HomeMy WebLinkAbout2023 FMC1
Jennifer Pruitt
Subject:SA002, AT&T Annual Monitor Certification & Spill Bucket Testing Notification (BKFDCA01), Bakersfield
Location:1520 20TH ST, BAKERSFIELD, CA 93301-4406
Start:Tue 10/17/2023 9:00 AM
End:Tue 10/17/2023 11:00 AM
Recurrence:(none)
Meeting Status:Meeting organizer
Organizer:Simplex Communication
Required Attendees:AGUILAR, ADOLFO; MEDINA, ELOISA; 'FLORES, CECILIA'; 'HAYN, CINDY H (ATTSI)' (ch1921@att.com) ; Brian
Harmon; Carlos Cardenas; Jennifer Pruitt; Maria Figueroa; Krystine Gossett; Eric Durham
Categories:Annual Monitoring Certification & Spill Bucket Testing, Legacy T Site
There is an AT&T Annual Monitoring Certification & Spill Bucket Test scheduled for this location on the date and time
indicated.
NOTE: -Next Overfill Test of the Overfill Alarm due in 2025
-Testing Permit #23-10000037
SA002 1520 20TH ST BAKERSFIELD 93301-4406
TEST DUE DATE 10/28/2023
PERMIT REQUIRED for TESTING
1. BILLING & PERMIT STATEMENT - FEE SCHEDULE (PDF)
2. UST TESTING APPLICATION (PDF)
Please contact the Compliance Manager with any questions and/or comments at:
simplexcommunication@tait.com
714.560.8200
Environmental Health/CUPA Contact Information:
Bakersfield City Fire Department
2101 H Street
Bakersfield, CA 93301
Method of Notification: Email
Contact (Once Permit is Approved):
https://www.bakersfieldcity.us/1048/Inspection‐Request
2
Test Results Submittal: USTResults@bakersfieldfire.us
1
Jennifer Pruitt
From:Luke Preece <lpreece@bakersfieldfire.us>
Sent:Tuesday, August 29, 2023 12:53 PM
To:Carlos Cardenas
Cc:Jennifer Pruitt
Subject:RE: ***Scheduling Request***AT&T Annual October Testing - Bakersfield Fire Dept.
External Email.
Carlos,
These times are good with me. I have you on the calendar.
Thank you
Luke Preece
Fire Prevention/Environmental Officer
Bakersfield Fire Department
email: lpreece@bakersfieldfire.us
web: www.bakersfieldfire.us
phone: 661-326-3659
From: Carlos Cardenas <ccardenas@TAIT.COM>
Sent: Tuesday, August 29, 2023 11:20 AM
To: Luke Preece <lpreece@bakersfieldfire.us>
Cc: Jennifer Pruitt <jpruitt@TAIT.COM>
Subject: ***Scheduling Request***AT&T Annual October Testing ‐ Bakersfield Fire Dept.
CAUTION: This email originated from outside your organization. Exercise caution when opening attachments or clicking
links, especially from unknown senders.
Hello Inspector Preece,
Thank you for the voicemail. Per your available dates, I was hoping we could schedule tesƟng for the following dates and
Ɵmes:
SA004, AT&T Annual Monitor Certification,
PLLD Testing & Spill Bucket Testing
Notification (BKFDCA12), Bakersfield
1918 M STREET
BAKERSFIELD, CA 93301
Mon 10/16/2023
9:00 AM
Permit #
23-10000038
SA004, AT&T Annual Precision Line Testing
Notification (BKFDCA12), Bakersfield
1918 M STREET
BAKERSFIELD, CA 93301
Mon 10/16/2023
9:00 AM
Permit #
23-10000039
SA002, AT&T Annual Monitor Certification
& Spill Bucket Testing Notification
(BKFDCA01), Bakersfield
1520 20TH ST
BAKERSFIELD, CA 93301
Tue 10/17/2023
9:00 AM
Permit #
23-10000037
Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date
Total # of Pages
SA002
✔
10029370 10/17/2023
PACIFIC BELL TELEPHONE CO. DBA AT&T CALIFORNIA
1520 20TH ST.BAKERSFIELD 93301
TAIT Environmental Services, Inc. (714) 560-8222
701 N. Parkcenter Dr., Santa Ana, CA 92705
Eric Durham
588098
10275565 10/17/2025
Veeder Root A23191 4/27/2024
10/17/2023
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either;܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications?܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid?܆܆܆܆
Are the audible and visual alarms operational?܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational?܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment?܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed?܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational?܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment?܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected?܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply)܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational?܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS 350 PLUS 120.00
✔✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 794380-208 / N/A Fill Sump Sensor
✔
L2 794380-208 / N/A Piping Sump Sensor
✔
L3 794380-208 / 454053 Day Tank Sensor ✔
L4 794380-208 / 454345 AST Annular Sensor ✔
L5 794390-420 / 453457 UST Annular Sensor ✔
L6 794380-208 / 877657 Trans Sensor ✔
L7 794380-208 / N/A Pump Box Sensor ✔
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated?܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected?܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected?܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected?܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected?܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test?܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks?܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed?܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements?܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
✔
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults?܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational?܆܆ ܆܆ ܆܆
Was accuracy of system’s product level readings tested?܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested?܆܆ ܆܆ ܆܆
Were all probes reinstalled properly?܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed?܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
✔
✔
✔
✔
✔
✔
Tank 1 Diesel 846390-105 / 234300 SA002U001
✔
Tank 2 Diesel 847390-301 / 620656 SA002A002
✔
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
10/17/2023
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Test Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
rnia Environme
nician Signatur
SA002
✔
10029370 10/17/2023
PACIFIC BELL TELEPHONE CO. DBA AT&T CALIFORNIA
1520 20TH ST. BAKERSFIELD 93301
TAIT Environmental Services, Inc. (714) 560-8222
701 N. Parkcenter Dr., Santa Ana, CA 92705
Eric Durham
588098
10275565 5/1/2025
Franklin Fueling Systems 7/19/2025
PEI/RP1200 Spill Containment SA002U001
10/17/2023
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
✔
✔
SA002U001
CNI
✔
✔
✔
✔
I50301
OCT 18, 2023 7:13 AM
# 1:BKFDCA01 SA002 T-S
I50302
OCT 18, 2023 7:13 AM
# 2:1520 20TH ST
I50303
OCT 18, 2023 7:13 AM
# 3:BAKERSFIELD,CA 93301
I50304
OCT 18, 2023 7:13 AM
# 4:661-869-1846
I51700
OCT 18, 2023 7:13 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50F00
OCT 18, 2023 7:13 AM
MON DD YYYY HH:MM:SS xM
I10200
OCT 18, 2023 7:13 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 162295 161967
2 INTERSTITIAL BD 201439 200536
3 UNUSED 15000000 15000000
4 UNUSED 15000000 15000000
5 UNUSED 15000000 15000000
6 UNUSED 15000000 15000000
7 UNUSED 15000000 15000000
8 UNUSED 15000000 15000000
9 RELAY BOARD 14933 14925
10 COMBO I/O BOARD 9929 9900
11 UNUSED 15000000 15000000
12 UNUSED 15000000 15000000
13 UNUSED 15000000 15000000
14 UNUSED 15000000 15000000
15 UNUSED 15000000 15000000
16 UNUSED 15000000 15000000
COMM 1 FAXMODEM BOARD 40571 40585
COMM 2 UNUSED 15000000 15000000
COMM 3 UNUSED 15000000 15000000
COMM 4 UNUSED 15000000 15000000
COMM 5 UNUSED 15000000 15000000
COMM 6 UNUSED 15000000 15000000
I60100
OCT 18, 2023 7:13 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK#SA002U001 ON
2 DIESEL TK#SA002A002 ON
3 OFF
4 OFF
I60200
OCT 18, 2023 7:13 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK#SA002U001
2 DIESEL TK#SA002A002
3
4
I60300
OCT 18, 2023 7:13 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK#SA002U001 1
2 DIESEL TK#SA002A002 1
3 3
4 4
I60400
OCT 18, 2023 7:13 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 8002
2 DIESEL TK#SA002A002 250
3 0
4 0
I60700
OCT 18, 2023 7:13 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA002U001 82.00
2 DIESEL TK#SA002A002 30.00
3 0.00
4 0.00
I60900
OCT 18, 2023 7:13 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK#SA002U001 0.000450
2 DIESEL TK#SA002A002 0.000450
3 0.000000
4 0.000000
I61200
OCT 18, 2023 7:14 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL MANIFOLDED TANKS
1 DIESEL TK#SA002U001 NONE
2 DIESEL TK#SA002A002 NONE
3 NONE
4 NONE
I62100
OCT 18, 2023 7:14 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 4000
2 DIESEL TK#SA002A002 105
3 0
4 0
I62200
OCT 18, 2023 7:14 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 7601
2 DIESEL TK#SA002A002 237
3 0
4 0
I62300
OCT 18, 2023 7:14 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 7201
2 DIESEL TK#SA002A002 225
3 0
4 0
I62400
OCT 18, 2023 7:14 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA002U001 2.0
2 DIESEL TK#SA002A002 2.0
I62800
OCT 18, 2023 7:14 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 8002
2 DIESEL TK#SA002A002 250
3 0
4 0
I62900
OCT 18, 2023 7:14 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA002U001 4000
2 DIESEL TK#SA002A002 125
3 0
4 0
I70300
OCT 18, 2023 7:14 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 FILL SUMP TRI-STATE (SINGLE FLOAT)
2 PIPING SUMP TRI-STATE (SINGLE FLOAT)
3 DAYTANK RUPTURE BASN TRI-STATE (SINGLE FLOAT)
4 DAY TANK ANNULAR TRI-STATE (SINGLE FLOAT)
5 ANNULAR UST TRI-STATE (SINGLE FLOAT)
6 TRANSITION SUMP TRI-STATE (SINGLE FLOAT)
7 REMOTE PUMP CABINET TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
I90200
OCT 18, 2023 7:14 AM
SOFTWARE REVISION LEVEL
VERSION 120.00
SOFTWARE# 346120-100-A
CREATED - 00.07.28.15.33
S-MODULE# 330160-002-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
I11100
OCT 18, 2023 7:14 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 2 TANK DIESEL TK#SA002A002 HIGH WATER ALARM CLEAR 10-17-23 11:12AM
T 2 TANK DIESEL TK#SA002A002 PROBE OUT CLEAR 10-17-23 11:10AM
T 2 TANK DIESEL TK#SA002A002 OVERFILL ALARM CLEAR 10-17-23 11:10AM
T 2 TANK DIESEL TK#SA002A002 PROBE OUT ALARM 10-17-23 11:10AM
T 2 TANK DIESEL TK#SA002A002 OVERFILL ALARM ALARM 10-17-23 11:09AM
T 2 TANK DIESEL TK#SA002A002 HIGH WATER ALARM ALARM 10-17-23 11:08AM
T 2 TANK DIESEL TK#SA002A002 PROBE OUT CLEAR 10-17-23 11:02AM
T 2 TANK DIESEL TK#SA002A002 PROBE OUT ALARM 10-17-23 11:00AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM CLEAR 10-17-23 10:59AM
L 3 OTHER DAYTANK RUPTURE BASN FUEL ALARM ALARM 10-17-23 10:53AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM CLEAR 10-17-23 10:52AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM ALARM 10-17-23 10:46AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM CLEAR 10-17-23 10:46AM
L 4 ANNULAR DAY TANK ANNULAR FUEL ALARM ALARM 10-17-23 10:46AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER ALARM CLEAR 10-17-23 10:12AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 10-17-23 10:12AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 10-17-23 10:11AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER ALARM ALARM 10-17-23 10:09AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM CLEAR 10-17-23 10:06AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM ALARM 10-17-23 10:05AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM CLEAR 10-17-23 10:04AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 10-17-23 10:03AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 10-17-23 10:02AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM ALARM 10-17-23 10:02AM
L 6 PIPE TRANSITION SUMP FUEL ALARM CLEAR 10-17-23 9:54AM
L 6 PIPE TRANSITION SUMP FUEL ALARM ALARM 10-17-23 9:41AM
L 7 OTHER REMOTE PUMP CABINET FUEL ALARM CLEAR 10-17-23 9:40AM
L 7 OTHER REMOTE PUMP CABINET FUEL ALARM ALARM 10-17-23 9:35AM
L 2 PIPE PIPING SUMP FUEL ALARM CLEAR 10-17-23 9:32AM
L 5 ANNULAR ANNULAR UST FUEL ALARM CLEAR 10-17-23 9:30AM
L 5 ANNULAR ANNULAR UST FUEL ALARM ALARM 10-17-23 9:30AM
L 2 PIPE PIPING SUMP FUEL ALARM ALARM 10-17-23 9:27AM
L 1 STP SUMP FILL SUMP FUEL ALARM CLEAR 10-17-23 9:27AM
L 1 STP SUMP FILL SUMP FUEL ALARM ALARM 10-17-23 9:25AM
L 1 STP SUMP FILL SUMP FUEL ALARM CLEAR 10-17-23 9:25AM
L 1 STP SUMP FILL SUMP FUEL ALARM ALARM 10-17-23 9:24AM
L 5 ANNULAR ANNULAR UST FUEL ALARM CLEAR 10-17-23 9:24AM
L 5 ANNULAR ANNULAR UST FUEL ALARM ALARM 10-17-23 9:20AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER ALARM CLEAR 4-03-23 9:10AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 4-03-23 9:10AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT ALARM 4-03-23 9:09AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER ALARM ALARM 4-03-23 9:06AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM CLEAR 4-03-23 9:03AM
T 1 TANK DIESEL TK#SA002U001 MAX PRODUCT ALARM CLEAR 4-03-23 9:02AM
T 1 TANK DIESEL TK#SA002U001 MAX PRODUCT ALARM ALARM 4-03-23 9:01AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM ALARM 4-03-23 9:01AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM CLEAR 4-03-23 9:01AM
T 1 TANK DIESEL TK#SA002U001 OVERFILL ALARM ALARM 4-03-23 8:59AM
T 1 TANK DIESEL TK#SA002U001 LOW PRODUCT ALARM CLEAR 4-03-23 8:59AM
T 1 TANK DIESEL TK#SA002U001 PROBE OUT CLEAR 4-03-23 8:58AM
I11200
OCT 18, 2023 7:15 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 10-17-23 11:18AM
SYSTEM PRINTER ERROR ALARM 10-17-23 11:18AM
T 2 TANK DIESEL TK#SA002A002 HIGH WATER WARNING CLEAR 10-17-23 11:12AM
T 2 TANK DIESEL TK#SA002A002 HIGH PRODUCT ALARM CLEAR 10-17-23 11:11AM
T 2 TANK DIESEL TK#SA002A002 HIGH PRODUCT ALARM ALARM 10-17-23 11:09AM
T 2 TANK DIESEL TK#SA002A002 HIGH WATER WARNING ALARM 10-17-23 11:08AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING CLEAR 10-17-23 10:12AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING ALARM 10-17-23 10:09AM
T 1 TANK DIESEL TK#SA002U001 HIGH PRODUCT ALARM CLEAR 10-17-23 10:05AM
T 1 TANK DIESEL TK#SA002U001 HIGH PRODUCT ALARM ALARM 10-17-23 10:05AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 10-17-23 10:04AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 10-17-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 9-07-23 9:01PM
SYSTEM PAPER OUT CLEAR 9-07-23 9:01PM
SYSTEM PAPER OUT ALARM 9-07-23 9:01PM
SYSTEM PAPER OUT CLEAR 9-07-23 9:01PM
SYSTEM PAPER OUT ALARM 9-07-23 9:01PM
SYSTEM PAPER OUT CLEAR 9-07-23 9:01PM
SYSTEM PRINTER ERROR ALARM 9-07-23 9:01PM
SYSTEM PAPER OUT ALARM 9-07-23 9:01PM
SYSTEM PRINTER ERROR CLEAR 9-07-23 8:59PM
SYSTEM PRINTER ERROR ALARM 9-07-23 8:59PM
SYSTEM PRINTER ERROR CLEAR 8-09-23 8:06PM
SYSTEM PAPER OUT CLEAR 8-09-23 8:06PM
SYSTEM PRINTER ERROR ALARM 8-09-23 8:06PM
SYSTEM PAPER OUT ALARM 8-09-23 8:06PM
SYSTEM PRINTER ERROR CLEAR 4-21-23 7:32PM
SYSTEM PRINTER ERROR ALARM 4-21-23 7:32PM
T 1 TANK DIESEL TK#SA002U001 LOW TEMP WARNING CLEAR 4-03-23 9:11AM
T 1 TANK DIESEL TK#SA002U001 LOW TEMP WARNING ALARM 4-03-23 9:10AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING CLEAR 4-03-23 9:10AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING ALARM 4-03-23 9:06AM
T 1 TANK DIESEL TK#SA002U001 HIGH PRODUCT ALARM CLEAR 4-03-23 9:02AM
T 1 TANK DIESEL TK#SA002U001 HIGH PRODUCT ALARM ALARM 4-03-23 9:01AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 4-03-23 8:59AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 4-03-23 8:57AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 3-15-23 9:50AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 3-15-23 9:49AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING CLEAR 3-15-23 9:45AM
T 1 TANK DIESEL TK#SA002U001 HIGH WATER WARNING ALARM 3-15-23 9:41AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 3-15-23 9:20AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL CLEAR 3-15-23 9:19AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL ALARM 12-23-22 4:19AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 12-23-22 4:19AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL CLEAR 12-23-22 3:45AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 12-23-22 3:45AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL ALARM 12-23-22 3:42AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED ALARM 12-23-22 3:41AM
T 1 TANK DIESEL TK#SA002U001 INVALID FUEL LEVEL CLEAR 12-23-22 3:39AM
T 1 TANK DIESEL TK#SA002U001 DELIVERY NEEDED CLEAR 12-23-22 3:39AM
I20600
OCT 18, 2023 7:16 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
TANK ALARM HISTORY
TANK 1 DIESEL TK#SA002U001
LEAK ALARM OCT 11, 2011 6:08 AM
OCT 14, 2010 2:44 PM
OCT 13, 2010 11:06 AM
HIGH WATER ALARM OCT 17, 2023 10:09 AM
APR 3, 2023 9:06 AM
MAR 15, 2023 9:41 AM
OVERFILL ALARM OCT 17, 2023 10:05 AM
APR 3, 2023 9:01 AM
APR 3, 2023 8:59 AM
LOW PRODUCT ALARM OCT 17, 2023 10:02 AM
APR 3, 2023 8:57 AM
MAR 15, 2023 9:49 AM
SUDDEN LOSS ALARM APR 4, 2010 3:43 PM
FEB 19, 2010 10:08 AM
FEB 19, 2010 10:05 AM
HIGH PRODUCT ALARM OCT 17, 2023 10:05 AM
APR 3, 2023 9:01 AM
OCT 29, 2021 9:12 AM
INVALID FUEL LEVEL DEC 23, 2022 4:19 AM
DEC 23, 2022 3:42 AM
DEC 23, 2022 2:25 AM
PROBE OUT OCT 17, 2023 10:11 AM
OCT 17, 2023 10:02 AM
APR 3, 2023 9:09 AM
HIGH WATER WARNING OCT 17, 2023 10:09 AM
APR 3, 2023 9:06 AM
MAR 15, 2023 9:41 AM
DELIVERY NEEDED OCT 17, 2023 10:02 AM
APR 3, 2023 8:57 AM
MAR 15, 2023 9:49 AM
MAX PRODUCT ALARM APR 3, 2023 9:01 AM
OCT 15, 2020 9:12 AM
OCT 23, 2019 9:13 AM
CSLD INCR RATE WARN DEC 10, 2008 9:38 AM
SEP 18, 2008 10:06 AM
SEP 18, 2008 6:58 AM
LOW TEMP WARNING APR 3, 2023 9:10 AM
OCT 28, 2022 9:32 AM
JAN 27, 2022 12:12 PM
TANK 2 DIESEL TK#SA002A002
SETUP DATA WARNING JAN 27, 2012 11:49 AM
HIGH WATER ALARM OCT 17, 2023 11:08 AM
OCT 28, 2022 10:13 AM
OCT 29, 2021 9:40 AM
OVERFILL ALARM OCT 17, 2023 11:09 AM
OCT 23, 2019 10:26 AM
NOV 2, 2018 10:38 AM
LOW PRODUCT ALARM OCT 23, 2019 10:24 AM
NOV 21, 2016 10:31 AM
JAN 7, 2014 9:54 AM
SUDDEN LOSS ALARM OCT 12, 2010 8:39 PM
FEB 19, 2010 9:55 AM
APR 28, 2009 11:13 AM
HIGH PRODUCT ALARM OCT 17, 2023 11:09 AM
OCT 28, 2022 10:03 AM
OCT 29, 2021 9:35 AM
INVALID FUEL LEVEL OCT 29, 2021 9:33 AM
OCT 23, 2019 10:24 AM
NOV 21, 2016 10:31 AM
PROBE OUT OCT 17, 2023 11:10 AM
OCT 17, 2023 11:00 AM
OCT 28, 2022 10:32 AM
HIGH WATER WARNING OCT 17, 2023 11:08 AM
OCT 28, 2022 10:13 AM
OCT 29, 2021 9:40 AM
DELIVERY NEEDED OCT 23, 2019 10:24 AM
NOV 2, 2018 10:37 AM
NOV 7, 2017 1:37 PM
MAX PRODUCT ALARM OCT 28, 2022 10:03 AM
OCT 29, 2021 9:35 AM
OCT 29, 2021 9:33 AM
LOW TEMP WARNING DEC 17, 2014 11:26 AM
JAN 22, 2013 10:14 AM
I30200
OCT 18, 2023 7:17 AM
BKFDCA01 SA002 T-S
1520 20TH ST
BAKERSFIELD,CA 93301
661-869-1846
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 FILL SUMP
OCT 17, 2023 9:25 AM FUEL ALARM
OCT 17, 2023 9:24 AM FUEL ALARM
OCT 28, 2022 9:09 AM FUEL ALARM
2 PIPING SUMP
OCT 17, 2023 9:27 AM FUEL ALARM
OCT 28, 2022 9:15 AM FUEL ALARM
OCT 29, 2021 8:37 AM FUEL ALARM
3 DAYTANK RUPTURE BASN
OCT 17, 2023 10:53 AM FUEL ALARM
JAN 9, 2023 10:04 AM FUEL ALARM
JAN 9, 2023 9:33 AM FUEL ALARM
4 DAY TANK ANNULAR
OCT 17, 2023 10:46 AM FUEL ALARM
OCT 17, 2023 10:46 AM FUEL ALARM
JAN 9, 2023 9:32 AM FUEL ALARM
5 ANNULAR UST
OCT 17, 2023 9:30 AM FUEL ALARM
OCT 17, 2023 9:20 AM FUEL ALARM
OCT 28, 2022 9:05 AM FUEL ALARM
6 TRANSITION SUMP
OCT 17, 2023 9:41 AM FUEL ALARM
OCT 28, 2022 9:37 AM FUEL ALARM
OCT 16, 2022 4:47 PM FUEL ALARM
7 REMOTE PUMP CABINET
OCT 17, 2023 9:35 AM FUEL ALARM
OCT 28, 2022 9:41 AM FUEL ALARM
OCT 25, 2022 8:40 AM SENSOR OUT ALARM
Identification of Test Procedures for Secondary Containment Testing
To Whom It May Concern:
Tait Environmental Services, Inc., utilizes the following procedures when conducting Secondary
Containment Testing:
1) Containment Sumps, Transition Sumps, UDCs – Tait follows PEI‐RP1200‐17 Section 6.6 for the
accelerated test method. Tait uses the Incon TS‐1000 hydrostatic test equipment following the
attached procedures.
2) Spill Buckets; Direct Bury & Contained in Sumps – Spill buckets contained in sumps are tested
per PEI‐1200‐17, Section 6.2, however Tait Pass/Fail threshold is 0” drop in one hour. Direct Bury
Spill Buckets are test the same as containment sumps per PEI‐1200‐17, Section 6.6.
3) Tank Annular Space – testing is conducted per PEI‐1200‐17, Section 4.2
4) Piping Secondary Containment – Testing is conducted per PEI‐RP1200‐17, Section 5.3
Please consider this letter as our Test Procedure utilized when conducting Secondary Containment
Testing in lieu of either parts or the whole RP1200 document due to copyright infringement.