HomeMy WebLinkAboutFMC 2023Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10159083 7/24/23
Jaco #7725 Fastrip #19 (South)
4901 South Union Avenue Bakersfield 93307
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Payton Phillips
1073967
9482312 0/15/20024
Veeder Root C27796 08/01/2024
7/24/23 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS-350 336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 UNL STP
L2 420 UNL Ann
L3 208 PREM STP
L4 420 PREM Ann
L5 208 DSL STP
L6 420 DSL Ann
L7 208 Disp 9-10
L8 208 Disp 11-12
L9 208 Disp 13-14
L10 208 Disp 15-16
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V UNLEADED
T2 FX1V PREM
T3 FX1DV Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Fill sumps have water. Upon arrival the tank pad was covered in water causing the DSL annular to get wet. I removed water
from Annular riser.
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
N/A
12,000 GALLON12,000 GALLONEXISTING BUILDING
NOPAR
KI
NG
G
W
PRICE SIGNPRICE SIGN12,000 GALLON87-1 UNLEADEDFV
STPL5H
HDUMPSTER
FFVSTPL3STPL1AL6AL4AL212,000 GALLONDIESEL87 UNLEADEDPREMIUM1112L81516L10910L71314L9#7-725FSTPL1V
AL8
AL6
AL4
AL2
FSTPL3V
FSTPL5V
FSTPL7
12,000 GALLON87-2 UNLEADED
12,000 GALLONPREMIUM
12,000 GALLONDIESEL
21L9
43L10
L14
65L11
87L12
L13
40' STORAGE CONTAINER
40' STORAGE CONTAINER
S. UNION AVE.PACHECO RD.N
#7-775
7-775
7-725
SLOPE
PROPERTY LINE
PROPERTY LINE
ADJACENT JACO PORPERTY TO THE SOUTH NOT SHOWN, FOR CLARITY
PROPANE TANK CAGE
167.17'
148.17'
315.86'108.70'63.50'172.22'
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
UST ELECTRICAL PANEL
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
W
G
H
725 LEGEND
L1 87 STP
L2 87 ANNULAR
L3 91 STP
L4 91 ANNULAR
L5 DSL STP
L6 DSL ANNULAR
L7 UDC 9 -10
L8 UDC 11 - 12
L9 UDC 13 - 14
L10 UDC 15 - 16
775 LEGEND
L1 87-1 STP
L2 87-1 ANNULAR
L3 87-2 STP
L4 87-2 ANNULAR
L5 91 STP
L6 91 ANNULAR
L7 DSL STP
L8 DSL ANNULAR
L9 UDC 1 -2
L10 UDC 3 - 4
L11 UDC 5 -6
L12 UDC 7 - 8
L13 N TRANS SUMP
L14 S TRANS SUMP
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 3/2 INCH DOUBLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULARA
P
V
SITE MAP
SCALE:
C1
VICINITY MAP
PROJECT DATA
1"=15'-0"
INCHES012
SHEET SIZE 22 X 34
4901 S. UNION AVE.
BAKERSFIELD, CA 93307
PROJECT OWNER:
JAMIESON HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FASTRIPS #7725 / #7775
#7725 CERS ID 10159083
FACILITY ID 15-021-100269
#7775 CERS ID 10159109
FACILITY ID 15-021-003076
4901 S. UNION AVE.
BAKERSFIELD, CA 93307
03/06/17 REV.S. UNION AVE.E. PACHECO RD.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #7725 Fastrip #19 (South)4901 South Union AvenueBakersfield1015908311-1215-16 Tested ESO also and it passed.MPDMPDMPDMPD9-1013-14ProductProductProductProductPayton Phillips
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10159083 7/24/23
Jaco #7725 Fastrip #19 (South)
4901 South Union Avenue Bakersfield 93307
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Payton Phillips
1073967
9482312 0/15/20024
OPW 0187328 08/14/24
PEI 1200 Hydrostatic Lake Test (OPW Spill buckets)
7/24/23 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1 UNL
OPW
T2 PREM
OPW
T3 DIESEL
OPW
07-24-23
Monitor Cert Printouts
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
SYSTEM SETUP
200
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
JUL 24, 2023 9:00 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNL 4074 35.76 0.0 81.8 7926
2 PREM 4318 37.34 0.8 82.2 7682
3 DSL 538 8.67 1.1 86.9 11462
I90500
JUL 24, 2023 9:00 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JUL 24, 2023 9:00 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JUL 24, 2023 9:00 AM
SHIFT TIME 1 : 12:00 AM
I50202
JUL 24, 2023 9:00 AM
SHIFT TIME 2 : DISABLED
I50203
JUL 24, 2023 9:00 AM
SHIFT TIME 3 : DISABLED
I50204
JUL 24, 2023 9:00 AM
SHIFT TIME 4 : DISABLED
I54600
JUL 24, 2023 9:00 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JUL 24, 2023 9:00 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JUL 24, 2023 9:00 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JUL 24, 2023 9:00 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JUL 24, 2023 9:00 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JUL 24, 2023 9:00 AM
PRINT TC VOLUMES
ENABLED
I50E00
JUL 24, 2023 9:00 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JUL 24, 2023 9:00 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JUL 24, 2023 9:00 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JUL 24, 2023 9:00 AM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
JUL 24, 2023 9:00 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JUL 24, 2023 9:00 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JUL 24, 2023 9:00 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JUL 24, 2023 9:00 AM
TANK CHART SECURITY
DISABLED
I5BD00
JUL 24, 2023 9:00 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JUL 24, 2023 9:00 AM
MASS/DENSITY
DISABLED
I88101
JUL 24, 2023 9:00 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JUL 24, 2023 9:00 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
JUL 24, 2023 9:00 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JUL 24, 2023 9:00 AM
I88105
JUL 24, 2023 9:00 AM
I88106
JUL 24, 2023 9:00 AM
I52000
JUL 24, 2023 9:00 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE ??? 24, 2023 DISABLED
2 ON DATE ??? 24, 2023 DISABLED
3 ON DATE ??? 24, 2023 DISABLED
4 ON DATE ??? 24, 2023 DISABLED
5 ON DATE ??? 24, 2023 DISABLED
6 ON DATE ??? 24, 2023 DISABLED
7 ON DATE ??? 24, 2023 DISABLED
8 ON DATE ??? 24, 2023 DISABLED
I60100
JUL 24, 2023 9:00 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNL ON
2 PREM ON
3 DSL ON
4 OFF
I60200
JUL 24, 2023 9:00 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNL
2 PREM
3 DSL
4
I60300
JUL 24, 2023 9:00 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNL 1
2 PREM 2
3 DSL 3
4 4
I60900
JUL 24, 2023 9:00 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNL 0.000700
2 PREM 0.000700
3 DSL 0.000450
4 0.000000
I60700
JUL 24, 2023 9:00 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNL 96.00
2 PREM 96.00
3 DSL 96.00
4 0.00
I60A00
JUL 24, 2023 9:00 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL
1 PT 12000 2 PREM 1 PT 12000 3 DSL
1 PT 12000 4 1 PT 0
I60400
JUL 24, 2023 9:00 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 12000
2 PREM 12000
3 DSL 12000
4 0
I60500
JUL 24, 2023 9:01 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNL 12000 0 0 0
2 PREM 12000 0 0 0
3 DSL 12000 0 0 0
4 0 0 0 0
I60600
JUL 24, 2023 9:01 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 PREM 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DSL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JUL 24, 2023 9:01 AM
TANK PRODUCT LABEL METER DATA
1 UNL NO
2 PREM NO
3 DSL NO
4 NO
I62F00
JUL 24, 2023 9:01 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNL 4.0 IN.
2 PREM 4.0 IN.
3 DSL 3.0 IN.
I62700
JUL 24, 2023 9:01 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNL 2.0
2 PREM 2.0
3 DSL 2.0
I64200
JUL 24, 2023 9:01 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNL LOW
2 PREM LOW
3 DSL LOW
I62400
JUL 24, 2023 9:01 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNL 3.0
2 PREM 3.0
3 DSL 3.0
I62800
JUL 24, 2023 9:01 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 12000
2 PREM 12000
3 DSL 12000
4 0
I62300
JUL 24, 2023 9:01 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 10800
2 PREM 10800
3 DSL 10800
4 0
I62200
JUL 24, 2023 9:01 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 11400
2 PREM 11400
3 DSL 11400
4 0
I62900
JUL 24, 2023 9:01 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1200
2 PREM 1200
3 DSL 1200
4 0
I62100
JUL 24, 2023 9:01 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1200
2 PREM 1200
3 DSL 1200
4 0
I62600
JUL 24, 2023 9:01 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 99
2 PREM 99
3 DSL 99
4 99
I62500
JUL 24, 2023 9:01 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 99
2 PREM 99
3 DSL 99
4 99
I60800
JUL 24, 2023 9:01 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNL 0.00
2 PREM 0.00
3 DSL 0.00
4 0.00
I60B00
JUL 24, 2023 9:01 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JUL 24, 2023 9:01 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNL 0.00
2 PREM 0.00
3 DSL 0.00
4 0.00
I61200
JUL 24, 2023 9:01 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNL NONE NONE
2 PREM NONE NONE
3 DSL NONE NONE
4 NONE NONE
I63600
JUL 24, 2023 9:01 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 120
2 PREM 120
3 DSL 120
4 0
I62A00
JUL 24, 2023 9:01 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 120
2 PREM 120
3 DSL 120
4 0
I62C00
JUL 24, 2023 9:01 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNL STANDARD
2 PREM STANDARD
3 DSL STANDARD
4 STANDARD
I62D00
JUL 24, 2023 9:01 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 PREM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DSL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JUL 24, 2023 9:01 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNL OFF OFF
2 PREM OFF OFF
3 DSL OFF OFF
4 OFF OFF
I63000
JUL 24, 2023 9:01 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNL OFF
2 PREM OFF
3 DSL OFF
4 OFF
I63200
JUL 24, 2023 9:01 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNL OFF
2 PREM OFF
3 DSL OFF
4 OFF
I61000
JUL 24, 2023 9:01 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNL 1
2 PREM 1
3 DSL 1
4 1
I63A00
JUL 24, 2023 9:01 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNL 10.00%
2 PREM 10.00%
3 DSL 10.00%
4 10.00%
I61100
JUL 24, 2023 9:01 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
OCT 1, 2014
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
JUL 24, 2023 9:01 AM
CSLD PROBABLITY OF DETECTION
I61400
JUL 24, 2023 9:01 AM
CSLD CLIMATE FACTOR
I61600
JUL 24, 2023 9:01 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNL IMMEDIATE
2 PREM IMMEDIATE
3 DSL IMMEDIATE
4 IMMEDIATE
I61A00
JUL 24, 2023 9:01 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNL DISABLED
2 PREM DISABLED
3 DSL DISABLED
4 DISABLED
I61B00
JUL 24, 2023 9:01 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JUL 24, 2023 9:01 AM
CSLD REPORT ONLY
I62B00
JUL 24, 2023 9:01 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNL ??? 0, 0
2 PREM ??? 0, 0
3 DSL ??? 0, 0
4 ??? 0, 0
I63300
JUL 24, 2023 9:01 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JUL 24, 2023 9:01 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 0
2 PREM 0
3 DSL 0
4 0
I63500
JUL 24, 2023 9:01 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1
2 PREM 1
3 DSL 1
4 1
I63900
JUL 24, 2023 9:01 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNL
END FACTOR: NONE
2 PREM
END FACTOR: NONE
3 DSL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
JUL 24, 2023 9:01 AM
I77700
JUL 24, 2023 9:01 AM
I77800
JUL 24, 2023 9:01 AM
I78C00
JUL 24, 2023 9:01 AM
I78300
JUL 24, 2023 9:01 AM
I78F00
JUL 24, 2023 9:01 AM
I78700
JUL 24, 2023 9:01 AM
I70200
JUL 24, 2023 9:01 AM
LIQUID LABEL
DEVICE LABEL
1 UNL STP
2 UNL ANN
3 PREM STP
4 PREM ANN
5 DSL STP
6 DSL ANN
7 DISP 9-10
8 DISP 11-12
9 DISP 13-14
10 DISP 15-16
11
12
13
14
15
16
I70300
JUL 24, 2023 9:01 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL STP TRI-STATE (SINGLE FLOAT)
2 UNL ANN TRI-STATE (SINGLE FLOAT)
3 PREM STP TRI-STATE (SINGLE FLOAT)
4 PREM ANN TRI-STATE (SINGLE FLOAT)
5 DSL STP TRI-STATE (SINGLE FLOAT)
6 DSL ANN TRI-STATE (SINGLE FLOAT)
7 DISP 9-10 TRI-STATE (SINGLE FLOAT)
8 DISP 11-12 TRI-STATE (SINGLE FLOAT)
9 DISP 13-14 TRI-STATE (SINGLE FLOAT)
10 DISP 15-16 TRI-STATE (SINGLE FLOAT)
11 TRI-STATE (SINGLE FLOAT)
12 TRI-STATE (SINGLE FLOAT)
13 TRI-STATE (SINGLE FLOAT)
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
JUL 24, 2023 9:01 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL STP STP SUMP
2 UNL ANN ANNULAR SPACE
3 PREM STP STP SUMP
4 PREM ANN ANNULAR SPACE
5 DSL STP STP SUMP
6 DSL ANN ANNULAR SPACE
7 DISP 9-10 DISPENSER PAN
8 DISP 11-12 DISPENSER PAN
9 DISP 13-14 DISPENSER PAN
10 DISP 15-16 DISPENSER PAN
11 OTHER SENSORS
12 OTHER SENSORS
13 OTHER SENSORS
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
JUL 24, 2023 9:01 AM
I74300
JUL 24, 2023 9:01 AM
I74400
JUL 24, 2023 9:01 AM
I74700
JUL 24, 2023 9:01 AM
I74800
JUL 24, 2023 9:01 AM
I74900
JUL 24, 2023 9:01 AM
I7BC00
JUL 24, 2023 9:01 AM
I80200
JUL 24, 2023 9:01 AM
I80300
JUL 24, 2023 9:01 AM
I80400
JUL 24, 2023 9:01 AM
I80700
JUL 24, 2023 9:01 AM
RELAY LABEL
DEVICE LABEL
1 UNL
2 PNL
3 DSL
4 OVERFILL
I80900
JUL 24, 2023 9:01 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNL NORMALLY CLOSED
2 PNL NORMALLY CLOSED
3 DSL NORMALLY CLOSED
4 OVERFILL NORMALLY OPEN
I80B00
JUL 24, 2023 9:01 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNL 1
2 PNL 2
3 DSL 3
4 OVERFILL NONE
I80A00
JUL 24, 2023 9:01 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNL STANDARD
2 PNL STANDARD
3 DSL STANDARD
4 OVERFILL STANDARD
I80C00
JUL 24, 2023 9:01 AM
I80800
JUL 24, 2023 9:01 AM
RELAY SETUP REPORT
R 1:UNL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L 1:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L 1:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD SETUP FAIL
ISD SENSOR OUT FAIL
PC-ISD FAILURE
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:PNL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L 3:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L 3:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD SETUP FAIL
ISD SENSOR OUT FAIL
PC-ISD FAILURE
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DSL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 3
LIQUID SENSOR ALMS
L 5:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L 5:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L 5:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
R 4:OVERFILL
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
I79000
JUL 24, 2023 9:02 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
JUL 24, 2023 9:02 AM
I72300
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VP 11-12 VAPOR PRESSURE
02 FM 9-10 AIR FLOW METER
03 FM 11-12 AIR FLOW METER
04 FM 13-14 AIR FLOW METER
05 FM 15-16 AIR FLOW METER
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
VAPOR PROCESSOR TYPE
NONE
IV4700
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
ACCEPT HIGH ORVR: YES
IV4A00
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 09 01 01 02 BLEND3
02 10 02 01 02 BLEND3
03 11 03 02 02 BLEND3
04 12 04 02 02 BLEND3
05 17 05 03 02 BLEND3
06 18 06 03 02 BLEND3
07 19 07 04 02 BLEND3
08 20 08 04 02 BLEND3
IV4B00
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
09 01 02/01 03/01 09/01 xx/xx
10 01 02/02 03/02 09/02 xx/xx
11 02 02/03 03/03 09/03 xx/xx
12 02 02/04 03/04 09/04 xx/xx
17 03 02/05 03/05 09/05 xx/xx
18 03 02/06 03/06 09/06 xx/xx
19 04 02/07 03/07 09/07 xx/xx
20 04 02/08 03/08 09/08 xx/xx
IV4900
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JUL 24, 2023 9:02 AM
ISD VERSION: 01.07
ALARM HISTORY (BEFORE)
I10200
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39474 39596
2 4 PROBE / G.T. 164070 164552
3 INTERSTITIAL BD 202298 202859
4 INTERSTITIAL BD 202477 202592
5 UNUSED 9673851 9595982
6 UNUSED 9671231 9570491
7 UNUSED 9663563 9579927
8 UNUSED 9664079 9570170
9 RELAY BOARD 15007 15043
10 UNUSED 9667206 9575142
11 UNUSED 9665638 9563699
12 UNUSED 9659087 9571192
13 UNUSED 9661450 9562738
14 UNUSED 9664199 9565300
15 UNUSED 9659817 9559792
16 UNUSED 9662373 9555479
COMM 1 ELEC DISP INT. 101300 101373
COMM 2 RS232 SERIAL BD 14985 15021
COMM 3 RS232 SERIAL BD 15007 15021
COMM 4 UNUSED 9671673 9572559
COMM 5 UNUSED 9661514 9563955
COMM 6 UNUSED 9661299 9566581
I90200
JUL 24, 2023 9:02 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 24, 2023 9:02 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 8 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-24-23 8:53AM
L 8 DISP PAN DISP 11-12 FUEL ALARM ALARM 7-24-23 8:53AM
L 6 ANNULAR DSL ANN FUEL ALARM ALARM 7-22-23 11:44PM
T 1 TANK UNL OVERFILL ALARM CLEAR 7-21-23 6:40AM
T 1 TANK UNL OVERFILL ALARM ALARM 7-21-23 6:35AM
T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-16-23 9:35AM
T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-16-23 6:12AM
T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-14-23 5:00PM
T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-14-23 4:28PM
T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-07-23 7:45PM
T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-07-23 5:02PM
L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L 4 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L 3 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L 5 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L10 DISP PAN DISP 15-16 SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM CLEAR 7-06-23 2:26PM
L10 DISP PAN DISP 15-16 SENSOR OUT ALARM ALARM 7-06-23 2:20PM
L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM ALARM 7-06-23 2:20PM
L 4 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-06-23 2:18PM
L 3 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-06-23 2:18PM
L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-06-23 2:18PM
L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-06-23 2:18PM
L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-06-23 2:18PM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-06-23 2:18PM
L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-06-23 2:18PM
L 5 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-06-23 2:18PM
L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-06-23 1:45PM
L 3 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-06-23 1:45PM
L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-06-23 1:45PM
L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-06-23 1:45PM
L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-06-23 1:45PM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-06-23 1:45PM
L 4 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-06-23 1:45PM
L 5 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-06-23 1:45PM
L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-06-23 1:42PM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-06-23 1:42PM
L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-06-23 1:42PM
L 4 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-06-23 1:42PM
L 3 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-06-23 1:42PM
L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-06-23 1:42PM
L 5 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-06-23 1:42PM
L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-06-23 1:42PM
L 8 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-06-23 1:26PM
L 4 ANNULAR PREM ANN FUEL ALARM CLEAR 7-06-23 1:26PM
L10 DISP PAN DISP 15-16 FUEL ALARM CLEAR 7-06-23 1:26PM
I11200
JUL 24, 2023 9:03 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK UNL DELIVERY NEEDED CLEAR 7-16-23 9:35AM
T 1 TANK UNL INVALID FUEL LEVEL CLEAR 7-16-23 9:33AM
T 1 TANK UNL INVALID FUEL LEVEL ALARM 7-16-23 9:19AM
T 1 TANK UNL DELIVERY NEEDED ALARM 7-16-23 6:12AM
T 1 TANK UNL DELIVERY NEEDED CLEAR 7-14-23 5:00PM
T 1 TANK UNL DELIVERY NEEDED ALARM 7-14-23 4:28PM
T 1 TANK UNL DELIVERY NEEDED CLEAR 7-07-23 7:45PM
T 1 TANK UNL INVALID FUEL LEVEL CLEAR 7-07-23 7:43PM
T 1 TANK UNL INVALID FUEL LEVEL ALARM 7-07-23 6:33PM
T 1 TANK UNL DELIVERY NEEDED ALARM 7-07-23 5:02PM
L12 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L11 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L14 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L13 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L15 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM
L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM
L14 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L13 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L12 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L11 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L15 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L14 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L13 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L12 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L11 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L16 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L15 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L14 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L13 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L12 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L11 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
SYSTEM PRINTER ERROR CLEAR 6-24-23 8:49AM
SYSTEM PAPER OUT CLEAR 6-24-23 8:49AM
SYSTEM PRINTER ERROR ALARM 6-24-23 8:44AM
SYSTEM PAPER OUT ALARM 6-24-23 8:44AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 6-17-23 10:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 6-12-23 10:02AM
T 1 TANK UNL DELIVERY NEEDED CLEAR 6-11-23 9:36PM
T 1 TANK UNL DELIVERY NEEDED ALARM 6-11-23 9:30PM
T 1 TANK UNL DELIVERY NEEDED CLEAR 6-03-23 10:14AM
T 1 TANK UNL INVALID FUEL LEVEL CLEAR 6-03-23 10:13AM
I20600
JUL 24, 2023 9:03 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
TANK ALARM HISTORY
TANK 1 UNL
OVERFILL ALARM JUL 21, 2023 6:35 AM
JUN 4, 2023 6:16 AM
MAY 31, 2023 10:50 AM
LOW PRODUCT ALARM JUL 16, 2023 6:12 AM
JUL 14, 2023 4:28 PM
JUL 7, 2023 5:02 PM
INVALID FUEL LEVEL JUL 16, 2023 9:19 AM
JUL 7, 2023 6:33 PM
JUN 3, 2023 7:13 AM
DELIVERY NEEDED JUL 16, 2023 6:12 AM
JUL 14, 2023 4:28 PM
JUL 7, 2023 5:02 PM
TANK 2 PREM
TANK 3 DSL
LOW PRODUCT ALARM FEB 13, 2021 8:05 AM
DELIVERY NEEDED FEB 13, 2021 8:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 24, 2023 9:03 AM
I30200
JUL 24, 2023 9:03 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL STP
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
JUL 6, 2023 1:42 PM SENSOR OUT ALARM
JUL 6, 2023 1:25 PM FUEL ALARM
2 UNL ANN
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
JUL 6, 2023 1:42 PM SENSOR OUT ALARM
JUL 6, 2023 1:25 PM FUEL ALARM
3 PREM STP
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
JUL 6, 2023 1:42 PM SENSOR OUT ALARM
JUL 6, 2023 1:25 PM FUEL ALARM
4 PREM ANN
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
JUL 6, 2023 1:42 PM SENSOR OUT ALARM
JUL 6, 2023 1:25 PM FUEL ALARM
5 DSL STP
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
JUL 6, 2023 1:42 PM SENSOR OUT ALARM
JUL 6, 2023 1:25 PM FUEL ALARM
6 DSL ANN
JUL 22, 2023 11:44 PM FUEL ALARM
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
JUL 6, 2023 1:42 PM SENSOR OUT ALARM
7 DISP 9-10
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
JUL 6, 2023 1:42 PM SENSOR OUT ALARM
JUL 6, 2023 1:25 PM FUEL ALARM
8 DISP 11-12
JUL 24, 2023 8:53 AM FUEL ALARM
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
JUL 6, 2023 1:42 PM SENSOR OUT ALARM
9 DISP 13-14
JUL 6, 2023 2:20 PM SENSOR OUT ALARM
JUL 6, 2023 1:25 PM FUEL ALARM
JUL 6, 2023 1:25 PM FUEL ALARM
10 DISP 15-16
JUL 6, 2023 2:20 PM SENSOR OUT ALARM
JUL 6, 2023 1:25 PM FUEL ALARM
JUL 6, 2023 1:24 PM SENSOR OUT ALARM
I31600
JUL 24, 2023 9:03 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP 11-12
2 FM 9-10
3 FM 11-12
4 FM 13-14
5 FM 15-16
I40200
JUL 24, 2023 9:03 AM
I40300
JUL 24, 2023 9:03 AM
I34200
JUL 24, 2023 9:03 AM
I34700
JUL 24, 2023 9:03 AM
IV0100
JUL 24, 2023 9:03 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-06-16 10:02:04 A/L RATIO DEGRADATION FP 3 BLEND3 0.79
23-06-15 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.78
23-06-14 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.77
23-06-13 10:02:26 A/L RATIO DEGRADATION FP 3 BLEND3 0.78
23-06-12 10:02:18 A/L RATIO DEGRADATION FP 3 BLEND3 0.79
22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-11-12 10:02:37 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-11-13 10:01:40 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-11-13 10:01:40 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
22-11-10 10:01:37 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-11-10 10:01:36 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-07-14 10:01:51 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-13 17:43:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-13 17:43:30 ISD STARTUP
23-07-13 17:23:56 ISD SHUTDOWN
23-07-07 10:02:03 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-06 14:31:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-06 14:31:18 ISD STARTUP
23-07-06 14:31:14 ISD SHUTDOWN
23-04-30 10:01:09 READINESS ISD:PP EVR:PP ISD & EVR READY
23-04-30 02:46:50 READINESS ISD:PP EVR:NN EVR READINESS PENDING
ALARM HISTORY (AFTER)
I10200
JUL 24, 2023 11:10 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 8SMARTSENSOR BD 39474 39399
2 4 PROBE / G.T. 164070 164012
3 INTERSTITIAL BD 202298 202106
4 INTERSTITIAL BD 202477 202241
5 UNUSED 9673851 9387821
6 UNUSED 9671231 9388210
7 UNUSED 9663563 9393293
8 UNUSED 9664079 9383841
9 RELAY BOARD 15007 14985
10 UNUSED 9667206 9394467
11 UNUSED 9665638 9381575
12 UNUSED 9659087 9386831
13 UNUSED 9661450 9384170
14 UNUSED 9664199 9391568
15 UNUSED 9659817 9388237
16 UNUSED 9662373 9389210
COMM 1 ELEC DISP INT. 101300 101203
COMM 2 RS232 SERIAL BD 14985 15007
COMM 3 RS232 SERIAL BD 15007 15007
COMM 4 UNUSED 9671673 9389557
COMM 5 UNUSED 9661514 9393320
COMM 6 UNUSED 9661299 9385685
I90200
JUL 24, 2023 11:10 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JUL 24, 2023 11:10 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 4 ANNULAR PREM ANN SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L 3 STP SUMP PREM STP SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L 2 ANNULAR UNL ANN SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L 5 STP SUMP DSL STP SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L10 DISP PAN DISP 15-16 SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM CLEAR 7-24-23 9:54AM
L 8 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 7-24-23 9:52AM
L 4 ANNULAR PREM ANN SENSOR OUT ALARM ALARM 7-24-23 9:52AM
L 3 STP SUMP PREM STP SENSOR OUT ALARM ALARM 7-24-23 9:52AM
L 7 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 7-24-23 9:52AM
L 2 ANNULAR UNL ANN SENSOR OUT ALARM ALARM 7-24-23 9:52AM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 7-24-23 9:52AM
L 1 STP SUMP UNL STP SENSOR OUT ALARM ALARM 7-24-23 9:52AM
L 5 STP SUMP DSL STP SENSOR OUT ALARM ALARM 7-24-23 9:52AM
L 6 ANNULAR DSL ANN FUEL ALARM CLEAR 7-24-23 9:52AM
L10 DISP PAN DISP 15-16 SENSOR OUT ALARM ALARM 7-24-23 9:51AM
L 9 DISP PAN DISP 13-14 SENSOR OUT ALARM ALARM 7-24-23 9:51AM
L 6 ANNULAR DSL ANN FUEL ALARM ALARM 7-24-23 9:49AM
L 8 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-24-23 9:40AM
L 8 DISP PAN DISP 11-12 FUEL ALARM ALARM 7-24-23 9:40AM
L 7 DISP PAN DISP 9-10 FUEL ALARM CLEAR 7-24-23 9:39AM
L 7 DISP PAN DISP 9-10 FUEL ALARM ALARM 7-24-23 9:39AM
L 9 DISP PAN DISP 13-14 FUEL ALARM CLEAR 7-24-23 9:38AM
L 9 DISP PAN DISP 13-14 FUEL ALARM ALARM 7-24-23 9:38AM
L10 DISP PAN DISP 15-16 FUEL ALARM CLEAR 7-24-23 9:37AM
L10 DISP PAN DISP 15-16 FUEL ALARM ALARM 7-24-23 9:37AM
L 1 STP SUMP UNL STP FUEL ALARM CLEAR 7-24-23 9:37AM
L 1 STP SUMP UNL STP FUEL ALARM ALARM 7-24-23 9:36AM
L 2 ANNULAR UNL ANN FUEL ALARM CLEAR 7-24-23 9:36AM
L 2 ANNULAR UNL ANN FUEL ALARM ALARM 7-24-23 9:35AM
L 4 ANNULAR PREM ANN FUEL ALARM CLEAR 7-24-23 9:34AM
L 4 ANNULAR PREM ANN FUEL ALARM ALARM 7-24-23 9:34AM
L 3 STP SUMP PREM STP FUEL ALARM CLEAR 7-24-23 9:34AM
L 3 STP SUMP PREM STP FUEL ALARM ALARM 7-24-23 9:33AM
L 6 ANNULAR DSL ANN FUEL ALARM CLEAR 7-24-23 9:32AM
L 5 STP SUMP DSL STP FUEL ALARM CLEAR 7-24-23 9:32AM
L 5 STP SUMP DSL STP FUEL ALARM ALARM 7-24-23 9:32AM
L 8 DISP PAN DISP 11-12 FUEL ALARM CLEAR 7-24-23 8:53AM
L 8 DISP PAN DISP 11-12 FUEL ALARM ALARM 7-24-23 8:53AM
L 6 ANNULAR DSL ANN FUEL ALARM ALARM 7-22-23 11:44PM
T 1 TANK UNL OVERFILL ALARM CLEAR 7-21-23 6:40AM
T 1 TANK UNL OVERFILL ALARM ALARM 7-21-23 6:35AM
T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-16-23 9:35AM
T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-16-23 6:12AM
T 1 TANK UNL LOW PRODUCT ALARM CLEAR 7-14-23 5:00PM
T 1 TANK UNL LOW PRODUCT ALARM ALARM 7-14-23 4:28PM
I11200
JUL 24, 2023 11:10 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK UNL DELIVERY NEEDED CLEAR 7-16-23 9:35AM
T 1 TANK UNL INVALID FUEL LEVEL CLEAR 7-16-23 9:33AM
T 1 TANK UNL INVALID FUEL LEVEL ALARM 7-16-23 9:19AM
T 1 TANK UNL DELIVERY NEEDED ALARM 7-16-23 6:12AM
T 1 TANK UNL DELIVERY NEEDED CLEAR 7-14-23 5:00PM
T 1 TANK UNL DELIVERY NEEDED ALARM 7-14-23 4:28PM
T 1 TANK UNL DELIVERY NEEDED CLEAR 7-07-23 7:45PM
T 1 TANK UNL INVALID FUEL LEVEL CLEAR 7-07-23 7:43PM
T 1 TANK UNL INVALID FUEL LEVEL ALARM 7-07-23 6:33PM
T 1 TANK UNL DELIVERY NEEDED ALARM 7-07-23 5:02PM
L12 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L11 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L14 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L13 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:26PM
L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L15 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM
L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM
L14 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L13 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L12 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L11 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L15 OTHER SETUP DATA WARNING ALARM 7-06-23 1:25PM
L16 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L15 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L14 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L13 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L12 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L11 OTHER SETUP DATA WARNING CLEAR 7-06-23 12:46PM
L16 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L15 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L14 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L13 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L12 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
L11 OTHER SETUP DATA WARNING ALARM 7-06-23 12:45PM
SYSTEM PRINTER ERROR CLEAR 6-24-23 8:49AM
SYSTEM PAPER OUT CLEAR 6-24-23 8:49AM
SYSTEM PRINTER ERROR ALARM 6-24-23 8:44AM
SYSTEM PAPER OUT ALARM 6-24-23 8:44AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN CLEAR 6-17-23 10:00AM
h 3 OTHER FP3: BLEND3 DEGRD COLLECT WARN ALARM 6-12-23 10:02AM
T 1 TANK UNL DELIVERY NEEDED CLEAR 6-11-23 9:36PM
T 1 TANK UNL DELIVERY NEEDED ALARM 6-11-23 9:30PM
T 1 TANK UNL DELIVERY NEEDED CLEAR 6-03-23 10:14AM
T 1 TANK UNL INVALID FUEL LEVEL CLEAR 6-03-23 10:13AM
I20600
JUL 24, 2023 11:10 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
TANK ALARM HISTORY
TANK 1 UNL
OVERFILL ALARM JUL 21, 2023 6:35 AM
JUN 4, 2023 6:16 AM
MAY 31, 2023 10:50 AM
LOW PRODUCT ALARM JUL 16, 2023 6:12 AM
JUL 14, 2023 4:28 PM
JUL 7, 2023 5:02 PM
INVALID FUEL LEVEL JUL 16, 2023 9:19 AM
JUL 7, 2023 6:33 PM
JUN 3, 2023 7:13 AM
DELIVERY NEEDED JUL 16, 2023 6:12 AM
JUL 14, 2023 4:28 PM
JUL 7, 2023 5:02 PM
TANK 2 PREM
TANK 3 DSL
LOW PRODUCT ALARM FEB 13, 2021 8:05 AM
DELIVERY NEEDED FEB 13, 2021 8:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JUL 24, 2023 11:10 AM
I30200
JUL 24, 2023 11:11 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL STP
JUL 24, 2023 9:52 AM SENSOR OUT ALARM
JUL 24, 2023 9:36 AM FUEL ALARM
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
2 UNL ANN
JUL 24, 2023 9:52 AM SENSOR OUT ALARM
JUL 24, 2023 9:35 AM FUEL ALARM
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
3 PREM STP
JUL 24, 2023 9:52 AM SENSOR OUT ALARM
JUL 24, 2023 9:33 AM FUEL ALARM
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
4 PREM ANN
JUL 24, 2023 9:52 AM SENSOR OUT ALARM
JUL 24, 2023 9:34 AM FUEL ALARM
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
5 DSL STP
JUL 24, 2023 9:52 AM SENSOR OUT ALARM
JUL 24, 2023 9:32 AM FUEL ALARM
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
6 DSL ANN
JUL 24, 2023 9:52 AM SENSOR OUT ALARM
JUL 24, 2023 9:49 AM FUEL ALARM
JUL 22, 2023 11:44 PM FUEL ALARM
7 DISP 9-10
JUL 24, 2023 9:52 AM SENSOR OUT ALARM
JUL 24, 2023 9:39 AM FUEL ALARM
JUL 6, 2023 2:18 PM SENSOR OUT ALARM
8 DISP 11-12
JUL 24, 2023 9:52 AM SENSOR OUT ALARM
JUL 24, 2023 9:40 AM FUEL ALARM
JUL 24, 2023 8:53 AM FUEL ALARM
9 DISP 13-14
JUL 24, 2023 9:51 AM SENSOR OUT ALARM
JUL 24, 2023 9:38 AM FUEL ALARM
JUL 6, 2023 2:20 PM SENSOR OUT ALARM
10 DISP 15-16
JUL 24, 2023 9:51 AM SENSOR OUT ALARM
JUL 24, 2023 9:37 AM FUEL ALARM
JUL 6, 2023 2:20 PM SENSOR OUT ALARM
I31600
JUL 24, 2023 11:11 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VP 11-12
2 FM 9-10
3 FM 11-12
4 FM 13-14
5 FM 15-16
I40200
JUL 24, 2023 11:11 AM
I40300
JUL 24, 2023 11:11 AM
I34200
JUL 24, 2023 11:11 AM
I34700
JUL 24, 2023 11:11 AM
IV0100
JUL 24, 2023 11:11 AM
FASTRIP 7725
4901 S UNION
BAKERSFIELD CA
661-397-9387
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-06-16 10:02:04 A/L RATIO DEGRADATION FP 3 BLEND3 0.79
23-06-15 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.78
23-06-14 10:02:11 A/L RATIO DEGRADATION FP 3 BLEND3 0.77
23-06-13 10:02:26 A/L RATIO DEGRADATION FP 3 BLEND3 0.78
23-06-12 10:02:18 A/L RATIO DEGRADATION FP 3 BLEND3 0.79
22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
22-11-12 10:02:38 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-11-12 10:02:37 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-11-13 10:01:40 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-11-13 10:01:40 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-11-13 10:01:39 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
22-11-10 10:01:37 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-11-10 10:01:36 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-07-24 10:02:13 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-24 09:56:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-24 09:56:18 ISD STARTUP
23-07-24 09:56:12 ISD SHUTDOWN
23-07-14 10:01:51 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-13 17:43:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-07-13 17:43:30 ISD STARTUP
23-07-13 17:23:56 ISD SHUTDOWN
23-07-07 10:02:03 READINESS ISD:PP EVR:PP ISD & EVR READY
23-07-06 14:31:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING