Loading...
HomeMy WebLinkAbout5269_Bakersfield CA_ELD-PT_CERT_Jlog_231023 1100Providers for MDleak® MSleak® DPleak®, MCleak® and PHDleak® Testing Technologies Page 1 of 2 Test Type: Job #: 5269 Facility Name: PO #: Prepared For: Site Address: City: State and Zip: CA 93308 Start Date:End Date: SYSTEM Test MDL TK-1 87 TK-2 87 TK-3 87 TK-4 91 TK-5 DSL TK-6 ADDTK- 7 DADD VR Product Primary MDleak:0.005 GPH PASS PASS PASS PASS PASS PASS PASS Product Secondary:0.005 GPH PASS PASS PASS PASS PASS PASS PASS Vent Primary MDleak:0.005 GPH PASS PASS PASS PASS PASS PASS PASS Vent Secondary:0.005 GPH PASS PASS PASS PASS PASS PASS PASS VR Primary MDleak:0.005 GPH PASS PASS PASS PASS NA NA NA VR Secondary:0.005 GPH PASS PASS PASS PASS NA NA NA Turbine Sump Fittings:0.005 GPH PASS PASS PASS PASS PASS PASS PASS Fill/Vapor Sump Fittings:0.005 GPH PASS PASS PASS PASS PASS PASS PASS UDC Fittings:0.005 GPH FAIL PASS PASS PASS PASS NA NA FAIL Vent Box Fittings 0.005 GPH PASS PASS PASS PASS PASS PASS PASS Remote Fill Primary:0.005 GPH NA NA NA PASS PASS NA NA Remote Fill Secondary:0.005 GPH NA NA NA PASS PASS NA NA Remote Fill VR 1st 0.005 GPH NA NA NA PASS NA NA NA Remote Fill 2nd 0.005 GPH NA NA NA PASS NA NA NA Primary Syphon Line:0.005 GPH PASS PASS PASS NA NA NA NA Syphon Secondary Syphon Line:0.005 GPH PASS PASS PASS NA NA NA NA Chase Line 1st:0.005 GPH PASS PASS PASS PASS PASS NA NA Chase Line 2nd 0.005 GPH PASS PASS PASS PASS PASS NA NA Jones Covey Group, Inc. Facility Certification CONFIDENTIAL Costco #688 10/3/20239/27/2023 3800 Rosedale HWY Bakersfiled Providers for MDleak® MSleak® DPleak®, MCleak® and PHDleak® Testing Technologies Page 2 of 2 Test Type: Facility Name: Job #: 5269 Prepared For: PO #: Site Address: City: State and Zip: CA 93308 Start Date:End Date: SYSTEM TK-1 87 TK-2 87 TK-3 87 TK-4 91 TK-5 DSL TK-6 ADDTK- 7 DADD VR 20000 20000 20000 30000 20000 2000 1500 CSI CSI CSI Xerxes CSI CSI CSI Brine Brine Brine Brine Brine Brine Brine Tank Sump Boots Turbine Bravo Bravo 15.00 0 0 0 Manufacture EVR: Certifying Field Technician: State Lic. # : Certification Leak Rate: Certifying Technician Signature: Date: Statement Confirmed by: Date: Costco #688 Jones Covey Group, Inc. Flex: If you have any questions on the testing please do not hesitate to call. @ 855-255-5325. I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is true and correct to the best of my knowledge. This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak sensitivity listed above by using one or more of the following DPleak®,MDleak®,MCleak and PHDleak®EPA aproved Methods.These Methods are the most versatile and comprehensive testing procedures offered to the petroleum industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®,MCleak,and PHDleak®Method can be assured that their facility has passed the Nation's highest standard in preventative leak detection. 21-1772 Facility Certification CONFIDENTIAL Office use only 10/15/2023 Depth to Ground Water: Component Manufacture: UDC/Dispensers Information Number of Dispensers: Manufacture: Shear Valve Manufacture: Containment Boots: Piping Information Product Lines: Vapor Return / Vent: Depth of Liquid Within Tank: 10/3/2023 3800 Rosedale HWY Bakersfiled 9/27/2023 10/3/2023 Ben Getz Tank Volume in Gallons: UST Manufacture: Type of Interstice: Depth To Top Tank: Tank Diameter: OPW Bravo Smith Smith Unisource Spill Buckets: