HomeMy WebLinkAbout2023 SB989 Repair (Rejected results)LINE ANNULAR TEST
11000 N. MoPac Expressway, Suite 500
Austin, Texas 78759
Phone: (512) 451-6334
Fax: (512) 459-1459 Date Printed and Mailed: 11/6/2023
BAKERSFIELD FIRE DEPARTMENT
OFFICE OF ENVIRONMENTAL SERVICES
INSPECTOR KRIS KARNS
1501 TRUXTUN AVE.
BAKERSFIELD, CA 93301
Test Date: 10/31/2023
Order Number: 3468985
Dear Regulator,
Enclosed are the results of recent testing performed at the following facility:
7-ELEVEN 37942/59987
3225 BUCK OWENS BLVD., HWY 99/HWY 58
BAKERSFIELD, CA 93301
In an effort to keep all our record keeping and reporting requirements as current as possible,
Tanknology kindly requests you notify Dawn Kohlmeyer in writing at dkohlmeyer@tanknology.com
when your CUPA requires all records to be submitted electronically via the CERS database. Your
assistance in this endeavor is greatly appreciated.
Testing performed:
Sincerely,
Dawn Kohlmeyer
Manager, Field Reporting
10134880 10/31/2023
7-ELEVEN 37942/59987
3225 BUCK OWENS BLVD., HWY 99/HWY 58 BAKERSFIELD 93301
Tanknology, Inc.800-964-1250
11000 N Mopac Expy #500 Austin, TX 78759
Jeffrey Crisostomo
743160
8199847 05/02/2025
05/02/2025
01/31/2025
ICC:CA UST Service Technician
Veeder Root:ATG Technician
Tanknology Certification:Level III Secondary Containment Testing Certification Exam 01/16/2025
pressure secondary lines
10/31/2023 6
pressure
dwfrg dwfrg dwfrg dwfrg
10:30 10:30 10:30 9:30
5psi 5 psi 5 psi 5 psi
11:30 11:30 11:30 10:30
0 psi 5 psi 5 psi 0 psi
5 0 0 5
0 0 0 0
Product Pipe for DIESEL STP
to FILTER
Product Pipe for DIESEL
FILTER to TRANSITION SUMP
Product Pipe for TRANSITION
SUMP to UDCS
TT-2 L1 (PREMIUM) STP
Containment 1 to 1/2
91 sec product and diesel product to filter secondary line failed.
Filter secondary to transition sump passed.
Transition secondary to dsl UDCs passed.
Repair maintenance should be onsite during testing per Fire inspector.
All secondary lines retest is inconclusive and cancelled by inspector.
Unleaded udc's has no power upon arrival.
all Unleaded impv is closed per inspector.
DSL impv still open due to employee can't find the udc keys.
All product was red tagged by Fire inspector.
Site Diagram
(This site diagram is for reference only and is not drawn to scale)
Work Order:3468985
Site ID / Name:37942/59987 / 7-ELEVEN 37942/59987
Address:3225 BUCK OWENS BLVD., HWY 99/HWY 58
City:BAKERSFIELD State:CA Zip:93301