ELECTRIC MATERIALS
HARVEST GROVE PHASE - 2 TRACT 6873
New Residential
LGI Homes, INC.
Gosford Road & McCutchens Road
Bakersfield
PM# 35274099
11/12/2021
21-146
Project Manager: Paul Giacalone
Designed By: Brian Rubio / BrianR@DryUtilityDesign.com
MATERIAL LIST BY LOCATION
LOCATION QUANTITY EACH/FT.MATERIAL CODE DESCRIPTION FOOTNOTE
800 1 EACH 18-0134 RISER BKT. COMBO ^
800 3 EACH 36-0673 10' LENGTH, 3" RISER MOULD.^
800 3 EACH 33-0306 CUTOUT, PT-44H ^
800 3 EACH 33-2276 FUSE, POWER TYPE "E", SMU-20, 23KV, 65 AMP ^
800 3 EACH 03-1942 CABLE TERM. #4-1/0A, 25KV ^
800 3 EACH 30-3845 CABLE PIN TERMINAL 1/0A ^
800 3 EACH 30-0425 FIRED WEDGE CONNECTOR ^
800 3 EACH 29-0290 PRIMARY LEAD WIRE, 2C ^
800 1 EACH 18-4223 CABLE GRIP, PT-7 ^
800 1 EACH 38-2045 CABLE PROTECTOR ^
800 2 EACH 37-3038 HIGH VOLTAGE SIGN ^
800 10 FT AS REQ'D RISER BUS, #6 Cu WIRE ^
801 1 EACH LABOR CONNECT SERVICE ^
1 1 EACH 36-0673 10' LENGTH, 3" RISER MOULD.
1 2 EACH 36-0542 3" PVC BACK-UP PLATE
1 2 EACH 36-0414 RISER BEND, 4"
1 2 EACH 36-0075 REDUCER BOOT, 4" X 3" X 2"
1 45 FT 29-0073 RISER BUS, #4Cu WIRE
1 1 EACH 18-7013 GROUND ROD, 5/8" x 8'
1 2 EACH 18-7012 GROUND ROD CLAMPS
2 647 FT 29-0047 CABLE, 3-1/0AL, EPR-CONC-ENCAP 25KV
2 6 EACH 38-4202 1/0A PRIMARY CABLE END CAP
2 4 EACH 50-0117 FRONT END PACK, 4"-6"
2 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
3 6 EACH 30-5244 CONNECTOR, COMPRESSION
3 15 FT 29-0074 WIRE, #2AWG, SOLID CU
3 EACH AS REQ'D PHASE AND VOLTAGE TAG
3 EACH AS REQ'D SECTIONALIZING TAG
3 2 EACH 36-2616 PRIMARY RACKING, KIT 2 (12" ROD)
4 597 FT 29-0047 CABLE, 3-1/0AL, EPR-CONC-ENCAP 25KV
4 6 EACH 38-4202 1/0A PRIMARY CABLE END CAP
4 3 EACH 50-0117 FRONT END PACK, 4"-6"
4 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
5 6 EACH 30-5244 CONNECTOR, COMPRESSION
5 15 FT 29-0074 WIRE, #2AWG, SOLID CU
5 EACH AS REQ'D PHASE AND VOLTAGE TAG
5 EACH AS REQ'D SECTIONALIZING TAG
5 2 EACH 36-2616 PRIMARY RACKING, KIT 2 (12" ROD)
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
6 268 FT 29-0047 CABLE, 3-1/0AL, EPR-CONC-ENCAP 25KV
6 6 EACH 38-4202 1/0A PRIMARY CABLE END CAP
6 2 EACH 50-0117 FRONT END PACK, 4"-6"
6 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
6 1 EACH LABOR CONNECT CONDUIT
6 182 FT 01-6472 CONDUIT, 4"
6 1 EACH 36-0761 BEND, 4", 22 DEG, 60"R
6 1 EACH 36-0415 BEND, 4", 90 DEG, 60"R
6 1 EACH 36-0414 BEND, 4", 90 DEG, 36"R
6 1 EACH 36-0423 BELL END, 4"
6 1 EACH 36-0443 TEMPORARY CAP PLUG, 4"
7 247 FT 29-0046 CABLE, 2-1/0AL, EPR-CONC-ENCAP 25KV
7 4 EACH 38-4202 1/0A PRIMARY CABLE END CAP
7 2 EACH 50-0117 FRONT END PACK, 4"-6"
7 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
7 233 FT 01-6472 CONDUIT, 4"
7 2 EACH 36-0805 BEND, 4", 11 DEG, 60"R
7 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
7 1 EACH 36-0415 BEND, 4", 90 DEG, 60"R
7 2 EACH 36-0423 BELL END, 4"
7 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
8 1 EACH 26-1509 TX,PM,100KVA,12/21,2 WIRE,LB,DF
8 1 EACH 36-0003 BOX PAD, 50" X 52" X 18"
8 2 EACH 30-0480 ELBOW, 200A, LB
8 2 EACH 30-0481 BUSHING INSERT, LB
8 2 EACH 30-0486 INSULATED BUSHING WELL PLUG
8 3 EACH 03-1604 SEC CONN, BAR TYPE
8 15 FT 29-0074 WIRE, #2AWG, SOLID CU
8 2 EACH 18-7013 GROUND ROD, 5/8"X8'
8 2 EACH 18-7012 GROUND ROD CLAMP, 5/8"
8 1 EACH 49-5228 COMPOUND CAULKING
8 1 EACH 01-6583 PADLOCK, CORPORATION
8 2 EACH 19-2874 BOLT, 1/2"-13 X 1 1/2"
8 2 EACH 19-5286 WASHER, 2 1/4" SQUARE
9 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
9 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
10 138 FT 29-4371 4/0A TPX 600V CABLE
10 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
10 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
10 2 EACH 50-0118 FRONT END PACK, 2"-3"
10 124 FT 01-6471 CONDUIT, 3"
10 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
10 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
10 2 EACH 36-0421 BELL END, 3"
10 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
11 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
11 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
12 79 FT 29-4371 4/0A TPX 600V CABLE
12 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
12 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
12 2 EACH 50-0118 FRONT END PACK, 2"-3"
12 65 FT 01-6471 CONDUIT, 3"
12 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
12 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
12 2 EACH 36-0421 BELL END, 3"
12 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
13 69 FT 29-4372 350A TPX 600V CABLE
13 4 EACH 38-4200 350A SECONDARY CABLE END CAP
13 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
13 2 EACH 50-0117 FRONT END PACK, 4"-6"
13 55 FT 01-6472 CONDUIT, 4"
13 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
13 3 EACH 36-0414 BEND, 4", 90 DEG, 36"R
13 2 EACH 36-0423 BELL END, 4"
13 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
14 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
14 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
15 62 FT 29-4372 350A TPX 600V CABLE
15 4 EACH 38-4200 350A SECONDARY CABLE END CAP
15 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
15 2 EACH 50-0117 FRONT END PACK, 4"-6"
15 58 FT 01-6472 CONDUIT, 4"
15 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
15 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
15 2 EACH 36-0423 BELL END, 4"
15 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
16 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
16 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
17 102 FT 29-4372 350A TPX 600V CABLE
17 4 EACH 38-4200 350A SECONDARY CABLE END CAP
17 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
17 2 EACH 50-0117 FRONT END PACK, 4"-6"
17 88 FT 01-6472 CONDUIT, 4"
17 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
17 3 EACH 36-0414 BEND, 4", 90 DEG, 36"R
17 2 EACH 36-0423 BELL END, 4"
17 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
18 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
18 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
19 1 EACH 36-0040 PAD-MOUNTED JUNCTION BOX, STEEL-NON CORRO
19 1 EACH 36-0038 JUNCTION BOX BAD, POLYMER CONCRETE
19 10 EACH 30-0481 BUSHING INSERT, LB
19 10 EACH 30-0480 ELBOW, 200A, LB
19 2 EACH 30-0486 INSULATED BUSHING WELL PLUG
19 15 FT 29-0074 WIRE, #2AWG, SOLID CU
19 2 EACH 18-7013 GROUND ROD, 5/8"X8'
19 4 EACH 18-7012 GROUND ROD CLAMP, 5/8"
19 4 EACH 30-5244 CONNECTOR, COMPRESSION
19 4 EACH 19-0445 ANCHOR BOLT
19 2 EACH 01-8799 FAULT INDICATOR BRACKET
19 1 EACH 36-2624 FAULT INDICATOR, 450 A, 3WIRE
19 2 EACH 36-2623 FAULT INDICATOR, 450 A, 2WIRE
20 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
20 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
21 244 FT 29-0047 CABLE, 3-1/0AL, EPR-CONC-ENCAP 25KV
21 6 EACH 38-4202 1/0A PRIMARY CABLE END CAP
21 2 EACH 50-0117 FRONT END PACK, 4"-6"
21 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
21 230 FT 01-6472 CONDUIT, 4"
21 2 EACH 36-0761 BEND, 4", 22 DEG, 60"R
21 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
21 2 EACH 36-0423 BELL END, 4"
21 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
22 124 FT 29-4371 4/0A TPX 600V CABLE
22 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
22 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
22 2 EACH 50-0118 FRONT END PACK, 2"-3"
22 110 FT 01-6471 CONDUIT, 3"
22 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
22 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
22 2 EACH 36-0421 BELL END, 3"
22 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
23 329 FT 29-0046 CABLE, 2-1/0AL, EPR-CONC-ENCAP 25KV
23 4 EACH 38-4202 1/0A PRIMARY CABLE END CAP
23 2 EACH 50-0117 FRONT END PACK, 4"-6"
23 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
23 315 FT 01-6472 CONDUIT, 4"
23 2 EACH 36-0805 BEND, 4", 11 DEG, 60"R
23 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
23 1 EACH 36-0415 BEND, 4", 90 DEG, 60"R
23 2 EACH 36-0423 BELL END, 4"
23 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
24 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
24 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
25 29 FT 29-4371 4/0A TPX 600V CABLE
25 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
25 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
25 2 EACH 50-0118 FRONT END PACK, 2"-3"
25 15 FT 01-6471 CONDUIT, 3"
25 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
25 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
25 2 EACH 36-0421 BELL END, 3"
25 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
26 1 EACH 26-1508 TX,PM,50KVA,12/21,2 WIRE,LB,DF
26 1 EACH 36-0001 BOX PAD, 36" X 52" X 18"
26 4 EACH 30-0480 ELBOW, 200A, LB
26 4 EACH 30-0481 BUSHING INSERT, LB
26 3 EACH 03-1604 SEC CONN, BAR TYPE
26 15 FT 29-0074 WIRE, #2AWG, SOLID CU
26 2 EACH 18-7013 GROUND ROD, 5/8"X8'
26 2 EACH 18-7012 GROUND ROD CLAMP, 5/8"
26 1 EACH 49-5228 COMPOUND CAULKING
26 1 EACH 01-6583 PADLOCK, CORPORATION
26 2 EACH 19-2874 BOLT, 1/2"-13 X 1 1/2"
26 2 EACH 19-5286 WASHER, 2 1/4" SQUARE
26 2 EACH 36-2623 FAULT INDICATOR, 450 A, 2WIRE
27 114 FT 29-4371 4/0A TPX 600V CABLE
27 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
27 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
27 2 EACH 50-0118 FRONT END PACK, 2"-3"
27 100 FT 01-6471 CONDUIT, 3"
27 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
27 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
27 2 EACH 36-0421 BELL END, 3"
27 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
28 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
28 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
29 232 FT 29-0046 CABLE, 2-1/0AL, EPR-CONC-ENCAP 25KV
29 4 EACH 38-4202 1/0A PRIMARY CABLE END CAP
29 2 EACH 50-0117 FRONT END PACK, 4"-6"
29 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
29 218 FT 01-6472 CONDUIT, 4"
29 2 EACH 36-0805 BEND, 4", 11 DEG, 60"R
29 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
29 1 EACH 36-0415 BEND, 4", 90 DEG, 60"R
29 2 EACH 36-0423 BELL END, 4"
29 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
30 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
30 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
31 95 FT 29-4371 4/0A TPX 600V CABLE
31 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
31 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
31 2 EACH 50-0118 FRONT END PACK, 2"-3"
31 81 FT 01-6471 CONDUIT, 3"
31 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
31 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
31 1 EACH 36-0328 BEND, 3", 90 DEG, 36"R
31 2 EACH 36-0421 BELL END, 3"
31 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
32 1 EACH 26-1508 TX,PM,50KVA,12/21,2 WIRE,LB,DF
32 1 EACH 36-0001 BOX PAD, 36" X 52" X 18"
32 4 EACH 30-0480 ELBOW, 200A, LB
32 4 EACH 30-0481 BUSHING INSERT, LB
32 3 EACH 03-1604 SEC CONN, BAR TYPE
32 15 FT 29-0074 WIRE, #2AWG, SOLID CU
32 2 EACH 18-7013 GROUND ROD, 5/8"X8'
32 2 EACH 18-7012 GROUND ROD CLAMP, 5/8"
32 1 EACH 49-5228 COMPOUND CAULKING
32 1 EACH 01-6583 PADLOCK, CORPORATION
32 2 EACH 19-2874 BOLT, 1/2"-13 X 1 1/2"
32 2 EACH 19-5286 WASHER, 2 1/4" SQUARE
32 2 EACH 36-2623 FAULT INDICATOR, 450 A, 2WIRE
33 75 FT 29-4371 4/0A TPX 600V CABLE
33 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
33 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
33 2 EACH 50-0118 FRONT END PACK, 2"-3"
33 61 FT 01-6471 CONDUIT, 3"
33 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
33 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
33 2 EACH 36-0421 BELL END, 3"
33 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
34 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
34 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
35 74 FT 29-4371 4/0A TPX 600V CABLE
35 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
35 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
35 2 EACH 50-0118 FRONT END PACK, 2"-3"
35 60 FT 01-6471 CONDUIT, 3"
35 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
35 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
35 2 EACH 36-0421 BELL END, 3"
35 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
36 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
36 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
37 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
37 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
38 346 FT 29-0046 CABLE, 2-1/0AL, EPR-CONC-ENCAP 25KV
38 4 EACH 38-4202 1/0A PRIMARY CABLE END CAP
38 2 EACH 50-0117 FRONT END PACK, 4"-6"
38 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
38 332 FT 01-6472 CONDUIT, 4"
38 2 EACH 36-0761 BEND, 4", 22 DEG, 60"R
38 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
38 2 EACH 36-0423 BELL END, 4"
38 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
39 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
39 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
40 66 FT 29-4371 4/0A TPX 600V CABLE
40 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
40 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
40 2 EACH 50-0118 FRONT END PACK, 2"-3"
40 52 FT 01-6471 CONDUIT, 3"
40 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
40 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
40 2 EACH 36-0421 BELL END, 3"
40 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
41 1 EACH 26-1533 TX,PM,100KVA,12/21KV, 3 WIRE, DF-LB
41 1 EACH 36-0003 BOX PAD, 50" X 52" X 18"
41 6 EACH 30-0480 ELBOW, 200A, LB
41 6 EACH 30-0481 BUSHING INSERT, LB
41 3 EACH 03-1604 SEC CONN, BAR TYPE
41 15 FT 29-0074 WIRE, #2AWG, SOLID CU
41 2 EACH 18-7013 GROUND ROD, 5/8"X8'
41 2 EACH 18-7012 GROUND ROD CLAMP, 5/8"
41 1 EACH 49-5228 COMPOUND CAULKING
41 1 EACH 01-6583 PADLOCK, CORPORATION
41 2 EACH 19-2874 BOLT, 1/2"-13 X 1 1/2"
41 2 EACH 19-5286 WASHER, 2 1/4" SQUARE
41 1 EACH 36-2624 FAULT INDICATOR, 450A, 3-WIRE
42 74 FT 29-4372 350A TPX 600V CABLE
42 4 EACH 38-4200 350A SECONDARY CABLE END CAP
42 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
42 2 EACH 50-0117 FRONT END PACK, 4"-6"
42 60 FT 01-6472 CONDUIT, 4"
42 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
42 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
42 2 EACH 36-0423 BELL END, 4"
42 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
43 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
43 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
44 134 FT 29-4372 350A TPX 600V CABLE
44 4 EACH 38-4200 350A SECONDARY CABLE END CAP
44 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
44 2 EACH 50-0117 FRONT END PACK, 4"-6"
44 120 FT 01-6472 CONDUIT, 4"
44 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
44 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
44 2 EACH 36-0423 BELL END, 4"
44 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
45 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
45 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
46 374 FT 29-0047 CABLE, 3-1/0AL, EPR-CONC-ENCAP 25KV
46 6 EACH 38-4202 1/0A PRIMARY CABLE END CAP
46 2 EACH 50-0117 FRONT END PACK, 4"-6"
46 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
46 360 FT 01-6472 CONDUIT, 4"
46 2 EACH 36-0761 BEND, 4", 22 DEG, 60"R
46 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
46 2 EACH 36-0423 BELL END, 4"
46 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
47 152 FT 29-4371 4/0A TPX 600V CABLE
47 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
47 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
47 2 EACH 50-0118 FRONT END PACK, 2"-3"
47 138 FT 01-6471 CONDUIT, 3"
47 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
47 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
47 2 EACH 36-0421 BELL END, 3"
47 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
48 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
48 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
49 64 FT 29-4372 350A TPX 600V CABLE
49 4 EACH 38-4200 350A SECONDARY CABLE END CAP
49 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
49 2 EACH 50-0117 FRONT END PACK, 4"-6"
49 50 FT 01-6472 CONDUIT, 4"
49 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
49 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
49 2 EACH 36-0423 BELL END, 4"
49 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
50 54 FT 29-4371 4/0A TPX 600V CABLE
50 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
50 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
50 2 EACH 50-0118 FRONT END PACK, 2"-3"
50 40 FT 01-6471 CONDUIT, 3"
50 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
50 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
50 2 EACH 36-0421 BELL END, 3"
50 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
51 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
51 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
52 1 EACH 26-1508 TX,PM,50KVA,12/21,2 WIRE,LB,DF
52 1 EACH 36-0001 BOX PAD, 36" X 52" X 18"
52 2 EACH 30-0480 ELBOW, 200A, LB
52 2 EACH 30-0481 BUSHING INSERT, LB
52 2 EACH 30-0486 INSULATED BUSHING WELL PLUG
52 3 EACH 03-1604 SEC CONN, BAR TYPE
52 15 FT 29-0074 WIRE, #2AWG, SOLID CU
52 2 EACH 18-7013 GROUND ROD, 5/8"X8'
52 2 EACH 18-7012 GROUND ROD CLAMP, 5/8"
52 1 EACH 49-5228 COMPOUND CAULKING
52 1 EACH 01-6583 PADLOCK, CORPORATION
52 2 EACH 19-2874 BOLT, 1/2"-13 X 1 1/2"
52 2 EACH 19-5286 WASHER, 2 1/4" SQUARE
53 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
53 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
54 74 FT 29-4371 4/0A TPX 600V CABLE
54 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
54 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
54 2 EACH 50-0118 FRONT END PACK, 2"-3"
54 60 FT 01-6471 CONDUIT, 3"
54 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
54 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
54 2 EACH 36-0421 BELL END, 3"
54 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
55 1 EACH 26-1533 TX,PM,100KVA,12/21KV, 3 WIRE, DF-LB
55 1 EACH 36-0003 BOX PAD, 50" X 52" X 18"
55 6 EACH 30-0480 ELBOW, 200A, LB
55 6 EACH 30-0481 BUSHING INSERT, LB
55 3 EACH 03-1604 SEC CONN, BAR TYPE
55 15 FT 29-0074 WIRE, #2AWG, SOLID CU
55 2 EACH 18-7013 GROUND ROD, 5/8"X8'
55 2 EACH 18-7012 GROUND ROD CLAMP, 5/8"
55 1 EACH 49-5228 COMPOUND CAULKING
55 1 EACH 01-6583 PADLOCK, CORPORATION
55 2 EACH 19-2874 BOLT, 1/2"-13 X 1 1/2"
55 2 EACH 19-5286 WASHER, 2 1/4" SQUARE
55 1 EACH 36-2624 FAULT INDICATOR, 450A, 3-WIRE
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
56 105 FT 29-0372 750A TPX 600V CABLE
56 4 EACH 38-4201 750A SECONDARY CABLE END CAP
56 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
56 2 EACH 50-0117 FRONT END PACK, 4"-6"
56 90 FT 01-6472 CONDUIT, 4"
56 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
56 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
56 2 EACH 36-0423 BELL END, 4"
56 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
57 1 EACH 04-0942 24" X 36" X 26" SEC BOX, IVT
57 1 EACH 02-6694 6-WAY SEC. BUS, (4) #6-350A, (2) 4/0A-1000A
58 64 FT 29-0372 750A TPX 600V CABLE
58 4 EACH 38-4201 750A SECONDARY CABLE END CAP
58 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
58 2 EACH 50-0117 FRONT END PACK, 4"-6"
58 49 FT 01-6472 CONDUIT, 4"
58 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
58 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
58 2 EACH 36-0423 BELL END, 4"
58 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
59 1 EACH 04-0942 24" X 36" X 26" SEC BOX, IVT
59 1 EACH 02-6694 6-WAY SEC. BUS, (4) #6-350A, (2) 4/0A-1000A
60 151 FT 29-4372 350A TPX 600V CABLE
60 4 EACH 38-4200 350A SECONDARY CABLE END CAP
60 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
60 2 EACH 50-0117 FRONT END PACK, 4"-6"
60 136 FT 01-6472 CONDUIT, 4"
60 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
60 3 EACH 36-0414 BEND, 4", 90 DEG, 36"R
60 2 EACH 36-0423 BELL END, 4"
60 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
61 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
61 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
62 133 FT 29-4371 4/0A TPX 600V CABLE
62 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
62 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
62 2 EACH 50-0118 FRONT END PACK, 2"-3"
62 119 FT 01-6471 CONDUIT, 3"
62 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
62 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
62 2 EACH 36-0421 BELL END, 3"
62 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
63 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
63 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
64 69 FT 29-4371 4/0A TPX 600V CABLE
64 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
64 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
64 2 EACH 50-0118 FRONT END PACK, 2"-3"
64 55 FT 01-6471 CONDUIT, 3"
64 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
64 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
64 2 EACH 36-0421 BELL END, 3"
64 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
65 1 EACH 26-1533 TX,PM,100KVA,12/21KV, 3 WIRE, DF-LB
65 1 EACH 36-0003 BOX PAD, 50" X 52" X 18"
65 5 EACH 30-0480 ELBOW, 200A, LB
65 5 EACH 30-0481 BUSHING INSERT, LB
65 1 EACH 30-0486 INSULATED BUSHING WELL PLUG
65 3 EACH 03-1604 SEC CONN, BAR TYPE
65 15 FT 29-0074 WIRE, #2AWG, SOLID CU
65 2 EACH 18-7013 GROUND ROD, 5/8"X8'
65 2 EACH 18-7012 GROUND ROD CLAMP, 5/8"
65 1 EACH 49-5228 COMPOUND CAULKING
65 1 EACH 01-6583 PADLOCK, CORPORATION
65 2 EACH 19-2874 BOLT, 1/2"-13 X 1 1/2"
65 2 EACH 19-5286 WASHER, 2 1/4" SQUARE
65 2 EACH 36-2623 FAULT INDICATOR, 450 A, 2WIRE
66 69 FT 29-4372 350A TPX 600V CABLE
66 4 EACH 38-4200 350A SECONDARY CABLE END CAP
66 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
66 2 EACH 50-0117 FRONT END PACK, 4"-6"
66 55 FT 01-6472 CONDUIT, 4"
66 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
66 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
66 2 EACH 36-0423 BELL END, 4"
66 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
67 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
67 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
68 124 FT 29-4372 350A TPX 600V CABLE
68 4 EACH 38-4200 350A SECONDARY CABLE END CAP
68 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
68 2 EACH 50-0117 FRONT END PACK, 4"-6"
68 110 FT 01-6472 CONDUIT, 4"
68 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
68 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
68 2 EACH 36-0423 BELL END, 4"
68 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
69 527 FT 29-0047 CABLE, 3-1/0AL, EPR-CONC-ENCAP 25KV
69 6 EACH 38-4202 1/0A PRIMARY CABLE END CAP
69 3 EACH 50-0117 FRONT END PACK, 4"-6"
69 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
69 513 FT 01-6472 CONDUIT, 4"
69 2 EACH 36-0805 BEND, 4", 11 DEG, 60"R
69 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
69 1 EACH 36-0415 BEND, 4", 90 DEG, 60"R
69 2 EACH 36-0423 BELL END, 4"
69 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
70 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
70 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
71 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
71 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
71 254 FT 29-4370 1/0A TPX 600V CABLE 1630
71 4 EACH 38-4198 1/0A SECONDARY CABLE END CAP 1630
71 2 EACH 38-4197 #2A SECONDARY CABLE END CAP 1630
71 2 EACH 50-0118 FRONT END PACK, 2"-3"1630
71 240 FT 01-6471 CONDUIT, 3"1632
71 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R 1632
71 1 EACH 36-0405 BEND, 3", 90 DEG, 24"R 1632
71 1 EACH 36-0328 BEND, 3", 90 DEG, 36"R 1632
71 1 EACH 36-0421 BELL END, 3"1632
71 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"1632
71 1 EACH NO CODE METER, CL.200, 100 AMS, 120/240 1PH.^
72 695 FT 29-0046 CABLE, 2-1/0AL, EPR-CONC-ENCAP 25KV
72 4 EACH 38-4202 1/0A PRIMARY CABLE END CAP
72 4 EACH 50-0117 FRONT END PACK, 4"-6"
72 1 EACH 50-0031 LUBRICANT, CABLE PULLING 2.5 GAL.
72 681 FT 01-6472 CONDUIT, 4"
72 2 EACH 36-0805 BEND, 4", 11 DEG, 60"R
72 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
72 1 EACH 36-0415 BEND, 4", 90 DEG, 60"R
72 2 EACH 36-0423 BELL END, 4"
72 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
73 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
73 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
74 156 FT 29-4372 350A TPX 600V CABLE
74 4 EACH 38-4200 350A SECONDARY CABLE END CAP
74 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
74 2 EACH 50-0117 FRONT END PACK, 4"-6"
74 142 FT 01-6472 CONDUIT, 4"
74 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
74 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
74 2 EACH 36-0423 BELL END, 4"
74 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
75 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
75 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
76 156 FT 29-4372 350A TPX 600V CABLE
76 4 EACH 38-4200 350A SECONDARY CABLE END CAP
76 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
76 2 EACH 50-0117 FRONT END PACK, 4"-6"
76 142 FT 01-6472 CONDUIT, 4"
76 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
76 3 EACH 36-0414 BEND, 4", 90 DEG, 36"R
76 2 EACH 36-0423 BELL END, 4"
76 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
77 1 EACH 04-0937 17" X 30" X 26" SEC BOX, IVT
77 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
78 69 FT 29-4372 350A TPX 600V CABLE
78 4 EACH 38-4200 350A SECONDARY CABLE END CAP
78 2 EACH 38-4199 4/0A SECONDARY CABLE END CAP
78 2 EACH 50-0117 FRONT END PACK, 4"-6"
78 55 FT 01-6472 CONDUIT, 4"
78 2 EACH 36-0760 BEND, 4", 22 DEG, 36"R
78 2 EACH 36-0414 BEND, 4", 90 DEG, 36"R
78 2 EACH 36-0423 BELL END, 4"
78 2 EACH 36-0443 TEMPORARY CAP PLUG, 4"
79 1 EACH 26-1533 TX,PM,100KVA,12/21KV, 3 WIRE, DF-LB
79 1 EACH 36-0003 BOX PAD, 50" X 52" X 18"
79 2 EACH 30-0480 ELBOW, 200A, LB
79 2 EACH 30-0481 BUSHING INSERT, LB
79 2 EACH 30-0486 INSULATED BUSHING WELL PLUG
79 3 EACH 03-1604 SEC CONN, BAR TYPE
79 15 FT 29-0074 WIRE, #2AWG, SOLID CU
79 2 EACH 18-7013 GROUND ROD, 5/8"X8'
79 2 EACH 18-7012 GROUND ROD CLAMP, 5/8"
79 1 EACH 49-5228 COMPOUND CAULKING
79 1 EACH 01-6583 PADLOCK, CORPORATION
79 2 EACH 19-2874 BOLT, 1/2"-13 X 1 1/2"
79 2 EACH 19-5286 WASHER, 2 1/4" SQUARE
80 69 FT 29-4371 4/0A TPX 600V CABLE
80 4 EACH 38-4199 4/0A SECONDARY CABLE END CAP
80 2 EACH 38-4198 1/0A SECONDARY CABLE END CAP
80 2 EACH 50-0118 FRONT END PACK, 2"-3"
80 55 FT 01-6471 CONDUIT, 3"
80 2 EACH 36-0800 BEND, 3", 22 DEG, 36"R
80 2 EACH 36-0405 BEND, 3", 90 DEG, 24"R
80 2 EACH 36-0421 BELL END, 3"
80 2 EACH 36-0441 TEMPORARY CAP PLUG, 3"
81 1 EACH 04-0936 17" X 30" X 18" SEC BOX, IVT
81 3 EACH 30-0552 6-WAY SEC. BUS, #6-350A
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
998 3592 FT 01-6471 CONDUIT, 3"1602
998 81 EACH 36-0405 BEND, 3", 90 DEG, 24"R 1602
998 30 EACH 36-0800 BEND, 3", 22.5 DEG, 36"R 1602
998 30 EACH 36-0328 BEND, 3", 90 DEG, 36"R 1602
998 81 EACH 36-0441 TEMPORARY CAP, 3"1602
998 81 EACH 36-0421 BELL END, 3"1602
999 6940 FT 29-4371 SERVICE CABLE, 4/0A TPX 1600
999 328 EACH 38-4199 4/0A CABLE END CAP 1600
999 164 EACH 38-4198 1/0A CABLE END CAP 1600
999 82 EACH 50-0118 FRONT END PACK, 2"-3"1600
999 2121 FT 01-6471 CONDUIT, 3"1603
999 82 EACH 36-0800 BEND, 3", 22.5 DEG, 36"R 1603
999 82 EACH 36-0441 TEMPORARY CAP, 3"1603
999 82 EACH NO CODE METER, CL.200, 200 AMS, 120/240 1PH.^
PM# 35274099
11/12/21
GDSI
"^" PG Ins Mat
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat"1602" Ap Ins Non Res Sv Dct Frnch
APPLICANT INSTALL MATERIAL SUMMARY
MATERIAL CODE FOOTNOTE DESCRIPTION EACH/FT.Total
01-6471 (blank)CONDUIT, 3"FT 1135
1602 CONDUIT, 3"FT 3592
1603 CONDUIT, 3"FT 2121
1632 CONDUIT, 3"FT 240
01-6472 (blank)CONDUIT, 4"FT 4274
01-6583 (blank)PADLOCK, CORPORATION EACH 8
01-8799 (blank)FAULT INDICATOR BRACKET EACH 2
02-6694 (blank)6-WAY SEC. BUS, (4) #6-350A, (2) 4/0A-1000A EACH 2
03-1604 (blank)SEC CONN, BAR TYPE EACH 24
04-0936 (blank)17" X 30" X 18" SEC BOX, IVT EACH 15
04-0937 (blank)17" X 30" X 26" SEC BOX, IVT EACH 1204-0942 (blank)24" X 36" X 26" SEC BOX, IVT EACH 2
18-7012 (blank)GROUND ROD CLAMPS EACH 2
GROUND ROD CLAMP, 5/8"EACH 20
18-7013 (blank)GROUND ROD, 5/8" x 8'EACH 1
GROUND ROD, 5/8"X8'EACH 18
19-0445 (blank)ANCHOR BOLT EACH 4
19-2874 (blank)BOLT, 1/2"-13 X 1 1/2"EACH 16
19-5286 (blank)WASHER, 2 1/4" SQUARE EACH 16
26-1508 (blank)TX,PM,50KVA,12/21,2 WIRE,LB,DF EACH 3
26-1509 (blank)TX,PM,100KVA,12/21,2 WIRE,LB,DF EACH 1
26-1533 (blank)TX,PM,100KVA,12/21KV, 3 WIRE, DF-LB EACH 4
29-0046 (blank)CABLE, 2-1/0AL, EPR-CONC-ENCAP 25KV FT 1849
29-0047 (blank)CABLE, 3-1/0AL, EPR-CONC-ENCAP 25KV FT 2657
29-0073 (blank)RISER BUS, #4Cu WIRE FT 45
29-0074 (blank)WIRE, #2AWG, SOLID CU FT 165
29-0372 (blank)750A TPX 600V CABLE FT 169
29-4370 1630 1/0A TPX 600V CABLE FT 254
29-4371 (blank)4/0A TPX 600V CABLE FT 1345
1600 SERVICE CABLE, 4/0A TPX FT 6940
29-4372 (blank)350A TPX 600V CABLE FT 1230
30-0480 (blank)ELBOW, 200A, LB EACH 41
30-0481 (blank)BUSHING INSERT, LB EACH 41
30-0486 (blank)INSULATED BUSHING WELL PLUG EACH 9
30-0552 (blank)6-WAY SEC. BUS, #6-350A EACH 81
30-5244 (blank)CONNECTOR, COMPRESSION EACH 1636-0001 (blank)BOX PAD, 36" X 52" X 18"EACH 3
36-0003 (blank)BOX PAD, 50" X 52" X 18"EACH 5
36-0038 (blank)JUNCTION BOX BAD, POLYMER CONCRETE EACH 1
36-0040 (blank)PAD-MOUNTED JUNCTION BOX, STEEL-NON COREACH 1
36-0075 (blank)REDUCER BOOT, 4" X 3" X 2"EACH 2
PM# 35274099
11/12/21GDSI 16
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch
"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat
"1602" Ap Ins Non Res Sv Dct Frnch
36-0328 (blank)BEND, 3", 90 DEG, 36"R EACH 1
1602 BEND, 3", 90 DEG, 36"R EACH 30
1632 BEND, 3", 90 DEG, 36"R EACH 1
36-0405 (blank)BEND, 3", 90 DEG, 24"R EACH 30
1602 BEND, 3", 90 DEG, 24"R EACH 81
1632 BEND, 3", 90 DEG, 24"R EACH 1
36-0414 (blank)BEND, 4", 90 DEG, 36"R EACH 49
RISER BEND, 4"EACH 236-0415 (blank)BEND, 4", 90 DEG, 60"R EACH 6
36-0421 (blank)BELL END, 3" EACH 30
1602 BELL END, 3"EACH 81
1632 BELL END, 3" EACH 1
36-0423 (blank)BELL END, 4"EACH 45
36-0441 (blank)TEMPORARY CAP PLUG, 3"EACH 30
1602 TEMPORARY CAP, 3"EACH 81
1603 TEMPORARY CAP, 3"EACH 82
1632 TEMPORARY CAP PLUG, 3"EACH 2
36-0443 (blank)TEMPORARY CAP PLUG, 4"EACH 45
36-0542 (blank)3" PVC BACK-UP PLATE EACH 2
36-0673 (blank)10' LENGTH, 3" RISER MOULD.EACH 1
36-0760 (blank)BEND, 4", 22 DEG, 36"R EACH 28
36-0761 (blank)BEND, 4", 22 DEG, 60"R EACH 7
36-0800 (blank)BEND, 3", 22 DEG, 36"R EACH 30
1602 BEND, 3", 22.5 DEG, 36"R EACH 30
1603 BEND, 3", 22.5 DEG, 36"R EACH 82
1632 BEND, 3", 22 DEG, 36"R EACH 2
36-0805 (blank)BEND, 4", 11 DEG, 60"R EACH 10
36-2616 (blank)PRIMARY RACKING, KIT 2 (12" ROD)EACH 4
36-2623 (blank)FAULT INDICATOR, 450 A, 2WIRE EACH 8
36-2624 (blank)FAULT INDICATOR, 450 A, 3WIRE EACH 1
FAULT INDICATOR, 450A, 3-WIRE EACH 2
38-4197 1630 #2A SECONDARY CABLE END CAP EACH 2
38-4198 (blank)1/0A SECONDARY CABLE END CAP EACH 3016001/0A CABLE END CAP EACH 164
1630 1/0A SECONDARY CABLE END CAP EACH 4
38-4199 (blank)4/0A SECONDARY CABLE END CAP EACH 88
1600 4/0A CABLE END CAP EACH 328
38-4200 (blank)350A SECONDARY CABLE END CAP EACH 48
38-4201 (blank)750A SECONDARY CABLE END CAP EACH 8
38-4202 (blank)1/0A PRIMARY CABLE END CAP EACH 56
49-5228 (blank)COMPOUND CAULKING EACH 8
50-0031 (blank)LUBRICANT, CABLE PULLING 2.5 GAL.EACH 11
50-0117 (blank)FRONT END PACK, 4"-6"EACH 56
PM# 35274099
11/12/21GDSI 17
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch
"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat
"1602" Ap Ins Non Res Sv Dct Frnch
50-0118 (blank)FRONT END PACK, 2"-3"EACH 30
1600 FRONT END PACK, 2"-3"EACH 82
1630 FRONT END PACK, 2"-3"EACH 2
AS REQ'D (blank)PHASE AND VOLTAGE TAG EACH
SECTIONALIZING TAG EACH
LABOR (blank)CONNECT CONDUIT EACH 1
PM# 35274099
11/12/21GDSI 18
"blank" Ap Ins Mat
"1600" Ap Ins Sv Mat"1602" Ap Ins Sv Dct Frnch
"1603" Ap Ins Sv Dt P/P"1630" Ap Ins Npn Res Sv Mat
"1602" Ap Ins Non Res Sv Dct Frnch
PG&E INSTALL MATERIAL SUMMARY
MATERIAL CODE FOOTNOTE DESCRIPTION EACH/FT.Total
03-1942 ^CABLE TERM. #4-1/0A, 25KV EACH 3
18-0134 ^RISER BKT. COMBO EACH 1
18-4223 ^CABLE GRIP, PT-7 EACH 1
29-0290 ^PRIMARY LEAD WIRE, 2C EACH 3
30-0425 ^FIRED WEDGE CONNECTOR EACH 3
30-3845 ^CABLE PIN TERMINAL 1/0A EACH 3
33-0306 ^CUTOUT, PT-44H EACH 3
33-2276 ^FUSE, POWER TYPE "E", SMU-20, 23KV, 65 AMPEACH 3
36-0673 ^10' LENGTH, 3" RISER MOULD.EACH 3
37-3038 ^HIGH VOLTAGE SIGN EACH 2
38-2045 ^CABLE PROTECTOR EACH 1
LABOR ^CONNECT SERVICE EACH 1
NO CODE ^METER, CL.200, 200 AMS, 120/240 1PH.EACH 82
METER, CL.200, 100 AMS, 120/240 1PH.EACH 1
PM# 3527409911/12/21
GDSI 19 "^" PG Inst Matl
PACIFIC GAS & ELECTRIC COMPANYCIRCUIT MAP CHANGE SHEET
Date
ILIS Event No.GIS Tag No.
Control Center/AOR Substation & Curcuit Number STOCKDALE 2112
Prepare By Engineering Approved By
BJ137-N13 & N14 Job Number
Purpose of Work NEW BUSINESS MAT
Location McCUTCHEN ROAD & GOSFORD ROAD Town
Loc.Location
800 E/S OF GOSFORD RD., 32' N/O McCUTHEN RD.
8 N/S OF AVACADO LN., 127' E/O STRAWBERRY LN.
41 E/S OF STRAWBERRY LN., 78' N/O CRANBERRY LN.
55 E/S OF STRAWBERRY LN., 218' S/O GOOSEBERRY AVE.
65 N/S OF GOOSEBERRY AVE., 265' E/O STRAWBERRY LN.
79 E/S OF CHERIMOYA., 127' S/O GOOSEBERRY AVE.
26 N/S OF CRANBERRY WY., 147' E/O STRAWBERRY LN.
32 E/S OF RASBERRY AVE., 48' N/O CRANBERRY WY.
52 E/S OF RASBERRY AVE., 127' N/O BANANA CLUSTER AVE.
19 E/S OF STRAWBERRY LN., 122' N/O AVACADO LN.
SEE KEY SKETCH
DateDate
DateDate
BAKERSFIELD
BAKERSFIELD
BAKERSFIELD
J-_____BAKERSFIELD
T-15
T-16
T-17
T-18
BAKERSFIELD
BAKERSFIELD
11/12/2021
New Equip. No.Serial No.Manufacture Date Manuf.
Map No.
BAKERSFIELD
B. RUBIO
35274099
Town
BAKERSFIELD
BAKERSFIELD
C/O-_____
T-11
Recorded at Control Center byWork competed by
BAKERSFIELD
BAKERSFIELD
T-12
T-13
T-14
Mapped by
Forward this completed form to
Forman must immediatley report any completed work. For partially completed work, circle the portion that was completed. Include the date & show "completed."
VOLTAGE & FLICKER DROP CALCULATIONS LOADING CRITERIA:CLIMATE ZONE R WITH 4 TON A/C
PM# 35274099 NEW SERVICE INFO:1,917 AVG. SQ.FT, 200 AMS
JOB# 21-146 4/0A TPX SVC IN 3" CONDUIT
T-11 LOTS 48/49
LOT 58
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 11 74 0.02392 1.77 100 KVA PM TX 0.53 1.2 0.64
350A TPX SEC 8 58 0.258 69 1.03 350A TPX SEC 0.0062 69 1.2 0.51
350A TPX SEC 4 34 0.258 62 0.54 350A TPX SEC 0.0062 62 1.2 0.46
350A TPX SEC 2 21 0.258 102 0.55 350A TPX SEC 0.0062 102 1.2 0.76
4/0A TPX SVC 1 13.3 0.381 99 0.50 4/0A TPX SVC 0.0091 99 1.2 1.08
TOTAL =4.4 VOLTS TOTAL 3.5 VOLTS
LOT 52
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 11 74 0.02392 1.77 100 KVA PM TX 0.53 1.2 0.64
4/0A TPX SEC 3 27 0.381 79 0.81 4/0A TPX SEC 0.0091 79 1.2 0.86
4/0A TPX SEC 1 13.3 0.381 138 0.70 4/0A TPX SEC 0.0091 138 1.2 1.51
4/0A TPX SVC 1 13.3 0.381 45 0.23 4/0A TPX SVC 0.0091 45 1.2 0.49
TOTAL =3.5 VOLTS TOTAL 3.5 VOLTS
T-12 LOTS 24/25
LOT 66
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 13 85 0.02392 2.03 100 KVA PM TX 0.53 1.2 0.64
350A TPX SEC 8 58 0.258 74 1.11 350A TPX SEC 0.0062 74 1.2 0.55
350A TPX SEC 4 34 0.258 134 1.18 350A TPX SEC 0.0062 134 1.2 1.00
4/0A TPX SVC 1 13.3 0.381 111 0.56 4/0A TPX SVC 0.0091 111 1.2 1.21TOTAL =4.9 VOLTS TOTAL 3.4 VOLTS
LOT 60
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 13 85 0.02392 2.03 100 KVA PM TX 0.53 1.2 0.64
4/0A TPX SEC 5 39 0.381 66 0.98 4/0A TPX SEC 0.0091 66 1.2 0.72
4/0A TPX SEC 2 21 0.381 124 0.99 4/0A TPX SEC 0.0091 124 1.2 1.35
4/0A TPX SVC 1 13.3 0.381 99 0.50 4/0A TPX SVC 0.0091 99 1.2 1.08
TOTAL =4.5 VOLTS TOTAL 3.8 VOLTS
PM# 3527409911/12/21GDSI 1
VOLTAGE & FLICKER DROP CALCULATIONS LOADING CRITERIA:CLIMATE ZONE R WITH 4 TON A/C
PM# 35274099 NEW SERVICE INFO:1,917 AVG. SQ.FT, 200 AMS
JOB# 21-146 4/0A TPX SVC IN 3" CONDUIT
T-13 LOTS 18/19 + (1) 100A POWER SUPPLY = 2KVA
LOT 1
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 12 + 1 80 0.02392 1.91 100 KVA PM TX 0.53 1.2 0.64
750A TPX SEC 8 + 1 60 0.1508 105 0.95 750A TPX SEC 0.0036 105 1.2 0.45
750A TPX SEC 5 + 1 41 0.1508 64 0.40 750A TPX SEC 0.0036 64 1.2 0.28
350A TPX SEC 3 + 1 29 0.258 151 1.13 350A TPX SEC 0.0062 151 1.2 1.12
4/0A TPX SVC 1 13.3 0.381 100 0.51 4/0A TPX SVC 0.0091 100 1.2 1.09TOTAL =4.9 VOLTS TOTAL 3.6 VOLTS
LOT 68
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 12 + 1 80 0.02392 1.91 100 KVA PM TX 0.53 1.2 0.64
4/0A TPX SEC 4 34 0.381 74 0.96 4/0A TPX SEC 0.0091 74 1.2 0.81
4/0A TPX SVC 1 13.3 0.381 122 0.62 4/0A TPX SVC 0.0091 122 1.2 1.33
TOTAL =3.5 VOLTS TOTAL 2.8 VOLTS
100A CATV
VOLTAGE DROP
# CUSTOMERS KVA K DISTANCE TOTAL
100 KVA PM TX 12 + 1 80 0.02392 1.91
750A TPX SEC 8 + 1 60 0.1508 105 0.95
750A TPX SEC 5 + 1 41 0.1508 64 0.40
350A TPX SEC 3 + 1 29 0.258 151 1.13
4/0A TPX SVC 1 2 0.701 254 0.36
TOTAL =4.7 VOLTS
T-14 LOTS 7/8
LOT 17
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 14 90 0.02392 2.15 100 KVA PM TX 0.53 1.2 0.64
350A TPX SEC 8 58 0.258 69 1.03 350A TPX SEC 0.0062 69 1.2 0.51
350A TPX SEC 4 34 0.258 124 1.09 350A TPX SEC 0.0062 124 1.2 0.92
4/0A TPX SVC 1 13.3 0.381 105 0.53 4/0A TPX SVC 0.0091 105 1.2 1.15
TOTAL =4.8 VOLTS TOTAL 3.2 VOLTS
LOT 11
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 14 90 0.02392 2.15 100 KVA PM TX 0.53 1.2 0.64
4/0A TPX SEC 6 46 0.381 69 1.21 4/0A TPX SEC 0.0091 69 1.2 0.75
4/0A TPX SEC 2 21 0.381 133 1.06 4/0A TPX SEC 0.0091 133 1.2 1.45
4/0A TPX SVC 1 13.3 0.381 58 0.29 4/0A TPX SVC 0.0091 58 1.2 0.63
TOTAL =4.7 VOLTS TOTAL 3.5 VOLTS
PM# 3527409911/12/21GDSI 2
VOLTAGE & FLICKER DROP CALCULATIONS LOADING CRITERIA:CLIMATE ZONE R WITH 4 TON A/C
PM# 35274099 NEW SERVICE INFO:1,917 AVG. SQ.FT, 200 AMS
JOB# 21-146 4/0A TPX SVC IN 3" CONDUIT
T-15 LOTS 74/75
LOT 81
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 10 74 0.02392 1.77 100 KVA PM TX 0.53 1.2 0.64
350A TPX SEC 8 58 0.258 69 1.03 350A TPX SEC 0.0062 69 1.2 0.51
350A TPX SEC 4 34 0.258 156 1.37 350A TPX SEC 0.0062 156 1.2 1.16
350A TPX SEC 2 21 0.258 100 0.54 350A TPX SEC 0.0062 100 1.2 0.74
4/0A TPX SVC 1 13.3 0.381 47 0.24 4/0A TPX SVC 0.0091 47 1.2 0.51TOTAL =5.0 VOLTS TOTAL 3.6 VOLTS
LOT 76
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 10 74 0.02392 1.77 100 KVA PM TX 0.53 1.2 0.64
4/0A TPX SEC 2 21 0.381 69 0.55 4/0A TPX SEC 0.0091 69 1.2 0.75
4/0A TPX SVC 1 13.3 0.381 47 0.24 4/0A TPX SVC 0.0091 47 1.2 0.51
TOTAL =2.6 VOLTS TOTAL 1.9 VOLTS
T-16 LOTS 25/26
LOT 41
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
50 KVA PM TX 7 51 0.04687 2.39 50 KVA PM TX 1 1.2 1.20
4/0A TPX SEC 4 34 0.381 114 1.48 4/0A TPX SEC 0.0091 114 1.2 1.24
4/0A TPX SEC 2 21 0.381 95 0.76 4/0A TPX SEC 0.0091 95 1.2 1.04
4/0A TPX SVC 1 13.3 0.381 47 0.24 4/0A TPX SVC 0.0091 47 1.2 0.51TOTAL =4.9 VOLTS TOTAL 4.0 VOLTS
LOT 46
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
50 KVA PM TX 7 51 0.04687 2.39 50 KVA PM TX 1 1.2 1.20
4/0A TPX SEC 3 27 0.381 29 0.30 4/0A TPX SEC 0.0091 29 1.2 0.32
4/0A TPX SVC 1 13.3 0.381 157 0.80 4/0A TPX SVC 0.0091 157 1.2 1.71TOTAL =3.5 VOLTS TOTAL 3.2 VOLTS
PM# 3527409911/12/21GDSI 3
VOLTAGE & FLICKER DROP CALCULATIONS LOADING CRITERIA:CLIMATE ZONE R WITH 4 TON A/C
PM# 35274099 NEW SERVICE INFO:1,917 AVG. SQ.FT, 200 AMS
JOB# 21-146 4/0A TPX SVC IN 3" CONDUIT
T-17 LOTS 39/40
LOT 28
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
50 KVA PM TX 6 46 0.04687 2.16 50 KVA PM TX 1 1.2 1.20
4/0A TPX SEC 6 46 0.381 75 1.31 4/0A TPX SEC 0.0091 75 1.2 0.82
4/0A TPX SEC 3 27 0.381 74 0.76 4/0A TPX SEC 0.0091 74 1.2 0.81
4/0A TPX SVC 1 13.3 0.381 136 0.69 4/0A TPX SVC 0.0091 136 1.2 1.49
TOTAL =4.9 VOLTS TOTAL 4.3 VOLTS
T-18 LOTS 34/35
LOT 30
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 8 58 0.02392 1.39 100 KVA PM TX 0.53 1.2 0.64
350A TPX SEC 6 46 0.258 64 0.76 350A TPX SEC 0.0062 64 1.2 0.48
4/0A TPX SEC 2 27 0.381 152 1.56 4/0A TPX SEC 0.0091 152 1.2 1.66
4/0A TPX SVC 1 13.3 0.381 129 0.65 4/0A TPX SVC 0.0091 129 1.2 1.41TOTAL =4.4 VOLTS TOTAL 4.2 VOLTS
LOT 33
VOLTAGE DROP VOLTAGE FLICKER
# CUSTOMERS KVA K DISTANCE TOTAL K DIST.A/C MULT.TOTAL
100 KVA PM TX 8 58 0.02392 1.39 100 KVA PM TX 0.53 1.2 0.64
4/0A TPX SEC 2 27 0.381 54 0.56 4/0A TPX SEC 0.0091 54 1.2 0.59
4/0A TPX SVC 1 13.3 0.381 139 0.70 4/0A TPX SVC 0.0091 139 1.2 1.52TOTAL =2.6 VOLTS TOTAL 2.7 VOLTS
PM# 3527409911/12/21GDSI 4
SERVICE SUMMARY
PM# 35274099200AMP PANELS
1602 (Stubs)
Franchise Conduit
1602 (Stubs) Franchise 90 Deg. 24" R
1602 (Stubs) Franchise 22 Deg. 36" R
1602 (Stubs) Franchise 90 Deg. 36" R
1603 PVT. PRP. Conduit
1603 PVT. PRP. 22 DEG 36" R
Total Service Length
1 61 1 1 1 25 1 100
2 6 1 25 1 45
3 6 1 27 1 474612514556127147
6 6 1 25 1 45
7 6 1 27 1 478612514596127147
10 6 1 30 1 50
11 6 1 30 1 50127911127112013791112511181478111251117
15 78 1 1 1 27 1 119168411125112317841112711251896111251136
19 6 1 25 1 45206127147216125145226127147
23 6 1 25 1 452461271472558111251972695111251134
27 95 1 1 1 25 1 134
28 95 1 1 1 27 1 13629881112511273088111271129
31 71 1 1 1 25 1 110
32 71 1 1 1 27 1 112331001251139343611125175
35 6 1 25 1 45
36 6 1 27 1 47376125145386125145396127147
40 6 1 25 1 454161271474266125110543661251105
44 58 1 25 1 97455812519746118111251157476125145
48 6 1 27 1 47
49 6 1 25 1 45506127147
Lot #
SERVICE SUMMARY
PM# 35274099200AMP PANELS
1602
(Stubs) Franchise Conduit
1602 (Stubs) Franchise 90
Deg. 24" R
1602 (Stubs) Franchise 22
Deg. 36" R
1602 (Stubs) Franchise 90
Deg. 36" R
1603 PVT. PRP.
Conduit
1603 PVT. PRP. 22
DEG 36" R
Total Service
Length
52 6 1 25 1 4553901112511295490111271131
55 88 1 1 1 27 1 129
56 88 1 1 1 25 1 127575812519758581271995958125197
60 58 1 27 1 99615812519762581271996358125197
64 58 1 27 1 99657011125110966701112711116781111251120
68 81 1 1 1 27 1 1226986111251126708611127112871701251110
72 70 1 27 1 112
73 6 1 25 1 45746127147756125145
76 6 1 27 1 47
77 0 20 1 10878701112511097970111271111
80 6 1 25 1 45
81 6 1 27 1 47826125145836127147
Totals 3592 81 30 30 2121 82 6940
Lot #
SERVICE SUMMARY
PM# 35274099200AMP PANELS
Total Number Of Lots 82 Total Meters 82
3" Conduit 3592
90 Deg. 24" Radius 8122 Deg. 36" Radius 3090 Deg. 36" Radius 30Bell Ends 81
Temporay Caps 81
3" Conduit 212122 Deg. 36" Radius 82Temporary Caps 82
Total Svc. Length 69404/0 Al Temp Caps 328
1/0 Al Temp Caps 164Front End Packs 82
1600 = LOC. 999
Results
1602 = LOC. 998
1603 = LOC. 999
CABLE PULLING CALCULATIONS
PM# 35274099
1/0A MAXIMUM TENSION = 1688/1688 LBS (GRIP/PULLING EYE)
DIRECTION OF PULL WITH LEAST TENSION AND LEAST # OF PULL SETUPS CONSIDERED
LOCATION 2 LOCATION 23
(3-1/0A EPR IN 4" CONDUIT)(2-1/0A EPR IN 4" CONDUIT)
BEND/STRAIGHT RUN TENSION OUT (LBS)BEND/STRAIGHT RUN TENSION OUT (LBS)
SECTION 1 90 DEG, 3' RADIUS 4 SECTION 1 90 DEG, 3' RADIUS 2SECTION 2 22 DEG, 5' RADIUS 6 SECTION 2 11 DEG, 5' RADIUS 3
SECTION 3 22'25 SECTION 3 137'65SECTION 4 90 DEG, 5' RADIUS 46 SECTION 4 90 DEG, 5' RADIUS 105
SECTION 5 625'577 SECTION 5 178'186SECTION 6 22 DEG, 5' RADIUS 666 SECTION 6 11 DEG, 5' RADIUS 197
SECTION 7 22 DEG, 5' RADIUS 768 SECTION 7 90 DEG, 3' RADIUS 316
LOCATION 4 LOCATION 29
(3-1/0A EPR IN 4" CONDUIT)(2-1/0A EPR IN 4" CONDUIT)
BEND/STRAIGHT RUN TENSION OUT (LBS)BEND/STRAIGHT RUN TENSION OUT (LBS)
SECTION 1 22 DEG, 5' RADIUS 2 SECTION 1 90 DEG, 3' RADIUS 2
SECTION 2 22 DEG, 5' RADIUS 3 SECTION 2 11 DEG, 5' RADIUS 3
SECTION 3 22'22 SECTION 3 40'21
SECTION 4 90 DEG, 5' RADIUS 41 SECTION 4 90 DEG, 5' RADIUS 34SECTION 5 178'192 SECTION 5 178'116
SECTION 6 90 DEG, 5' RADIUS 345 SECTION 6 11 DEG, 5' RADIUS 123SECTION 7 397'683 SECTION 7 90 DEG, 3' RADIUS 196
SECTION 8 22 DEG, 5' RADIUS 788
SECTION 9 22 DEG, 5' RADIUS 908 LOCATION 38
(2-1/0A EPR IN 4" CONDUIT)LOCATION 6
(3-1/0A EPR IN 4" CONDUIT)BEND/STRAIGHT RUN TENSION OUT (LBS)
SECTION 1 90 DEG, 3' RADIUS 2
BEND/STRAIGHT RUN TENSION OUT (LBS)SECTION 2 22 DEG, 5' RADIUS 3
SECTION 1 90 DEG, 3' RADIUS 4 SECTION 3 332'155
SECTION 2 22 DEG, 5' RADIUS 6 SECTION 4 22 DEG, 5' RADIUS 174
SECTION 3 114'103 SECTION 5 90 DEG, 3' RADIUS 279
SECTION 4 90 DEG, 5' RADIUS 185
SECTION 5 123'289 LOCATION 46
SECTION 6 22 DEG, 5' RADIUS 334 (3-1/0A EPR IN 4" CONDUIT)
SECTION 7 22 DEG, 5' RADIUS 385
BEND/STRAIGHT RUN TENSION OUT (LBS)LOCATION 7 SECTION 1 90 DEG, 3' RADIUS 4
(2-1/0A EPR IN 4" CONDUIT)SECTION 2 22 DEG, 5' RADIUS 6SECTION 3 360'312
BEND/STRAIGHT RUN TENSION OUT (LBS)SECTION 4 22 DEG, 5' RADIUS 360
SECTION 1 90 DEG, 3' RADIUS 2 SECTION 5 90 DEG, 3' RADIUS 645
SECTION 2 11 DEG, 5' RADIUS 3
SECTION 3 114'55 LOCATION 69
SECTION 4 90 DEG, 5' RADIUS 88 (3-1/0A EPR IN 4" CONDUIT)
SECTION 5 119'142SECTION 6 11 DEG, 5' RADIUS 151 BEND/STRAIGHT RUN TENSION OUT (LBS)
SECTION 7 90 DEG, 3' RADIUS 242 SECTION 1 90 DEG, 3' RADIUS 4
SECTION 2 11 DEG, 5' RADIUS 5LOCATION 21 SECTION 3 256'223
(3-1/0A EPR IN 4" CONDUIT)SECTION 4 90 DEG, 5' RADIUS 400SECTION 5 257'618
BEND/STRAIGHT RUN TENSION OUT (LBS)SECTION 6 11 DEG, 5' RADIUS 664SECTION 1 90 DEG, 3' RADIUS 4 SECTION 7 90 DEG, 3' RADIUS 1190
SECTION 2 22 DEG, 5' RADIUS 6
SECTION 3 230'202 LOCATION 72
SECTION 4 22 DEG, 5' RADIUS 233 (2-1/0A EPR IN 4" CONDUIT)
SECTION 5 90 DEG, 3' RADIUS 417
BEND/STRAIGHT RUN TENSION OUT (LBS)
SECTION 1 90 DEG, 3' RADIUS 2SECTION 2 11 DEG, 5' RADIUS 3
SECTION 3 178'84
SECTION 4 90 DEG, 5' RADIUS 135
SECTION 5 503'365
SECTION 6 11 DEG, 5' RADIUS 386
SECTION 7 90 DEG, 3' RADIUS 619
PM# 3527409911/12/21GDSI 1
Pole ID:21-146 NB PL LOC 800.pplx O-Calc®Pro Analysis -GO 95 Friday,November 12,2021 11:13 AM
User:BRubio GDSINC OCP:6.02 *Includes Load Factor(s)Page 1 of 4 2 Worst Wind Per Guy Wire 3Wind At 266.3°
Pole Num:Unset Pole Length /Class:55 /1 Code:GO 95 Structure Type:Unguyed Tangent
PM Order Number 35274099 Species:DOUGLAS FIR GO 95 Rule:At Installation (New)Pole Strength Factor:0.33
Estimator LAN ID Unset Setting Depth (ft):8.5 Construction Grade:B Transverse Wind LF:1.00
Sketch Location 800 G/L Circumference (in):45.51 Loading District:Light Wire Tension LF:1.00
Joint Pole Number Unset G/L Fiber Stress (psi):7,600 Ice Thickness (in):0.00 Vertical LF:1.00
Notification 121534031 Allowable Stress (psi):2,485 Wind Speed (mph):55.90 Pole Factor of Safety:4.82
PLDBID Unset Fiber Stress Ht.Reduc:No Wind Pressure (psf):8.00 Vertical Factor of Safety:34.88
Latitude:0 Longitude:0 Elevation:0'Bending Factor of Safety:4.87
Pole Capacity Utilization (%)
Crossarm allowance 300 lbs
Height
(ft)
Wind Angle
(deg)
Maximum 62.2 0.0 266.3
Groundline 62.2 0.0 266.3
Vertical 8.6 25.8 266.3
Pole Moments (ft-lb)
Crossarm allowance 300 lbs
Load Angle
(deg)
Wind Angle
(deg)
Max Cap Util 38,045 268.5 266.3
Groundline 38,045 268.5 266.3
GL Allowable 61,786
Overturn 126,000
Pole ID:21-146 NB PL LOC 800.pplx O-Calc®Pro Analysis -GO 95 Friday,November 12,2021 11:13 AM
User:BRubio GDSINC OCP:6.02 *Includes Load Factor(s)Page 2 of 4 2 Worst Wind Per Guy Wire 3Wind At 266.3°
Groundline Load Summary -Reporting Angle Mode:Load -Reporting Angle:268.5°
Shear
Load*
(lbs)
Applied
Load
(%)
Bending
Moment
(ft-lb)
Applied
Moment
(%)
Pole
Capacity
(%)
Bending
Stress
(+/-psi)
Vertical
Load
(lbs)
Vertical
Stress
(psi)
Total
Stress
(psi)
Pole
Capacity
(%)
Powers 670 60.3 27,594 72.5 44.7 1,110 479 3 1,112 44.8
GenericEquipments 12 1.1 474 1.3 0.8 19 60 0 19 0.8
Pole 358 32.2 8,164 21.5 13.2 328 2,070 13 341 13.7
Crossarms 2 0.2 89 0.2 0.1 4 70 0 4 0.2
Risers 61 5.5 1,445 3.8 2.3 58 35 0 58 2.3
Insulators 7 0.6 279 0.7 0.5 11 33 0 11 0.5
Pole Load 1,110 100.0 38,045 100.0 61.6 1,530 2,747 17 1,546 62.2
Pole Reserve Capacity 23,741 38.4 955 939 37.8
Load Summary by Owner -Reporting Angle Mode:Load -Reporting Angle:268.5°
Shear
Load*
(lbs)
Applied
Load
(%)
Bending
Moment
(ft-lb)
Applied
Moment
(%)
Pole
Capacity
(%)
Bending
Stress
(+/-psi)
Vertical
Load
(lbs)
Vertical
Stress
(psi)
Total
Stress
(psi)
Pole
Capacity
(%)
PG&E 752 67.8 29,881 78.5 48.4 1,202 677 4 1,206 48.5
Pole 358 32.2 8,164 21.5 13.2 328 2,070 13 341 13.7
Totals:1,110 100.0 38,045 100.0 61.6 1,530 2,747 17 1,546 62.2
Detailed Load Components:
Power Owner Height
(ft)
Horiz.
Offset
(in)
Cable
Diameter
(in)
Sag at
Max
Temp
(ft)
Cable
Weight
(lbs/ft)
Lead/Span
Length
(ft)
Span
Angle
(deg)
Wire
Length
(ft)
Tension
(lbs)
Tension
Moment*
(ft-lb)
Offset
Moment*
(ft-lb)
Wind
Moment*
(ft-lb)
Moment
at GL*
(ft-lb)
Primary 715 AAC (VIOLET)
SHORT SPAN
PG&E 40.82 44.48 0.9740 3.94 0.707 216.0 180.0 216.1 2,195 2,334 -281 2,859 4,912
Primary 715 AAC (VIOLET)
SHORT SPAN
PG&E 40.82 44.48 0.9740 4.45 0.707 236.0 358.0 236.1 2,195 798 -307 3,130 3,621
Primary 715 AAC (VIOLET)
SHORT SPAN
PG&E 40.82 44.48 0.9740 3.94 0.707 216.0 180.0 216.1 2,195 2,334 279 2,859 5,472
Primary 715 AAC (VIOLET)
SHORT SPAN
PG&E 40.82 44.48 0.9740 4.45 0.707 236.0 358.0 236.1 2,195 798 304 3,130 4,232
Primary 715 AAC (VIOLET)
SHORT SPAN
PG&E 40.82 19.14 0.9740 3.94 0.707 216.0 180.0 216.1 2,195 2,334 113 2,859 5,306
Primary 715 AAC (VIOLET)
SHORT SPAN
PG&E 40.82 19.14 0.9740 4.45 0.707 236.0 358.0 236.1 2,195 798 124 3,130 4,052
Totals:9,394 233 17,968 27,594
Pole ID:21-146 NB PL LOC 800.pplx O-Calc®Pro Analysis -GO 95 Friday,November 12,2021 11:13 AM
User:BRubio GDSINC OCP:6.02 *Includes Load Factor(s)Page 3 of 4 2 Worst Wind Per Guy Wire 3Wind At 266.3°
GenericEquipment Owner Height
(ft)
Horiz.
Offset
(in)
Offset
Angle
(deg)
Rotate
Angle
(deg)
Unit
Weight
(lbs)
Unit
Height
(in)
Unit
Depth
(in)
Unit
Diameter
(in)
Unit
Length
(in)
Offset
Moment*
(ft-lb)
Wind
Moment*
(ft-lb)
Moment
at GL*
(ft-lb)
Cylinder Disconnect Switch 1 PG&E 36.92 44.03 180.0 0.0 20.00 18.00 --4.00 ---73 148 75
Cylinder Disconnect Switch 2 PG&E 36.92 44.03 180.0 0.0 20.00 18.00 --4.00 --73 148 221
Cylinder Disconnect Switch 3 PG&E 36.92 18.07 180.0 0.0 20.00 18.00 --4.00 --30 148 178
Totals:30 444 474
Crossarm Owner Height
(ft)
Horiz.
Offset
(in)
Offset
Angle
(deg)
Rotate
Angle
(deg)
Unit
Weight
(lbs)
Unit
Height
(in)
Unit Depth
(in)
Unit
Length
(in)
Offset
Moment*
(ft-lb)
Wind
Moment*
(ft-lb)
Moment at
GL*
(ft-lb)
Normal 8 Composite TangentArm PG&E 40.00 6.52 0.0 0.0 34.00 4.63 3.63 96.00 0 62 62
Normal Cutout Arm-3 Wire PG&E 37.00 5.90 0.0 0.0 36.00 4.00 2.00 92.00 0 28 28
Totals:-1 90 89
Riser Owner Height
(ft)
Horiz.
Offset
(in)
Offset
Angle
(deg)
Rotate
Angle
(deg)
Unit
Weight
(lbs)
Unit
Height
(in)
Unit
Depth
(in)
Unit
Diameter
(in)
Unit
Length
(in)
Offset
Moment*
(ft-lb)
Wind
Moment*
(ft-lb)
Moment
at GL*
(ft-lb)
Riser 315.0°H:35.0 Riser PG&E 35.00 7.53 315.0 315.0 35.00 420.00 3.50 3.50 420.00 15 1,430 1,445
Totals:15 1,430 1,445
Insulator Owner Height
(ft)
Horiz.
Offset
(in)
Offset
Angle
(deg)
Rotate
Angle
(deg)
Unit
Weight
(lbs)
Unit
Diameter
(in)
Unit
Length
(in)
Offset
Moment*
(ft-lb)
Wind
Moment*
(ft-lb)
Moment at
GL*
(ft-lb)
Pin Insulator PG&E 40.19 44.00 81.6 0.0 6.00 5.50 7.50 0 92 92
Pin Insulator PG&E 40.19 -44.00 278.4 0.0 6.00 5.50 7.50 0 92 92
Pin Insulator PG&E 40.19 -18.00 289.9 0.0 6.00 5.50 7.50 0 92 92
Bolt Cutout PG&E 37.17 44.00 82.4 180.0 5.00 3.00 0.10 0 1 1
Bolt Cutout PG&E 37.17 -44.00 277.6 180.0 5.00 3.00 0.10 0 1 1
Bolt Cutout PG&E 37.17 -18.00 288.1 180.0 5.00 3.00 0.10 0 1 1
Totals:0 279 279
Pole Buckling
Buckling
Constant
Buckling
Column
Height*
(ft)
Buckling
Section
Height
(%Buckling
Col.Hgt.)
Buckling
Section
Diameter
(in)
Minimum
Buckling
Diameter at
GL
(in)
Diameter at
Tip
(in)
Diameter at
GL
(in)
Modulus of
Elasticity
(psi)
Pole
Density
(pcf)
Ice Density
(pcf)
Pole Tip
Height
(ft)
Buckling
Load
Capacity at
Height
(lbs)
Buckling
Load
Applied at
Height
(lbs)
Buckling
Load Factor
of Safety
2.00 25.82 33.39 13.39 7.85 8.60 14.49 2.38e+6 60.00 57.00 46.50 31,797 319.46 11.63
Pole ID:21-146 NB PL LOC 800.pplx O-Calc®Pro Analysis -GO 95 Friday,November 12,2021 11:13 AM
User:BRubio GDSINC OCP:6.02 *Includes Load Factor(s)Page 4 of 4 2 Worst Wind Per Guy Wire 3Wind At 266.3°
Notes
Date Author Description
1/30/2018 ben1 Outside top (pin/post)insulators are at 44",inside are at 18"
M150591
PUPI series 2200
Outside top (pin/post)insulators are at 44",inside are at 18".
Outside Dead-Ends are at 40.5".
Comes w/bushings for insulator pins8/3/2015 ben1 Install C/O Arm min 2.5 ft below Primary Conductor
Install C/O Arm min 2.5 ft below Primary Conductor