PREM 1200 3 DSL 1200 4 0 I62100 JUL 24, 2023 9:01 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1200 2 PREM 1200 3 DSL 1200 4 0 I62600 JUL 24, 2023 9:01 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 PREM 99 3 DSL 99 4 99 I62500 JUL 24, 2023 9:01 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 PREM 99 3 DSL 99 4 99 I60800 JUL 24, 2023 9:01 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNL 0.00 2 PREM 0.00 3 DSL 0.00 4 0.00 I60B00 JUL 24, 2023 9:01 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JUL 24, 2023 9:01 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNL 0.00 2 PREM 0.00 3 DSL 0.00 4 0.00 I61200 JUL 24, 2023 9:01 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNL NONE NONE 2 PREM NONE NONE 3 DSL NONE NONE 4 NONE NONE I63600 JUL 24, 2023 9:01 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 120 2 PREM 120 3 DSL 120 4 0 I62A00 JUL 24, 2023 9:01 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 120 2 PREM 120 3 DSL 120 4 0 I62C00 JUL 24, 2023 9:01 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNL STANDARD 2 PREM STANDARD 3 DSL STANDARD 4 STANDARD I62D00 JUL 24, 2023 9:01 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PREM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DSL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JUL 24, 2023 9:01 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNL OFF OFF 2 PREM OFF OFF 3 DSL OFF OFF 4 OFF OFF I63000 JUL 24, 2023 9:01 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNL OFF 2 PREM OFF 3 DSL OFF 4 OFF I63200 JUL 24, 2023 9:01 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNL OFF 2 PREM OFF 3 DSL OFF 4 OFF I61000 JUL 24, 2023 9:01 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNL 1 2 PREM 1 3 DSL 1 4 1 I63A00 JUL 24, 2023 9:01 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNL 10.00% 2 PREM 10.00% 3 DSL 10.00% 4 10.00% I61100 JUL 24, 2023 9:01 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK OCT 1, 2014 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JUL 24, 2023 9:01 AM CSLD PROBABLITY OF DETECTION I61400 JUL 24, 2023 9:01 AM CSLD CLIMATE FACTOR I61600 JUL 24, 2023 9:01 AM TANK PRODUCT LABEL CAL UPDATE 1 UNL IMMEDIATE 2 PREM IMMEDIATE 3 DSL IMMEDIATE 4 IMMEDIATE I61A00 JUL 24, 2023 9:01 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNL DISABLED 2 PREM DISABLED 3 DSL DISABLED 4 DISABLED I61B00 JUL 24, 2023 9:01 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JUL 24, 2023 9:01 AM CSLD REPORT ONLY I62B00 JUL 24, 2023 9:01 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNL ??? 0, 0 2 PREM ??? 0, 0 3 DSL ??? 0, 0 4 ??? 0, 0 I63300 JUL 24, 2023 9:01 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JUL 24, 2023 9:01 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 0 2 PREM 0 3 DSL 0 4 0 I63500 JUL 24, 2023 9:01 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 2 PREM 1 3 DSL 1 4 1 I63900 JUL 24, 2023 9:01 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNL END FACTOR: NONE 2 PREM END FACTOR: NONE 3 DSL END FACTOR: NONE 4 END FACTOR: NONE I78000 JUL 24, 2023 9:01 AM I77700 JUL 24, 2023 9:01 AM I77800 JUL 24, 2023 9:01 AM I78C00 JUL 24, 2023 9:01 AM I78300 JUL 24, 2023 9:01 AM I78F00 JUL 24, 2023 9:01 AM I78700 JUL 24, 2023 9:01 AM I70200 JUL 24, 2023 9:01 AM LIQUID LABEL DEVICE LABEL 1 UNL STP 2 UNL ANN 3 PREM STP 4 PREM ANN 5 DSL STP 6 DSL ANN 7 DISP 9-10 8 DISP 11-12 9 DISP 13-14 10 DISP 15-16 11 12 13 14 15 16 I70300 JUL 24, 2023 9:01 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL STP TRI-STATE (SINGLE FLOAT) 2 UNL ANN TRI-STATE (SINGLE FLOAT) 3 PREM STP TRI-STATE (SINGLE FLOAT) 4 PREM ANN TRI-STATE (SINGLE FLOAT) 5 DSL STP TRI-STATE (SINGLE FLOAT) 6 DSL ANN TRI-STATE (SINGLE FLOAT) 7 DISP 9-10 TRI-STATE (SINGLE FLOAT) 8 DISP 11-12 TRI-STATE (SINGLE FLOAT) 9 DISP 13-14 TRI-STATE (SINGLE FLOAT) 10 DISP 15-16 TRI-STATE (SINGLE FLOAT) 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JUL 24, 2023 9:01 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL STP STP SUMP 2 UNL ANN ANNULAR SPACE 3 PREM STP STP SUMP 4 PREM ANN ANNULAR SPACE 5 DSL STP STP SUMP 6 DSL ANN ANNULAR SPACE 7 DISP 9-10 DISPENSER PAN 8 DISP 11-12 DISPENSER PAN 9 DISP 13-14 DISPENSER PAN 10 DISP 15-16 DISPENSER PAN 11 OTHER SENSORS 12 OTHER SENSORS 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 JUL 24, 2023 9:01 AM I74300 JUL 24, 2023 9:01 AM I74400 JUL 24, 2023 9:01 AM I74700 JUL 24, 2023 9:01 AM I74800 JUL 24, 2023 9:01 AM I74900 JUL 24, 2023 9:01 AM I7BC00 JUL 24, 2023 9:01 AM I80200 JUL 24, 2023 9:01 AM I80300 JUL 24, 2023 9:01 AM I80400 JUL 24, 2023 9:01 AM I80700 JUL 24, 2023 9:01 AM RELAY LABEL DEVICE LABEL 1 UNL 2 PNL 3 DSL 4 OVERFILL I80900 JUL 24, 2023 9:01 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL NORMALLY CLOSED 2 PNL NORMALLY CLOSED 3 DSL NORMALLY CLOSED 4 OVERFILL NORMALLY OPEN I80B00 JUL 24, 2023 9:01 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNL 1 2 PNL 2 3 DSL 3 4 OVERFILL NONE I80A00 JUL 24, 2023 9:01 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNL STANDARD 2 PNL STANDARD 3 DSL STANDARD 4 OVERFILL STANDARD I80C00 JUL 24, 2023 9:01 AM I80800 JUL 24, 2023 9:01 AM RELAY SETUP REPORT R 1:UNL TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L 1:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 1:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL PC-ISD FAILURE ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PNL TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 3:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L 3:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 3:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD SETUP FAIL ISD SENSOR OUT FAIL PC-ISD FAILURE ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DSL TYPE: STANDARD NORMALLY CLOSED TANK #: 3 LIQUID SENSOR ALMS L 5:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L 5:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 5:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM R 4:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 JUL 24, 2023 9:02 AM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 JUL 24, 2023 9:02 AM I72300 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VP 11-12 VAPOR PRESSURE 02 FM 9-10 AIR FLOW METER 03 FM 11-12 AIR FLOW METER 04 FM 13-14 AIR FLOW METER 05 FM 15-16 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 VAPOR PROCESSOR TYPE NONE IV4700 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ACCEPT HIGH ORVR: YES IV4A00 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 09 01 01 02 BLEND3 02 10 02 01 02 BLEND3 03 11 03 02 02 BLEND3 04 12 04 02 02 BLEND3 05 17 05 03 02 BLEND3 06 18 06 03 02 BLEND3 07 19 07 04 02 BLEND3 08 20 08 04 02 BLEND3 IV4B00 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 09 01 02/01 03/01 09/01 xx/xx 10 01 02/02 03/02 09/02 xx/xx 11 02 02/03 03/03 09/03 xx/xx 12 02 02/04 03/04 09/04 xx/xx 17 03 02/05 03/05 09/05 xx/xx 18 03 02/06 03/06 09/06 xx/xx 19 04 02/07 03/07 09/07 xx/xx 20 04 02/08 03/08 09/08 xx/xx IV4900 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JUL 24, 2023 9:02 AM ISD VERSION: 01.07 ALARM HISTORY (BEFORE) I10200 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39474 39596 2 4 PROBE / G.T. 164070 164552 3 INTERSTITIAL BD 202298 202859 4 INTERSTITIAL BD 202477 202592 5 UNUSED 9673851 9595982 6 UNUSED 9671231 9570491 7 UNUSED 9663563 9579927 8 UNUSED 9664079 9570170 9 RELAY BOARD 15007 15043 10 UNUSED 9667206 9575142 11 UNUSED 9665638 9563699 12 UNUSED 9659087 9571192 13 UNUSED 9661450 9562738 14 UNUSED 9664199 9565300 15 UNUSED 9659817 9559792 16 UNUSED 9662373 9555479 COMM 1 ELEC DISP INT. 101300 101373 COMM 2 RS232 SERIAL BD 14985 15021 COMM 3 RS232 SERIAL BD 15007 15021 COMM 4 UNUSED 9671673 9572559 COMM 5 UNUSED 9661514 9563955 COMM 6 UNUSED 9661299 9566581 I90200 JUL 24, 2023 9:02 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUL 24, 2023 9:02 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 8 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-24-23 8:53AM L 8 DISP PAN DISP 11-12 FUEL ALARM ALARM 7-24-23 8:53AM L 6 ANNULAR DSL ANN FUEL ALARM ALARM 7-22-23 11:44PM T 1 TANK UNL OVERFILL ALARM CLEAR 7-21-23 6:40AM T 1 TANK UNL OVERFILL ALARM ALARM 7-21-23 6:35AM T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-16-23 9:35AM T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-16-23 6:12AM T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-14-23 5:00PM T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-14-23 4:28PM T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-07-23 7:45PM T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-07-23 5:02PM L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L 4 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L 3 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L 5 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L10 DISP PAN DISP 15-16 SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM CLEAR 7-06-23 2:26PM L10 DISP PAN DISP 15-16 SENSOR OUT ALARM ALARM 7-06-23 2:20PM L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM ALARM 7-06-23 2:20PM L 4 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-06-23 2:18PM L 3 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-06-23 2:18PM L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-06-23 2:18PM L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-06-23 2:18PM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-06-23 2:18PM L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-06-23 2:18PM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-06-23 2:18PM L 5 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-06-23 2:18PM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-06-23 1:45PM L 3 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-06-23 1:45PM L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-06-23 1:45PM L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-06-23 1:45PM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-06-23 1:45PM L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-06-23 1:45PM L 4 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-06-23 1:45PM L 5 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-06-23 1:45PM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-06-23 1:42PM L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-06-23 1:42PM L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-06-23 1:42PM L 4 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-06-23 1:42PM L 3 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-06-23 1:42PM L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-06-23 1:42PM L 5 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-06-23 1:42PM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-06-23 1:42PM L 8 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-06-23 1:26PM L 4 ANNULAR PREM ANN FUEL ALARM CLEAR 7-06-23 1:26PM L10 DISP PAN DISP 15-16 FUEL ALARM CLEAR 7-06-23 1:26PM I11200 JUL 24, 2023 9:03 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK UNL DELIVERY NEEDED CLEAR 7-16-23 9:35AM T 1 TANK UNL INVALID FUEL LEVEL CLEAR 7-16-23 9:33AM T 1 TANK UNL INVALID FUEL LEVEL ALARM 7-16-23 9:19AM T 1 TANK UNL DELIVERY NEEDED ALARM 7-16-23 6:12AM T 1 TANK UNL DELIVERY NEEDED CLEAR 7-14-23 5:00PM T 1 TANK UNL DELIVERY NEEDED ALARM 7-14-23 4:28PM T 1 TANK UNL DELIVERY NEEDED CLEAR 7-07-23 7:45PM T 1 TANK UNL INVALID FUEL LEVEL CLEAR 7-07-23 7:43PM T 1 TANK UNL INVALID FUEL LEVEL ALARM 7-07-23 6:33PM T 1 TANK UNL DELIVERY NEEDED ALARM 7-07-23 5:02PM L12 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L11 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L14 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L13 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L15 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM L14 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L13 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L12 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L11 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L15 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L14 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L13 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L12 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L11 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L16 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L15 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L14 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L13 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L12 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L11 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM SYSTEM PRINTER ERROR CLEAR 6-24-23 8:49AM SYSTEM PAPER OUT CLEAR 6-24-23 8:49AM SYSTEM PRINTER ERROR ALARM 6-24-23 8:44AM SYSTEM PAPER OUT ALARM 6-24-23 8:44AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 6-17-23 10:00AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 6-12-23 10:02AM T 1 TANK UNL DELIVERY NEEDED CLEAR 6-11-23 9:36PM T 1 TANK UNL DELIVERY NEEDED ALARM 6-11-23 9:30PM T 1 TANK UNL DELIVERY NEEDED CLEAR 6-03-23 10:14AM T 1 TANK UNL INVALID FUEL LEVEL CLEAR 6-03-23 10:13AM I20600 JUL 24, 2023 9:03 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 TANK ALARM HISTORY TANK 1 UNL OVERFILL ALARM JUL 21, 2023 6:35 AM JUN 4, 2023 6:16 AM MAY 31, 2023 10:50 AM LOW PRODUCT ALARM JUL 16, 2023 6:12 AM JUL 14, 2023 4:28 PM JUL 7, 2023 5:02 PM INVALID FUEL LEVEL JUL 16, 2023 9:19 AM JUL 7, 2023 6:33 PM JUN 3, 2023 7:13 AM DELIVERY NEEDED JUL 16, 2023 6:12 AM JUL 14, 2023 4:28 PM JUL 7, 2023 5:02 PM TANK 2 PREM TANK 3 DSL LOW PRODUCT ALARM FEB 13, 2021 8:05 AM DELIVERY NEEDED FEB 13, 2021 8:05 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUL 24, 2023 9:03 AM I30200 JUL 24, 2023 9:03 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP JUL 6, 2023 2:18 PM SENSOR OUT ALARM JUL 6, 2023 1:42 PM SENSOR OUT ALARM JUL 6, 2023 1:25 PM FUEL ALARM 2 UNL ANN JUL 6, 2023 2:18 PM SENSOR OUT ALARM JUL 6, 2023 1:42 PM SENSOR OUT ALARM JUL 6, 2023 1:25 PM FUEL ALARM 3 PREM STP JUL 6, 2023 2:18 PM SENSOR OUT ALARM JUL 6, 2023 1:42 PM SENSOR OUT ALARM JUL 6, 2023 1:25 PM FUEL ALARM 4 PREM ANN JUL 6, 2023 2:18 PM SENSOR OUT ALARM JUL 6, 2023 1:42 PM SENSOR OUT ALARM JUL 6, 2023 1:25 PM FUEL ALARM 5 DSL STP JUL 6, 2023 2:18 PM SENSOR OUT ALARM JUL 6, 2023 1:42 PM SENSOR OUT ALARM JUL 6, 2023 1:25 PM FUEL ALARM 6 DSL ANN JUL 22, 2023 11:44 PM FUEL ALARM JUL 6, 2023 2:18 PM SENSOR OUT ALARM JUL 6, 2023 1:42 PM SENSOR OUT ALARM 7 DISP 9-10 JUL 6, 2023 2:18 PM SENSOR OUT ALARM JUL 6, 2023 1:42 PM SENSOR OUT ALARM JUL 6, 2023 1:25 PM FUEL ALARM 8 DISP 11-12 JUL 24, 2023 8:53 AM FUEL ALARM JUL 6, 2023 2:18 PM SENSOR OUT ALARM JUL 6, 2023 1:42 PM SENSOR OUT ALARM 9 DISP 13-14 JUL 6, 2023 2:20 PM SENSOR OUT ALARM JUL 6, 2023 1:25 PM FUEL ALARM JUL 6, 2023 1:25 PM FUEL ALARM 10 DISP 15-16 JUL 6, 2023 2:20 PM SENSOR OUT ALARM JUL 6, 2023 1:25 PM FUEL ALARM JUL 6, 2023 1:24 PM SENSOR OUT ALARM I31600 JUL 24, 2023 9:03 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP 11-12 2 FM 9-10 3 FM 11-12 4 FM 13-14 5 FM 15-16 I40200 JUL 24, 2023 9:03 AM I40300 JUL 24, 2023 9:03 AM I34200 JUL 24, 2023 9:03 AM I34700 JUL 24, 2023 9:03 AM IV0100 JUL 24, 2023 9:03 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-06-16 10:02:04 A/L RATIO DEGRADATION FP 3 BLEND3 0.79 23-06-15 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.78 23-06-14 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.77 23-06-13 10:02:26 A/L RATIO DEGRADATION FP 3 BLEND3 0.78 23-06-12 10:02:18 A/L RATIO DEGRADATION FP 3 BLEND3 0.79 22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 22-11-12 10:02:37 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-11-13 10:01:40 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-11-13 10:01:40 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 22-11-10 10:01:37 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-11-10 10:01:36 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-07-14 10:01:51 READINESS ISD:PP EVR:PP ISD & EVR READY 23-07-13 17:43:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-07-13 17:43:30 ISD STARTUP 23-07-13 17:23:56 ISD SHUTDOWN 23-07-07 10:02:03 READINESS ISD:PP EVR:PP ISD & EVR READY 23-07-06 14:31:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-07-06 14:31:18 ISD STARTUP 23-07-06 14:31:14 ISD SHUTDOWN 23-04-30 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY 23-04-30 02:46:50 READINESS ISD:PP EVR:NN EVR READINESS PENDING ALARM HISTORY (AFTER) I10200 JUL 24, 2023 11:10 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39474 39399 2 4 PROBE / G.T. 164070 164012 3 INTERSTITIAL BD 202298 202106 4 INTERSTITIAL BD 202477 202241 5 UNUSED 9673851 9387821 6 UNUSED 9671231 9388210 7 UNUSED 9663563 9393293 8 UNUSED 9664079 9383841 9 RELAY BOARD 15007 14985 10 UNUSED 9667206 9394467 11 UNUSED 9665638 9381575 12 UNUSED 9659087 9386831 13 UNUSED 9661450 9384170 14 UNUSED 9664199 9391568 15 UNUSED 9659817 9388237 16 UNUSED 9662373 9389210 COMM 1 ELEC DISP INT. 101300 101203 COMM 2 RS232 SERIAL BD 14985 15007 COMM 3 RS232 SERIAL BD 15007 15007 COMM 4 UNUSED 9671673 9389557 COMM 5 UNUSED 9661514 9393320 COMM 6 UNUSED 9661299 9385685 I90200 JUL 24, 2023 11:10 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JUL 24, 2023 11:10 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 4 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L 3 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L 5 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L10 DISP PAN DISP 15-16 SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM CLEAR 7-24-23 9:54AM L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-24-23 9:52AM L 4 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-24-23 9:52AM L 3 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-24-23 9:52AM L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-24-23 9:52AM L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-24-23 9:52AM L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-24-23 9:52AM L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-24-23 9:52AM L 5 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-24-23 9:52AM L 6 ANNULAR DSL ANN FUEL ALARM CLEAR 7-24-23 9:52AM L10 DISP PAN DISP 15-16 SENSOR OUT ALARM ALARM 7-24-23 9:51AM L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM ALARM 7-24-23 9:51AM L 6 ANNULAR DSL ANN FUEL ALARM ALARM 7-24-23 9:49AM L 8 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-24-23 9:40AM L 8 DISP PAN DISP 11-12 FUEL ALARM ALARM 7-24-23 9:40AM L 7 DISP PAN DISP 9-10 FUEL ALARM CLEAR 7-24-23 9:39AM L 7 DISP PAN DISP 9-10 FUEL ALARM ALARM 7-24-23 9:39AM L 9 DISP PAN DISP 13-14 FUEL ALARM CLEAR 7-24-23 9:38AM L 9 DISP PAN DISP 13-14 FUEL ALARM ALARM 7-24-23 9:38AM L10 DISP PAN DISP 15-16 FUEL ALARM CLEAR 7-24-23 9:37AM L10 DISP PAN DISP 15-16 FUEL ALARM ALARM 7-24-23 9:37AM L 1 STP SUMP UNL STP FUEL ALARM CLEAR 7-24-23 9:37AM L 1 STP SUMP UNL STP FUEL ALARM ALARM 7-24-23 9:36AM L 2 ANNULAR UNL ANN FUEL ALARM CLEAR 7-24-23 9:36AM L 2 ANNULAR UNL ANN FUEL ALARM ALARM 7-24-23 9:35AM L 4 ANNULAR PREM ANN FUEL ALARM CLEAR 7-24-23 9:34AM L 4 ANNULAR PREM ANN FUEL ALARM ALARM 7-24-23 9:34AM L 3 STP SUMP PREM STP FUEL ALARM CLEAR 7-24-23 9:34AM L 3 STP SUMP PREM STP FUEL ALARM ALARM 7-24-23 9:33AM L 6 ANNULAR DSL ANN FUEL ALARM CLEAR 7-24-23 9:32AM L 5 STP SUMP DSL STP FUEL ALARM CLEAR 7-24-23 9:32AM L 5 STP SUMP DSL STP FUEL ALARM ALARM 7-24-23 9:32AM L 8 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-24-23 8:53AM L 8 DISP PAN DISP 11-12 FUEL ALARM ALARM 7-24-23 8:53AM L 6 ANNULAR DSL ANN FUEL ALARM ALARM 7-22-23 11:44PM T 1 TANK UNL OVERFILL ALARM CLEAR 7-21-23 6:40AM T 1 TANK UNL OVERFILL ALARM ALARM 7-21-23 6:35AM T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-16-23 9:35AM T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-16-23 6:12AM T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-14-23 5:00PM T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-14-23 4:28PM I11200 JUL 24, 2023 11:10 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK UNL DELIVERY NEEDED CLEAR 7-16-23 9:35AM T 1 TANK UNL INVALID FUEL LEVEL CLEAR 7-16-23 9:33AM T 1 TANK UNL INVALID FUEL LEVEL ALARM 7-16-23 9:19AM T 1 TANK UNL DELIVERY NEEDED ALARM 7-16-23 6:12AM T 1 TANK UNL DELIVERY NEEDED CLEAR 7-14-23 5:00PM T 1 TANK UNL DELIVERY NEEDED ALARM 7-14-23 4:28PM T 1 TANK UNL DELIVERY NEEDED CLEAR 7-07-23 7:45PM T 1 TANK UNL INVALID FUEL LEVEL CLEAR 7-07-23 7:43PM T 1 TANK UNL INVALID FUEL LEVEL ALARM 7-07-23 6:33PM T 1 TANK UNL DELIVERY NEEDED ALARM 7-07-23 5:02PM L12 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L11 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L14 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L13 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L15 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM L14 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L13 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L12 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L11 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L15 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L14 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L13 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L12 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L11 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM L16 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L15 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L14 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L13 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L12 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM L11 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM SYSTEM PRINTER ERROR CLEAR 6-24-23 8:49AM SYSTEM PAPER OUT CLEAR 6-24-23 8:49AM SYSTEM PRINTER ERROR ALARM 6-24-23 8:44AM SYSTEM PAPER OUT ALARM 6-24-23 8:44AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 6-17-23 10:00AM h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 6-12-23 10:02AM T 1 TANK UNL DELIVERY NEEDED CLEAR 6-11-23 9:36PM T 1 TANK UNL DELIVERY NEEDED ALARM 6-11-23 9:30PM T 1 TANK UNL DELIVERY NEEDED CLEAR 6-03-23 10:14AM T 1 TANK UNL INVALID FUEL LEVEL CLEAR 6-03-23 10:13AM I20600 JUL 24, 2023 11:10 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 TANK ALARM HISTORY TANK 1 UNL OVERFILL ALARM JUL 21, 2023 6:35 AM JUN 4, 2023 6:16 AM MAY 31, 2023 10:50 AM LOW PRODUCT ALARM JUL 16, 2023 6:12 AM JUL 14, 2023 4:28 PM JUL 7, 2023 5:02 PM INVALID FUEL LEVEL JUL 16, 2023 9:19 AM JUL 7, 2023 6:33 PM JUN 3, 2023 7:13 AM DELIVERY NEEDED JUL 16, 2023 6:12 AM JUL 14, 2023 4:28 PM JUL 7, 2023 5:02 PM TANK 2 PREM TANK 3 DSL LOW PRODUCT ALARM FEB 13, 2021 8:05 AM DELIVERY NEEDED FEB 13, 2021 8:05 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JUL 24, 2023 11:10 AM I30200 JUL 24, 2023 11:11 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL STP JUL 24, 2023 9:52 AM SENSOR OUT ALARM JUL 24, 2023 9:36 AM FUEL ALARM JUL 6, 2023 2:18 PM SENSOR OUT ALARM 2 UNL ANN JUL 24, 2023 9:52 AM SENSOR OUT ALARM JUL 24, 2023 9:35 AM FUEL ALARM JUL 6, 2023 2:18 PM SENSOR OUT ALARM 3 PREM STP JUL 24, 2023 9:52 AM SENSOR OUT ALARM JUL 24, 2023 9:33 AM FUEL ALARM JUL 6, 2023 2:18 PM SENSOR OUT ALARM 4 PREM ANN JUL 24, 2023 9:52 AM SENSOR OUT ALARM JUL 24, 2023 9:34 AM FUEL ALARM JUL 6, 2023 2:18 PM SENSOR OUT ALARM 5 DSL STP JUL 24, 2023 9:52 AM SENSOR OUT ALARM JUL 24, 2023 9:32 AM FUEL ALARM JUL 6, 2023 2:18 PM SENSOR OUT ALARM 6 DSL ANN JUL 24, 2023 9:52 AM SENSOR OUT ALARM JUL 24, 2023 9:49 AM FUEL ALARM JUL 22, 2023 11:44 PM FUEL ALARM 7 DISP 9-10 JUL 24, 2023 9:52 AM SENSOR OUT ALARM JUL 24, 2023 9:39 AM FUEL ALARM JUL 6, 2023 2:18 PM SENSOR OUT ALARM 8 DISP 11-12 JUL 24, 2023 9:52 AM SENSOR OUT ALARM JUL 24, 2023 9:40 AM FUEL ALARM JUL 24, 2023 8:53 AM FUEL ALARM 9 DISP 13-14 JUL 24, 2023 9:51 AM SENSOR OUT ALARM JUL 24, 2023 9:38 AM FUEL ALARM JUL 6, 2023 2:20 PM SENSOR OUT ALARM 10 DISP 15-16 JUL 24, 2023 9:51 AM SENSOR OUT ALARM JUL 24, 2023 9:37 AM FUEL ALARM JUL 6, 2023 2:20 PM SENSOR OUT ALARM I31600 JUL 24, 2023 11:11 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VP 11-12 2 FM 9-10 3 FM 11-12 4 FM 13-14 5 FM 15-16 I40200 JUL 24, 2023 11:11 AM I40300 JUL 24, 2023 11:11 AM I34200 JUL 24, 2023 11:11 AM I34700 JUL 24, 2023 11:11 AM IV0100 JUL 24, 2023 11:11 AM FASTRIP 7725 4901 S UNION BAKERSFIELD CA 661-397-9387 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME : 99% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-06-16 10:02:04 A/L RATIO DEGRADATION FP 3 BLEND3 0.79 23-06-15 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.78 23-06-14 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.77 23-06-13 10:02:26 A/L RATIO DEGRADATION FP 3 BLEND3 0.78 23-06-12 10:02:18 A/L RATIO DEGRADATION FP 3 BLEND3 0.79 22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 22-11-12 10:02:37 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-11-13 10:01:40 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-11-13 10:01:40 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 22-11-10 10:01:37 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-11-10 10:01:36 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-07-24 10:02:13 READINESS ISD:PP EVR:PP ISD & EVR READY 23-07-24 09:56:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-07-24 09:56:18 ISD STARTUP 23-07-24 09:56:12 ISD SHUTDOWN 23-07-14 10:01:51 READINESS ISD:PP EVR:PP ISD & EVR READY 23-07-13 17:43:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-07-13 17:43:30 ISD STARTUP 23-07-13 17:23:56 ISD SHUTDOWN 23-07-07 10:02:03 READINESS ISD:PP EVR:PP ISD & EVR READY 23-07-06 14:31:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING