HomeMy WebLinkAboutFMC 2023Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10123120 11-30-23
Sparkling Image Carwash
2301 H Street Bakersfield 93301
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Rockland Kirk
1073967
10241356 9-29-24
VMI #5255 10-3-24
GVR C32654 10-13-24
11-30-23 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder-Root TLS-350
336.00
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 DISP 1-2
L2 208 DISP 3-4
L3 208 DISP 11-12
L4 208 DISP 7-8
L5 208 DISP 9-10
L6 208 DISP 5-6
L7 208 DISP 13-14
L8 208 DISP 15-16
L9 208 UNLEADED SUMP
L10 208 SUPREME SUMP
L11 208 DIESEL SUMP
L12 UNK UNLEADED ANNULAR
L13 UNK SUPREME ANNULAR
L14 UNK DIESEL ANNULAR
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V REGULAR UNLEADED
T2 FX1V SUPREME UNLEADED
T3 FX1DV DIESEL
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Sparkling Image Carwash2301 H StreetBakersfield101231201-23-4 5-68791DSL8791879187911-21-23-45-67-87-8ProductProductProductProductProductProductProductProductProductRockland Kirk
APPENDIX C-10
7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB8715-16ProductProduct13-14918713-14ProductProduct11-12918711-12ProductProduct9-10DSL919-10ProductProduct9-1087DSL7-8ProductRockland Kirk
APPENDIX C-10
7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBProduct15-16DSL9115-16ProductRockland Kirk■
■
■■
■
■
■
■
■
■
■
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date Total # of Pages
10123120 11-30-23
Sparkling Image Carwash
2301 H Street Bakersfield 93301
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Rockland Kirk
1073967
10241356 9-29-24
FFS PHASE 1 EVR 1016693714 10-16-24
PEI RP 1200 SPILL BUCKETS
11-30-23 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1 87
PHILTITE
91 spill bucket and cap was replaced, 87 spill bucket drain was disassembled, cleaned out and reassembled. Both passed
retests.
T2 91
PHILTITE
T3 DSL
PHILTITE
Responses Received:
200
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
NOV 30, 2023 9:01 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 87 7191 55.51 1.0 65.0 4809
2 SUPREME 91 4489 38.44 0.0 65.8 7511
3 DIESEL 1907 20.73 0.0 75.2 10093
I90500
NOV 30, 2023 9:02 AM
SOFTWARE REVISION LEVEL
VERSION 336.00
SOFTWARE# 346336-100-A
CREATED - 19.12.13.15.19
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
BIR
FUEL MANAGER
ISD/APM
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I50500
NOV 30, 2023 9:02 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
NOV 30, 2023 9:02 AM
SHIFT TIME 1 : 12:00 AM
I50202
NOV 30, 2023 9:02 AM
SHIFT TIME 2 : 6:00 AM
I50203
NOV 30, 2023 9:02 AM
SHIFT TIME 3 : 12:00 PM
I50204
NOV 30, 2023 9:02 AM
SHIFT TIME 4 : 6:00 PM
I54600
NOV 30, 2023 9:02 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
NOV 30, 2023 9:02 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
NOV 30, 2023 9:02 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
NOV 30, 2023 9:02 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
NOV 30, 2023 9:02 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
NOV 30, 2023 9:02 AM
PRINT TC VOLUMES
ENABLED
I50E00
NOV 30, 2023 9:02 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
NOV 30, 2023 9:02 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
NOV 30, 2023 9:02 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
NOV 30, 2023 9:02 AM
DAYLIGHT SAVING TIME
ENABLED OFF
I51B00
NOV 30, 2023 9:02 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
NOV 30, 2023 9:02 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
NOV 30, 2023 9:02 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
NOV 30, 2023 9:02 AM
TANK CHART SECURITY
DISABLED
I5BD00
NOV 30, 2023 9:02 AM
CUSTOM ALARM LABELS
DISABLED
I56000
NOV 30, 2023 9:02 AM
MASS/DENSITY
DISABLED
I88101
NOV 30, 2023 9:02 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
NOV 30, 2023 9:02 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 1200
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
NOV 30, 2023 9:02 AM
PORT SETTINGS:
COMM BOARD : 3 (S-SAT )
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
DTR NORMAL STATE: HIGH
I88104
NOV 30, 2023 9:02 AM
I88105
NOV 30, 2023 9:02 AM
I88106
NOV 30, 2023 9:02 AM
PORT SETTINGS:
COMM BOARD : 6 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I52000
NOV 30, 2023 9:02 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 WEEKLY SUN 9:30 PM
2 WEEKLY SUN 9:30 PM
3 WEEKLY SUN 9:30 PM
4 WEEKLY SUN 9:30 PM
5 WEEKLY SUN 9:30 PM
6 WEEKLY SUN 9:30 PM
7 WEEKLY SUN 9:30 PM
8 VEEDER ROOT (FMS) WEEKLY SUN 9:30 PM
I60100
NOV 30, 2023 9:02 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED 87 ON
2 SUPREME 91 ON
3 DIESEL ON
4 OFF
I60200
NOV 30, 2023 9:02 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED 87
2 SUPREME 91
3 DIESEL
4
I60300
NOV 30, 2023 9:02 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 87 1
2 SUPREME 91 2
3 DIESEL 3
4 4
I60900
NOV 30, 2023 9:02 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 87 0.000700
2 SUPREME 91 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
NOV 30, 2023 9:02 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 87 96.00
2 SUPREME 91 96.00
3 DIESEL 96.00
4 0.00
I60A00
NOV 30, 2023 9:02 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 87
1 PT 12000 2 SUPREME 91 1 PT 12000 3 DIESEL
1 PT 12000 4 1 PT 0
I60400
NOV 30, 2023 9:02 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 12000
2 SUPREME 91 12000
3 DIESEL 12000
4 0
I60500
NOV 30, 2023 9:03 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 12000 0 0 0
2 SUPREME 91 12000 0 0 0
3 DIESEL 12000 0 0 0
4 0 0 0 0
I60600
NOV 30, 2023 9:03 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 SUPREME 91 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DIESEL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
NOV 30, 2023 9:03 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED 87 NO
2 SUPREME 91 NO
3 DIESEL NO
4 NO
I62F00
NOV 30, 2023 9:03 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 87 4.0 IN.
2 SUPREME 91 4.0 IN.
3 DIESEL 4.0 IN.
I62700
NOV 30, 2023 9:03 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 87 2.0
2 SUPREME 91 2.0
3 DIESEL 2.0
I64200
NOV 30, 2023 9:03 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED 87 LOW
2 SUPREME 91 LOW
3 DIESEL LOW
I62400
NOV 30, 2023 9:03 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 87 3.0
2 SUPREME 91 3.0
3 DIESEL 3.0
I62800
NOV 30, 2023 9:03 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 12000
2 SUPREME 91 12000
3 DIESEL 12000
4 0
I62300
NOV 30, 2023 9:03 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 10800
2 SUPREME 91 10800
3 DIESEL 10800
4 0
I62200
NOV 30, 2023 9:03 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 11400
2 SUPREME 91 11400
3 DIESEL 11400
4 0
I62900
NOV 30, 2023 9:03 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 1200
2 SUPREME 91 1200
3 DIESEL 1200
4 0
I62100
NOV 30, 2023 9:03 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 451
2 SUPREME 91 451
3 DIESEL 451
4 0
I62600
NOV 30, 2023 9:03 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 99
2 SUPREME 91 99
3 DIESEL 99
4 99
I62500
NOV 30, 2023 9:03 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 99
2 SUPREME 91 99
3 DIESEL 99
4 99
I60800
NOV 30, 2023 9:03 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 87 -3.00
2 SUPREME 91 -2.00
3 DIESEL 0.00
4 0.00
I60B00
NOV 30, 2023 9:03 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
NOV 30, 2023 9:03 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 87 0.00
2 SUPREME 91 0.00
3 DIESEL 0.00
4 0.00
I61200
NOV 30, 2023 9:03 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED 87 NONE NONE
2 SUPREME 91 NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
NOV 30, 2023 9:03 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 120
2 SUPREME 91 120
3 DIESEL 120
4 0
I62A00
NOV 30, 2023 9:04 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 120
2 SUPREME 91 120
3 DIESEL 120
4 0
I62C00
NOV 30, 2023 9:04 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED 87 STANDARD
2 SUPREME 91 STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
NOV 30, 2023 9:04 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED 87 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 SUPREME 91 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
NOV 30, 2023 9:04 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED 87 OFF OFF
2 SUPREME 91 OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
NOV 30, 2023 9:04 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED 87 OFF
2 SUPREME 91 OFF
3 DIESEL OFF
4 OFF
I63200
NOV 30, 2023 9:04 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED 87 OFF
2 SUPREME 91 OFF
3 DIESEL OFF
4 OFF
I61000
NOV 30, 2023 9:04 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 87 1
2 SUPREME 91 1
3 DIESEL 1
4 1
I63A00
NOV 30, 2023 9:04 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 87 10.00%
2 SUPREME 91 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
NOV 30, 2023 9:04 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JUL 23, 2010
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
NOV 30, 2023 9:04 AM
CSLD PROBABLITY OF DETECTION
I61400
NOV 30, 2023 9:04 AM
CSLD CLIMATE FACTOR
I61600
NOV 30, 2023 9:04 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED 87 IMMEDIATE
2 SUPREME 91 IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
NOV 30, 2023 9:04 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED 87 DISABLED
2 SUPREME 91 DISABLED
3 DIESEL DISABLED
4 DISABLED
I61B00
NOV 30, 2023 9:04 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
NOV 30, 2023 9:04 AM
CSLD REPORT ONLY
I62B00
NOV 30, 2023 9:04 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED 87 ??? 0, 0
2 SUPREME 91 ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
NOV 30, 2023 9:04 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
NOV 30, 2023 9:04 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 0
2 SUPREME 91 0
3 DIESEL 0
4 0
I63500
NOV 30, 2023 9:04 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 87 1
2 SUPREME 91 1
3 DIESEL 1
4 1
I63900
NOV 30, 2023 9:04 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED 87
END FACTOR: NONE
2 SUPREME 91
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
NOV 30, 2023 9:04 AM
I77700
NOV 30, 2023 9:04 AM
I77800
NOV 30, 2023 9:04 AM
I78C00
NOV 30, 2023 9:04 AM
I78300
NOV 30, 2023 9:04 AM
I78F00
NOV 30, 2023 9:04 AM
I78700
NOV 30, 2023 9:04 AM
I70200
NOV 30, 2023 9:04 AM
LIQUID LABEL
DEVICE LABEL
1 DISP. 1-2
2 DISP. 3-4
3 DISP. 11-12
4 DISP. 7-8
5 DISP. 9-10
6 DISP 5-6
7 DISP. 13-14
8 DISP. 15-16
9 UNLEADED SUMP
10 SUPREME SUMP
11 DIESEL SUMP
12 UNLEADED ANNULAR
13 SUPREME ANNULAR
14 DIESEL ANNULAR
15 UNLEADED ANN
16
17 UNL ANNULAR
18
19 UNL ANNULAR
20
21
22
23
24 BUBBA SENSOR
I70300
NOV 30, 2023 9:05 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 DISP. 1-2 TRI-STATE (SINGLE FLOAT)
2 DISP. 3-4 TRI-STATE (SINGLE FLOAT)
3 DISP. 11-12 TRI-STATE (SINGLE FLOAT)
4 DISP. 7-8 TRI-STATE (SINGLE FLOAT)
5 DISP. 9-10 TRI-STATE (SINGLE FLOAT)
6 DISP 5-6 TRI-STATE (SINGLE FLOAT)
7 DISP. 13-14 TRI-STATE (SINGLE FLOAT)
8 DISP. 15-16 TRI-STATE (SINGLE FLOAT)
9 UNLEADED SUMP TRI-STATE (SINGLE FLOAT)
10 SUPREME SUMP TRI-STATE (SINGLE FLOAT)
11 DIESEL SUMP TRI-STATE (SINGLE FLOAT)
12 UNLEADED ANNULAR NORMALLY CLOSED
13 SUPREME ANNULAR NORMALLY CLOSED
14 DIESEL ANNULAR NORMALLY CLOSED
15 UNLEADED ANN NORMALLY CLOSED
16 TRI-STATE (SINGLE FLOAT)
17 UNL ANNULAR NORMALLY CLOSED
18 TRI-STATE (SINGLE FLOAT)
19 UNL ANNULAR NORMALLY CLOSED
20 TRI-STATE (SINGLE FLOAT)
21 TRI-STATE (SINGLE FLOAT)
22 TRI-STATE (SINGLE FLOAT)
23 TRI-STATE (SINGLE FLOAT)
24 BUBBA SENSOR NORMALLY CLOSED
I70400
NOV 30, 2023 9:05 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 DISP. 1-2 DISPENSER PAN
2 DISP. 3-4 DISPENSER PAN
3 DISP. 11-12 DISPENSER PAN
4 DISP. 7-8 DISPENSER PAN
5 DISP. 9-10 DISPENSER PAN
6 DISP 5-6 DISPENSER PAN
7 DISP. 13-14 DISPENSER PAN
8 DISP. 15-16 DISPENSER PAN
9 UNLEADED SUMP STP SUMP
10 SUPREME SUMP STP SUMP
11 DIESEL SUMP STP SUMP
12 UNLEADED ANNULAR ANNULAR SPACE
13 SUPREME ANNULAR ANNULAR SPACE
14 DIESEL ANNULAR ANNULAR SPACE
15 UNLEADED ANN ANNULAR SPACE
16 OTHER SENSORS
17 UNL ANNULAR ANNULAR SPACE
18 OTHER SENSORS
19 UNL ANNULAR ANNULAR SPACE
20 OTHER SENSORS
21 OTHER SENSORS
22 OTHER SENSORS
23 OTHER SENSORS
24 BUBBA SENSOR OTHER SENSORS
I74200
NOV 30, 2023 9:05 AM
I74300
NOV 30, 2023 9:05 AM
I74400
NOV 30, 2023 9:05 AM
I74700
NOV 30, 2023 9:05 AM
I74800
NOV 30, 2023 9:05 AM
I74900
NOV 30, 2023 9:05 AM
I7BC00
NOV 30, 2023 9:05 AM
I80200
NOV 30, 2023 9:05 AM
I80300
NOV 30, 2023 9:05 AM
I80400
NOV 30, 2023 9:05 AM
I80700
NOV 30, 2023 9:05 AM
RELAY LABEL
DEVICE LABEL
1 UNLEADED 87
2 SUPREME
3 DIESEL
4 OVERFILL ALARM
5 REMOTE ALARMS
6 REMOTE ALARM
7
8
I80900
NOV 30, 2023 9:05 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNLEADED 87 NORMALLY CLOSED
2 SUPREME NORMALLY CLOSED
3 DIESEL NORMALLY CLOSED
4 OVERFILL ALARM NORMALLY OPEN
5 REMOTE ALARMS NORMALLY CLOSED
6 REMOTE ALARM NORMALLY CLOSED
7 NORMALLY OPEN
8 NORMALLY OPEN
I80B00
NOV 30, 2023 9:05 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNLEADED 87 1
2 SUPREME 2
3 DIESEL 3
4 OVERFILL ALARM NONE
5 REMOTE ALARMS NONE
6 REMOTE ALARM NONE
7 NONE
8 NONE
I80A00
NOV 30, 2023 9:05 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNLEADED 87 STANDARD
2 SUPREME STANDARD
3 DIESEL STANDARD
4 OVERFILL ALARM STANDARD
5 REMOTE ALARMS STANDARD
6 REMOTE ALARM STANDARD
7 STANDARD
8 STANDARD
I80C00
NOV 30, 2023 9:05 AM
I80800
NOV 30, 2023 9:05 AM
RELAY SETUP REPORT
R 1:UNLEADED 87
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
IN-TANK ALARMS
T 1:LEAK ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:SUPREME
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
IN-TANK ALARMS
T 2:LEAK ALARM
T 2:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L10:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L10:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DIESEL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 3
IN-TANK ALARMS
T 3:LEAK ALARM
T 3:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 8:FUEL ALARM
L11:FUEL ALARM
L 1:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L 1:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 8:SHORT ALARM
L11:SHORT ALARM
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
R 5:REMOTE ALARMS
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: NONE
IN-TANK ALARMS
ALL:LEAK ALARM
ALL:HIGH WATER ALARM
ALL:OVERFILL ALARM
ALL:LOW PRODUCT ALARM
ALL:SUDDEN LOSS ALARM
ALL:HIGH PRODUCT ALARM
ALL:INVALID FUEL LEVEL
ALL:PROBE OUT
ALL:HIGH WATER WARNING
ALL:DELIVERY NEEDED
ALL:MAX PRODUCT ALARM
ALL:GROSS TEST FAIL
ALL:PERIODIC TEST FAIL
ALL:ANNUAL TEST FAIL
ALL:PER TST NEEDED WRN
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L15:FUEL ALARM
L16:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L16:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
L15:SHORT ALARM
L16:SHORT ALARM
SMARTSENSOR ALARMS
ALL:SETUP DATA WARNING
ALL:COMMUNICATION ALARM
ALL:SENSOR FAULT ALARM
ALL:SENSOR FAULT WARN
ISD SITE ALARMS
ISD STAGE I WARN
ISD GROSS PRES WARN
ISD GROSS PRES FAIL
ISD DEGRD PRES WARN
ISD DEGRD PRES FAIL
ISD VAPOR LEAK WARN
ISD VAPOR LEAK FAIL
ISD VP PRES WARN
ISD VP PRES FAIL
ISD VP STATUS WARN
ISD VP STATUS FAIL
MISSING RELAY SETUP
MISSING HOSE SETUP
MISSING TANK SETUP
MISS VAPOR FLOW MTR
MISS VAPOR PRES SEN
MISSING VP INPUT
ISD SETUP WARN
ISD SETUP FAIL
ISD SENSOR OUT WARN
ISD SENSOR OUT FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT WARN
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT WARN
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT WARN
ALL:FLOW COLLECT FAIL
ALL:AIRFLOW MTR SETUP
VAPOR FLW MTR ALMS
ALL:CHK VAPOR FLOW MTR
R 6:REMOTE ALARM
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L15:FUEL ALARM
L16:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L15:SENSOR OUT ALARM
L16:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
L15:SHORT ALARM
L16:SHORT ALARM
SMARTSENSOR ALARMS
ALL:COMMUNICATION ALARM
ISD SITE ALARMS
ISD STAGE I WARN
ISD GROSS PRES WARN
ISD GROSS PRES FAIL
ISD DEGRD PRES WARN
ISD DEGRD PRES FAIL
ISD VAPOR LEAK WARN
ISD VAPOR LEAK FAIL
ISD VP PRES WARN
ISD VP PRES FAIL
ISD VP STATUS WARN
ISD VP STATUS FAIL
MISSING RELAY SETUP
MISSING HOSE SETUP
ISD SENSOR OUT WARN
ISD SENSOR OUT FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT WARN
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT WARN
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT WARN
ALL:FLOW COLLECT FAIL
ALL:AIRFLOW MTR SETUP
VAPOR FLW MTR ALMS
ALL:CHK VAPOR FLOW MTR
R 7:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 8:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
NOV 30, 2023 9:07 AM
EDIM:1 VR:349643-001-B TD:97.10.27.11.25
I79100
NOV 30, 2023 9:07 AM
I72300
NOV 30, 2023 9:07 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 FM 1-2 AIR FLOW METER
02 FM 3-4 AIR FLOW METER
03 FM 5-6 AIR FLOW METER
04 FM 7-8 AIR FLOW METER
05 FM 9-10 AIR FLOW METER
06 FM 11-12 AIR FLOW METER
07 FM 13-14 AIR FLOW METER
08 PRESSURE SENSOR VAPOR PRESSURE
09 FM 15-16 AIR FLOW METER
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
NOV 30, 2023 9:08 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
NOV 30, 2023 9:08 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
NOV 30, 2023 9:08 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
VAPOR PROCESSOR TYPE
NONE
IV4700
NOV 30, 2023 9:08 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
ASSESSMENT TIME
START TIME: 9:22 AM
TIME DELAY MINUTES: 1
IV5200
NOV 30, 2023 9:08 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
ACCEPT HIGH ORVR: YES
IV4A00
NOV 30, 2023 9:08 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 06 BLEND3
02 02 02 01 06 BLEND3
03 03 03 02 06 BLEND3
04 04 04 02 06 BLEND3
05 05 05 03 06 BLEND3
06 06 06 03 06 BLEND3
07 07 07 04 06 BLEND3
08 08 08 04 06 BLEND3
09 09 09 05 06 BLEND3
10 16 10 05 06 BLEND3
11 17 11 06 06 BLEND3
12 18 12 06 06 BLEND3
13 19 13 07 06 BLEND3
14 20 14 07 06 BLEND3
15 21 15 08 06 BLEND3
16 22 16 08 06 BLEND3
IV4B00
NOV 30, 2023 9:08 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 01/01 02/01 09/01 xx/xx
02 01 01/02 09/02 02/02 xx/xx
03 02 01/03 09/03 02/03 xx/xx
04 02 01/04 09/04 02/04 xx/xx
05 03 01/05 09/05 02/05 xx/xx
06 03 01/06 09/06 02/06 xx/xx
07 04 01/07 09/07 02/07 xx/xx
08 04 01/08 09/08 02/08 xx/xx
09 05 01/09 09/09 02/09 xx/xx
16 05 01/10 09/10 02/10 xx/xx
17 06 01/11 09/11 02/11 xx/xx
18 06 01/12 09/12 02/12 xx/xx
19 07 01/13 09/13 02/13 xx/xx
20 07 01/14 09/14 02/14 xx/xx
21 08 01/15 09/15 02/15 xx/xx
22 08 01/16 09/16 02/16 xx/xx
IV4900
NOV 30, 2023 9:08 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
NOV 30, 2023 9:08 AM
ISD VERSION: 01.06
Responses Received:
I20600
NOV 30, 2023 8:41 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
TANK ALARM HISTORY
TANK 1 UNLEADED 87
OVERFILL ALARM OCT 28, 2021 10:52 AM
NOV 2, 2020 2:36 AM
PROBE OUT OCT 28, 2021 10:56 AM
OCT 28, 2021 10:42 AM
DEC 15, 2020 5:47 PM
LOW TEMP WARNING OCT 28, 2021 10:57 AM
OCT 28, 2021 10:43 AM
TANK 2 SUPREME 91
OVERFILL ALARM OCT 28, 2021 10:50 AM
PROBE OUT FEB 3, 2022 8:33 AM
OCT 28, 2021 10:54 AM
OCT 28, 2021 10:41 AM
DELIVERY NEEDED JUL 18, 2020 9:15 PM
LOW TEMP WARNING OCT 28, 2021 10:55 AM
OCT 28, 2021 10:42 AM
TANK 3 DIESEL
OVERFILL ALARM OCT 28, 2021 10:46 AM
PROBE OUT OCT 28, 2021 10:52 AM
OCT 28, 2021 10:40 AM
DELIVERY NEEDED NOV 23, 2022 6:41 AM
SEP 8, 2022 9:20 AM
JUN 23, 2022 3:08 PM
LOW TEMP WARNING OCT 28, 2021 10:54 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
I10200
NOV 30, 2023 8:55 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 UNUSED 9852359 9915123
2 4 PROBE / G.T. 163465 163643
3 8SMARTSENSOR BD 39589 39625
4 7SMARTSENSOR BD 507789 508533
5 INTERSTITIAL BD 201480 201920
6 INTERSTITIAL BD 202096 202397
7 INTERSTITIAL BD 200750 201035
8 UNUSED 9828973 9896622
9 RELAY BOARD 15000 15007
10 RELAY BOARD 14934 14963
11 UNUSED 9834834 9898864
12 UNUSED 9823885 9895355
13 UNUSED 9823820 9881278
14 UNUSED 9810856 9886552
15 UNUSED 9818236 9886748
16 UNUSED 9817272 9886987
COMM 1 ELEC DISP INT. 100586 100792
COMM 2 RS232 SERIAL BD 14934 15007
COMM 3 SERIAL SAT BD 480450 481201
COMM 4 UNUSED 9832382 9891368
COMM 5 UNUSED 9816090 9889973
COMM 6 RS232 SERIAL BD 9816856 14920
I90200
NOV 30, 2023 8:56 AM
SOFTWARE REVISION LEVEL
VERSION 336.00
SOFTWARE# 346336-100-A
CREATED - 19.12.13.15.19
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
BIR
FUEL MANAGER
ISD/APM
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I11100
NOV 30, 2023 8:56 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L12 ANNULAR UNLEADED ANNULAR FUEL ALARM CLEAR 11-30-23 8:54AM
L12 ANNULAR UNLEADED ANNULAR FUEL ALARM ALARM 11-27-23 8:54PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT FAIL CLEAR 11-24-23 2:06PM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT FAIL ALARM 11-24-23 9:25AM
L14 ANNULAR DIESEL ANNULAR FUEL ALARM CLEAR 11-21-23 11:50AM
L13 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-21-23 11:49AM
L12 ANNULAR UNLEADED ANNULAR FUEL ALARM CLEAR 11-21-23 11:48AM
L 5 DISP PAN DISP. 9-10 FUEL ALARM CLEAR 11-21-23 10:55AM
L 5 DISP PAN DISP. 9-10 FUEL ALARM ALARM 11-21-23 10:51AM
L 6 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM
L 5 DISP PAN DISP. 9-10 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM
L11 STP SUMP DIESEL SUMP SENSOR OUT ALARM CLEAR 11-21-23 10:26AM
L10 STP SUMP SUPREME SUMP SENSOR OUT ALARM CLEAR 11-21-23 10:26AM
L 9 STP SUMP UNLEADED SUMP SENSOR OUT ALARM CLEAR 11-21-23 10:26AM
L 2 DISP PAN DISP. 3-4 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM
L 1 DISP PAN DISP. 1-2 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM
L 8 DISP PAN DISP. 15-16 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM
L 7 DISP PAN DISP. 13-14 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM
L 2 DISP PAN DISP. 3-4 SENSOR OUT ALARM ALARM 11-21-23 10:26AM
L 1 DISP PAN DISP. 1-2 SENSOR OUT ALARM ALARM 11-21-23 10:25AM
L 8 DISP PAN DISP. 15-16 SENSOR OUT ALARM ALARM 11-21-23 10:25AM
L 7 DISP PAN DISP. 13-14 SENSOR OUT ALARM ALARM 11-21-23 10:25AM
L 6 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 11-21-23 10:25AM
L 5 DISP PAN DISP. 9-10 SENSOR OUT ALARM ALARM 11-21-23 10:25AM
L11 STP SUMP DIESEL SUMP SENSOR OUT ALARM ALARM 11-21-23 10:25AM
L10 STP SUMP SUPREME SUMP SENSOR OUT ALARM ALARM 11-21-23 10:25AM
L 9 STP SUMP UNLEADED SUMP SENSOR OUT ALARM ALARM 11-21-23 10:25AM
L14 ANNULAR DIESEL ANNULAR FUEL ALARM ALARM 11-21-23 10:24AM
L13 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-21-23 10:20AM
L12 ANNULAR UNLEADED ANNULAR FUEL ALARM ALARM 11-21-23 10:17AM
L11 STP SUMP DIESEL SUMP FUEL ALARM CLEAR 11-21-23 9:43AM
L11 STP SUMP DIESEL SUMP FUEL ALARM ALARM 11-21-23 9:43AM
L10 STP SUMP SUPREME SUMP FUEL ALARM CLEAR 11-21-23 9:43AM
L10 STP SUMP SUPREME SUMP FUEL ALARM ALARM 11-21-23 9:42AM
L 9 STP SUMP UNLEADED SUMP FUEL ALARM CLEAR 11-21-23 9:42AM
L 9 STP SUMP UNLEADED SUMP FUEL ALARM ALARM 11-21-23 9:42AM
L 4 DISP PAN DISP. 7-8 FUEL ALARM CLEAR 11-21-23 9:42AM
L 4 DISP PAN DISP. 7-8 FUEL ALARM ALARM 11-21-23 9:41AM
L 6 DISP PAN DISP 5-6 FUEL ALARM CLEAR 11-21-23 9:41AM
L 6 DISP PAN DISP 5-6 FUEL ALARM ALARM 11-21-23 9:41AM
L 2 DISP PAN DISP. 3-4 FUEL ALARM CLEAR 11-21-23 9:41AM
L 2 DISP PAN DISP. 3-4 FUEL ALARM ALARM 11-21-23 9:40AM
L 1 DISP PAN DISP. 1-2 FUEL ALARM CLEAR 11-21-23 9:40AM
L 1 DISP PAN DISP. 1-2 FUEL ALARM ALARM 11-21-23 9:40AM
L 8 DISP PAN DISP. 15-16 FUEL ALARM CLEAR 11-21-23 9:39AM
L 8 DISP PAN DISP. 15-16 FUEL ALARM ALARM 11-21-23 9:39AM
L 7 DISP PAN DISP. 13-14 FUEL ALARM CLEAR 11-21-23 9:39AM
L 7 DISP PAN DISP. 13-14 FUEL ALARM ALARM 11-21-23 9:38AM
L 3 DISP PAN DISP. 11-12 FUEL ALARM CLEAR 11-21-23 9:38AM
L 3 DISP PAN DISP. 11-12 FUEL ALARM ALARM 11-21-23 9:38AM
I11200
NOV 30, 2023 8:56 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-28-23 9:26AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 9:22AM
OTHER ISD GROSS PRES WARN CLEAR 11-24-23 8:00AM
OTHER ISD GROSS PRES WARN ALARM 11-23-23 9:25AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-17-23 9:25AM
OTHER ISD GROSS PRES WARN CLEAR 11-17-23 8:41AM
OTHER ISD GROSS PRES WARN ALARM 11-15-23 9:26AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-13-23 9:58AM
SYSTEM PRINTER ERROR CLEAR 11-12-23 8:36AM
SYSTEM PAPER OUT CLEAR 11-12-23 8:36AM
SYSTEM PRINTER ERROR ALARM 11-12-23 8:36AM
SYSTEM PAPER OUT ALARM 11-12-23 8:36AM
SYSTEM PRINTER ERROR CLEAR 11-12-23 8:36AM
SYSTEM PAPER OUT CLEAR 11-12-23 8:36AM
SYSTEM PRINTER ERROR ALARM 11-12-23 8:35AM
SYSTEM PAPER OUT ALARM 11-12-23 8:35AM
SYSTEM PRINTER ERROR CLEAR 11-12-23 8:35AM
SYSTEM PAPER OUT CLEAR 11-12-23 8:35AM
SYSTEM PRINTER ERROR ALARM 11-12-23 12:00AM
SYSTEM PAPER OUT ALARM 11-12-23 12:00AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-11-23 9:26AM
OTHER ISD GROSS PRES WARN CLEAR 11-08-23 9:49AM
OTHER ISD GROSS PRES WARN ALARM 11-08-23 9:25AM
OTHER ISD GROSS PRES WARN CLEAR 11-01-23 3:06PM
OTHER ISD GROSS PRES WARN ALARM 11-01-23 9:24AM
OTHER ISD GROSS PRES WARN CLEAR 10-26-23 8:33AM
OTHER ISD GROSS PRES WARN ALARM 10-25-23 9:24AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:04AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:04AM
SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM
SYSTEM PAPER OUT ALARM 10-25-23 8:03AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:03AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:03AM
SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM
SYSTEM PAPER OUT ALARM 10-25-23 8:03AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:03AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:03AM
SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM
SYSTEM PAPER OUT ALARM 10-25-23 8:03AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:02AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:02AM
SYSTEM PRINTER ERROR ALARM 10-25-23 8:02AM
SYSTEM PAPER OUT ALARM 10-25-23 8:02AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:01AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:01AM
SYSTEM PRINTER ERROR ALARM 10-24-23 12:00PM
SYSTEM PAPER OUT ALARM 10-24-23 12:00PM
OTHER ISD GROSS PRES WARN CLEAR 10-18-23 2:51PM
OTHER ISD GROSS PRES WARN ALARM 10-18-23 9:24AM
OTHER ISD GROSS PRES WARN CLEAR 10-11-23 9:26AM
I20600
NOV 30, 2023 8:57 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
TANK ALARM HISTORY
TANK 1 UNLEADED 87
OVERFILL ALARM OCT 28, 2021 10:52 AM
NOV 2, 2020 2:36 AM
PROBE OUT OCT 28, 2021 10:56 AM
OCT 28, 2021 10:42 AM
DEC 15, 2020 5:47 PM
LOW TEMP WARNING OCT 28, 2021 10:57 AM
OCT 28, 2021 10:43 AM
TANK 2 SUPREME 91
OVERFILL ALARM OCT 28, 2021 10:50 AM
PROBE OUT FEB 3, 2022 8:33 AM
OCT 28, 2021 10:54 AM
OCT 28, 2021 10:41 AM
DELIVERY NEEDED JUL 18, 2020 9:15 PM
LOW TEMP WARNING OCT 28, 2021 10:55 AM
OCT 28, 2021 10:42 AM
TANK 3 DIESEL
OVERFILL ALARM OCT 28, 2021 10:46 AM
PROBE OUT OCT 28, 2021 10:52 AM
OCT 28, 2021 10:40 AM
DELIVERY NEEDED NOV 23, 2022 6:41 AM
SEP 8, 2022 9:20 AM
JUN 23, 2022 3:08 PM
LOW TEMP WARNING OCT 28, 2021 10:54 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
NOV 30, 2023 8:57 AM
I30200
NOV 30, 2023 8:57 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP. 1-2
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
NOV 21, 2023 9:40 AM FUEL ALARM
DEC 21, 2022 10:16 AM SENSOR OUT ALARM
2 DISP. 3-4
NOV 21, 2023 10:26 AM SENSOR OUT ALARM
NOV 21, 2023 9:40 AM FUEL ALARM
DEC 21, 2022 10:16 AM SENSOR OUT ALARM
3 DISP. 11-12
NOV 21, 2023 9:38 AM FUEL ALARM
DEC 21, 2022 10:16 AM SENSOR OUT ALARM
DEC 21, 2022 10:10 AM FUEL ALARM
4 DISP. 7-8
NOV 21, 2023 9:41 AM FUEL ALARM
DEC 21, 2022 10:16 AM SENSOR OUT ALARM
DEC 21, 2022 10:09 AM FUEL ALARM
5 DISP. 9-10
NOV 21, 2023 10:51 AM FUEL ALARM
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
NOV 21, 2023 9:37 AM FUEL ALARM
6 DISP 5-6
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
NOV 21, 2023 9:41 AM FUEL ALARM
DEC 21, 2022 10:16 AM SENSOR OUT ALARM
7 DISP. 13-14
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
NOV 21, 2023 9:38 AM FUEL ALARM
DEC 21, 2022 10:16 AM SENSOR OUT ALARM
8 DISP. 15-16
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
NOV 21, 2023 9:39 AM FUEL ALARM
DEC 21, 2022 10:11 AM FUEL ALARM
9 UNLEADED SUMP
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
NOV 21, 2023 9:42 AM FUEL ALARM
DEC 21, 2022 10:16 AM SENSOR OUT ALARM
10 SUPREME SUMP
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
NOV 21, 2023 9:42 AM FUEL ALARM
DEC 21, 2022 10:16 AM SENSOR OUT ALARM
11 DIESEL SUMP
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
NOV 21, 2023 9:43 AM FUEL ALARM
DEC 21, 2022 10:16 AM SENSOR OUT ALARM
12 UNLEADED ANNULAR
NOV 27, 2023 8:54 PM FUEL ALARM
NOV 21, 2023 10:17 AM FUEL ALARM
DEC 21, 2022 10:30 AM FUEL ALARM
13 SUPREME ANNULAR
NOV 21, 2023 10:20 AM FUEL ALARM
DEC 21, 2022 1:37 PM FUEL ALARM
DEC 21, 2022 10:29 AM FUEL ALARM
14 DIESEL ANNULAR
NOV 21, 2023 10:24 AM FUEL ALARM
SEP 19, 2023 12:50 PM FUEL ALARM
DEC 21, 2022 10:26 AM FUEL ALARM
I31600
NOV 30, 2023 8:58 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 FM 1-2
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
2 FM 3-4
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
3 FM 5-6
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
4 FM 7-8
5 FM 9-10
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
6 FM 11-12
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
7 FM 13-14
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
8 PRESSURE SENSOR
9 FM 15-16
I40200
NOV 30, 2023 8:58 AM
I40300
NOV 30, 2023 8:58 AM
I34200
NOV 30, 2023 8:58 AM
I34700
NOV 30, 2023 8:58 AM
IV0100
NOV 30, 2023 8:58 AM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN
EVR VAPOR CONTAINMENT :NOTEST
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-11-29 09:28:25 A/L RATIO DEGRADATION FP 2 BLEND3 0.61
23-11-28 09:26:17 A/L RATIO DEGRADATION FP 2 BLEND3 0.61
23-11-23 09:25:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.34
23-11-23 09:25:10 A/L RATIO DEGRADATION FP 2 BLEND3 0.78
23-11-22 09:25:13 A/L RATIO DEGRADATION FP 2 BLEND3 0.78
23-11-21 09:25:05 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-11-20 09:25:24 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-11-19 09:25:13 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-11-18 09:25:12 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-11-17 09:25:41 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-11-24 09:25:46 A/L RATIO DEGRADATION FP 2 BLEND3 0.78
22-08-05 09:25:27 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.46
22-07-22 09:27:21 A/L RATIO DEGRADATION FP15 BLEND3 1.67
21-03-12 09:26:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55
20-11-26 09:26:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.30
20-11-12 09:24:44 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55
20-05-04 09:26:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 24.17
20-04-07 09:26:07 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.27
19-08-03 10:03:31 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
19-07-03 10:03:50 SENSOR OUT SELFTEST s 9
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-11-24 14:06:04 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
23-11-24 14:05:54 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
23-11-24 14:05:46 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-24 10:47:16 PUMPS MANUALLY RE-ENABLED
23-11-24 09:25:46 A/L RATIO GROSS DEGRADATION DISABLED FP 02 BLEND3
23-11-24 08:00:39 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-22 09:25:13 READINESS ISD:PP EVR:PP ISD & EVR READY
23-11-21 10:27:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-11-21 10:27:18 ISD STARTUP
23-11-21 10:27:03 ISD SHUTDOWN
Responses Received:
I10200
NOV 30, 2023 12:44 PM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 UNUSED 9852359 9859602
2 4 PROBE / G.T.163465 163426
3 8SMARTSENSOR BD 39589 39507
4 7SMARTSENSOR BD 507789 507019
5 INTERSTITIAL BD 201480 201581
6 INTERSTITIAL BD 202096 201856
7 INTERSTITIAL BD 200750 200527
8 UNUSED 9828973 9840106
9 RELAY BOARD 15000 14970
10 RELAY BOARD 14934 14948
11 UNUSED 9834834 9845595
12 UNUSED 9823885 9841920
13 UNUSED 9823820 9823964
14 UNUSED 9810856 9848675
15 UNUSED 9818236 9837365
16 UNUSED 9817272 9837431
COMM 1 ELEC DISP INT.100586 100620
COMM 2 RS232 SERIAL BD 14934 14948
COMM 3 SERIAL SAT BD 480450 480661
COMM 4 UNUSED 9832382 9833602
COMM 5 UNUSED 9816090 9844648
COMM 6 RS232 SERIAL BD 9816856 14904
I90200
NOV 30, 2023 12:44 PM
SOFTWARE REVISION LEVEL
VERSION 336.00
SOFTWARE# 346336-100-A
CREATED - 19.12.13.15.19
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
CSLD
BIR
FUEL MANAGER
ISD/APM
PLLD
0.10 AUTO
0.20 REPETITIV
WPLLD
0.10 AUTO
0.20 REPETITIV
I11100
NOV 30, 2023 12:44 PM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L14 ANNULAR DIESEL ANNULAR FUEL ALARM CLEAR 11-30-23 9:45AM
L13 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-30-23 9:45AM
L12 ANNULAR UNLEADED ANNULAR FUEL ALARM CLEAR 11-30-23 9:44AM
L 8 DISP PAN DISP. 15-16 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L 2 DISP PAN DISP. 3-4 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L 7 DISP PAN DISP. 13-14 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L 6 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L 1 DISP PAN DISP. 1-2 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L 5 DISP PAN DISP. 9-10 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L 4 DISP PAN DISP. 7-8 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L 3 DISP PAN DISP. 11-12 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L11 STP SUMP DIESEL SUMP SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L10 STP SUMP SUPREME SUMP SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L 9 STP SUMP UNLEADED SUMP SENSOR OUT ALARM CLEAR 11-30-23 9:42AM
L 2 DISP PAN DISP. 3-4 SENSOR OUT ALARM ALARM 11-30-23 9:42AM
L 8 DISP PAN DISP. 15-16 SENSOR OUT ALARM ALARM 11-30-23 9:42AM
L 7 DISP PAN DISP. 13-14 SENSOR OUT ALARM ALARM 11-30-23 9:42AM
L 1 DISP PAN DISP. 1-2 SENSOR OUT ALARM ALARM 11-30-23 9:42AM
L 6 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 11-30-23 9:42AM
L 5 DISP PAN DISP. 9-10 SENSOR OUT ALARM ALARM 11-30-23 9:42AM
L 4 DISP PAN DISP. 7-8 SENSOR OUT ALARM ALARM 11-30-23 9:42AM
L 3 DISP PAN DISP. 11-12 SENSOR OUT ALARM ALARM 11-30-23 9:42AM
L11 STP SUMP DIESEL SUMP SENSOR OUT ALARM ALARM 11-30-23 9:41AM
L10 STP SUMP SUPREME SUMP SENSOR OUT ALARM ALARM 11-30-23 9:41AM
L 9 STP SUMP UNLEADED SUMP SENSOR OUT ALARM ALARM 11-30-23 9:41AM
L13 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-30-23 9:38AM
L14 ANNULAR DIESEL ANNULAR FUEL ALARM ALARM 11-30-23 9:36AM
L12 ANNULAR UNLEADED ANNULAR FUEL ALARM ALARM 11-30-23 9:35AM
L 9 STP SUMP UNLEADED SUMP FUEL ALARM CLEAR 11-30-23 9:33AM
L 9 STP SUMP UNLEADED SUMP FUEL ALARM ALARM 11-30-23 9:33AM
L10 STP SUMP SUPREME SUMP FUEL ALARM CLEAR 11-30-23 9:33AM
L10 STP SUMP SUPREME SUMP FUEL ALARM ALARM 11-30-23 9:33AM
L11 STP SUMP DIESEL SUMP FUEL ALARM CLEAR 11-30-23 9:33AM
L11 STP SUMP DIESEL SUMP FUEL ALARM ALARM 11-30-23 9:33AM
L 1 DISP PAN DISP. 1-2 FUEL ALARM CLEAR 11-30-23 9:32AM
L 1 DISP PAN DISP. 1-2 FUEL ALARM ALARM 11-30-23 9:32AM
L 2 DISP PAN DISP. 3-4 FUEL ALARM CLEAR 11-30-23 9:32AM
L 2 DISP PAN DISP. 3-4 FUEL ALARM ALARM 11-30-23 9:31AM
L 6 DISP PAN DISP 5-6 FUEL ALARM CLEAR 11-30-23 9:31AM
L 6 DISP PAN DISP 5-6 FUEL ALARM ALARM 11-30-23 9:31AM
L 4 DISP PAN DISP. 7-8 FUEL ALARM CLEAR 11-30-23 9:30AM
L 4 DISP PAN DISP. 7-8 FUEL ALARM ALARM 11-30-23 9:30AM
L 5 DISP PAN DISP. 9-10 FUEL ALARM CLEAR 11-30-23 9:30AM
L 5 DISP PAN DISP. 9-10 FUEL ALARM ALARM 11-30-23 9:30AM
L 3 DISP PAN DISP. 11-12 FUEL ALARM CLEAR 11-30-23 9:29AM
L 3 DISP PAN DISP. 11-12 FUEL ALARM ALARM 11-30-23 9:29AM
L 7 DISP PAN DISP. 13-14 FUEL ALARM CLEAR 11-30-23 9:29AM
L 7 DISP PAN DISP. 13-14 FUEL ALARM ALARM 11-30-23 9:29AM
L 8 DISP PAN DISP. 15-16 FUEL ALARM CLEAR 11-30-23 9:28AM
L 8 DISP PAN DISP. 15-16 FUEL ALARM ALARM 11-30-23 9:28AM
I11200
NOV 30, 2023 12:45 PM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-30-23 9:05AM
SYSTEM PRINTER ERROR CLEAR 11-30-23 9:00AM
SYSTEM PAPER OUT CLEAR 11-30-23 9:00AM
SYSTEM PRINTER ERROR ALARM 11-30-23 8:57AM
SYSTEM PAPER OUT ALARM 11-30-23 8:57AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-28-23 9:26AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 9:22AM
OTHER ISD GROSS PRES WARN CLEAR 11-24-23 8:00AM
OTHER ISD GROSS PRES WARN ALARM 11-23-23 9:25AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-17-23 9:25AM
OTHER ISD GROSS PRES WARN CLEAR 11-17-23 8:41AM
OTHER ISD GROSS PRES WARN ALARM 11-15-23 9:26AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-13-23 9:58AM
SYSTEM PRINTER ERROR CLEAR 11-12-23 8:36AM
SYSTEM PAPER OUT CLEAR 11-12-23 8:36AM
SYSTEM PRINTER ERROR ALARM 11-12-23 8:36AM
SYSTEM PAPER OUT ALARM 11-12-23 8:36AM
SYSTEM PRINTER ERROR CLEAR 11-12-23 8:36AM
SYSTEM PAPER OUT CLEAR 11-12-23 8:36AM
SYSTEM PRINTER ERROR ALARM 11-12-23 8:35AM
SYSTEM PAPER OUT ALARM 11-12-23 8:35AM
SYSTEM PRINTER ERROR CLEAR 11-12-23 8:35AM
SYSTEM PAPER OUT CLEAR 11-12-23 8:35AM
SYSTEM PRINTER ERROR ALARM 11-12-23 12:00AM
SYSTEM PAPER OUT ALARM 11-12-23 12:00AM
h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-11-23 9:26AM
OTHER ISD GROSS PRES WARN CLEAR 11-08-23 9:49AM
OTHER ISD GROSS PRES WARN ALARM 11-08-23 9:25AM
OTHER ISD GROSS PRES WARN CLEAR 11-01-23 3:06PM
OTHER ISD GROSS PRES WARN ALARM 11-01-23 9:24AM
OTHER ISD GROSS PRES WARN CLEAR 10-26-23 8:33AM
OTHER ISD GROSS PRES WARN ALARM 10-25-23 9:24AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:04AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:04AM
SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM
SYSTEM PAPER OUT ALARM 10-25-23 8:03AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:03AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:03AM
SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM
SYSTEM PAPER OUT ALARM 10-25-23 8:03AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:03AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:03AM
SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM
SYSTEM PAPER OUT ALARM 10-25-23 8:03AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:02AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:02AM
SYSTEM PRINTER ERROR ALARM 10-25-23 8:02AM
SYSTEM PAPER OUT ALARM 10-25-23 8:02AM
SYSTEM PRINTER ERROR CLEAR 10-25-23 8:01AM
SYSTEM PAPER OUT CLEAR 10-25-23 8:01AM
I20600
NOV 30, 2023 12:45 PM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
TANK ALARM HISTORY
TANK 1 UNLEADED 87
OVERFILL ALARM OCT 28, 2021 10:52 AM
NOV 2, 2020 2:36 AM
PROBE OUT OCT 28, 2021 10:56 AM
OCT 28, 2021 10:42 AM
DEC 15, 2020 5:47 PM
LOW TEMP WARNING OCT 28, 2021 10:57 AM
OCT 28, 2021 10:43 AM
TANK 2 SUPREME 91
OVERFILL ALARM OCT 28, 2021 10:50 AM
PROBE OUT FEB 3, 2022 8:33 AM
OCT 28, 2021 10:54 AM
OCT 28, 2021 10:41 AM
DELIVERY NEEDED JUL 18, 2020 9:15 PM
LOW TEMP WARNING OCT 28, 2021 10:55 AM
OCT 28, 2021 10:42 AM
TANK 3 DIESEL
OVERFILL ALARM OCT 28, 2021 10:46 AM
PROBE OUT OCT 28, 2021 10:52 AM
OCT 28, 2021 10:40 AM
DELIVERY NEEDED NOV 23, 2022 6:41 AM
SEP 8, 2022 9:20 AM
JUN 23, 2022 3:08 PM
LOW TEMP WARNING OCT 28, 2021 10:54 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
NOV 30, 2023 12:46 PM
I30200
NOV 30, 2023 12:46 PM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP. 1-2
NOV 30, 2023 9:42 AM SENSOR OUT ALARM
NOV 30, 2023 9:32 AM FUEL ALARM
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
2 DISP. 3-4
NOV 30, 2023 9:42 AM SENSOR OUT ALARM
NOV 30, 2023 9:31 AM FUEL ALARM
NOV 21, 2023 10:26 AM SENSOR OUT ALARM
3 DISP. 11-12
NOV 30, 2023 9:42 AM SENSOR OUT ALARM
NOV 30, 2023 9:29 AM FUEL ALARM
NOV 21, 2023 9:38 AM FUEL ALARM
4 DISP. 7-8
NOV 30, 2023 9:42 AM SENSOR OUT ALARM
NOV 30, 2023 9:30 AM FUEL ALARM
NOV 21, 2023 9:41 AM FUEL ALARM
5 DISP. 9-10
NOV 30, 2023 9:42 AM SENSOR OUT ALARM
NOV 30, 2023 9:30 AM FUEL ALARM
NOV 21, 2023 10:51 AM FUEL ALARM
6 DISP 5-6
NOV 30, 2023 9:42 AM SENSOR OUT ALARM
NOV 30, 2023 9:31 AM FUEL ALARM
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
7 DISP. 13-14
NOV 30, 2023 9:42 AM SENSOR OUT ALARM
NOV 30, 2023 9:29 AM FUEL ALARM
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
8 DISP. 15-16
NOV 30, 2023 9:42 AM SENSOR OUT ALARM
NOV 30, 2023 9:28 AM FUEL ALARM
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
9 UNLEADED SUMP
NOV 30, 2023 9:41 AM SENSOR OUT ALARM
NOV 30, 2023 9:33 AM FUEL ALARM
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
10 SUPREME SUMP
NOV 30, 2023 9:41 AM SENSOR OUT ALARM
NOV 30, 2023 9:33 AM FUEL ALARM
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
11 DIESEL SUMP
NOV 30, 2023 9:41 AM SENSOR OUT ALARM
NOV 30, 2023 9:33 AM FUEL ALARM
NOV 21, 2023 10:25 AM SENSOR OUT ALARM
12 UNLEADED ANNULAR
NOV 30, 2023 9:35 AM FUEL ALARM
NOV 27, 2023 8:54 PM FUEL ALARM
NOV 21, 2023 10:17 AM FUEL ALARM
13 SUPREME ANNULAR
NOV 30, 2023 9:38 AM FUEL ALARM
NOV 21, 2023 10:20 AM FUEL ALARM
DEC 21, 2022 1:37 PM FUEL ALARM
14 DIESEL ANNULAR
NOV 30, 2023 9:36 AM FUEL ALARM
NOV 21, 2023 10:24 AM FUEL ALARM
SEP 19, 2023 12:50 PM FUEL ALARM
I31600
NOV 30, 2023 12:46 PM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 FM 1-2
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
2 FM 3-4
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
3 FM 5-6
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
4 FM 7-8
5 FM 9-10
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
6 FM 11-12
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
7 FM 13-14
DEC 13, 2019 8:39 AM COMMUNICATION ALARM
8 PRESSURE SENSOR
9 FM 15-16
I40200
NOV 30, 2023 12:46 PM
I40300
NOV 30, 2023 12:46 PM
I34200
NOV 30, 2023 12:46 PM
I34700
NOV 30, 2023 12:46 PM
IV0100
NOV 30, 2023 12:46 PM
286917 SPARKLING IMA
2301 H ST.
BAKERSFIELD,CA 93301
661-324-8455
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-11-29 09:28:25 A/L RATIO DEGRADATION FP 2 BLEND3 0.61
23-11-28 09:26:17 A/L RATIO DEGRADATION FP 2 BLEND3 0.61
23-11-23 09:25:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.34
23-11-23 09:25:10 A/L RATIO DEGRADATION FP 2 BLEND3 0.78
23-11-22 09:25:13 A/L RATIO DEGRADATION FP 2 BLEND3 0.78
23-11-21 09:25:05 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-11-20 09:25:24 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-11-19 09:25:13 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-11-18 09:25:12 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
23-11-17 09:25:41 A/L RATIO DEGRADATION FP 2 BLEND3 0.77
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-11-24 09:25:46 A/L RATIO DEGRADATION FP 2 BLEND3 0.78
22-08-05 09:25:27 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.46
22-07-22 09:27:21 A/L RATIO DEGRADATION FP15 BLEND3 1.67
21-03-12 09:26:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55
20-11-26 09:26:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.30
20-11-12 09:24:44 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55
20-05-04 09:26:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 24.17
20-04-07 09:26:07 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.27
19-08-03 10:03:31 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD
19-07-03 10:03:50 SENSOR OUT SELFTEST s 9
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-11-30 09:43:03 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-11-30 09:43:03 ISD STARTUP
23-11-30 09:42:44 ISD SHUTDOWN
23-11-30 09:05:13 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
23-11-24 14:06:04 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
23-11-24 14:05:54 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED
23-11-24 14:05:46 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-24 10:47:16 PUMPS MANUALLY RE-ENABLED
23-11-24 09:25:46 A/L RATIO GROSS DEGRADATION DISABLED FP 02 BLEND3
23-11-24 08:00:39 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED