HomeMy WebLinkAboutFMC 2023Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date 10026730 08/22/2023 FJM White Lane Gas, LLC 2601 White Lane Bakersfield 93304 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Brandon Nunez 1073967 10226373 09/06/2024 VeederRoot TLS-3XX Technician - C32655 10/11/2024 Vaporless Manufacturing Inc. 10/21/2024 OPW - 1193585 04/14/2025 08/22/2023 Total # of Pages 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 VeederRoot TLS-350 334.01 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 91 Premium STP L2 208 91 Premium Fill L3 208 87 Unleaded STP L4 208 87 Unleaded Fill L5 208 Dispenser 1-2 L6 208 Dispenser 3-4 L7 208 Dispenser 5-6 L8 208 Dispenser 7-8 L9 420 87-91 ANN Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V 87 Unleaded T2 FX1V 91 Premium Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. 8/22/2023 APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  FJM White Lane Gas, LLC2601 White LaneBakersfield100267303-47-8MDPMPDMPDMPD1-25-6ProductProductProductProductBrandon Nunez Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10026730 08/22/2023 FJM White Lane Gas, LLC 2601 White Lane Bakersfield 93304 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Brandon Nunez 1073967 10226373 09/06/2024 OPW - 1193585 04/14/2025 PEI 1200 1 Hour Hydrostatic All Spill Containers 08/22/2023 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1: 91 PNL OPW T2: 87 UNL OPW FJM MOBIL System Setup Responses Received: 200 MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 08-22-23 8:38 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 PREM 91 2086 35.03 0.0 84.5 5914 2 UNLEADED 87 3501 38.00 0.0 86.3 8499 I90500 08-22-23 8:38 AM SOFTWARE REVISION LEVEL VERSION 334.01 SOFTWARE# 346334-100-B CREATED - 17.01.09.16.10 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 08-22-23 8:38 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MM-DD-YY HH:MM:SS xM I50201 08-22-23 8:38 AM SHIFT TIME 1 : 12:00 AM I50202 08-22-23 8:38 AM SHIFT TIME 2 : 12:05 AM I50203 08-22-23 8:38 AM SHIFT TIME 3 : DISABLED I50204 08-22-23 8:38 AM SHIFT TIME 4 : DISABLED I54600 08-22-23 8:38 AM TANK PER TST NEEDED WRN: DISABLED I54900 08-22-23 8:38 AM TANK ANN TST NEEDED WRN: DISABLED I55300 08-22-23 8:38 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 08-22-23 8:38 AM LINE PER TST NEEDED WRN: DISABLED I55900 08-22-23 8:38 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 08-22-23 8:38 AM PRINT TC VOLUMES ENABLED I50E00 08-22-23 8:38 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 08-22-23 8:38 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 08-22-23 8:38 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 08-22-23 8:38 AM DAYLIGHT SAVING TIME DISABLED I51B00 08-22-23 8:38 AM I51600 08-22-23 8:38 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 08-22-23 8:38 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 08-22-23 8:38 AM TANK CHART SECURITY DISABLED I5BD00 08-22-23 8:38 AM CUSTOM ALARM LABELS DISABLED I56000 08-22-23 8:38 AM MASS/DENSITY DISABLED I88101 08-22-23 8:38 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88102 08-22-23 8:38 AM PORT SETTINGS: COMM BOARD : 2 (EDIM ) RS-232 SECURITY CODE : DISABLED I88103 08-22-23 8:38 AM I88104 08-22-23 8:38 AM I88105 08-22-23 8:38 AM I88106 08-22-23 8:38 AM I52000 08-22-23 8:38 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE AUG 21, 2017 DISABLED 2 ON DATE AUG 21, 2017 DISABLED 3 ON DATE AUG 21, 2017 DISABLED 4 ON DATE AUG 21, 2017 DISABLED 5 ON DATE AUG 21, 2017 DISABLED 6 ON DATE AUG 21, 2017 DISABLED 7 ON DATE AUG 21, 2017 DISABLED 8 ON DATE AUG 21, 2017 DISABLED I60100 08-22-23 8:38 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 PREM 91 ON 2 UNLEADED 87 ON 3 OFF 4 OFF I60200 08-22-23 8:38 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 PREM 91 2 UNLEADED 87 3 4 I60300 08-22-23 8:38 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 PREM 91 2 2 UNLEADED 87 1 3 3 4 4 I60900 08-22-23 8:38 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 PREM 91 0.000700 2 UNLEADED 87 0.000700 3 0.000000 4 0.000000 I60700 08-22-23 8:38 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 PREM 91 114.00 2 UNLEADED 87 114.00 3 0.00 4 0.00 I60A00 08-22-23 8:38 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 PREM 91 1 PT 8000 2 UNLEADED 87 1 PT 12000 3 1 PT 0 4 1 PT 0 I60400 08-22-23 8:38 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 PREM 91 8000 2 UNLEADED 87 12000 3 0 4 0 I60500 08-22-23 8:38 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 PREM 91 8000 0 0 0 2 UNLEADED 87 12000 0 0 0 3 0 0 0 0 4 0 0 0 0 I60600 08-22-23 8:38 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 PREM 91 8000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 UNLEADED 87 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 08-22-23 8:38 AM TANK PRODUCT LABEL METER DATA 1 PREM 91 NO 2 UNLEADED 87 NO 3 NO 4 NO I62F00 08-22-23 8:38 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 PREM 91 4.0 IN. 2 UNLEADED 87 4.0 IN. I62700 08-22-23 8:38 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 PREM 91 2.0 2 UNLEADED 87 2.0 I64200 08-22-23 8:38 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 PREM 91 LOW 2 UNLEADED 87 LOW I62400 08-22-23 8:38 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 PREM 91 2.5 2 UNLEADED 87 2.5 I62800 08-22-23 8:38 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 8000 2 UNLEADED 87 12000 3 0 4 0 I62300 08-22-23 8:38 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 7200 2 UNLEADED 87 10800 3 0 4 0 I62200 08-22-23 8:38 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 7600 2 UNLEADED 87 11400 3 0 4 0 I62900 08-22-23 8:38 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 2000 2 UNLEADED 87 2040 3 0 4 0 I62100 08-22-23 8:38 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 500 2 UNLEADED 87 600 3 0 4 0 I62600 08-22-23 8:38 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 99 2 UNLEADED 87 99 3 99 4 99 I62500 08-22-23 8:38 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 99 2 UNLEADED 87 99 3 99 4 99 I60800 08-22-23 8:38 AM TANK TILT TANK PRODUCT LABEL INCHES 1 PREM 91 0.00 2 UNLEADED 87 0.00 3 0.00 4 0.00 I60B00 08-22-23 8:38 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 08-22-23 8:38 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 PREM 91 0.00 2 UNLEADED 87 0.00 3 0.00 4 0.00 I61200 08-22-23 8:38 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 PREM 91 NONE NONE 2 UNLEADED 87 NONE NONE 3 NONE NONE 4 NONE NONE I63600 08-22-23 8:38 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 PREM 91 0 2 UNLEADED 87 0 3 0 4 0 I62A00 08-22-23 8:38 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 PREM 91 0 2 UNLEADED 87 0 3 0 4 0 I62C00 08-22-23 8:38 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 PREM 91 STANDARD 2 UNLEADED 87 STANDARD 3 STANDARD 4 STANDARD I62D00 08-22-23 8:38 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 PREM 91 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 UNLEADED 87 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 08-22-23 8:38 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 PREM 91 OFF OFF 2 UNLEADED 87 OFF OFF 3 OFF OFF 4 OFF OFF I63000 08-22-23 8:38 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 PREM 91 OFF 2 UNLEADED 87 OFF 3 OFF 4 OFF I63200 08-22-23 8:38 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 PREM 91 OFF 2 UNLEADED 87 OFF 3 OFF 4 OFF I61000 08-22-23 8:38 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 PREM 91 1 2 UNLEADED 87 1 3 1 4 1 I63A00 08-22-23 8:38 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 PREM 91 10.00% 2 UNLEADED 87 10.00% 3 10.00% 4 10.00% I61100 08-22-23 8:38 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK FEB 27, 2020 START TIME : 7:55 PM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 08-22-23 8:38 AM CSLD PROBABLITY OF DETECTION I61400 08-22-23 8:38 AM CSLD CLIMATE FACTOR I61600 08-22-23 8:38 AM TANK PRODUCT LABEL CAL UPDATE 1 PREM 91 IMMEDIATE 2 UNLEADED 87 IMMEDIATE 3 IMMEDIATE 4 IMMEDIATE I61A00 08-22-23 8:38 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 PREM 91 DISABLED 2 UNLEADED 87 DISABLED 3 DISABLED 4 DISABLED I61B00 08-22-23 8:38 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 08-22-23 8:38 AM CSLD REPORT ONLY I62B00 08-22-23 8:38 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 PREM 91 00-00-00 2 UNLEADED 87 00-00-00 3 00-00-00 4 00-00-00 I63300 08-22-23 8:38 AM LEAK TEST REPORT FORMAT: NORMAL I63400 08-22-23 8:38 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 0 2 UNLEADED 87 0 3 0 4 0 I63500 08-22-23 8:38 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 PREM 91 1 2 UNLEADED 87 1 3 1 4 1 I63900 08-22-23 8:38 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 PREM 91 END FACTOR: NONE 2 UNLEADED 87 END FACTOR: NONE 3 END FACTOR: NONE 4 END FACTOR: NONE I78000 08-22-23 8:38 AM I77700 08-22-23 8:38 AM I77800 08-22-23 8:38 AM I78C00 08-22-23 8:38 AM I78300 08-22-23 8:38 AM I78F00 08-22-23 8:38 AM I78700 08-22-23 8:38 AM I70200 08-22-23 8:38 AM LIQUID LABEL DEVICE LABEL 1 91 STP 2 91 FILL SUMP 3 87 STP 4 87 FILL SUMP 5 UDC 1-2 6 UDC 3-4 7 UDC 5-6 8 UDC 7-8 9 ANNULAR 87-91 10 11 12 13 14 15 16 I70300 08-22-23 8:38 AM LIQUID TYPE SENSOR LOCATION TYPE 1 91 STP TRI-STATE (SINGLE FLOAT) 2 91 FILL SUMP TRI-STATE (SINGLE FLOAT) 3 87 STP TRI-STATE (SINGLE FLOAT) 4 87 FILL SUMP TRI-STATE (SINGLE FLOAT) 5 UDC 1-2 TRI-STATE (SINGLE FLOAT) 6 UDC 3-4 TRI-STATE (SINGLE FLOAT) 7 UDC 5-6 TRI-STATE (SINGLE FLOAT) 8 UDC 7-8 TRI-STATE (SINGLE FLOAT) 9 ANNULAR 87-91 TRI-STATE (SINGLE FLOAT) 10 TRI-STATE (SINGLE FLOAT) 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 08-22-23 8:38 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 91 STP STP SUMP 2 91 FILL SUMP PIPING SUMP 3 87 STP STP SUMP 4 87 FILL SUMP PIPING SUMP 5 UDC 1-2 DISPENSER PAN 6 UDC 3-4 DISPENSER PAN 7 UDC 5-6 DISPENSER PAN 8 UDC 7-8 DISPENSER PAN 9 ANNULAR 87-91 ANNULAR SPACE 10 OTHER SENSORS 11 OTHER SENSORS 12 OTHER SENSORS 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 08-22-23 8:38 AM I74300 08-22-23 8:38 AM I74400 08-22-23 8:38 AM I74700 08-22-23 8:38 AM I74800 08-22-23 8:39 AM I74900 08-22-23 8:39 AM I7BC00 08-22-23 8:39 AM I80200 08-22-23 8:39 AM I80300 08-22-23 8:39 AM I80400 08-22-23 8:39 AM I80700 08-22-23 8:39 AM RELAY LABEL DEVICE LABEL 1 87 UNLEADED 2 PREM 91 3 4 I80900 08-22-23 8:39 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 87 UNLEADED NORMALLY CLOSED 2 PREM 91 NORMALLY CLOSED 3 NORMALLY OPEN 4 NORMALLY OPEN I80B00 08-22-23 8:39 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 87 UNLEADED 2 2 PREM 91 1 3 NONE 4 NONE I80A00 08-22-23 8:39 AM RELAY TYPE RELAY DESIGNATION TYPE 1 87 UNLEADED STANDARD 2 PREM 91 STANDARD 3 STANDARD 4 STANDARD I80C00 08-22-23 8:39 AM I80800 08-22-23 8:39 AM RELAY SETUP REPORT R 1:87 UNLEADED TYPE: STANDARD NORMALLY CLOSED TANK #: 2 IN-TANK ALARMS T 2:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 3:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PREM 91 TYPE: STANDARD NORMALLY CLOSED TANK #: 1 IN-TANK ALARMS T 1:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 1:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL PMC ALARMS VP EMISSIONS FAIL R 3: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 08-22-23 8:39 AM EDIM:1 VR:349867-001-D TD:17.02.14.08.38 I79100 08-22-23 8:39 AM I72300 08-22-23 8:39 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VAPOR PRESSURE VAPOR PRESSURE 02 FLOW METER 1-2 AIR FLOW METER 03 FLOW METER 3-4 AIR FLOW METER 04 FLOW METER 5-6 AIR FLOW METER 05 FLOW METER 7-8 AIR FLOW METER 06 VP UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 08-22-23 8:39 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 EVR/ISD SETUP TYPE: BALANCE IV4F00 08-22-23 8:39 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 08-22-23 8:39 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 VAPOR PROCESSOR TYPE NONE IV4700 08-22-23 8:39 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 08-22-23 8:39 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ACCEPT HIGH ORVR: YES IV4A00 08-22-23 8:39 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 02 BLEND3 02 02 02 01 02 BLEND3 03 03 03 02 02 BLEND3 04 04 04 02 02 BLEND3 05 05 05 03 02 BLEND3 06 06 06 03 02 BLEND3 07 07 07 04 02 BLEND3 08 08 08 04 02 BLEND3 IV4B00 08-22-23 8:39 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 01/01 09/01 xx/xx 02 01 02/02 01/02 09/02 xx/xx 03 02 02/03 01/03 09/03 xx/xx 04 02 02/04 01/04 09/04 xx/xx 05 03 02/05 01/05 09/05 xx/xx 06 03 02/06 01/06 09/06 xx/xx 07 04 02/07 01/07 09/07 xx/xx 08 04 02/08 01/08 09/08 xx/xx IV4900 08-22-23 8:39 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 08-22-23 8:39 AM ISD VERSION: 01.05 FJM MOBIL Pre Alarm History Responses Received: I10200 08-22-23 8:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 164738 163898 2 INTERSTITIAL BD 202007 201438 3 INTERSTITIAL BD 202007 201416 4 7SMARTSENSOR BD 507999 506036 5 UNUSED 9903073 9750733 6 UNUSED 9868832 9726376 7 UNUSED 9858988 9721638 8 UNUSED 9856420 9716318 9 RELAY BOARD 14987 14952 10 UNUSED 9859521 9727585 11 UNUSED 9850410 9713765 12 UNUSED 9848494 9712394 13 UNUSED 9844907 9710648 14 UNUSED 9838935 9710440 15 UNUSED 9845213 9707073 16 UNUSED 9841504 9704642 COMM 1 RS232 SERIAL BD 14946 14931 COMM 2 ELEC DISP INT. 101209 101007 COMM 3 UNUSED 9847618 9721995 COMM 4 UNUSED 9841748 9707863 COMM 5 UNUSED 9837448 9703894 COMM 6 UNUSED 9840158 9707323 I90200 08-22-23 8:40 AM SOFTWARE REVISION LEVEL VERSION 334.01 SOFTWARE# 346334-100-B CREATED - 17.01.09.16.10 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 08-22-23 8:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME E 1 OTHER COMMUNICATION ALARM CLEAR 08-16-23 8:14 PM E 1 OTHER COMMUNICATION ALARM ALARM 08-16-23 8:12 PM E 1 OTHER COMMUNICATION ALARM CLEAR 08-13-23 9:40 AM E 1 OTHER COMMUNICATION ALARM ALARM 08-13-23 9:40 AM E 1 OTHER COMMUNICATION ALARM CLEAR 08-13-23 9:40 AM E 1 OTHER COMMUNICATION ALARM ALARM 08-13-23 9:40 AM E 1 OTHER COMMUNICATION ALARM CLEAR 08-04-23 10:01 PM E 1 OTHER COMMUNICATION ALARM ALARM 08-04-23 9:56 PM E 1 OTHER COMMUNICATION ALARM CLEAR 08-04-23 11:38 AM E 1 OTHER COMMUNICATION ALARM ALARM 08-04-23 11:37 AM E 1 OTHER COMMUNICATION ALARM CLEAR 07-21-23 12:19 PM E 1 OTHER COMMUNICATION ALARM ALARM 07-21-23 12:19 PM E 1 OTHER COMMUNICATION ALARM CLEAR 07-21-23 12:19 PM E 1 OTHER COMMUNICATION ALARM ALARM 07-21-23 12:19 PM E 1 OTHER COMMUNICATION ALARM CLEAR 06-27-23 1:13 PM E 1 OTHER COMMUNICATION ALARM ALARM 06-27-23 1:06 PM E 1 OTHER COMMUNICATION ALARM CLEAR 06-23-23 12:55 PM E 1 OTHER COMMUNICATION ALARM ALARM 06-23-23 12:53 PM E 1 OTHER COMMUNICATION ALARM CLEAR 06-23-23 12:31 PM E 1 OTHER COMMUNICATION ALARM ALARM 06-23-23 12:31 PM E 1 OTHER COMMUNICATION ALARM CLEAR 06-23-23 12:29 PM E 1 OTHER COMMUNICATION ALARM ALARM 06-23-23 12:13 PM E 1 OTHER COMMUNICATION ALARM CLEAR 05-19-23 12:12 PM E 1 OTHER COMMUNICATION ALARM ALARM 05-19-23 12:10 PM E 1 OTHER COMMUNICATION ALARM CLEAR 04-03-23 2:12 AM E 1 OTHER COMMUNICATION ALARM ALARM 04-03-23 2:12 AM L 1 STP SUMP 91 STP FUEL ALARM CLEAR 03-03-23 3:44 PM L 1 STP SUMP 91 STP FUEL ALARM ALARM 03-03-23 3:41 PM L 1 STP SUMP 91 STP FUEL ALARM CLEAR 03-03-23 2:41 PM L 1 STP SUMP 91 STP FUEL ALARM ALARM 03-03-23 2:41 PM L 4 PIPE 87 FILL SUMP FUEL ALARM CLEAR 03-03-23 2:23 PM L 4 PIPE 87 FILL SUMP FUEL ALARM ALARM 03-03-23 10:18 AM E 1 OTHER COMMUNICATION ALARM CLEAR 01-30-23 3:18 AM E 1 OTHER COMMUNICATION ALARM ALARM 01-30-23 3:18 AM L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 1 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM CLEAR 10-03-22 9:46 AM L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM ALARM 10-03-22 9:46 AM L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 10-03-22 9:45 AM I11200 08-22-23 8:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD GROSS PRES WARN ALARM 08-17-23 10:07 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 08-15-23 10:07 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-15-23 10:01 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 08-14-23 12:55 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-13-23 10:47 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 08-06-23 7:58 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-06-23 7:50 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 08-05-23 11:37 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-03-23 7:04 PM OTHER ISD VAPOR LEAK WARN CLEAR 08-01-23 10:05 AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN CLEAR 08-01-23 10:00 AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN ALARM 07-31-23 10:08 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-29-23 10:00 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-28-23 10:07 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-27-23 12:17 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 07-27-23 12:13 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 07-27-23 11:40 AM OTHER ISD VAPOR LEAK WARN ALARM 07-27-23 10:07 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-24-23 10:00 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-23-23 10:40 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-23-23 10:06 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-18-23 7:57 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 07-18-23 7:53 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 07-17-23 5:18 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-14-23 12:14 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-08-23 7:44 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-04-23 10:35 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-29-23 6:21 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-26-23 1:19 PM OTHER ISD VAPOR LEAK WARN CLEAR 06-23-23 11:45 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-21-23 8:10 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-21-23 8:07 AM OTHER ISD VAPOR LEAK WARN ALARM 06-20-23 10:04 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 06-20-23 7:50 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-18-23 12:32 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-11-23 7:47 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-11-23 7:37 PM SYSTEM PRINTER ERROR CLEAR 06-10-23 8:09 PM SYSTEM PAPER OUT CLEAR 06-10-23 8:09 PM SYSTEM PRINTER ERROR ALARM 06-10-23 8:08 PM SYSTEM PAPER OUT ALARM 06-10-23 8:08 PM SYSTEM SOFTWARE MODULE WARN CLEAR 06-10-23 7:40 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 06-09-23 5:30 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-08-23 9:13 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-01-23 7:02 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-01-23 7:01 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 05-31-23 9:02 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 05-29-23 1:01 PM OTHER ISD VAPOR LEAK WARN CLEAR 05-26-23 10:44 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 05-23-23 12:01 PM I20600 08-22-23 8:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 TANK ALARM HISTORY TANK 1 PREM 91 DELIVERY NEEDED 08-13-23 10:47 AM 08-03-23 7:04 PM 07-23-23 10:40 AM PER TST NEEDED ALM 12-23-19 12:00 AM ANN TST NEEDED ALM 12-23-19 12:00 AM TANK 2 UNLEADED 87 OVERFILL ALARM 04-07-22 5:47 AM 03-30-22 6:00 AM 01-13-22 11:28 PM LOW PRODUCT ALARM 07-11-20 12:04 PM 05-18-19 7:09 AM 01-14-19 5:41 PM HIGH PRODUCT ALARM 04-07-22 5:49 AM 06-09-20 5:58 AM 03-23-20 4:17 AM DELIVERY NEEDED 08-14-23 12:55 PM 08-05-23 11:37 AM 07-27-23 11:40 AM PER TST NEEDED ALM 12-23-19 12:00 AM ANN TST NEEDED ALM 12-23-19 12:00 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 08-22-23 8:40 AM I30200 08-22-23 8:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 91 STP 03-03-23 3:41 PM FUEL ALARM 03-03-23 2:41 PM FUEL ALARM 10-03-22 9:45 AM SENSOR OUT ALARM 2 91 FILL SUMP 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:35 AM FUEL ALARM 08-11-21 11:15 AM FUEL ALARM 3 87 STP 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:34 AM FUEL ALARM 10-03-22 9:31 AM SENSOR OUT ALARM 4 87 FILL SUMP 03-03-23 10:18 AM FUEL ALARM 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:36 AM FUEL ALARM 5 UDC 1-2 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:39 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 6 UDC 3-4 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:40 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 7 UDC 5-6 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:39 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 8 UDC 7-8 10-03-22 9:45 AM SENSOR OUT ALARM 10-03-22 9:38 AM FUEL ALARM 08-11-21 9:28 AM SENSOR OUT ALARM 9 ANNULAR 87-91 10-03-22 9:46 AM SENSOR OUT ALARM 10-03-22 9:37 AM FUEL ALARM 10-03-22 9:37 AM FUEL ALARM I31600 08-22-23 8:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VAPOR PRESSURE 01-29-20 12:19 PM COMMUNICATION ALARM 12-22-17 10:25 AM COMMUNICATION ALARM 12-22-17 9:52 AM COMMUNICATION ALARM 2 FLOW METER 1-2 12-22-17 10:00 AM COMMUNICATION ALARM 3 FLOW METER 3-4 12-22-17 10:00 AM COMMUNICATION ALARM 08-21-17 2:18 PM COMMUNICATION ALARM 4 FLOW METER 5-6 12-03-20 8:21 AM COMMUNICATION ALARM 12-22-17 10:00 AM COMMUNICATION ALARM 08-22-17 10:48 AM COMMUNICATION ALARM 5 FLOW METER 7-8 12-22-17 10:00 AM COMMUNICATION ALARM 08-21-17 2:18 PM COMMUNICATION ALARM I40200 08-22-23 8:40 AM I40300 08-22-23 8:40 AM I34200 08-22-23 8:40 AM I34700 08-22-23 8:40 AM IV0100 08-22-23 8:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-08-21 10:03:16 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-08-20 10:03:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-08-19 10:04:52 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-08-18 10:05:58 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-08-17 10:07:33 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-07-31 10:08:32 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 26.24 23-07-31 10:08:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 0.58 23-07-30 10:07:21 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.44 23-07-29 10:07:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.88 23-07-28 10:07:54 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.33 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-08-09 10:07:29 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 22-07-25 10:07:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 22-05-06 10:06:28 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 21-07-14 10:01:12 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-13 10:01:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-12 10:06:23 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-03 10:06:30 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 18-08-07 10:08:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 18-06-12 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 18-06-11 10:06:56 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-08-21 10:03:16 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-20 10:03:45 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-19 10:04:52 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-18 10:05:58 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-17 10:07:33 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-16 20:10:51 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-08-16 20:10:51 ISD STARTUP 23-08-16 19:14:39 ISD SHUTDOWN 23-06-28 10:11:21 READINESS ISD:PP EVR:PP ISD & EVR READY 23-06-27 13:04:24 READINESS ISD:PP EVR:NN EVR READINESS PENDING Post Alarm History Responses Received: I10200 08-22-23 10:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 164738 163279 2 INTERSTITIAL BD 202007 200827 3 INTERSTITIAL BD 202007 200783 4 7SMARTSENSOR BD 507999 504253 5 UNUSED 9903073 9680454 6 UNUSED 9868832 9660350 7 UNUSED 9858988 9671242 8 UNUSED 9856420 9687240 9 RELAY BOARD 14987 14978 10 UNUSED 9859521 9668009 11 UNUSED 9850410 9672307 12 UNUSED 9848494 9688496 13 UNUSED 9844907 9680838 14 UNUSED 9838935 9663435 15 UNUSED 9845213 9660010 16 UNUSED 9841504 9672477 COMM 1 RS232 SERIAL BD 14946 14957 COMM 2 ELEC DISP INT. 101209 100989 COMM 3 UNUSED 9847618 9684922 COMM 4 UNUSED 9841748 9687262 COMM 5 UNUSED 9837448 9674051 COMM 6 UNUSED 9840158 9657798 I90200 08-22-23 10:40 AM SOFTWARE REVISION LEVEL VERSION 334.01 SOFTWARE# 346334-100-B CREATED - 17.01.09.16.10 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 08-22-23 10:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM L 3 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM L 1 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM CLEAR 08-22-23 9:14 AM L 8 DISP PAN UDC 7-8 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM L 7 DISP PAN UDC 5-6 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM L 2 PIPE 91 FILL SUMP SENSOR OUT ALARM ALARM 08-22-23 9:14 AM L 3 STP SUMP 87 STP SENSOR OUT ALARM ALARM 08-22-23 9:14 AM L 4 PIPE 87 FILL SUMP SENSOR OUT ALARM ALARM 08-22-23 9:14 AM L 6 DISP PAN UDC 3-4 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM L 1 STP SUMP 91 STP SENSOR OUT ALARM ALARM 08-22-23 9:14 AM L 5 DISP PAN UDC 1-2 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM L 9 ANNULAR ANNULAR 87-91 SENSOR OUT ALARM ALARM 08-22-23 9:14 AM L 8 DISP PAN UDC 7-8 FUEL ALARM CLEAR 08-22-23 9:11 AM L 8 DISP PAN UDC 7-8 FUEL ALARM ALARM 08-22-23 9:11 AM L 7 DISP PAN UDC 5-6 FUEL ALARM CLEAR 08-22-23 9:10 AM L 7 DISP PAN UDC 5-6 FUEL ALARM ALARM 08-22-23 9:10 AM L 5 DISP PAN UDC 1-2 FUEL ALARM CLEAR 08-22-23 9:09 AM L 5 DISP PAN UDC 1-2 FUEL ALARM ALARM 08-22-23 9:09 AM L 6 DISP PAN UDC 3-4 FUEL ALARM CLEAR 08-22-23 9:08 AM L 6 DISP PAN UDC 3-4 FUEL ALARM ALARM 08-22-23 9:07 AM L 9 ANNULAR ANNULAR 87-91 FUEL ALARM CLEAR 08-22-23 9:06 AM L 9 ANNULAR ANNULAR 87-91 FUEL ALARM ALARM 08-22-23 9:06 AM L 4 PIPE 87 FILL SUMP FUEL ALARM CLEAR 08-22-23 9:06 AM L 4 PIPE 87 FILL SUMP FUEL ALARM ALARM 08-22-23 9:06 AM L 3 STP SUMP 87 STP FUEL ALARM CLEAR 08-22-23 9:05 AM L 3 STP SUMP 87 STP FUEL ALARM ALARM 08-22-23 9:04 AM L 2 PIPE 91 FILL SUMP FUEL ALARM CLEAR 08-22-23 9:04 AM L 2 PIPE 91 FILL SUMP FUEL ALARM ALARM 08-22-23 9:04 AM L 1 STP SUMP 91 STP FUEL ALARM CLEAR 08-22-23 9:02 AM L 1 STP SUMP 91 STP FUEL ALARM ALARM 08-22-23 9:02 AM E 1 OTHER COMMUNICATION ALARM CLEAR 08-16-23 8:14 PM E 1 OTHER COMMUNICATION ALARM ALARM 08-16-23 8:12 PM E 1 OTHER COMMUNICATION ALARM CLEAR 08-13-23 9:40 AM E 1 OTHER COMMUNICATION ALARM ALARM 08-13-23 9:40 AM E 1 OTHER COMMUNICATION ALARM CLEAR 08-13-23 9:40 AM E 1 OTHER COMMUNICATION ALARM ALARM 08-13-23 9:40 AM E 1 OTHER COMMUNICATION ALARM CLEAR 08-04-23 10:01 PM E 1 OTHER COMMUNICATION ALARM ALARM 08-04-23 9:56 PM E 1 OTHER COMMUNICATION ALARM CLEAR 08-04-23 11:38 AM E 1 OTHER COMMUNICATION ALARM ALARM 08-04-23 11:37 AM E 1 OTHER COMMUNICATION ALARM CLEAR 07-21-23 12:19 PM E 1 OTHER COMMUNICATION ALARM ALARM 07-21-23 12:19 PM E 1 OTHER COMMUNICATION ALARM CLEAR 07-21-23 12:19 PM E 1 OTHER COMMUNICATION ALARM ALARM 07-21-23 12:19 PM I11200 08-22-23 10:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD GROSS PRES WARN ALARM 08-17-23 10:07 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 08-15-23 10:07 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-15-23 10:01 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 08-14-23 12:55 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-13-23 10:47 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 08-06-23 7:58 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 08-06-23 7:50 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 08-05-23 11:37 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 08-03-23 7:04 PM OTHER ISD VAPOR LEAK WARN CLEAR 08-01-23 10:05 AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN CLEAR 08-01-23 10:00 AM h 2 OTHER FP2: BLEND3 FLOW COLLECT WARN ALARM 07-31-23 10:08 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-29-23 10:00 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-28-23 10:07 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-27-23 12:17 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 07-27-23 12:13 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 07-27-23 11:40 AM OTHER ISD VAPOR LEAK WARN ALARM 07-27-23 10:07 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 07-24-23 10:00 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-23-23 10:40 AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 07-23-23 10:06 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-18-23 7:57 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 07-18-23 7:53 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 07-17-23 5:18 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-14-23 12:14 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 07-08-23 7:44 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 07-04-23 10:35 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-29-23 6:21 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-26-23 1:19 PM OTHER ISD VAPOR LEAK WARN CLEAR 06-23-23 11:45 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-21-23 8:10 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-21-23 8:07 AM OTHER ISD VAPOR LEAK WARN ALARM 06-20-23 10:04 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 06-20-23 7:50 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-18-23 12:32 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-11-23 7:47 PM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-11-23 7:37 PM SYSTEM PRINTER ERROR CLEAR 06-10-23 8:09 PM SYSTEM PAPER OUT CLEAR 06-10-23 8:09 PM SYSTEM PRINTER ERROR ALARM 06-10-23 8:08 PM SYSTEM PAPER OUT ALARM 06-10-23 8:08 PM SYSTEM SOFTWARE MODULE WARN CLEAR 06-10-23 7:40 PM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 06-09-23 5:30 PM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 06-08-23 9:13 AM T 1 TANK PREM 91 DELIVERY NEEDED CLEAR 06-01-23 7:02 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 06-01-23 7:01 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED ALARM 05-31-23 9:02 AM T 1 TANK PREM 91 DELIVERY NEEDED ALARM 05-29-23 1:01 PM OTHER ISD VAPOR LEAK WARN CLEAR 05-26-23 10:44 AM T 2 TANK UNLEADED 87 DELIVERY NEEDED CLEAR 05-23-23 12:01 PM I20600 08-22-23 10:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 TANK ALARM HISTORY TANK 1 PREM 91 DELIVERY NEEDED 08-13-23 10:47 AM 08-03-23 7:04 PM 07-23-23 10:40 AM PER TST NEEDED ALM 12-23-19 12:00 AM ANN TST NEEDED ALM 12-23-19 12:00 AM TANK 2 UNLEADED 87 OVERFILL ALARM 04-07-22 5:47 AM 03-30-22 6:00 AM 01-13-22 11:28 PM LOW PRODUCT ALARM 07-11-20 12:04 PM 05-18-19 7:09 AM 01-14-19 5:41 PM HIGH PRODUCT ALARM 04-07-22 5:49 AM 06-09-20 5:58 AM 03-23-20 4:17 AM DELIVERY NEEDED 08-14-23 12:55 PM 08-05-23 11:37 AM 07-27-23 11:40 AM PER TST NEEDED ALM 12-23-19 12:00 AM ANN TST NEEDED ALM 12-23-19 12:00 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 08-22-23 10:40 AM I30200 08-22-23 10:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 91 STP 08-22-23 9:14 AM SENSOR OUT ALARM 08-22-23 9:02 AM FUEL ALARM 03-03-23 3:41 PM FUEL ALARM 2 91 FILL SUMP 08-22-23 9:14 AM SENSOR OUT ALARM 08-22-23 9:04 AM FUEL ALARM 10-03-22 9:45 AM SENSOR OUT ALARM 3 87 STP 08-22-23 9:14 AM SENSOR OUT ALARM 08-22-23 9:04 AM FUEL ALARM 10-03-22 9:45 AM SENSOR OUT ALARM 4 87 FILL SUMP 08-22-23 9:14 AM SENSOR OUT ALARM 08-22-23 9:06 AM FUEL ALARM 03-03-23 10:18 AM FUEL ALARM 5 UDC 1-2 08-22-23 9:14 AM SENSOR OUT ALARM 08-22-23 9:09 AM FUEL ALARM 10-03-22 9:45 AM SENSOR OUT ALARM 6 UDC 3-4 08-22-23 9:14 AM SENSOR OUT ALARM 08-22-23 9:07 AM FUEL ALARM 10-03-22 9:45 AM SENSOR OUT ALARM 7 UDC 5-6 08-22-23 9:14 AM SENSOR OUT ALARM 08-22-23 9:10 AM FUEL ALARM 10-03-22 9:45 AM SENSOR OUT ALARM 8 UDC 7-8 08-22-23 9:14 AM SENSOR OUT ALARM 08-22-23 9:11 AM FUEL ALARM 10-03-22 9:45 AM SENSOR OUT ALARM 9 ANNULAR 87-91 08-22-23 9:14 AM SENSOR OUT ALARM 08-22-23 9:06 AM FUEL ALARM 10-03-22 9:46 AM SENSOR OUT ALARM I31600 08-22-23 10:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VAPOR PRESSURE 01-29-20 12:19 PM COMMUNICATION ALARM 12-22-17 10:25 AM COMMUNICATION ALARM 12-22-17 9:52 AM COMMUNICATION ALARM 2 FLOW METER 1-2 12-22-17 10:00 AM COMMUNICATION ALARM 3 FLOW METER 3-4 12-22-17 10:00 AM COMMUNICATION ALARM 08-21-17 2:18 PM COMMUNICATION ALARM 4 FLOW METER 5-6 12-03-20 8:21 AM COMMUNICATION ALARM 12-22-17 10:00 AM COMMUNICATION ALARM 08-22-17 10:48 AM COMMUNICATION ALARM 5 FLOW METER 7-8 12-22-17 10:00 AM COMMUNICATION ALARM 08-21-17 2:18 PM COMMUNICATION ALARM I40200 08-22-23 10:40 AM I40300 08-22-23 10:40 AM I34200 08-22-23 10:40 AM I34700 08-22-23 10:40 AM IV0100 08-22-23 10:40 AM MOBIL 2601 WHITE LANE BAKERSFIELD CA 16613971520 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME : 99% EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-08-22 10:02:21 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-08-21 10:03:16 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-08-20 10:03:45 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-08-19 10:04:52 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-08-18 10:05:58 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-08-17 10:07:33 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 5.00 23-07-31 10:08:32 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 26.24 23-07-31 10:08:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 0.58 23-07-30 10:07:21 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.44 23-07-29 10:07:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 15.88 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 22-08-09 10:07:29 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 22-07-25 10:07:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 22-05-06 10:06:28 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 21-07-14 10:01:12 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-13 10:01:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-12 10:06:23 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 21-07-03 10:06:30 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 18-08-07 10:08:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 18-06-12 10:07:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 18-06-11 10:06:56 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-08-22 10:02:21 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-22 09:15:26 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-08-22 09:15:26 ISD STARTUP 23-08-22 09:15:18 ISD SHUTDOWN 23-08-21 10:03:16 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-20 10:03:45 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-19 10:04:52 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-18 10:05:58 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-17 10:07:33 READINESS ISD:PP EVR:PF CHECK EVR SYSTEM 23-08-16 20:10:51 READINESS ISD:PP EVR:NN EVR READINESS PENDING