HomeMy WebLinkAbout5269_Bakersfield CA_ELD-PT_CERT_Jlog_231023 1100Providers for MDleak® MSleak® DPleak®, MCleak® and
PHDleak® Testing Technologies
Page 1 of 2
Test Type: Job #: 5269
Facility Name: PO #:
Prepared For:
Site Address:
City:
State and Zip: CA 93308
Start Date:End Date:
SYSTEM Test MDL TK-1 87 TK-2 87 TK-3 87 TK-4 91 TK-5 DSL TK-6 ADDTK- 7 DADD VR
Product Primary MDleak:0.005 GPH PASS PASS PASS PASS PASS PASS PASS
Product Secondary:0.005 GPH PASS PASS PASS PASS PASS PASS PASS
Vent Primary MDleak:0.005 GPH PASS PASS PASS PASS PASS PASS PASS
Vent Secondary:0.005 GPH PASS PASS PASS PASS PASS PASS PASS
VR Primary MDleak:0.005 GPH PASS PASS PASS PASS NA NA NA
VR Secondary:0.005 GPH PASS PASS PASS PASS NA NA NA
Turbine Sump Fittings:0.005 GPH PASS PASS PASS PASS PASS PASS PASS
Fill/Vapor Sump Fittings:0.005 GPH PASS PASS PASS PASS PASS PASS PASS
UDC Fittings:0.005 GPH FAIL PASS PASS PASS PASS NA NA FAIL
Vent Box Fittings 0.005 GPH PASS PASS PASS PASS PASS PASS PASS
Remote Fill Primary:0.005 GPH NA NA NA PASS PASS NA NA
Remote Fill Secondary:0.005 GPH NA NA NA PASS PASS NA NA
Remote Fill VR 1st 0.005 GPH NA NA NA PASS NA NA NA
Remote Fill 2nd 0.005 GPH NA NA NA PASS NA NA NA
Primary Syphon Line:0.005 GPH PASS PASS PASS NA NA NA NA
Syphon Secondary Syphon Line:0.005 GPH PASS PASS PASS NA NA NA NA
Chase Line 1st:0.005 GPH PASS PASS PASS PASS PASS NA NA
Chase Line 2nd 0.005 GPH PASS PASS PASS PASS PASS NA NA
Jones Covey Group, Inc.
Facility Certification CONFIDENTIAL
Costco #688
10/3/20239/27/2023
3800 Rosedale HWY
Bakersfiled
Providers for MDleak® MSleak® DPleak®, MCleak® and
PHDleak® Testing Technologies
Page 2 of 2
Test Type:
Facility Name: Job #: 5269
Prepared For: PO #:
Site Address:
City:
State and Zip: CA 93308
Start Date:End Date:
SYSTEM TK-1 87 TK-2 87 TK-3 87 TK-4 91 TK-5 DSL TK-6 ADDTK- 7 DADD VR
20000 20000 20000 30000 20000 2000 1500
CSI CSI CSI Xerxes CSI CSI CSI
Brine Brine Brine Brine Brine Brine Brine
Tank Sump Boots Turbine
Bravo Bravo
15.00 0 0 0
Manufacture
EVR:
Certifying Field Technician: State Lic. # :
Certification Leak Rate:
Certifying Technician Signature: Date:
Statement Confirmed by: Date:
Costco #688
Jones Covey Group, Inc.
Flex:
If you have any questions on the testing please do not hesitate to call. @ 855-255-5325.
I declare under penalty of perjury that I am a licensed tester in one of the above methods listed by the National
Workgroup on Leak Detection Evaluations (NWGLDE)organization and that the information contained in this report is
true and correct to the best of my knowledge.
This is a statement to confirm that the components listed above,at the time of testing,have been tested to a leak
sensitivity listed above by using one or more of the following DPleak®,MDleak®,MCleak and PHDleak®EPA aproved
Methods.These Methods are the most versatile and comprehensive testing procedures offered to the petroleum
industry.All petroleum owners and contractors which utilize the DPleak®,MDleak®,MCleak,and PHDleak®Method can
be assured that their facility has passed the Nation's highest standard in preventative leak detection.
21-1772
Facility Certification CONFIDENTIAL
Office use only
10/15/2023
Depth to Ground Water:
Component Manufacture:
UDC/Dispensers Information
Number of Dispensers:
Manufacture:
Shear Valve Manufacture:
Containment Boots:
Piping Information
Product Lines:
Vapor Return / Vent:
Depth of Liquid Within Tank:
10/3/2023
3800 Rosedale HWY
Bakersfiled
9/27/2023 10/3/2023
Ben Getz
Tank Volume in Gallons:
UST Manufacture:
Type of Interstice:
Depth To Top Tank:
Tank Diameter:
OPW
Bravo
Smith
Smith
Unisource
Spill Buckets: