HomeMy WebLinkAboutFMC 2023Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10155965 10-5-23
Jaco #5562 Fastrip #6
1640 S Chester Ave Bakersfield 93304
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Rockland Kirk
1073967
10241356 9-29-24
VMI #5255 10-3-24
GVR C32654 9-28-24
10-5-23 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder-Root TLS-350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 UNL1 STP
L2 420 UNL1 ANN
L3 208 DIESEL STP
L4 420 DIESEL ANN
L5 208 PNL STP
L6 420 PNL ANN
L7 208 UNL2 SYPH STP
L8 420 UNL2 SYPH ANN
L9 208 DISP 1-2
L10 208 DISP 3-4
L11 208 DISP 5-6
L12 208 DISP 7-8
L13 208 TRAN NO.
L14 208 TRAN SO
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V UNL1, UNL2 SYPH
T2 FX1DV DIESEL
T3 FX1V PNL
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
T1 107 UNL
T2 197 DIESEL
T3 107 PNL
T4 107 UNL2
Pulled approx 4 gal out of rim of DSL STP. Also wiped fluid out of UDC 1-2 and North Transition Sump with rags.
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
NOPARKING
ASTPL5
STPL3
STPL1
STPL7
12,000 GALLON87-1 UNLEADED
12,000 GALLON87-2 UNLEADEDSIPHON
12,000 GALLONDIESEL
12,000 GALLON91 PREMIUM VF L6
F A
V
L4
AF
L13
L2
VF AL8
L10 L12
L11L9
L14
12 56
7 834
EXISTING BUILDING
GHW
PROPERTY LINE
CHESTER AVE MING AVEPROPERTY LINEN
CATCHBASINPRICE SIGN40' STORAGE CONTAINERDUMPSTER
ALLEYALLEY
LEGEND
L1 87-1 STP
L2 87-1 ANNULAR
L3 DSL STP
L4 DSL ANNULAR
L5 91 STP
L6 91 ANNULAR
L7 87-2 SIPHON STP
L8 87-2 ANNULAR
L9 UDC 1 - 2
L10 UDC 3 - 4
L11 UDC 5 - 6
L12 UDC 7 - 8
L13 N TRANS SUMP
L14 S TRANS SUMP
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 2 INCH SINGLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
UST ELECTRICAL PANEL
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
G
A
H
P
V
SITE MAP
PROJECT OWNER:
JACO HILL
PO. BOX 82515
BAKERSFIELD, CA 93308
CONTACT:
SITE PLOT PLAN FOR:
FACILITY 015-021-002928
CERS 10155965
FASTRIP #5562
1640 S CHESTER AVE.
BAKERSFIELD, CA 93304
10/24/16 REV.
C1
VICINITY MAP
PROJECT DATA
1"=10'-0"
INCHES012
SHEET SIZE 22 X 34
SCALE:
1640 S CHESTER AVE.
BAKERSFIELD, CA 93304
S CH
ES
T
ER
AVE
MING AVE
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Jaco #5562 Fastrip #61640 S Chester AveBakersfield101559651-21-2 3-4878991DSL87899187891-21-23-43-45-65-6ProductProductProductProductProductProductProductProductProductRockland Kirk
APPENDIX C-10
7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB917-8ProductProduct7-889877-8ProductProduct5-6DSL915-6ProductRockland Kirk
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10155965 10-5-23
Jaco #5562 Fastrip #6
1640 S Chester Ave Bakersfield 93304
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Rockland Kirk
1073967
10241356 9-29-24
OPW PHASE 1 EVR 1193547 2-15-25
RP 1200 SPILL BUCKETS
10-5-23 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1 UNL
OPW
T2 DSL
OPW
T3 PNL
OPW
T4 UNL2
OPW
Responses Received:
200
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
OCT 5, 2023 1:30 PM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNL 9748 72.32 0.0 79.0 2314
2 DIESEL 4281 36.96 0.0 85.5 7781
3 PNL 7205 55.37 0.0 80.4 4857
4 UNL 2 SIPHON 9009 67.13 0.0 78.1 3053
I90500
OCT 5, 2023 1:30 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
OCT 5, 2023 1:30 PM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
OCT 5, 2023 1:30 PM
SHIFT TIME 1 : DISABLED
I50202
OCT 5, 2023 1:30 PM
SHIFT TIME 2 : DISABLED
I50203
OCT 5, 2023 1:30 PM
SHIFT TIME 3 : DISABLED
I50204
OCT 5, 2023 1:30 PM
SHIFT TIME 4 : DISABLED
I54600
OCT 5, 2023 1:30 PM
TANK PER TST NEEDED WRN: DISABLED
I54900
OCT 5, 2023 1:30 PM
TANK ANN TST NEEDED WRN: DISABLED
I55300
OCT 5, 2023 1:30 PM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
OCT 5, 2023 1:30 PM
LINE PER TST NEEDED WRN: DISABLED
I55900
OCT 5, 2023 1:30 PM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
OCT 5, 2023 1:30 PM
PRINT TC VOLUMES
ENABLED
I50E00
OCT 5, 2023 1:30 PM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
OCT 5, 2023 1:30 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
OCT 5, 2023 1:30 PM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
OCT 5, 2023 1:30 PM
DAYLIGHT SAVING TIME
ENABLED ON
I51B00
OCT 5, 2023 1:30 PM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
OCT 5, 2023 1:30 PM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
OCT 5, 2023 1:30 PM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
OCT 5, 2023 1:30 PM
TANK CHART SECURITY
DISABLED
I5BD00
OCT 5, 2023 1:30 PM
CUSTOM ALARM LABELS
DISABLED
I56000
OCT 5, 2023 1:31 PM
MASS/DENSITY
DISABLED
I88101
OCT 5, 2023 1:31 PM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88102
OCT 5, 2023 1:31 PM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
OCT 5, 2023 1:31 PM
PORT SETTINGS:
COMM BOARD : 3 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88104
OCT 5, 2023 1:31 PM
I88105
OCT 5, 2023 1:31 PM
I88106
OCT 5, 2023 1:31 PM
I52000
OCT 5, 2023 1:31 PM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE FEB 28, 2020 DISABLED
2 ON DATE FEB 28, 2020 DISABLED
3 ON DATE FEB 28, 2020 DISABLED
4 ON DATE FEB 28, 2020 DISABLED
5 ON DATE FEB 28, 2020 DISABLED
6 ON DATE FEB 28, 2020 DISABLED
7 ON DATE FEB 28, 2020 DISABLED
8 ON DATE FEB 28, 2020 DISABLED
I60100
OCT 5, 2023 1:31 PM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNL ON
2 DIESEL ON
3 PNL ON
4 UNL 2 SIPHON ON
I60200
OCT 5, 2023 1:31 PM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNL
2 DIESEL
3 PNL
4 UNL 2 SIPHON
I60300
OCT 5, 2023 1:31 PM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNL 1
2 DIESEL 2
3 PNL 3
4 UNL 2 SIPHON 4
I60900
OCT 5, 2023 1:31 PM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNL 0.000700
2 DIESEL 0.000450
3 PNL 0.000700
4 UNL 2 SIPHON 0.000700
I60700
OCT 5, 2023 1:31 PM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNL 96.00
2 DIESEL 96.00
3 PNL 96.00
4 UNL 2 SIPHON 96.00
I60A00
OCT 5, 2023 1:31 PM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL
1 PT 12062 2 DIESEL 1 PT 12062 3 PNL
1 PT 12062 4 UNL 2 SIPHON 1 PT 12062
I60400
OCT 5, 2023 1:31 PM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 12062
2 DIESEL 12062
3 PNL 12062
4 UNL 2 SIPHON 12062
I60500
OCT 5, 2023 1:31 PM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNL 12062 0 0 0
2 DIESEL 12062 0 0 0
3 PNL 12062 0 0 0
4 UNL 2 SIPHON 12062 0 0 0
I60600
OCT 5, 2023 1:31 PM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNL 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 DIESEL 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 PNL 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 UNL 2 SIPHON 12062 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
OCT 5, 2023 1:31 PM
TANK PRODUCT LABEL METER DATA
1 UNL NO
2 DIESEL NO
3 PNL NO
4 UNL 2 SIPHON NO
I62F00
OCT 5, 2023 1:31 PM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNL 4.0 IN.
2 DIESEL 4.0 IN.
3 PNL 3.0 IN.
4 UNL 2 SIPHON 3.0 IN.
I62700
OCT 5, 2023 1:31 PM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNL 2.0
2 DIESEL 2.0
3 PNL 2.0
4 UNL 2 SIPHON 2.0
I64200
OCT 5, 2023 1:31 PM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNL LOW
2 DIESEL LOW
3 PNL LOW
4 UNL 2 SIPHON LOW
I62400
OCT 5, 2023 1:31 PM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNL 3.0
2 DIESEL 3.0
3 PNL 3.0
4 UNL 2 SIPHON 3.0
I62800
OCT 5, 2023 1:31 PM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 12062
2 DIESEL 12062
3 PNL 12062
4 UNL 2 SIPHON 12062
I62300
OCT 5, 2023 1:31 PM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 10856
2 DIESEL 10856
3 PNL 10856
4 UNL 2 SIPHON 10856
I62200
OCT 5, 2023 1:31 PM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 11459
2 DIESEL 11459
3 PNL 11459
4 UNL 2 SIPHON 11459
I62900
OCT 5, 2023 1:31 PM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1809
2 DIESEL 1809
3 PNL 1809
4 UNL 2 SIPHON 1809
I62100
OCT 5, 2023 1:31 PM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 500
2 DIESEL 500
3 PNL 500
4 UNL 2 SIPHON 500
I62600
OCT 5, 2023 1:31 PM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 99
2 DIESEL 99
3 PNL 99
4 UNL 2 SIPHON 99
I62500
OCT 5, 2023 1:31 PM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 99
2 DIESEL 99
3 PNL 99
4 UNL 2 SIPHON 99
I60800
OCT 5, 2023 1:31 PM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNL 4.50
2 DIESEL -3.00
3 PNL 4.30
4 UNL 2 SIPHON 4.44
I60B00
OCT 5, 2023 1:31 PM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
OCT 5, 2023 1:31 PM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNL 0.00
2 DIESEL 0.00
3 PNL 0.00
4 UNL 2 SIPHON 0.00
I61200
OCT 5, 2023 1:31 PM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNL NONE NONE
2 DIESEL NONE NONE
3 PNL NONE NONE
4 UNL 2 SIPHON NONE NONE
I63600
OCT 5, 2023 1:31 PM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 1220
2 DIESEL 120
3 PNL 120
4 UNL 2 SIPHON 120
I62A00
OCT 5, 2023 1:31 PM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNL 0
2 DIESEL 0
3 PNL 0
4 UNL 2 SIPHON 120
I62C00
OCT 5, 2023 1:31 PM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNL STANDARD
2 DIESEL STANDARD
3 PNL STANDARD
4 UNL 2 SIPHON STANDARD
I62D00
OCT 5, 2023 1:31 PM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
2 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 PNL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 UNL 2 SIPHON GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
OCT 5, 2023 1:31 PM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNL OFF OFF
2 DIESEL OFF OFF
3 PNL OFF OFF
4 UNL 2 SIPHON OFF OFF
I63000
OCT 5, 2023 1:31 PM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNL OFF
2 DIESEL OFF
3 PNL OFF
4 UNL 2 SIPHON OFF
I63200
OCT 5, 2023 1:31 PM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNL OFF
2 DIESEL OFF
3 PNL OFF
4 UNL 2 SIPHON OFF
I61000
OCT 5, 2023 1:31 PM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNL 1
2 DIESEL 1
3 PNL 1
4 UNL 2 SIPHON 1
I63A00
OCT 5, 2023 1:31 PM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNL 10.00%
2 DIESEL 10.00%
3 PNL 10.00%
4 UNL 2 SIPHON 10.00%
I61100
OCT 5, 2023 1:31 PM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : TANK 1
MAR 19, 2009
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
TEST ON DATE : TANK 2
MAR 19, 2009
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
TEST ON DATE : TANK 3
MAR 19, 2009
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
TEST ON DATE : TANK 4
MAR 19, 2009
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
OCT 5, 2023 1:31 PM
CSLD PROBABLITY OF DETECTION
I61400
OCT 5, 2023 1:31 PM
CSLD CLIMATE FACTOR
I61600
OCT 5, 2023 1:31 PM
TANK PRODUCT LABEL CAL UPDATE
1 UNL IMMEDIATE
2 DIESEL IMMEDIATE
3 PNL IMMEDIATE
4 UNL 2 SIPHON IMMEDIATE
I61A00
OCT 5, 2023 1:31 PM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNL DISABLED
2 DIESEL DISABLED
3 PNL DISABLED
4 UNL 2 SIPHON DISABLED
I61B00
OCT 5, 2023 1:31 PM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
OCT 5, 2023 1:31 PM
CSLD REPORT ONLY
I62B00
OCT 5, 2023 1:31 PM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNL ??? 0, 0
2 DIESEL ??? 0, 0
3 PNL ??? 0, 0
4 UNL 2 SIPHON ??? 0, 0
I63300
OCT 5, 2023 1:31 PM
LEAK TEST REPORT FORMAT: NORMAL
I63400
OCT 5, 2023 1:31 PM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 0
2 DIESEL 0
3 PNL 0
4 UNL 2 SIPHON 0
I63500
OCT 5, 2023 1:31 PM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNL 1
2 DIESEL 1
3 PNL 1
4 UNL 2 SIPHON 1
I63900
OCT 5, 2023 1:31 PM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNL
END FACTOR: NONE
2 DIESEL
END FACTOR: NONE
3 PNL
END FACTOR: NONE
4 UNL 2 SIPHON
END FACTOR: NONE
I78000
OCT 5, 2023 1:31 PM
I77700
OCT 5, 2023 1:31 PM
I77800
OCT 5, 2023 1:31 PM
I78C00
OCT 5, 2023 1:31 PM
I78300
OCT 5, 2023 1:31 PM
I78F00
OCT 5, 2023 1:31 PM
I78700
OCT 5, 2023 1:31 PM
I70200
OCT 5, 2023 1:31 PM
LIQUID LABEL
DEVICE LABEL
1 UNL 1 STP
2 UNL1 ANN
3 DIESEL STP
4 DIESEL ANN
5 PNL STP
6 PNL ANN
7 UNL2 SIPON STP
8 UNL2 ANN
9 DISP 1-2
10 DISP 3-4
11 DISP 5-6
12 DISP 7-8
13 TRAN NO.
14 TRAN SO.
15
16
I70300
OCT 5, 2023 1:31 PM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNL 1 STP TRI-STATE (SINGLE FLOAT)
2 UNL1 ANN TRI-STATE (SINGLE FLOAT)
3 DIESEL STP TRI-STATE (SINGLE FLOAT)
4 DIESEL ANN TRI-STATE (SINGLE FLOAT)
5 PNL STP TRI-STATE (SINGLE FLOAT)
6 PNL ANN TRI-STATE (SINGLE FLOAT)
7 UNL2 SIPON STP TRI-STATE (SINGLE FLOAT)
8 UNL2 ANN TRI-STATE (SINGLE FLOAT)
9 DISP 1-2 TRI-STATE (SINGLE FLOAT)
10 DISP 3-4 TRI-STATE (SINGLE FLOAT)
11 DISP 5-6 TRI-STATE (SINGLE FLOAT)
12 DISP 7-8 TRI-STATE (SINGLE FLOAT)
13 TRAN NO. TRI-STATE (SINGLE FLOAT)
14 TRAN SO. TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
OCT 5, 2023 1:31 PM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNL 1 STP STP SUMP
2 UNL1 ANN ANNULAR SPACE
3 DIESEL STP STP SUMP
4 DIESEL ANN ANNULAR SPACE
5 PNL STP STP SUMP
6 PNL ANN ANNULAR SPACE
7 UNL2 SIPON STP STP SUMP
8 UNL2 ANN ANNULAR SPACE
9 DISP 1-2 DISPENSER PAN
10 DISP 3-4 DISPENSER PAN
11 DISP 5-6 DISPENSER PAN
12 DISP 7-8 DISPENSER PAN
13 TRAN NO. PIPING SUMP
14 TRAN SO. PIPING SUMP
15 OTHER SENSORS
16 OTHER SENSORS
I74200
OCT 5, 2023 1:31 PM
I74300
OCT 5, 2023 1:31 PM
I74400
OCT 5, 2023 1:31 PM
I74700
OCT 5, 2023 1:31 PM
I74800
OCT 5, 2023 1:31 PM
I74900
OCT 5, 2023 1:31 PM
I7BC00
OCT 5, 2023 1:31 PM
I80200
OCT 5, 2023 1:31 PM
I80300
OCT 5, 2023 1:31 PM
I80400
OCT 5, 2023 1:31 PM
I80700
OCT 5, 2023 1:31 PM
RELAY LABEL
DEVICE LABEL
1 UNL 1
2 DIESEL
3 PNL
4
5 OVERFILL ALARM
6
7
8
I80900
OCT 5, 2023 1:31 PM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNL 1 NORMALLY OPEN
2 DIESEL NORMALLY CLOSED
3 PNL NORMALLY OPEN
4 NORMALLY OPEN
5 OVERFILL ALARM NORMALLY OPEN
6 NORMALLY OPEN
7 NORMALLY OPEN
8 NORMALLY OPEN
I80B00
OCT 5, 2023 1:31 PM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNL 1 1
2 DIESEL 2
3 PNL 3
4 NONE
5 OVERFILL ALARM NONE
6 NONE
7 NONE
8 NONE
I80A00
OCT 5, 2023 1:31 PM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNL 1 PUMP CONTROL OUTPUT
2 DIESEL STANDARD
3 PNL PUMP CONTROL OUTPUT
4 STANDARD
5 OVERFILL ALARM STANDARD
6 STANDARD
7 STANDARD
8 STANDARD
I80C00
OCT 5, 2023 1:31 PM
I80800
OCT 5, 2023 1:31 PM
RELAY SETUP REPORT
R 1:UNL 1
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 1:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 1:SHORT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:DIESEL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 9:FUEL ALARM
L11:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 3:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 9:SHORT ALARM
L11:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
R 3:PNL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 3
LIQUID SENSOR ALMS
L 5:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L 5:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 5:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 6:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 7:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 8:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
OCT 5, 2023 1:32 PM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
OCT 5, 2023 1:32 PM
I72300
OCT 5, 2023 1:32 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 V.P.SENSOR DISP 3-4 VAPOR PRESSURE
02 F.M.DISP 1-2 AIR FLOW METER
03 F.M.DISP 3-4 AIR FLOW METER
04 F.M.DISP 5-6 AIR FLOW METER
05 F.M.DISP 7-8 AIR FLOW METER
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
OCT 5, 2023 1:32 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
OCT 5, 2023 1:32 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
OCT 5, 2023 1:32 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
VAPOR PROCESSOR TYPE
NONE
IV4700
OCT 5, 2023 1:32 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
OCT 5, 2023 1:32 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
ACCEPT HIGH ORVR: YES
IV4A00
OCT 5, 2023 1:32 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 03 BLEND3
02 02 02 01 03 BLEND3
03 03 03 02 03 BLEND3
04 04 04 02 03 BLEND3
05 05 05 03 03 BLEND3
06 06 06 03 03 BLEND3
07 07 07 04 03 BLEND3
08 08 08 04 03 BLEND3
IV4B00
OCT 5, 2023 1:32 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
IV4900
OCT 5, 2023 1:32 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
OCT 5, 2023 1:32 PM
ISD VERSION: 01.07
Responses Received:
I10200
OCT 5, 2023 1:28 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 509328 507862
2 4 PROBE / G.T. 161808 161479
3 INTERSTITIAL BD 202847 202275
4 INTERSTITIAL BD 202871 202491
5 UNUSED 4718355 4784002
6 UNUSED 4717361 4777812
7 UNUSED 4715263 4774442
8 UNUSED 4709191 4783870
9 STP SENSE BOARD 33285 33164
10 RELAY BOARD 14947 14896
11 RELAY BOARD 15036 14984
12 UNUSED 4719178 4783901
13 UNUSED 4712774 4779473
14 UNUSED 4714717 4777645
15 UNUSED 4712598 4782205
16 UNUSED 4716528 4779958
COMM 1 RS232 SERIAL BD 14969 14918
COMM 2 RS232 SERIAL BD 15014 14962
COMM 3 ELEC DISP INT. 101433 101210
COMM 4 UNUSED 4715998 4780729
COMM 5 UNUSED 4712774 4781081
COMM 6 UNUSED 4713591 4779759
I90200
OCT 5, 2023 1:28 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
OCT 5, 2023 1:28 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 4 TANK UNL 2 SIPHON OVERFILL ALARM CLEAR 10-05-23 3:24AM
T 4 TANK UNL 2 SIPHON OVERFILL ALARM ALARM 10-05-23 3:20AM
T 1 TANK UNL OVERFILL ALARM CLEAR 10-03-23 7:09PM
T 1 TANK UNL OVERFILL ALARM ALARM 10-03-23 7:07PM
T 1 TANK UNL SUDDEN LOSS ALARM CLEAR 9-26-23 1:11PM
T 3 TANK PNL SUDDEN LOSS ALARM CLEAR 9-26-23 1:11PM
T 1 TANK UNL SUDDEN LOSS ALARM ALARM 9-26-23 12:29PM
T 3 TANK PNL SUDDEN LOSS ALARM ALARM 9-26-23 12:27PM
L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L 7 STP SUMP UNL2 SIPON STP SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L 3 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L 5 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L14 PIPE TRAN SO. SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L13 PIPE TRAN NO. SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 9-26-23 10:19AM
L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L 7 STP SUMP UNL2 SIPON STP SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L 3 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L14 PIPE TRAN SO. SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L 5 STP SUMP PNL STP SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L13 PIPE TRAN NO. SENSOR OUT ALARM ALARM 9-26-23 10:19AM
L 8 ANNULAR UNL2 ANN FUEL ALARM CLEAR 9-26-23 10:16AM
L 2 ANNULAR UNL1 ANN FUEL ALARM CLEAR 9-26-23 10:15AM
L 2 ANNULAR UNL1 ANN FUEL ALARM ALARM 9-26-23 10:15AM
L 8 ANNULAR UNL2 ANN FUEL ALARM ALARM 9-26-23 10:15AM
L 4 ANNULAR DIESEL ANN FUEL ALARM CLEAR 9-26-23 10:15AM
L 6 ANNULAR PNL ANN FUEL ALARM CLEAR 9-26-23 10:15AM
L 6 ANNULAR PNL ANN FUEL ALARM ALARM 9-26-23 10:14AM
L 4 ANNULAR DIESEL ANN FUEL ALARM ALARM 9-26-23 10:14AM
L14 PIPE TRAN SO. FUEL ALARM CLEAR 9-26-23 10:13AM
L14 PIPE TRAN SO. FUEL ALARM ALARM 9-26-23 10:13AM
L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 9-26-23 10:12AM
L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 9-26-23 10:12AM
L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 9-26-23 10:12AM
L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 9-26-23 10:12AM
I11200
OCT 5, 2023 1:28 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 9-09-23 6:02AM
SYSTEM PAPER OUT CLEAR 9-09-23 6:02AM
SYSTEM PRINTER ERROR ALARM 9-09-23 5:59AM
SYSTEM PAPER OUT ALARM 9-09-23 5:59AM
T 1 TANK UNL HIGH PRODUCT ALARM CLEAR 9-04-23 1:08PM
T 1 TANK UNL HIGH PRODUCT ALARM ALARM 9-04-23 1:02PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 9-02-23 10:00AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 9-01-23 10:01AM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 8-27-23 10:00AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 8-27-23 10:00AM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN ALARM 8-26-23 10:01AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN ALARM 8-26-23 10:01AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 8-20-23 10:00AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 8-19-23 10:01AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM
SYSTEM PAPER OUT ALARM 8-14-23 7:38AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM
SYSTEM PAPER OUT ALARM 8-14-23 7:38AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM
SYSTEM PAPER OUT ALARM 8-14-23 7:38AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM
SYSTEM PAPER OUT ALARM 8-14-23 7:38AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:37AM
SYSTEM PAPER OUT ALARM 8-14-23 7:37AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:37AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:37AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:37AM
SYSTEM PAPER OUT ALARM 8-14-23 7:37AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:37AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:37AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:34AM
SYSTEM PAPER OUT ALARM 8-14-23 7:34AM
OTHER ISD VAPOR LEAK WARN CLEAR 7-28-23 10:00AM
OTHER ISD VAPOR LEAK WARN ALARM 7-27-23 10:01AM
T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-19-23 6:52PM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-19-23 1:33PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 7-05-23 10:00AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 7-04-23 10:01AM
T 2 TANK DIESEL DELIVERY NEEDED CLEAR 6-22-23 2:57PM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 6-22-23 12:37PM
I20600
OCT 5, 2023 1:28 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
TANK ALARM HISTORY
TANK 1 UNL
OVERFILL ALARM OCT 3, 2023 7:07 PM
SEP 7, 2023 7:44 PM
SEP 7, 2023 7:35 PM
SUDDEN LOSS ALARM SEP 26, 2023 12:29 PM
JUN 6, 2023 1:32 AM
JUN 6, 2023 1:10 AM
HIGH PRODUCT ALARM SEP 4, 2023 1:02 PM
TANK 2 DIESEL
DELIVERY NEEDED JUL 19, 2023 1:33 PM
JUN 22, 2023 12:37 PM
APR 24, 2023 11:07 AM
TANK 3 PNL
OVERFILL ALARM FEB 26, 2023 12:23 PM
SUDDEN LOSS ALARM SEP 26, 2023 12:27 PM
TANK 4 UNL 2 SIPHON
OVERFILL ALARM OCT 5, 2023 3:20 AM
DEC 11, 2022 5:34 PM
SEP 24, 2022 5:01 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
OCT 5, 2023 1:29 PM
I30200
OCT 5, 2023 1:29 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL 1 STP
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:08 AM FUEL ALARM
SEP 13, 2023 2:56 PM FUEL ALARM
2 UNL1 ANN
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:15 AM FUEL ALARM
SEP 13, 2023 3:05 PM FUEL ALARM
3 DIESEL STP
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:08 AM FUEL ALARM
SEP 13, 2023 2:56 PM FUEL ALARM
4 DIESEL ANN
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:14 AM FUEL ALARM
SEP 13, 2023 3:05 PM FUEL ALARM
5 PNL STP
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:08 AM FUEL ALARM
SEP 13, 2023 2:55 PM FUEL ALARM
6 PNL ANN
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:14 AM FUEL ALARM
SEP 13, 2023 3:04 PM FUEL ALARM
7 UNL2 SIPON STP
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:09 AM FUEL ALARM
SEP 13, 2023 1:39 PM SENSOR OUT ALARM
8 UNL2 ANN
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:15 AM FUEL ALARM
SEP 13, 2023 3:05 PM FUEL ALARM
9 DISP 1-2
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:12 AM FUEL ALARM
SEP 26, 2023 10:12 AM FUEL ALARM
10 DISP 3-4
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:10 AM FUEL ALARM
SEP 13, 2023 1:39 PM SENSOR OUT ALARM
11 DISP 5-6
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:11 AM FUEL ALARM
SEP 13, 2023 1:38 PM SENSOR OUT ALARM
12 DISP 7-8
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:10 AM FUEL ALARM
SEP 13, 2023 1:38 PM SENSOR OUT ALARM
13 TRAN NO.
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:11 AM FUEL ALARM
SEP 13, 2023 1:38 PM SENSOR OUT ALARM
14 TRAN SO.
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
SEP 26, 2023 10:13 AM FUEL ALARM
SEP 13, 2023 1:38 PM SENSOR OUT ALARM
I31600
OCT 5, 2023 1:29 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 V.P.SENSOR DISP 3-4
2 F.M.DISP 1-2
3 F.M.DISP 3-4
4 F.M.DISP 5-6
5 F.M.DISP 7-8
I40200
OCT 5, 2023 1:29 PM
I40300
OCT 5, 2023 1:29 PM
I34200
OCT 5, 2023 1:29 PM
I34700
OCT 5, 2023 1:29 PM
IV0100
OCT 5, 2023 1:29 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-09-01 10:01:55 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
23-08-26 10:01:45 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
23-08-26 10:01:45 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
23-08-19 10:01:59 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
23-07-27 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.82
23-07-04 10:01:14 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
23-06-17 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.68
23-06-02 10:01:22 A/L RATIO DEGRADATION FP 8 BLEND3 0.80
23-05-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-05-17 10:01:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-08-27 10:01:33 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
23-08-27 10:01:33 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
23-05-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
22-07-03 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.76
22-05-26 10:01:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
22-05-26 10:01:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
22-02-21 10:01:43 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-02-21 10:01:42 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-02-20 10:01:42 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-02-20 10:01:41 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-09-27 10:01:37 READINESS ISD:PP EVR:PP ISD & EVR READY
23-09-26 10:17:38 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-09-26 10:17:38 ISD STARTUP
23-09-26 10:17:25 ISD SHUTDOWN
23-09-14 10:01:49 READINESS ISD:PP EVR:PP ISD & EVR READY
23-09-13 13:36:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-09-13 13:36:39 ISD STARTUP
23-09-13 13:35:14 ISD SHUTDOWN
23-09-07 19:22:41 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
23-08-28 09:35:03 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
Responses Received:
I10200
OCT 5, 2023 4:11 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 509328 507844
2 4 PROBE / G.T. 161808 161362
3 INTERSTITIAL BD 202847 202044
4 INTERSTITIAL BD 202871 202308
5 UNUSED 4718355 4661856
6 UNUSED 4717361 4657445
7 UNUSED 4715263 4657908
8 UNUSED 4709191 4650763
9 STP SENSE BOARD 33285 33136
10 RELAY BOARD 14947 14888
11 RELAY BOARD 15036 14999
12 UNUSED 4719178 4661929
13 UNUSED 4712774 4655137
14 UNUSED 4714717 4651807
15 UNUSED 4712598 4653417
16 UNUSED 4716528 4655313
COMM 1 RS232 SERIAL BD 14969 14910
COMM 2 RS232 SERIAL BD 15014 14976
COMM 3 ELEC DISP INT. 101433 101125
COMM 4 UNUSED 4715998 4657188
COMM 5 UNUSED 4712774 4656129
COMM 6 UNUSED 4713591 4659900
I90200
OCT 5, 2023 4:11 PM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
OCT 5, 2023 4:11 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 2 ANNULAR UNL1 ANN FUEL ALARM CLEAR 10-05-23 2:14PM
L 8 ANNULAR UNL2 ANN FUEL ALARM CLEAR 10-05-23 2:14PM
L 4 ANNULAR DIESEL ANN FUEL ALARM CLEAR 10-05-23 2:14PM
L 6 ANNULAR PNL ANN FUEL ALARM CLEAR 10-05-23 2:14PM
L 8 ANNULAR UNL2 ANN FUEL ALARM ALARM 10-05-23 2:13PM
L 2 ANNULAR UNL1 ANN FUEL ALARM ALARM 10-05-23 2:13PM
L 4 ANNULAR DIESEL ANN FUEL ALARM ALARM 10-05-23 2:13PM
L 6 ANNULAR PNL ANN FUEL ALARM ALARM 10-05-23 2:13PM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L 5 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L 3 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L13 PIPE TRAN NO. SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L14 PIPE TRAN SO. SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L 7 STP SUMP UNL2 SIPON STP SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 10-05-23 1:55PM
L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L 7 STP SUMP UNL2 SIPON STP SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L14 PIPE TRAN SO. SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L 3 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L13 PIPE TRAN NO. SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L 5 STP SUMP PNL STP SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 10-05-23 1:51PM
L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 10-05-23 1:47PM
L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 10-05-23 1:46PM
L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 10-05-23 1:45PM
L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 10-05-23 1:45PM
L13 PIPE TRAN NO. FUEL ALARM CLEAR 10-05-23 1:44PM
L13 PIPE TRAN NO. FUEL ALARM ALARM 10-05-23 1:44PM
L14 PIPE TRAN SO. FUEL ALARM CLEAR 10-05-23 1:43PM
L14 PIPE TRAN SO. FUEL ALARM ALARM 10-05-23 1:43PM
L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 10-05-23 1:42PM
L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 10-05-23 1:42PM
L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 10-05-23 1:41PM
L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 10-05-23 1:41PM
L 5 STP SUMP PNL STP FUEL ALARM CLEAR 10-05-23 1:40PM
L 5 STP SUMP PNL STP FUEL ALARM ALARM 10-05-23 1:40PM
I11200
OCT 5, 2023 4:12 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 10-05-23 1:53PM
SYSTEM PAPER OUT CLEAR 10-05-23 1:53PM
SYSTEM PRINTER ERROR ALARM 10-05-23 1:51PM
SYSTEM PAPER OUT ALARM 10-05-23 1:51PM
SYSTEM PRINTER ERROR CLEAR 9-09-23 6:02AM
SYSTEM PAPER OUT CLEAR 9-09-23 6:02AM
SYSTEM PRINTER ERROR ALARM 9-09-23 5:59AM
SYSTEM PAPER OUT ALARM 9-09-23 5:59AM
T 1 TANK UNL HIGH PRODUCT ALARM CLEAR 9-04-23 1:08PM
T 1 TANK UNL HIGH PRODUCT ALARM ALARM 9-04-23 1:02PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 9-02-23 10:00AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 9-01-23 10:01AM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 8-27-23 10:00AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 8-27-23 10:00AM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN ALARM 8-26-23 10:01AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN ALARM 8-26-23 10:01AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 8-20-23 10:00AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 8-19-23 10:01AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM
SYSTEM PAPER OUT ALARM 8-14-23 7:38AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM
SYSTEM PAPER OUT ALARM 8-14-23 7:38AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM
SYSTEM PAPER OUT ALARM 8-14-23 7:38AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM
SYSTEM PAPER OUT ALARM 8-14-23 7:38AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:37AM
SYSTEM PAPER OUT ALARM 8-14-23 7:37AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:37AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:37AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:37AM
SYSTEM PAPER OUT ALARM 8-14-23 7:37AM
SYSTEM PRINTER ERROR CLEAR 8-14-23 7:37AM
SYSTEM PAPER OUT CLEAR 8-14-23 7:37AM
SYSTEM PRINTER ERROR ALARM 8-14-23 7:34AM
SYSTEM PAPER OUT ALARM 8-14-23 7:34AM
OTHER ISD VAPOR LEAK WARN CLEAR 7-28-23 10:00AM
OTHER ISD VAPOR LEAK WARN ALARM 7-27-23 10:01AM
T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-19-23 6:52PM
T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-19-23 1:33PM
I20600
OCT 5, 2023 4:12 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
TANK ALARM HISTORY
TANK 1 UNL
OVERFILL ALARM OCT 3, 2023 7:07 PM
SEP 7, 2023 7:44 PM
SEP 7, 2023 7:35 PM
SUDDEN LOSS ALARM SEP 26, 2023 12:29 PM
JUN 6, 2023 1:32 AM
JUN 6, 2023 1:10 AM
HIGH PRODUCT ALARM SEP 4, 2023 1:02 PM
TANK 2 DIESEL
DELIVERY NEEDED JUL 19, 2023 1:33 PM
JUN 22, 2023 12:37 PM
APR 24, 2023 11:07 AM
TANK 3 PNL
OVERFILL ALARM FEB 26, 2023 12:23 PM
SUDDEN LOSS ALARM SEP 26, 2023 12:27 PM
TANK 4 UNL 2 SIPHON
OVERFILL ALARM OCT 5, 2023 3:20 AM
DEC 11, 2022 5:34 PM
SEP 24, 2022 5:01 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
OCT 5, 2023 4:12 PM
I30200
OCT 5, 2023 4:12 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNL 1 STP
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:38 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
2 UNL1 ANN
OCT 5, 2023 2:13 PM FUEL ALARM
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
3 DIESEL STP
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:39 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
4 DIESEL ANN
OCT 5, 2023 2:13 PM FUEL ALARM
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
5 PNL STP
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:40 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
6 PNL ANN
OCT 5, 2023 2:13 PM FUEL ALARM
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
7 UNL2 SIPON STP
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:37 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
8 UNL2 ANN
OCT 5, 2023 2:13 PM FUEL ALARM
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
9 DISP 1-2
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:46 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
10 DISP 3-4
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:41 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
11 DISP 5-6
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:45 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
12 DISP 7-8
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:42 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
13 TRAN NO.
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:44 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
14 TRAN SO.
OCT 5, 2023 1:51 PM SENSOR OUT ALARM
OCT 5, 2023 1:43 PM FUEL ALARM
SEP 26, 2023 10:19 AM SENSOR OUT ALARM
I31600
OCT 5, 2023 4:12 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 V.P.SENSOR DISP 3-4
2 F.M.DISP 1-2
3 F.M.DISP 3-4
4 F.M.DISP 5-6
5 F.M.DISP 7-8
I40200
OCT 5, 2023 4:12 PM
I40300
OCT 5, 2023 4:12 PM
I34200
OCT 5, 2023 4:12 PM
I34700
OCT 5, 2023 4:12 PM
IV0100
OCT 5, 2023 4:12 PM
FASTRIP 562
MING-CHESTER
BAKERSFIELD CA
661-397-8606
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-09-01 10:01:55 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
23-08-26 10:01:45 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
23-08-26 10:01:45 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
23-08-19 10:01:59 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
23-07-27 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.82
23-07-04 10:01:14 A/L RATIO DEGRADATION FP 2 BLEND3 0.80
23-06-17 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.68
23-06-02 10:01:22 A/L RATIO DEGRADATION FP 8 BLEND3 0.80
23-05-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD
23-05-17 10:01:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-08-27 10:01:33 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
23-08-27 10:01:33 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
23-05-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
22-07-03 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.76
22-05-26 10:01:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD
22-05-26 10:01:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
22-02-21 10:01:43 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-02-21 10:01:42 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
22-02-20 10:01:42 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD
22-02-20 10:01:41 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-10-05 13:49:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-10-05 13:49:30 ISD STARTUP
23-10-05 13:48:27 ISD SHUTDOWN
23-09-27 10:01:37 READINESS ISD:PP EVR:PP ISD & EVR READY
23-09-26 10:17:38 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-09-26 10:17:38 ISD STARTUP
23-09-26 10:17:25 ISD SHUTDOWN
23-09-14 10:01:49 READINESS ISD:PP EVR:PP ISD & EVR READY
23-09-13 13:36:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-09-13 13:36:39 ISD STARTUP