HomeMy WebLinkAboutFMC 2023Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date
10026730 08/22/2023
FJM White Lane Gas, LLC
2601 White Lane Bakersfield 93304
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
VeederRoot TLS-3XX Technician - C32655 10/11/2024
Vaporless Manufacturing Inc. 10/21/2024
OPW - 1193585 04/14/2025
08/22/2023
Total # of Pages
6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS-350
334.01
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 91 Premium STP
L2 208 91 Premium Fill
L3 208 87 Unleaded STP
L4 208 87 Unleaded Fill
L5 208 Dispenser 1-2
L6 208 Dispenser 3-4
L7 208 Dispenser 5-6
L8 208 Dispenser 7-8
L9 420 87-91 ANN
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 Unleaded
T2 FX1V 91 Premium
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
8/22/2023
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& FJM White Lane Gas, LLC2601 White LaneBakersfield100267303-47-8MDPMPDMPDMPD1-25-6ProductProductProductProductBrandon Nunez
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10026730 08/22/2023
FJM White Lane Gas, LLC
2601 White Lane Bakersfield 93304
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
OPW - 1193585 04/14/2025
PEI 1200 1 Hour Hydrostatic All Spill Containers
08/22/2023 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1: 91 PNL
OPW
T2: 87 UNL
OPW
FJM MOBIL System Setup
Responses Received:
200
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
08-22-23 8:38 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 PREM 91 2086 35.03 0.0 84.5 5914
2 UNLEADED 87 3501 38.00 0.0 86.3 8499
I90500
08-22-23 8:38 AM
SOFTWARE REVISION LEVEL
VERSION 334.01
SOFTWARE# 346334-100-B
CREATED - 17.01.09.16.10
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
08-22-23 8:38 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MM-DD-YY HH:MM:SS xM
I50201
08-22-23 8:38 AM
SHIFT TIME 1 : 12:00 AM
I50202
08-22-23 8:38 AM
SHIFT TIME 2 : 12:05 AM
I50203
08-22-23 8:38 AM
SHIFT TIME 3 : DISABLED
I50204
08-22-23 8:38 AM
SHIFT TIME 4 : DISABLED
I54600
08-22-23 8:38 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
08-22-23 8:38 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
08-22-23 8:38 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
08-22-23 8:38 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
08-22-23 8:38 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
08-22-23 8:38 AM
PRINT TC VOLUMES
ENABLED
I50E00
08-22-23 8:38 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
08-22-23 8:38 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
08-22-23 8:38 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
08-22-23 8:38 AM
DAYLIGHT SAVING TIME
DISABLED
I51B00
08-22-23 8:38 AM
I51600
08-22-23 8:38 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
08-22-23 8:38 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
08-22-23 8:38 AM
TANK CHART SECURITY
DISABLED
I5BD00
08-22-23 8:38 AM
CUSTOM ALARM LABELS
DISABLED
I56000
08-22-23 8:38 AM
MASS/DENSITY
DISABLED
I88101
08-22-23 8:38 AM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88102
08-22-23 8:38 AM
PORT SETTINGS:
COMM BOARD : 2 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88103
08-22-23 8:38 AM
I88104
08-22-23 8:38 AM
I88105
08-22-23 8:38 AM
I88106
08-22-23 8:38 AM
I52000
08-22-23 8:38 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE AUG 21, 2017 DISABLED
2 ON DATE AUG 21, 2017 DISABLED
3 ON DATE AUG 21, 2017 DISABLED
4 ON DATE AUG 21, 2017 DISABLED
5 ON DATE AUG 21, 2017 DISABLED
6 ON DATE AUG 21, 2017 DISABLED
7 ON DATE AUG 21, 2017 DISABLED
8 ON DATE AUG 21, 2017 DISABLED
I60100
08-22-23 8:38 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 PREM 91 ON
2 UNLEADED 87 ON
3 OFF
4 OFF
I60200
08-22-23 8:38 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 PREM 91
2 UNLEADED 87
3
4
I60300
08-22-23 8:38 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 PREM 91 2
2 UNLEADED 87 1
3 3
4 4
I60900
08-22-23 8:38 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 PREM 91 0.000700
2 UNLEADED 87 0.000700
3 0.000000
4 0.000000
I60700
08-22-23 8:38 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 PREM 91 114.00
2 UNLEADED 87 114.00
3 0.00
4 0.00
I60A00
08-22-23 8:38 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 PREM 91 1 PT
8000 2 UNLEADED 87 1 PT 12000 3
1 PT 0 4 1 PT 0
I60400
08-22-23 8:38 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 PREM 91 8000
2 UNLEADED 87 12000
3 0
4 0
I60500
08-22-23 8:38 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 PREM 91 8000 0 0 0
2 UNLEADED 87 12000 0 0 0
3 0 0 0 0
4 0 0 0 0
I60600
08-22-23 8:38 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 PREM 91 8000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 UNLEADED 87 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
08-22-23 8:38 AM
TANK PRODUCT LABEL METER DATA
1 PREM 91 NO
2 UNLEADED 87 NO
3 NO
4 NO
I62F00
08-22-23 8:38 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 PREM 91 4.0 IN.
2 UNLEADED 87 4.0 IN.
I62700
08-22-23 8:38 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 PREM 91 2.0
2 UNLEADED 87 2.0
I64200
08-22-23 8:38 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 PREM 91 LOW
2 UNLEADED 87 LOW
I62400
08-22-23 8:38 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 PREM 91 2.5
2 UNLEADED 87 2.5
I62800
08-22-23 8:38 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 8000
2 UNLEADED 87 12000
3 0
4 0
I62300
08-22-23 8:38 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 7200
2 UNLEADED 87 10800
3 0
4 0
I62200
08-22-23 8:38 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 7600
2 UNLEADED 87 11400
3 0
4 0
I62900
08-22-23 8:38 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 2000
2 UNLEADED 87 2040
3 0
4 0
I62100
08-22-23 8:38 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 500
2 UNLEADED 87 600
3 0
4 0
I62600
08-22-23 8:38 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 99
2 UNLEADED 87 99
3 99
4 99
I62500
08-22-23 8:38 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 99
2 UNLEADED 87 99
3 99
4 99
I60800
08-22-23 8:38 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 PREM 91 0.00
2 UNLEADED 87 0.00
3 0.00
4 0.00
I60B00
08-22-23 8:38 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
08-22-23 8:38 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 PREM 91 0.00
2 UNLEADED 87 0.00
3 0.00
4 0.00
I61200
08-22-23 8:38 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 PREM 91 NONE NONE
2 UNLEADED 87 NONE NONE
3 NONE NONE
4 NONE NONE
I63600
08-22-23 8:38 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 PREM 91 0
2 UNLEADED 87 0
3 0
4 0
I62A00
08-22-23 8:38 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 PREM 91 0
2 UNLEADED 87 0
3 0
4 0
I62C00
08-22-23 8:38 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 PREM 91 STANDARD
2 UNLEADED 87 STANDARD
3 STANDARD
4 STANDARD
I62D00
08-22-23 8:38 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 PREM 91 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 UNLEADED 87 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
08-22-23 8:38 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 PREM 91 OFF OFF
2 UNLEADED 87 OFF OFF
3 OFF OFF
4 OFF OFF
I63000
08-22-23 8:38 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 PREM 91 OFF
2 UNLEADED 87 OFF
3 OFF
4 OFF
I63200
08-22-23 8:38 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 PREM 91 OFF
2 UNLEADED 87 OFF
3 OFF
4 OFF
I61000
08-22-23 8:38 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 PREM 91 1
2 UNLEADED 87 1
3 1
4 1
I63A00
08-22-23 8:38 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 PREM 91 10.00%
2 UNLEADED 87 10.00%
3 10.00%
4 10.00%
I61100
08-22-23 8:38 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
FEB 27, 2020
START TIME : 7:55 PM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
08-22-23 8:38 AM
CSLD PROBABLITY OF DETECTION
I61400
08-22-23 8:38 AM
CSLD CLIMATE FACTOR
I61600
08-22-23 8:38 AM
TANK PRODUCT LABEL CAL UPDATE
1 PREM 91 IMMEDIATE
2 UNLEADED 87 IMMEDIATE
3 IMMEDIATE
4 IMMEDIATE
I61A00
08-22-23 8:38 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 PREM 91 DISABLED
2 UNLEADED 87 DISABLED
3 DISABLED
4 DISABLED
I61B00
08-22-23 8:38 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
08-22-23 8:38 AM
CSLD REPORT ONLY
I62B00
08-22-23 8:38 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 PREM 91 00-00-00
2 UNLEADED 87 00-00-00
3 00-00-00
4 00-00-00
I63300
08-22-23 8:38 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
08-22-23 8:38 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 0
2 UNLEADED 87 0
3 0
4 0
I63500
08-22-23 8:38 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 PREM 91 1
2 UNLEADED 87 1
3 1
4 1
I63900
08-22-23 8:38 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 PREM 91
END FACTOR: NONE
2 UNLEADED 87
END FACTOR: NONE
3
END FACTOR: NONE
4
END FACTOR: NONE
I78000
08-22-23 8:38 AM
I77700
08-22-23 8:38 AM
I77800
08-22-23 8:38 AM
I78C00
08-22-23 8:38 AM
I78300
08-22-23 8:38 AM
I78F00
08-22-23 8:38 AM
I78700
08-22-23 8:38 AM
I70200
08-22-23 8:38 AM
LIQUID LABEL
DEVICE LABEL
1 91 STP
2 91 FILL SUMP
3 87 STP
4 87 FILL SUMP
5 UDC 1-2
6 UDC 3-4
7 UDC 5-6
8 UDC 7-8
9 ANNULAR 87-91
10
11
12
13
14
15
16
I70300
08-22-23 8:38 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 91 STP TRI-STATE (SINGLE FLOAT)
2 91 FILL SUMP TRI-STATE (SINGLE FLOAT)
3 87 STP TRI-STATE (SINGLE FLOAT)
4 87 FILL SUMP TRI-STATE (SINGLE FLOAT)
5 UDC 1-2 TRI-STATE (SINGLE FLOAT)
6 UDC 3-4 TRI-STATE (SINGLE FLOAT)
7 UDC 5-6 TRI-STATE (SINGLE FLOAT)
8 UDC 7-8 TRI-STATE (SINGLE FLOAT)
9 ANNULAR 87-91 TRI-STATE (SINGLE FLOAT)
10 TRI-STATE (SINGLE FLOAT)
11 TRI-STATE (SINGLE FLOAT)
12 TRI-STATE (SINGLE FLOAT)
13 TRI-STATE (SINGLE FLOAT)
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
08-22-23 8:38 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 91 STP STP SUMP
2 91 FILL SUMP PIPING SUMP
3 87 STP STP SUMP
4 87 FILL SUMP PIPING SUMP
5 UDC 1-2 DISPENSER PAN
6 UDC 3-4 DISPENSER PAN
7 UDC 5-6 DISPENSER PAN
8 UDC 7-8 DISPENSER PAN
9 ANNULAR 87-91 ANNULAR SPACE
10 OTHER SENSORS
11 OTHER SENSORS
12 OTHER SENSORS
13 OTHER SENSORS
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
08-22-23 8:38 AM
I74300
08-22-23 8:38 AM
I74400
08-22-23 8:38 AM
I74700
08-22-23 8:38 AM
I74800
08-22-23 8:39 AM
I74900
08-22-23 8:39 AM
I7BC00
08-22-23 8:39 AM
I80200
08-22-23 8:39 AM
I80300
08-22-23 8:39 AM
I80400
08-22-23 8:39 AM
I80700
08-22-23 8:39 AM
RELAY LABEL
DEVICE LABEL
1 87 UNLEADED
2 PREM 91
3
4
I80900
08-22-23 8:39 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 87 UNLEADED NORMALLY CLOSED
2 PREM 91 NORMALLY CLOSED
3 NORMALLY OPEN
4 NORMALLY OPEN
I80B00
08-22-23 8:39 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 87 UNLEADED 2
2 PREM 91 1
3 NONE
4 NONE
I80A00
08-22-23 8:39 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 87 UNLEADED STANDARD
2 PREM 91 STANDARD
3 STANDARD
4 STANDARD
I80C00
08-22-23 8:39 AM
I80800
08-22-23 8:39 AM
RELAY SETUP REPORT
R 1:87 UNLEADED
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
IN-TANK ALARMS
T 2:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:PREM 91
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
IN-TANK ALARMS
T 1:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 1:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
PMC ALARMS
VP EMISSIONS FAIL
R 3:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
08-22-23 8:39 AM
EDIM:1 VR:349867-001-D TD:17.02.14.08.38
I79100
08-22-23 8:39 AM
I72300
08-22-23 8:39 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VAPOR PRESSURE VAPOR PRESSURE
02 FLOW METER 1-2 AIR FLOW METER
03 FLOW METER 3-4 AIR FLOW METER
04 FLOW METER 5-6 AIR FLOW METER
05 FLOW METER 7-8 AIR FLOW METER
06 VP UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
08-22-23 8:39 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
08-22-23 8:39 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
08-22-23 8:39 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
VAPOR PROCESSOR TYPE
NONE
IV4700
08-22-23 8:39 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
08-22-23 8:39 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
ACCEPT HIGH ORVR: YES
IV4A00
08-22-23 8:39 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 02 BLEND3
02 02 02 01 02 BLEND3
03 03 03 02 02 BLEND3
04 04 04 02 02 BLEND3
05 05 05 03 02 BLEND3
06 06 06 03 02 BLEND3
07 07 07 04 02 BLEND3
08 08 08 04 02 BLEND3
IV4B00
08-22-23 8:39 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 01/01 09/01 xx/xx
02 01 02/02 01/02 09/02 xx/xx
03 02 02/03 01/03 09/03 xx/xx
04 02 02/04 01/04 09/04 xx/xx
05 03 02/05 01/05 09/05 xx/xx
06 03 02/06 01/06 09/06 xx/xx
07 04 02/07 01/07 09/07 xx/xx
08 04 02/08 01/08 09/08 xx/xx
IV4900
08-22-23 8:39 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
08-22-23 8:39 AM
ISD VERSION: 01.05
FJM MOBIL Pre Alarm History
Responses Received:
I10200
08-22-23 8:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164738 163898
2 INTERSTITIAL BD 202007 201438
3 INTERSTITIAL BD 202007 201416
4 7SMARTSENSOR BD 507999 506036
5 UNUSED 9903073 9750733
6 UNUSED 9868832 9726376
7 UNUSED 9858988 9721638
8 UNUSED 9856420 9716318
9 RELAY BOARD 14987 14952
10 UNUSED 9859521 9727585
11 UNUSED 9850410 9713765
12 UNUSED 9848494 9712394
13 UNUSED 9844907 9710648
14 UNUSED 9838935 9710440
15 UNUSED 9845213 9707073
16 UNUSED 9841504 9704642
COMM 1 RS232 SERIAL BD 14946 14931
COMM 2 ELEC DISP INT. 101209 101007
COMM 3 UNUSED 9847618 9721995
COMM 4 UNUSED 9841748 9707863
COMM 5 UNUSED 9837448 9703894
COMM 6 UNUSED 9840158 9707323
I90200
08-22-23 8:40 AM
SOFTWARE REVISION LEVEL
VERSION 334.01
SOFTWARE# 346334-100-B
CREATED - 17.01.09.16.10
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
08-22-23 8:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
E 1 OTHER COMMUNICATION ALARM CLEAR 08-16-23 8:14 PM
E 1 OTHER COMMUNICATION ALARM ALARM 08-16-23 8:12 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 08-13-23 9:40 AM
E 1 OTHER COMMUNICATION ALARM ALARM 08-13-23 9:40 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 08-13-23 9:40 AM
E 1 OTHER COMMUNICATION ALARM ALARM 08-13-23 9:40 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 08-04-23 10:01 PM
E 1 OTHER COMMUNICATION ALARM ALARM 08-04-23 9:56 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 08-04-23 11:38 AM
E 1 OTHER COMMUNICATION ALARM ALARM 08-04-23 11:37 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 07-21-23 12:19 PM
E 1 OTHER COMMUNICATION ALARM ALARM 07-21-23 12:19 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 07-21-23 12:19 PM
E 1 OTHER COMMUNICATION ALARM ALARM 07-21-23 12:19 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 06-27-23 1:13 PM
E 1 OTHER COMMUNICATION ALARM ALARM 06-27-23 1:06 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 06-23-23 12:55 PM
E 1 OTHER COMMUNICATION ALARM ALARM 06-23-23 12:53 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 06-23-23 12:31 PM
E 1 OTHER COMMUNICATION ALARM ALARM 06-23-23 12:31 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 06-23-23 12:29 PM
E 1 OTHER COMMUNICATION ALARM ALARM 06-23-23 12:13 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 05-19-23 12:12 PM
E 1 OTHER COMMUNICATION ALARM ALARM 05-19-23 12:10 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 04-03-23 2:12 AM
E 1 OTHER COMMUNICATION ALARM ALARM 04-03-23 2:12 AM
L 1 STP SUMP 91 STP FUEL ALARM CLEAR 03-03-23 3:44 PM
L 1 STP SUMP 91 STP FUEL ALARM ALARM 03-03-23 3:41 PM
L 1 STP SUMP 91 STP FUEL ALARM CLEAR 03-03-23 2:41 PM
L 1 STP SUMP 91 STP FUEL ALARM ALARM 03-03-23 2:41 PM
L 4 PIPE 87 FILL SUMP FUEL ALARM CLEAR 03-03-23 2:23 PM
L 4 PIPE 87 FILL SUMP FUEL ALARM ALARM 03-03-23 10:18 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 01-30-23 3:18 AM
E 1 OTHER COMMUNICATION ALARM ALARM 01-30-23 3:18 AM
L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM
L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM
L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM
L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM
L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM
L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM
L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM
L 1 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM
L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM
L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM ALARM 10-03-22 9:46 AM
L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM
L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM
L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM
L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM
L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM
L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM
I11200
08-22-23 8:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
OTHER ISD GROSS PRES WARN ALARM 08-17-23 10:07 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 08-15-23 10:07 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-15-23 10:01 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 08-14-23 12:55 PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-13-23 10:47 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 08-06-23 7:58 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-06-23 7:50 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 08-05-23 11:37 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-03-23 7:04 PM
OTHER ISD VAPOR LEAK WARN CLEAR 08-01-23 10:05 AM
h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN CLEAR 08-01-23 10:00 AM
h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN ALARM 07-31-23 10:08 AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-29-23 10:00 AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-28-23 10:07 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-27-23 12:17 PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 07-27-23 12:13 PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 07-27-23 11:40 AM
OTHER ISD VAPOR LEAK WARN ALARM 07-27-23 10:07 AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-24-23 10:00 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-23-23 10:40 AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-23-23 10:06 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-18-23 7:57 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 07-18-23 7:53 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 07-17-23 5:18 PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-14-23 12:14 PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-08-23 7:44 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-04-23 10:35 PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-29-23 6:21 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-26-23 1:19 PM
OTHER ISD VAPOR LEAK WARN CLEAR 06-23-23 11:45 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-21-23 8:10 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-21-23 8:07 AM
OTHER ISD VAPOR LEAK WARN ALARM 06-20-23 10:04 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 06-20-23 7:50 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-18-23 12:32 PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-11-23 7:47 PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-11-23 7:37 PM
SYSTEM PRINTER ERROR CLEAR 06-10-23 8:09 PM
SYSTEM PAPER OUT CLEAR 06-10-23 8:09 PM
SYSTEM PRINTER ERROR ALARM 06-10-23 8:08 PM
SYSTEM PAPER OUT ALARM 06-10-23 8:08 PM
SYSTEM SOFTWARE MODULE WARN CLEAR 06-10-23 7:40 PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 06-09-23 5:30 PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-08-23 9:13 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-01-23 7:02 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-01-23 7:01 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 05-31-23 9:02 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 05-29-23 1:01 PM
OTHER ISD VAPOR LEAK WARN CLEAR 05-26-23 10:44 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 05-23-23 12:01 PM
I20600
08-22-23 8:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
TANK ALARM HISTORY
TANK 1 PREM 91
DELIVERY NEEDED 08-13-23 10:47 AM
08-03-23 7:04 PM
07-23-23 10:40 AM
PER TST NEEDED ALM 12-23-19 12:00 AM
ANN TST NEEDED ALM 12-23-19 12:00 AM
TANK 2 UNLEADED 87
OVERFILL ALARM 04-07-22 5:47 AM
03-30-22 6:00 AM
01-13-22 11:28 PM
LOW PRODUCT ALARM 07-11-20 12:04 PM
05-18-19 7:09 AM
01-14-19 5:41 PM
HIGH PRODUCT ALARM 04-07-22 5:49 AM
06-09-20 5:58 AM
03-23-20 4:17 AM
DELIVERY NEEDED 08-14-23 12:55 PM
08-05-23 11:37 AM
07-27-23 11:40 AM
PER TST NEEDED ALM 12-23-19 12:00 AM
ANN TST NEEDED ALM 12-23-19 12:00 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
08-22-23 8:40 AM
I30200
08-22-23 8:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 91 STP
03-03-23 3:41 PM FUEL ALARM
03-03-23 2:41 PM FUEL ALARM
10-03-22 9:45 AM SENSOR OUT ALARM
2 91 FILL SUMP
10-03-22 9:45 AM SENSOR OUT ALARM
10-03-22 9:35 AM FUEL ALARM
08-11-21 11:15 AM FUEL ALARM
3 87 STP
10-03-22 9:45 AM SENSOR OUT ALARM
10-03-22 9:34 AM FUEL ALARM
10-03-22 9:31 AM SENSOR OUT ALARM
4 87 FILL SUMP
03-03-23 10:18 AM FUEL ALARM
10-03-22 9:45 AM SENSOR OUT ALARM
10-03-22 9:36 AM FUEL ALARM
5 UDC 1-2
10-03-22 9:45 AM SENSOR OUT ALARM
10-03-22 9:39 AM FUEL ALARM
08-11-21 9:28 AM SENSOR OUT ALARM
6 UDC 3-4
10-03-22 9:45 AM SENSOR OUT ALARM
10-03-22 9:40 AM FUEL ALARM
08-11-21 9:28 AM SENSOR OUT ALARM
7 UDC 5-6
10-03-22 9:45 AM SENSOR OUT ALARM
10-03-22 9:39 AM FUEL ALARM
08-11-21 9:28 AM SENSOR OUT ALARM
8 UDC 7-8
10-03-22 9:45 AM SENSOR OUT ALARM
10-03-22 9:38 AM FUEL ALARM
08-11-21 9:28 AM SENSOR OUT ALARM
9 ANNULAR 87-91
10-03-22 9:46 AM SENSOR OUT ALARM
10-03-22 9:37 AM FUEL ALARM
10-03-22 9:37 AM FUEL ALARM
I31600
08-22-23 8:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VAPOR PRESSURE
01-29-20 12:19 PM COMMUNICATION ALARM
12-22-17 10:25 AM COMMUNICATION ALARM
12-22-17 9:52 AM COMMUNICATION ALARM
2 FLOW METER 1-2
12-22-17 10:00 AM COMMUNICATION ALARM
3 FLOW METER 3-4
12-22-17 10:00 AM COMMUNICATION ALARM
08-21-17 2:18 PM COMMUNICATION ALARM
4 FLOW METER 5-6
12-03-20 8:21 AM COMMUNICATION ALARM
12-22-17 10:00 AM COMMUNICATION ALARM
08-22-17 10:48 AM COMMUNICATION ALARM
5 FLOW METER 7-8
12-22-17 10:00 AM COMMUNICATION ALARM
08-21-17 2:18 PM COMMUNICATION ALARM
I40200
08-22-23 8:40 AM
I40300
08-22-23 8:40 AM
I34200
08-22-23 8:40 AM
I34700
08-22-23 8:40 AM
IV0100
08-22-23 8:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :WARN
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-08-21 10:03:16 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-08-20 10:03:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-08-19 10:04:52 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-08-18 10:05:58 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-08-17 10:07:33 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-07-31 10:08:32 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 26.24
23-07-31 10:08:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 0.58
23-07-30 10:07:21 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.44
23-07-29 10:07:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.88
23-07-28 10:07:54 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.33
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-08-09 10:07:29 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3
22-07-25 10:07:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
22-05-06 10:06:28 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3
21-07-14 10:01:12 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
21-07-13 10:01:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
21-07-12 10:06:23 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
21-07-03 10:06:30 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3
18-08-07 10:08:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3
18-06-12 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
18-06-11 10:06:56 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-08-21 10:03:16 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-20 10:03:45 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-19 10:04:52 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-18 10:05:58 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-17 10:07:33 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-16 20:10:51 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-08-16 20:10:51 ISD STARTUP
23-08-16 19:14:39 ISD SHUTDOWN
23-06-28 10:11:21 READINESS ISD:PP EVR:PP ISD & EVR READY
23-06-27 13:04:24 READINESS ISD:PP EVR:NN EVR READINESS PENDING
Post Alarm History
Responses Received:
I10200
08-22-23 10:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164738 163279
2 INTERSTITIAL BD 202007 200827
3 INTERSTITIAL BD 202007 200783
4 7SMARTSENSOR BD 507999 504253
5 UNUSED 9903073 9680454
6 UNUSED 9868832 9660350
7 UNUSED 9858988 9671242
8 UNUSED 9856420 9687240
9 RELAY BOARD 14987 14978
10 UNUSED 9859521 9668009
11 UNUSED 9850410 9672307
12 UNUSED 9848494 9688496
13 UNUSED 9844907 9680838
14 UNUSED 9838935 9663435
15 UNUSED 9845213 9660010
16 UNUSED 9841504 9672477
COMM 1 RS232 SERIAL BD 14946 14957
COMM 2 ELEC DISP INT. 101209 100989
COMM 3 UNUSED 9847618 9684922
COMM 4 UNUSED 9841748 9687262
COMM 5 UNUSED 9837448 9674051
COMM 6 UNUSED 9840158 9657798
I90200
08-22-23 10:40 AM
SOFTWARE REVISION LEVEL
VERSION 334.01
SOFTWARE# 346334-100-B
CREATED - 17.01.09.16.10
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
08-22-23 10:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM
L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM
L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM
L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM
L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM
L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM
L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM
L 1 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM
L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM
L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM
L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM
L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM ALARM 08-22-23 9:14 AM
L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 08-22-23 9:14 AM
L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM ALARM 08-22-23 9:14 AM
L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM
L 1 STP SUMP 91 STP SENSOR OUT ALARM ALARM 08-22-23 9:14 AM
L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM
L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM
L 8 DISP PAN UDC 7-8 FUEL ALARM CLEAR 08-22-23 9:11 AM
L 8 DISP PAN UDC 7-8 FUEL ALARM ALARM 08-22-23 9:11 AM
L 7 DISP PAN UDC 5-6 FUEL ALARM CLEAR 08-22-23 9:10 AM
L 7 DISP PAN UDC 5-6 FUEL ALARM ALARM 08-22-23 9:10 AM
L 5 DISP PAN UDC 1-2 FUEL ALARM CLEAR 08-22-23 9:09 AM
L 5 DISP PAN UDC 1-2 FUEL ALARM ALARM 08-22-23 9:09 AM
L 6 DISP PAN UDC 3-4 FUEL ALARM CLEAR 08-22-23 9:08 AM
L 6 DISP PAN UDC 3-4 FUEL ALARM ALARM 08-22-23 9:07 AM
L 9 ANNULAR ANNULAR 87-91 FUEL ALARM CLEAR 08-22-23 9:06 AM
L 9 ANNULAR ANNULAR 87-91 FUEL ALARM ALARM 08-22-23 9:06 AM
L 4 PIPE 87 FILL SUMP FUEL ALARM CLEAR 08-22-23 9:06 AM
L 4 PIPE 87 FILL SUMP FUEL ALARM ALARM 08-22-23 9:06 AM
L 3 STP SUMP 87 STP FUEL ALARM CLEAR 08-22-23 9:05 AM
L 3 STP SUMP 87 STP FUEL ALARM ALARM 08-22-23 9:04 AM
L 2 PIPE 91 FILL SUMP FUEL ALARM CLEAR 08-22-23 9:04 AM
L 2 PIPE 91 FILL SUMP FUEL ALARM ALARM 08-22-23 9:04 AM
L 1 STP SUMP 91 STP FUEL ALARM CLEAR 08-22-23 9:02 AM
L 1 STP SUMP 91 STP FUEL ALARM ALARM 08-22-23 9:02 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 08-16-23 8:14 PM
E 1 OTHER COMMUNICATION ALARM ALARM 08-16-23 8:12 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 08-13-23 9:40 AM
E 1 OTHER COMMUNICATION ALARM ALARM 08-13-23 9:40 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 08-13-23 9:40 AM
E 1 OTHER COMMUNICATION ALARM ALARM 08-13-23 9:40 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 08-04-23 10:01 PM
E 1 OTHER COMMUNICATION ALARM ALARM 08-04-23 9:56 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 08-04-23 11:38 AM
E 1 OTHER COMMUNICATION ALARM ALARM 08-04-23 11:37 AM
E 1 OTHER COMMUNICATION ALARM CLEAR 07-21-23 12:19 PM
E 1 OTHER COMMUNICATION ALARM ALARM 07-21-23 12:19 PM
E 1 OTHER COMMUNICATION ALARM CLEAR 07-21-23 12:19 PM
E 1 OTHER COMMUNICATION ALARM ALARM 07-21-23 12:19 PM
I11200
08-22-23 10:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
OTHER ISD GROSS PRES WARN ALARM 08-17-23 10:07 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 08-15-23 10:07 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-15-23 10:01 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 08-14-23 12:55 PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-13-23 10:47 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 08-06-23 7:58 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-06-23 7:50 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 08-05-23 11:37 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-03-23 7:04 PM
OTHER ISD VAPOR LEAK WARN CLEAR 08-01-23 10:05 AM
h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN CLEAR 08-01-23 10:00 AM
h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN ALARM 07-31-23 10:08 AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-29-23 10:00 AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-28-23 10:07 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-27-23 12:17 PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 07-27-23 12:13 PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 07-27-23 11:40 AM
OTHER ISD VAPOR LEAK WARN ALARM 07-27-23 10:07 AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-24-23 10:00 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-23-23 10:40 AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-23-23 10:06 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-18-23 7:57 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 07-18-23 7:53 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 07-17-23 5:18 PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-14-23 12:14 PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-08-23 7:44 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-04-23 10:35 PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-29-23 6:21 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-26-23 1:19 PM
OTHER ISD VAPOR LEAK WARN CLEAR 06-23-23 11:45 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-21-23 8:10 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-21-23 8:07 AM
OTHER ISD VAPOR LEAK WARN ALARM 06-20-23 10:04 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 06-20-23 7:50 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-18-23 12:32 PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-11-23 7:47 PM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-11-23 7:37 PM
SYSTEM PRINTER ERROR CLEAR 06-10-23 8:09 PM
SYSTEM PAPER OUT CLEAR 06-10-23 8:09 PM
SYSTEM PRINTER ERROR ALARM 06-10-23 8:08 PM
SYSTEM PAPER OUT ALARM 06-10-23 8:08 PM
SYSTEM SOFTWARE MODULE WARN CLEAR 06-10-23 7:40 PM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 06-09-23 5:30 PM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-08-23 9:13 AM
T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-01-23 7:02 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-01-23 7:01 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 05-31-23 9:02 AM
T 1 TANK PREM 91 DELIVERY NEEDED ALARM 05-29-23 1:01 PM
OTHER ISD VAPOR LEAK WARN CLEAR 05-26-23 10:44 AM
T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 05-23-23 12:01 PM
I20600
08-22-23 10:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
TANK ALARM HISTORY
TANK 1 PREM 91
DELIVERY NEEDED 08-13-23 10:47 AM
08-03-23 7:04 PM
07-23-23 10:40 AM
PER TST NEEDED ALM 12-23-19 12:00 AM
ANN TST NEEDED ALM 12-23-19 12:00 AM
TANK 2 UNLEADED 87
OVERFILL ALARM 04-07-22 5:47 AM
03-30-22 6:00 AM
01-13-22 11:28 PM
LOW PRODUCT ALARM 07-11-20 12:04 PM
05-18-19 7:09 AM
01-14-19 5:41 PM
HIGH PRODUCT ALARM 04-07-22 5:49 AM
06-09-20 5:58 AM
03-23-20 4:17 AM
DELIVERY NEEDED 08-14-23 12:55 PM
08-05-23 11:37 AM
07-27-23 11:40 AM
PER TST NEEDED ALM 12-23-19 12:00 AM
ANN TST NEEDED ALM 12-23-19 12:00 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
08-22-23 10:40 AM
I30200
08-22-23 10:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 91 STP
08-22-23 9:14 AM SENSOR OUT ALARM
08-22-23 9:02 AM FUEL ALARM
03-03-23 3:41 PM FUEL ALARM
2 91 FILL SUMP
08-22-23 9:14 AM SENSOR OUT ALARM
08-22-23 9:04 AM FUEL ALARM
10-03-22 9:45 AM SENSOR OUT ALARM
3 87 STP
08-22-23 9:14 AM SENSOR OUT ALARM
08-22-23 9:04 AM FUEL ALARM
10-03-22 9:45 AM SENSOR OUT ALARM
4 87 FILL SUMP
08-22-23 9:14 AM SENSOR OUT ALARM
08-22-23 9:06 AM FUEL ALARM
03-03-23 10:18 AM FUEL ALARM
5 UDC 1-2
08-22-23 9:14 AM SENSOR OUT ALARM
08-22-23 9:09 AM FUEL ALARM
10-03-22 9:45 AM SENSOR OUT ALARM
6 UDC 3-4
08-22-23 9:14 AM SENSOR OUT ALARM
08-22-23 9:07 AM FUEL ALARM
10-03-22 9:45 AM SENSOR OUT ALARM
7 UDC 5-6
08-22-23 9:14 AM SENSOR OUT ALARM
08-22-23 9:10 AM FUEL ALARM
10-03-22 9:45 AM SENSOR OUT ALARM
8 UDC 7-8
08-22-23 9:14 AM SENSOR OUT ALARM
08-22-23 9:11 AM FUEL ALARM
10-03-22 9:45 AM SENSOR OUT ALARM
9 ANNULAR 87-91
08-22-23 9:14 AM SENSOR OUT ALARM
08-22-23 9:06 AM FUEL ALARM
10-03-22 9:46 AM SENSOR OUT ALARM
I31600
08-22-23 10:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VAPOR PRESSURE
01-29-20 12:19 PM COMMUNICATION ALARM
12-22-17 10:25 AM COMMUNICATION ALARM
12-22-17 9:52 AM COMMUNICATION ALARM
2 FLOW METER 1-2
12-22-17 10:00 AM COMMUNICATION ALARM
3 FLOW METER 3-4
12-22-17 10:00 AM COMMUNICATION ALARM
08-21-17 2:18 PM COMMUNICATION ALARM
4 FLOW METER 5-6
12-03-20 8:21 AM COMMUNICATION ALARM
12-22-17 10:00 AM COMMUNICATION ALARM
08-22-17 10:48 AM COMMUNICATION ALARM
5 FLOW METER 7-8
12-22-17 10:00 AM COMMUNICATION ALARM
08-21-17 2:18 PM COMMUNICATION ALARM
I40200
08-22-23 10:40 AM
I40300
08-22-23 10:40 AM
I34200
08-22-23 10:40 AM
I34700
08-22-23 10:40 AM
IV0100
08-22-23 10:40 AM
MOBIL
2601 WHITE LANE
BAKERSFIELD CA
16613971520
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :WARN
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-08-22 10:02:21 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-08-21 10:03:16 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-08-20 10:03:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-08-19 10:04:52 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-08-18 10:05:58 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-08-17 10:07:33 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00
23-07-31 10:08:32 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 26.24
23-07-31 10:08:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 0.58
23-07-30 10:07:21 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.44
23-07-29 10:07:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.88
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
22-08-09 10:07:29 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3
22-07-25 10:07:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
22-05-06 10:06:28 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3
21-07-14 10:01:12 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
21-07-13 10:01:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
21-07-12 10:06:23 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
21-07-03 10:06:30 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3
18-08-07 10:08:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3
18-06-12 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
18-06-11 10:06:56 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-08-22 10:02:21 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-22 09:15:26 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-08-22 09:15:26 ISD STARTUP
23-08-22 09:15:18 ISD SHUTDOWN
23-08-21 10:03:16 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-20 10:03:45 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-19 10:04:52 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-18 10:05:58 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-17 10:07:33 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM
23-08-16 20:10:51 READINESS ISD:PP EVR:NN EVR READINESS PENDING