HomeMy WebLinkAbout2023 FMC1
Jennifer Pruitt
Subject:SA098, AT&T Annual Monitor Certification & Spill Bucket Testing Notification (BKFDCA14), Bakersfield
Location:3221 S. H STREET, BAKERSFIELD, CA 93304-5649
Start:Tue 10/17/2023 11:00 AM
End:Tue 10/17/2023 1:00 PM
Recurrence:(none)
Meeting Status:Meeting organizer
Organizer:Simplex Communication
Required Attendees:AGUILAR, ADOLFO; MEDINA, ELOISA; 'FLORES, CECILIA'; 'HAYN, CINDY H (ATTSI)' (ch1921@att.com) ; Carlos
Cardenas; Jennifer Pruitt; Maria Figueroa; Krystine Gossett; Eric Durham
Categories:Annual Monitoring Certification & Spill Bucket Testing, Legacy S Site
There is an AT&T Annual monitor certification and spill bucket test scheduled for this location on the date and time
indicated.
NOTE: -Next Overfill Test of the Overfill Alarm due in 2025
-Testing Permit #23-10000040
SA098 3221 S. H STREET BAKERSFIELD 93304-5649
TEST DUE DATE 10/21/2023
PERMIT REQUIRED for TESTING
1. BILLING & PERMIT STATEMENT - FEE SCHEDULE (PDF)
2. UST TESTING APPLICATION (PDF)
Please contact the Compliance Manager with any questions and/or comments at:
simplexcommunication@tait.com
714.560.8200
Environmental Health/CUPA Contact Information:
Bakersfield City Fire Department
2101 H Street
Bakersfield, CA 93301
Method of Notification: Email
Contact (Once Permit is Approved):
https://www.bakersfieldcity.us/1048/Inspection‐Request
2
Test Results Submittal: USTResults@bakersfieldfire.us
1
Jennifer Pruitt
From:Luke Preece <lpreece@bakersfieldfire.us>
Sent:Tuesday, August 29, 2023 12:53 PM
To:Carlos Cardenas
Cc:Jennifer Pruitt
Subject:RE: ***Scheduling Request***AT&T Annual October Testing - Bakersfield Fire Dept.
External Email.
Carlos,
These times are good with me. I have you on the calendar.
Thank you
Luke Preece
Fire Prevention/Environmental Officer
Bakersfield Fire Department
email: lpreece@bakersfieldfire.us
web: www.bakersfieldfire.us
phone: 661-326-3659
From: Carlos Cardenas <ccardenas@TAIT.COM>
Sent: Tuesday, August 29, 2023 11:20 AM
To: Luke Preece <lpreece@bakersfieldfire.us>
Cc: Jennifer Pruitt <jpruitt@TAIT.COM>
Subject: ***Scheduling Request***AT&T Annual October Testing ‐ Bakersfield Fire Dept.
CAUTION: This email originated from outside your organization. Exercise caution when opening attachments or clicking
links, especially from unknown senders.
Hello Inspector Preece,
Thank you for the voicemail. Per your available dates, I was hoping we could schedule tesƟng for the following dates and
Ɵmes:
SA004, AT&T Annual Monitor Certification,
PLLD Testing & Spill Bucket Testing
Notification (BKFDCA12), Bakersfield
1918 M STREET
BAKERSFIELD, CA 93301
Mon 10/16/2023
9:00 AM
Permit #
23-10000038
SA004, AT&T Annual Precision Line Testing
Notification (BKFDCA12), Bakersfield
1918 M STREET
BAKERSFIELD, CA 93301
Mon 10/16/2023
9:00 AM
Permit #
23-10000039
SA002, AT&T Annual Monitor Certification
& Spill Bucket Testing Notification
(BKFDCA01), Bakersfield
1520 20TH ST
BAKERSFIELD, CA 93301
Tue 10/17/2023
9:00 AM
Permit #
23-10000037
2
SA098, AT&T Annual Monitor Certification
& Spill Bucket Testing Notification
(BKFDCA14), Bakersfield
3221 S. H STREET
BAKERSFIELD, CA 93304
Tue 10/17/2023
11:00 AM
Permit #
23-10000040
Carlos E. Cardenas | TAIT Environmental Services, Inc.
Project Manager
701 N. Parkcenter Dr., Santa Ana, CA 92705
P: 714-567-6418 C: 909-230-8256
ccardenas@tait.com | www.tait.com
This email message, including any attachment(s), is intended only for the recipient(s) named above. It may contain information that is confidential, privileged, or protected by
law. The unlawful use, distribution, or publication of this information is strictly prohibited. If you receive this communication in error, please notify the sender immediately by
return email and delete the original message, including all attachment(s).
Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date
Total # of Pages
SA098
✔
10023352 10/17/2023
10/17/2023
PACIFIC BELL TELEPHONE CO. DBA AT&T CALIFORNIA
3221 S. H ST. BAKERSFIELD 93304
TAIT Environmental Services, Inc. (714) 560-8222
701 N. Parkcenter Dr., Santa Ana, CA 92705
Eric Durham
588098
10275565 5/1/2025
Veeder Root A23191 4/27/2024
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either;܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications?܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid?܆܆܆܆
Are the audible and visual alarms operational?܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational?܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment?܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed?܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational?܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment?܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected?܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply)܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational?܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS 350 PLUS 324.01
✔✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 794390-420 / 940306 Annular Sensor
✔
L2 794380-208 / 762065 Fill Sump Sensor
✔
L3 794380-208 / 519636 Piping Sump Sensor ✔
L4 794380-208 / 492898 Transition Box Sensor ✔
L5 794390-420 / 619734 Generator Room Piping Pan Sensor ✔
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated?܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected?܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected?܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected?܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected?܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test?܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks?܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed?܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements?܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
✔
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults?܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational?܆܆ ܆܆ ܆܆
Was accuracy of system’s product level readings tested?܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested?܆܆ ܆܆ ܆܆
Were all probes reinstalled properly?܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed?܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
✔
✔
✔
✔
✔
✔
Tank 1 Diesel 847390-107 / 726884 SA098U001
✔
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
10/17/2023
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Test Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
Environmenta
an Signature
SA098
✔
10023352 10/17/2023
10/17/2023
PACIFIC BELL TELEPHONE CO. DBA AT&T CALIFORNIA
3221 S. H ST. BAKERSFIELD 93304
TAIT Environmental Services, Inc. (714) 560-8222
701 N. Parkcenter Dr., Santa Ana, CA 92705
Eric Durham
588098
10275565 5/1/2025
Franklin Fueling Systems 7/19/2025
PEI / RP 1200 Spill Containment SA098U001
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
✔
✔
SA098U001
Phil Tite
✔
✔
✔
✔
I50301
OCT 18, 2023 6:52 AM
# 1:BKFDCA14 SA098 S-S
I50302
OCT 18, 2023 6:52 AM
# 2:3221 S. H ST.
I50303
OCT 18, 2023 6:52 AM
# 3:BAKERSFIELD,CA 93304
I50304
OCT 18, 2023 6:52 AM
# 4:661-832-8370
I51700
OCT 18, 2023 6:53 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50F00
OCT 18, 2023 6:53 AM
MON DD YYYY HH:MM:SS xM
I10200
OCT 18, 2023 6:53 AM
BKFDCA14 SA098 S-S
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 163785 161800
2 INTERSTITIAL BD 200879 199435
3 UNUSED 10306571 10234923
4 UNUSED 10265262 10216210
5 UNUSED 10261818 10225825
6 UNUSED 10249310 10216667
7 UNUSED 10253984 10221375
8 UNUSED 10247323 10224077
9 RELAY BOARD 14983 14981
10 UNUSED 10251789 10223827
11 UNUSED 10242063 10217411
12 UNUSED 10251033 10226112
13 UNUSED 10239736 10220728
14 UNUSED 10246737 10222457
15 UNUSED 10242820 10222556
16 UNUSED 10238506 10217014
COMM 1 FAXMODEM BOARD 40172 40086
COMM 2 UNUSED 10240833 10217967
COMM 3 UNUSED 10246661 10224741
COMM 4 UNUSED 10237503 10219795
COMM 5 UNUSED 10242385 10219298
COMM 6 UNUSED 10240341 10226072
I60100
OCT 18, 2023 6:54 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 DIESEL TK#SA098U001 ON
2 OFF
3 OFF
4 OFF
I60200
OCT 18, 2023 6:54 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 DIESEL TK#SA098U001
2
3
4
I60300
OCT 18, 2023 6:54 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 DIESEL TK#SA098U001 1
2 2
3 3
4 4
I60400
OCT 18, 2023 6:54 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 6016
2 5036
3 0
4 0
I60700
OCT 18, 2023 6:54 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA098U001 95.75
2 92.00
3 0.00
4 0.00
I60900
OCT 18, 2023 6:54 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 DIESEL TK#SA098U001 0.000450
2 0.000450
3 0.000000
4 0.000000
I61200
OCT 18, 2023 6:54 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 DIESEL TK#SA098U001 NONE NONE
2 NONE NONE
3 NONE NONE
4 NONE NONE
I62100
OCT 18, 2023 6:54 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 2000
2 3000
3 0
4 0
I62200
OCT 18, 2023 6:54 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 4784
2 4784
3 0
4 0
I62300
OCT 18, 2023 6:54 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 4532
2 4532
3 0
4 0
I62400
OCT 18, 2023 6:54 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 DIESEL TK#SA098U001 2.0
I62800
OCT 18, 2023 6:54 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 6016
2 5036
3 0
4 0
I62900
OCT 18, 2023 6:54 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 DIESEL TK#SA098U001 3000
2 3525
3 0
4 0
I70300
OCT 18, 2023 6:54 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 ANNULAR SPACE SENSOR TRI-STATE (SINGLE FLOAT)
2 FILL SUMP SENSOR TRI-STATE (SINGLE FLOAT)
3 PIPING SUMP SENSOR TRI-STATE (SINGLE FLOAT)
4 TRANSITION SUMP TRI-STATE (SINGLE FLOAT)
5 PIPING PAN TRI-STATE (SINGLE FLOAT)
6 TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
I90200
OCT 18, 2023 6:55 AM
SOFTWARE REVISION LEVEL
VERSION 324.01
SOFTWARE# 346324-100-B
CREATED - 03.11.10.17.15
S-MODULE# 330160-002-A
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
I11100
OCT 18, 2023 6:55 AM
BKFDCA14 SA098 S-S
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK DIESEL TK#SA098U001 HIGH WATER ALARM CLEAR 10-17-23 12:58PM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 10-17-23 12:58PM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM CLEAR 10-17-23 12:56PM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 10-17-23 12:56PM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM ALARM 10-17-23 12:54PM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM CLEAR 10-17-23 12:54PM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM ALARM 10-17-23 12:52PM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER ALARM ALARM 10-17-23 12:47PM
T 1 TANK DIESEL TK#SA098U001 LOW PRODUCT ALARM CLEAR 10-17-23 12:44PM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 10-17-23 12:44PM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 10-17-23 12:43PM
T 1 TANK DIESEL TK#SA098U001 LOW PRODUCT ALARM ALARM 10-17-23 12:43PM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM CLEAR 10-17-23 12:42PM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM ALARM 10-17-23 12:42PM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM CLEAR 10-17-23 12:41PM
L 5 PIPE PIPING PAN FUEL ALARM CLEAR 10-17-23 12:39PM
L 5 PIPE PIPING PAN FUEL ALARM ALARM 10-17-23 12:36PM
L 4 PIPE TRANSITION SUMP FUEL ALARM CLEAR 10-17-23 12:36PM
L 4 PIPE TRANSITION SUMP FUEL ALARM ALARM 10-17-23 12:34PM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM ALARM 10-17-23 12:31PM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM CLEAR 10-17-23 12:31PM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM ALARM 10-17-23 12:29PM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM CLEAR 10-17-23 12:28PM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM ALARM 10-17-23 12:25PM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER ALARM CLEAR 10-21-22 9:42AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 10-21-22 9:41AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 10-21-22 9:41AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER ALARM ALARM 10-21-22 9:37AM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM CLEAR 10-21-22 9:34AM
T 1 TANK DIESEL TK#SA098U001 OVERFILL ALARM ALARM 10-21-22 9:31AM
T 1 TANK DIESEL TK#SA098U001 LOW PRODUCT ALARM CLEAR 10-21-22 9:30AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 10-21-22 9:30AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 10-21-22 9:29AM
T 1 TANK DIESEL TK#SA098U001 LOW PRODUCT ALARM ALARM 10-21-22 9:29AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 10-21-22 9:29AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT ALARM 10-21-22 9:27AM
L 5 PIPE PIPING PAN FUEL ALARM CLEAR 10-21-22 9:23AM
L 5 PIPE PIPING PAN FUEL ALARM ALARM 10-21-22 9:23AM
L 5 PIPE PIPING PAN FUEL ALARM CLEAR 10-21-22 9:20AM
L 5 PIPE PIPING PAN FUEL ALARM ALARM 10-21-22 9:20AM
L 4 PIPE TRANSITION SUMP FUEL ALARM CLEAR 10-21-22 9:18AM
L 4 PIPE TRANSITION SUMP FUEL ALARM ALARM 10-21-22 9:16AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM CLEAR 10-21-22 9:15AM
L 3 PIPE PIPING SUMP SENSOR FUEL ALARM ALARM 10-21-22 9:14AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM CLEAR 10-21-22 9:11AM
L 2 OTHER FILL SUMP SENSOR FUEL ALARM ALARM 10-21-22 9:09AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM CLEAR 10-21-22 9:05AM
L 1 ANNULAR ANNULAR SPACE SENSOR FUEL ALARM ALARM 10-21-22 9:04AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER ALARM CLEAR 10-20-21 9:47AM
T 1 TANK DIESEL TK#SA098U001 PROBE OUT CLEAR 10-20-21 9:46AM
I11200
OCT 18, 2023 6:56 AM
BKFDCA14 SA098 S-S
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 10-17-23 1:25PM
SYSTEM PRINTER ERROR ALARM 10-17-23 1:25PM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING CLEAR 10-17-23 12:58PM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING CLEAR 10-17-23 12:58PM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING ALARM 10-17-23 12:58PM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM CLEAR 10-17-23 12:58PM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM ALARM 10-17-23 12:54PM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING ALARM 10-17-23 12:47PM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED CLEAR 10-17-23 12:44PM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED ALARM 10-17-23 12:43PM
SYSTEM PRINTER ERROR CLEAR 4-20-23 8:11PM
SYSTEM PAPER OUT CLEAR 4-20-23 8:11PM
SYSTEM PRINTER ERROR ALARM 4-20-23 8:11PM
SYSTEM PAPER OUT ALARM 4-20-23 8:11PM
SYSTEM PRINTER ERROR CLEAR 2-23-23 6:06PM
SYSTEM PAPER OUT CLEAR 2-23-23 6:06PM
SYSTEM PRINTER ERROR ALARM 2-23-23 6:06PM
SYSTEM PAPER OUT ALARM 2-23-23 6:06PM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING CLEAR 10-21-22 9:42AM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING ALARM 10-21-22 9:42AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING CLEAR 10-21-22 9:42AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING ALARM 10-21-22 9:37AM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM CLEAR 10-21-22 9:33AM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM ALARM 10-21-22 9:33AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED CLEAR 10-21-22 9:30AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED ALARM 10-21-22 9:27AM
SYSTEM PRINTER ERROR CLEAR 10-20-21 10:45AM
SYSTEM PAPER OUT CLEAR 10-20-21 10:45AM
SYSTEM PRINTER ERROR ALARM 10-20-21 10:44AM
SYSTEM PAPER OUT ALARM 10-20-21 10:44AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED CLEAR 10-20-21 9:47AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING CLEAR 10-20-21 9:47AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED ALARM 10-20-21 9:47AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING ALARM 10-20-21 9:42AM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM CLEAR 10-20-21 9:37AM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM ALARM 10-20-21 9:37AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED CLEAR 10-20-21 9:34AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED ALARM 10-20-21 9:34AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING CLEAR 10-09-20 9:39AM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING CLEAR 10-09-20 9:39AM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING ALARM 10-09-20 9:39AM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM CLEAR 10-09-20 9:39AM
T 1 TANK DIESEL TK#SA098U001 HIGH PRODUCT ALARM ALARM 10-09-20 9:35AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED CLEAR 10-09-20 9:35AM
T 1 TANK DIESEL TK#SA098U001 HIGH WATER WARNING ALARM 10-09-20 9:31AM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED ALARM 10-09-20 9:28AM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING CLEAR 10-16-19 12:46PM
T 1 TANK DIESEL TK#SA098U001 LOW TEMP WARNING ALARM 10-16-19 12:46PM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED CLEAR 10-16-19 12:46PM
T 1 TANK DIESEL TK#SA098U001 DELIVERY NEEDED ALARM 10-16-19 12:42PM
I20600
OCT 18, 2023 6:57 AM
BKFDCA14 SA098 S-S
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
TANK ALARM HISTORY
TANK 1 DIESEL TK#SA098U001
SETUP DATA WARNING APR 26, 2004 3:45 PM
LEAK ALARM JUN 2, 2006 9:35 AM
HIGH WATER ALARM OCT 17, 2023 12:47 PM
OCT 21, 2022 9:37 AM
OCT 20, 2021 9:42 AM
OVERFILL ALARM OCT 17, 2023 12:54 PM
OCT 17, 2023 12:52 PM
OCT 21, 2022 9:31 AM
LOW PRODUCT ALARM OCT 17, 2023 12:43 PM
OCT 21, 2022 9:29 AM
OCT 20, 2021 9:34 AM
SUDDEN LOSS ALARM JUN 2, 2006 9:04 AM
HIGH PRODUCT ALARM OCT 17, 2023 12:54 PM
OCT 21, 2022 9:33 AM
OCT 20, 2021 9:37 AM
INVALID FUEL LEVEL OCT 5, 2018 9:29 AM
OCT 26, 2016 9:33 AM
NOV 12, 2015 9:28 AM
PROBE OUT OCT 17, 2023 12:56 PM
OCT 17, 2023 12:43 PM
OCT 21, 2022 9:41 AM
HIGH WATER WARNING OCT 17, 2023 12:47 PM
OCT 21, 2022 9:37 AM
OCT 20, 2021 9:42 AM
DELIVERY NEEDED OCT 17, 2023 12:43 PM
OCT 21, 2022 9:27 AM
OCT 20, 2021 9:47 AM
MAX PRODUCT ALARM OCT 9, 2020 9:35 AM
OCT 16, 2019 12:29 PM
OCT 5, 2018 9:39 AM
PERIODIC TEST FAIL JUN 14, 2006 1:38 AM
JUN 3, 2006 9:55 AM
MAY 11, 2006 7:55 AM
CSLD INCR RATE WARN NOV 9, 2004 11:34 AM
OCT 23, 2004 10:39 AM
LOW TEMP WARNING OCT 17, 2023 12:58 PM
OCT 21, 2022 9:42 AM
OCT 9, 2020 9:39 AM
I30200
OCT 18, 2023 6:57 AM
BKFDCA14 SA098 S-S
3221 S. H ST.
BAKERSFIELD,CA 93304
661-832-8370
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 ANNULAR SPACE SENSOR
OCT 17, 2023 12:25 PM FUEL ALARM
OCT 21, 2022 9:04 AM FUEL ALARM
OCT 20, 2021 9:13 AM FUEL ALARM
2 FILL SUMP SENSOR
OCT 17, 2023 12:42 PM FUEL ALARM
OCT 17, 2023 12:29 PM FUEL ALARM
OCT 21, 2022 9:09 AM FUEL ALARM
3 PIPING SUMP SENSOR
OCT 17, 2023 12:31 PM FUEL ALARM
OCT 21, 2022 9:14 AM FUEL ALARM
OCT 20, 2021 9:22 AM FUEL ALARM
4 TRANSITION SUMP
OCT 17, 2023 12:34 PM FUEL ALARM
OCT 21, 2022 9:16 AM FUEL ALARM
OCT 20, 2021 9:25 AM FUEL ALARM
5 PIPING PAN
OCT 17, 2023 12:36 PM FUEL ALARM
OCT 21, 2022 9:23 AM FUEL ALARM
OCT 21, 2022 9:20 AM FUEL ALARM
Identification of Test Procedures for Secondary Containment Testing
To Whom It May Concern:
Tait Environmental Services, Inc., utilizes the following procedures when conducting Secondary
Containment Testing:
1) Containment Sumps, Transition Sumps, UDCs – Tait follows PEI‐RP1200‐17 Section 6.6 for the
accelerated test method. Tait uses the Incon TS‐1000 hydrostatic test equipment following the
attached procedures.
2) Spill Buckets; Direct Bury & Contained in Sumps – Spill buckets contained in sumps are tested
per PEI‐1200‐17, Section 6.2, however Tait Pass/Fail threshold is 0” drop in one hour. Direct Bury
Spill Buckets are test the same as containment sumps per PEI‐1200‐17, Section 6.6.
3) Tank Annular Space – testing is conducted per PEI‐1200‐17, Section 4.2
4) Piping Secondary Containment – Testing is conducted per PEI‐RP1200‐17, Section 5.3
Please consider this letter as our Test Procedure utilized when conducting Secondary Containment
Testing in lieu of either parts or the whole RP1200 document due to copyright infringement.