HomeMy WebLinkAboutFMC 2023Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10123120 11-30-23 Sparkling Image Carwash 2301 H Street Bakersfield 93301 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Rockland Kirk 1073967 10241356 9-29-24 VMI #5255 10-3-24 GVR C32654 10-13-24 11-30-23 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder-Root TLS-350 336.00 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 DISP 1-2 L2 208 DISP 3-4 L3 208 DISP 11-12 L4 208 DISP 7-8 L5 208 DISP 9-10 L6 208 DISP 5-6 L7 208 DISP 13-14 L8 208 DISP 15-16 L9 208 UNLEADED SUMP L10 208 SUPREME SUMP L11 208 DIESEL SUMP L12 UNK UNLEADED ANNULAR L13 UNK SUPREME ANNULAR L14 UNK DIESEL ANNULAR Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V REGULAR UNLEADED T2 FX1V SUPREME UNLEADED T3 FX1DV DIESEL Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Sparkling Image Carwash2301 H StreetBakersfield101231201-23-4 5-68791DSL8791879187911-21-23-45-67-87-8ProductProductProductProductProductProductProductProductProductRockland Kirk APPENDIX C-10 7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB8715-16ProductProduct13-14918713-14ProductProduct11-12918711-12ProductProduct9-10DSL919-10ProductProduct9-1087DSL7-8ProductRockland Kirk APPENDIX C-10 7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'  6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBProduct15-16DSL9115-16ProductRockland Kirk■ ■ ■■ ■ ■ ■ ■ ■ ■ ■ Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10123120 11-30-23 Sparkling Image Carwash 2301 H Street Bakersfield 93301 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Rockland Kirk 1073967 10241356 9-29-24 FFS PHASE 1 EVR 1016693714 10-16-24 PEI RP 1200 SPILL BUCKETS 11-30-23 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1 87 PHILTITE 91 spill bucket and cap was replaced, 87 spill bucket drain was disassembled, cleaned out and reassembled. Both passed retests. T2 91 PHILTITE T3 DSL PHILTITE Responses Received: 200 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 NOV 30, 2023 9:01 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 87 7191 55.51 1.0 65.0 4809 2 SUPREME 91 4489 38.44 0.0 65.8 7511 3 DIESEL 1907 20.73 0.0 75.2 10093 I90500 NOV 30, 2023 9:02 AM SOFTWARE REVISION LEVEL VERSION 336.00 SOFTWARE# 346336-100-A CREATED - 19.12.13.15.19 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS CSLD BIR FUEL MANAGER ISD/APM PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETITIV I50500 NOV 30, 2023 9:02 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 NOV 30, 2023 9:02 AM SHIFT TIME 1 : 12:00 AM I50202 NOV 30, 2023 9:02 AM SHIFT TIME 2 : 6:00 AM I50203 NOV 30, 2023 9:02 AM SHIFT TIME 3 : 12:00 PM I50204 NOV 30, 2023 9:02 AM SHIFT TIME 4 : 6:00 PM I54600 NOV 30, 2023 9:02 AM TANK PER TST NEEDED WRN: DISABLED I54900 NOV 30, 2023 9:02 AM TANK ANN TST NEEDED WRN: DISABLED I55300 NOV 30, 2023 9:02 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 NOV 30, 2023 9:02 AM LINE PER TST NEEDED WRN: DISABLED I55900 NOV 30, 2023 9:02 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 NOV 30, 2023 9:02 AM PRINT TC VOLUMES ENABLED I50E00 NOV 30, 2023 9:02 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 NOV 30, 2023 9:02 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 NOV 30, 2023 9:02 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 NOV 30, 2023 9:02 AM DAYLIGHT SAVING TIME ENABLED OFF I51B00 NOV 30, 2023 9:02 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 NOV 30, 2023 9:02 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 NOV 30, 2023 9:02 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 NOV 30, 2023 9:02 AM TANK CHART SECURITY DISABLED I5BD00 NOV 30, 2023 9:02 AM CUSTOM ALARM LABELS DISABLED I56000 NOV 30, 2023 9:02 AM MASS/DENSITY DISABLED I88101 NOV 30, 2023 9:02 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 NOV 30, 2023 9:02 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 1200 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88103 NOV 30, 2023 9:02 AM PORT SETTINGS: COMM BOARD : 3 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88104 NOV 30, 2023 9:02 AM I88105 NOV 30, 2023 9:02 AM I88106 NOV 30, 2023 9:02 AM PORT SETTINGS: COMM BOARD : 6 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I52000 NOV 30, 2023 9:02 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 WEEKLY SUN 9:30 PM 2 WEEKLY SUN 9:30 PM 3 WEEKLY SUN 9:30 PM 4 WEEKLY SUN 9:30 PM 5 WEEKLY SUN 9:30 PM 6 WEEKLY SUN 9:30 PM 7 WEEKLY SUN 9:30 PM 8 VEEDER ROOT (FMS) WEEKLY SUN 9:30 PM I60100 NOV 30, 2023 9:02 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED 87 ON 2 SUPREME 91 ON 3 DIESEL ON 4 OFF I60200 NOV 30, 2023 9:02 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 87 2 SUPREME 91 3 DIESEL 4 I60300 NOV 30, 2023 9:02 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 87 1 2 SUPREME 91 2 3 DIESEL 3 4 4 I60900 NOV 30, 2023 9:02 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 87 0.000700 2 SUPREME 91 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 NOV 30, 2023 9:02 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 87 96.00 2 SUPREME 91 96.00 3 DIESEL 96.00 4 0.00 I60A00 NOV 30, 2023 9:02 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 87 1 PT 12000 2 SUPREME 91 1 PT 12000 3 DIESEL 1 PT 12000 4 1 PT 0 I60400 NOV 30, 2023 9:02 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 12000 2 SUPREME 91 12000 3 DIESEL 12000 4 0 I60500 NOV 30, 2023 9:03 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 12000 0 0 0 2 SUPREME 91 12000 0 0 0 3 DIESEL 12000 0 0 0 4 0 0 0 0 I60600 NOV 30, 2023 9:03 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 SUPREME 91 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 NOV 30, 2023 9:03 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED 87 NO 2 SUPREME 91 NO 3 DIESEL NO 4 NO I62F00 NOV 30, 2023 9:03 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 87 4.0 IN. 2 SUPREME 91 4.0 IN. 3 DIESEL 4.0 IN. I62700 NOV 30, 2023 9:03 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 87 2.0 2 SUPREME 91 2.0 3 DIESEL 2.0 I64200 NOV 30, 2023 9:03 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED 87 LOW 2 SUPREME 91 LOW 3 DIESEL LOW I62400 NOV 30, 2023 9:03 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 87 3.0 2 SUPREME 91 3.0 3 DIESEL 3.0 I62800 NOV 30, 2023 9:03 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 12000 2 SUPREME 91 12000 3 DIESEL 12000 4 0 I62300 NOV 30, 2023 9:03 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 10800 2 SUPREME 91 10800 3 DIESEL 10800 4 0 I62200 NOV 30, 2023 9:03 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 11400 2 SUPREME 91 11400 3 DIESEL 11400 4 0 I62900 NOV 30, 2023 9:03 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 1200 2 SUPREME 91 1200 3 DIESEL 1200 4 0 I62100 NOV 30, 2023 9:03 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 451 2 SUPREME 91 451 3 DIESEL 451 4 0 I62600 NOV 30, 2023 9:03 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 99 2 SUPREME 91 99 3 DIESEL 99 4 99 I62500 NOV 30, 2023 9:03 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 99 2 SUPREME 91 99 3 DIESEL 99 4 99 I60800 NOV 30, 2023 9:03 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 87 -3.00 2 SUPREME 91 -2.00 3 DIESEL 0.00 4 0.00 I60B00 NOV 30, 2023 9:03 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 NOV 30, 2023 9:03 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 87 0.00 2 SUPREME 91 0.00 3 DIESEL 0.00 4 0.00 I61200 NOV 30, 2023 9:03 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED 87 NONE NONE 2 SUPREME 91 NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 NOV 30, 2023 9:03 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 120 2 SUPREME 91 120 3 DIESEL 120 4 0 I62A00 NOV 30, 2023 9:04 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 120 2 SUPREME 91 120 3 DIESEL 120 4 0 I62C00 NOV 30, 2023 9:04 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED 87 STANDARD 2 SUPREME 91 STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 NOV 30, 2023 9:04 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED 87 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 SUPREME 91 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 NOV 30, 2023 9:04 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED 87 OFF OFF 2 SUPREME 91 OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 NOV 30, 2023 9:04 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED 87 OFF 2 SUPREME 91 OFF 3 DIESEL OFF 4 OFF I63200 NOV 30, 2023 9:04 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED 87 OFF 2 SUPREME 91 OFF 3 DIESEL OFF 4 OFF I61000 NOV 30, 2023 9:04 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 87 1 2 SUPREME 91 1 3 DIESEL 1 4 1 I63A00 NOV 30, 2023 9:04 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 87 10.00% 2 SUPREME 91 10.00% 3 DIESEL 10.00% 4 10.00% I61100 NOV 30, 2023 9:04 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK JUL 23, 2010 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 NOV 30, 2023 9:04 AM CSLD PROBABLITY OF DETECTION I61400 NOV 30, 2023 9:04 AM CSLD CLIMATE FACTOR I61600 NOV 30, 2023 9:04 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED 87 IMMEDIATE 2 SUPREME 91 IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 NOV 30, 2023 9:04 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED 87 DISABLED 2 SUPREME 91 DISABLED 3 DIESEL DISABLED 4 DISABLED I61B00 NOV 30, 2023 9:04 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 NOV 30, 2023 9:04 AM CSLD REPORT ONLY I62B00 NOV 30, 2023 9:04 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED 87 ??? 0, 0 2 SUPREME 91 ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 NOV 30, 2023 9:04 AM LEAK TEST REPORT FORMAT: NORMAL I63400 NOV 30, 2023 9:04 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 0 2 SUPREME 91 0 3 DIESEL 0 4 0 I63500 NOV 30, 2023 9:04 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 87 1 2 SUPREME 91 1 3 DIESEL 1 4 1 I63900 NOV 30, 2023 9:04 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED 87 END FACTOR: NONE 2 SUPREME 91 END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 NOV 30, 2023 9:04 AM I77700 NOV 30, 2023 9:04 AM I77800 NOV 30, 2023 9:04 AM I78C00 NOV 30, 2023 9:04 AM I78300 NOV 30, 2023 9:04 AM I78F00 NOV 30, 2023 9:04 AM I78700 NOV 30, 2023 9:04 AM I70200 NOV 30, 2023 9:04 AM LIQUID LABEL DEVICE LABEL 1 DISP. 1-2 2 DISP. 3-4 3 DISP. 11-12 4 DISP. 7-8 5 DISP. 9-10 6 DISP 5-6 7 DISP. 13-14 8 DISP. 15-16 9 UNLEADED SUMP 10 SUPREME SUMP 11 DIESEL SUMP 12 UNLEADED ANNULAR 13 SUPREME ANNULAR 14 DIESEL ANNULAR 15 UNLEADED ANN 16 17 UNL ANNULAR 18 19 UNL ANNULAR 20 21 22 23 24 BUBBA SENSOR I70300 NOV 30, 2023 9:05 AM LIQUID TYPE SENSOR LOCATION TYPE 1 DISP. 1-2 TRI-STATE (SINGLE FLOAT) 2 DISP. 3-4 TRI-STATE (SINGLE FLOAT) 3 DISP. 11-12 TRI-STATE (SINGLE FLOAT) 4 DISP. 7-8 TRI-STATE (SINGLE FLOAT) 5 DISP. 9-10 TRI-STATE (SINGLE FLOAT) 6 DISP 5-6 TRI-STATE (SINGLE FLOAT) 7 DISP. 13-14 TRI-STATE (SINGLE FLOAT) 8 DISP. 15-16 TRI-STATE (SINGLE FLOAT) 9 UNLEADED SUMP TRI-STATE (SINGLE FLOAT) 10 SUPREME SUMP TRI-STATE (SINGLE FLOAT) 11 DIESEL SUMP TRI-STATE (SINGLE FLOAT) 12 UNLEADED ANNULAR NORMALLY CLOSED 13 SUPREME ANNULAR NORMALLY CLOSED 14 DIESEL ANNULAR NORMALLY CLOSED 15 UNLEADED ANN NORMALLY CLOSED 16 TRI-STATE (SINGLE FLOAT) 17 UNL ANNULAR NORMALLY CLOSED 18 TRI-STATE (SINGLE FLOAT) 19 UNL ANNULAR NORMALLY CLOSED 20 TRI-STATE (SINGLE FLOAT) 21 TRI-STATE (SINGLE FLOAT) 22 TRI-STATE (SINGLE FLOAT) 23 TRI-STATE (SINGLE FLOAT) 24 BUBBA SENSOR NORMALLY CLOSED I70400 NOV 30, 2023 9:05 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 DISP. 1-2 DISPENSER PAN 2 DISP. 3-4 DISPENSER PAN 3 DISP. 11-12 DISPENSER PAN 4 DISP. 7-8 DISPENSER PAN 5 DISP. 9-10 DISPENSER PAN 6 DISP 5-6 DISPENSER PAN 7 DISP. 13-14 DISPENSER PAN 8 DISP. 15-16 DISPENSER PAN 9 UNLEADED SUMP STP SUMP 10 SUPREME SUMP STP SUMP 11 DIESEL SUMP STP SUMP 12 UNLEADED ANNULAR ANNULAR SPACE 13 SUPREME ANNULAR ANNULAR SPACE 14 DIESEL ANNULAR ANNULAR SPACE 15 UNLEADED ANN ANNULAR SPACE 16 OTHER SENSORS 17 UNL ANNULAR ANNULAR SPACE 18 OTHER SENSORS 19 UNL ANNULAR ANNULAR SPACE 20 OTHER SENSORS 21 OTHER SENSORS 22 OTHER SENSORS 23 OTHER SENSORS 24 BUBBA SENSOR OTHER SENSORS I74200 NOV 30, 2023 9:05 AM I74300 NOV 30, 2023 9:05 AM I74400 NOV 30, 2023 9:05 AM I74700 NOV 30, 2023 9:05 AM I74800 NOV 30, 2023 9:05 AM I74900 NOV 30, 2023 9:05 AM I7BC00 NOV 30, 2023 9:05 AM I80200 NOV 30, 2023 9:05 AM I80300 NOV 30, 2023 9:05 AM I80400 NOV 30, 2023 9:05 AM I80700 NOV 30, 2023 9:05 AM RELAY LABEL DEVICE LABEL 1 UNLEADED 87 2 SUPREME 3 DIESEL 4 OVERFILL ALARM 5 REMOTE ALARMS 6 REMOTE ALARM 7 8 I80900 NOV 30, 2023 9:05 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNLEADED 87 NORMALLY CLOSED 2 SUPREME NORMALLY CLOSED 3 DIESEL NORMALLY CLOSED 4 OVERFILL ALARM NORMALLY OPEN 5 REMOTE ALARMS NORMALLY CLOSED 6 REMOTE ALARM NORMALLY CLOSED 7 NORMALLY OPEN 8 NORMALLY OPEN I80B00 NOV 30, 2023 9:05 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNLEADED 87 1 2 SUPREME 2 3 DIESEL 3 4 OVERFILL ALARM NONE 5 REMOTE ALARMS NONE 6 REMOTE ALARM NONE 7 NONE 8 NONE I80A00 NOV 30, 2023 9:05 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNLEADED 87 STANDARD 2 SUPREME STANDARD 3 DIESEL STANDARD 4 OVERFILL ALARM STANDARD 5 REMOTE ALARMS STANDARD 6 REMOTE ALARM STANDARD 7 STANDARD 8 STANDARD I80C00 NOV 30, 2023 9:05 AM I80800 NOV 30, 2023 9:05 AM RELAY SETUP REPORT R 1:UNLEADED 87 TYPE: STANDARD NORMALLY CLOSED TANK #: 1 IN-TANK ALARMS T 1:LEAK ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L12:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:SUPREME TYPE: STANDARD NORMALLY CLOSED TANK #: 2 IN-TANK ALARMS T 2:LEAK ALARM T 2:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L10:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L10:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L10:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DIESEL TYPE: STANDARD NORMALLY CLOSED TANK #: 3 IN-TANK ALARMS T 3:LEAK ALARM T 3:LOW PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 8:FUEL ALARM L11:FUEL ALARM L 1:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 1:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 8:SHORT ALARM L11:SHORT ALARM R 4:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM R 5:REMOTE ALARMS TYPE: STANDARD NORMALLY CLOSED TANK #: NONE IN-TANK ALARMS ALL:LEAK ALARM ALL:HIGH WATER ALARM ALL:OVERFILL ALARM ALL:LOW PRODUCT ALARM ALL:SUDDEN LOSS ALARM ALL:HIGH PRODUCT ALARM ALL:INVALID FUEL LEVEL ALL:PROBE OUT ALL:HIGH WATER WARNING ALL:DELIVERY NEEDED ALL:MAX PRODUCT ALARM ALL:GROSS TEST FAIL ALL:PERIODIC TEST FAIL ALL:ANNUAL TEST FAIL ALL:PER TST NEEDED WRN LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L16:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L15:SENSOR OUT ALARM L16:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM L15:SHORT ALARM L16:SHORT ALARM SMARTSENSOR ALARMS ALL:SETUP DATA WARNING ALL:COMMUNICATION ALARM ALL:SENSOR FAULT ALARM ALL:SENSOR FAULT WARN ISD SITE ALARMS ISD STAGE I WARN ISD GROSS PRES WARN ISD GROSS PRES FAIL ISD DEGRD PRES WARN ISD DEGRD PRES FAIL ISD VAPOR LEAK WARN ISD VAPOR LEAK FAIL ISD VP PRES WARN ISD VP PRES FAIL ISD VP STATUS WARN ISD VP STATUS FAIL MISSING RELAY SETUP MISSING HOSE SETUP MISSING TANK SETUP MISS VAPOR FLOW MTR MISS VAPOR PRES SEN MISSING VP INPUT ISD SETUP WARN ISD SETUP FAIL ISD SENSOR OUT WARN ISD SENSOR OUT FAIL ISD HOSE ALARMS ALL:GROSS COLLECT WARN ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT WARN ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT WARN ALL:FLOW COLLECT FAIL ALL:AIRFLOW MTR SETUP VAPOR FLW MTR ALMS ALL:CHK VAPOR FLOW MTR R 6:REMOTE ALARM TYPE: STANDARD NORMALLY CLOSED TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L15:FUEL ALARM L16:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L15:SENSOR OUT ALARM L16:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM L15:SHORT ALARM L16:SHORT ALARM SMARTSENSOR ALARMS ALL:COMMUNICATION ALARM ISD SITE ALARMS ISD STAGE I WARN ISD GROSS PRES WARN ISD GROSS PRES FAIL ISD DEGRD PRES WARN ISD DEGRD PRES FAIL ISD VAPOR LEAK WARN ISD VAPOR LEAK FAIL ISD VP PRES WARN ISD VP PRES FAIL ISD VP STATUS WARN ISD VP STATUS FAIL MISSING RELAY SETUP MISSING HOSE SETUP ISD SENSOR OUT WARN ISD SENSOR OUT FAIL ISD HOSE ALARMS ALL:GROSS COLLECT WARN ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT WARN ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT WARN ALL:FLOW COLLECT FAIL ALL:AIRFLOW MTR SETUP VAPOR FLW MTR ALMS ALL:CHK VAPOR FLOW MTR R 7: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 8: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 NOV 30, 2023 9:07 AM EDIM:1 VR:349643-001-B TD:97.10.27.11.25 I79100 NOV 30, 2023 9:07 AM I72300 NOV 30, 2023 9:07 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 FM 1-2 AIR FLOW METER 02 FM 3-4 AIR FLOW METER 03 FM 5-6 AIR FLOW METER 04 FM 7-8 AIR FLOW METER 05 FM 9-10 AIR FLOW METER 06 FM 11-12 AIR FLOW METER 07 FM 13-14 AIR FLOW METER 08 PRESSURE SENSOR VAPOR PRESSURE 09 FM 15-16 AIR FLOW METER 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 NOV 30, 2023 9:08 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 NOV 30, 2023 9:08 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 NOV 30, 2023 9:08 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 VAPOR PROCESSOR TYPE NONE IV4700 NOV 30, 2023 9:08 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 ASSESSMENT TIME START TIME: 9:22 AM TIME DELAY MINUTES: 1 IV5200 NOV 30, 2023 9:08 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 ACCEPT HIGH ORVR: YES IV4A00 NOV 30, 2023 9:08 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 06 BLEND3 02 02 02 01 06 BLEND3 03 03 03 02 06 BLEND3 04 04 04 02 06 BLEND3 05 05 05 03 06 BLEND3 06 06 06 03 06 BLEND3 07 07 07 04 06 BLEND3 08 08 08 04 06 BLEND3 09 09 09 05 06 BLEND3 10 16 10 05 06 BLEND3 11 17 11 06 06 BLEND3 12 18 12 06 06 BLEND3 13 19 13 07 06 BLEND3 14 20 14 07 06 BLEND3 15 21 15 08 06 BLEND3 16 22 16 08 06 BLEND3 IV4B00 NOV 30, 2023 9:08 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 01/01 02/01 09/01 xx/xx 02 01 01/02 09/02 02/02 xx/xx 03 02 01/03 09/03 02/03 xx/xx 04 02 01/04 09/04 02/04 xx/xx 05 03 01/05 09/05 02/05 xx/xx 06 03 01/06 09/06 02/06 xx/xx 07 04 01/07 09/07 02/07 xx/xx 08 04 01/08 09/08 02/08 xx/xx 09 05 01/09 09/09 02/09 xx/xx 16 05 01/10 09/10 02/10 xx/xx 17 06 01/11 09/11 02/11 xx/xx 18 06 01/12 09/12 02/12 xx/xx 19 07 01/13 09/13 02/13 xx/xx 20 07 01/14 09/14 02/14 xx/xx 21 08 01/15 09/15 02/15 xx/xx 22 08 01/16 09/16 02/16 xx/xx IV4900 NOV 30, 2023 9:08 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 NOV 30, 2023 9:08 AM ISD VERSION: 01.06 Responses Received: I20600 NOV 30, 2023 8:41 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 TANK ALARM HISTORY TANK 1 UNLEADED 87 OVERFILL ALARM OCT 28, 2021 10:52 AM NOV 2, 2020 2:36 AM PROBE OUT OCT 28, 2021 10:56 AM OCT 28, 2021 10:42 AM DEC 15, 2020 5:47 PM LOW TEMP WARNING OCT 28, 2021 10:57 AM OCT 28, 2021 10:43 AM TANK 2 SUPREME 91 OVERFILL ALARM OCT 28, 2021 10:50 AM PROBE OUT FEB 3, 2022 8:33 AM OCT 28, 2021 10:54 AM OCT 28, 2021 10:41 AM DELIVERY NEEDED JUL 18, 2020 9:15 PM LOW TEMP WARNING OCT 28, 2021 10:55 AM OCT 28, 2021 10:42 AM TANK 3 DIESEL OVERFILL ALARM OCT 28, 2021 10:46 AM PROBE OUT OCT 28, 2021 10:52 AM OCT 28, 2021 10:40 AM DELIVERY NEEDED NOV 23, 2022 6:41 AM SEP 8, 2022 9:20 AM JUN 23, 2022 3:08 PM LOW TEMP WARNING OCT 28, 2021 10:54 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 I10200 NOV 30, 2023 8:55 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9852359 9915123 2 4 PROBE / G.T. 163465 163643 3 8SMARTSENSOR BD 39589 39625 4 7SMARTSENSOR BD 507789 508533 5 INTERSTITIAL BD 201480 201920 6 INTERSTITIAL BD 202096 202397 7 INTERSTITIAL BD 200750 201035 8 UNUSED 9828973 9896622 9 RELAY BOARD 15000 15007 10 RELAY BOARD 14934 14963 11 UNUSED 9834834 9898864 12 UNUSED 9823885 9895355 13 UNUSED 9823820 9881278 14 UNUSED 9810856 9886552 15 UNUSED 9818236 9886748 16 UNUSED 9817272 9886987 COMM 1 ELEC DISP INT. 100586 100792 COMM 2 RS232 SERIAL BD 14934 15007 COMM 3 SERIAL SAT BD 480450 481201 COMM 4 UNUSED 9832382 9891368 COMM 5 UNUSED 9816090 9889973 COMM 6 RS232 SERIAL BD 9816856 14920 I90200 NOV 30, 2023 8:56 AM SOFTWARE REVISION LEVEL VERSION 336.00 SOFTWARE# 346336-100-A CREATED - 19.12.13.15.19 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS CSLD BIR FUEL MANAGER ISD/APM PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETITIV I11100 NOV 30, 2023 8:56 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L12 ANNULAR UNLEADED ANNULAR FUEL ALARM CLEAR 11-30-23 8:54AM L12 ANNULAR UNLEADED ANNULAR FUEL ALARM ALARM 11-27-23 8:54PM h 2 OTHER FP2: BLEND3 DEGRD COLLECT FAIL CLEAR 11-24-23 2:06PM h 2 OTHER FP2: BLEND3 DEGRD COLLECT FAIL ALARM 11-24-23 9:25AM L14 ANNULAR DIESEL ANNULAR FUEL ALARM CLEAR 11-21-23 11:50AM L13 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-21-23 11:49AM L12 ANNULAR UNLEADED ANNULAR FUEL ALARM CLEAR 11-21-23 11:48AM L 5 DISP PAN DISP. 9-10 FUEL ALARM CLEAR 11-21-23 10:55AM L 5 DISP PAN DISP. 9-10 FUEL ALARM ALARM 11-21-23 10:51AM L 6 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM L 5 DISP PAN DISP. 9-10 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM L11 STP SUMP DIESEL SUMP SENSOR OUT ALARM CLEAR 11-21-23 10:26AM L10 STP SUMP SUPREME SUMP SENSOR OUT ALARM CLEAR 11-21-23 10:26AM L 9 STP SUMP UNLEADED SUMP SENSOR OUT ALARM CLEAR 11-21-23 10:26AM L 2 DISP PAN DISP. 3-4 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM L 1 DISP PAN DISP. 1-2 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM L 8 DISP PAN DISP. 15-16 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM L 7 DISP PAN DISP. 13-14 SENSOR OUT ALARM CLEAR 11-21-23 10:26AM L 2 DISP PAN DISP. 3-4 SENSOR OUT ALARM ALARM 11-21-23 10:26AM L 1 DISP PAN DISP. 1-2 SENSOR OUT ALARM ALARM 11-21-23 10:25AM L 8 DISP PAN DISP. 15-16 SENSOR OUT ALARM ALARM 11-21-23 10:25AM L 7 DISP PAN DISP. 13-14 SENSOR OUT ALARM ALARM 11-21-23 10:25AM L 6 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 11-21-23 10:25AM L 5 DISP PAN DISP. 9-10 SENSOR OUT ALARM ALARM 11-21-23 10:25AM L11 STP SUMP DIESEL SUMP SENSOR OUT ALARM ALARM 11-21-23 10:25AM L10 STP SUMP SUPREME SUMP SENSOR OUT ALARM ALARM 11-21-23 10:25AM L 9 STP SUMP UNLEADED SUMP SENSOR OUT ALARM ALARM 11-21-23 10:25AM L14 ANNULAR DIESEL ANNULAR FUEL ALARM ALARM 11-21-23 10:24AM L13 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-21-23 10:20AM L12 ANNULAR UNLEADED ANNULAR FUEL ALARM ALARM 11-21-23 10:17AM L11 STP SUMP DIESEL SUMP FUEL ALARM CLEAR 11-21-23 9:43AM L11 STP SUMP DIESEL SUMP FUEL ALARM ALARM 11-21-23 9:43AM L10 STP SUMP SUPREME SUMP FUEL ALARM CLEAR 11-21-23 9:43AM L10 STP SUMP SUPREME SUMP FUEL ALARM ALARM 11-21-23 9:42AM L 9 STP SUMP UNLEADED SUMP FUEL ALARM CLEAR 11-21-23 9:42AM L 9 STP SUMP UNLEADED SUMP FUEL ALARM ALARM 11-21-23 9:42AM L 4 DISP PAN DISP. 7-8 FUEL ALARM CLEAR 11-21-23 9:42AM L 4 DISP PAN DISP. 7-8 FUEL ALARM ALARM 11-21-23 9:41AM L 6 DISP PAN DISP 5-6 FUEL ALARM CLEAR 11-21-23 9:41AM L 6 DISP PAN DISP 5-6 FUEL ALARM ALARM 11-21-23 9:41AM L 2 DISP PAN DISP. 3-4 FUEL ALARM CLEAR 11-21-23 9:41AM L 2 DISP PAN DISP. 3-4 FUEL ALARM ALARM 11-21-23 9:40AM L 1 DISP PAN DISP. 1-2 FUEL ALARM CLEAR 11-21-23 9:40AM L 1 DISP PAN DISP. 1-2 FUEL ALARM ALARM 11-21-23 9:40AM L 8 DISP PAN DISP. 15-16 FUEL ALARM CLEAR 11-21-23 9:39AM L 8 DISP PAN DISP. 15-16 FUEL ALARM ALARM 11-21-23 9:39AM L 7 DISP PAN DISP. 13-14 FUEL ALARM CLEAR 11-21-23 9:39AM L 7 DISP PAN DISP. 13-14 FUEL ALARM ALARM 11-21-23 9:38AM L 3 DISP PAN DISP. 11-12 FUEL ALARM CLEAR 11-21-23 9:38AM L 3 DISP PAN DISP. 11-12 FUEL ALARM ALARM 11-21-23 9:38AM I11200 NOV 30, 2023 8:56 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-28-23 9:26AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 9:22AM OTHER ISD GROSS PRES WARN CLEAR 11-24-23 8:00AM OTHER ISD GROSS PRES WARN ALARM 11-23-23 9:25AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-17-23 9:25AM OTHER ISD GROSS PRES WARN CLEAR 11-17-23 8:41AM OTHER ISD GROSS PRES WARN ALARM 11-15-23 9:26AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-13-23 9:58AM SYSTEM PRINTER ERROR CLEAR 11-12-23 8:36AM SYSTEM PAPER OUT CLEAR 11-12-23 8:36AM SYSTEM PRINTER ERROR ALARM 11-12-23 8:36AM SYSTEM PAPER OUT ALARM 11-12-23 8:36AM SYSTEM PRINTER ERROR CLEAR 11-12-23 8:36AM SYSTEM PAPER OUT CLEAR 11-12-23 8:36AM SYSTEM PRINTER ERROR ALARM 11-12-23 8:35AM SYSTEM PAPER OUT ALARM 11-12-23 8:35AM SYSTEM PRINTER ERROR CLEAR 11-12-23 8:35AM SYSTEM PAPER OUT CLEAR 11-12-23 8:35AM SYSTEM PRINTER ERROR ALARM 11-12-23 12:00AM SYSTEM PAPER OUT ALARM 11-12-23 12:00AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-11-23 9:26AM OTHER ISD GROSS PRES WARN CLEAR 11-08-23 9:49AM OTHER ISD GROSS PRES WARN ALARM 11-08-23 9:25AM OTHER ISD GROSS PRES WARN CLEAR 11-01-23 3:06PM OTHER ISD GROSS PRES WARN ALARM 11-01-23 9:24AM OTHER ISD GROSS PRES WARN CLEAR 10-26-23 8:33AM OTHER ISD GROSS PRES WARN ALARM 10-25-23 9:24AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:04AM SYSTEM PAPER OUT CLEAR 10-25-23 8:04AM SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM SYSTEM PAPER OUT ALARM 10-25-23 8:03AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:03AM SYSTEM PAPER OUT CLEAR 10-25-23 8:03AM SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM SYSTEM PAPER OUT ALARM 10-25-23 8:03AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:03AM SYSTEM PAPER OUT CLEAR 10-25-23 8:03AM SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM SYSTEM PAPER OUT ALARM 10-25-23 8:03AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:02AM SYSTEM PAPER OUT CLEAR 10-25-23 8:02AM SYSTEM PRINTER ERROR ALARM 10-25-23 8:02AM SYSTEM PAPER OUT ALARM 10-25-23 8:02AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:01AM SYSTEM PAPER OUT CLEAR 10-25-23 8:01AM SYSTEM PRINTER ERROR ALARM 10-24-23 12:00PM SYSTEM PAPER OUT ALARM 10-24-23 12:00PM OTHER ISD GROSS PRES WARN CLEAR 10-18-23 2:51PM OTHER ISD GROSS PRES WARN ALARM 10-18-23 9:24AM OTHER ISD GROSS PRES WARN CLEAR 10-11-23 9:26AM I20600 NOV 30, 2023 8:57 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 TANK ALARM HISTORY TANK 1 UNLEADED 87 OVERFILL ALARM OCT 28, 2021 10:52 AM NOV 2, 2020 2:36 AM PROBE OUT OCT 28, 2021 10:56 AM OCT 28, 2021 10:42 AM DEC 15, 2020 5:47 PM LOW TEMP WARNING OCT 28, 2021 10:57 AM OCT 28, 2021 10:43 AM TANK 2 SUPREME 91 OVERFILL ALARM OCT 28, 2021 10:50 AM PROBE OUT FEB 3, 2022 8:33 AM OCT 28, 2021 10:54 AM OCT 28, 2021 10:41 AM DELIVERY NEEDED JUL 18, 2020 9:15 PM LOW TEMP WARNING OCT 28, 2021 10:55 AM OCT 28, 2021 10:42 AM TANK 3 DIESEL OVERFILL ALARM OCT 28, 2021 10:46 AM PROBE OUT OCT 28, 2021 10:52 AM OCT 28, 2021 10:40 AM DELIVERY NEEDED NOV 23, 2022 6:41 AM SEP 8, 2022 9:20 AM JUN 23, 2022 3:08 PM LOW TEMP WARNING OCT 28, 2021 10:54 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 NOV 30, 2023 8:57 AM I30200 NOV 30, 2023 8:57 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DISP. 1-2 NOV 21, 2023 10:25 AM SENSOR OUT ALARM NOV 21, 2023 9:40 AM FUEL ALARM DEC 21, 2022 10:16 AM SENSOR OUT ALARM 2 DISP. 3-4 NOV 21, 2023 10:26 AM SENSOR OUT ALARM NOV 21, 2023 9:40 AM FUEL ALARM DEC 21, 2022 10:16 AM SENSOR OUT ALARM 3 DISP. 11-12 NOV 21, 2023 9:38 AM FUEL ALARM DEC 21, 2022 10:16 AM SENSOR OUT ALARM DEC 21, 2022 10:10 AM FUEL ALARM 4 DISP. 7-8 NOV 21, 2023 9:41 AM FUEL ALARM DEC 21, 2022 10:16 AM SENSOR OUT ALARM DEC 21, 2022 10:09 AM FUEL ALARM 5 DISP. 9-10 NOV 21, 2023 10:51 AM FUEL ALARM NOV 21, 2023 10:25 AM SENSOR OUT ALARM NOV 21, 2023 9:37 AM FUEL ALARM 6 DISP 5-6 NOV 21, 2023 10:25 AM SENSOR OUT ALARM NOV 21, 2023 9:41 AM FUEL ALARM DEC 21, 2022 10:16 AM SENSOR OUT ALARM 7 DISP. 13-14 NOV 21, 2023 10:25 AM SENSOR OUT ALARM NOV 21, 2023 9:38 AM FUEL ALARM DEC 21, 2022 10:16 AM SENSOR OUT ALARM 8 DISP. 15-16 NOV 21, 2023 10:25 AM SENSOR OUT ALARM NOV 21, 2023 9:39 AM FUEL ALARM DEC 21, 2022 10:11 AM FUEL ALARM 9 UNLEADED SUMP NOV 21, 2023 10:25 AM SENSOR OUT ALARM NOV 21, 2023 9:42 AM FUEL ALARM DEC 21, 2022 10:16 AM SENSOR OUT ALARM 10 SUPREME SUMP NOV 21, 2023 10:25 AM SENSOR OUT ALARM NOV 21, 2023 9:42 AM FUEL ALARM DEC 21, 2022 10:16 AM SENSOR OUT ALARM 11 DIESEL SUMP NOV 21, 2023 10:25 AM SENSOR OUT ALARM NOV 21, 2023 9:43 AM FUEL ALARM DEC 21, 2022 10:16 AM SENSOR OUT ALARM 12 UNLEADED ANNULAR NOV 27, 2023 8:54 PM FUEL ALARM NOV 21, 2023 10:17 AM FUEL ALARM DEC 21, 2022 10:30 AM FUEL ALARM 13 SUPREME ANNULAR NOV 21, 2023 10:20 AM FUEL ALARM DEC 21, 2022 1:37 PM FUEL ALARM DEC 21, 2022 10:29 AM FUEL ALARM 14 DIESEL ANNULAR NOV 21, 2023 10:24 AM FUEL ALARM SEP 19, 2023 12:50 PM FUEL ALARM DEC 21, 2022 10:26 AM FUEL ALARM I31600 NOV 30, 2023 8:58 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 FM 1-2 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 2 FM 3-4 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 3 FM 5-6 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 4 FM 7-8 5 FM 9-10 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 6 FM 11-12 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 7 FM 13-14 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 8 PRESSURE SENSOR 9 FM 15-16 I40200 NOV 30, 2023 8:58 AM I40300 NOV 30, 2023 8:58 AM I34200 NOV 30, 2023 8:58 AM I34700 NOV 30, 2023 8:58 AM IV0100 NOV 30, 2023 8:58 AM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.06 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :WARN EVR VAPOR CONTAINMENT :NOTEST ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-11-29 09:28:25 A/L RATIO DEGRADATION FP 2 BLEND3 0.61 23-11-28 09:26:17 A/L RATIO DEGRADATION FP 2 BLEND3 0.61 23-11-23 09:25:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.34 23-11-23 09:25:10 A/L RATIO DEGRADATION FP 2 BLEND3 0.78 23-11-22 09:25:13 A/L RATIO DEGRADATION FP 2 BLEND3 0.78 23-11-21 09:25:05 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 23-11-20 09:25:24 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 23-11-19 09:25:13 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 23-11-18 09:25:12 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 23-11-17 09:25:41 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-11-24 09:25:46 A/L RATIO DEGRADATION FP 2 BLEND3 0.78 22-08-05 09:25:27 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.46 22-07-22 09:27:21 A/L RATIO DEGRADATION FP15 BLEND3 1.67 21-03-12 09:26:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55 20-11-26 09:26:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.30 20-11-12 09:24:44 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55 20-05-04 09:26:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 24.17 20-04-07 09:26:07 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.27 19-08-03 10:03:31 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 19-07-03 10:03:50 SENSOR OUT SELFTEST s 9 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-11-24 14:06:04 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED 23-11-24 14:05:54 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED 23-11-24 14:05:46 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-24 10:47:16 PUMPS MANUALLY RE-ENABLED 23-11-24 09:25:46 A/L RATIO GROSS DEGRADATION DISABLED FP 02 BLEND3 23-11-24 08:00:39 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-22 09:25:13 READINESS ISD:PP EVR:PP ISD & EVR READY 23-11-21 10:27:18 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-11-21 10:27:18 ISD STARTUP 23-11-21 10:27:03 ISD SHUTDOWN Responses Received: I10200 NOV 30, 2023 12:44 PM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9852359 9859602 2 4 PROBE / G.T.163465 163426 3 8SMARTSENSOR BD 39589 39507 4 7SMARTSENSOR BD 507789 507019 5 INTERSTITIAL BD 201480 201581 6 INTERSTITIAL BD 202096 201856 7 INTERSTITIAL BD 200750 200527 8 UNUSED 9828973 9840106 9 RELAY BOARD 15000 14970 10 RELAY BOARD 14934 14948 11 UNUSED 9834834 9845595 12 UNUSED 9823885 9841920 13 UNUSED 9823820 9823964 14 UNUSED 9810856 9848675 15 UNUSED 9818236 9837365 16 UNUSED 9817272 9837431 COMM 1 ELEC DISP INT.100586 100620 COMM 2 RS232 SERIAL BD 14934 14948 COMM 3 SERIAL SAT BD 480450 480661 COMM 4 UNUSED 9832382 9833602 COMM 5 UNUSED 9816090 9844648 COMM 6 RS232 SERIAL BD 9816856 14904 I90200 NOV 30, 2023 12:44 PM SOFTWARE REVISION LEVEL VERSION 336.00 SOFTWARE# 346336-100-A CREATED - 19.12.13.15.19 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS CSLD BIR FUEL MANAGER ISD/APM PLLD 0.10 AUTO 0.20 REPETITIV WPLLD 0.10 AUTO 0.20 REPETITIV I11100 NOV 30, 2023 12:44 PM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L14 ANNULAR DIESEL ANNULAR FUEL ALARM CLEAR 11-30-23 9:45AM L13 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-30-23 9:45AM L12 ANNULAR UNLEADED ANNULAR FUEL ALARM CLEAR 11-30-23 9:44AM L 8 DISP PAN DISP. 15-16 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L 2 DISP PAN DISP. 3-4 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L 7 DISP PAN DISP. 13-14 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L 6 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L 1 DISP PAN DISP. 1-2 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L 5 DISP PAN DISP. 9-10 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L 4 DISP PAN DISP. 7-8 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L 3 DISP PAN DISP. 11-12 SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L11 STP SUMP DIESEL SUMP SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L10 STP SUMP SUPREME SUMP SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L 9 STP SUMP UNLEADED SUMP SENSOR OUT ALARM CLEAR 11-30-23 9:42AM L 2 DISP PAN DISP. 3-4 SENSOR OUT ALARM ALARM 11-30-23 9:42AM L 8 DISP PAN DISP. 15-16 SENSOR OUT ALARM ALARM 11-30-23 9:42AM L 7 DISP PAN DISP. 13-14 SENSOR OUT ALARM ALARM 11-30-23 9:42AM L 1 DISP PAN DISP. 1-2 SENSOR OUT ALARM ALARM 11-30-23 9:42AM L 6 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 11-30-23 9:42AM L 5 DISP PAN DISP. 9-10 SENSOR OUT ALARM ALARM 11-30-23 9:42AM L 4 DISP PAN DISP. 7-8 SENSOR OUT ALARM ALARM 11-30-23 9:42AM L 3 DISP PAN DISP. 11-12 SENSOR OUT ALARM ALARM 11-30-23 9:42AM L11 STP SUMP DIESEL SUMP SENSOR OUT ALARM ALARM 11-30-23 9:41AM L10 STP SUMP SUPREME SUMP SENSOR OUT ALARM ALARM 11-30-23 9:41AM L 9 STP SUMP UNLEADED SUMP SENSOR OUT ALARM ALARM 11-30-23 9:41AM L13 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-30-23 9:38AM L14 ANNULAR DIESEL ANNULAR FUEL ALARM ALARM 11-30-23 9:36AM L12 ANNULAR UNLEADED ANNULAR FUEL ALARM ALARM 11-30-23 9:35AM L 9 STP SUMP UNLEADED SUMP FUEL ALARM CLEAR 11-30-23 9:33AM L 9 STP SUMP UNLEADED SUMP FUEL ALARM ALARM 11-30-23 9:33AM L10 STP SUMP SUPREME SUMP FUEL ALARM CLEAR 11-30-23 9:33AM L10 STP SUMP SUPREME SUMP FUEL ALARM ALARM 11-30-23 9:33AM L11 STP SUMP DIESEL SUMP FUEL ALARM CLEAR 11-30-23 9:33AM L11 STP SUMP DIESEL SUMP FUEL ALARM ALARM 11-30-23 9:33AM L 1 DISP PAN DISP. 1-2 FUEL ALARM CLEAR 11-30-23 9:32AM L 1 DISP PAN DISP. 1-2 FUEL ALARM ALARM 11-30-23 9:32AM L 2 DISP PAN DISP. 3-4 FUEL ALARM CLEAR 11-30-23 9:32AM L 2 DISP PAN DISP. 3-4 FUEL ALARM ALARM 11-30-23 9:31AM L 6 DISP PAN DISP 5-6 FUEL ALARM CLEAR 11-30-23 9:31AM L 6 DISP PAN DISP 5-6 FUEL ALARM ALARM 11-30-23 9:31AM L 4 DISP PAN DISP. 7-8 FUEL ALARM CLEAR 11-30-23 9:30AM L 4 DISP PAN DISP. 7-8 FUEL ALARM ALARM 11-30-23 9:30AM L 5 DISP PAN DISP. 9-10 FUEL ALARM CLEAR 11-30-23 9:30AM L 5 DISP PAN DISP. 9-10 FUEL ALARM ALARM 11-30-23 9:30AM L 3 DISP PAN DISP. 11-12 FUEL ALARM CLEAR 11-30-23 9:29AM L 3 DISP PAN DISP. 11-12 FUEL ALARM ALARM 11-30-23 9:29AM L 7 DISP PAN DISP. 13-14 FUEL ALARM CLEAR 11-30-23 9:29AM L 7 DISP PAN DISP. 13-14 FUEL ALARM ALARM 11-30-23 9:29AM L 8 DISP PAN DISP. 15-16 FUEL ALARM CLEAR 11-30-23 9:28AM L 8 DISP PAN DISP. 15-16 FUEL ALARM ALARM 11-30-23 9:28AM I11200 NOV 30, 2023 12:45 PM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-30-23 9:05AM SYSTEM PRINTER ERROR CLEAR 11-30-23 9:00AM SYSTEM PAPER OUT CLEAR 11-30-23 9:00AM SYSTEM PRINTER ERROR ALARM 11-30-23 8:57AM SYSTEM PAPER OUT ALARM 11-30-23 8:57AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-28-23 9:26AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-24-23 9:22AM OTHER ISD GROSS PRES WARN CLEAR 11-24-23 8:00AM OTHER ISD GROSS PRES WARN ALARM 11-23-23 9:25AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-17-23 9:25AM OTHER ISD GROSS PRES WARN CLEAR 11-17-23 8:41AM OTHER ISD GROSS PRES WARN ALARM 11-15-23 9:26AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN CLEAR 11-13-23 9:58AM SYSTEM PRINTER ERROR CLEAR 11-12-23 8:36AM SYSTEM PAPER OUT CLEAR 11-12-23 8:36AM SYSTEM PRINTER ERROR ALARM 11-12-23 8:36AM SYSTEM PAPER OUT ALARM 11-12-23 8:36AM SYSTEM PRINTER ERROR CLEAR 11-12-23 8:36AM SYSTEM PAPER OUT CLEAR 11-12-23 8:36AM SYSTEM PRINTER ERROR ALARM 11-12-23 8:35AM SYSTEM PAPER OUT ALARM 11-12-23 8:35AM SYSTEM PRINTER ERROR CLEAR 11-12-23 8:35AM SYSTEM PAPER OUT CLEAR 11-12-23 8:35AM SYSTEM PRINTER ERROR ALARM 11-12-23 12:00AM SYSTEM PAPER OUT ALARM 11-12-23 12:00AM h 2 OTHER FP2: BLEND3 DEGRD COLLECT WARN ALARM 11-11-23 9:26AM OTHER ISD GROSS PRES WARN CLEAR 11-08-23 9:49AM OTHER ISD GROSS PRES WARN ALARM 11-08-23 9:25AM OTHER ISD GROSS PRES WARN CLEAR 11-01-23 3:06PM OTHER ISD GROSS PRES WARN ALARM 11-01-23 9:24AM OTHER ISD GROSS PRES WARN CLEAR 10-26-23 8:33AM OTHER ISD GROSS PRES WARN ALARM 10-25-23 9:24AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:04AM SYSTEM PAPER OUT CLEAR 10-25-23 8:04AM SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM SYSTEM PAPER OUT ALARM 10-25-23 8:03AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:03AM SYSTEM PAPER OUT CLEAR 10-25-23 8:03AM SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM SYSTEM PAPER OUT ALARM 10-25-23 8:03AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:03AM SYSTEM PAPER OUT CLEAR 10-25-23 8:03AM SYSTEM PRINTER ERROR ALARM 10-25-23 8:03AM SYSTEM PAPER OUT ALARM 10-25-23 8:03AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:02AM SYSTEM PAPER OUT CLEAR 10-25-23 8:02AM SYSTEM PRINTER ERROR ALARM 10-25-23 8:02AM SYSTEM PAPER OUT ALARM 10-25-23 8:02AM SYSTEM PRINTER ERROR CLEAR 10-25-23 8:01AM SYSTEM PAPER OUT CLEAR 10-25-23 8:01AM I20600 NOV 30, 2023 12:45 PM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 TANK ALARM HISTORY TANK 1 UNLEADED 87 OVERFILL ALARM OCT 28, 2021 10:52 AM NOV 2, 2020 2:36 AM PROBE OUT OCT 28, 2021 10:56 AM OCT 28, 2021 10:42 AM DEC 15, 2020 5:47 PM LOW TEMP WARNING OCT 28, 2021 10:57 AM OCT 28, 2021 10:43 AM TANK 2 SUPREME 91 OVERFILL ALARM OCT 28, 2021 10:50 AM PROBE OUT FEB 3, 2022 8:33 AM OCT 28, 2021 10:54 AM OCT 28, 2021 10:41 AM DELIVERY NEEDED JUL 18, 2020 9:15 PM LOW TEMP WARNING OCT 28, 2021 10:55 AM OCT 28, 2021 10:42 AM TANK 3 DIESEL OVERFILL ALARM OCT 28, 2021 10:46 AM PROBE OUT OCT 28, 2021 10:52 AM OCT 28, 2021 10:40 AM DELIVERY NEEDED NOV 23, 2022 6:41 AM SEP 8, 2022 9:20 AM JUN 23, 2022 3:08 PM LOW TEMP WARNING OCT 28, 2021 10:54 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 NOV 30, 2023 12:46 PM I30200 NOV 30, 2023 12:46 PM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DISP. 1-2 NOV 30, 2023 9:42 AM SENSOR OUT ALARM NOV 30, 2023 9:32 AM FUEL ALARM NOV 21, 2023 10:25 AM SENSOR OUT ALARM 2 DISP. 3-4 NOV 30, 2023 9:42 AM SENSOR OUT ALARM NOV 30, 2023 9:31 AM FUEL ALARM NOV 21, 2023 10:26 AM SENSOR OUT ALARM 3 DISP. 11-12 NOV 30, 2023 9:42 AM SENSOR OUT ALARM NOV 30, 2023 9:29 AM FUEL ALARM NOV 21, 2023 9:38 AM FUEL ALARM 4 DISP. 7-8 NOV 30, 2023 9:42 AM SENSOR OUT ALARM NOV 30, 2023 9:30 AM FUEL ALARM NOV 21, 2023 9:41 AM FUEL ALARM 5 DISP. 9-10 NOV 30, 2023 9:42 AM SENSOR OUT ALARM NOV 30, 2023 9:30 AM FUEL ALARM NOV 21, 2023 10:51 AM FUEL ALARM 6 DISP 5-6 NOV 30, 2023 9:42 AM SENSOR OUT ALARM NOV 30, 2023 9:31 AM FUEL ALARM NOV 21, 2023 10:25 AM SENSOR OUT ALARM 7 DISP. 13-14 NOV 30, 2023 9:42 AM SENSOR OUT ALARM NOV 30, 2023 9:29 AM FUEL ALARM NOV 21, 2023 10:25 AM SENSOR OUT ALARM 8 DISP. 15-16 NOV 30, 2023 9:42 AM SENSOR OUT ALARM NOV 30, 2023 9:28 AM FUEL ALARM NOV 21, 2023 10:25 AM SENSOR OUT ALARM 9 UNLEADED SUMP NOV 30, 2023 9:41 AM SENSOR OUT ALARM NOV 30, 2023 9:33 AM FUEL ALARM NOV 21, 2023 10:25 AM SENSOR OUT ALARM 10 SUPREME SUMP NOV 30, 2023 9:41 AM SENSOR OUT ALARM NOV 30, 2023 9:33 AM FUEL ALARM NOV 21, 2023 10:25 AM SENSOR OUT ALARM 11 DIESEL SUMP NOV 30, 2023 9:41 AM SENSOR OUT ALARM NOV 30, 2023 9:33 AM FUEL ALARM NOV 21, 2023 10:25 AM SENSOR OUT ALARM 12 UNLEADED ANNULAR NOV 30, 2023 9:35 AM FUEL ALARM NOV 27, 2023 8:54 PM FUEL ALARM NOV 21, 2023 10:17 AM FUEL ALARM 13 SUPREME ANNULAR NOV 30, 2023 9:38 AM FUEL ALARM NOV 21, 2023 10:20 AM FUEL ALARM DEC 21, 2022 1:37 PM FUEL ALARM 14 DIESEL ANNULAR NOV 30, 2023 9:36 AM FUEL ALARM NOV 21, 2023 10:24 AM FUEL ALARM SEP 19, 2023 12:50 PM FUEL ALARM I31600 NOV 30, 2023 12:46 PM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 FM 1-2 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 2 FM 3-4 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 3 FM 5-6 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 4 FM 7-8 5 FM 9-10 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 6 FM 11-12 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 7 FM 13-14 DEC 13, 2019 8:39 AM COMMUNICATION ALARM 8 PRESSURE SENSOR 9 FM 15-16 I40200 NOV 30, 2023 12:46 PM I40300 NOV 30, 2023 12:46 PM I34200 NOV 30, 2023 12:46 PM I34700 NOV 30, 2023 12:46 PM IV0100 NOV 30, 2023 12:46 PM 286917 SPARKLING IMA 2301 H ST. BAKERSFIELD,CA 93301 661-324-8455 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.06 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-11-29 09:28:25 A/L RATIO DEGRADATION FP 2 BLEND3 0.61 23-11-28 09:26:17 A/L RATIO DEGRADATION FP 2 BLEND3 0.61 23-11-23 09:25:10 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.34 23-11-23 09:25:10 A/L RATIO DEGRADATION FP 2 BLEND3 0.78 23-11-22 09:25:13 A/L RATIO DEGRADATION FP 2 BLEND3 0.78 23-11-21 09:25:05 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 23-11-20 09:25:24 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 23-11-19 09:25:13 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 23-11-18 09:25:12 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 23-11-17 09:25:41 A/L RATIO DEGRADATION FP 2 BLEND3 0.77 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-11-24 09:25:46 A/L RATIO DEGRADATION FP 2 BLEND3 0.78 22-08-05 09:25:27 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.46 22-07-22 09:27:21 A/L RATIO DEGRADATION FP15 BLEND3 1.67 21-03-12 09:26:38 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55 20-11-26 09:26:56 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.30 20-11-12 09:24:44 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.55 20-05-04 09:26:50 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 24.17 20-04-07 09:26:07 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.27 19-08-03 10:03:31 A/L RATIO GROSS BLOCKAGE FP 6 BLEND3 BLKD 19-07-03 10:03:50 SENSOR OUT SELFTEST s 9 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-11-30 09:43:03 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-11-30 09:43:03 ISD STARTUP 23-11-30 09:42:44 ISD SHUTDOWN 23-11-30 09:05:13 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED 23-11-24 14:06:04 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED 23-11-24 14:05:54 CONTAINMENT VAPOR LEAKAGE TEST MANUALLY CLEARED 23-11-24 14:05:46 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-24 10:47:16 PUMPS MANUALLY RE-ENABLED 23-11-24 09:25:46 A/L RATIO GROSS DEGRADATION DISABLED FP 02 BLEND3 23-11-24 08:00:39 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED