HomeMy WebLinkAbout2024 FMCAppendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10884616 1/10/2024
Samco Buena Vista
825 Buena Vista Rd Bakersfield 93311
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fisher
1073967
10278702 3/10/25
Veeder Root - C33847 07/24/25
Vaporless Manufacturing LLC 03/14/25
EMCO #1142
1/10/2024 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS350
335.00
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208/304 DISPENSER 15/16
L2 208/304 DISPENSER 13/14
L3 208/304 DISPENSER 9/10
L4 208/304 DISPENSER 11/12
L5 208/304 DISPENSER 7/8
L6 208/304 DISPENSER 5/6
L7 208/304 DISPENSER 1/2
L8 208/304 DISPENSER 3/4
L9 208/304 UNLEADED STP
L10 208/304 UNLEADED FILL
L11 208/304 PREMIUM STP
L12 208/304 PREMIUM FILL
L13 208/304 DIESEL STP
L14 208/304 DIESEL FILL
L15 208/304 VENT BOX
S11 463/464 Supreme Vent
S17 420 Unleaded Tank
S18 463/464 Unleaded Product
S19 463/464 Vapor Return
S20 420 Supreme-Diesel Tank
S21 463/464 Premium Product
S22 463/464 Unleaded Vent
S23 463/464 Diesel Product
S24 463/464 Diesel Vent
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 Unleaded
T2 FX1V 91 Premium
T3 LD2000 Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Samco Buena Vista825 Buena Vista RdBakersfield108846163/47/8 11/12MPDMPDMPDMPDMPDMPDMPDMPD1/25/69/1013/1415/16ProductProductProductProductProductProductProductProductMark Fisher
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10884616 1/10/2024
Samco Buena Vista
825 Buena Vista Rd Bakersfield 93311
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fisher
1073967
10278702 3/10/25
EMCO #3308 3/17/25
PEI1200, 1 hour hydrostatic test All Spill Buckets
1/10/2024 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
87
EMCO
91
EMCO
Diesel
EMCO
Buena SamCo Setup
Responses Received:
200
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
JAN 10, 2024 9:12 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED 12963 74.09 0.0 54.5 7037
2 PREMIUM 6773 66.09 0.0 62.6 5227
3 DIESEL 5612 79.34 0.0 62.7 2388
I90500
JAN 10, 2024 9:12 AM
SOFTWARE REVISION LEVEL
VERSION 335.00
SOFTWARE# 346335-100-A
CREATED - 18.08.27.10.22
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JAN 10, 2024 9:12 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JAN 10, 2024 9:12 AM
SHIFT TIME 1 : DISABLED
I50202
JAN 10, 2024 9:12 AM
SHIFT TIME 2 : DISABLED
I50203
JAN 10, 2024 9:12 AM
SHIFT TIME 3 : DISABLED
I50204
JAN 10, 2024 9:12 AM
SHIFT TIME 4 : DISABLED
I54600
JAN 10, 2024 9:12 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JAN 10, 2024 9:12 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JAN 10, 2024 9:12 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JAN 10, 2024 9:12 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JAN 10, 2024 9:12 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JAN 10, 2024 9:12 AM
PRINT TC VOLUMES
ENABLED
I50E00
JAN 10, 2024 9:12 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JAN 10, 2024 9:12 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JAN 10, 2024 9:12 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JAN 10, 2024 9:12 AM
DAYLIGHT SAVING TIME
ENABLED OFF
I51B00
JAN 10, 2024 9:12 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JAN 10, 2024 9:12 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JAN 10, 2024 9:12 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JAN 10, 2024 9:12 AM
TANK CHART SECURITY
DISABLED
I5BD00
JAN 10, 2024 9:13 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JAN 10, 2024 9:13 AM
MASS/DENSITY
DISABLED
I88101
JAN 10, 2024 9:13 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JAN 10, 2024 9:13 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
JAN 10, 2024 9:13 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 1200
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JAN 10, 2024 9:13 AM
I88105
JAN 10, 2024 9:13 AM
PORT SETTINGS:
COMM BOARD : 5 (S-SAT )
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
DTR NORMAL STATE: HIGH
I88106
JAN 10, 2024 9:13 AM
I52000
JAN 10, 2024 9:13 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE AUG 30, 2022 DISABLED
2 ON DATE AUG 30, 2022 DISABLED
3 ON DATE AUG 30, 2022 DISABLED
4 ON DATE AUG 30, 2022 DISABLED
5 ON DATE AUG 30, 2022 DISABLED
6 ON DATE AUG 30, 2022 DISABLED
7 ON DATE AUG 30, 2022 DISABLED
8 ON DATE JAN 26, 2022 11:13 AM
I60100
JAN 10, 2024 9:13 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED ON
2 PREMIUM ON
3 DIESEL ON
4 OFF
I60200
JAN 10, 2024 9:13 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4
I60300
JAN 10, 2024 9:13 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL 3
4 4
I60900
JAN 10, 2024 9:13 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED 0.000700
2 PREMIUM 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
JAN 10, 2024 9:13 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED 120.00
2 PREMIUM 120.00
3 DIESEL 120.00
4 0.00
I60A00
JAN 10, 2024 9:13 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED
1 PT 20000 2 PREMIUM 1 PT 12000 3 DIESEL
1 PT 8000 4 1 PT 0
I60400
JAN 10, 2024 9:13 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 20000
2 PREMIUM 12000
3 DIESEL 8000
4 0
I60500
JAN 10, 2024 9:13 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 20000 0 0 0
2 PREMIUM 12000 0 0 0
3 DIESEL 8000 0 0 0
4 0 0 0 0
I60600
JAN 10, 2024 9:13 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED 20000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 PREMIUM 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DIESEL 8000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JAN 10, 2024 9:13 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NO
2 PREMIUM NO
3 DIESEL NO
4 NO
I62F00
JAN 10, 2024 9:13 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED 4.0 IN. PS
2 PREMIUM 4.0 IN. PS
3 DIESEL 4.0 IN. PS
I62700
JAN 10, 2024 9:13 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 3.0
2 PREMIUM 3.0
3 DIESEL 3.0
I64200
JAN 10, 2024 9:13 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED LOW
2 PREMIUM LOW
3 DIESEL LOW
I62400
JAN 10, 2024 9:13 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED 4.0
2 PREMIUM 4.0
3 DIESEL 4.0
I62800
JAN 10, 2024 9:13 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 20000
2 PREMIUM 12000
3 DIESEL 8000
4 0
I62300
JAN 10, 2024 9:13 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 18000
2 PREMIUM 10800
3 DIESEL 7200
4 0
I62200
JAN 10, 2024 9:13 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 19000
2 PREMIUM 11400
3 DIESEL 7600
4 0
I62900
JAN 10, 2024 9:13 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 2000
2 PREMIUM 1200
3 DIESEL 800
4 0
I62100
JAN 10, 2024 9:13 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1000
2 PREMIUM 1000
3 DIESEL 500
4 0
I62600
JAN 10, 2024 9:13 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I62500
JAN 10, 2024 9:13 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 99
2 PREMIUM 99
3 DIESEL 99
4 99
I60800
JAN 10, 2024 9:13 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 0.00
3 DIESEL 0.00
4 0.00
I60B00
JAN 10, 2024 9:13 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JAN 10, 2024 9:13 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED 0.00
2 PREMIUM 0.00
3 DIESEL 0.00
4 0.00
I61200
JAN 10, 2024 9:13 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NONE NONE
2 PREMIUM NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
JAN 10, 2024 9:13 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 200
2 PREMIUM 120
3 DIESEL 80
4 0
I62A00
JAN 10, 2024 9:13 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED 200
2 PREMIUM 120
3 DIESEL 80
4 0
I62C00
JAN 10, 2024 9:13 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED STANDARD
2 PREMIUM STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
JAN 10, 2024 9:13 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JAN 10, 2024 9:13 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED OFF OFF
2 PREMIUM OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
JAN 10, 2024 9:13 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I63200
JAN 10, 2024 9:13 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED OFF
2 PREMIUM OFF
3 DIESEL OFF
4 OFF
I61000
JAN 10, 2024 9:13 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63A00
JAN 10, 2024 9:13 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED 10.00%
2 PREMIUM 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
JAN 10, 2024 9:13 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ANNUALLY: ALL TANK
JAN WEEK 1 MON
START TIME : 2:00 AM
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:ENABLED
I61300
JAN 10, 2024 9:13 AM
CSLD PROBABLITY OF DETECTION
I61400
JAN 10, 2024 9:13 AM
CSLD CLIMATE FACTOR
I61600
JAN 10, 2024 9:13 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED IMMEDIATE
2 PREMIUM IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
JAN 10, 2024 9:13 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED ENABLED
2 PREMIUM ENABLED
3 DIESEL ENABLED
4 ENABLED
I61B00
JAN 10, 2024 9:13 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JAN 10, 2024 9:13 AM
CSLD REPORT ONLY
I62B00
JAN 10, 2024 9:13 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED ??? 0, 0
2 PREMIUM ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
JAN 10, 2024 9:13 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JAN 10, 2024 9:13 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 0
2 PREMIUM 0
3 DIESEL 0
4 0
I63500
JAN 10, 2024 9:13 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED 1
2 PREMIUM 1
3 DIESEL 1
4 1
I63900
JAN 10, 2024 9:13 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED
END FACTOR: NONE
2 PREMIUM
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
JAN 10, 2024 9:13 AM
I77700
JAN 10, 2024 9:13 AM
I77800
JAN 10, 2024 9:13 AM
I78C00
JAN 10, 2024 9:13 AM
I78300
JAN 10, 2024 9:13 AM
I78F00
JAN 10, 2024 9:13 AM
I78700
JAN 10, 2024 9:13 AM
I70200
JAN 10, 2024 9:13 AM
LIQUID LABEL
DEVICE LABEL
1 DISP. 15-16
2 DISP. 13-14
3 DISP. 9-10
4 DISP. 11-12
5 DISP. 7-8
6 DISP. 5-6
7 DISP. 1-2
8 DISP. 3-4
9 UNL STP
10 UNL FILL
11 PREMIUM STP
12 PREMIUM FILL
13 DIESEL STP
14 DIESEL FILL
15 VENT BOX
16
I70300
JAN 10, 2024 9:13 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 DISP. 15-16 DW SUMP 2-1
2 DISP. 13-14 DW SUMP 2-1
3 DISP. 9-10 DW SUMP 2-1
4 DISP. 11-12 DW SUMP 2-1
5 DISP. 7-8 DW SUMP 2-1
6 DISP. 5-6 DW SUMP 2-1
7 DISP. 1-2 DW SUMP 2-1
8 DISP. 3-4 DW SUMP 2-1
9 UNL STP DW SUMP 2-1
10 UNL FILL DW SUMP 2-1
11 PREMIUM STP DW SUMP 2-1
12 PREMIUM FILL DW SUMP 2-1
13 DIESEL STP DW SUMP 2-1
14 DIESEL FILL DW SUMP 2-1
15 VENT BOX DW SUMP 2-1
16 TRI-STATE (SINGLE FLOAT)
I70400
JAN 10, 2024 9:13 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 DISP. 15-16 DISPENSER PAN
2 DISP. 13-14 DISPENSER PAN
3 DISP. 9-10 DISPENSER PAN
4 DISP. 11-12 DISPENSER PAN
5 DISP. 7-8 DISPENSER PAN
6 DISP. 5-6 DISPENSER PAN
7 DISP. 1-2 DISPENSER PAN
8 DISP. 3-4 DISPENSER PAN
9 UNL STP STP SUMP
10 UNL FILL OTHER SENSORS
11 PREMIUM STP STP SUMP
12 PREMIUM FILL STP SUMP
13 DIESEL STP STP SUMP
14 DIESEL FILL OTHER SENSORS
15 VENT BOX OTHER SENSORS
16 OTHER SENSORS
I74200
JAN 10, 2024 9:13 AM
I74300
JAN 10, 2024 9:13 AM
I74400
JAN 10, 2024 9:13 AM
I74700
JAN 10, 2024 9:13 AM
I74800
JAN 10, 2024 9:13 AM
I74900
JAN 10, 2024 9:13 AM
I7BC00
JAN 10, 2024 9:13 AM
I80200
JAN 10, 2024 9:13 AM
I80300
JAN 10, 2024 9:13 AM
I80400
JAN 10, 2024 9:13 AM
I80700
JAN 10, 2024 9:13 AM
RELAY LABEL
DEVICE LABEL
1 UNLEADED
2 PREMIUM
3 DIESEL
4 OVERFILL ALARM
I80900
JAN 10, 2024 9:13 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 UNLEADED NORMALLY OPEN
2 PREMIUM NORMALLY OPEN
3 DIESEL NORMALLY OPEN
4 OVERFILL ALARM NORMALLY OPEN
I80B00
JAN 10, 2024 9:13 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 UNLEADED 1
2 PREMIUM 2
3 DIESEL 3
4 OVERFILL ALARM NONE
I80A00
JAN 10, 2024 9:13 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 UNLEADED PUMP CONTROL OUTPUT
2 PREMIUM PUMP CONTROL OUTPUT
3 DIESEL PUMP CONTROL OUTPUT
4 OVERFILL ALARM STANDARD
I80C00
JAN 10, 2024 9:13 AM
I80800
JAN 10, 2024 9:13 AM
RELAY SETUP REPORT
R 1:UNLEADED
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L11:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L11:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:PREMIUM
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 2:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 9:FUEL ALARM
L11:FUEL ALARM
L 1:SENSOR OUT ALARM
L 2:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L 1:SHORT ALARM
L 2:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
L 9:SHORT ALARM
L11:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:DIESEL
TYPE:
PUMP CONTROL OUTPUT
TANK #: 3
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 8:FUEL ALARM
L13:FUEL ALARM
L 1:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 1:SHORT ALARM
L 8:SHORT ALARM
L13:SHORT ALARM
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
I79000
JAN 10, 2024 9:14 AM
EDIM:1 VR:349867-001-D TD:17.02.14.08.38
I79100
JAN 10, 2024 9:14 AM
I72300
JAN 10, 2024 9:14 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 DISP. 15-16 FM AIR FLOW METER
02 DISP. 13-14 FM AIR FLOW METER
03 DISP. 9-10 FM AIR FLOW METER
04 DISP. 11-12 FM AIR FLOW METER
05 DISP. 7-8 FM AIR FLOW METER
06 DISP. 5-6 FM AIR FLOW METER
07 DISP. 1-2 FM AIR FLOW METER
08 ATM ATM P SENSOR
09 DISP. 3-4 FM AIR FLOW METER
10 DISP. 3-4 PS VAPOR PRESSURE
11 SUPREME VENT VAC SENSOR
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNL. TANK VAC SENSOR
18 UNL. PRODUCT VAC SENSOR
19 VAPOR RETURN VAC SENSOR
20 SUPREME-DIESEL TANK VAC SENSOR
21 PREMIUM PRODUCT VAC SENSOR
22 UNL. VENT VAC SENSOR
23 DIESEL PRODUCT VAC SENSOR
24 DIESEL VENT VAC SENSOR
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JAN 10, 2024 9:14 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
JAN 10, 2024 9:14 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JAN 10, 2024 9:14 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
VAPOR PROCESSOR TYPE
NONE
IV4700
JAN 10, 2024 9:14 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
ASSESSMENT TIME
START TIME: 10:01 AM
TIME DELAY MINUTES: 1
IV5200
JAN 10, 2024 9:14 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
ACCEPT HIGH ORVR: YES
IV4A00
JAN 10, 2024 9:14 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 07 02 BLEND3
02 02 02 07 02 BLEND3
03 03 03 08 02 BLEND3
04 04 04 08 02 BLEND3
05 05 05 06 02 BLEND3
06 06 06 06 02 BLEND3
07 07 07 05 02 BLEND3
08 08 08 05 02 BLEND3
09 09 09 03 02 BLEND3
10 16 10 03 02 BLEND3
11 17 11 04 02 BLEND3
12 18 12 04 02 BLEND3
13 19 13 02 02 BLEND3
14 20 14 02 02 BLEND3
15 21 15 01 02 BLEND3
16 22 16 01 02 BLEND3
IV4B00
JAN 10, 2024 9:14 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 07 02/01 09/01 01/01 xx/xx
02 07 02/02 09/02 01/02 xx/xx
03 08 02/03 09/03 01/03 xx/xx
04 08 02/04 09/04 01/04 xx/xx
05 06 02/05 09/05 01/05 xx/xx
06 06 02/06 09/06 01/06 xx/xx
07 05 02/07 09/07 01/07 xx/xx
08 05 02/08 09/08 01/08 xx/xx
09 03 02/09 09/09 01/09 xx/xx
16 03 02/10 09/10 01/10 xx/xx
17 04 02/11 09/11 01/11 xx/xx
18 04 02/12 09/12 01/12 xx/xx
19 02 02/13 09/13 01/13 xx/xx
20 02 02/14 09/14 01/14 xx/xx
21 01 02/15 09/15 01/15 xx/xx
22 01 02/16 09/16 01/16 xx/xx
IV4900
JAN 10, 2024 9:14 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JAN 10, 2024 9:14 AM
ISD VERSION: 01.05
Buena SamCo Alarm History
Responses Received:
I10200
JAN 10, 2024 9:15 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164370 163547
2 7SMARTSENSOR BD 511611 511039
3 8SMARTSENSOR BD 39931 39838
4 8SMARTSENSOR BD 39740 39709
5 INTERSTITIAL BD 202409 201973
6 INTERSTITIAL BD 202694 202107
7 UNUSED 9797011 9670977
8 UNUSED 9795854 9646894
9 RELAY BOARD 15197 15172
10 STP SENSE BOARD 33411 33390
11 UNUSED 9809786 9655715
12 UNUSED 9797780 9657472
13 UNUSED 9787330 9679820
14 UNUSED 9768975 9668164
15 UNUSED 9773180 9649073
16 UNUSED 9784934 9642945
COMM 1 ELEC DISP INT. 101730 101655
COMM 2 RS232 SERIAL BD 15134 15129
COMM 3 RS232 SERIAL BD 15049 15043
COMM 4 UNUSED 9797486 9692954
COMM 5 SERIAL SAT BD 487156 487293
COMM 6 UNUSED 9797843 9649523
I90200
JAN 10, 2024 9:15 AM
SOFTWARE REVISION LEVEL
VERSION 335.00
SOFTWARE# 346335-100-A
CREATED - 18.08.27.10.22
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JAN 10, 2024 9:15 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK UNLEADED OVERFILL ALARM CLEAR 1-03-24 10:16AM
T 1 TANK UNLEADED OVERFILL ALARM ALARM 1-03-24 10:14AM
L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 12-16-23 2:30PM
T 1 TANK UNLEADED OVERFILL ALARM CLEAR 12-16-23 6:34AM
T 1 TANK UNLEADED OVERFILL ALARM ALARM 12-16-23 6:26AM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-15-23 1:54PM
L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM CLEAR 12-15-23 10:56AM
L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM ALARM 12-15-23 8:13AM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-14-23 10:58PM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-14-23 4:03PM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-13-23 11:20PM
L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 12-13-23 9:21PM
L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 12-13-23 5:41PM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-13-23 1:52PM
L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 12-13-23 7:03AM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-13-23 1:47AM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-12-23 12:21PM
T 3 TANK DIESEL SUDDEN LOSS ALARM CLEAR 12-12-23 4:33AM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-12-23 3:54AM
T 3 TANK DIESEL LOW PRODUCT ALARM CLEAR 12-12-23 3:14AM
T 3 TANK DIESEL SUDDEN LOSS ALARM ALARM 12-12-23 3:01AM
T 3 TANK DIESEL LOW PRODUCT ALARM ALARM 12-12-23 3:00AM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-11-23 12:58PM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-11-23 12:09AM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-10-23 3:06PM
L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 12-10-23 1:59PM
L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 12-10-23 1:56AM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-09-23 9:41PM
L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 12-09-23 3:46PM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-09-23 3:28PM
L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 12-09-23 9:31AM
L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-09-23 1:49AM
T 1 TANK UNLEADED OVERFILL ALARM CLEAR 11-24-23 7:07AM
T 1 TANK UNLEADED OVERFILL ALARM ALARM 11-24-23 7:04AM
T 1 TANK UNLEADED OVERFILL ALARM CLEAR 11-14-23 8:02AM
T 1 TANK UNLEADED OVERFILL ALARM ALARM 11-14-23 7:56AM
h12 OTHER FP12: BLEND3 FLOW COLLECT FAIL CLEAR 11-01-23 11:00AM
h12 OTHER FP12: BLEND3 FLOW COLLECT FAIL ALARM 11-01-23 10:03AM
L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 10-31-23 9:51AM
L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM CLEAR 10-31-23 9:38AM
L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 10-29-23 4:14AM
L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM ALARM 10-29-23 1:37AM
L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM CLEAR 10-28-23 4:39PM
L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM ALARM 10-28-23 9:56AM
T 1 TANK UNLEADED OVERFILL ALARM CLEAR 10-16-23 3:57AM
T 1 TANK UNLEADED OVERFILL ALARM ALARM 10-16-23 3:52AM
L 1 DISP PAN DISP. 15-16 LOW LIQUID ALARM CLEAR 10-04-23 11:54AM
L 1 DISP PAN DISP. 15-16 LOW LIQUID ALARM ALARM 10-04-23 11:49AM
L 1 DISP PAN DISP. 15-16 LOW LIQUID ALARM CLEAR 10-04-23 11:42AM
L 1 DISP PAN DISP. 15-16 LOW LIQUID ALARM ALARM 10-04-23 11:42AM
I11200
JAN 10, 2024 9:15 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h11 OTHER FP11: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM
h10 OTHER FP10: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM
h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM
OTHER ISD VAPOR LEAK WARN ALARM 1-06-24 10:02AM
h11 OTHER FP11: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM
h10 OTHER FP10: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM
h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM
h16 OTHER FP16: BLEND3 FLOW COLLECT WARN CLEAR 1-03-24 10:01AM
h16 OTHER FP16: BLEND3 FLOW COLLECT WARN ALARM 1-02-24 10:02AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 1-01-24 10:01AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 1-01-24 10:01AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 12-31-23 10:03AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 12-31-23 10:03AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-31-23 10:01AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-30-23 10:04AM
h10 OTHER FP10: BLEND3 FLOW COLLECT WARN CLEAR 12-29-23 10:01AM
h10 OTHER FP10: BLEND3 FLOW COLLECT WARN ALARM 12-28-23 10:04AM
h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN CLEAR 12-27-23 10:01AM
h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN ALARM 12-26-23 10:03AM
SYSTEM PRINTER ERROR CLEAR 12-21-23 7:25AM
SYSTEM PAPER OUT CLEAR 12-21-23 7:25AM
SYSTEM PRINTER ERROR ALARM 12-21-23 7:23AM
SYSTEM PAPER OUT ALARM 12-21-23 7:23AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-20-23 10:01AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-19-23 10:03AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 12-16-23 9:51AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 12-16-23 6:30AM
T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 12-12-23 3:14AM
T 3 TANK DIESEL DELIVERY NEEDED CLEAR 12-12-23 3:14AM
T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 12-12-23 3:00AM
T 3 TANK DIESEL DELIVERY NEEDED ALARM 12-12-23 3:00AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 12-11-23 10:01AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 12-10-23 10:03AM
SYSTEM PRINTER ERROR CLEAR 12-09-23 3:50PM
SYSTEM PRINTER ERROR ALARM 12-09-23 3:49PM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-07-23 10:01AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-06-23 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 12-06-23 6:19AM
OTHER ISD GROSS PRES WARN ALARM 12-05-23 10:03AM
h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN CLEAR 12-04-23 10:01AM
h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN ALARM 12-03-23 10:04AM
h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN CLEAR 12-02-23 10:01AM
h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN ALARM 12-01-23 10:04AM
SYSTEM PRINTER ERROR CLEAR 11-28-23 12:54PM
SYSTEM PAPER OUT CLEAR 11-28-23 12:54PM
SYSTEM PRINTER ERROR ALARM 11-28-23 12:54PM
SYSTEM PAPER OUT ALARM 11-28-23 12:54PM
OTHER ISD GROSS PRES WARN CLEAR 11-22-23 6:27AM
OTHER ISD GROSS PRES WARN ALARM 11-20-23 10:03AM
h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN CLEAR 11-20-23 10:01AM
I20600
JAN 10, 2024 9:15 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JAN 3, 2024 10:14 AM
DEC 16, 2023 6:26 AM
NOV 24, 2023 7:04 AM
LOW PRODUCT ALARM MAR 13, 2023 7:04 PM
HIGH PRODUCT ALARM DEC 16, 2023 6:30 AM
NOV 14, 2023 7:59 AM
INVALID FUEL LEVEL MAR 13, 2023 8:41 PM
DELIVERY NEEDED MAR 13, 2023 4:59 PM
TANK 2 PREMIUM
LOW PRODUCT ALARM AUG 29, 2023 6:07 PM
DELIVERY NEEDED AUG 29, 2023 4:38 PM
TANK 3 DIESEL
LOW PRODUCT ALARM DEC 12, 2023 3:00 AM
SUDDEN LOSS ALARM DEC 12, 2023 3:01 AM
INVALID FUEL LEVEL DEC 12, 2023 3:00 AM
DELIVERY NEEDED DEC 12, 2023 3:00 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JAN 10, 2024 9:16 AM
I30200
JAN 10, 2024 9:16 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP. 15-16
OCT 4, 2023 11:49 AM LOW LIQUID ALARM
OCT 4, 2023 11:42 AM LOW LIQUID ALARM
OCT 4, 2023 11:31 AM LOW LIQUID ALARM
2 DISP. 13-14
MAR 2, 2023 9:20 AM FUEL ALARM
MAR 2, 2023 9:07 AM SETUP DATA WARNING
3 DISP. 9-10
DEC 15, 2023 8:13 AM LOW LIQUID ALARM
OCT 29, 2023 1:37 AM LOW LIQUID ALARM
OCT 28, 2023 9:56 AM LOW LIQUID ALARM
4 DISP. 11-12
MAR 2, 2023 9:18 AM FUEL ALARM
MAR 2, 2023 9:07 AM SETUP DATA WARNING
5 DISP. 7-8
MAR 2, 2023 9:17 AM FUEL ALARM
MAR 2, 2023 9:10 AM SENSOR OUT ALARM
MAR 2, 2023 9:07 AM SETUP DATA WARNING
6 DISP. 5-6
MAR 2, 2023 9:18 AM FUEL ALARM
MAR 2, 2023 9:10 AM SENSOR OUT ALARM
MAR 2, 2023 9:07 AM SETUP DATA WARNING
7 DISP. 1-2
DEC 14, 2023 10:58 PM LOW LIQUID ALARM
DEC 13, 2023 11:20 PM LOW LIQUID ALARM
DEC 13, 2023 1:47 AM LOW LIQUID ALARM
8 DISP. 3-4
MAR 2, 2023 9:16 AM FUEL ALARM
MAR 2, 2023 9:10 AM SENSOR OUT ALARM
MAR 2, 2023 9:07 AM SETUP DATA WARNING
9 UNL STP
MAR 2, 2023 9:13 AM FUEL ALARM
MAR 2, 2023 9:10 AM SENSOR OUT ALARM
MAR 2, 2023 9:07 AM SETUP DATA WARNING
10 UNL FILL
DEC 13, 2023 9:21 PM LOW LIQUID ALARM
DEC 13, 2023 7:03 AM LOW LIQUID ALARM
DEC 10, 2023 1:56 AM LOW LIQUID ALARM
11 PREMIUM STP
MAR 2, 2023 9:14 AM FUEL ALARM
MAR 2, 2023 9:10 AM SENSOR OUT ALARM
MAR 2, 2023 9:07 AM SETUP DATA WARNING
12 PREMIUM FILL
SEP 7, 2023 8:56 AM LOW LIQUID ALARM
SEP 7, 2023 8:55 AM LOW LIQUID ALARM
SEP 2, 2023 1:03 PM LOW LIQUID ALARM
13 DIESEL STP
MAR 2, 2023 9:13 AM FUEL ALARM
MAR 2, 2023 9:10 AM SENSOR OUT ALARM
MAR 2, 2023 9:07 AM SETUP DATA WARNING
14 DIESEL FILL
AUG 20, 2023 8:09 PM FUEL ALARM
MAR 2, 2023 9:13 AM FUEL ALARM
MAR 2, 2023 9:07 AM SETUP DATA WARNING
15 VENT BOX
MAR 2, 2023 9:07 AM SETUP DATA WARNING
I31600
JAN 10, 2024 9:16 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP. 15-16 FM
2 DISP. 13-14 FM
3 DISP. 9-10 FM
4 DISP. 11-12 FM
5 DISP. 7-8 FM
6 DISP. 5-6 FM
7 DISP. 1-2 FM
8 ATM
9 DISP. 3-4 FM
10 DISP. 3-4 PS
11 SUPREME VENT
JUN 14, 2023 1:54 PM COMMUNICATION ALARM
JUN 14, 2023 1:47 PM COMMUNICATION ALARM
17 UNL. TANK
APR 11, 2023 2:22 PM SENSOR FAULT ALARM
APR 11, 2023 1:08 PM SENSOR FAULT ALARM
APR 11, 2023 1:03 PM NO VACUUM ALARM
18 UNL. PRODUCT
JUN 22, 2023 9:41 AM NO VACUUM ALARM
JUN 16, 2023 10:00 AM NO VACUUM ALARM
JUN 14, 2023 2:55 PM NO VACUUM ALARM
19 VAPOR RETURN
JUN 14, 2023 2:55 PM NO VACUUM ALARM
APR 11, 2023 12:32 PM NO VACUUM ALARM
APR 11, 2023 12:24 PM SENSOR FAULT ALARM
20 SUPREME-DIESEL TANK
21 PREMIUM PRODUCT
22 UNL. VENT
JUN 16, 2023 8:30 AM NO VACUUM ALARM
JUN 16, 2023 8:24 AM VACUUM WARNING
JUN 16, 2023 8:17 AM NO VACUUM ALARM
23 DIESEL PRODUCT
24 DIESEL VENT
I40200
JAN 10, 2024 9:16 AM
I40300
JAN 10, 2024 9:16 AM
I34200
JAN 10, 2024 9:16 AM
I34700
JAN 10, 2024 9:16 AM
IV0100
JAN 10, 2024 9:16 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :WARN
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-01-09 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.63
24-01-08 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 25.01
24-01-07 10:02:10 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 27.95
24-01-06 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 27.25
24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP11 BLEND3 0.56
24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP10 BLEND3 0.59
24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 0.57
24-01-02 10:02:55 FLOW PERFORMANCE HOSE BLOCKAGE FP16 BLEND3 0.59
23-12-31 10:03:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 BLKD
23-12-31 10:03:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.52
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-11-01 10:03:26 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
23-09-02 10:03:13 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3
23-08-29 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3
23-05-28 10:03:20 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3
23-05-25 10:03:16 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
23-05-20 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3
23-05-20 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3
23-05-07 10:03:49 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3
23-05-06 10:03:13 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3
23-05-01 10:03:52 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-12-06 06:19:57 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-22 06:27:22 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-14 07:52:44 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-06 10:33:04 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-05 01:00:00 TIME CHANGE DETECTED AT: 23-11-05 02:00:13
23-11-01 11:00:16 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED
23-11-01 10:05:05 PUMPS MANUALLY RE-ENABLED
23-11-01 10:03:26 FLOW PERFORMANCE BLK DISABLED FP 12 BLEND3
23-10-31 13:15:48 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED
23-10-30 07:05:28 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
Buena SamCo Alarm History After
Responses Received:
I10200
JAN 10, 2024 11:53 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 4 PROBE / G.T. 164370 163465
2 7SMARTSENSOR BD 511611 509762
3 8SMARTSENSOR BD 39931 39857
4 8SMARTSENSOR BD 39740 39706
5 INTERSTITIAL BD 202409 202078
6 INTERSTITIAL BD 202694 202368
7 UNUSED 9797011 9711184
8 UNUSED 9795854 9719573
9 RELAY BOARD 15197 15179
10 STP SENSE BOARD 33411 33418
11 UNUSED 9809786 9728471
12 UNUSED 9797780 9715438
13 UNUSED 9787330 9696540
14 UNUSED 9768975 9682244
15 UNUSED 9773180 9697182
16 UNUSED 9784934 9716807
COMM 1 ELEC DISP INT. 101730 101683
COMM 2 RS232 SERIAL BD 15134 15136
COMM 3 RS232 SERIAL BD 15049 15028
COMM 4 UNUSED 9797486 9703260
COMM 5 SERIAL SAT BD 487156 486071
COMM 6 UNUSED 9797843 9728257
I90200
JAN 10, 2024 11:53 AM
SOFTWARE REVISION LEVEL
VERSION 335.00
SOFTWARE# 346335-100-A
CREATED - 18.08.27.10.22
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JAN 10, 2024 11:53 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L14 OTHER DIESEL FILL LOW LIQUID ALARM CLEAR 1-10-24 11:50AM
L14 OTHER DIESEL FILL LOW LIQUID ALARM ALARM 1-10-24 11:50AM
L14 OTHER DIESEL FILL FUEL ALARM CLEAR 1-10-24 11:42AM
L14 OTHER DIESEL FILL FUEL ALARM ALARM 1-10-24 11:42AM
L15 OTHER VENT BOX FUEL ALARM CLEAR 1-10-24 11:41AM
L15 OTHER VENT BOX FUEL ALARM ALARM 1-10-24 11:41AM
L 9 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 1-10-24 11:23AM
L15 OTHER VENT BOX SENSOR OUT ALARM CLEAR 1-10-24 11:23AM
L12 STP SUMP PREMIUM FILL SENSOR OUT ALARM CLEAR 1-10-24 11:23AM
L10 STP SUMP UNL FILL SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L14 OTHER DIESEL FILL SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L13 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L11 STP SUMP PREMIUM STP SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 9 STP SUMP UNL STP SENSOR OUT ALARM ALARM 1-10-24 11:22AM
L 9 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 2 DISP PAN DISP. 13-14 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 1 DISP PAN DISP. 15-16 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 4 DISP PAN DISP. 11-12 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 7 DISP PAN DISP. 1-2 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 5 DISP PAN DISP. 7-8 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 3 DISP PAN DISP. 9-10 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 8 DISP PAN DISP. 3-4 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 6 DISP PAN DISP. 5-6 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM
L 4 DISP PAN DISP. 11-12 SENSOR OUT ALARM ALARM 1-10-24 11:22AM
L 2 DISP PAN DISP. 13-14 SENSOR OUT ALARM ALARM 1-10-24 11:22AM
L 1 DISP PAN DISP. 15-16 SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L 6 DISP PAN DISP. 5-6 SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L 5 DISP PAN DISP. 7-8 SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L 3 DISP PAN DISP. 9-10 SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L 8 DISP PAN DISP. 3-4 SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L 7 DISP PAN DISP. 1-2 SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L15 OTHER VENT BOX SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L14 OTHER DIESEL FILL SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L12 STP SUMP PREMIUM FILL SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L13 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L11 STP SUMP PREMIUM STP SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L10 STP SUMP UNL FILL SENSOR OUT ALARM ALARM 1-10-24 11:21AM
L 9 STP SUMP UNL STP SENSOR OUT ALARM ALARM 1-10-24 11:21AM
s18 OTHER UNL. PRODUCT NO VACUUM ALARM CLEAR 1-10-24 10:50AM
s22 OTHER UNL. VENT NO VACUUM ALARM CLEAR 1-10-24 10:44AM
s22 OTHER UNL. VENT NO VACUUM ALARM ALARM 1-10-24 10:43AM
s21 OTHER PREMIUM PRODUCT HIGH LIQUID ALARM CLEAR 1-10-24 10:43AM
s19 OTHER VAPOR RETURN HIGH LIQUID ALARM CLEAR 1-10-24 10:43AM
s11 OTHER SUPREME VENT HIGH LIQUID ALARM CLEAR 1-10-24 10:43AM
s18 OTHER UNL. PRODUCT NO VACUUM ALARM ALARM 1-10-24 10:43AM
s19 OTHER VAPOR RETURN NO VACUUM ALARM CLEAR 1-10-24 10:43AM
s19 OTHER VAPOR RETURN HIGH LIQUID ALARM ALARM 1-10-24 10:43AM
s11 OTHER SUPREME VENT NO VACUUM ALARM CLEAR 1-10-24 10:42AM
s21 OTHER PREMIUM PRODUCT NO VACUUM ALARM CLEAR 1-10-24 10:42AM
s21 OTHER PREMIUM PRODUCT HIGH LIQUID ALARM ALARM 1-10-24 10:42AM
I11200
JAN 10, 2024 11:53 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 1-10-24 9:19AM
SYSTEM PAPER OUT CLEAR 1-10-24 9:19AM
SYSTEM PRINTER ERROR ALARM 1-10-24 9:18AM
SYSTEM PAPER OUT ALARM 1-10-24 9:18AM
h11 OTHER FP11: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM
h10 OTHER FP10: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM
h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM
OTHER ISD VAPOR LEAK WARN ALARM 1-06-24 10:02AM
h11 OTHER FP11: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM
h10 OTHER FP10: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM
h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM
h16 OTHER FP16: BLEND3 FLOW COLLECT WARN CLEAR 1-03-24 10:01AM
h16 OTHER FP16: BLEND3 FLOW COLLECT WARN ALARM 1-02-24 10:02AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 1-01-24 10:01AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 1-01-24 10:01AM
h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 12-31-23 10:03AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 12-31-23 10:03AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-31-23 10:01AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-30-23 10:04AM
h10 OTHER FP10: BLEND3 FLOW COLLECT WARN CLEAR 12-29-23 10:01AM
h10 OTHER FP10: BLEND3 FLOW COLLECT WARN ALARM 12-28-23 10:04AM
h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN CLEAR 12-27-23 10:01AM
h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN ALARM 12-26-23 10:03AM
SYSTEM PRINTER ERROR CLEAR 12-21-23 7:25AM
SYSTEM PAPER OUT CLEAR 12-21-23 7:25AM
SYSTEM PRINTER ERROR ALARM 12-21-23 7:23AM
SYSTEM PAPER OUT ALARM 12-21-23 7:23AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-20-23 10:01AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-19-23 10:03AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 12-16-23 9:51AM
T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 12-16-23 6:30AM
T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 12-12-23 3:14AM
T 3 TANK DIESEL DELIVERY NEEDED CLEAR 12-12-23 3:14AM
T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 12-12-23 3:00AM
T 3 TANK DIESEL DELIVERY NEEDED ALARM 12-12-23 3:00AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 12-11-23 10:01AM
h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 12-10-23 10:03AM
SYSTEM PRINTER ERROR CLEAR 12-09-23 3:50PM
SYSTEM PRINTER ERROR ALARM 12-09-23 3:49PM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-07-23 10:01AM
h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-06-23 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 12-06-23 6:19AM
OTHER ISD GROSS PRES WARN ALARM 12-05-23 10:03AM
h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN CLEAR 12-04-23 10:01AM
h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN ALARM 12-03-23 10:04AM
h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN CLEAR 12-02-23 10:01AM
h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN ALARM 12-01-23 10:04AM
SYSTEM PRINTER ERROR CLEAR 11-28-23 12:54PM
SYSTEM PAPER OUT CLEAR 11-28-23 12:54PM
SYSTEM PRINTER ERROR ALARM 11-28-23 12:54PM
I20600
JAN 10, 2024 11:53 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
TANK ALARM HISTORY
TANK 1 UNLEADED
OVERFILL ALARM JAN 3, 2024 10:14 AM
DEC 16, 2023 6:26 AM
NOV 24, 2023 7:04 AM
LOW PRODUCT ALARM MAR 13, 2023 7:04 PM
HIGH PRODUCT ALARM DEC 16, 2023 6:30 AM
NOV 14, 2023 7:59 AM
INVALID FUEL LEVEL MAR 13, 2023 8:41 PM
DELIVERY NEEDED MAR 13, 2023 4:59 PM
TANK 2 PREMIUM
LOW PRODUCT ALARM AUG 29, 2023 6:07 PM
DELIVERY NEEDED AUG 29, 2023 4:38 PM
TANK 3 DIESEL
LOW PRODUCT ALARM DEC 12, 2023 3:00 AM
SUDDEN LOSS ALARM DEC 12, 2023 3:01 AM
INVALID FUEL LEVEL DEC 12, 2023 3:00 AM
DELIVERY NEEDED DEC 12, 2023 3:00 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JAN 10, 2024 11:54 AM
I30200
JAN 10, 2024 11:54 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP. 15-16
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 10:22 AM LOW LIQUID ALARM
JAN 10, 2024 10:21 AM FUEL ALARM
2 DISP. 13-14
JAN 10, 2024 11:22 AM SENSOR OUT ALARM
JAN 10, 2024 10:21 AM LOW LIQUID ALARM
JAN 10, 2024 10:20 AM FUEL ALARM
3 DISP. 9-10
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 10:18 AM LOW LIQUID ALARM
JAN 10, 2024 10:18 AM FUEL ALARM
4 DISP. 11-12
JAN 10, 2024 11:22 AM SENSOR OUT ALARM
JAN 10, 2024 10:17 AM LOW LIQUID ALARM
JAN 10, 2024 10:16 AM FUEL ALARM
5 DISP. 7-8
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 10:15 AM LOW LIQUID ALARM
JAN 10, 2024 10:14 AM FUEL ALARM
6 DISP. 5-6
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 10:13 AM LOW LIQUID ALARM
JAN 10, 2024 10:12 AM FUEL ALARM
7 DISP. 1-2
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 10:11 AM FUEL ALARM
JAN 10, 2024 10:11 AM LOW LIQUID ALARM
8 DISP. 3-4
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 10:10 AM LOW LIQUID ALARM
JAN 10, 2024 10:09 AM FUEL ALARM
9 UNL STP
JAN 10, 2024 11:22 AM SENSOR OUT ALARM
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 9:55 AM LOW LIQUID ALARM
10 UNL FILL
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 10:02 AM LOW LIQUID ALARM
JAN 10, 2024 10:02 AM FUEL ALARM
11 PREMIUM STP
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 9:58 AM LOW LIQUID ALARM
JAN 10, 2024 9:58 AM FUEL ALARM
12 PREMIUM FILL
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 10:00 AM LOW LIQUID ALARM
JAN 10, 2024 9:59 AM FUEL ALARM
13 DIESEL STP
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 9:56 AM LOW LIQUID ALARM
JAN 10, 2024 9:55 AM FUEL ALARM
14 DIESEL FILL
JAN 10, 2024 11:50 AM LOW LIQUID ALARM
JAN 10, 2024 11:42 AM FUEL ALARM
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
15 VENT BOX
JAN 10, 2024 11:41 AM FUEL ALARM
JAN 10, 2024 11:21 AM SENSOR OUT ALARM
JAN 10, 2024 10:24 AM LOW LIQUID ALARM
I31600
JAN 10, 2024 11:54 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP. 15-16 FM
2 DISP. 13-14 FM
3 DISP. 9-10 FM
4 DISP. 11-12 FM
5 DISP. 7-8 FM
6 DISP. 5-6 FM
7 DISP. 1-2 FM
8 ATM
9 DISP. 3-4 FM
10 DISP. 3-4 PS
11 SUPREME VENT
JAN 10, 2024 10:42 AM HIGH LIQUID ALARM
JAN 10, 2024 10:42 AM NO VACUUM ALARM
JUN 14, 2023 1:54 PM COMMUNICATION ALARM
17 UNL. TANK
JAN 10, 2024 10:31 AM HIGH LIQUID ALARM
JAN 10, 2024 10:30 AM NO VACUUM ALARM
APR 11, 2023 2:22 PM SENSOR FAULT ALARM
18 UNL. PRODUCT
JAN 10, 2024 10:43 AM NO VACUUM ALARM
JAN 10, 2024 10:41 AM HIGH LIQUID ALARM
JUN 22, 2023 9:41 AM NO VACUUM ALARM
19 VAPOR RETURN
JAN 10, 2024 10:43 AM HIGH LIQUID ALARM
JAN 10, 2024 10:42 AM NO VACUUM ALARM
JAN 10, 2024 10:41 AM HIGH LIQUID ALARM
20 SUPREME-DIESEL TANK
JAN 10, 2024 10:33 AM HIGH LIQUID ALARM
JAN 10, 2024 10:33 AM NO VACUUM ALARM
21 PREMIUM PRODUCT
JAN 10, 2024 10:42 AM HIGH LIQUID ALARM
JAN 10, 2024 10:42 AM NO VACUUM ALARM
22 UNL. VENT
JAN 10, 2024 10:43 AM NO VACUUM ALARM
JAN 10, 2024 10:41 AM HIGH LIQUID ALARM
JUN 16, 2023 8:30 AM NO VACUUM ALARM
23 DIESEL PRODUCT
JAN 10, 2024 10:41 AM NO VACUUM ALARM
JAN 10, 2024 10:40 AM HIGH LIQUID ALARM
24 DIESEL VENT
JAN 10, 2024 10:41 AM NO VACUUM ALARM
JAN 10, 2024 10:40 AM NO VACUUM ALARM
JAN 10, 2024 10:40 AM HIGH LIQUID ALARM
I40200
JAN 10, 2024 11:54 AM
I40300
JAN 10, 2024 11:54 AM
I34200
JAN 10, 2024 11:54 AM
I34700
JAN 10, 2024 11:54 AM
IV0100
JAN 10, 2024 11:54 AM
874249 SAMCO 8
825 BUENA VISTA RD
BAKERSFIELD CA 93311
661-412-7136
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :WARN
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-01-10 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 22.18
24-01-09 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.63
24-01-08 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 25.01
24-01-07 10:02:10 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 27.95
24-01-06 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 27.25
24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP11 BLEND3 0.56
24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP10 BLEND3 0.59
24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 0.57
24-01-02 10:02:55 FLOW PERFORMANCE HOSE BLOCKAGE FP16 BLEND3 0.59
23-12-31 10:03:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 BLKD
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-11-01 10:03:26 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
23-09-02 10:03:13 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3
23-08-29 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3
23-05-28 10:03:20 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3
23-05-25 10:03:16 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3
23-05-20 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3
23-05-20 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3
23-05-07 10:03:49 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3
23-05-06 10:03:13 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3
23-05-01 10:03:52 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-01-10 11:24:48 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-01-10 11:24:48 ISD STARTUP
24-01-10 11:24:16 ISD SHUTDOWN
23-12-06 06:19:57 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-22 06:27:22 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-14 07:52:44 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-06 10:33:04 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-05 01:00:00 TIME CHANGE DETECTED AT: 23-11-05 02:00:13
23-11-01 11:00:16 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED
23-11-01 10:05:05 PUMPS MANUALLY RE-ENABLED