HomeMy WebLinkAboutFMC 2023Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10022950 8-23-23 Grand Avenue Coast, Inc. (ARCO AMPM) 4203 Ming Avenue Bakersfield 93309 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Rockland Kirk 1073967 10241356 9-29-24 VMI #5255 10-3-24 GVR C32654 9-28-24 8-23-23 5 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder-Root TLS-350 336.01 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 409 87 REG UNL ANN L2 208 87 REG UNL STP L3 208 87 REG UNL FILL S L4 409 87 REG UNL 2 ANN L5 208 87 REG UNL 2 SYPHON L6 208 87 UNL REG M FILL L7 409 87 REG UNL 3 ANN L8 208 87 REG UNL SYPHON L9 208 87 REG UNL N FILL L10 409 91 PREM UNL ANN L11 208 91 PREM UNL FILL L12 208 91 PREM UNL STP L13 208 DISP 1-2 L14 208 DISP 3-4 L15 208 DISP 5-6 L16 208 DISP 7-8 L17 208 DISP 9-10 L18 208 DISP 11-12 Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Q1 PLLD 87 REG UNL Q2 PLLD 91 PREM UNL Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Grand Avenue Coast, Inc. (ARCO AMPM)4203 Ming AvenueBakersfield100229501-22-3 3-48791879187918791871-22-33-45-65-67-8ProductProductProductProductProductProductProductProductProductRockland Kirk APPENDIX C-10 7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB9111-12ProductProduct11-1287919-10ProductProduct9-1087917-8ProductRockland Kirk Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10022950 8-23-23 Grand Avenue Coast, Inc. (ARCO AMPM) 4203 Ming Avenue Bakersfield 93309 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Rockland Kirk 1073967 10241356 9-29-24 OPW Phase 1 EVR 1193547 2-15-25 RP 1200 Spill buckets 8-23-23 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1 87 OPW T3 87 spill bucket had to be retested with a new cap. Passed. L9 was present upon arrival. Pull a little bit of fluid from T3 and T4 fill sumps. Alarm went away. T2 87 OPW T3 87 OPW T4 91 OPW Responses Received: 200 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 AUG 23, 2023 8:44 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 1 3676 37.68 0.0 83.8 6324 2 UNLEADED 2 TURBN 4005 40.16 0.8 84.3 5995 3 UNLEADED 3 4348 42.72 0.0 82.1 5652 4 PREMIUM 3969 39.89 0.0 83.0 6031 I90500 AUG 23, 2023 8:44 AM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 AUG 23, 2023 8:44 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 AUG 23, 2023 8:44 AM SHIFT TIME 1 : DISABLED I50202 AUG 23, 2023 8:44 AM SHIFT TIME 2 : DISABLED I50203 AUG 23, 2023 8:44 AM SHIFT TIME 3 : DISABLED I50204 AUG 23, 2023 8:44 AM SHIFT TIME 4 : DISABLED I54600 AUG 23, 2023 8:44 AM TANK PER TST NEEDED WRN: DISABLED I54900 AUG 23, 2023 8:44 AM TANK ANN TST NEEDED WRN: DISABLED I55300 AUG 23, 2023 8:44 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 AUG 23, 2023 8:44 AM LINE PER TST NEEDED WRN: DISABLED I55900 AUG 23, 2023 8:44 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 AUG 23, 2023 8:44 AM PRINT TC VOLUMES ENABLED I50E00 AUG 23, 2023 8:44 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 AUG 23, 2023 8:44 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 AUG 23, 2023 8:44 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 AUG 23, 2023 8:44 AM DAYLIGHT SAVING TIME ENABLED ON I51B00 AUG 23, 2023 8:44 AM DAYLIGHT SAVING TIME START DATE APR WEEK 1 SUN 2:00 AM END DATE OCT WEEK 6 SUN 2:00 AM I51600 AUG 23, 2023 8:44 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 AUG 23, 2023 8:44 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 AUG 23, 2023 8:44 AM TANK CHART SECURITY DISABLED I5BD00 AUG 23, 2023 8:44 AM CUSTOM ALARM LABELS DISABLED I56000 AUG 23, 2023 8:44 AM MASS/DENSITY DISABLED I88101 AUG 23, 2023 8:44 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 AUG 23, 2023 8:44 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88103 AUG 23, 2023 8:44 AM PORT SETTINGS: COMM BOARD : 3 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88104 AUG 23, 2023 8:44 AM I88105 AUG 23, 2023 8:44 AM PORT SETTINGS: COMM BOARD : 5 (RS-485) BAUD RATE : 1200 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88106 AUG 23, 2023 8:44 AM PORT SETTINGS: COMM BOARD : 6 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I52000 AUG 23, 2023 8:44 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE JUL 17, 2006 DISABLED 2 ON DATE JUL 17, 2006 DISABLED 3 ON DATE JUL 17, 2006 DISABLED 4 ON DATE JUL 17, 2006 DISABLED 5 ON DATE JUL 17, 2006 DISABLED 6 ON DATE JUL 17, 2006 DISABLED 7 ON DATE JUL 17, 2006 DISABLED 8 VEEDER ROOT (FMS) ON DATE JUN 13, 2006 11:46 AM I60100 AUG 23, 2023 8:44 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED 1 ON 2 UNLEADED 2 TURBN ON 3 UNLEADED 3 ON 4 PREMIUM ON I60200 AUG 23, 2023 8:44 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 1 2 UNLEADED 2 TURBN 3 UNLEADED 3 4 PREMIUM I60300 AUG 23, 2023 8:44 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 1 2 UNLEADED 2 TURBN 1 3 UNLEADED 3 1 4 PREMIUM 2 I60900 AUG 23, 2023 8:44 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 1 0.000700 2 UNLEADED 2 TURBN 0.000700 3 UNLEADED 3 0.000700 4 PREMIUM 0.000700 I60700 AUG 23, 2023 8:44 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 1 96.00 2 UNLEADED 2 TURBN 96.00 3 UNLEADED 3 96.00 4 PREMIUM 96.00 I60A00 AUG 23, 2023 8:44 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 4 PTS 10000 2 UNLEADED 2 TURBN 4 PTS 10000 3 UNLEADED 3 4 PTS 10000 4 PREMIUM 4 PTS 10000 I60400 AUG 23, 2023 8:44 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 10000 2 UNLEADED 2 TURBN 10000 3 UNLEADED 3 10000 4 PREMIUM 10000 I60500 AUG 23, 2023 8:44 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 10000 8079 5061 1973 2 UNLEADED 2 TURBN 10000 8079 5061 1973 3 UNLEADED 3 10000 8079 5061 1973 4 PREMIUM 10000 8079 5061 1973 I60600 AUG 23, 2023 8:44 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 10000 0 0 0 0 8079 0 0 0 0 5061 0 0 0 0 1973 0 0 0 0 2 UNLEADED 2 TURBN 10000 0 0 0 0 8079 0 0 0 0 5061 0 0 0 0 1973 0 0 0 0 3 UNLEADED 3 10000 0 0 0 0 8079 0 0 0 0 5061 0 0 0 0 1973 0 0 0 0 4 PREMIUM 10000 0 0 0 0 8079 0 0 0 0 5061 0 0 0 0 1973 0 0 0 0 I61500 AUG 23, 2023 8:44 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED 1 NO 2 UNLEADED 2 TURBN NO 3 UNLEADED 3 NO 4 PREMIUM NO I62F00 AUG 23, 2023 8:44 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 1 4.0 IN. 2 UNLEADED 2 TURBN 4.0 IN. 3 UNLEADED 3 4.0 IN. 4 PREMIUM 4.0 IN. I62700 AUG 23, 2023 8:44 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 2.5 2 UNLEADED 2 TURBN 2.5 3 UNLEADED 3 2.5 4 PREMIUM 2.5 I64200 AUG 23, 2023 8:44 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED 1 LOW 2 UNLEADED 2 TURBN LOW 3 UNLEADED 3 LOW 4 PREMIUM LOW I62400 AUG 23, 2023 8:44 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 3.0 2 UNLEADED 2 TURBN 3.0 3 UNLEADED 3 3.0 4 PREMIUM 3.0 I62800 AUG 23, 2023 8:44 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 10000 2 UNLEADED 2 TURBN 10000 3 UNLEADED 3 10000 4 PREMIUM 10000 I62300 AUG 23, 2023 8:44 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 9000 2 UNLEADED 2 TURBN 9000 3 UNLEADED 3 9000 4 PREMIUM 9000 I62200 AUG 23, 2023 8:44 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 9500 2 UNLEADED 2 TURBN 9500 3 UNLEADED 3 9500 4 PREMIUM 9500 I62900 AUG 23, 2023 8:44 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 2000 2 UNLEADED 2 TURBN 2000 3 UNLEADED 3 2000 4 PREMIUM 2000 I62100 AUG 23, 2023 8:44 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 1000 2 UNLEADED 2 TURBN 1000 3 UNLEADED 3 1000 4 PREMIUM 1000 I62600 AUG 23, 2023 8:44 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 99 2 UNLEADED 2 TURBN 99 3 UNLEADED 3 99 4 PREMIUM 99 I62500 AUG 23, 2023 8:44 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 99 2 UNLEADED 2 TURBN 99 3 UNLEADED 3 99 4 PREMIUM 99 I60800 AUG 23, 2023 8:44 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 1 0.00 2 UNLEADED 2 TURBN 0.00 3 UNLEADED 3 0.00 4 PREMIUM 0.00 I60B00 AUG 23, 2023 8:44 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 AUG 23, 2023 8:44 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 1 0.00 2 UNLEADED 2 TURBN 0.00 3 UNLEADED 3 0.00 4 PREMIUM 0.00 I61200 AUG 23, 2023 8:44 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED 1 NONE NONE 2 UNLEADED 2 TURBN NONE NONE 3 UNLEADED 3 NONE NONE 4 PREMIUM NONE NONE I63600 AUG 23, 2023 8:44 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 0 2 UNLEADED 2 TURBN 0 3 UNLEADED 3 0 4 PREMIUM 0 I62A00 AUG 23, 2023 8:44 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 0 2 UNLEADED 2 TURBN 0 3 UNLEADED 3 0 4 PREMIUM 0 I62C00 AUG 23, 2023 8:44 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED 1 STANDARD 2 UNLEADED 2 TURBN STANDARD 3 UNLEADED 3 STANDARD 4 PREMIUM STANDARD I62D00 AUG 23, 2023 8:44 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED 1 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 UNLEADED 2 TURBN GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 UNLEADED 3 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 AUG 23, 2023 8:44 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED 1 OFF OFF 2 UNLEADED 2 TURBN OFF OFF 3 UNLEADED 3 OFF OFF 4 PREMIUM OFF OFF I63000 AUG 23, 2023 8:45 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED 1 OFF 2 UNLEADED 2 TURBN OFF 3 UNLEADED 3 OFF 4 PREMIUM OFF I63200 AUG 23, 2023 8:45 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED 1 OFF 2 UNLEADED 2 TURBN OFF 3 UNLEADED 3 OFF 4 PREMIUM OFF I61000 AUG 23, 2023 8:45 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 2 2 UNLEADED 2 TURBN 2 3 UNLEADED 3 2 4 PREMIUM 2 I63A00 AUG 23, 2023 8:45 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 1 10.00% 2 UNLEADED 2 TURBN 10.00% 3 UNLEADED 3 10.00% 4 PREMIUM 3.00% I61100 AUG 23, 2023 8:45 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK NOV 10, 2003 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 AUG 23, 2023 8:45 AM CSLD PROBABLITY OF DETECTION I61400 AUG 23, 2023 8:45 AM CSLD CLIMATE FACTOR I61600 AUG 23, 2023 8:45 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED 1 IMMEDIATE 2 UNLEADED 2 TURBN IMMEDIATE 3 UNLEADED 3 IMMEDIATE 4 PREMIUM IMMEDIATE I61A00 AUG 23, 2023 8:45 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED 1 DISABLED 2 UNLEADED 2 TURBN DISABLED 3 UNLEADED 3 DISABLED 4 PREMIUM DISABLED I61B00 AUG 23, 2023 8:45 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 AUG 23, 2023 8:45 AM CSLD REPORT ONLY I62B00 AUG 23, 2023 8:45 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED 1 ??? 0, 0 2 UNLEADED 2 TURBN ??? 0, 0 3 UNLEADED 3 ??? 0, 0 4 PREMIUM ??? 0, 0 I63300 AUG 23, 2023 8:45 AM LEAK TEST REPORT FORMAT: NORMAL I63400 AUG 23, 2023 8:45 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 0 2 UNLEADED 2 TURBN 0 3 UNLEADED 3 0 4 PREMIUM 0 I63500 AUG 23, 2023 8:45 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 1 2 UNLEADED 2 TURBN 1 3 UNLEADED 3 1 4 PREMIUM 1 I63900 AUG 23, 2023 8:45 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED 1 END FACTOR: NONE 2 UNLEADED 2 TURBN END FACTOR: NONE 3 UNLEADED 3 END FACTOR: NONE 4 PREMIUM END FACTOR: NONE I78000 AUG 23, 2023 8:45 AM PRESSURE LINE LEAK SETUP Q 1:87 REG UNL TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN: 499 FEET 3.0IN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 1:UNLEADED 1 DISPENSE MODE: STANDARD SENSOR: NON-VENTED PRESSURE OFFSET: 0.0PSI MECHANICAL BLENDER: NO Q 2:92 PREM UNL TYP:2.0/3.0IN FIBERGLASS 2.0IN DIA LEN: 300 FEET 3.0IN DIA LEN: 0 FEET SHUTDOWN RATE: 3.0 GPH LOW PRESSURE SHUTOFF:NO LOW PRESSURE : 0 PSI T 4:PREMIUM DISPENSE MODE: STANDARD SENSOR: NON-VENTED PRESSURE OFFSET: 0.0PSI MECHANICAL BLENDER: NO I77700 AUG 23, 2023 8:45 AM I77800 AUG 23, 2023 8:45 AM I78C00 AUG 23, 2023 8:45 AM I78300 AUG 23, 2023 8:45 AM I78F00 AUG 23, 2023 8:45 AM PRESSURE LINE LEAK DISPENSE THRESHOLD LINE LOW PRESSURE Q 1:87 REG UNL 0 PSI Q 2:92 PREM UNL 0 PSI Q 3: 0 PSI I78700 AUG 23, 2023 8:45 AM PRESSURE LLD SETUP REPORT Q 1:87 REG UNL LIQUID SENSOR ALMS L 2:FUEL ALARM L 5:FUEL ALARM L 8:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L16:FUEL ALARM L17:FUEL ALARM L18:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM PRESSURE LINE LEAK ALL:PLLD OPEN ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL Q 2:92 PREM UNL LIQUID SENSOR ALMS L 2:FUEL ALARM L 5:FUEL ALARM L 8:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L16:FUEL ALARM L17:FUEL ALARM L18:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM PRESSURE LINE LEAK ALL:PLLD OPEN ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD SETUP WARN ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL Q 3: - NO ALARM ASSIGNMENTS - I70200 AUG 23, 2023 8:45 AM LIQUID LABEL DEVICE LABEL 1 87 REG UNL ANNULAR 2 87 REG UNL STP 3 87 REG UNL FILL S 4 87 REG UNL 2 ANNULAR 5 87 REG UNL 2 SYPHON 6 87 REG UNL M FILL 7 87 REG UNL 3 ANNULAR 8 87 REG UNL 3 SYPHON 9 87 REG UNL N FILL 10 91 PREM UNL ANNULAR 11 91 PEM UNL FILL 12 91 PREM UNL STP 13 DIRP 1-2 14 DISP 3-4 15 DISP 5-6 16 DISP 7-8 17 DISP 9-10 18 DISP 11-12 19 20 21 22 23 24 I70300 AUG 23, 2023 8:45 AM LIQUID TYPE SENSOR LOCATION TYPE 1 87 REG UNL ANNULAR TRI-STATE (SINGLE FLOAT) 2 87 REG UNL STP TRI-STATE (SINGLE FLOAT) 3 87 REG UNL FILL S TRI-STATE (SINGLE FLOAT) 4 87 REG UNL 2 ANNULAR TRI-STATE (SINGLE FLOAT) 5 87 REG UNL 2 SYPHON TRI-STATE (SINGLE FLOAT) 6 87 REG UNL M FILL TRI-STATE (SINGLE FLOAT) 7 87 REG UNL 3 ANNULAR TRI-STATE (SINGLE FLOAT) 8 87 REG UNL 3 SYPHON TRI-STATE (SINGLE FLOAT) 9 87 REG UNL N FILL TRI-STATE (SINGLE FLOAT) 10 91 PREM UNL ANNULAR TRI-STATE (SINGLE FLOAT) 11 91 PEM UNL FILL TRI-STATE (SINGLE FLOAT) 12 91 PREM UNL STP TRI-STATE (SINGLE FLOAT) 13 DIRP 1-2 TRI-STATE (SINGLE FLOAT) 14 DISP 3-4 TRI-STATE (SINGLE FLOAT) 15 DISP 5-6 TRI-STATE (SINGLE FLOAT) 16 DISP 7-8 TRI-STATE (SINGLE FLOAT) 17 DISP 9-10 TRI-STATE (SINGLE FLOAT) 18 DISP 11-12 TRI-STATE (SINGLE FLOAT) 19 TRI-STATE (SINGLE FLOAT) 20 TRI-STATE (SINGLE FLOAT) 21 TRI-STATE (SINGLE FLOAT) 22 TRI-STATE (SINGLE FLOAT) 23 TRI-STATE (SINGLE FLOAT) 24 TRI-STATE (SINGLE FLOAT) I70400 AUG 23, 2023 8:45 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 87 REG UNL ANNULAR ANNULAR SPACE 2 87 REG UNL STP STP SUMP 3 87 REG UNL FILL S PIPING SUMP 4 87 REG UNL 2 ANNULAR ANNULAR SPACE 5 87 REG UNL 2 SYPHON STP SUMP 6 87 REG UNL M FILL PIPING SUMP 7 87 REG UNL 3 ANNULAR ANNULAR SPACE 8 87 REG UNL 3 SYPHON PIPING SUMP 9 87 REG UNL N FILL PIPING SUMP 10 91 PREM UNL ANNULAR ANNULAR SPACE 11 91 PEM UNL FILL STP SUMP 12 91 PREM UNL STP PIPING SUMP 13 DIRP 1-2 DISPENSER PAN 14 DISP 3-4 DISPENSER PAN 15 DISP 5-6 DISPENSER PAN 16 DISP 7-8 DISPENSER PAN 17 DISP 9-10 DISPENSER PAN 18 DISP 11-12 DISPENSER PAN 19 OTHER SENSORS 20 OTHER SENSORS 21 OTHER SENSORS 22 OTHER SENSORS 23 OTHER SENSORS 24 OTHER SENSORS I74200 AUG 23, 2023 8:45 AM I74300 AUG 23, 2023 8:45 AM I74400 AUG 23, 2023 8:45 AM I74700 AUG 23, 2023 8:45 AM I74800 AUG 23, 2023 8:45 AM I74900 AUG 23, 2023 8:45 AM I7BC00 AUG 23, 2023 8:45 AM I80200 AUG 23, 2023 8:45 AM I80300 AUG 23, 2023 8:45 AM I80400 AUG 23, 2023 8:45 AM I80700 AUG 23, 2023 8:45 AM RELAY LABEL DEVICE LABEL 1 2 3 ALARM 4 I80900 AUG 23, 2023 8:45 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 NORMALLY OPEN 2 NORMALLY OPEN 3 ALARM NORMALLY OPEN 4 NORMALLY OPEN I80B00 AUG 23, 2023 8:45 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 NONE 2 NONE 3 ALARM NONE 4 NONE I80A00 AUG 23, 2023 8:45 AM RELAY TYPE RELAY DESIGNATION TYPE 1 STANDARD 2 STANDARD 3 ALARM STANDARD 4 STANDARD I80C00 AUG 23, 2023 8:45 AM I80800 AUG 23, 2023 8:45 AM RELAY SETUP REPORT R 1: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 2: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 3:ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 AUG 23, 2023 8:45 AM EDIM:1 VR:349866-001-E TD:19.10.30.16.33 I79100 AUG 23, 2023 8:45 AM I72300 AUG 23, 2023 8:45 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 DIS 1-2 AIR FLOW METER 02 DIS 3-4 AIR FLOW METER 03 DIS 5-6 AIR FLOW METER 04 DIS 7-8 AIR FLOW METER 05 DIS 9-10 AIR FLOW METER 06 DIS 11-12 AIR FLOW METER 07 VAPOR PRESS SENSOR VAPOR PRESSURE 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 AUG 23, 2023 8:45 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 EVR/ISD SETUP TYPE: BALANCE IV4F00 AUG 23, 2023 8:45 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 AUG 23, 2023 8:45 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 VAPOR PROCESSOR TYPE NONE IV4700 AUG 23, 2023 8:45 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 ASSESSMENT TIME START TIME: 11:59 PM TIME DELAY MINUTES: 1 IV5200 AUG 23, 2023 8:45 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 ACCEPT HIGH ORVR: NO IV4A00 AUG 23, 2023 8:45 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 00 01 01 UU BLEND3 02 01 02 01 UU BLEND3 03 02 03 02 UU BLEND3 04 03 04 02 UU BLEND3 05 04 05 03 UU BLEND3 06 05 06 03 UU BLEND3 07 06 07 04 UU BLEND3 08 07 08 04 UU BLEND3 09 08 09 05 UU BLEND3 10 09 10 05 UU BLEND3 11 10 11 06 UU BLEND3 12 11 12 06 UU BLEND3 IV4B00 AUG 23, 2023 8:45 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 00 01 00/01 03/01 09/01 xx/xx 01 01 00/02 03/02 09/02 xx/xx 02 02 00/03 03/03 09/03 xx/xx 03 02 00/04 03/04 09/04 xx/xx 04 03 00/05 03/05 09/05 xx/xx 05 03 00/06 03/06 09/06 xx/xx 06 04 00/07 03/07 09/07 xx/xx 07 04 00/08 03/08 09/08 xx/xx 08 05 00/09 03/09 09/09 xx/xx 09 05 00/10 03/10 09/10 xx/xx 10 06 00/11 03/11 09/11 xx/xx 11 06 00/12 03/12 09/12 xx/xx IV4900 AUG 23, 2023 8:45 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 AUG 23, 2023 8:45 AM ISD VERSION: 01.05 Responses Received: I10200 AUG 23, 2023 8:58 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 INTERSTITIAL BD 203872 203492 2 INTERSTITIAL BD 203464 203516 3 INTERSTITIAL BD 203153 202724 4 PLLD SENSOR BD 3932 3958 5 4 PROBE / G.T. 165488 165394 6 8SMARTSENSOR BD 40245 40155 7 UNUSED 9801818 9800155 8 UNUSED 9790023 9783235 9 RELAY BOARD 15068 15083 10 PLLD POWER BD 101943 101860 11 UNUSED 9799782 9798483 12 UNUSED 9788700 9793902 13 UNUSED 9786792 9786904 14 UNUSED 9794241 9790311 15 UNUSED 9788884 9775716 16 UNUSED 9778883 9783014 COMM 1 ELEC DISP INT. 102717 102636 COMM 2 RS232 SERIAL BD 15091 15037 COMM 3 SERIAL SAT BD 488929 487931 COMM 4 UNUSED 9790264 9789022 COMM 5 RS485 SERIAL BD 69401 69277 COMM 6 RS232 SERIAL BD 15114 15060 I90200 AUG 23, 2023 8:58 AM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 AUG 23, 2023 8:58 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-21-23 7:16AM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-21-23 7:16AM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM CLEAR 8-21-23 7:16AM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM ALARM 8-21-23 7:16AM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-21-23 7:16AM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-21-23 7:16AM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 9:30PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 9:30PM L12 PIPE 91 PREM UNL STP FUEL ALARM CLEAR 8-20-23 9:30PM L12 PIPE 91 PREM UNL STP FUEL ALARM ALARM 8-20-23 8:45PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 8:45PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 8:45PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 7:00PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 7:00PM L12 PIPE 91 PREM UNL STP FUEL ALARM CLEAR 8-20-23 7:00PM L12 PIPE 91 PREM UNL STP FUEL ALARM ALARM 8-20-23 7:00PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 7:00PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 7:00PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 6:45PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 6:45PM L12 PIPE 91 PREM UNL STP FUEL ALARM CLEAR 8-20-23 6:45PM L12 PIPE 91 PREM UNL STP FUEL ALARM ALARM 8-20-23 5:44PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 5:44PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 5:44PM L 9 PIPE 87 REG UNL N FILL FUEL ALARM ALARM 8-20-23 3:53PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 3:20PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 3:20PM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM CLEAR 8-20-23 3:20PM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM ALARM 8-20-23 3:20PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 3:20PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 3:20PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 3:13PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 3:13PM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM CLEAR 8-20-23 3:13PM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM ALARM 8-20-23 3:13PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 3:13PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 3:13PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 2:40PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 2:40PM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM CLEAR 8-20-23 2:40PM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM ALARM 8-20-23 2:35PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 2:35PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 2:35PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 2:27PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 2:27PM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM CLEAR 8-20-23 2:27PM L 5 STP SUMP 87 REG UNL 2 SYPHON FUEL ALARM ALARM 8-20-23 2:19PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 2:19PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-20-23 2:19PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-20-23 1:42PM I11200 AUG 23, 2023 8:58 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 8-21-23 11:56PM SYSTEM PAPER OUT CLEAR 8-21-23 11:56PM SYSTEM PRINTER ERROR ALARM 8-21-23 7:54AM SYSTEM PAPER OUT ALARM 8-21-23 7:54AM SYSTEM PRINTER ERROR CLEAR 8-14-23 3:08PM SYSTEM PAPER OUT CLEAR 8-14-23 3:08PM SYSTEM PRINTER ERROR ALARM 8-14-23 3:07PM SYSTEM PAPER OUT ALARM 8-14-23 3:07PM T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-10-23 11:27PM T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-10-23 2:59PM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 8-02-23 6:43AM T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED CLEAR 8-02-23 6:34AM SYSTEM PRINTER ERROR CLEAR 8-02-23 6:14AM SYSTEM PRINTER ERROR ALARM 8-02-23 6:14AM SYSTEM PRINTER ERROR CLEAR 8-02-23 6:13AM SYSTEM PAPER OUT CLEAR 8-02-23 6:13AM SYSTEM PRINTER ERROR ALARM 8-02-23 6:11AM SYSTEM PAPER OUT ALARM 8-02-23 6:11AM T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED ALARM 8-02-23 6:10AM SYSTEM PRINTER ERROR CLEAR 8-02-23 6:10AM SYSTEM PRINTER ERROR ALARM 8-02-23 6:10AM SYSTEM PRINTER ERROR CLEAR 8-02-23 6:08AM SYSTEM PAPER OUT CLEAR 8-02-23 6:08AM T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 8-01-23 5:45PM SYSTEM PRINTER ERROR ALARM 7-29-23 12:07PM SYSTEM PAPER OUT ALARM 7-29-23 12:07PM T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 7-22-23 10:50PM T 4 TANK PREMIUM DELIVERY NEEDED ALARM 7-22-23 6:42AM T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 7-19-23 4:34PM T 4 TANK PREMIUM DELIVERY NEEDED ALARM 7-19-23 5:39AM SYSTEM PRINTER ERROR CLEAR 7-17-23 2:33PM SYSTEM PAPER OUT CLEAR 7-17-23 2:33PM SYSTEM PAPER OUT ALARM 7-17-23 2:33PM SYSTEM PRINTER ERROR ALARM 7-17-23 2:33PM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 7-08-23 1:35AM T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 7-08-23 1:14AM T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 7-07-23 7:38PM T 4 TANK PREMIUM DELIVERY NEEDED ALARM 7-07-23 11:08AM SYSTEM PRINTER ERROR CLEAR 7-04-23 12:59PM SYSTEM PAPER OUT CLEAR 7-04-23 12:59PM SYSTEM PAPER OUT ALARM 7-04-23 12:59PM SYSTEM PRINTER ERROR ALARM 7-04-23 12:59PM SYSTEM PRINTER ERROR CLEAR 7-04-23 12:59PM SYSTEM PAPER OUT CLEAR 7-04-23 12:59PM SYSTEM PAPER OUT ALARM 7-04-23 12:59PM SYSTEM PRINTER ERROR ALARM 7-04-23 12:58PM SYSTEM PRINTER ERROR CLEAR 7-04-23 12:58PM SYSTEM PAPER OUT CLEAR 7-04-23 12:58PM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 7-04-23 12:39PM SYSTEM PRINTER ERROR ALARM 7-04-23 12:33PM I20600 AUG 23, 2023 8:58 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 TANK ALARM HISTORY TANK 1 UNLEADED 1 SETUP DATA WARNING MAR 24, 2021 9:18 AM LOW PRODUCT ALARM OCT 21, 2022 3:49 PM MAY 2, 2022 6:19 PM SUDDEN LOSS ALARM JUN 5, 2023 2:59 AM JUN 3, 2023 3:24 AM JUN 3, 2023 2:30 AM HIGH PRODUCT ALARM MAR 24, 2021 9:18 AM DELIVERY NEEDED AUG 1, 2023 5:45 PM JUL 7, 2023 7:38 PM JUL 4, 2023 12:27 PM TANK 2 UNLEADED 2 TURBN SETUP DATA WARNING MAR 24, 2021 9:20 AM LOW PRODUCT ALARM OCT 21, 2022 6:36 PM HIGH PRODUCT ALARM MAR 24, 2021 9:20 AM DELIVERY NEEDED AUG 2, 2023 6:10 AM MAY 27, 2023 11:02 PM APR 8, 2023 6:13 PM TANK 3 UNLEADED 3 SETUP DATA WARNING MAR 24, 2021 9:22 AM LOW PRODUCT ALARM OCT 22, 2022 5:31 AM HIGH PRODUCT ALARM MAR 24, 2021 9:22 AM DELIVERY NEEDED APR 9, 2023 10:03 PM OCT 21, 2022 11:10 AM AUG 20, 2022 1:42 PM TANK 4 PREMIUM SETUP DATA WARNING MAR 24, 2021 9:24 AM HIGH PRODUCT ALARM MAR 24, 2021 9:24 AM DELIVERY NEEDED AUG 10, 2023 2:59 PM JUL 22, 2023 6:42 AM JUL 19, 2023 5:39 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 AUG 23, 2023 8:59 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:87 REG UNL AUG 21, 2023 7:16 AM PLLD SHUTDOWN ALARM AUG 20, 2023 8:45 PM PLLD SHUTDOWN ALARM AUG 20, 2023 7:00 PM PLLD SHUTDOWN ALARM AUG 20, 2023 5:44 PM PLLD SHUTDOWN ALARM AUG 20, 2023 3:20 PM PLLD SHUTDOWN ALARM AUG 20, 2023 3:13 PM PLLD SHUTDOWN ALARM AUG 20, 2023 2:35 PM PLLD SHUTDOWN ALARM AUG 20, 2023 2:19 PM PLLD SHUTDOWN ALARM AUG 20, 2023 12:32 PM PLLD SHUTDOWN ALARM AUG 2, 2023 12:59 AM CONT HANDLE ALM Q 2:92 PREM UNL AUG 21, 2023 7:16 AM PLLD SHUTDOWN ALARM AUG 20, 2023 8:45 PM PLLD SHUTDOWN ALARM AUG 20, 2023 7:00 PM PLLD SHUTDOWN ALARM AUG 20, 2023 5:44 PM PLLD SHUTDOWN ALARM AUG 20, 2023 3:20 PM PLLD SHUTDOWN ALARM AUG 20, 2023 3:13 PM PLLD SHUTDOWN ALARM AUG 20, 2023 2:35 PM PLLD SHUTDOWN ALARM AUG 20, 2023 2:19 PM PLLD SHUTDOWN ALARM AUG 20, 2023 12:32 PM PLLD SHUTDOWN ALARM JUN 13, 2023 3:28 PM PLLD SHUTDOWN ALARM I30200 AUG 23, 2023 8:59 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 REG UNL ANNULAR AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:35 AM FUEL ALARM AUG 19, 2022 9:35 AM FUEL ALARM 2 87 REG UNL STP JUN 13, 2023 3:28 PM FUEL ALARM MAR 15, 2023 5:48 AM SETUP DATA WARNING MAR 15, 2023 2:46 AM SENSOR OUT ALARM 3 87 REG UNL FILL S MAR 25, 2023 11:46 PM FUEL ALARM MAR 25, 2023 11:46 PM SENSOR OUT ALARM MAR 25, 2023 1:15 PM FUEL ALARM 4 87 REG UNL 2 ANNULAR AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:47 AM FUEL ALARM AUG 19, 2022 9:40 AM FUEL ALARM 5 87 REG UNL 2 SYPHON AUG 21, 2023 7:16 AM FUEL ALARM AUG 20, 2023 3:20 PM FUEL ALARM AUG 20, 2023 3:13 PM FUEL ALARM 6 87 REG UNL M FILL JUL 11, 2023 5:14 AM FUEL ALARM JUN 13, 2023 3:55 PM FUEL ALARM JUN 6, 2023 10:43 PM FUEL ALARM 7 87 REG UNL 3 ANNULAR AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:40 AM FUEL ALARM AUG 19, 2022 9:37 AM FUEL ALARM 8 87 REG UNL 3 SYPHON JUN 13, 2023 3:27 PM FUEL ALARM AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:30 AM FUEL ALARM 9 87 REG UNL N FILL AUG 20, 2023 3:53 PM FUEL ALARM JUN 17, 2023 5:30 PM FUEL ALARM JUN 13, 2023 3:54 PM FUEL ALARM 10 91 PREM UNL ANNULAR JUN 7, 2023 5:05 PM SENSOR OUT ALARM MAY 23, 2023 8:15 AM SENSOR OUT ALARM MAY 17, 2023 5:09 AM SENSOR OUT ALARM 11 91 PEM UNL FILL JUL 9, 2023 10:31 PM FUEL ALARM JUN 26, 2023 3:01 PM FUEL ALARM JUN 13, 2023 3:52 PM FUEL ALARM 12 91 PREM UNL STP AUG 20, 2023 8:45 PM FUEL ALARM AUG 20, 2023 7:00 PM FUEL ALARM AUG 20, 2023 5:44 PM FUEL ALARM 13 DIRP 1-2 AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:52 AM FUEL ALARM AUG 24, 2021 10:08 AM SENSOR OUT ALARM 14 DISP 3-4 AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:52 AM FUEL ALARM AUG 24, 2021 10:09 AM SENSOR OUT ALARM 15 DISP 5-6 AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:50 AM FUEL ALARM DEC 23, 2021 6:39 PM SENSOR OUT ALARM 16 DISP 7-8 AUG 19, 2022 9:59 AM FUEL ALARM AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:51 AM FUEL ALARM 17 DISP 9-10 AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:49 AM FUEL ALARM AUG 24, 2021 10:09 AM SENSOR OUT ALARM 18 DISP 11-12 AUG 19, 2022 9:55 AM SENSOR OUT ALARM AUG 19, 2022 9:49 AM FUEL ALARM AUG 24, 2021 10:09 AM SENSOR OUT ALARM I31600 AUG 23, 2023 8:59 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 DIS 1-2 2 DIS 3-4 3 DIS 5-6 4 DIS 7-8 5 DIS 9-10 6 DIS 11-12 7 VAPOR PRESS SENSOR I40200 AUG 23, 2023 8:59 AM I40300 AUG 23, 2023 8:59 AM I34200 AUG 23, 2023 8:59 AM I34700 AUG 23, 2023 8:59 AM IV0100 AUG 23, 2023 8:59 AM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-05-23 00:01:14 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 31.27 23-05-16 00:02:28 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.47 23-05-15 00:02:24 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.13 23-05-14 00:02:26 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.49 23-05-13 00:02:32 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.72 23-05-12 00:02:31 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.10 23-05-11 00:02:21 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.76 23-05-10 00:01:11 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 19.89 23-05-03 00:01:27 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.65 23-05-02 00:02:08 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.22 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-05-17 00:02:27 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.61 23-05-04 00:01:26 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.38 23-04-21 00:02:18 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 19.29 23-04-08 00:02:31 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.84 23-03-26 00:01:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.51 23-03-25 00:01:25 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.24 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-06-03 00:02:48 READINESS ISD:PP EVR:PP ISD & EVR READY 23-06-02 00:03:04 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-06-01 00:03:08 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-31 00:03:15 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-30 00:02:51 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-29 00:02:34 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-28 00:04:08 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-27 00:03:06 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-26 00:01:07 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-25 00:00:22 READINESS ISD:PP EVR:NP EVR READINESS PENDING Responses Received: I10200 AUG 23, 2023 1:43 PM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 INTERSTITIAL BD 203872 203737 2 INTERSTITIAL BD 203464 203713 3 INTERSTITIAL BD 203153 203208 4 PLLD SENSOR BD 3932 3942 5 4 PROBE / G.T. 165488 165704 6 8SMARTSENSOR BD 40245 40209 7 UNUSED 9801818 9766288 8 UNUSED 9790023 9762175 9 RELAY BOARD 15068 15084 10 PLLD POWER BD 101943 101917 11 UNUSED 9799782 9748453 12 UNUSED 9788700 9757442 13 UNUSED 9786792 9759499 14 UNUSED 9794241 9748707 15 UNUSED 9788884 9744432 16 UNUSED 9778883 9745934 COMM 1 ELEC DISP INT. 102717 102790 COMM 2 RS232 SERIAL BD 15091 15107 COMM 3 SERIAL SAT BD 488929 488988 COMM 4 UNUSED 9790264 9762388 COMM 5 RS485 SERIAL BD 69401 69417 COMM 6 RS232 SERIAL BD 15114 15084 I90200 AUG 23, 2023 1:43 PM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 AUG 23, 2023 1:43 PM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME E 1 OTHER G COMMUNICATION ALARM ALARM 8-23-23 1:38PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-23-23 12:10PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-23-23 12:10PM L16 DISP PAN DISP 7-8 FUEL ALARM CLEAR 8-23-23 12:10PM L16 DISP PAN DISP 7-8 FUEL ALARM ALARM 8-23-23 12:01PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-23-23 12:01PM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-23-23 12:01PM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-23-23 11:59AM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM CLEAR 8-23-23 11:59AM L 4 ANNULAR 87 REG UNL 2 ANNULAR SENSOR OUT ALARM CLEAR 8-23-23 11:59AM L 3 PIPE 87 REG UNL FILL S SENSOR OUT ALARM CLEAR 8-23-23 11:59AM L 7 ANNULAR 87 REG UNL 3 ANNULAR SENSOR OUT ALARM CLEAR 8-23-23 11:59AM L 2 STP SUMP 87 REG UNL STP SENSOR OUT ALARM CLEAR 8-23-23 11:59AM L 1 ANNULAR 87 REG UNL ANNULAR SENSOR OUT ALARM CLEAR 8-23-23 11:59AM L 1 ANNULAR 87 REG UNL ANNULAR FUEL ALARM ALARM 8-23-23 11:59AM L 6 PIPE 87 REG UNL M FILL SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L 8 PIPE 87 REG UNL 3 SYPHON SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L 5 STP SUMP 87 REG UNL 2 SYPHON SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L10 ANNULAR 91 PREM UNL ANNULAR SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L15 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L14 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L16 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L13 DISP PAN DIRP 1-2 SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L12 PIPE 91 PREM UNL STP SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L11 STP SUMP 91 PEM UNL FILL SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L 9 PIPE 87 REG UNL N FILL SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L18 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L17 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 8-23-23 11:58AM L10 ANNULAR 91 PREM UNL ANNULAR SENSOR OUT ALARM ALARM 8-23-23 11:56AM L16 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 8-23-23 11:56AM L12 PIPE 91 PREM UNL STP SENSOR OUT ALARM ALARM 8-23-23 11:56AM L11 STP SUMP 91 PEM UNL FILL SENSOR OUT ALARM ALARM 8-23-23 11:56AM L18 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 8-23-23 11:56AM L17 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 8-23-23 11:56AM L 9 PIPE 87 REG UNL N FILL SENSOR OUT ALARM ALARM 8-23-23 11:56AM L15 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 8-23-23 11:56AM L 7 ANNULAR 87 REG UNL 3 ANNULAR SENSOR OUT ALARM ALARM 8-23-23 11:56AM L14 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 8-23-23 11:56AM L13 DISP PAN DIRP 1-2 SENSOR OUT ALARM ALARM 8-23-23 11:56AM L 2 STP SUMP 87 REG UNL STP SENSOR OUT ALARM ALARM 8-23-23 11:56AM L 5 STP SUMP 87 REG UNL 2 SYPHON SENSOR OUT ALARM ALARM 8-23-23 11:56AM L 1 ANNULAR 87 REG UNL ANNULAR SENSOR OUT ALARM ALARM 8-23-23 11:56AM L 1 ANNULAR 87 REG UNL ANNULAR FUEL ALARM CLEAR 8-23-23 11:56AM L 4 ANNULAR 87 REG UNL 2 ANNULAR SENSOR OUT ALARM ALARM 8-23-23 11:56AM L 3 PIPE 87 REG UNL FILL S SENSOR OUT ALARM ALARM 8-23-23 11:56AM L 8 PIPE 87 REG UNL 3 SYPHON SENSOR OUT ALARM ALARM 8-23-23 11:56AM L 6 PIPE 87 REG UNL M FILL SENSOR OUT ALARM ALARM 8-23-23 11:56AM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM ALARM 8-23-23 11:56AM Q 1 OTHER 87 REG UNL PLLD SHUTDOWN ALARM ALARM 8-23-23 11:56AM Q 2 OTHER 92 PREM UNL PLLD SHUTDOWN ALARM CLEAR 8-23-23 11:51AM I11200 AUG 23, 2023 1:43 PM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 8-23-23 12:21PM SYSTEM PAPER OUT CLEAR 8-23-23 12:21PM SYSTEM PRINTER ERROR ALARM 8-23-23 11:56AM SYSTEM PAPER OUT ALARM 8-23-23 11:56AM SYSTEM PRINTER ERROR CLEAR 8-21-23 11:56PM SYSTEM PAPER OUT CLEAR 8-21-23 11:56PM SYSTEM PRINTER ERROR ALARM 8-21-23 7:54AM SYSTEM PAPER OUT ALARM 8-21-23 7:54AM SYSTEM PRINTER ERROR CLEAR 8-14-23 3:08PM SYSTEM PAPER OUT CLEAR 8-14-23 3:08PM SYSTEM PRINTER ERROR ALARM 8-14-23 3:07PM SYSTEM PAPER OUT ALARM 8-14-23 3:07PM T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 8-10-23 11:27PM T 4 TANK PREMIUM DELIVERY NEEDED ALARM 8-10-23 2:59PM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 8-02-23 6:43AM T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED CLEAR 8-02-23 6:34AM SYSTEM PRINTER ERROR CLEAR 8-02-23 6:14AM SYSTEM PRINTER ERROR ALARM 8-02-23 6:14AM SYSTEM PRINTER ERROR CLEAR 8-02-23 6:13AM SYSTEM PAPER OUT CLEAR 8-02-23 6:13AM SYSTEM PRINTER ERROR ALARM 8-02-23 6:11AM SYSTEM PAPER OUT ALARM 8-02-23 6:11AM T 2 TANK UNLEADED 2 TURBN DELIVERY NEEDED ALARM 8-02-23 6:10AM SYSTEM PRINTER ERROR CLEAR 8-02-23 6:10AM SYSTEM PRINTER ERROR ALARM 8-02-23 6:10AM SYSTEM PRINTER ERROR CLEAR 8-02-23 6:08AM SYSTEM PAPER OUT CLEAR 8-02-23 6:08AM T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 8-01-23 5:45PM SYSTEM PRINTER ERROR ALARM 7-29-23 12:07PM SYSTEM PAPER OUT ALARM 7-29-23 12:07PM T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 7-22-23 10:50PM T 4 TANK PREMIUM DELIVERY NEEDED ALARM 7-22-23 6:42AM T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 7-19-23 4:34PM T 4 TANK PREMIUM DELIVERY NEEDED ALARM 7-19-23 5:39AM SYSTEM PRINTER ERROR CLEAR 7-17-23 2:33PM SYSTEM PAPER OUT CLEAR 7-17-23 2:33PM SYSTEM PAPER OUT ALARM 7-17-23 2:33PM SYSTEM PRINTER ERROR ALARM 7-17-23 2:33PM T 1 TANK UNLEADED 1 DELIVERY NEEDED CLEAR 7-08-23 1:35AM T 4 TANK PREMIUM DELIVERY NEEDED CLEAR 7-08-23 1:14AM T 1 TANK UNLEADED 1 DELIVERY NEEDED ALARM 7-07-23 7:38PM T 4 TANK PREMIUM DELIVERY NEEDED ALARM 7-07-23 11:08AM SYSTEM PRINTER ERROR CLEAR 7-04-23 12:59PM SYSTEM PAPER OUT CLEAR 7-04-23 12:59PM SYSTEM PAPER OUT ALARM 7-04-23 12:59PM SYSTEM PRINTER ERROR ALARM 7-04-23 12:59PM SYSTEM PRINTER ERROR CLEAR 7-04-23 12:59PM SYSTEM PAPER OUT CLEAR 7-04-23 12:59PM SYSTEM PAPER OUT ALARM 7-04-23 12:59PM SYSTEM PRINTER ERROR ALARM 7-04-23 12:58PM I20600 AUG 23, 2023 1:44 PM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 TANK ALARM HISTORY TANK 1 UNLEADED 1 SETUP DATA WARNING MAR 24, 2021 9:18 AM LOW PRODUCT ALARM OCT 21, 2022 3:49 PM MAY 2, 2022 6:19 PM SUDDEN LOSS ALARM JUN 5, 2023 2:59 AM JUN 3, 2023 3:24 AM JUN 3, 2023 2:30 AM HIGH PRODUCT ALARM MAR 24, 2021 9:18 AM DELIVERY NEEDED AUG 1, 2023 5:45 PM JUL 7, 2023 7:38 PM JUL 4, 2023 12:27 PM TANK 2 UNLEADED 2 TURBN SETUP DATA WARNING MAR 24, 2021 9:20 AM LOW PRODUCT ALARM OCT 21, 2022 6:36 PM HIGH PRODUCT ALARM MAR 24, 2021 9:20 AM DELIVERY NEEDED AUG 2, 2023 6:10 AM MAY 27, 2023 11:02 PM APR 8, 2023 6:13 PM TANK 3 UNLEADED 3 SETUP DATA WARNING MAR 24, 2021 9:22 AM LOW PRODUCT ALARM OCT 22, 2022 5:31 AM HIGH PRODUCT ALARM MAR 24, 2021 9:22 AM DELIVERY NEEDED APR 9, 2023 10:03 PM OCT 21, 2022 11:10 AM AUG 20, 2022 1:42 PM TANK 4 PREMIUM SETUP DATA WARNING MAR 24, 2021 9:24 AM HIGH PRODUCT ALARM MAR 24, 2021 9:24 AM DELIVERY NEEDED AUG 10, 2023 2:59 PM JUL 22, 2023 6:42 AM JUL 19, 2023 5:39 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 AUG 23, 2023 1:44 PM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 PRESSURE LINE LEAK ALARM HISTORY REPORT Q 1:87 REG UNL AUG 23, 2023 12:01 PM PLLD SHUTDOWN ALARM AUG 23, 2023 11:56 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:42 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:42 AM GROSS LINE FAIL AUG 23, 2023 11:36 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:31 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:30 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:29 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:28 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:27 AM PLLD SHUTDOWN ALARM Q 2:92 PREM UNL AUG 23, 2023 12:01 PM PLLD SHUTDOWN ALARM AUG 23, 2023 11:56 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:49 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:49 AM GROSS LINE FAIL AUG 23, 2023 11:36 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:31 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:30 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:29 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:28 AM PLLD SHUTDOWN ALARM AUG 23, 2023 11:27 AM PLLD SHUTDOWN ALARM I30200 AUG 23, 2023 1:44 PM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 REG UNL ANNULAR AUG 23, 2023 11:59 AM FUEL ALARM AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 10:10 AM FUEL ALARM 2 87 REG UNL STP AUG 23, 2023 11:56 AM SENSOR OUT ALARM JUN 13, 2023 3:28 PM FUEL ALARM MAR 15, 2023 5:48 AM SETUP DATA WARNING 3 87 REG UNL FILL S AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 10:37 AM FUEL ALARM MAR 25, 2023 11:46 PM FUEL ALARM 4 87 REG UNL 2 ANNULAR AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 10:36 AM FUEL ALARM AUG 23, 2023 10:03 AM FUEL ALARM 5 87 REG UNL 2 SYPHON AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 11:24 AM FUEL ALARM AUG 23, 2023 10:11 AM FUEL ALARM 6 87 REG UNL M FILL AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 10:37 AM FUEL ALARM JUL 11, 2023 5:14 AM FUEL ALARM 7 87 REG UNL 3 ANNULAR AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 10:35 AM FUEL ALARM AUG 23, 2023 10:02 AM FUEL ALARM 8 87 REG UNL 3 SYPHON AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 11:24 AM FUEL ALARM JUN 13, 2023 3:27 PM FUEL ALARM 9 87 REG UNL N FILL AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 10:38 AM FUEL ALARM AUG 20, 2023 3:53 PM FUEL ALARM 10 91 PREM UNL ANNULAR AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 10:34 AM FUEL ALARM AUG 23, 2023 10:12 AM SENSOR OUT ALARM 11 91 PEM UNL FILL AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 10:38 AM FUEL ALARM JUL 9, 2023 10:31 PM FUEL ALARM 12 91 PREM UNL STP AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 20, 2023 8:45 PM FUEL ALARM AUG 20, 2023 7:00 PM FUEL ALARM 13 DIRP 1-2 AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 11:25 AM FUEL ALARM AUG 19, 2022 9:55 AM SENSOR OUT ALARM 14 DISP 3-4 AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 11:29 AM FUEL ALARM AUG 19, 2022 9:55 AM SENSOR OUT ALARM 15 DISP 5-6 AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 11:27 AM FUEL ALARM AUG 19, 2022 9:55 AM SENSOR OUT ALARM 16 DISP 7-8 AUG 23, 2023 12:01 PM FUEL ALARM AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 11:36 AM FUEL ALARM 17 DISP 9-10 AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 11:31 AM FUEL ALARM AUG 19, 2022 9:55 AM SENSOR OUT ALARM 18 DISP 11-12 AUG 23, 2023 11:56 AM SENSOR OUT ALARM AUG 23, 2023 11:30 AM FUEL ALARM AUG 19, 2022 9:55 AM SENSOR OUT ALARM I31600 AUG 23, 2023 1:44 PM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 DIS 1-2 2 DIS 3-4 3 DIS 5-6 4 DIS 7-8 5 DIS 9-10 6 DIS 11-12 7 VAPOR PRESS SENSOR I40200 AUG 23, 2023 1:44 PM I40300 AUG 23, 2023 1:44 PM I34200 AUG 23, 2023 1:44 PM I34700 AUG 23, 2023 1:44 PM IV0100 AUG 23, 2023 1:44 PM 243508 ARCO AM-PM 4203 MING AVE BAKERSFIELD CA. 661-834-1076 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-05-23 00:01:14 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 31.27 23-05-16 00:02:28 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.47 23-05-15 00:02:24 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.13 23-05-14 00:02:26 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.49 23-05-13 00:02:32 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.72 23-05-12 00:02:31 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.10 23-05-11 00:02:21 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 20.76 23-05-10 00:01:11 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 19.89 23-05-03 00:01:27 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.65 23-05-02 00:02:08 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.22 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-05-17 00:02:27 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.61 23-05-04 00:01:26 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.38 23-04-21 00:02:18 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 19.29 23-04-08 00:02:31 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.84 23-03-26 00:01:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 17.51 23-03-25 00:01:25 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 16.24 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-08-23 11:59:42 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-08-23 11:59:42 ISD STARTUP 23-08-23 11:59:26 ISD SHUTDOWN 23-06-03 00:02:48 READINESS ISD:PP EVR:PP ISD & EVR READY 23-06-02 00:03:04 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-06-01 00:03:08 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-31 00:03:15 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-30 00:02:51 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-29 00:02:34 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-05-28 00:04:08 READINESS ISD:PP EVR:NP EVR READINESS PENDING