HomeMy WebLinkAbout2024 FMCAppendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10884616 1/10/2024 Samco Buena Vista 825 Buena Vista Rd Bakersfield 93311 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fisher 1073967 10278702 3/10/25 Veeder Root - C33847 07/24/25 Vaporless Manufacturing LLC 03/14/25 EMCO #1142 1/10/2024 6 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder Root TLS350 335.00 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208/304 DISPENSER 15/16 L2 208/304 DISPENSER 13/14 L3 208/304 DISPENSER 9/10 L4 208/304 DISPENSER 11/12 L5 208/304 DISPENSER 7/8 L6 208/304 DISPENSER 5/6 L7 208/304 DISPENSER 1/2 L8 208/304 DISPENSER 3/4 L9 208/304 UNLEADED STP L10 208/304 UNLEADED FILL L11 208/304 PREMIUM STP L12 208/304 PREMIUM FILL L13 208/304 DIESEL STP L14 208/304 DIESEL FILL L15 208/304 VENT BOX S11 463/464 Supreme Vent S17 420 Unleaded Tank S18 463/464 Unleaded Product S19 463/464 Vapor Return S20 420 Supreme-Diesel Tank S21 463/464 Premium Product S22 463/464 Unleaded Vent S23 463/464 Diesel Product S24 463/464 Diesel Vent Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V 87 Unleaded T2 FX1V 91 Premium T3 LD2000 Diesel Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Samco Buena Vista825 Buena Vista RdBakersfield108846163/47/8 11/12MPDMPDMPDMPDMPDMPDMPDMPD1/25/69/1013/1415/16ProductProductProductProductProductProductProductProductMark Fisher Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10884616 1/10/2024 Samco Buena Vista 825 Buena Vista Rd Bakersfield 93311 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fisher 1073967 10278702 3/10/25 EMCO #3308 3/17/25 PEI1200, 1 hour hydrostatic test All Spill Buckets 1/10/2024 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. 87 EMCO 91 EMCO Diesel EMCO Buena SamCo Setup Responses Received: 200 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 JAN 10, 2024 9:12 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED 12963 74.09 0.0 54.5 7037 2 PREMIUM 6773 66.09 0.0 62.6 5227 3 DIESEL 5612 79.34 0.0 62.7 2388 I90500 JAN 10, 2024 9:12 AM SOFTWARE REVISION LEVEL VERSION 335.00 SOFTWARE# 346335-100-A CREATED - 18.08.27.10.22 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JAN 10, 2024 9:12 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JAN 10, 2024 9:12 AM SHIFT TIME 1 : DISABLED I50202 JAN 10, 2024 9:12 AM SHIFT TIME 2 : DISABLED I50203 JAN 10, 2024 9:12 AM SHIFT TIME 3 : DISABLED I50204 JAN 10, 2024 9:12 AM SHIFT TIME 4 : DISABLED I54600 JAN 10, 2024 9:12 AM TANK PER TST NEEDED WRN: DISABLED I54900 JAN 10, 2024 9:12 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JAN 10, 2024 9:12 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JAN 10, 2024 9:12 AM LINE PER TST NEEDED WRN: DISABLED I55900 JAN 10, 2024 9:12 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JAN 10, 2024 9:12 AM PRINT TC VOLUMES ENABLED I50E00 JAN 10, 2024 9:12 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JAN 10, 2024 9:12 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JAN 10, 2024 9:12 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JAN 10, 2024 9:12 AM DAYLIGHT SAVING TIME ENABLED OFF I51B00 JAN 10, 2024 9:12 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 JAN 10, 2024 9:12 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JAN 10, 2024 9:12 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JAN 10, 2024 9:12 AM TANK CHART SECURITY DISABLED I5BD00 JAN 10, 2024 9:13 AM CUSTOM ALARM LABELS DISABLED I56000 JAN 10, 2024 9:13 AM MASS/DENSITY DISABLED I88101 JAN 10, 2024 9:13 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JAN 10, 2024 9:13 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JAN 10, 2024 9:13 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 1200 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88104 JAN 10, 2024 9:13 AM I88105 JAN 10, 2024 9:13 AM PORT SETTINGS: COMM BOARD : 5 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88106 JAN 10, 2024 9:13 AM I52000 JAN 10, 2024 9:13 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE AUG 30, 2022 DISABLED 2 ON DATE AUG 30, 2022 DISABLED 3 ON DATE AUG 30, 2022 DISABLED 4 ON DATE AUG 30, 2022 DISABLED 5 ON DATE AUG 30, 2022 DISABLED 6 ON DATE AUG 30, 2022 DISABLED 7 ON DATE AUG 30, 2022 DISABLED 8 ON DATE JAN 26, 2022 11:13 AM I60100 JAN 10, 2024 9:13 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED ON 2 PREMIUM ON 3 DIESEL ON 4 OFF I60200 JAN 10, 2024 9:13 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED 2 PREMIUM 3 DIESEL 4 I60300 JAN 10, 2024 9:13 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 2 3 DIESEL 3 4 4 I60900 JAN 10, 2024 9:13 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED 0.000700 2 PREMIUM 0.000700 3 DIESEL 0.000450 4 0.000000 I60700 JAN 10, 2024 9:13 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED 120.00 2 PREMIUM 120.00 3 DIESEL 120.00 4 0.00 I60A00 JAN 10, 2024 9:13 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED 1 PT 20000 2 PREMIUM 1 PT 12000 3 DIESEL 1 PT 8000 4 1 PT 0 I60400 JAN 10, 2024 9:13 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 20000 2 PREMIUM 12000 3 DIESEL 8000 4 0 I60500 JAN 10, 2024 9:13 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 20000 0 0 0 2 PREMIUM 12000 0 0 0 3 DIESEL 8000 0 0 0 4 0 0 0 0 I60600 JAN 10, 2024 9:13 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED 20000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 PREMIUM 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DIESEL 8000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JAN 10, 2024 9:13 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED NO 2 PREMIUM NO 3 DIESEL NO 4 NO I62F00 JAN 10, 2024 9:13 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED 4.0 IN. PS 2 PREMIUM 4.0 IN. PS 3 DIESEL 4.0 IN. PS I62700 JAN 10, 2024 9:13 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 3.0 2 PREMIUM 3.0 3 DIESEL 3.0 I64200 JAN 10, 2024 9:13 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED LOW 2 PREMIUM LOW 3 DIESEL LOW I62400 JAN 10, 2024 9:13 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED 4.0 2 PREMIUM 4.0 3 DIESEL 4.0 I62800 JAN 10, 2024 9:13 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 20000 2 PREMIUM 12000 3 DIESEL 8000 4 0 I62300 JAN 10, 2024 9:13 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 18000 2 PREMIUM 10800 3 DIESEL 7200 4 0 I62200 JAN 10, 2024 9:13 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 19000 2 PREMIUM 11400 3 DIESEL 7600 4 0 I62900 JAN 10, 2024 9:13 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 2000 2 PREMIUM 1200 3 DIESEL 800 4 0 I62100 JAN 10, 2024 9:13 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1000 2 PREMIUM 1000 3 DIESEL 500 4 0 I62600 JAN 10, 2024 9:13 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I62500 JAN 10, 2024 9:13 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 99 2 PREMIUM 99 3 DIESEL 99 4 99 I60800 JAN 10, 2024 9:13 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 PREMIUM 0.00 3 DIESEL 0.00 4 0.00 I60B00 JAN 10, 2024 9:13 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JAN 10, 2024 9:13 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED 0.00 2 PREMIUM 0.00 3 DIESEL 0.00 4 0.00 I61200 JAN 10, 2024 9:13 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NONE NONE 2 PREMIUM NONE NONE 3 DIESEL NONE NONE 4 NONE NONE I63600 JAN 10, 2024 9:13 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 200 2 PREMIUM 120 3 DIESEL 80 4 0 I62A00 JAN 10, 2024 9:13 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED 200 2 PREMIUM 120 3 DIESEL 80 4 0 I62C00 JAN 10, 2024 9:13 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED STANDARD 2 PREMIUM STANDARD 3 DIESEL STANDARD 4 STANDARD I62D00 JAN 10, 2024 9:13 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JAN 10, 2024 9:13 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED OFF OFF 2 PREMIUM OFF OFF 3 DIESEL OFF OFF 4 OFF OFF I63000 JAN 10, 2024 9:13 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I63200 JAN 10, 2024 9:13 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED OFF 2 PREMIUM OFF 3 DIESEL OFF 4 OFF I61000 JAN 10, 2024 9:13 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63A00 JAN 10, 2024 9:13 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED 10.00% 2 PREMIUM 10.00% 3 DIESEL 10.00% 4 10.00% I61100 JAN 10, 2024 9:13 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ANNUALLY: ALL TANK JAN WEEK 1 MON START TIME : 2:00 AM TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:ENABLED I61300 JAN 10, 2024 9:13 AM CSLD PROBABLITY OF DETECTION I61400 JAN 10, 2024 9:13 AM CSLD CLIMATE FACTOR I61600 JAN 10, 2024 9:13 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED IMMEDIATE 2 PREMIUM IMMEDIATE 3 DIESEL IMMEDIATE 4 IMMEDIATE I61A00 JAN 10, 2024 9:13 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED ENABLED 2 PREMIUM ENABLED 3 DIESEL ENABLED 4 ENABLED I61B00 JAN 10, 2024 9:13 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JAN 10, 2024 9:13 AM CSLD REPORT ONLY I62B00 JAN 10, 2024 9:13 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED ??? 0, 0 2 PREMIUM ??? 0, 0 3 DIESEL ??? 0, 0 4 ??? 0, 0 I63300 JAN 10, 2024 9:13 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JAN 10, 2024 9:13 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 0 2 PREMIUM 0 3 DIESEL 0 4 0 I63500 JAN 10, 2024 9:13 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED 1 2 PREMIUM 1 3 DIESEL 1 4 1 I63900 JAN 10, 2024 9:13 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED END FACTOR: NONE 2 PREMIUM END FACTOR: NONE 3 DIESEL END FACTOR: NONE 4 END FACTOR: NONE I78000 JAN 10, 2024 9:13 AM I77700 JAN 10, 2024 9:13 AM I77800 JAN 10, 2024 9:13 AM I78C00 JAN 10, 2024 9:13 AM I78300 JAN 10, 2024 9:13 AM I78F00 JAN 10, 2024 9:13 AM I78700 JAN 10, 2024 9:13 AM I70200 JAN 10, 2024 9:13 AM LIQUID LABEL DEVICE LABEL 1 DISP. 15-16 2 DISP. 13-14 3 DISP. 9-10 4 DISP. 11-12 5 DISP. 7-8 6 DISP. 5-6 7 DISP. 1-2 8 DISP. 3-4 9 UNL STP 10 UNL FILL 11 PREMIUM STP 12 PREMIUM FILL 13 DIESEL STP 14 DIESEL FILL 15 VENT BOX 16 I70300 JAN 10, 2024 9:13 AM LIQUID TYPE SENSOR LOCATION TYPE 1 DISP. 15-16 DW SUMP 2-1 2 DISP. 13-14 DW SUMP 2-1 3 DISP. 9-10 DW SUMP 2-1 4 DISP. 11-12 DW SUMP 2-1 5 DISP. 7-8 DW SUMP 2-1 6 DISP. 5-6 DW SUMP 2-1 7 DISP. 1-2 DW SUMP 2-1 8 DISP. 3-4 DW SUMP 2-1 9 UNL STP DW SUMP 2-1 10 UNL FILL DW SUMP 2-1 11 PREMIUM STP DW SUMP 2-1 12 PREMIUM FILL DW SUMP 2-1 13 DIESEL STP DW SUMP 2-1 14 DIESEL FILL DW SUMP 2-1 15 VENT BOX DW SUMP 2-1 16 TRI-STATE (SINGLE FLOAT) I70400 JAN 10, 2024 9:13 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 DISP. 15-16 DISPENSER PAN 2 DISP. 13-14 DISPENSER PAN 3 DISP. 9-10 DISPENSER PAN 4 DISP. 11-12 DISPENSER PAN 5 DISP. 7-8 DISPENSER PAN 6 DISP. 5-6 DISPENSER PAN 7 DISP. 1-2 DISPENSER PAN 8 DISP. 3-4 DISPENSER PAN 9 UNL STP STP SUMP 10 UNL FILL OTHER SENSORS 11 PREMIUM STP STP SUMP 12 PREMIUM FILL STP SUMP 13 DIESEL STP STP SUMP 14 DIESEL FILL OTHER SENSORS 15 VENT BOX OTHER SENSORS 16 OTHER SENSORS I74200 JAN 10, 2024 9:13 AM I74300 JAN 10, 2024 9:13 AM I74400 JAN 10, 2024 9:13 AM I74700 JAN 10, 2024 9:13 AM I74800 JAN 10, 2024 9:13 AM I74900 JAN 10, 2024 9:13 AM I7BC00 JAN 10, 2024 9:13 AM I80200 JAN 10, 2024 9:13 AM I80300 JAN 10, 2024 9:13 AM I80400 JAN 10, 2024 9:13 AM I80700 JAN 10, 2024 9:13 AM RELAY LABEL DEVICE LABEL 1 UNLEADED 2 PREMIUM 3 DIESEL 4 OVERFILL ALARM I80900 JAN 10, 2024 9:13 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 UNLEADED NORMALLY OPEN 2 PREMIUM NORMALLY OPEN 3 DIESEL NORMALLY OPEN 4 OVERFILL ALARM NORMALLY OPEN I80B00 JAN 10, 2024 9:13 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 UNLEADED 1 2 PREMIUM 2 3 DIESEL 3 4 OVERFILL ALARM NONE I80A00 JAN 10, 2024 9:13 AM RELAY TYPE RELAY DESIGNATION TYPE 1 UNLEADED PUMP CONTROL OUTPUT 2 PREMIUM PUMP CONTROL OUTPUT 3 DIESEL PUMP CONTROL OUTPUT 4 OVERFILL ALARM STANDARD I80C00 JAN 10, 2024 9:13 AM I80800 JAN 10, 2024 9:13 AM RELAY SETUP REPORT R 1:UNLEADED TYPE: PUMP CONTROL OUTPUT TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L11:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L11:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:PREMIUM TYPE: PUMP CONTROL OUTPUT TANK #: 2 LIQUID SENSOR ALMS L 1:FUEL ALARM L 2:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 9:FUEL ALARM L11:FUEL ALARM L 1:SENSOR OUT ALARM L 2:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L11:SENSOR OUT ALARM L 1:SHORT ALARM L 2:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM L 9:SHORT ALARM L11:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:DIESEL TYPE: PUMP CONTROL OUTPUT TANK #: 3 LIQUID SENSOR ALMS L 1:FUEL ALARM L 8:FUEL ALARM L13:FUEL ALARM L 1:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L13:SENSOR OUT ALARM L 1:SHORT ALARM L 8:SHORT ALARM L13:SHORT ALARM R 4:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM I79000 JAN 10, 2024 9:14 AM EDIM:1 VR:349867-001-D TD:17.02.14.08.38 I79100 JAN 10, 2024 9:14 AM I72300 JAN 10, 2024 9:14 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 DISP. 15-16 FM AIR FLOW METER 02 DISP. 13-14 FM AIR FLOW METER 03 DISP. 9-10 FM AIR FLOW METER 04 DISP. 11-12 FM AIR FLOW METER 05 DISP. 7-8 FM AIR FLOW METER 06 DISP. 5-6 FM AIR FLOW METER 07 DISP. 1-2 FM AIR FLOW METER 08 ATM ATM P SENSOR 09 DISP. 3-4 FM AIR FLOW METER 10 DISP. 3-4 PS VAPOR PRESSURE 11 SUPREME VENT VAC SENSOR 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNL. TANK VAC SENSOR 18 UNL. PRODUCT VAC SENSOR 19 VAPOR RETURN VAC SENSOR 20 SUPREME-DIESEL TANK VAC SENSOR 21 PREMIUM PRODUCT VAC SENSOR 22 UNL. VENT VAC SENSOR 23 DIESEL PRODUCT VAC SENSOR 24 DIESEL VENT VAC SENSOR 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JAN 10, 2024 9:14 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 EVR/ISD SETUP TYPE: BALANCE IV4F00 JAN 10, 2024 9:14 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JAN 10, 2024 9:14 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 VAPOR PROCESSOR TYPE NONE IV4700 JAN 10, 2024 9:14 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 ASSESSMENT TIME START TIME: 10:01 AM TIME DELAY MINUTES: 1 IV5200 JAN 10, 2024 9:14 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 ACCEPT HIGH ORVR: YES IV4A00 JAN 10, 2024 9:14 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 07 02 BLEND3 02 02 02 07 02 BLEND3 03 03 03 08 02 BLEND3 04 04 04 08 02 BLEND3 05 05 05 06 02 BLEND3 06 06 06 06 02 BLEND3 07 07 07 05 02 BLEND3 08 08 08 05 02 BLEND3 09 09 09 03 02 BLEND3 10 16 10 03 02 BLEND3 11 17 11 04 02 BLEND3 12 18 12 04 02 BLEND3 13 19 13 02 02 BLEND3 14 20 14 02 02 BLEND3 15 21 15 01 02 BLEND3 16 22 16 01 02 BLEND3 IV4B00 JAN 10, 2024 9:14 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 07 02/01 09/01 01/01 xx/xx 02 07 02/02 09/02 01/02 xx/xx 03 08 02/03 09/03 01/03 xx/xx 04 08 02/04 09/04 01/04 xx/xx 05 06 02/05 09/05 01/05 xx/xx 06 06 02/06 09/06 01/06 xx/xx 07 05 02/07 09/07 01/07 xx/xx 08 05 02/08 09/08 01/08 xx/xx 09 03 02/09 09/09 01/09 xx/xx 16 03 02/10 09/10 01/10 xx/xx 17 04 02/11 09/11 01/11 xx/xx 18 04 02/12 09/12 01/12 xx/xx 19 02 02/13 09/13 01/13 xx/xx 20 02 02/14 09/14 01/14 xx/xx 21 01 02/15 09/15 01/15 xx/xx 22 01 02/16 09/16 01/16 xx/xx IV4900 JAN 10, 2024 9:14 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JAN 10, 2024 9:14 AM ISD VERSION: 01.05 Buena SamCo Alarm History Responses Received: I10200 JAN 10, 2024 9:15 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 164370 163547 2 7SMARTSENSOR BD 511611 511039 3 8SMARTSENSOR BD 39931 39838 4 8SMARTSENSOR BD 39740 39709 5 INTERSTITIAL BD 202409 201973 6 INTERSTITIAL BD 202694 202107 7 UNUSED 9797011 9670977 8 UNUSED 9795854 9646894 9 RELAY BOARD 15197 15172 10 STP SENSE BOARD 33411 33390 11 UNUSED 9809786 9655715 12 UNUSED 9797780 9657472 13 UNUSED 9787330 9679820 14 UNUSED 9768975 9668164 15 UNUSED 9773180 9649073 16 UNUSED 9784934 9642945 COMM 1 ELEC DISP INT. 101730 101655 COMM 2 RS232 SERIAL BD 15134 15129 COMM 3 RS232 SERIAL BD 15049 15043 COMM 4 UNUSED 9797486 9692954 COMM 5 SERIAL SAT BD 487156 487293 COMM 6 UNUSED 9797843 9649523 I90200 JAN 10, 2024 9:15 AM SOFTWARE REVISION LEVEL VERSION 335.00 SOFTWARE# 346335-100-A CREATED - 18.08.27.10.22 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JAN 10, 2024 9:15 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK UNLEADED OVERFILL ALARM CLEAR 1-03-24 10:16AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 1-03-24 10:14AM L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 12-16-23 2:30PM T 1 TANK UNLEADED OVERFILL ALARM CLEAR 12-16-23 6:34AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 12-16-23 6:26AM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-15-23 1:54PM L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM CLEAR 12-15-23 10:56AM L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM ALARM 12-15-23 8:13AM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-14-23 10:58PM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-14-23 4:03PM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-13-23 11:20PM L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 12-13-23 9:21PM L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 12-13-23 5:41PM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-13-23 1:52PM L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 12-13-23 7:03AM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-13-23 1:47AM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-12-23 12:21PM T 3 TANK DIESEL SUDDEN LOSS ALARM CLEAR 12-12-23 4:33AM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-12-23 3:54AM T 3 TANK DIESEL LOW PRODUCT ALARM CLEAR 12-12-23 3:14AM T 3 TANK DIESEL SUDDEN LOSS ALARM ALARM 12-12-23 3:01AM T 3 TANK DIESEL LOW PRODUCT ALARM ALARM 12-12-23 3:00AM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-11-23 12:58PM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-11-23 12:09AM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-10-23 3:06PM L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 12-10-23 1:59PM L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 12-10-23 1:56AM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-09-23 9:41PM L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 12-09-23 3:46PM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM CLEAR 12-09-23 3:28PM L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 12-09-23 9:31AM L 7 DISP PAN DISP. 1-2 LOW LIQUID ALARM ALARM 12-09-23 1:49AM T 1 TANK UNLEADED OVERFILL ALARM CLEAR 11-24-23 7:07AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 11-24-23 7:04AM T 1 TANK UNLEADED OVERFILL ALARM CLEAR 11-14-23 8:02AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 11-14-23 7:56AM h12 OTHER FP12: BLEND3 FLOW COLLECT FAIL CLEAR 11-01-23 11:00AM h12 OTHER FP12: BLEND3 FLOW COLLECT FAIL ALARM 11-01-23 10:03AM L10 OTHER UNL FILL LOW LIQUID ALARM CLEAR 10-31-23 9:51AM L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM CLEAR 10-31-23 9:38AM L10 OTHER UNL FILL LOW LIQUID ALARM ALARM 10-29-23 4:14AM L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM ALARM 10-29-23 1:37AM L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM CLEAR 10-28-23 4:39PM L 3 DISP PAN DISP. 9-10 LOW LIQUID ALARM ALARM 10-28-23 9:56AM T 1 TANK UNLEADED OVERFILL ALARM CLEAR 10-16-23 3:57AM T 1 TANK UNLEADED OVERFILL ALARM ALARM 10-16-23 3:52AM L 1 DISP PAN DISP. 15-16 LOW LIQUID ALARM CLEAR 10-04-23 11:54AM L 1 DISP PAN DISP. 15-16 LOW LIQUID ALARM ALARM 10-04-23 11:49AM L 1 DISP PAN DISP. 15-16 LOW LIQUID ALARM CLEAR 10-04-23 11:42AM L 1 DISP PAN DISP. 15-16 LOW LIQUID ALARM ALARM 10-04-23 11:42AM I11200 JAN 10, 2024 9:15 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h11 OTHER FP11: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM h10 OTHER FP10: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM OTHER ISD VAPOR LEAK WARN ALARM 1-06-24 10:02AM h11 OTHER FP11: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM h10 OTHER FP10: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM h16 OTHER FP16: BLEND3 FLOW COLLECT WARN CLEAR 1-03-24 10:01AM h16 OTHER FP16: BLEND3 FLOW COLLECT WARN ALARM 1-02-24 10:02AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 1-01-24 10:01AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 1-01-24 10:01AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 12-31-23 10:03AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 12-31-23 10:03AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-31-23 10:01AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-30-23 10:04AM h10 OTHER FP10: BLEND3 FLOW COLLECT WARN CLEAR 12-29-23 10:01AM h10 OTHER FP10: BLEND3 FLOW COLLECT WARN ALARM 12-28-23 10:04AM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN CLEAR 12-27-23 10:01AM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN ALARM 12-26-23 10:03AM SYSTEM PRINTER ERROR CLEAR 12-21-23 7:25AM SYSTEM PAPER OUT CLEAR 12-21-23 7:25AM SYSTEM PRINTER ERROR ALARM 12-21-23 7:23AM SYSTEM PAPER OUT ALARM 12-21-23 7:23AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-20-23 10:01AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-19-23 10:03AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 12-16-23 9:51AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 12-16-23 6:30AM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 12-12-23 3:14AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 12-12-23 3:14AM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 12-12-23 3:00AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 12-12-23 3:00AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 12-11-23 10:01AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 12-10-23 10:03AM SYSTEM PRINTER ERROR CLEAR 12-09-23 3:50PM SYSTEM PRINTER ERROR ALARM 12-09-23 3:49PM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-07-23 10:01AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-06-23 10:03AM OTHER ISD GROSS PRES WARN CLEAR 12-06-23 6:19AM OTHER ISD GROSS PRES WARN ALARM 12-05-23 10:03AM h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN CLEAR 12-04-23 10:01AM h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN ALARM 12-03-23 10:04AM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN CLEAR 12-02-23 10:01AM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN ALARM 12-01-23 10:04AM SYSTEM PRINTER ERROR CLEAR 11-28-23 12:54PM SYSTEM PAPER OUT CLEAR 11-28-23 12:54PM SYSTEM PRINTER ERROR ALARM 11-28-23 12:54PM SYSTEM PAPER OUT ALARM 11-28-23 12:54PM OTHER ISD GROSS PRES WARN CLEAR 11-22-23 6:27AM OTHER ISD GROSS PRES WARN ALARM 11-20-23 10:03AM h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN CLEAR 11-20-23 10:01AM I20600 JAN 10, 2024 9:15 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JAN 3, 2024 10:14 AM DEC 16, 2023 6:26 AM NOV 24, 2023 7:04 AM LOW PRODUCT ALARM MAR 13, 2023 7:04 PM HIGH PRODUCT ALARM DEC 16, 2023 6:30 AM NOV 14, 2023 7:59 AM INVALID FUEL LEVEL MAR 13, 2023 8:41 PM DELIVERY NEEDED MAR 13, 2023 4:59 PM TANK 2 PREMIUM LOW PRODUCT ALARM AUG 29, 2023 6:07 PM DELIVERY NEEDED AUG 29, 2023 4:38 PM TANK 3 DIESEL LOW PRODUCT ALARM DEC 12, 2023 3:00 AM SUDDEN LOSS ALARM DEC 12, 2023 3:01 AM INVALID FUEL LEVEL DEC 12, 2023 3:00 AM DELIVERY NEEDED DEC 12, 2023 3:00 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JAN 10, 2024 9:16 AM I30200 JAN 10, 2024 9:16 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DISP. 15-16 OCT 4, 2023 11:49 AM LOW LIQUID ALARM OCT 4, 2023 11:42 AM LOW LIQUID ALARM OCT 4, 2023 11:31 AM LOW LIQUID ALARM 2 DISP. 13-14 MAR 2, 2023 9:20 AM FUEL ALARM MAR 2, 2023 9:07 AM SETUP DATA WARNING 3 DISP. 9-10 DEC 15, 2023 8:13 AM LOW LIQUID ALARM OCT 29, 2023 1:37 AM LOW LIQUID ALARM OCT 28, 2023 9:56 AM LOW LIQUID ALARM 4 DISP. 11-12 MAR 2, 2023 9:18 AM FUEL ALARM MAR 2, 2023 9:07 AM SETUP DATA WARNING 5 DISP. 7-8 MAR 2, 2023 9:17 AM FUEL ALARM MAR 2, 2023 9:10 AM SENSOR OUT ALARM MAR 2, 2023 9:07 AM SETUP DATA WARNING 6 DISP. 5-6 MAR 2, 2023 9:18 AM FUEL ALARM MAR 2, 2023 9:10 AM SENSOR OUT ALARM MAR 2, 2023 9:07 AM SETUP DATA WARNING 7 DISP. 1-2 DEC 14, 2023 10:58 PM LOW LIQUID ALARM DEC 13, 2023 11:20 PM LOW LIQUID ALARM DEC 13, 2023 1:47 AM LOW LIQUID ALARM 8 DISP. 3-4 MAR 2, 2023 9:16 AM FUEL ALARM MAR 2, 2023 9:10 AM SENSOR OUT ALARM MAR 2, 2023 9:07 AM SETUP DATA WARNING 9 UNL STP MAR 2, 2023 9:13 AM FUEL ALARM MAR 2, 2023 9:10 AM SENSOR OUT ALARM MAR 2, 2023 9:07 AM SETUP DATA WARNING 10 UNL FILL DEC 13, 2023 9:21 PM LOW LIQUID ALARM DEC 13, 2023 7:03 AM LOW LIQUID ALARM DEC 10, 2023 1:56 AM LOW LIQUID ALARM 11 PREMIUM STP MAR 2, 2023 9:14 AM FUEL ALARM MAR 2, 2023 9:10 AM SENSOR OUT ALARM MAR 2, 2023 9:07 AM SETUP DATA WARNING 12 PREMIUM FILL SEP 7, 2023 8:56 AM LOW LIQUID ALARM SEP 7, 2023 8:55 AM LOW LIQUID ALARM SEP 2, 2023 1:03 PM LOW LIQUID ALARM 13 DIESEL STP MAR 2, 2023 9:13 AM FUEL ALARM MAR 2, 2023 9:10 AM SENSOR OUT ALARM MAR 2, 2023 9:07 AM SETUP DATA WARNING 14 DIESEL FILL AUG 20, 2023 8:09 PM FUEL ALARM MAR 2, 2023 9:13 AM FUEL ALARM MAR 2, 2023 9:07 AM SETUP DATA WARNING 15 VENT BOX MAR 2, 2023 9:07 AM SETUP DATA WARNING I31600 JAN 10, 2024 9:16 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 DISP. 15-16 FM 2 DISP. 13-14 FM 3 DISP. 9-10 FM 4 DISP. 11-12 FM 5 DISP. 7-8 FM 6 DISP. 5-6 FM 7 DISP. 1-2 FM 8 ATM 9 DISP. 3-4 FM 10 DISP. 3-4 PS 11 SUPREME VENT JUN 14, 2023 1:54 PM COMMUNICATION ALARM JUN 14, 2023 1:47 PM COMMUNICATION ALARM 17 UNL. TANK APR 11, 2023 2:22 PM SENSOR FAULT ALARM APR 11, 2023 1:08 PM SENSOR FAULT ALARM APR 11, 2023 1:03 PM NO VACUUM ALARM 18 UNL. PRODUCT JUN 22, 2023 9:41 AM NO VACUUM ALARM JUN 16, 2023 10:00 AM NO VACUUM ALARM JUN 14, 2023 2:55 PM NO VACUUM ALARM 19 VAPOR RETURN JUN 14, 2023 2:55 PM NO VACUUM ALARM APR 11, 2023 12:32 PM NO VACUUM ALARM APR 11, 2023 12:24 PM SENSOR FAULT ALARM 20 SUPREME-DIESEL TANK 21 PREMIUM PRODUCT 22 UNL. VENT JUN 16, 2023 8:30 AM NO VACUUM ALARM JUN 16, 2023 8:24 AM VACUUM WARNING JUN 16, 2023 8:17 AM NO VACUUM ALARM 23 DIESEL PRODUCT 24 DIESEL VENT I40200 JAN 10, 2024 9:16 AM I40300 JAN 10, 2024 9:16 AM I34200 JAN 10, 2024 9:16 AM I34700 JAN 10, 2024 9:16 AM IV0100 JAN 10, 2024 9:16 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-01-09 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.63 24-01-08 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 25.01 24-01-07 10:02:10 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 27.95 24-01-06 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 27.25 24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP11 BLEND3 0.56 24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP10 BLEND3 0.59 24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 0.57 24-01-02 10:02:55 FLOW PERFORMANCE HOSE BLOCKAGE FP16 BLEND3 0.59 23-12-31 10:03:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 BLKD 23-12-31 10:03:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 3 BLEND3 0.52 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-11-01 10:03:26 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 23-09-02 10:03:13 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 23-08-29 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3 23-05-28 10:03:20 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 23-05-25 10:03:16 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 23-05-20 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3 23-05-20 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 23-05-07 10:03:49 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3 23-05-06 10:03:13 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 23-05-01 10:03:52 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-12-06 06:19:57 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-22 06:27:22 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-14 07:52:44 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-06 10:33:04 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-05 01:00:00 TIME CHANGE DETECTED AT: 23-11-05 02:00:13 23-11-01 11:00:16 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 23-11-01 10:05:05 PUMPS MANUALLY RE-ENABLED 23-11-01 10:03:26 FLOW PERFORMANCE BLK DISABLED FP 12 BLEND3 23-10-31 13:15:48 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 23-10-30 07:05:28 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED Buena SamCo Alarm History After Responses Received: I10200 JAN 10, 2024 11:53 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 4 PROBE / G.T. 164370 163465 2 7SMARTSENSOR BD 511611 509762 3 8SMARTSENSOR BD 39931 39857 4 8SMARTSENSOR BD 39740 39706 5 INTERSTITIAL BD 202409 202078 6 INTERSTITIAL BD 202694 202368 7 UNUSED 9797011 9711184 8 UNUSED 9795854 9719573 9 RELAY BOARD 15197 15179 10 STP SENSE BOARD 33411 33418 11 UNUSED 9809786 9728471 12 UNUSED 9797780 9715438 13 UNUSED 9787330 9696540 14 UNUSED 9768975 9682244 15 UNUSED 9773180 9697182 16 UNUSED 9784934 9716807 COMM 1 ELEC DISP INT. 101730 101683 COMM 2 RS232 SERIAL BD 15134 15136 COMM 3 RS232 SERIAL BD 15049 15028 COMM 4 UNUSED 9797486 9703260 COMM 5 SERIAL SAT BD 487156 486071 COMM 6 UNUSED 9797843 9728257 I90200 JAN 10, 2024 11:53 AM SOFTWARE REVISION LEVEL VERSION 335.00 SOFTWARE# 346335-100-A CREATED - 18.08.27.10.22 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JAN 10, 2024 11:53 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L14 OTHER DIESEL FILL LOW LIQUID ALARM CLEAR 1-10-24 11:50AM L14 OTHER DIESEL FILL LOW LIQUID ALARM ALARM 1-10-24 11:50AM L14 OTHER DIESEL FILL FUEL ALARM CLEAR 1-10-24 11:42AM L14 OTHER DIESEL FILL FUEL ALARM ALARM 1-10-24 11:42AM L15 OTHER VENT BOX FUEL ALARM CLEAR 1-10-24 11:41AM L15 OTHER VENT BOX FUEL ALARM ALARM 1-10-24 11:41AM L 9 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 1-10-24 11:23AM L15 OTHER VENT BOX SENSOR OUT ALARM CLEAR 1-10-24 11:23AM L12 STP SUMP PREMIUM FILL SENSOR OUT ALARM CLEAR 1-10-24 11:23AM L10 STP SUMP UNL FILL SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L14 OTHER DIESEL FILL SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L13 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L11 STP SUMP PREMIUM STP SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 9 STP SUMP UNL STP SENSOR OUT ALARM ALARM 1-10-24 11:22AM L 9 STP SUMP UNL STP SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 2 DISP PAN DISP. 13-14 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 1 DISP PAN DISP. 15-16 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 4 DISP PAN DISP. 11-12 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 7 DISP PAN DISP. 1-2 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 5 DISP PAN DISP. 7-8 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 3 DISP PAN DISP. 9-10 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 8 DISP PAN DISP. 3-4 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 6 DISP PAN DISP. 5-6 SENSOR OUT ALARM CLEAR 1-10-24 11:22AM L 4 DISP PAN DISP. 11-12 SENSOR OUT ALARM ALARM 1-10-24 11:22AM L 2 DISP PAN DISP. 13-14 SENSOR OUT ALARM ALARM 1-10-24 11:22AM L 1 DISP PAN DISP. 15-16 SENSOR OUT ALARM ALARM 1-10-24 11:21AM L 6 DISP PAN DISP. 5-6 SENSOR OUT ALARM ALARM 1-10-24 11:21AM L 5 DISP PAN DISP. 7-8 SENSOR OUT ALARM ALARM 1-10-24 11:21AM L 3 DISP PAN DISP. 9-10 SENSOR OUT ALARM ALARM 1-10-24 11:21AM L 8 DISP PAN DISP. 3-4 SENSOR OUT ALARM ALARM 1-10-24 11:21AM L 7 DISP PAN DISP. 1-2 SENSOR OUT ALARM ALARM 1-10-24 11:21AM L15 OTHER VENT BOX SENSOR OUT ALARM ALARM 1-10-24 11:21AM L14 OTHER DIESEL FILL SENSOR OUT ALARM ALARM 1-10-24 11:21AM L12 STP SUMP PREMIUM FILL SENSOR OUT ALARM ALARM 1-10-24 11:21AM L13 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 1-10-24 11:21AM L11 STP SUMP PREMIUM STP SENSOR OUT ALARM ALARM 1-10-24 11:21AM L10 STP SUMP UNL FILL SENSOR OUT ALARM ALARM 1-10-24 11:21AM L 9 STP SUMP UNL STP SENSOR OUT ALARM ALARM 1-10-24 11:21AM s18 OTHER UNL. PRODUCT NO VACUUM ALARM CLEAR 1-10-24 10:50AM s22 OTHER UNL. VENT NO VACUUM ALARM CLEAR 1-10-24 10:44AM s22 OTHER UNL. VENT NO VACUUM ALARM ALARM 1-10-24 10:43AM s21 OTHER PREMIUM PRODUCT HIGH LIQUID ALARM CLEAR 1-10-24 10:43AM s19 OTHER VAPOR RETURN HIGH LIQUID ALARM CLEAR 1-10-24 10:43AM s11 OTHER SUPREME VENT HIGH LIQUID ALARM CLEAR 1-10-24 10:43AM s18 OTHER UNL. PRODUCT NO VACUUM ALARM ALARM 1-10-24 10:43AM s19 OTHER VAPOR RETURN NO VACUUM ALARM CLEAR 1-10-24 10:43AM s19 OTHER VAPOR RETURN HIGH LIQUID ALARM ALARM 1-10-24 10:43AM s11 OTHER SUPREME VENT NO VACUUM ALARM CLEAR 1-10-24 10:42AM s21 OTHER PREMIUM PRODUCT NO VACUUM ALARM CLEAR 1-10-24 10:42AM s21 OTHER PREMIUM PRODUCT HIGH LIQUID ALARM ALARM 1-10-24 10:42AM I11200 JAN 10, 2024 11:53 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 1-10-24 9:19AM SYSTEM PAPER OUT CLEAR 1-10-24 9:19AM SYSTEM PRINTER ERROR ALARM 1-10-24 9:18AM SYSTEM PAPER OUT ALARM 1-10-24 9:18AM h11 OTHER FP11: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM h10 OTHER FP10: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN CLEAR 1-07-24 10:01AM OTHER ISD VAPOR LEAK WARN ALARM 1-06-24 10:02AM h11 OTHER FP11: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM h10 OTHER FP10: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM h 9 OTHER FP9: BLEND3 FLOW COLLECT WARN ALARM 1-06-24 10:02AM h16 OTHER FP16: BLEND3 FLOW COLLECT WARN CLEAR 1-03-24 10:01AM h16 OTHER FP16: BLEND3 FLOW COLLECT WARN ALARM 1-02-24 10:02AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN CLEAR 1-01-24 10:01AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 1-01-24 10:01AM h 5 OTHER FP5: BLEND3 FLOW COLLECT WARN ALARM 12-31-23 10:03AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 12-31-23 10:03AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-31-23 10:01AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-30-23 10:04AM h10 OTHER FP10: BLEND3 FLOW COLLECT WARN CLEAR 12-29-23 10:01AM h10 OTHER FP10: BLEND3 FLOW COLLECT WARN ALARM 12-28-23 10:04AM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN CLEAR 12-27-23 10:01AM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN ALARM 12-26-23 10:03AM SYSTEM PRINTER ERROR CLEAR 12-21-23 7:25AM SYSTEM PAPER OUT CLEAR 12-21-23 7:25AM SYSTEM PRINTER ERROR ALARM 12-21-23 7:23AM SYSTEM PAPER OUT ALARM 12-21-23 7:23AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-20-23 10:01AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-19-23 10:03AM T 1 TANK UNLEADED HIGH PRODUCT ALARM CLEAR 12-16-23 9:51AM T 1 TANK UNLEADED HIGH PRODUCT ALARM ALARM 12-16-23 6:30AM T 3 TANK DIESEL INVALID FUEL LEVEL CLEAR 12-12-23 3:14AM T 3 TANK DIESEL DELIVERY NEEDED CLEAR 12-12-23 3:14AM T 3 TANK DIESEL INVALID FUEL LEVEL ALARM 12-12-23 3:00AM T 3 TANK DIESEL DELIVERY NEEDED ALARM 12-12-23 3:00AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN CLEAR 12-11-23 10:01AM h 3 OTHER FP3: BLEND3 FLOW COLLECT WARN ALARM 12-10-23 10:03AM SYSTEM PRINTER ERROR CLEAR 12-09-23 3:50PM SYSTEM PRINTER ERROR ALARM 12-09-23 3:49PM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN CLEAR 12-07-23 10:01AM h 4 OTHER FP4: BLEND3 FLOW COLLECT WARN ALARM 12-06-23 10:03AM OTHER ISD GROSS PRES WARN CLEAR 12-06-23 6:19AM OTHER ISD GROSS PRES WARN ALARM 12-05-23 10:03AM h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN CLEAR 12-04-23 10:01AM h 6 OTHER FP6: BLEND3 FLOW COLLECT WARN ALARM 12-03-23 10:04AM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN CLEAR 12-02-23 10:01AM h 1 OTHER FP1: BLEND3 FLOW COLLECT WARN ALARM 12-01-23 10:04AM SYSTEM PRINTER ERROR CLEAR 11-28-23 12:54PM SYSTEM PAPER OUT CLEAR 11-28-23 12:54PM SYSTEM PRINTER ERROR ALARM 11-28-23 12:54PM I20600 JAN 10, 2024 11:53 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 TANK ALARM HISTORY TANK 1 UNLEADED OVERFILL ALARM JAN 3, 2024 10:14 AM DEC 16, 2023 6:26 AM NOV 24, 2023 7:04 AM LOW PRODUCT ALARM MAR 13, 2023 7:04 PM HIGH PRODUCT ALARM DEC 16, 2023 6:30 AM NOV 14, 2023 7:59 AM INVALID FUEL LEVEL MAR 13, 2023 8:41 PM DELIVERY NEEDED MAR 13, 2023 4:59 PM TANK 2 PREMIUM LOW PRODUCT ALARM AUG 29, 2023 6:07 PM DELIVERY NEEDED AUG 29, 2023 4:38 PM TANK 3 DIESEL LOW PRODUCT ALARM DEC 12, 2023 3:00 AM SUDDEN LOSS ALARM DEC 12, 2023 3:01 AM INVALID FUEL LEVEL DEC 12, 2023 3:00 AM DELIVERY NEEDED DEC 12, 2023 3:00 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JAN 10, 2024 11:54 AM I30200 JAN 10, 2024 11:54 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 DISP. 15-16 JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 10:22 AM LOW LIQUID ALARM JAN 10, 2024 10:21 AM FUEL ALARM 2 DISP. 13-14 JAN 10, 2024 11:22 AM SENSOR OUT ALARM JAN 10, 2024 10:21 AM LOW LIQUID ALARM JAN 10, 2024 10:20 AM FUEL ALARM 3 DISP. 9-10 JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 10:18 AM LOW LIQUID ALARM JAN 10, 2024 10:18 AM FUEL ALARM 4 DISP. 11-12 JAN 10, 2024 11:22 AM SENSOR OUT ALARM JAN 10, 2024 10:17 AM LOW LIQUID ALARM JAN 10, 2024 10:16 AM FUEL ALARM 5 DISP. 7-8 JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 10:15 AM LOW LIQUID ALARM JAN 10, 2024 10:14 AM FUEL ALARM 6 DISP. 5-6 JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 10:13 AM LOW LIQUID ALARM JAN 10, 2024 10:12 AM FUEL ALARM 7 DISP. 1-2 JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 10:11 AM FUEL ALARM JAN 10, 2024 10:11 AM LOW LIQUID ALARM 8 DISP. 3-4 JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 10:10 AM LOW LIQUID ALARM JAN 10, 2024 10:09 AM FUEL ALARM 9 UNL STP JAN 10, 2024 11:22 AM SENSOR OUT ALARM JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 9:55 AM LOW LIQUID ALARM 10 UNL FILL JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 10:02 AM LOW LIQUID ALARM JAN 10, 2024 10:02 AM FUEL ALARM 11 PREMIUM STP JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 9:58 AM LOW LIQUID ALARM JAN 10, 2024 9:58 AM FUEL ALARM 12 PREMIUM FILL JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 10:00 AM LOW LIQUID ALARM JAN 10, 2024 9:59 AM FUEL ALARM 13 DIESEL STP JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 9:56 AM LOW LIQUID ALARM JAN 10, 2024 9:55 AM FUEL ALARM 14 DIESEL FILL JAN 10, 2024 11:50 AM LOW LIQUID ALARM JAN 10, 2024 11:42 AM FUEL ALARM JAN 10, 2024 11:21 AM SENSOR OUT ALARM 15 VENT BOX JAN 10, 2024 11:41 AM FUEL ALARM JAN 10, 2024 11:21 AM SENSOR OUT ALARM JAN 10, 2024 10:24 AM LOW LIQUID ALARM I31600 JAN 10, 2024 11:54 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 DISP. 15-16 FM 2 DISP. 13-14 FM 3 DISP. 9-10 FM 4 DISP. 11-12 FM 5 DISP. 7-8 FM 6 DISP. 5-6 FM 7 DISP. 1-2 FM 8 ATM 9 DISP. 3-4 FM 10 DISP. 3-4 PS 11 SUPREME VENT JAN 10, 2024 10:42 AM HIGH LIQUID ALARM JAN 10, 2024 10:42 AM NO VACUUM ALARM JUN 14, 2023 1:54 PM COMMUNICATION ALARM 17 UNL. TANK JAN 10, 2024 10:31 AM HIGH LIQUID ALARM JAN 10, 2024 10:30 AM NO VACUUM ALARM APR 11, 2023 2:22 PM SENSOR FAULT ALARM 18 UNL. PRODUCT JAN 10, 2024 10:43 AM NO VACUUM ALARM JAN 10, 2024 10:41 AM HIGH LIQUID ALARM JUN 22, 2023 9:41 AM NO VACUUM ALARM 19 VAPOR RETURN JAN 10, 2024 10:43 AM HIGH LIQUID ALARM JAN 10, 2024 10:42 AM NO VACUUM ALARM JAN 10, 2024 10:41 AM HIGH LIQUID ALARM 20 SUPREME-DIESEL TANK JAN 10, 2024 10:33 AM HIGH LIQUID ALARM JAN 10, 2024 10:33 AM NO VACUUM ALARM 21 PREMIUM PRODUCT JAN 10, 2024 10:42 AM HIGH LIQUID ALARM JAN 10, 2024 10:42 AM NO VACUUM ALARM 22 UNL. VENT JAN 10, 2024 10:43 AM NO VACUUM ALARM JAN 10, 2024 10:41 AM HIGH LIQUID ALARM JUN 16, 2023 8:30 AM NO VACUUM ALARM 23 DIESEL PRODUCT JAN 10, 2024 10:41 AM NO VACUUM ALARM JAN 10, 2024 10:40 AM HIGH LIQUID ALARM 24 DIESEL VENT JAN 10, 2024 10:41 AM NO VACUUM ALARM JAN 10, 2024 10:40 AM NO VACUUM ALARM JAN 10, 2024 10:40 AM HIGH LIQUID ALARM I40200 JAN 10, 2024 11:54 AM I40300 JAN 10, 2024 11:54 AM I34200 JAN 10, 2024 11:54 AM I34700 JAN 10, 2024 11:54 AM IV0100 JAN 10, 2024 11:54 AM 874249 SAMCO 8 825 BUENA VISTA RD BAKERSFIELD CA 93311 661-412-7136 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-01-10 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 22.18 24-01-09 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.63 24-01-08 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 25.01 24-01-07 10:02:10 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 27.95 24-01-06 10:02:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 27.25 24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP11 BLEND3 0.56 24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP10 BLEND3 0.59 24-01-06 10:02:09 FLOW PERFORMANCE HOSE BLOCKAGE FP 9 BLEND3 0.57 24-01-02 10:02:55 FLOW PERFORMANCE HOSE BLOCKAGE FP16 BLEND3 0.59 23-12-31 10:03:32 FLOW PERFORMANCE HOSE BLOCKAGE FP 5 BLEND3 BLKD FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-11-01 10:03:26 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 23-09-02 10:03:13 FLOW PERFORMANCE HOSE BLOCKAGE FP 8 BLEND3 23-08-29 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3 23-05-28 10:03:20 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 23-05-25 10:03:16 FLOW PERFORMANCE HOSE BLOCKAGE FP12 BLEND3 23-05-20 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3 23-05-20 10:03:17 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 23-05-07 10:03:49 FLOW PERFORMANCE HOSE BLOCKAGE FP13 BLEND3 23-05-06 10:03:13 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 23-05-01 10:03:52 FLOW PERFORMANCE HOSE BLOCKAGE FP 2 BLEND3 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-01-10 11:24:48 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-01-10 11:24:48 ISD STARTUP 24-01-10 11:24:16 ISD SHUTDOWN 23-12-06 06:19:57 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-22 06:27:22 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-14 07:52:44 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-06 10:33:04 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-05 01:00:00 TIME CHANGE DETECTED AT: 23-11-05 02:00:13 23-11-01 11:00:16 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 23-11-01 10:05:05 PUMPS MANUALLY RE-ENABLED