Loading...
HomeMy WebLinkAboutFMC 2023Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10125802 12/14/2023 Samco White Ln 3300 White Ln Bakersfield 93309 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Brandon Nunez 1073967 10226373 9/6/2024 VeederRoot - C32655 10/11/24 Vaporless manufacturing Inc - 5265 10/21/24 Phil-Tite - 1016703714 12/07/24 12/14/2023 5 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 VedderRoot TLS-350 336.01 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 Disp 1-2 L2 208 Disp 5-6 L3 208 Disp 3-4 L4 208 Disp 7-8 L5 208 Disp 9-10 L7 208 Disp 11-12 L9 208 87 STP L10 420 87 ANN L11 208 87 FILL L12 420 91 ANN L13 208 91 STP L14 208 91 FILL Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 Fx1v 87 Unleaded T2 Fx1v 91 Premium Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Samco White Ln3300 White LnBakersfield101258023-47-8 11-12MPDMPDMPDMPDMPDMPD1-25-69-10ProductProductProductProductProductProductBrandon Nunez Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10125802 12/14/2023 Samco White Ln 3300 White Ln Bakersfield 93309 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Brandon Nunez 1073967 10226373 9/6/2024 Phil-Tite - 1016703714 12/7/24 PEI-1200 1 Hour Hydrostatic All spill containers 12/14/2023 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1: 87 UNL Phil-Tite T2: 91 PNL Phil-Tite SamCo White Lane System Setup Responses Received: 200 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 DEC 14, 2023 9:00 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 SUPREM 5693 46.07 0.0 61.0 6307 2 UNLEADED 9262 69.21 0.8 56.8 2738 I90500 DEC 14, 2023 9:00 AM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 DEC 14, 2023 9:00 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 DEC 14, 2023 9:00 AM SHIFT TIME 1 : DISABLED I50202 DEC 14, 2023 9:00 AM SHIFT TIME 2 : DISABLED I50203 DEC 14, 2023 9:00 AM SHIFT TIME 3 : DISABLED I50204 DEC 14, 2023 9:00 AM SHIFT TIME 4 : DISABLED I54600 DEC 14, 2023 9:00 AM TANK PER TST NEEDED WRN: DISABLED I54900 DEC 14, 2023 9:00 AM TANK ANN TST NEEDED WRN: DISABLED I55300 DEC 14, 2023 9:00 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 DEC 14, 2023 9:00 AM LINE PER TST NEEDED WRN: DISABLED I55900 DEC 14, 2023 9:00 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 DEC 14, 2023 9:00 AM PRINT TC VOLUMES ENABLED I50E00 DEC 14, 2023 9:00 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 DEC 14, 2023 9:00 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 DEC 14, 2023 9:00 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 DEC 14, 2023 9:00 AM DAYLIGHT SAVING TIME ENABLED OFF I51B00 DEC 14, 2023 9:00 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 DEC 14, 2023 9:00 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 DEC 14, 2023 9:00 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 DEC 14, 2023 9:00 AM TANK CHART SECURITY DISABLED I5BD00 DEC 14, 2023 9:00 AM CUSTOM ALARM LABELS DISABLED I56000 DEC 14, 2023 9:00 AM MASS/DENSITY DISABLED I88101 DEC 14, 2023 9:00 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 DEC 14, 2023 9:00 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 DEC 14, 2023 9:00 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 1200 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88104 DEC 14, 2023 9:00 AM I88105 DEC 14, 2023 9:00 AM PORT SETTINGS: COMM BOARD : 5 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 2 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88106 DEC 14, 2023 9:00 AM I52000 DEC 14, 2023 9:00 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE FEB 28, 2017 DISABLED 2 ON DATE FEB 28, 2017 DISABLED 3 ON DATE FEB 28, 2017 DISABLED 4 ON DATE FEB 28, 2017 DISABLED 5 ON DATE FEB 28, 2017 DISABLED 6 ON DATE FEB 28, 2017 DISABLED 7 ON DATE FEB 28, 2017 DISABLED 8 WEEKLY FRI 4:41 PM I60100 DEC 14, 2023 9:00 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 SUPREM ON 2 UNLEADED ON 3 OFF 4 OFF I60200 DEC 14, 2023 9:00 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 SUPREM 2 UNLEADED 3 4 I60300 DEC 14, 2023 9:00 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 SUPREM 1 2 UNLEADED 2 3 3 4 4 I60900 DEC 14, 2023 9:00 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 SUPREM 0.000700 2 UNLEADED 0.000700 3 0.000000 4 0.000000 I60700 DEC 14, 2023 9:00 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 SUPREM 96.00 2 UNLEADED 96.00 3 0.00 4 0.00 I60A00 DEC 14, 2023 9:00 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 SUPREM 1 PT 12000 2 UNLEADED 1 PT 12000 3 1 PT 0 4 1 PT 0 I60400 DEC 14, 2023 9:00 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 SUPREM 12000 2 UNLEADED 12000 3 0 4 0 I60500 DEC 14, 2023 9:00 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 SUPREM 12000 0 0 0 2 UNLEADED 12000 0 0 0 3 0 0 0 0 4 0 0 0 0 I60600 DEC 14, 2023 9:00 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 SUPREM 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 UNLEADED 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 DEC 14, 2023 9:00 AM TANK PRODUCT LABEL METER DATA 1 SUPREM NO 2 UNLEADED NO 3 NO 4 NO I62F00 DEC 14, 2023 9:00 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 SUPREM 4.0 IN. 2 UNLEADED 4.0 IN. I62700 DEC 14, 2023 9:00 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 SUPREM 2.0 2 UNLEADED 2.0 I64200 DEC 14, 2023 9:00 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 SUPREM LOW 2 UNLEADED LOW I62400 DEC 14, 2023 9:00 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 SUPREM 3.0 2 UNLEADED 3.0 I62800 DEC 14, 2023 9:00 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREM 12000 2 UNLEADED 12000 3 0 4 0 I62300 DEC 14, 2023 9:00 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREM 10800 2 UNLEADED 10800 3 0 4 0 I62200 DEC 14, 2023 9:00 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREM 11400 2 UNLEADED 11400 3 0 4 0 I62900 DEC 14, 2023 9:00 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREM 1200 2 UNLEADED 1200 3 0 4 0 I62100 DEC 14, 2023 9:00 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREM 1200 2 UNLEADED 1200 3 0 4 0 I62600 DEC 14, 2023 9:00 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREM 99 2 UNLEADED 99 3 99 4 99 I62500 DEC 14, 2023 9:00 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREM 99 2 UNLEADED 99 3 99 4 99 I60800 DEC 14, 2023 9:00 AM TANK TILT TANK PRODUCT LABEL INCHES 1 SUPREM 0.00 2 UNLEADED 0.00 3 0.00 4 0.00 I60B00 DEC 14, 2023 9:00 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 DEC 14, 2023 9:00 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 SUPREM 0.00 2 UNLEADED 0.00 3 0.00 4 0.00 I61200 DEC 14, 2023 9:00 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 SUPREM NONE NONE 2 UNLEADED NONE NONE 3 NONE NONE 4 NONE NONE I63600 DEC 14, 2023 9:00 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 SUPREM 1200 2 UNLEADED 1200 3 0 4 0 I62A00 DEC 14, 2023 9:00 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 SUPREM 1200 2 UNLEADED 1200 3 0 4 0 I62C00 DEC 14, 2023 9:00 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 SUPREM STANDARD 2 UNLEADED STANDARD 3 STANDARD 4 STANDARD I62D00 DEC 14, 2023 9:00 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 SUPREM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 DEC 14, 2023 9:00 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 SUPREM OFF OFF 2 UNLEADED OFF OFF 3 OFF OFF 4 OFF OFF I63000 DEC 14, 2023 9:00 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 SUPREM OFF 2 UNLEADED OFF 3 OFF 4 OFF I63200 DEC 14, 2023 9:00 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 SUPREM OFF 2 UNLEADED OFF 3 OFF 4 OFF I61000 DEC 14, 2023 9:00 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 SUPREM 1 2 UNLEADED 1 3 1 4 1 I63A00 DEC 14, 2023 9:00 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 SUPREM 10.00% 2 UNLEADED 10.00% 3 10.00% 4 10.00% I61100 DEC 14, 2023 9:00 AM LEAK TEST METHOD - - - - - - - - - - - - TEST MONTHLY : ALL TANK WEEK 1 MON START TIME : 2:00 AM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:ENABLED I61300 DEC 14, 2023 9:00 AM CSLD PROBABLITY OF DETECTION I61400 DEC 14, 2023 9:00 AM CSLD CLIMATE FACTOR I61600 DEC 14, 2023 9:00 AM TANK PRODUCT LABEL CAL UPDATE 1 SUPREM IMMEDIATE 2 UNLEADED IMMEDIATE 3 IMMEDIATE 4 IMMEDIATE I61A00 DEC 14, 2023 9:00 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 SUPREM ENABLED 2 UNLEADED ENABLED 3 ENABLED 4 ENABLED I61B00 DEC 14, 2023 9:00 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 DEC 14, 2023 9:00 AM CSLD REPORT ONLY I62B00 DEC 14, 2023 9:00 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 SUPREM ??? 0, 0 2 UNLEADED ??? 0, 0 3 ??? 0, 0 4 ??? 0, 0 I63300 DEC 14, 2023 9:00 AM LEAK TEST REPORT FORMAT: NORMAL I63400 DEC 14, 2023 9:00 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREM 0 2 UNLEADED 0 3 0 4 0 I63500 DEC 14, 2023 9:00 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 SUPREM 1 2 UNLEADED 1 3 1 4 1 I63900 DEC 14, 2023 9:00 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 SUPREM END FACTOR: NONE 2 UNLEADED END FACTOR: NONE 3 END FACTOR: NONE 4 END FACTOR: NONE I78000 DEC 14, 2023 9:00 AM I77700 DEC 14, 2023 9:00 AM I77800 DEC 14, 2023 9:00 AM I78C00 DEC 14, 2023 9:00 AM I78300 DEC 14, 2023 9:00 AM I78F00 DEC 14, 2023 9:00 AM I78700 DEC 14, 2023 9:00 AM I70200 DEC 14, 2023 9:00 AM LIQUID LABEL DEVICE LABEL 1 DISP 1-2 2 DISP 5-6 3 DISP 3-4 4 DISP 7-8 5 DISP 9-10 6 91 FILL 7 DISP 11-12 8 DISP 3-4 9 87 STP 10 87 ANN 11 87 FILL 12 91 ANN 13 91 STP 14 91 FILL 15 DISP 11-12 16 I70300 DEC 14, 2023 9:00 AM LIQUID TYPE SENSOR LOCATION TYPE 1 DISP 1-2 TRI-STATE (SINGLE FLOAT) 2 DISP 5-6 TRI-STATE (SINGLE FLOAT) 3 DISP 3-4 TRI-STATE (SINGLE FLOAT) 4 DISP 7-8 TRI-STATE (SINGLE FLOAT) 5 DISP 9-10 TRI-STATE (SINGLE FLOAT) 6 91 FILL TRI-STATE (SINGLE FLOAT) 7 DISP 11-12 TRI-STATE (SINGLE FLOAT) 8 DISP 3-4 TRI-STATE (SINGLE FLOAT) 9 87 STP TRI-STATE (SINGLE FLOAT) 10 87 ANN TRI-STATE (SINGLE FLOAT) 11 87 FILL TRI-STATE (SINGLE FLOAT) 12 91 ANN TRI-STATE (SINGLE FLOAT) 13 91 STP TRI-STATE (SINGLE FLOAT) 14 91 FILL TRI-STATE (SINGLE FLOAT) 15 DISP 11-12 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 DEC 14, 2023 9:00 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 DISP 1-2 DISPENSER PAN 2 DISP 5-6 DISPENSER PAN 3 DISP 3-4 DISPENSER PAN 4 DISP 7-8 DISPENSER PAN 5 DISP 9-10 DISPENSER PAN 6 91 FILL PIPING SUMP 7 DISP 11-12 DISPENSER PAN 8 DISP 3-4 DISPENSER PAN 9 87 STP STP SUMP 10 87 ANN ANNULAR SPACE 11 87 FILL PIPING SUMP 12 91 ANN ANNULAR SPACE 13 91 STP STP SUMP 14 91 FILL PIPING SUMP 15 DISP 11-12 DISPENSER PAN 16 OTHER SENSORS I74200 DEC 14, 2023 9:00 AM I74300 DEC 14, 2023 9:00 AM I74400 DEC 14, 2023 9:00 AM I74700 DEC 14, 2023 9:00 AM I74800 DEC 14, 2023 9:00 AM I74900 DEC 14, 2023 9:01 AM I7BC00 DEC 14, 2023 9:01 AM I80200 DEC 14, 2023 9:01 AM I80300 DEC 14, 2023 9:01 AM I80400 DEC 14, 2023 9:01 AM I80700 DEC 14, 2023 9:01 AM RELAY LABEL DEVICE LABEL 1 POSTITIVE SHUT OFF 2 OVERFILL ALARM 3 4 I80900 DEC 14, 2023 9:01 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 POSTITIVE SHUT OFF NORMALLY CLOSED 2 OVERFILL ALARM NORMALLY OPEN 3 NORMALLY OPEN 4 NORMALLY OPEN I80B00 DEC 14, 2023 9:01 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 POSTITIVE SHUT OFF 1 2 OVERFILL ALARM NONE 3 NONE 4 NONE I80A00 DEC 14, 2023 9:01 AM RELAY TYPE RELAY DESIGNATION TYPE 1 POSTITIVE SHUT OFF STANDARD 2 OVERFILL ALARM STANDARD 3 STANDARD 4 STANDARD I80C00 DEC 14, 2023 9:01 AM I80800 DEC 14, 2023 9:01 AM RELAY SETUP REPORT R 1:POSTITIVE SHUT OFF TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 7:FUEL ALARM L 9:FUEL ALARM L13:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 7:SHORT ALARM L 9:SHORT ALARM L13:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS h13:GROSS COLLECT FAIL h14:GROSS COLLECT FAIL h15:GROSS COLLECT FAIL h16:GROSS COLLECT FAIL h17:GROSS COLLECT FAIL h18:GROSS COLLECT FAIL h19:GROSS COLLECT FAIL h20:GROSS COLLECT FAIL h21:GROSS COLLECT FAIL h22:GROSS COLLECT FAIL h23:GROSS COLLECT FAIL h24:GROSS COLLECT FAIL h25:GROSS COLLECT FAIL h26:GROSS COLLECT FAIL h27:GROSS COLLECT FAIL h28:GROSS COLLECT FAIL h29:GROSS COLLECT FAIL h30:GROSS COLLECT FAIL h31:GROSS COLLECT FAIL h32:GROSS COLLECT FAIL h33:GROSS COLLECT FAIL h34:GROSS COLLECT FAIL h35:GROSS COLLECT FAIL h36:GROSS COLLECT FAIL h37:GROSS COLLECT FAIL h38:GROSS COLLECT FAIL h39:GROSS COLLECT FAIL h40:GROSS COLLECT FAIL h41:GROSS COLLECT FAIL h42:GROSS COLLECT FAIL h43:GROSS COLLECT FAIL h44:GROSS COLLECT FAIL h45:GROSS COLLECT FAIL h46:GROSS COLLECT FAIL h47:GROSS COLLECT FAIL h48:GROSS COLLECT FAIL h49:GROSS COLLECT FAIL h50:GROSS COLLECT FAIL h51:GROSS COLLECT FAIL h52:GROSS COLLECT FAIL h53:GROSS COLLECT FAIL h54:GROSS COLLECT FAIL h55:GROSS COLLECT FAIL h56:GROSS COLLECT FAIL h57:GROSS COLLECT FAIL h58:GROSS COLLECT FAIL h59:GROSS COLLECT FAIL h60:GROSS COLLECT FAIL h61:GROSS COLLECT FAIL h62:GROSS COLLECT FAIL h63:GROSS COLLECT FAIL h64:GROSS COLLECT FAIL h65:GROSS COLLECT FAIL h66:GROSS COLLECT FAIL h67:GROSS COLLECT FAIL h68:GROSS COLLECT FAIL h69:GROSS COLLECT FAIL h70:GROSS COLLECT FAIL h71:GROSS COLLECT FAIL h72:GROSS COLLECT FAIL h73:GROSS COLLECT FAIL h74:GROSS COLLECT FAIL h75:GROSS COLLECT FAIL h76:GROSS COLLECT FAIL h77:GROSS COLLECT FAIL h78:GROSS COLLECT FAIL h79:GROSS COLLECT FAIL h80:GROSS COLLECT FAIL h81:GROSS COLLECT FAIL h82:GROSS COLLECT FAIL h83:GROSS COLLECT FAIL h84:GROSS COLLECT FAIL h85:GROSS COLLECT FAIL h86:GROSS COLLECT FAIL h87:GROSS COLLECT FAIL h88:GROSS COLLECT FAIL h89:GROSS COLLECT FAIL h90:GROSS COLLECT FAIL h91:GROSS COLLECT FAIL h92:GROSS COLLECT FAIL h93:GROSS COLLECT FAIL h94:GROSS COLLECT FAIL h95:GROSS COLLECT FAIL h96:GROSS COLLECT FAIL h97:GROSS COLLECT FAIL h98:GROSS COLLECT FAIL h99:GROSS COLLECT FAIL h13:DEGRD COLLECT FAIL h14:DEGRD COLLECT FAIL h15:DEGRD COLLECT FAIL h16:DEGRD COLLECT FAIL h17:DEGRD COLLECT FAIL h18:DEGRD COLLECT FAIL h19:DEGRD COLLECT FAIL h20:DEGRD COLLECT FAIL h21:DEGRD COLLECT FAIL h22:DEGRD COLLECT FAIL h23:DEGRD COLLECT FAIL h24:DEGRD COLLECT FAIL h25:DEGRD COLLECT FAIL h26:DEGRD COLLECT FAIL h27:DEGRD COLLECT FAIL h28:DEGRD COLLECT FAIL h29:DEGRD COLLECT FAIL h30:DEGRD COLLECT FAIL h31:DEGRD COLLECT FAIL h32:DEGRD COLLECT FAIL h33:DEGRD COLLECT FAIL h34:DEGRD COLLECT FAIL h35:DEGRD COLLECT FAIL h36:DEGRD COLLECT FAIL h37:DEGRD COLLECT FAIL h38:DEGRD COLLECT FAIL h39:DEGRD COLLECT FAIL h40:DEGRD COLLECT FAIL h41:DEGRD COLLECT FAIL h42:DEGRD COLLECT FAIL h43:DEGRD COLLECT FAIL h44:DEGRD COLLECT FAIL h45:DEGRD COLLECT FAIL h46:DEGRD COLLECT FAIL h47:DEGRD COLLECT FAIL h48:DEGRD COLLECT FAIL h49:DEGRD COLLECT FAIL h50:DEGRD COLLECT FAIL h51:DEGRD COLLECT FAIL h52:DEGRD COLLECT FAIL h53:DEGRD COLLECT FAIL h54:DEGRD COLLECT FAIL h55:DEGRD COLLECT FAIL h56:DEGRD COLLECT FAIL h57:DEGRD COLLECT FAIL h58:DEGRD COLLECT FAIL h59:DEGRD COLLECT FAIL h60:DEGRD COLLECT FAIL h61:DEGRD COLLECT FAIL h62:DEGRD COLLECT FAIL h63:DEGRD COLLECT FAIL h64:DEGRD COLLECT FAIL h65:DEGRD COLLECT FAIL h66:DEGRD COLLECT FAIL h67:DEGRD COLLECT FAIL h68:DEGRD COLLECT FAIL h69:DEGRD COLLECT FAIL h70:DEGRD COLLECT FAIL h71:DEGRD COLLECT FAIL h72:DEGRD COLLECT FAIL h73:DEGRD COLLECT FAIL h74:DEGRD COLLECT FAIL h75:DEGRD COLLECT FAIL h76:DEGRD COLLECT FAIL h77:DEGRD COLLECT FAIL h78:DEGRD COLLECT FAIL h79:DEGRD COLLECT FAIL h80:DEGRD COLLECT FAIL h81:DEGRD COLLECT FAIL h82:DEGRD COLLECT FAIL h83:DEGRD COLLECT FAIL h84:DEGRD COLLECT FAIL h85:DEGRD COLLECT FAIL h86:DEGRD COLLECT FAIL h87:DEGRD COLLECT FAIL h88:DEGRD COLLECT FAIL h89:DEGRD COLLECT FAIL h90:DEGRD COLLECT FAIL h91:DEGRD COLLECT FAIL h92:DEGRD COLLECT FAIL h93:DEGRD COLLECT FAIL h94:DEGRD COLLECT FAIL h95:DEGRD COLLECT FAIL h96:DEGRD COLLECT FAIL h97:DEGRD COLLECT FAIL h98:DEGRD COLLECT FAIL h99:DEGRD COLLECT FAIL h13:FLOW COLLECT FAIL h14:FLOW COLLECT FAIL h15:FLOW COLLECT FAIL h16:FLOW COLLECT FAIL h17:FLOW COLLECT FAIL h18:FLOW COLLECT FAIL h19:FLOW COLLECT FAIL h20:FLOW COLLECT FAIL h21:FLOW COLLECT FAIL h22:FLOW COLLECT FAIL h23:FLOW COLLECT FAIL h24:FLOW COLLECT FAIL h25:FLOW COLLECT FAIL h26:FLOW COLLECT FAIL h27:FLOW COLLECT FAIL h28:FLOW COLLECT FAIL h29:FLOW COLLECT FAIL h30:FLOW COLLECT FAIL h31:FLOW COLLECT FAIL h32:FLOW COLLECT FAIL h33:FLOW COLLECT FAIL h34:FLOW COLLECT FAIL h35:FLOW COLLECT FAIL h36:FLOW COLLECT FAIL h37:FLOW COLLECT FAIL h38:FLOW COLLECT FAIL h39:FLOW COLLECT FAIL h40:FLOW COLLECT FAIL h41:FLOW COLLECT FAIL h42:FLOW COLLECT FAIL h43:FLOW COLLECT FAIL h44:FLOW COLLECT FAIL h45:FLOW COLLECT FAIL h46:FLOW COLLECT FAIL h47:FLOW COLLECT FAIL h48:FLOW COLLECT FAIL h49:FLOW COLLECT FAIL h50:FLOW COLLECT FAIL h51:FLOW COLLECT FAIL h52:FLOW COLLECT FAIL h53:FLOW COLLECT FAIL h54:FLOW COLLECT FAIL h55:FLOW COLLECT FAIL h56:FLOW COLLECT FAIL h57:FLOW COLLECT FAIL h58:FLOW COLLECT FAIL h59:FLOW COLLECT FAIL h60:FLOW COLLECT FAIL h61:FLOW COLLECT FAIL h62:FLOW COLLECT FAIL h63:FLOW COLLECT FAIL h64:FLOW COLLECT FAIL h65:FLOW COLLECT FAIL h66:FLOW COLLECT FAIL h67:FLOW COLLECT FAIL h68:FLOW COLLECT FAIL h69:FLOW COLLECT FAIL h70:FLOW COLLECT FAIL h71:FLOW COLLECT FAIL h72:FLOW COLLECT FAIL h73:FLOW COLLECT FAIL h74:FLOW COLLECT FAIL h75:FLOW COLLECT FAIL h76:FLOW COLLECT FAIL h77:FLOW COLLECT FAIL h78:FLOW COLLECT FAIL h79:FLOW COLLECT FAIL h80:FLOW COLLECT FAIL h81:FLOW COLLECT FAIL h82:FLOW COLLECT FAIL h83:FLOW COLLECT FAIL h84:FLOW COLLECT FAIL h85:FLOW COLLECT FAIL h86:FLOW COLLECT FAIL h87:FLOW COLLECT FAIL h88:FLOW COLLECT FAIL h89:FLOW COLLECT FAIL h90:FLOW COLLECT FAIL h91:FLOW COLLECT FAIL h92:FLOW COLLECT FAIL h93:FLOW COLLECT FAIL h94:FLOW COLLECT FAIL h95:FLOW COLLECT FAIL h96:FLOW COLLECT FAIL h97:FLOW COLLECT FAIL h98:FLOW COLLECT FAIL h99:FLOW COLLECT FAIL R 2:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM R 3: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 4: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - I79000 DEC 14, 2023 9:01 AM EDIM:1 VR:349867-001-C TD:16.05.27.07.44 I79100 DEC 14, 2023 9:01 AM I72300 DEC 14, 2023 9:01 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 FM 1-2 AIR FLOW METER 02 UNKNOWN 03 FM 5-6 AIR FLOW METER 04 FM 7-8 AIR FLOW METER 05 FM 9-10 AIR FLOW METER 06 FM 11-12 AIR FLOW METER 07 FM 3-4 AIR FLOW METER 08 PS 1-2 VAPOR PRESSURE 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 DEC 14, 2023 9:01 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 EVR/ISD SETUP TYPE: BALANCE IV4F00 DEC 14, 2023 9:01 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 DEC 14, 2023 9:01 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 VAPOR PROCESSOR TYPE NONE IV4700 DEC 14, 2023 9:01 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 DEC 14, 2023 9:01 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 ACCEPT HIGH ORVR: YES IV4A00 DEC 14, 2023 9:01 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 UU BLEND3 02 02 02 01 UU BLEND3 03 03 03 06 UU BLEND3 04 04 04 06 UU BLEND3 05 05 05 02 UU BLEND3 06 06 06 02 UU BLEND3 07 07 07 03 UU BLEND3 08 08 08 03 UU BLEND3 09 09 09 04 UU BLEND3 10 16 10 04 UU BLEND3 11 17 11 05 UU BLEND3 12 18 12 05 UU BLEND3 IV4B00 DEC 14, 2023 9:01 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 09/01 01/01 xx/xx 02 01 02/02 09/02 01/02 xx/xx 03 06 02/03 09/03 01/03 xx/xx 04 06 02/04 09/04 01/04 xx/xx 05 02 02/05 09/05 01/05 xx/xx 06 02 02/06 09/06 01/06 xx/xx 07 03 02/07 09/07 01/07 xx/xx 08 03 02/08 09/08 01/08 xx/xx 09 04 02/09 09/09 01/09 xx/xx 16 04 02/10 09/10 01/10 xx/xx 17 05 02/11 09/11 01/11 xx/xx 18 05 02/12 09/12 01/12 xx/xx IV4900 DEC 14, 2023 9:01 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 DEC 14, 2023 9:01 AM ISD VERSION: 01.05 SamCo White Lane Pre Alarm History Responses Received: I10200 DEC 14, 2023 9:02 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39616 39595 2 4 PROBE / G.T. 163711 163619 3 INTERSTITIAL BD 201522 201495 4 INTERSTITIAL BD 201289 201401 5 UNUSED 9922524 9845654 6 UNUSED 9907690 9831796 7 UNUSED 9915587 9833925 8 UNUSED 9907646 9836552 9 UNUSED 9907173 9834336 10 RELAY BOARD 14999 15044 11 UNUSED 9912594 9840223 12 UNUSED 9902690 9848420 13 UNUSED 9902021 9837143 14 UNUSED 9903850 9836985 15 UNUSED 9899656 9841287 16 UNUSED 9908935 9837324 COMM 1 ELEC DISP INT. 101163 101306 COMM 2 RS232 SERIAL BD 15022 14999 COMM 3 RS232 SERIAL BD 15044 15044 COMM 4 UNUSED 9906995 9842283 COMM 5 SERIAL SAT BD 480692 481403 COMM 6 UNUSED 9915493 9833702 I90200 DEC 14, 2023 9:02 AM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 DEC 14, 2023 9:02 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L14 PIPE 91 FILL FUEL ALARM CLEAR 12-13-23 9:08AM L14 PIPE 91 FILL FUEL ALARM ALARM 12-10-23 9:44AM OTHER ISD VAPOR LEAK FAIL CLEAR 9-27-23 7:35AM OTHER ISD VAPOR LEAK FAIL ALARM 9-26-23 10:04AM E 1 OTHER COMMUNICATION ALARM CLEAR 8-25-23 10:50AM E 1 OTHER COMMUNICATION ALARM ALARM 8-25-23 10:06AM L11 PIPE 87 FILL FUEL ALARM CLEAR 8-21-23 11:01AM L11 PIPE 87 FILL FUEL ALARM ALARM 8-20-23 7:20PM D 8 OTHER AUTODIAL FAILURE CLEAR 8-11-23 4:45PM D 8 OTHER AUTODIAL FAILURE ALARM 8-04-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 8-04-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 7-28-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 7-28-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 7-22-23 10:26AM D 8 OTHER AUTODIAL FAILURE CLEAR 7-22-23 10:26AM D 8 OTHER AUTODIAL FAILURE ALARM 7-21-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 7-21-23 5:06PM h 4 OTHER FP4: BLEND3 FLOW COLLECT FAIL CLEAR 7-21-23 10:00AM D 8 OTHER AUTODIAL FAILURE ALARM 7-20-23 10:29AM D 8 OTHER AUTODIAL FAILURE CLEAR 7-20-23 10:29AM h 4 OTHER FP4: BLEND3 FLOW COLLECT FAIL ALARM 7-20-23 10:04AM D 8 OTHER AUTODIAL FAILURE ALARM 7-19-23 10:29AM D 8 OTHER AUTODIAL FAILURE CLEAR 7-19-23 10:29AM D 8 OTHER AUTODIAL FAILURE ALARM 7-16-23 3:17AM D 8 OTHER AUTODIAL FAILURE CLEAR 7-16-23 3:17AM D 8 OTHER AUTODIAL FAILURE ALARM 7-14-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 7-14-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 7-14-23 3:13AM D 8 OTHER AUTODIAL FAILURE CLEAR 7-14-23 3:13AM T 2 TANK UNLEADED OVERFILL ALARM CLEAR 7-14-23 2:51AM T 2 TANK UNLEADED OVERFILL ALARM ALARM 7-14-23 2:48AM D 8 OTHER AUTODIAL FAILURE ALARM 7-07-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 7-07-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 6-30-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 6-30-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 6-23-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 6-23-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 6-16-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 6-16-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 6-09-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 6-09-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 6-02-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 6-02-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 5-26-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 5-26-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 5-19-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 5-19-23 5:06PM D 8 OTHER AUTODIAL FAILURE ALARM 5-12-23 5:06PM D 8 OTHER AUTODIAL FAILURE CLEAR 5-05-23 4:43PM D 8 OTHER AUTODIAL FAILURE ALARM 5-02-23 4:53PM I11200 DEC 14, 2023 9:02 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD DEGRD PRES WARN CLEAR 11-05-23 6:16PM OTHER ISD DEGRD PRES WARN ALARM 11-05-23 10:04AM OTHER ISD GROSS PRES WARN CLEAR 10-18-23 10:00AM OTHER ISD GROSS PRES WARN ALARM 10-17-23 10:04AM OTHER ISD GROSS PRES WARN CLEAR 10-10-23 10:16AM h 8 OTHER FP8: BLEND3 FLOW COLLECT WARN CLEAR 10-10-23 10:00AM h 8 OTHER FP8: BLEND3 FLOW COLLECT WARN ALARM 10-09-23 10:04AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 10-09-23 10:00AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 10-08-23 10:04AM OTHER ISD GROSS PRES WARN ALARM 10-04-23 10:04AM SYSTEM PRINTER ERROR CLEAR 9-28-23 6:58AM SYSTEM PAPER OUT CLEAR 9-28-23 6:58AM SYSTEM PAPER OUT ALARM 9-28-23 6:58AM SYSTEM PRINTER ERROR ALARM 9-28-23 6:58AM SYSTEM PRINTER ERROR CLEAR 9-28-23 6:57AM SYSTEM PRINTER ERROR ALARM 9-28-23 6:57AM SYSTEM PRINTER ERROR CLEAR 9-28-23 6:57AM SYSTEM PAPER OUT CLEAR 9-28-23 6:57AM SYSTEM PRINTER ERROR ALARM 9-28-23 6:56AM SYSTEM PAPER OUT ALARM 9-28-23 6:56AM OTHER ISD VAPOR LEAK WARN CLEAR 9-26-23 10:04AM OTHER ISD VAPOR LEAK WARN ALARM 9-19-23 10:05AM SYSTEM PRINTER ERROR CLEAR 9-04-23 9:37AM SYSTEM PAPER OUT CLEAR 9-04-23 9:37AM SYSTEM PAPER OUT ALARM 9-04-23 9:37AM SYSTEM PRINTER ERROR ALARM 9-04-23 9:20AM SYSTEM PRINTER ERROR CLEAR 9-01-23 7:09PM SYSTEM PAPER OUT CLEAR 9-01-23 7:09PM SYSTEM PRINTER ERROR ALARM 9-01-23 7:08PM SYSTEM PAPER OUT ALARM 9-01-23 7:08PM SYSTEM PRINTER ERROR CLEAR 9-01-23 7:08PM SYSTEM PAPER OUT CLEAR 9-01-23 7:08PM SYSTEM PRINTER ERROR ALARM 9-01-23 7:07PM SYSTEM PAPER OUT ALARM 9-01-23 7:07PM SYSTEM PRINTER ERROR CLEAR 8-09-23 10:22PM SYSTEM PAPER OUT CLEAR 8-09-23 10:22PM SYSTEM PRINTER ERROR ALARM 8-09-23 10:22PM SYSTEM PAPER OUT ALARM 8-09-23 10:22PM SYSTEM PRINTER ERROR CLEAR 8-09-23 8:10AM SYSTEM PAPER OUT CLEAR 8-09-23 8:10AM SYSTEM PAPER OUT ALARM 8-09-23 8:10AM SYSTEM PRINTER ERROR ALARM 8-09-23 8:10AM SYSTEM PRINTER ERROR CLEAR 8-09-23 8:10AM SYSTEM PRINTER ERROR ALARM 8-09-23 8:10AM SYSTEM PRINTER ERROR CLEAR 8-09-23 8:10AM SYSTEM PAPER OUT CLEAR 8-09-23 8:10AM SYSTEM PRINTER ERROR ALARM 8-09-23 8:10AM SYSTEM PAPER OUT ALARM 8-09-23 8:10AM SYSTEM PRINTER ERROR CLEAR 8-09-23 8:10AM SYSTEM PAPER OUT CLEAR 8-09-23 8:10AM I20600 DEC 14, 2023 9:02 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 TANK ALARM HISTORY TANK 1 SUPREM OVERFILL ALARM DEC 9, 2021 10:35 AM LOW PRODUCT ALARM DEC 9, 2021 10:28 AM INVALID FUEL LEVEL DEC 9, 2021 10:28 AM PROBE OUT DEC 9, 2021 10:38 AM DEC 9, 2021 10:29 AM DELIVERY NEEDED DEC 9, 2021 10:28 AM LOW TEMP WARNING DEC 9, 2021 10:38 AM TANK 2 UNLEADED OVERFILL ALARM JUL 14, 2023 2:48 AM MAR 15, 2023 12:24 AM JAN 2, 2023 3:06 AM LOW PRODUCT ALARM DEC 9, 2021 10:57 AM DEC 9, 2021 10:41 AM INVALID FUEL LEVEL DEC 9, 2021 10:57 AM PROBE OUT DEC 9, 2021 10:56 AM DEC 9, 2021 10:40 AM DELIVERY NEEDED DEC 9, 2021 10:57 AM DEC 9, 2021 10:41 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 DEC 14, 2023 9:02 AM I30200 DEC 14, 2023 9:02 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DISP 1-2 DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 9:02 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 2 DISP 5-6 DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 9:03 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 3 DISP 3-4 DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 9:02 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 4 DISP 7-8 DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 9:04 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 5 DISP 9-10 DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 9:04 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 7 DISP 11-12 DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 9:05 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 9 87 STP DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 9:01 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 10 87 ANN DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 8:53 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 11 87 FILL AUG 20, 2023 7:20 PM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 8:50 AM FUEL ALARM 12 91 ANN DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 8:55 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 13 91 STP DEC 8, 2022 9:11 AM SENSOR OUT ALARM DEC 8, 2022 9:01 AM FUEL ALARM DEC 9, 2021 9:15 AM SENSOR OUT ALARM 14 91 FILL DEC 10, 2023 9:44 AM FUEL ALARM FEB 25, 2023 2:22 AM FUEL ALARM DEC 8, 2022 12:51 PM FUEL ALARM I31600 DEC 14, 2023 9:03 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 FM 1-2 3 FM 5-6 4 FM 7-8 5 FM 9-10 6 FM 11-12 7 FM 3-4 8 PS 1-2 I40200 DEC 14, 2023 9:03 AM I40300 DEC 14, 2023 9:03 AM I34200 DEC 14, 2023 9:03 AM I34700 DEC 14, 2023 9:03 AM IV0100 DEC 14, 2023 9:03 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-12-13 10:04:08 23-12-12 10:04:09 23-12-11 10:04:39 23-12-10 10:03:32 23-11-05 10:04:59 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.30 23-10-17 10:04:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.69 23-10-10 10:04:39 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.58 23-10-09 10:04:37 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.58 23-10-09 10:04:37 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 0.57 23-10-08 10:04:29 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.58 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-09-26 10:04:42 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 23-07-20 10:04:35 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 23-04-19 10:03:16 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 22-12-21 10:04:43 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 84.61 22-11-29 10:02:05 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 292.13 22-10-24 10:01:56 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 204.97 22-10-23 10:02:11 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 151.29 21-08-11 10:05:48 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 21-07-06 10:02:35 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD 21-07-06 10:02:35 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-11-20 10:04:04 READINESS ISD:PP EVR:PP ISD & EVR READY 23-11-19 10:04:13 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-11-18 10:04:28 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-11-17 10:04:36 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-11-16 10:04:37 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-11-16 00:34:08 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-11-16 00:34:08 ISD STARTUP 23-11-16 00:33:57 ISD SHUTDOWN 23-11-15 15:37:54 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-11-15 15:37:54 ISD STARTUP Post Alarm History Responses Received: I10200 DEC 14, 2023 11:13 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 8SMARTSENSOR BD 39616 39566 2 4 PROBE / G.T. 163711 163488 3 INTERSTITIAL BD 201522 201265 4 INTERSTITIAL BD 201289 201148 5 UNUSED 9922524 9849024 6 UNUSED 9907690 9849069 7 UNUSED 9915587 9852272 8 UNUSED 9907646 9843204 9 UNUSED 9907173 9835067 10 RELAY BOARD 14999 15022 11 UNUSED 9912594 9839331 12 UNUSED 9902690 9822999 13 UNUSED 9902021 9841609 14 UNUSED 9903850 9847519 15 UNUSED 9899656 9837549 16 UNUSED 9908935 9849098 COMM 1 ELEC DISP INT. 101163 101138 COMM 2 RS232 SERIAL BD 15022 15022 COMM 3 RS232 SERIAL BD 15044 15044 COMM 4 UNUSED 9906995 9846053 COMM 5 SERIAL SAT BD 480692 480584 COMM 6 UNUSED 9915493 9852211 I90200 DEC 14, 2023 11:13 AM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 DEC 14, 2023 11:13 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L11 PIPE 87 FILL SENSOR OUT ALARM CLEAR 12-14-23 9:49AM L14 PIPE 91 FILL SENSOR OUT ALARM CLEAR 12-14-23 9:49AM L 9 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 12-14-23 9:49AM L13 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 12-14-23 9:49AM L12 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 12-14-23 9:49AM L10 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 12-14-23 9:49AM L 3 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 12-14-23 9:48AM L 2 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 12-14-23 9:48AM L 7 DISP PAN DISP 11-12 SENSOR OUT ALARM CLEAR 12-14-23 9:48AM L 1 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 12-14-23 9:48AM L 5 DISP PAN DISP 9-10 SENSOR OUT ALARM CLEAR 12-14-23 9:48AM L 4 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 12-14-23 9:48AM L 7 DISP PAN DISP 11-12 SENSOR OUT ALARM ALARM 12-14-23 9:48AM L 5 DISP PAN DISP 9-10 SENSOR OUT ALARM ALARM 12-14-23 9:48AM L 4 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 12-14-23 9:48AM L12 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 12-14-23 9:48AM L 3 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 12-14-23 9:48AM L11 PIPE 87 FILL SENSOR OUT ALARM ALARM 12-14-23 9:48AM L10 ANNULAR 87 ANN SENSOR OUT ALARM ALARM 12-14-23 9:48AM L 2 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 12-14-23 9:48AM L14 PIPE 91 FILL SENSOR OUT ALARM ALARM 12-14-23 9:48AM L 9 STP SUMP 87 STP SENSOR OUT ALARM ALARM 12-14-23 9:48AM L 1 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 12-14-23 9:48AM L13 STP SUMP 91 STP SENSOR OUT ALARM ALARM 12-14-23 9:48AM L10 ANNULAR 87 ANN FUEL ALARM CLEAR 12-14-23 9:41AM L10 ANNULAR 87 ANN FUEL ALARM ALARM 12-14-23 9:40AM L12 ANNULAR 91 ANN FUEL ALARM CLEAR 12-14-23 9:37AM L12 ANNULAR 91 ANN FUEL ALARM ALARM 12-14-23 9:37AM L 7 DISP PAN DISP 11-12 FUEL ALARM CLEAR 12-14-23 9:35AM L 7 DISP PAN DISP 11-12 FUEL ALARM ALARM 12-14-23 9:35AM L 5 DISP PAN DISP 9-10 FUEL ALARM CLEAR 12-14-23 9:35AM L 5 DISP PAN DISP 9-10 FUEL ALARM ALARM 12-14-23 9:34AM L 4 DISP PAN DISP 7-8 FUEL ALARM CLEAR 12-14-23 9:34AM L 4 DISP PAN DISP 7-8 FUEL ALARM ALARM 12-14-23 9:34AM L 2 DISP PAN DISP 5-6 FUEL ALARM CLEAR 12-14-23 9:33AM L 2 DISP PAN DISP 5-6 FUEL ALARM ALARM 12-14-23 9:33AM L 3 DISP PAN DISP 3-4 FUEL ALARM CLEAR 12-14-23 9:33AM L 3 DISP PAN DISP 3-4 FUEL ALARM ALARM 12-14-23 9:33AM L 1 DISP PAN DISP 1-2 FUEL ALARM CLEAR 12-14-23 9:32AM L 1 DISP PAN DISP 1-2 FUEL ALARM ALARM 12-14-23 9:32AM L11 PIPE 87 FILL FUEL ALARM CLEAR 12-14-23 9:31AM L11 PIPE 87 FILL FUEL ALARM ALARM 12-14-23 9:31AM L14 PIPE 91 FILL FUEL ALARM CLEAR 12-14-23 9:30AM L14 PIPE 91 FILL FUEL ALARM ALARM 12-14-23 9:30AM L13 STP SUMP 91 STP FUEL ALARM CLEAR 12-14-23 9:30AM L13 STP SUMP 91 STP FUEL ALARM ALARM 12-14-23 9:30AM L 9 STP SUMP 87 STP FUEL ALARM CLEAR 12-14-23 9:29AM L 9 STP SUMP 87 STP FUEL ALARM ALARM 12-14-23 9:29AM L14 PIPE 91 FILL FUEL ALARM CLEAR 12-13-23 9:08AM L14 PIPE 91 FILL FUEL ALARM ALARM 12-10-23 9:44AM I11200 DEC 14, 2023 11:13 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD DEGRD PRES WARN CLEAR 11-05-23 6:16PM OTHER ISD DEGRD PRES WARN ALARM 11-05-23 10:04AM OTHER ISD GROSS PRES WARN CLEAR 10-18-23 10:00AM OTHER ISD GROSS PRES WARN ALARM 10-17-23 10:04AM OTHER ISD GROSS PRES WARN CLEAR 10-10-23 10:16AM h 8 OTHER FP8: BLEND3 FLOW COLLECT WARN CLEAR 10-10-23 10:00AM h 8 OTHER FP8: BLEND3 FLOW COLLECT WARN ALARM 10-09-23 10:04AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 10-09-23 10:00AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 10-08-23 10:04AM OTHER ISD GROSS PRES WARN ALARM 10-04-23 10:04AM SYSTEM PRINTER ERROR CLEAR 9-28-23 6:58AM SYSTEM PAPER OUT CLEAR 9-28-23 6:58AM SYSTEM PAPER OUT ALARM 9-28-23 6:58AM SYSTEM PRINTER ERROR ALARM 9-28-23 6:58AM SYSTEM PRINTER ERROR CLEAR 9-28-23 6:57AM SYSTEM PRINTER ERROR ALARM 9-28-23 6:57AM SYSTEM PRINTER ERROR CLEAR 9-28-23 6:57AM SYSTEM PAPER OUT CLEAR 9-28-23 6:57AM SYSTEM PRINTER ERROR ALARM 9-28-23 6:56AM SYSTEM PAPER OUT ALARM 9-28-23 6:56AM OTHER ISD VAPOR LEAK WARN CLEAR 9-26-23 10:04AM OTHER ISD VAPOR LEAK WARN ALARM 9-19-23 10:05AM SYSTEM PRINTER ERROR CLEAR 9-04-23 9:37AM SYSTEM PAPER OUT CLEAR 9-04-23 9:37AM SYSTEM PAPER OUT ALARM 9-04-23 9:37AM SYSTEM PRINTER ERROR ALARM 9-04-23 9:20AM SYSTEM PRINTER ERROR CLEAR 9-01-23 7:09PM SYSTEM PAPER OUT CLEAR 9-01-23 7:09PM SYSTEM PRINTER ERROR ALARM 9-01-23 7:08PM SYSTEM PAPER OUT ALARM 9-01-23 7:08PM SYSTEM PRINTER ERROR CLEAR 9-01-23 7:08PM SYSTEM PAPER OUT CLEAR 9-01-23 7:08PM SYSTEM PRINTER ERROR ALARM 9-01-23 7:07PM SYSTEM PAPER OUT ALARM 9-01-23 7:07PM SYSTEM PRINTER ERROR CLEAR 8-09-23 10:22PM SYSTEM PAPER OUT CLEAR 8-09-23 10:22PM SYSTEM PRINTER ERROR ALARM 8-09-23 10:22PM SYSTEM PAPER OUT ALARM 8-09-23 10:22PM SYSTEM PRINTER ERROR CLEAR 8-09-23 8:10AM SYSTEM PAPER OUT CLEAR 8-09-23 8:10AM SYSTEM PAPER OUT ALARM 8-09-23 8:10AM SYSTEM PRINTER ERROR ALARM 8-09-23 8:10AM SYSTEM PRINTER ERROR CLEAR 8-09-23 8:10AM SYSTEM PRINTER ERROR ALARM 8-09-23 8:10AM SYSTEM PRINTER ERROR CLEAR 8-09-23 8:10AM SYSTEM PAPER OUT CLEAR 8-09-23 8:10AM SYSTEM PRINTER ERROR ALARM 8-09-23 8:10AM SYSTEM PAPER OUT ALARM 8-09-23 8:10AM SYSTEM PRINTER ERROR CLEAR 8-09-23 8:10AM SYSTEM PAPER OUT CLEAR 8-09-23 8:10AM I20600 DEC 14, 2023 11:14 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 TANK ALARM HISTORY TANK 1 SUPREM OVERFILL ALARM DEC 9, 2021 10:35 AM LOW PRODUCT ALARM DEC 9, 2021 10:28 AM INVALID FUEL LEVEL DEC 9, 2021 10:28 AM PROBE OUT DEC 9, 2021 10:38 AM DEC 9, 2021 10:29 AM DELIVERY NEEDED DEC 9, 2021 10:28 AM LOW TEMP WARNING DEC 9, 2021 10:38 AM TANK 2 UNLEADED OVERFILL ALARM JUL 14, 2023 2:48 AM MAR 15, 2023 12:24 AM JAN 2, 2023 3:06 AM LOW PRODUCT ALARM DEC 9, 2021 10:57 AM DEC 9, 2021 10:41 AM INVALID FUEL LEVEL DEC 9, 2021 10:57 AM PROBE OUT DEC 9, 2021 10:56 AM DEC 9, 2021 10:40 AM DELIVERY NEEDED DEC 9, 2021 10:57 AM DEC 9, 2021 10:41 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 DEC 14, 2023 11:14 AM I30200 DEC 14, 2023 11:14 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DISP 1-2 DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:32 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 2 DISP 5-6 DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:33 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 3 DISP 3-4 DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:33 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 4 DISP 7-8 DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:34 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 5 DISP 9-10 DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:34 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 7 DISP 11-12 DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:35 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 9 87 STP DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:29 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 10 87 ANN DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:40 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 11 87 FILL DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:31 AM FUEL ALARM AUG 20, 2023 7:20 PM FUEL ALARM 12 91 ANN DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:37 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 13 91 STP DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:30 AM FUEL ALARM DEC 8, 2022 9:11 AM SENSOR OUT ALARM 14 91 FILL DEC 14, 2023 9:48 AM SENSOR OUT ALARM DEC 14, 2023 9:30 AM FUEL ALARM DEC 10, 2023 9:44 AM FUEL ALARM I31600 DEC 14, 2023 11:14 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 FM 1-2 3 FM 5-6 4 FM 7-8 5 FM 9-10 6 FM 11-12 7 FM 3-4 8 PS 1-2 I40200 DEC 14, 2023 11:14 AM I40300 DEC 14, 2023 11:14 AM I34200 DEC 14, 2023 11:14 AM I34700 DEC 14, 2023 11:14 AM IV0100 DEC 14, 2023 11:14 AM 208402 CHVRNSAMCO 2 3300 WHITE LN. BAKERSFIELD,CA 93309 661-827 0487 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME : 99% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-12-13 10:04:08 23-12-12 10:04:09 23-12-11 10:04:39 23-12-10 10:03:32 23-11-05 10:04:59 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.30 23-10-17 10:04:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.69 23-10-10 10:04:39 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.58 23-10-09 10:04:37 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.58 23-10-09 10:04:37 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 0.57 23-10-08 10:04:29 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.58 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-09-26 10:04:42 VAPOR CONTAINMENT LEAKAGE GROSS FAIL 23-07-20 10:04:35 FLOW PERFORMANCE HOSE BLOCKAGE FP 4 BLEND3 23-04-19 10:03:16 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 22-12-21 10:04:43 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 84.61 22-11-29 10:02:05 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 292.13 22-10-24 10:01:56 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 204.97 22-10-23 10:02:11 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 151.29 21-08-11 10:05:48 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 21-07-06 10:02:35 A/L RATIO GROSS BLOCKAGE FP12 BLEND3 BLKD 21-07-06 10:02:35 A/L RATIO GROSS BLOCKAGE FP11 BLEND3 BLKD SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-12-14 10:04:41 READINESS ISD:PP EVR:PP ISD & EVR READY 23-12-14 09:49:35 READINESS ISD:PP EVR:NN EVR READINESS PENDING 23-12-14 09:49:35 ISD STARTUP 23-12-14 09:49:27 ISD SHUTDOWN 23-11-20 10:04:04 READINESS ISD:PP EVR:PP ISD & EVR READY 23-11-19 10:04:13 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-11-18 10:04:28 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-11-17 10:04:36 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-11-16 10:04:37 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-11-16 00:34:08 READINESS ISD:PP EVR:NN EVR READINESS PENDING