HomeMy WebLinkAboutFMC 2023Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10155965 10-5-23 Jaco #5562 Fastrip #6 1640 S Chester Ave Bakersfield 93304 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Rockland Kirk 1073967 10241356 9-29-24 VMI #5255 10-3-24 GVR C32654 9-28-24 10-5-23 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder-Root TLS-350 336.02 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 UNL1 STP L2 420 UNL1 ANN L3 208 DIESEL STP L4 420 DIESEL ANN L5 208 PNL STP L6 420 PNL ANN L7 208 UNL2 SYPH STP L8 420 UNL2 SYPH ANN L9 208 DISP 1-2 L10 208 DISP 3-4 L11 208 DISP 5-6 L12 208 DISP 7-8 L13 208 TRAN NO. L14 208 TRAN SO Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V UNL1, UNL2 SYPH T2 FX1DV DIESEL T3 FX1V PNL Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ T1 107 UNL T2 197 DIESEL T3 107 PNL T4 107 UNL2 Pulled approx 4 gal out of rim of DSL STP. Also wiped fluid out of UDC 1-2 and North Transition Sump with rags. Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. NOPARKING ASTPL5 STPL3 STPL1 STPL7 12,000 GALLON87-1 UNLEADED 12,000 GALLON87-2 UNLEADEDSIPHON 12,000 GALLONDIESEL 12,000 GALLON91 PREMIUM VF L6 F A V L4 AF L13 L2 VF AL8 L10 L12 L11L9 L14 12 56 7 834 EXISTING BUILDING GHW PROPERTY LINE CHESTER AVE MING AVEPROPERTY LINEN CATCHBASINPRICE SIGN40' STORAGE CONTAINERDUMPSTER ALLEYALLEY LEGEND L1 87-1 STP L2 87-1 ANNULAR L3 DSL STP L4 DSL ANNULAR L5 91 STP L6 91 ANNULAR L7 87-2 SIPHON STP L8 87-2 ANNULAR L9 UDC 1 - 2 L10 UDC 3 - 4 L11 UDC 5 - 6 L12 UDC 7 - 8 L13 N TRANS SUMP L14 S TRANS SUMP 87 GAS 3/2 INCH DBL WALLED PIPE 91 GAS 3/2 INCH DBL WALLED PIPE DIESEL 3/2 INCH DBL WALLED PIPE VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE VAPOR VENT 2 INCH SINGLE WALLED PIPE PRODUCT SPILL CONTAINER VAPOR SPILL CONTAINER ANNULAR EMERGENCY SHUT-OFF OVERFILL ALARM FIRE EXTINGUISHER GAS METER SHUT-OFF HEALY CAS EVACUATION MEETING POINT CIRCUIT BREAKER UST ELECTRICAL PANEL AUTOMATIC TANK GAUGE AIR AND WATER DISPENSER HAZWASTE DRUM G A H P V SITE MAP PROJECT OWNER: JACO HILL PO. BOX 82515 BAKERSFIELD, CA 93308 CONTACT: SITE PLOT PLAN FOR: FACILITY 015-021-002928 CERS 10155965 FASTRIP #5562 1640 S CHESTER AVE. BAKERSFIELD, CA 93304 10/24/16 REV. C1 VICINITY MAP PROJECT DATA 1"=10'-0" INCHES012 SHEET SIZE 22 X 34 SCALE: 1640 S CHESTER AVE. BAKERSFIELD, CA 93304 S CH ES T ER AVE MING AVE APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Jaco #5562 Fastrip #61640 S Chester AveBakersfield101559651-21-2 3-4878991DSL87899187891-21-23-43-45-65-6ProductProductProductProductProductProductProductProductProductRockland Kirk APPENDIX C-10 7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB917-8ProductProduct7-889877-8ProductProduct5-6DSL915-6ProductRockland Kirk Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10155965 10-5-23 Jaco #5562 Fastrip #6 1640 S Chester Ave Bakersfield 93304 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Rockland Kirk 1073967 10241356 9-29-24 OPW PHASE 1 EVR 1193547 2-15-25 RP 1200 SPILL BUCKETS 10-5-23 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1 UNL OPW T2 DSL OPW T3 PNL OPW T4 UNL2 OPW Responses Received: 200 FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 OCT 5, 2023 1:30 PM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNL 9748 72.32 0.0 79.0 2314 2 DIESEL 4281 36.96 0.0 85.5 7781 3 PNL 7205 55.37 0.0 80.4 4857 4 UNL 2 SIPHON 9009 67.13 0.0 78.1 3053 I90500 OCT 5, 2023 1:30 PM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 OCT 5, 2023 1:30 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 OCT 5, 2023 1:30 PM SHIFT TIME 1 : DISABLED I50202 OCT 5, 2023 1:30 PM SHIFT TIME 2 : DISABLED I50203 OCT 5, 2023 1:30 PM SHIFT TIME 3 : DISABLED I50204 OCT 5, 2023 1:30 PM SHIFT TIME 4 : DISABLED I54600 OCT 5, 2023 1:30 PM TANK PER TST NEEDED WRN: DISABLED I54900 OCT 5, 2023 1:30 PM TANK ANN TST NEEDED WRN: DISABLED I55300 OCT 5, 2023 1:30 PM LINE RE-ENABLE METHOD PASS LINE TEST I55600 OCT 5, 2023 1:30 PM LINE PER TST NEEDED WRN: DISABLED I55900 OCT 5, 2023 1:30 PM LINE ANN TST NEEDED WRN: DISABLED I50D00 OCT 5, 2023 1:30 PM PRINT TC VOLUMES ENABLED I50E00 OCT 5, 2023 1:30 PM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 OCT 5, 2023 1:30 PM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 OCT 5, 2023 1:30 PM H-PROTOCOL DATA FORMAT HEIGHT I51A01 OCT 5, 2023 1:30 PM DAYLIGHT SAVING TIME ENABLED ON I51B00 OCT 5, 2023 1:30 PM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 OCT 5, 2023 1:30 PM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 OCT 5, 2023 1:30 PM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 OCT 5, 2023 1:30 PM TANK CHART SECURITY DISABLED I5BD00 OCT 5, 2023 1:30 PM CUSTOM ALARM LABELS DISABLED I56000 OCT 5, 2023 1:31 PM MASS/DENSITY DISABLED I88101 OCT 5, 2023 1:31 PM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88102 OCT 5, 2023 1:31 PM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 OCT 5, 2023 1:31 PM PORT SETTINGS: COMM BOARD : 3 (EDIM ) RS-232 SECURITY CODE : DISABLED I88104 OCT 5, 2023 1:31 PM I88105 OCT 5, 2023 1:31 PM I88106 OCT 5, 2023 1:31 PM I52000 OCT 5, 2023 1:31 PM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE FEB 28, 2020 DISABLED 2 ON DATE FEB 28, 2020 DISABLED 3 ON DATE FEB 28, 2020 DISABLED 4 ON DATE FEB 28, 2020 DISABLED 5 ON DATE FEB 28, 2020 DISABLED 6 ON DATE FEB 28, 2020 DISABLED 7 ON DATE FEB 28, 2020 DISABLED 8 ON DATE FEB 28, 2020 DISABLED I60100 OCT 5, 2023 1:31 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNL ON 2 DIESEL ON 3 PNL ON 4 UNL 2 SIPHON ON I60200 OCT 5, 2023 1:31 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNL 2 DIESEL 3 PNL 4 UNL 2 SIPHON I60300 OCT 5, 2023 1:31 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNL 1 2 DIESEL 2 3 PNL 3 4 UNL 2 SIPHON 4 I60900 OCT 5, 2023 1:31 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNL 0.000700 2 DIESEL 0.000450 3 PNL 0.000700 4 UNL 2 SIPHON 0.000700 I60700 OCT 5, 2023 1:31 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNL 96.00 2 DIESEL 96.00 3 PNL 96.00 4 UNL 2 SIPHON 96.00 I60A00 OCT 5, 2023 1:31 PM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNL 1 PT 12062 2 DIESEL 1 PT 12062 3 PNL 1 PT 12062 4 UNL 2 SIPHON 1 PT 12062 I60400 OCT 5, 2023 1:31 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 12062 2 DIESEL 12062 3 PNL 12062 4 UNL 2 SIPHON 12062 I60500 OCT 5, 2023 1:31 PM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12062 0 0 0 2 DIESEL 12062 0 0 0 3 PNL 12062 0 0 0 4 UNL 2 SIPHON 12062 0 0 0 I60600 OCT 5, 2023 1:31 PM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNL 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 DIESEL 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 PNL 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 UNL 2 SIPHON 12062 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 OCT 5, 2023 1:31 PM TANK PRODUCT LABEL METER DATA 1 UNL NO 2 DIESEL NO 3 PNL NO 4 UNL 2 SIPHON NO I62F00 OCT 5, 2023 1:31 PM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNL 4.0 IN. 2 DIESEL 4.0 IN. 3 PNL 3.0 IN. 4 UNL 2 SIPHON 3.0 IN. I62700 OCT 5, 2023 1:31 PM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNL 2.0 2 DIESEL 2.0 3 PNL 2.0 4 UNL 2 SIPHON 2.0 I64200 OCT 5, 2023 1:31 PM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNL LOW 2 DIESEL LOW 3 PNL LOW 4 UNL 2 SIPHON LOW I62400 OCT 5, 2023 1:31 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNL 3.0 2 DIESEL 3.0 3 PNL 3.0 4 UNL 2 SIPHON 3.0 I62800 OCT 5, 2023 1:31 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 12062 2 DIESEL 12062 3 PNL 12062 4 UNL 2 SIPHON 12062 I62300 OCT 5, 2023 1:31 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 10856 2 DIESEL 10856 3 PNL 10856 4 UNL 2 SIPHON 10856 I62200 OCT 5, 2023 1:31 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 11459 2 DIESEL 11459 3 PNL 11459 4 UNL 2 SIPHON 11459 I62900 OCT 5, 2023 1:31 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1809 2 DIESEL 1809 3 PNL 1809 4 UNL 2 SIPHON 1809 I62100 OCT 5, 2023 1:31 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 500 2 DIESEL 500 3 PNL 500 4 UNL 2 SIPHON 500 I62600 OCT 5, 2023 1:31 PM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 DIESEL 99 3 PNL 99 4 UNL 2 SIPHON 99 I62500 OCT 5, 2023 1:31 PM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 99 2 DIESEL 99 3 PNL 99 4 UNL 2 SIPHON 99 I60800 OCT 5, 2023 1:31 PM TANK TILT TANK PRODUCT LABEL INCHES 1 UNL 4.50 2 DIESEL -3.00 3 PNL 4.30 4 UNL 2 SIPHON 4.44 I60B00 OCT 5, 2023 1:31 PM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 OCT 5, 2023 1:31 PM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNL 0.00 2 DIESEL 0.00 3 PNL 0.00 4 UNL 2 SIPHON 0.00 I61200 OCT 5, 2023 1:31 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNL NONE NONE 2 DIESEL NONE NONE 3 PNL NONE NONE 4 UNL 2 SIPHON NONE NONE I63600 OCT 5, 2023 1:31 PM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 1220 2 DIESEL 120 3 PNL 120 4 UNL 2 SIPHON 120 I62A00 OCT 5, 2023 1:31 PM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNL 0 2 DIESEL 0 3 PNL 0 4 UNL 2 SIPHON 120 I62C00 OCT 5, 2023 1:31 PM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNL STANDARD 2 DIESEL STANDARD 3 PNL STANDARD 4 UNL 2 SIPHON STANDARD I62D00 OCT 5, 2023 1:31 PM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED 2 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 PNL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 UNL 2 SIPHON GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 OCT 5, 2023 1:31 PM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNL OFF OFF 2 DIESEL OFF OFF 3 PNL OFF OFF 4 UNL 2 SIPHON OFF OFF I63000 OCT 5, 2023 1:31 PM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNL OFF 2 DIESEL OFF 3 PNL OFF 4 UNL 2 SIPHON OFF I63200 OCT 5, 2023 1:31 PM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNL OFF 2 DIESEL OFF 3 PNL OFF 4 UNL 2 SIPHON OFF I61000 OCT 5, 2023 1:31 PM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNL 1 2 DIESEL 1 3 PNL 1 4 UNL 2 SIPHON 1 I63A00 OCT 5, 2023 1:31 PM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNL 10.00% 2 DIESEL 10.00% 3 PNL 10.00% 4 UNL 2 SIPHON 10.00% I61100 OCT 5, 2023 1:31 PM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : TANK 1 MAR 19, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED TEST ON DATE : TANK 2 MAR 19, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED TEST ON DATE : TANK 3 MAR 19, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED TEST ON DATE : TANK 4 MAR 19, 2009 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 OCT 5, 2023 1:31 PM CSLD PROBABLITY OF DETECTION I61400 OCT 5, 2023 1:31 PM CSLD CLIMATE FACTOR I61600 OCT 5, 2023 1:31 PM TANK PRODUCT LABEL CAL UPDATE 1 UNL IMMEDIATE 2 DIESEL IMMEDIATE 3 PNL IMMEDIATE 4 UNL 2 SIPHON IMMEDIATE I61A00 OCT 5, 2023 1:31 PM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNL DISABLED 2 DIESEL DISABLED 3 PNL DISABLED 4 UNL 2 SIPHON DISABLED I61B00 OCT 5, 2023 1:31 PM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 OCT 5, 2023 1:31 PM CSLD REPORT ONLY I62B00 OCT 5, 2023 1:31 PM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNL ??? 0, 0 2 DIESEL ??? 0, 0 3 PNL ??? 0, 0 4 UNL 2 SIPHON ??? 0, 0 I63300 OCT 5, 2023 1:31 PM LEAK TEST REPORT FORMAT: NORMAL I63400 OCT 5, 2023 1:31 PM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 0 2 DIESEL 0 3 PNL 0 4 UNL 2 SIPHON 0 I63500 OCT 5, 2023 1:31 PM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNL 1 2 DIESEL 1 3 PNL 1 4 UNL 2 SIPHON 1 I63900 OCT 5, 2023 1:31 PM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNL END FACTOR: NONE 2 DIESEL END FACTOR: NONE 3 PNL END FACTOR: NONE 4 UNL 2 SIPHON END FACTOR: NONE I78000 OCT 5, 2023 1:31 PM I77700 OCT 5, 2023 1:31 PM I77800 OCT 5, 2023 1:31 PM I78C00 OCT 5, 2023 1:31 PM I78300 OCT 5, 2023 1:31 PM I78F00 OCT 5, 2023 1:31 PM I78700 OCT 5, 2023 1:31 PM I70200 OCT 5, 2023 1:31 PM LIQUID LABEL DEVICE LABEL 1 UNL 1 STP 2 UNL1 ANN 3 DIESEL STP 4 DIESEL ANN 5 PNL STP 6 PNL ANN 7 UNL2 SIPON STP 8 UNL2 ANN 9 DISP 1-2 10 DISP 3-4 11 DISP 5-6 12 DISP 7-8 13 TRAN NO. 14 TRAN SO. 15 16 I70300 OCT 5, 2023 1:31 PM LIQUID TYPE SENSOR LOCATION TYPE 1 UNL 1 STP TRI-STATE (SINGLE FLOAT) 2 UNL1 ANN TRI-STATE (SINGLE FLOAT) 3 DIESEL STP TRI-STATE (SINGLE FLOAT) 4 DIESEL ANN TRI-STATE (SINGLE FLOAT) 5 PNL STP TRI-STATE (SINGLE FLOAT) 6 PNL ANN TRI-STATE (SINGLE FLOAT) 7 UNL2 SIPON STP TRI-STATE (SINGLE FLOAT) 8 UNL2 ANN TRI-STATE (SINGLE FLOAT) 9 DISP 1-2 TRI-STATE (SINGLE FLOAT) 10 DISP 3-4 TRI-STATE (SINGLE FLOAT) 11 DISP 5-6 TRI-STATE (SINGLE FLOAT) 12 DISP 7-8 TRI-STATE (SINGLE FLOAT) 13 TRAN NO. TRI-STATE (SINGLE FLOAT) 14 TRAN SO. TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 OCT 5, 2023 1:31 PM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNL 1 STP STP SUMP 2 UNL1 ANN ANNULAR SPACE 3 DIESEL STP STP SUMP 4 DIESEL ANN ANNULAR SPACE 5 PNL STP STP SUMP 6 PNL ANN ANNULAR SPACE 7 UNL2 SIPON STP STP SUMP 8 UNL2 ANN ANNULAR SPACE 9 DISP 1-2 DISPENSER PAN 10 DISP 3-4 DISPENSER PAN 11 DISP 5-6 DISPENSER PAN 12 DISP 7-8 DISPENSER PAN 13 TRAN NO. PIPING SUMP 14 TRAN SO. PIPING SUMP 15 OTHER SENSORS 16 OTHER SENSORS I74200 OCT 5, 2023 1:31 PM I74300 OCT 5, 2023 1:31 PM I74400 OCT 5, 2023 1:31 PM I74700 OCT 5, 2023 1:31 PM I74800 OCT 5, 2023 1:31 PM I74900 OCT 5, 2023 1:31 PM I7BC00 OCT 5, 2023 1:31 PM I80200 OCT 5, 2023 1:31 PM I80300 OCT 5, 2023 1:31 PM I80400 OCT 5, 2023 1:31 PM I80700 OCT 5, 2023 1:31 PM RELAY LABEL DEVICE LABEL 1 UNL 1 2 DIESEL 3 PNL 4 5 OVERFILL ALARM 6 7 8 I80900 OCT 5, 2023 1:31 PM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNL 1 NORMALLY OPEN 2 DIESEL NORMALLY CLOSED 3 PNL NORMALLY OPEN 4 NORMALLY OPEN 5 OVERFILL ALARM NORMALLY OPEN 6 NORMALLY OPEN 7 NORMALLY OPEN 8 NORMALLY OPEN I80B00 OCT 5, 2023 1:31 PM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNL 1 1 2 DIESEL 2 3 PNL 3 4 NONE 5 OVERFILL ALARM NONE 6 NONE 7 NONE 8 NONE I80A00 OCT 5, 2023 1:31 PM RELAY TYPE RELAY DESIGNATION TYPE 1 UNL 1 PUMP CONTROL OUTPUT 2 DIESEL STANDARD 3 PNL PUMP CONTROL OUTPUT 4 STANDARD 5 OVERFILL ALARM STANDARD 6 STANDARD 7 STANDARD 8 STANDARD I80C00 OCT 5, 2023 1:31 PM I80800 OCT 5, 2023 1:31 PM RELAY SETUP REPORT R 1:UNL 1 TYPE: PUMP CONTROL OUTPUT TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 7:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 1:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 7:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:DIESEL TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 3:FUEL ALARM L 9:FUEL ALARM L11:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L11:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 9:SHORT ALARM L11:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM R 3:PNL TYPE: PUMP CONTROL OUTPUT TANK #: 3 LIQUID SENSOR ALMS L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 5:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM R 6: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 7: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 8: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 OCT 5, 2023 1:32 PM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 OCT 5, 2023 1:32 PM I72300 OCT 5, 2023 1:32 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 V.P.SENSOR DISP 3-4 VAPOR PRESSURE 02 F.M.DISP 1-2 AIR FLOW METER 03 F.M.DISP 3-4 AIR FLOW METER 04 F.M.DISP 5-6 AIR FLOW METER 05 F.M.DISP 7-8 AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 OCT 5, 2023 1:32 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 OCT 5, 2023 1:32 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 OCT 5, 2023 1:32 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 VAPOR PROCESSOR TYPE NONE IV4700 OCT 5, 2023 1:32 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 OCT 5, 2023 1:32 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 ACCEPT HIGH ORVR: YES IV4A00 OCT 5, 2023 1:32 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 03 BLEND3 02 02 02 01 03 BLEND3 03 03 03 02 03 BLEND3 04 04 04 02 03 BLEND3 05 05 05 03 03 BLEND3 06 06 06 03 03 BLEND3 07 07 07 04 03 BLEND3 08 08 08 04 03 BLEND3 IV4B00 OCT 5, 2023 1:32 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 03/01 09/01 xx/xx 02 01 02/02 03/02 09/02 xx/xx 03 02 02/03 03/03 09/03 xx/xx 04 02 02/04 03/04 09/04 xx/xx 05 03 02/05 03/05 09/05 xx/xx 06 03 02/06 03/06 09/06 xx/xx 07 04 02/07 03/07 09/07 xx/xx 08 04 02/08 03/08 09/08 xx/xx IV4900 OCT 5, 2023 1:32 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 OCT 5, 2023 1:32 PM ISD VERSION: 01.07 Responses Received: I10200 OCT 5, 2023 1:28 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 509328 507862 2 4 PROBE / G.T. 161808 161479 3 INTERSTITIAL BD 202847 202275 4 INTERSTITIAL BD 202871 202491 5 UNUSED 4718355 4784002 6 UNUSED 4717361 4777812 7 UNUSED 4715263 4774442 8 UNUSED 4709191 4783870 9 STP SENSE BOARD 33285 33164 10 RELAY BOARD 14947 14896 11 RELAY BOARD 15036 14984 12 UNUSED 4719178 4783901 13 UNUSED 4712774 4779473 14 UNUSED 4714717 4777645 15 UNUSED 4712598 4782205 16 UNUSED 4716528 4779958 COMM 1 RS232 SERIAL BD 14969 14918 COMM 2 RS232 SERIAL BD 15014 14962 COMM 3 ELEC DISP INT. 101433 101210 COMM 4 UNUSED 4715998 4780729 COMM 5 UNUSED 4712774 4781081 COMM 6 UNUSED 4713591 4779759 I90200 OCT 5, 2023 1:28 PM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 OCT 5, 2023 1:28 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 4 TANK UNL 2 SIPHON OVERFILL ALARM CLEAR 10-05-23 3:24AM T 4 TANK UNL 2 SIPHON OVERFILL ALARM ALARM 10-05-23 3:20AM T 1 TANK UNL OVERFILL ALARM CLEAR 10-03-23 7:09PM T 1 TANK UNL OVERFILL ALARM ALARM 10-03-23 7:07PM T 1 TANK UNL SUDDEN LOSS ALARM CLEAR 9-26-23 1:11PM T 3 TANK PNL SUDDEN LOSS ALARM CLEAR 9-26-23 1:11PM T 1 TANK UNL SUDDEN LOSS ALARM ALARM 9-26-23 12:29PM T 3 TANK PNL SUDDEN LOSS ALARM ALARM 9-26-23 12:27PM L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L 7 STP SUMP UNL2 SIPON STP SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L 3 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L 5 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L14 PIPE TRAN SO. SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L13 PIPE TRAN NO. SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 9-26-23 10:19AM L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM ALARM 9-26-23 10:19AM L 7 STP SUMP UNL2 SIPON STP SENSOR OUT ALARM ALARM 9-26-23 10:19AM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 9-26-23 10:19AM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 9-26-23 10:19AM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 9-26-23 10:19AM L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM 9-26-23 10:19AM L 3 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 9-26-23 10:19AM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 9-26-23 10:19AM L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM ALARM 9-26-23 10:19AM L14 PIPE TRAN SO. SENSOR OUT ALARM ALARM 9-26-23 10:19AM L 5 STP SUMP PNL STP SENSOR OUT ALARM ALARM 9-26-23 10:19AM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 9-26-23 10:19AM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 9-26-23 10:19AM L13 PIPE TRAN NO. SENSOR OUT ALARM ALARM 9-26-23 10:19AM L 8 ANNULAR UNL2 ANN FUEL ALARM CLEAR 9-26-23 10:16AM L 2 ANNULAR UNL1 ANN FUEL ALARM CLEAR 9-26-23 10:15AM L 2 ANNULAR UNL1 ANN FUEL ALARM ALARM 9-26-23 10:15AM L 8 ANNULAR UNL2 ANN FUEL ALARM ALARM 9-26-23 10:15AM L 4 ANNULAR DIESEL ANN FUEL ALARM CLEAR 9-26-23 10:15AM L 6 ANNULAR PNL ANN FUEL ALARM CLEAR 9-26-23 10:15AM L 6 ANNULAR PNL ANN FUEL ALARM ALARM 9-26-23 10:14AM L 4 ANNULAR DIESEL ANN FUEL ALARM ALARM 9-26-23 10:14AM L14 PIPE TRAN SO. FUEL ALARM CLEAR 9-26-23 10:13AM L14 PIPE TRAN SO. FUEL ALARM ALARM 9-26-23 10:13AM L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 9-26-23 10:12AM L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 9-26-23 10:12AM L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 9-26-23 10:12AM L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 9-26-23 10:12AM I11200 OCT 5, 2023 1:28 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 9-09-23 6:02AM SYSTEM PAPER OUT CLEAR 9-09-23 6:02AM SYSTEM PRINTER ERROR ALARM 9-09-23 5:59AM SYSTEM PAPER OUT ALARM 9-09-23 5:59AM T 1 TANK UNL HIGH PRODUCT ALARM CLEAR 9-04-23 1:08PM T 1 TANK UNL HIGH PRODUCT ALARM ALARM 9-04-23 1:02PM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 9-02-23 10:00AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 9-01-23 10:01AM h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 8-27-23 10:00AM h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 8-27-23 10:00AM h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN ALARM 8-26-23 10:01AM h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN ALARM 8-26-23 10:01AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 8-20-23 10:00AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 8-19-23 10:01AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM SYSTEM PAPER OUT ALARM 8-14-23 7:38AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM SYSTEM PAPER OUT ALARM 8-14-23 7:38AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM SYSTEM PAPER OUT ALARM 8-14-23 7:38AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM SYSTEM PAPER OUT ALARM 8-14-23 7:38AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:37AM SYSTEM PAPER OUT ALARM 8-14-23 7:37AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:37AM SYSTEM PAPER OUT CLEAR 8-14-23 7:37AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:37AM SYSTEM PAPER OUT ALARM 8-14-23 7:37AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:37AM SYSTEM PAPER OUT CLEAR 8-14-23 7:37AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:34AM SYSTEM PAPER OUT ALARM 8-14-23 7:34AM OTHER ISD VAPOR LEAK WARN CLEAR 7-28-23 10:00AM OTHER ISD VAPOR LEAK WARN ALARM 7-27-23 10:01AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-19-23 6:52PM T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-19-23 1:33PM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 7-05-23 10:00AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 7-04-23 10:01AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 6-22-23 2:57PM T 2 TANK DIESEL DELIVERY NEEDED ALARM 6-22-23 12:37PM I20600 OCT 5, 2023 1:28 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 TANK ALARM HISTORY TANK 1 UNL OVERFILL ALARM OCT 3, 2023 7:07 PM SEP 7, 2023 7:44 PM SEP 7, 2023 7:35 PM SUDDEN LOSS ALARM SEP 26, 2023 12:29 PM JUN 6, 2023 1:32 AM JUN 6, 2023 1:10 AM HIGH PRODUCT ALARM SEP 4, 2023 1:02 PM TANK 2 DIESEL DELIVERY NEEDED JUL 19, 2023 1:33 PM JUN 22, 2023 12:37 PM APR 24, 2023 11:07 AM TANK 3 PNL OVERFILL ALARM FEB 26, 2023 12:23 PM SUDDEN LOSS ALARM SEP 26, 2023 12:27 PM TANK 4 UNL 2 SIPHON OVERFILL ALARM OCT 5, 2023 3:20 AM DEC 11, 2022 5:34 PM SEP 24, 2022 5:01 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 OCT 5, 2023 1:29 PM I30200 OCT 5, 2023 1:29 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL 1 STP SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:08 AM FUEL ALARM SEP 13, 2023 2:56 PM FUEL ALARM 2 UNL1 ANN SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:15 AM FUEL ALARM SEP 13, 2023 3:05 PM FUEL ALARM 3 DIESEL STP SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:08 AM FUEL ALARM SEP 13, 2023 2:56 PM FUEL ALARM 4 DIESEL ANN SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:14 AM FUEL ALARM SEP 13, 2023 3:05 PM FUEL ALARM 5 PNL STP SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:08 AM FUEL ALARM SEP 13, 2023 2:55 PM FUEL ALARM 6 PNL ANN SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:14 AM FUEL ALARM SEP 13, 2023 3:04 PM FUEL ALARM 7 UNL2 SIPON STP SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:09 AM FUEL ALARM SEP 13, 2023 1:39 PM SENSOR OUT ALARM 8 UNL2 ANN SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:15 AM FUEL ALARM SEP 13, 2023 3:05 PM FUEL ALARM 9 DISP 1-2 SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:12 AM FUEL ALARM SEP 26, 2023 10:12 AM FUEL ALARM 10 DISP 3-4 SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:10 AM FUEL ALARM SEP 13, 2023 1:39 PM SENSOR OUT ALARM 11 DISP 5-6 SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:11 AM FUEL ALARM SEP 13, 2023 1:38 PM SENSOR OUT ALARM 12 DISP 7-8 SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:10 AM FUEL ALARM SEP 13, 2023 1:38 PM SENSOR OUT ALARM 13 TRAN NO. SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:11 AM FUEL ALARM SEP 13, 2023 1:38 PM SENSOR OUT ALARM 14 TRAN SO. SEP 26, 2023 10:19 AM SENSOR OUT ALARM SEP 26, 2023 10:13 AM FUEL ALARM SEP 13, 2023 1:38 PM SENSOR OUT ALARM I31600 OCT 5, 2023 1:29 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 V.P.SENSOR DISP 3-4 2 F.M.DISP 1-2 3 F.M.DISP 3-4 4 F.M.DISP 5-6 5 F.M.DISP 7-8 I40200 OCT 5, 2023 1:29 PM I40300 OCT 5, 2023 1:29 PM I34200 OCT 5, 2023 1:29 PM I34700 OCT 5, 2023 1:29 PM IV0100 OCT 5, 2023 1:29 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-09-01 10:01:55 A/L RATIO DEGRADATION FP 2 BLEND3 0.80 23-08-26 10:01:45 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-08-26 10:01:45 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 23-08-19 10:01:59 A/L RATIO DEGRADATION FP 2 BLEND3 0.80 23-07-27 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.82 23-07-04 10:01:14 A/L RATIO DEGRADATION FP 2 BLEND3 0.80 23-06-17 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.68 23-06-02 10:01:22 A/L RATIO DEGRADATION FP 8 BLEND3 0.80 23-05-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 23-05-17 10:01:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-08-27 10:01:33 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-08-27 10:01:33 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 23-05-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 22-07-03 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.76 22-05-26 10:01:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 22-05-26 10:01:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 22-02-21 10:01:43 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-02-21 10:01:42 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 22-02-20 10:01:42 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-02-20 10:01:41 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-09-27 10:01:37 READINESS ISD:PP EVR:PP ISD & EVR READY 23-09-26 10:17:38 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-09-26 10:17:38 ISD STARTUP 23-09-26 10:17:25 ISD SHUTDOWN 23-09-14 10:01:49 READINESS ISD:PP EVR:PP ISD & EVR READY 23-09-13 13:36:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-09-13 13:36:39 ISD STARTUP 23-09-13 13:35:14 ISD SHUTDOWN 23-09-07 19:22:41 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED 23-08-28 09:35:03 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED Responses Received: I10200 OCT 5, 2023 4:11 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 509328 507844 2 4 PROBE / G.T. 161808 161362 3 INTERSTITIAL BD 202847 202044 4 INTERSTITIAL BD 202871 202308 5 UNUSED 4718355 4661856 6 UNUSED 4717361 4657445 7 UNUSED 4715263 4657908 8 UNUSED 4709191 4650763 9 STP SENSE BOARD 33285 33136 10 RELAY BOARD 14947 14888 11 RELAY BOARD 15036 14999 12 UNUSED 4719178 4661929 13 UNUSED 4712774 4655137 14 UNUSED 4714717 4651807 15 UNUSED 4712598 4653417 16 UNUSED 4716528 4655313 COMM 1 RS232 SERIAL BD 14969 14910 COMM 2 RS232 SERIAL BD 15014 14976 COMM 3 ELEC DISP INT. 101433 101125 COMM 4 UNUSED 4715998 4657188 COMM 5 UNUSED 4712774 4656129 COMM 6 UNUSED 4713591 4659900 I90200 OCT 5, 2023 4:11 PM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 OCT 5, 2023 4:11 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 2 ANNULAR UNL1 ANN FUEL ALARM CLEAR 10-05-23 2:14PM L 8 ANNULAR UNL2 ANN FUEL ALARM CLEAR 10-05-23 2:14PM L 4 ANNULAR DIESEL ANN FUEL ALARM CLEAR 10-05-23 2:14PM L 6 ANNULAR PNL ANN FUEL ALARM CLEAR 10-05-23 2:14PM L 8 ANNULAR UNL2 ANN FUEL ALARM ALARM 10-05-23 2:13PM L 2 ANNULAR UNL1 ANN FUEL ALARM ALARM 10-05-23 2:13PM L 4 ANNULAR DIESEL ANN FUEL ALARM ALARM 10-05-23 2:13PM L 6 ANNULAR PNL ANN FUEL ALARM ALARM 10-05-23 2:13PM L 6 ANNULAR PNL ANN SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L 5 STP SUMP PNL STP SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L 3 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L13 PIPE TRAN NO. SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L14 PIPE TRAN SO. SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L 7 STP SUMP UNL2 SIPON STP SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 10-05-23 1:55PM L 8 ANNULAR UNL2 ANN SENSOR OUT ALARM ALARM 10-05-23 1:51PM L 7 STP SUMP UNL2 SIPON STP SENSOR OUT ALARM ALARM 10-05-23 1:51PM L14 PIPE TRAN SO. SENSOR OUT ALARM ALARM 10-05-23 1:51PM L 6 ANNULAR PNL ANN SENSOR OUT ALARM ALARM 10-05-23 1:51PM L12 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 10-05-23 1:51PM L11 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 10-05-23 1:51PM L10 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 10-05-23 1:51PM L 4 ANNULAR DIESEL ANN SENSOR OUT ALARM ALARM 10-05-23 1:51PM L 3 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 10-05-23 1:51PM L 2 ANNULAR UNL1 ANN SENSOR OUT ALARM ALARM 10-05-23 1:51PM L13 PIPE TRAN NO. SENSOR OUT ALARM ALARM 10-05-23 1:51PM L 5 STP SUMP PNL STP SENSOR OUT ALARM ALARM 10-05-23 1:51PM L 9 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 10-05-23 1:51PM L 1 STP SUMP UNL 1 STP SENSOR OUT ALARM ALARM 10-05-23 1:51PM L 9 DISP PAN DISP 1-2 FUEL ALARM CLEAR 10-05-23 1:47PM L 9 DISP PAN DISP 1-2 FUEL ALARM ALARM 10-05-23 1:46PM L11 DISP PAN DISP 5-6 FUEL ALARM CLEAR 10-05-23 1:45PM L11 DISP PAN DISP 5-6 FUEL ALARM ALARM 10-05-23 1:45PM L13 PIPE TRAN NO. FUEL ALARM CLEAR 10-05-23 1:44PM L13 PIPE TRAN NO. FUEL ALARM ALARM 10-05-23 1:44PM L14 PIPE TRAN SO. FUEL ALARM CLEAR 10-05-23 1:43PM L14 PIPE TRAN SO. FUEL ALARM ALARM 10-05-23 1:43PM L12 DISP PAN DISP 7-8 FUEL ALARM CLEAR 10-05-23 1:42PM L12 DISP PAN DISP 7-8 FUEL ALARM ALARM 10-05-23 1:42PM L10 DISP PAN DISP 3-4 FUEL ALARM CLEAR 10-05-23 1:41PM L10 DISP PAN DISP 3-4 FUEL ALARM ALARM 10-05-23 1:41PM L 5 STP SUMP PNL STP FUEL ALARM CLEAR 10-05-23 1:40PM L 5 STP SUMP PNL STP FUEL ALARM ALARM 10-05-23 1:40PM I11200 OCT 5, 2023 4:12 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 10-05-23 1:53PM SYSTEM PAPER OUT CLEAR 10-05-23 1:53PM SYSTEM PRINTER ERROR ALARM 10-05-23 1:51PM SYSTEM PAPER OUT ALARM 10-05-23 1:51PM SYSTEM PRINTER ERROR CLEAR 9-09-23 6:02AM SYSTEM PAPER OUT CLEAR 9-09-23 6:02AM SYSTEM PRINTER ERROR ALARM 9-09-23 5:59AM SYSTEM PAPER OUT ALARM 9-09-23 5:59AM T 1 TANK UNL HIGH PRODUCT ALARM CLEAR 9-04-23 1:08PM T 1 TANK UNL HIGH PRODUCT ALARM ALARM 9-04-23 1:02PM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 9-02-23 10:00AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 9-01-23 10:01AM h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 8-27-23 10:00AM h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 8-27-23 10:00AM h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN ALARM 8-26-23 10:01AM h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN ALARM 8-26-23 10:01AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 8-20-23 10:00AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 8-19-23 10:01AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM SYSTEM PAPER OUT ALARM 8-14-23 7:38AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM SYSTEM PAPER OUT ALARM 8-14-23 7:38AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM SYSTEM PAPER OUT ALARM 8-14-23 7:38AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:38AM SYSTEM PAPER OUT ALARM 8-14-23 7:38AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:38AM SYSTEM PAPER OUT CLEAR 8-14-23 7:38AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:37AM SYSTEM PAPER OUT ALARM 8-14-23 7:37AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:37AM SYSTEM PAPER OUT CLEAR 8-14-23 7:37AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:37AM SYSTEM PAPER OUT ALARM 8-14-23 7:37AM SYSTEM PRINTER ERROR CLEAR 8-14-23 7:37AM SYSTEM PAPER OUT CLEAR 8-14-23 7:37AM SYSTEM PRINTER ERROR ALARM 8-14-23 7:34AM SYSTEM PAPER OUT ALARM 8-14-23 7:34AM OTHER ISD VAPOR LEAK WARN CLEAR 7-28-23 10:00AM OTHER ISD VAPOR LEAK WARN ALARM 7-27-23 10:01AM T 2 TANK DIESEL DELIVERY NEEDED CLEAR 7-19-23 6:52PM T 2 TANK DIESEL DELIVERY NEEDED ALARM 7-19-23 1:33PM I20600 OCT 5, 2023 4:12 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 TANK ALARM HISTORY TANK 1 UNL OVERFILL ALARM OCT 3, 2023 7:07 PM SEP 7, 2023 7:44 PM SEP 7, 2023 7:35 PM SUDDEN LOSS ALARM SEP 26, 2023 12:29 PM JUN 6, 2023 1:32 AM JUN 6, 2023 1:10 AM HIGH PRODUCT ALARM SEP 4, 2023 1:02 PM TANK 2 DIESEL DELIVERY NEEDED JUL 19, 2023 1:33 PM JUN 22, 2023 12:37 PM APR 24, 2023 11:07 AM TANK 3 PNL OVERFILL ALARM FEB 26, 2023 12:23 PM SUDDEN LOSS ALARM SEP 26, 2023 12:27 PM TANK 4 UNL 2 SIPHON OVERFILL ALARM OCT 5, 2023 3:20 AM DEC 11, 2022 5:34 PM SEP 24, 2022 5:01 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 OCT 5, 2023 4:12 PM I30200 OCT 5, 2023 4:12 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNL 1 STP OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:38 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 2 UNL1 ANN OCT 5, 2023 2:13 PM FUEL ALARM OCT 5, 2023 1:51 PM SENSOR OUT ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 3 DIESEL STP OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:39 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 4 DIESEL ANN OCT 5, 2023 2:13 PM FUEL ALARM OCT 5, 2023 1:51 PM SENSOR OUT ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 5 PNL STP OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:40 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 6 PNL ANN OCT 5, 2023 2:13 PM FUEL ALARM OCT 5, 2023 1:51 PM SENSOR OUT ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 7 UNL2 SIPON STP OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:37 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 8 UNL2 ANN OCT 5, 2023 2:13 PM FUEL ALARM OCT 5, 2023 1:51 PM SENSOR OUT ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 9 DISP 1-2 OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:46 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 10 DISP 3-4 OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:41 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 11 DISP 5-6 OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:45 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 12 DISP 7-8 OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:42 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 13 TRAN NO. OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:44 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM 14 TRAN SO. OCT 5, 2023 1:51 PM SENSOR OUT ALARM OCT 5, 2023 1:43 PM FUEL ALARM SEP 26, 2023 10:19 AM SENSOR OUT ALARM I31600 OCT 5, 2023 4:12 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 V.P.SENSOR DISP 3-4 2 F.M.DISP 1-2 3 F.M.DISP 3-4 4 F.M.DISP 5-6 5 F.M.DISP 7-8 I40200 OCT 5, 2023 4:12 PM I40300 OCT 5, 2023 4:12 PM I34200 OCT 5, 2023 4:12 PM I34700 OCT 5, 2023 4:12 PM IV0100 OCT 5, 2023 4:12 PM FASTRIP 562 MING-CHESTER BAKERSFIELD CA 661-397-8606 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-09-01 10:01:55 A/L RATIO DEGRADATION FP 2 BLEND3 0.80 23-08-26 10:01:45 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-08-26 10:01:45 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 23-08-19 10:01:59 A/L RATIO DEGRADATION FP 2 BLEND3 0.80 23-07-27 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 9.82 23-07-04 10:01:14 A/L RATIO DEGRADATION FP 2 BLEND3 0.80 23-06-17 10:01:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 8.68 23-06-02 10:01:22 A/L RATIO DEGRADATION FP 8 BLEND3 0.80 23-05-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 5 BLEND3 BLKD 23-05-17 10:01:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-08-27 10:01:33 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 23-08-27 10:01:33 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 23-05-18 10:01:09 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 22-07-03 10:01:09 A/L RATIO DEGRADATION FP 7 BLEND3 0.76 22-05-26 10:01:09 A/L RATIO GROSS BLOCKAGE FP 4 BLEND3 BLKD 22-05-26 10:01:09 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 22-02-21 10:01:43 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-02-21 10:01:42 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 22-02-20 10:01:42 A/L RATIO GROSS BLOCKAGE FP 8 BLEND3 BLKD 22-02-20 10:01:41 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-10-05 13:49:30 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-10-05 13:49:30 ISD STARTUP 23-10-05 13:48:27 ISD SHUTDOWN 23-09-27 10:01:37 READINESS ISD:PP EVR:PP ISD & EVR READY 23-09-26 10:17:38 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-09-26 10:17:38 ISD STARTUP 23-09-26 10:17:25 ISD SHUTDOWN 23-09-14 10:01:49 READINESS ISD:PP EVR:PP ISD & EVR READY 23-09-13 13:36:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-09-13 13:36:39 ISD STARTUP