Loading...
HomeMy WebLinkAboutEMC 2024Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10159161 1/10/2024 Jaco #7721 Fastrip #22 (North) 4013 S Union Ave Bakersfield 93307 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 10278702 1073967 10278702 3/10/25 Veeder Root - C33847 07/24/25 1/10/2024 5 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 Veeder Root TLS350 336.02 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 87 STP L2 420 87 Annular L3 208 91 STP L4 420 91 Annular L5 208 Diesel STP L6 420 Diesel Annular L9 208 Dispenser 9/10 L10 208 Dispenser 11/12 L11 208 Dispenser 13/14 L12 208 Dispenser 15/16 L13 208 Dispenser 17/18 L14 208 Dispenser 19/20 Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ No leak detectors were tested today as it was strictly an Electronic Monitor Certification from a cold start. Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. 1/10/24 F EXISTING BUILDING NOPARKING 56L11 #7-781 78L10 34L12 12L9 12,000 GALLON87-1 UNLEADED 12,000 GALLON87-2 UNLEADED 12,000 GALLONPREMIUM 12,000 GALLONDIESEL V AL2 STPL1 FV AL6 STPL5 FV AL8 STPL7 F AL4 STPL3 109L91413L121211L101615L122019L141817L1312,000 GALLON87 UNLEADED12,000 GALLONPREMIUM12,000 GALLONDIESELFAL6STPL5FVAL4STPL3FVAL2STPL1NOPARKING G W 7-721 7-781 #7-721DUMPSTER H H PRICE SIGN PRICE SIGN 40' STORAGE CONTA INER S. H ST.WHITE LN.PROPERTY LINE PROPERTY LINE N CAT C HBAS I N 721 LEGEND L1 87 STP L2 87 ANNULAR L3 91 STP L4 91 ANNULAR L5 DSL STP L6 DSL ANNULAR L9 UDC 9 - 10 L10 UDC 11 -12 L11 UDC 13 - 14 L12 UDC 15 - 16 L13 UDC 17 - 18 L14 UDC 19 - 20 781 LEGEND L1 87-1 STP L2 87-1 ANNULAR L3 DSL STP L4 DSL ANNULAR L5 87-2 STP L6 87-2 ANNULAR L7 91 STP L8 91 ANNULAR L9 UDC 1 -2 L10 UDC 7 - 8 L11 UDC 5 -6 L12 UDC 3 - 4 87 GAS 3/2 INCH DBL WALLED PIPE 91 GAS 3/2 INCH DBL WALLED PIPE DIESEL 3/2 INCH DBL WALLED PIPE VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE VAPOR VENT 3/2 INCH DOUBLE WALLED PIPE PRODUCT SPILL CONTAINER VAPOR SPILL CONTAINER ANNULAR EMERGENCY SHUT-OFF OVERFILL ALARM FIRE EXTINGUISHER GAS METER SHUT-OFF WATER METER SHUT-SHUT OFF HEALY CAS EVACUATION MEETING POINT CIRCUIT BREAKER UST ELECTRICAL PANEL AUTOMATIC TANK GAUGE AIR AND WATER DISPENSER HAZWASTE DRUM W G A H P V SCALE: SITE MAP C1 VICINITY MAP PROJECT DATA 3/32"=1'-0" INCHES012 SHEET SIZE 22 X 34 4013 S. H ST. BAKERSFIELD, CA 93304 PROJECT OWNER: JAMIESON HILL PO. BOX 82515 BAKERSFIELD, CA 93380 CONTACT: SITE PLOT PLAN FOR: FASTRIP #7721 FACILITY ID 15-021-100296 CERS ID 10159161 FASTRIP #7781 FACILITY ID 15-021-003022 CERS ID 10159163 4013 S. H ST. BAKERSFIELD, CA 93304 03/02/17 REV.S. H ST.WHITE LN. FASTRIP #7721 SYSTEM SETUP Responses Received: 200 FASTRIP 4013 S H ST BAKERSFIELD JAN 10, 2024 2:14 PM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 87 6523 51.29 0.0 57.3 5477 2 91 6573 51.60 0.0 63.0 5427 3 DSL 124 3.22 0.0 69.2 11876 I90500 JAN 10, 2024 2:14 PM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JAN 10, 2024 2:14 PM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JAN 10, 2024 2:14 PM SHIFT TIME 1 : 6:00 AM I50202 JAN 10, 2024 2:14 PM SHIFT TIME 2 : DISABLED I50203 JAN 10, 2024 2:14 PM SHIFT TIME 3 : DISABLED I50204 JAN 10, 2024 2:14 PM SHIFT TIME 4 : DISABLED I54600 JAN 10, 2024 2:14 PM TANK PER TST NEEDED WRN: DISABLED I54900 JAN 10, 2024 2:14 PM TANK ANN TST NEEDED WRN: DISABLED I55300 JAN 10, 2024 2:14 PM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JAN 10, 2024 2:14 PM LINE PER TST NEEDED WRN: DISABLED I55900 JAN 10, 2024 2:14 PM LINE ANN TST NEEDED WRN: DISABLED I50D00 JAN 10, 2024 2:14 PM PRINT TC VOLUMES ENABLED I50E00 JAN 10, 2024 2:14 PM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JAN 10, 2024 2:14 PM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JAN 10, 2024 2:14 PM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JAN 10, 2024 2:14 PM DAYLIGHT SAVING TIME DISABLED I51B00 JAN 10, 2024 2:14 PM I51600 JAN 10, 2024 2:14 PM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JAN 10, 2024 2:14 PM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JAN 10, 2024 2:14 PM TANK CHART SECURITY DISABLED I5BD00 JAN 10, 2024 2:14 PM CUSTOM ALARM LABELS DISABLED I56000 JAN 10, 2024 2:14 PM MASS/DENSITY DISABLED I88101 JAN 10, 2024 2:14 PM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JAN 10, 2024 2:14 PM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88103 JAN 10, 2024 2:14 PM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 JAN 10, 2024 2:14 PM I88105 JAN 10, 2024 2:14 PM I88106 JAN 10, 2024 2:14 PM I52000 JAN 10, 2024 2:14 PM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE JUN 30, 2022 DISABLED 2 ON DATE JUN 30, 2022 DISABLED 3 ON DATE JUN 30, 2022 DISABLED 4 ON DATE JUN 30, 2022 DISABLED 5 ON DATE JUN 30, 2022 DISABLED 6 ON DATE JUN 30, 2022 DISABLED 7 ON DATE JUN 30, 2022 DISABLED 8 ON DATE JUN 30, 2022 DISABLED I60100 JAN 10, 2024 2:14 PM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 87 ON 2 91 ON 3 DSL ON 4 OFF I60200 JAN 10, 2024 2:14 PM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 87 2 91 3 DSL 4 I60300 JAN 10, 2024 2:14 PM TANK PRODUCT CODE TANK PRODUCT LABEL 1 87 1 2 91 2 3 DSL 3 4 4 I60900 JAN 10, 2024 2:14 PM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 87 0.000700 2 91 0.000700 3 DSL 0.000450 4 0.000000 I60700 JAN 10, 2024 2:14 PM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 87 96.00 2 91 96.00 3 DSL 96.00 4 0.00 I60A00 JAN 10, 2024 2:14 PM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 87 1 PT 12000 2 91 1 PT 12000 3 DSL 1 PT 12000 4 1 PT 0 I60400 JAN 10, 2024 2:14 PM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 87 12000 2 91 12000 3 DSL 12000 4 0 I60500 JAN 10, 2024 2:14 PM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 87 12000 0 0 0 2 91 12000 0 0 0 3 DSL 12000 0 0 0 4 0 0 0 0 I60600 JAN 10, 2024 2:14 PM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 87 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 91 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 3 DSL 12000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JAN 10, 2024 2:14 PM TANK PRODUCT LABEL METER DATA 1 87 NO 2 91 NO 3 DSL NO 4 NO I62F00 JAN 10, 2024 2:14 PM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 87 4.0 IN. 2 91 4.0 IN. 3 DSL 4.0 IN. I62700 JAN 10, 2024 2:15 PM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 87 2.0 2 91 2.0 3 DSL 2.0 I64200 JAN 10, 2024 2:15 PM WATER ALARM FILTER TANK PRODUCT LABEL 1 87 LOW 2 91 LOW 3 DSL LOW I62400 JAN 10, 2024 2:15 PM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 87 3.0 2 91 3.0 3 DSL 3.0 I62800 JAN 10, 2024 2:15 PM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 87 12000 2 91 12000 3 DSL 12000 4 0 I62300 JAN 10, 2024 2:15 PM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 87 10800 2 91 10800 3 DSL 10800 4 0 I62200 JAN 10, 2024 2:15 PM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 87 11400 2 91 11400 3 DSL 11400 4 0 I62900 JAN 10, 2024 2:15 PM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 87 1200 2 91 1200 3 DSL 120 4 0 I62100 JAN 10, 2024 2:15 PM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 87 1200 2 91 1200 3 DSL 100 4 0 I62600 JAN 10, 2024 2:15 PM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 87 99 2 91 99 3 DSL 99 4 99 I62500 JAN 10, 2024 2:15 PM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 87 99 2 91 99 3 DSL 99 4 99 I60800 JAN 10, 2024 2:15 PM TANK TILT TANK PRODUCT LABEL INCHES 1 87 0.00 2 91 0.00 3 DSL 0.00 4 0.00 I60B00 JAN 10, 2024 2:15 PM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JAN 10, 2024 2:15 PM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 87 0.00 2 91 0.00 3 DSL 0.00 4 0.00 I61200 JAN 10, 2024 2:15 PM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 87 NONE NONE 2 91 NONE NONE 3 DSL NONE NONE 4 NONE NONE I63600 JAN 10, 2024 2:15 PM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 87 120 2 91 120 3 DSL 120 4 0 I62A00 JAN 10, 2024 2:15 PM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 87 120 2 91 120 3 DSL 120 4 0 I62C00 JAN 10, 2024 2:15 PM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 87 STANDARD 2 91 STANDARD 3 DSL STANDARD 4 STANDARD I62D00 JAN 10, 2024 2:15 PM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 87 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 91 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 DSL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JAN 10, 2024 2:15 PM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 87 OFF OFF 2 91 OFF OFF 3 DSL OFF OFF 4 OFF OFF I63000 JAN 10, 2024 2:15 PM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 87 OFF 2 91 OFF 3 DSL OFF 4 OFF I63200 JAN 10, 2024 2:15 PM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 87 OFF 2 91 OFF 3 DSL OFF 4 OFF I61000 JAN 10, 2024 2:15 PM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 87 1 2 91 1 3 DSL 1 4 1 I63A00 JAN 10, 2024 2:15 PM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 87 10.00% 2 91 10.00% 3 DSL 1.00% 4 10.00% I61100 JAN 10, 2024 2:15 PM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK FEB 13, 2021 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JAN 10, 2024 2:15 PM CSLD PROBABLITY OF DETECTION I61400 JAN 10, 2024 2:15 PM CSLD CLIMATE FACTOR I61600 JAN 10, 2024 2:15 PM TANK PRODUCT LABEL CAL UPDATE 1 87 IMMEDIATE 2 91 IMMEDIATE 3 DSL IMMEDIATE 4 IMMEDIATE I61A00 JAN 10, 2024 2:15 PM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 87 DISABLED 2 91 DISABLED 3 DSL DISABLED 4 DISABLED I61B00 JAN 10, 2024 2:15 PM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JAN 10, 2024 2:15 PM CSLD REPORT ONLY I62B00 JAN 10, 2024 2:15 PM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 87 ??? 0, 0 2 91 ??? 0, 0 3 DSL ??? 0, 0 4 ??? 0, 0 I63300 JAN 10, 2024 2:15 PM LEAK TEST REPORT FORMAT: NORMAL I63400 JAN 10, 2024 2:15 PM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 87 0 2 91 0 3 DSL 0 4 0 I63500 JAN 10, 2024 2:15 PM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 87 1 2 91 1 3 DSL 1 4 1 I63900 JAN 10, 2024 2:15 PM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 87 END FACTOR: NONE 2 91 END FACTOR: NONE 3 DSL END FACTOR: NONE 4 END FACTOR: NONE I78000 JAN 10, 2024 2:15 PM I77700 JAN 10, 2024 2:15 PM I77800 JAN 10, 2024 2:15 PM I78C00 JAN 10, 2024 2:15 PM I78300 JAN 10, 2024 2:15 PM I78F00 JAN 10, 2024 2:15 PM I78700 JAN 10, 2024 2:15 PM I70200 JAN 10, 2024 2:15 PM LIQUID LABEL DEVICE LABEL 1 87 STP 2 87 ANN 3 91 STP 4 91 ANN 5 DEISE STP 6 DSL ANN 7 8 9 9-10 10 11-12 11 13-14 12 15-16 13 17-18 14 19-20 15 16 I70300 JAN 10, 2024 2:15 PM LIQUID TYPE SENSOR LOCATION TYPE 1 87 STP TRI-STATE (SINGLE FLOAT) 2 87 ANN TRI-STATE (SINGLE FLOAT) 3 91 STP TRI-STATE (SINGLE FLOAT) 4 91 ANN TRI-STATE (SINGLE FLOAT) 5 DEISE STP TRI-STATE (SINGLE FLOAT) 6 DSL ANN TRI-STATE (SINGLE FLOAT) 7 TRI-STATE (SINGLE FLOAT) 8 TRI-STATE (SINGLE FLOAT) 9 9-10 TRI-STATE (SINGLE FLOAT) 10 11-12 TRI-STATE (SINGLE FLOAT) 11 13-14 TRI-STATE (SINGLE FLOAT) 12 15-16 TRI-STATE (SINGLE FLOAT) 13 17-18 TRI-STATE (SINGLE FLOAT) 14 19-20 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JAN 10, 2024 2:15 PM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 87 STP STP SUMP 2 87 ANN ANNULAR SPACE 3 91 STP STP SUMP 4 91 ANN ANNULAR SPACE 5 DEISE STP STP SUMP 6 DSL ANN ANNULAR SPACE 7 OTHER SENSORS 8 OTHER SENSORS 9 9-10 DISPENSER PAN 10 11-12 DISPENSER PAN 11 13-14 DISPENSER PAN 12 15-16 DISPENSER PAN 13 17-18 DISPENSER PAN 14 19-20 DISPENSER PAN 15 OTHER SENSORS 16 OTHER SENSORS I74200 JAN 10, 2024 2:15 PM I74300 JAN 10, 2024 2:15 PM I74400 JAN 10, 2024 2:15 PM I74700 JAN 10, 2024 2:15 PM I74800 JAN 10, 2024 2:15 PM I74900 JAN 10, 2024 2:15 PM I7BC00 JAN 10, 2024 2:15 PM I80200 JAN 10, 2024 2:15 PM I80300 JAN 10, 2024 2:15 PM I80400 JAN 10, 2024 2:15 PM I80700 JAN 10, 2024 2:15 PM RELAY LABEL DEVICE LABEL 1 87 2 91 3 DSL 4 OVERFILL I80900 JAN 10, 2024 2:15 PM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 87 NORMALLY OPEN 2 91 NORMALLY OPEN 3 DSL NORMALLY CLOSED 4 OVERFILL NORMALLY OPEN I80B00 JAN 10, 2024 2:15 PM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 87 1 2 91 2 3 DSL NONE 4 OVERFILL 4 I80A00 JAN 10, 2024 2:15 PM RELAY TYPE RELAY DESIGNATION TYPE 1 87 PUMP CONTROL OUTPUT 2 91 PUMP CONTROL OUTPUT 3 DSL STANDARD 4 OVERFILL STANDARD I80C00 JAN 10, 2024 2:15 PM I80800 JAN 10, 2024 2:15 PM RELAY SETUP REPORT R 1:87 TYPE: PUMP CONTROL OUTPUT TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 1:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L 1:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L14:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL R 2:91 TYPE: PUMP CONTROL OUTPUT TANK #: 2 LIQUID SENSOR ALMS L 1:FUEL ALARM L 3:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 1:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM L 1:SHORT ALARM L 3:SHORT ALARM L 9:SHORT ALARM L10:SHORT ALARM L11:SHORT ALARM L12:SHORT ALARM L13:SHORT ALARM L14:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS h13:GROSS COLLECT FAIL h14:GROSS COLLECT FAIL h15:GROSS COLLECT FAIL h16:GROSS COLLECT FAIL h17:GROSS COLLECT FAIL h18:GROSS COLLECT FAIL h19:GROSS COLLECT FAIL h20:GROSS COLLECT FAIL h21:GROSS COLLECT FAIL h22:GROSS COLLECT FAIL h23:GROSS COLLECT FAIL h24:GROSS COLLECT FAIL h25:GROSS COLLECT FAIL h26:GROSS COLLECT FAIL h27:GROSS COLLECT FAIL h28:GROSS COLLECT FAIL h29:GROSS COLLECT FAIL h30:GROSS COLLECT FAIL h31:GROSS COLLECT FAIL h32:GROSS COLLECT FAIL h33:GROSS COLLECT FAIL h34:GROSS COLLECT FAIL h35:GROSS COLLECT FAIL h36:GROSS COLLECT FAIL h37:GROSS COLLECT FAIL h38:GROSS COLLECT FAIL h39:GROSS COLLECT FAIL h40:GROSS COLLECT FAIL h41:GROSS COLLECT FAIL h42:GROSS COLLECT FAIL h43:GROSS COLLECT FAIL h44:GROSS COLLECT FAIL h45:GROSS COLLECT FAIL h46:GROSS COLLECT FAIL h47:GROSS COLLECT FAIL h48:GROSS COLLECT FAIL h49:GROSS COLLECT FAIL h50:GROSS COLLECT FAIL h51:GROSS COLLECT FAIL h52:GROSS COLLECT FAIL h53:GROSS COLLECT FAIL h54:GROSS COLLECT FAIL h55:GROSS COLLECT FAIL h56:GROSS COLLECT FAIL h57:GROSS COLLECT FAIL h58:GROSS COLLECT FAIL h59:GROSS COLLECT FAIL h60:GROSS COLLECT FAIL h61:GROSS COLLECT FAIL h62:GROSS COLLECT FAIL h63:GROSS COLLECT FAIL h64:GROSS COLLECT FAIL h65:GROSS COLLECT FAIL h66:GROSS COLLECT FAIL h67:GROSS COLLECT FAIL h68:GROSS COLLECT FAIL h69:GROSS COLLECT FAIL h70:GROSS COLLECT FAIL h71:GROSS COLLECT FAIL h72:GROSS COLLECT FAIL h73:GROSS COLLECT FAIL h74:GROSS COLLECT FAIL h75:GROSS COLLECT FAIL h76:GROSS COLLECT FAIL h77:GROSS COLLECT FAIL h78:GROSS COLLECT FAIL h79:GROSS COLLECT FAIL h80:GROSS COLLECT FAIL h81:GROSS COLLECT FAIL h82:GROSS COLLECT FAIL h83:GROSS COLLECT FAIL h84:GROSS COLLECT FAIL h85:GROSS COLLECT FAIL h86:GROSS COLLECT FAIL h87:GROSS COLLECT FAIL h88:GROSS COLLECT FAIL h89:GROSS COLLECT FAIL h90:GROSS COLLECT FAIL h91:GROSS COLLECT FAIL h92:GROSS COLLECT FAIL h93:GROSS COLLECT FAIL h94:GROSS COLLECT FAIL h95:GROSS COLLECT FAIL h96:GROSS COLLECT FAIL h97:GROSS COLLECT FAIL h98:GROSS COLLECT FAIL h99:GROSS COLLECT FAIL h13:DEGRD COLLECT FAIL h14:DEGRD COLLECT FAIL h15:DEGRD COLLECT FAIL h16:DEGRD COLLECT FAIL h17:DEGRD COLLECT FAIL h18:DEGRD COLLECT FAIL h19:DEGRD COLLECT FAIL h20:DEGRD COLLECT FAIL h21:DEGRD COLLECT FAIL h22:DEGRD COLLECT FAIL h23:DEGRD COLLECT FAIL h24:DEGRD COLLECT FAIL h25:DEGRD COLLECT FAIL h26:DEGRD COLLECT FAIL h27:DEGRD COLLECT FAIL h28:DEGRD COLLECT FAIL h29:DEGRD COLLECT FAIL h30:DEGRD COLLECT FAIL h31:DEGRD COLLECT FAIL h32:DEGRD COLLECT FAIL h33:DEGRD COLLECT FAIL h34:DEGRD COLLECT FAIL h35:DEGRD COLLECT FAIL h36:DEGRD COLLECT FAIL h37:DEGRD COLLECT FAIL h38:DEGRD COLLECT FAIL h39:DEGRD COLLECT FAIL h40:DEGRD COLLECT FAIL h41:DEGRD COLLECT FAIL h42:DEGRD COLLECT FAIL h43:DEGRD COLLECT FAIL h44:DEGRD COLLECT FAIL h45:DEGRD COLLECT FAIL h46:DEGRD COLLECT FAIL h47:DEGRD COLLECT FAIL h48:DEGRD COLLECT FAIL h49:DEGRD COLLECT FAIL h50:DEGRD COLLECT FAIL h51:DEGRD COLLECT FAIL h52:DEGRD COLLECT FAIL h53:DEGRD COLLECT FAIL h54:DEGRD COLLECT FAIL h55:DEGRD COLLECT FAIL h56:DEGRD COLLECT FAIL h57:DEGRD COLLECT FAIL h58:DEGRD COLLECT FAIL h59:DEGRD COLLECT FAIL h60:DEGRD COLLECT FAIL h61:DEGRD COLLECT FAIL h62:DEGRD COLLECT FAIL h63:DEGRD COLLECT FAIL h64:DEGRD COLLECT FAIL h65:DEGRD COLLECT FAIL h66:DEGRD COLLECT FAIL h67:DEGRD COLLECT FAIL h68:DEGRD COLLECT FAIL h69:DEGRD COLLECT FAIL h70:DEGRD COLLECT FAIL h71:DEGRD COLLECT FAIL h72:DEGRD COLLECT FAIL h73:DEGRD COLLECT FAIL h74:DEGRD COLLECT FAIL h75:DEGRD COLLECT FAIL h76:DEGRD COLLECT FAIL h77:DEGRD COLLECT FAIL h78:DEGRD COLLECT FAIL h79:DEGRD COLLECT FAIL h80:DEGRD COLLECT FAIL h81:DEGRD COLLECT FAIL h82:DEGRD COLLECT FAIL h83:DEGRD COLLECT FAIL h84:DEGRD COLLECT FAIL h85:DEGRD COLLECT FAIL h86:DEGRD COLLECT FAIL h87:DEGRD COLLECT FAIL h88:DEGRD COLLECT FAIL h89:DEGRD COLLECT FAIL h90:DEGRD COLLECT FAIL h91:DEGRD COLLECT FAIL h92:DEGRD COLLECT FAIL h93:DEGRD COLLECT FAIL h94:DEGRD COLLECT FAIL h95:DEGRD COLLECT FAIL h96:DEGRD COLLECT FAIL h97:DEGRD COLLECT FAIL h98:DEGRD COLLECT FAIL h99:DEGRD COLLECT FAIL R 3:DSL TYPE: STANDARD NORMALLY CLOSED TANK #: NONE LIQUID SENSOR ALMS L 1:FUEL ALARM L 5:FUEL ALARM L 9:FUEL ALARM L10:FUEL ALARM L11:FUEL ALARM L12:FUEL ALARM L13:FUEL ALARM L14:FUEL ALARM L 5:SENSOR OUT ALARM L 9:SENSOR OUT ALARM L10:SENSOR OUT ALARM L11:SENSOR OUT ALARM L12:SENSOR OUT ALARM L13:SENSOR OUT ALARM L14:SENSOR OUT ALARM R 4:OVERFILL TYPE: STANDARD NORMALLY OPEN TANK #: 4 IN-TANK ALARMS ALL:LEAK ALARM ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM I79000 JAN 10, 2024 2:16 PM EDIM:1 VR:349634-003-C TD:06.05.11.11.15 I79100 JAN 10, 2024 2:16 PM I72300 JAN 10, 2024 2:16 PM FASTRIP 4013 S H ST BAKERSFIELD SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 VPS VAPOR PRESSURE 02 FM1 AIR FLOW METER 03 FM2 AIR FLOW METER 04 FM3 AIR FLOW METER 05 FM4 AIR FLOW METER 06 FM5 AIR FLOW METER 07 FM6 AIR FLOW METER 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JAN 10, 2024 2:16 PM FASTRIP 4013 S H ST BAKERSFIELD EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JAN 10, 2024 2:16 PM FASTRIP 4013 S H ST BAKERSFIELD NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JAN 10, 2024 2:16 PM FASTRIP 4013 S H ST BAKERSFIELD VAPOR PROCESSOR TYPE NONE IV4700 JAN 10, 2024 2:16 PM FASTRIP 4013 S H ST BAKERSFIELD ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 JAN 10, 2024 2:16 PM FASTRIP 4013 S H ST BAKERSFIELD ACCEPT HIGH ORVR: YES IV4A00 JAN 10, 2024 2:16 PM FASTRIP 4013 S H ST BAKERSFIELD ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 09 01 05 UU BLEND3 02 10 02 05 UU BLEND3 03 11 03 06 UU BLEND3 04 12 04 06 UU BLEND3 05 17 05 01 UU BLEND3 06 18 06 01 UU BLEND3 07 19 07 02 UU BLEND3 08 20 08 02 UU BLEND3 09 21 09 03 UU BLEND3 10 22 10 03 UU BLEND3 11 23 11 04 UU BLEND3 12 24 12 04 UU BLEND3 IV4B00 JAN 10, 2024 2:16 PM FASTRIP 4013 S H ST BAKERSFIELD PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 09 05 02/01 03/01 09/01 xx/xx 10 05 02/02 03/02 09/02 xx/xx 11 06 02/03 03/03 09/03 xx/xx 12 06 02/04 03/04 09/04 xx/xx 17 01 02/05 03/05 09/05 xx/xx 18 01 02/06 03/06 09/06 xx/xx 19 02 02/07 03/07 09/07 xx/xx 20 02 02/08 03/08 09/08 xx/xx 21 03 02/09 03/09 09/09 xx/xx 22 03 02/10 03/10 09/10 xx/xx 23 04 02/11 03/11 09/11 xx/xx 24 04 02/12 03/12 09/12 xx/xx IV4900 JAN 10, 2024 2:16 PM FASTRIP 4013 S H ST BAKERSFIELD LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JAN 10, 2024 2:16 PM ISD VERSION: 01.07 FASTRIP #7721 ALARM HISTORY BEFORE: Responses Received: I10200 JAN 10, 2024 2:17 PM FASTRIP 4013 S H ST BAKERSFIELD SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 506485 505293 2 INTERSTITIAL BD 202115 201907 3 4 PROBE / G.T. 162865 162759 4 INTERSTITIAL BD 200843 200745 5 UNUSED 4919832 4892167 6 UNUSED 4914353 4889192 7 UNUSED 4913506 4891642 8 UNUSED 4916136 4889783 9 STP SENSE BOARD 33110 33073 10 RELAY BOARD 14978 14963 11 UNUSED 4915571 4893495 12 UNUSED 4912180 4889755 13 UNUSED 4912528 4891570 14 UNUSED 4913267 4891002 15 UNUSED 4911897 4889230 16 UNUSED 4913984 4889690 COMM 1 ELEC DISP INT. 101006 101009 COMM 2 RS232 SERIAL BD 15000 14985 COMM 3 RS232 SERIAL BD 14956 14919 COMM 4 UNUSED 4917115 4892270 COMM 5 UNUSED 4911723 4889974 COMM 6 UNUSED 4912180 4892576 I90200 JAN 10, 2024 2:17 PM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JAN 10, 2024 2:17 PM FASTRIP 4013 S H ST BAKERSFIELD PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME T 1 TANK 87 OVERFILL ALARM CLEAR 1-06-24 2:12AM T 1 TANK 87 OVERFILL ALARM ALARM 1-06-24 2:06AM T 1 TANK 87 OVERFILL ALARM CLEAR 1-01-24 10:19AM T 1 TANK 87 OVERFILL ALARM ALARM 1-01-24 10:17AM T 1 TANK 87 OVERFILL ALARM CLEAR 12-23-23 11:47AM T 1 TANK 87 OVERFILL ALARM ALARM 12-23-23 11:44AM OTHER MISSING HOSE SETUP CLEAR 12-21-23 1:58PM OTHER MISS VAPOR FLOW MTR CLEAR 12-21-23 1:24PM OTHER MISS VAPOR FLOW MTR ALARM 12-21-23 1:17PM OTHER MISS VAPOR FLOW MTR CLEAR 12-21-23 1:15PM OTHER MISS VAPOR FLOW MTR ALARM 12-21-23 1:12PM OTHER MISSING HOSE SETUP ALARM 12-21-23 1:12PM f 5 OTHER FM1 CHK VAPOR FLOW MTR CLEAR 12-21-23 1:01PM f 5 OTHER FM1 CHK VAPOR FLOW MTR ALARM 12-21-23 10:02AM f 5 OTHER FM1 CHK VAPOR FLOW MTR CLEAR 12-18-23 10:00AM T 1 TANK 87 OVERFILL ALARM CLEAR 12-17-23 1:26AM T 1 TANK 87 OVERFILL ALARM ALARM 12-17-23 1:24AM f 5 OTHER FM1 CHK VAPOR FLOW MTR ALARM 12-16-23 10:01AM f 5 OTHER FM1 CHK VAPOR FLOW MTR CLEAR 12-14-23 10:00AM f 5 OTHER FM1 CHK VAPOR FLOW MTR ALARM 12-13-23 10:01AM f 6 OTHER FM2 CHK VAPOR FLOW MTR CLEAR 12-12-23 10:00AM f 6 OTHER FM2 CHK VAPOR FLOW MTR ALARM 12-11-23 10:01AM f 5 OTHER FM1 CHK VAPOR FLOW MTR CLEAR 12-10-23 10:00AM f 5 OTHER FM1 CHK VAPOR FLOW MTR ALARM 12-09-23 10:01AM f 3 OTHER FM5 CHK VAPOR FLOW MTR CLEAR 12-08-23 12:19PM T 1 TANK 87 OVERFILL ALARM CLEAR 12-08-23 11:02AM T 1 TANK 87 OVERFILL ALARM ALARM 12-08-23 11:00AM f 3 OTHER FM5 CHK VAPOR FLOW MTR ALARM 12-08-23 10:03AM f 6 OTHER FM2 CHK VAPOR FLOW MTR CLEAR 12-07-23 10:00AM f 6 OTHER FM2 CHK VAPOR FLOW MTR ALARM 12-06-23 10:01AM T 1 TANK 87 OVERFILL ALARM CLEAR 12-06-23 2:54AM T 1 TANK 87 OVERFILL ALARM ALARM 12-06-23 2:50AM h12 OTHER FP12: BLEND3 AIRFLOW MTR SETUP CLEAR 12-04-23 12:56PM h11 OTHER FP11: BLEND3 AIRFLOW MTR SETUP CLEAR 12-04-23 12:50PM h12 OTHER FP12: BLEND3 AIRFLOW MTR SETUP ALARM 12-04-23 12:03PM h11 OTHER FP11: BLEND3 AIRFLOW MTR SETUP ALARM 12-04-23 12:01PM f 6 OTHER FM2 CHK VAPOR FLOW MTR CLEAR 12-04-23 11:59AM f 6 OTHER FM2 CHK VAPOR FLOW MTR ALARM 12-04-23 10:01AM L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L 2 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L 5 STP SUMP DEISE STP SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L14 DISP PAN 19-20 SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L13 DISP PAN 17-18 SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L12 DISP PAN 15-16 SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L11 DISP PAN 13-14 SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L10 DISP PAN 11-12 SENSOR OUT ALARM CLEAR 12-03-23 12:05PM L 9 DISP PAN 9-10 SENSOR OUT ALARM CLEAR 12-03-23 12:05PM I11200 JAN 10, 2024 2:17 PM FASTRIP 4013 S H ST BAKERSFIELD NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 12-21-23 1:03PM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 12-21-23 1:03PM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 12-21-23 1:03PM OTHER ISD SENSOR OUT WARN CLEAR 12-21-23 1:01PM OTHER ISD SENSOR OUT WARN ALARM 12-21-23 10:02AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 12-19-23 10:02AM OTHER ISD SENSOR OUT WARN CLEAR 12-18-23 10:02AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 12-17-23 10:02AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 12-17-23 10:02AM OTHER ISD SENSOR OUT WARN ALARM 12-16-23 10:01AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 12-15-23 1:18PM OTHER ISD SENSOR OUT WARN CLEAR 12-14-23 10:01AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 12-14-23 10:01AM OTHER ISD SENSOR OUT WARN ALARM 12-13-23 10:01AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 12-12-23 12:21PM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 12-12-23 12:21PM OTHER ISD SENSOR OUT WARN CLEAR 12-12-23 10:02AM OTHER ISD SENSOR OUT WARN ALARM 12-11-23 10:01AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 12-11-23 10:01AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 12-11-23 10:01AM OTHER ISD SENSOR OUT WARN CLEAR 12-10-23 10:01AM OTHER ISD SENSOR OUT WARN ALARM 12-09-23 10:01AM OTHER ISD SENSOR OUT WARN CLEAR 12-08-23 12:19PM OTHER ISD SENSOR OUT WARN ALARM 12-08-23 10:03AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 4:15PM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 4:15PM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 4:14PM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 4:14PM OTHER ISD SENSOR OUT WARN CLEAR 12-07-23 10:02AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN ALARM 12-07-23 10:02AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 12-07-23 10:02AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 12-07-23 10:02AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 12-07-23 10:02AM OTHER ISD SENSOR OUT WARN ALARM 12-06-23 10:01AM OTHER ISD SENSOR OUT WARN CLEAR 12-04-23 12:44PM OTHER ISD SENSOR OUT WARN ALARM 12-04-23 10:01AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:08AM SYSTEM PAPER OUT CLEAR 2-13-21 8:08AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:08AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:08AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:08AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:08AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:08AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:07AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:07AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:07AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:05AM SYSTEM PAPER OUT ALARM 2-13-21 8:05AM T 3 TANK DSL INVALID FUEL LEVEL ALARM 2-13-21 8:05AM I20600 JAN 10, 2024 2:17 PM FASTRIP 4013 S H ST BAKERSFIELD TANK ALARM HISTORY TANK 1 87 OVERFILL ALARM JAN 6, 2024 2:06 AM JAN 1, 2024 10:17 AM DEC 23, 2023 11:44 AM TANK 2 91 TANK 3 DSL INVALID FUEL LEVEL FEB 13, 2021 8:05 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JAN 10, 2024 2:17 PM I30200 JAN 10, 2024 2:17 PM FASTRIP 4013 S H ST BAKERSFIELD LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 STP DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:57 AM FUEL ALARM 2 87 ANN DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:43 AM FUEL ALARM 3 91 STP DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:57 AM FUEL ALARM 4 91 ANN DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:42 AM FUEL ALARM 5 DEISE STP DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:56 AM FUEL ALARM 6 DSL ANN DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:42 AM FUEL ALARM 9 9-10 DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:55 AM FUEL ALARM 10 11-12 DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:55 AM FUEL ALARM 11 13-14 DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:56 AM FUEL ALARM 12 15-16 DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:54 AM FUEL ALARM 13 17-18 DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:54 AM FUEL ALARM 14 19-20 DEC 3, 2023 12:04 PM SENSOR OUT ALARM DEC 3, 2023 11:53 AM FUEL ALARM I31600 JAN 10, 2024 2:17 PM FASTRIP 4013 S H ST BAKERSFIELD SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VPS 2 FM1 3 FM2 4 FM3 5 FM4 6 FM5 7 FM6 I40200 JAN 10, 2024 2:17 PM I40300 JAN 10, 2024 2:17 PM I34200 JAN 10, 2024 2:17 PM I34700 JAN 10, 2024 2:17 PM IV0100 JAN 10, 2024 2:17 PM FASTRIP 4013 S H ST BAKERSFIELD ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-12-21 10:02:53 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 5:FM1 23-12-21 10:02:53 A/L RATIO DEGRADATION FP12 BLEND3 0.74 23-12-21 10:02:53 A/L RATIO DEGRADATION FP10 BLEND3 0.75 23-12-21 10:02:53 A/L RATIO DEGRADATION FP 9 BLEND3 0.60 23-12-20 10:02:46 A/L RATIO DEGRADATION FP12 BLEND3 0.71 23-12-20 10:02:46 A/L RATIO DEGRADATION FP10 BLEND3 0.75 23-12-20 10:02:46 A/L RATIO DEGRADATION FP 9 BLEND3 0.60 23-12-19 10:02:54 A/L RATIO DEGRADATION FP12 BLEND3 0.72 23-12-19 10:02:54 A/L RATIO DEGRADATION FP10 BLEND3 0.75 23-12-19 10:02:54 A/L RATIO DEGRADATION FP 9 BLEND3 0.55 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-12-23 10:02:49 READINESS ISD:PP EVR:PP ISD & EVR READY 23-12-22 10:02:59 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-12-21 13:17:40 READINESS ISD:PF EVR:NNN CHECK ISD SENSORS 23-12-21 13:17:40 ISD STARTUP 23-12-21 13:17:29 ISD SHUTDOWN 23-12-21 13:16:03 READINESS ISD:PF EVR:NNN CHECK ISD SENSORS 23-12-21 13:16:03 ISD STARTUP 23-12-21 13:15:52 ISD SHUTDOWN 23-12-21 13:03:40 COLLECTION TEST HH12 GRADE TEST MANUALLY CLEARED 23-12-21 13:03:35 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED AFTER Responses Received: I10200 JAN 10, 2024 2:52 PM FASTRIP 4013 S H ST BAKERSFIELD SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 506485 505817 2 INTERSTITIAL BD 202115 202057 3 4 PROBE / G.T. 162865 162817 4 INTERSTITIAL BD 200843 200756 5 UNUSED 4919832 4891966 6 UNUSED 4914353 4891639 7 UNUSED 4913506 4892402 8 UNUSED 4916136 4890373 9 STP SENSE BOARD 33110 33088 10 RELAY BOARD 14978 14978 11 UNUSED 4915571 4892137 12 UNUSED 4912180 4888624 13 UNUSED 4912528 4889759 14 UNUSED 4913267 4892137 15 UNUSED 4911897 4892573 16 UNUSED 4913984 4887795 COMM 1 ELEC DISP INT. 101006 101014 COMM 2 RS232 SERIAL BD 15000 15000 COMM 3 RS232 SERIAL BD 14956 14956 COMM 4 UNUSED 4917115 4892748 COMM 5 UNUSED 4911723 4888363 COMM 6 UNUSED 4912180 4889824 I90200 JAN 10, 2024 2:52 PM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JAN 10, 2024 2:52 PM FASTRIP 4013 S H ST BAKERSFIELD PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 1-10-24 2:46PM L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 1-10-24 2:46PM L 5 STP SUMP DEISE STP SENSOR OUT ALARM CLEAR 1-10-24 2:46PM L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 1-10-24 2:46PM L 2 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 1-10-24 2:46PM L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 1-10-24 2:46PM L 9 DISP PAN 9-10 SENSOR OUT ALARM CLEAR 1-10-24 2:46PM L14 DISP PAN 19-20 SENSOR OUT ALARM CLEAR 1-10-24 2:45PM L11 DISP PAN 13-14 SENSOR OUT ALARM CLEAR 1-10-24 2:45PM L13 DISP PAN 17-18 SENSOR OUT ALARM CLEAR 1-10-24 2:45PM L12 DISP PAN 15-16 SENSOR OUT ALARM CLEAR 1-10-24 2:45PM L10 DISP PAN 11-12 SENSOR OUT ALARM CLEAR 1-10-24 2:45PM L14 DISP PAN 19-20 SENSOR OUT ALARM ALARM 1-10-24 2:45PM L13 DISP PAN 17-18 SENSOR OUT ALARM ALARM 1-10-24 2:45PM L12 DISP PAN 15-16 SENSOR OUT ALARM ALARM 1-10-24 2:45PM L11 DISP PAN 13-14 SENSOR OUT ALARM ALARM 1-10-24 2:45PM L10 DISP PAN 11-12 SENSOR OUT ALARM ALARM 1-10-24 2:45PM L 9 DISP PAN 9-10 SENSOR OUT ALARM ALARM 1-10-24 2:45PM L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 1-10-24 2:45PM L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 1-10-24 2:45PM L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 1-10-24 2:45PM L 2 ANNULAR 87 ANN SENSOR OUT ALARM ALARM 1-10-24 2:45PM L 5 STP SUMP DEISE STP SENSOR OUT ALARM ALARM 1-10-24 2:45PM L 1 STP SUMP 87 STP SENSOR OUT ALARM ALARM 1-10-24 2:45PM L12 DISP PAN 15-16 FUEL ALARM CLEAR 1-10-24 2:41PM L12 DISP PAN 15-16 FUEL ALARM ALARM 1-10-24 2:41PM L13 DISP PAN 17-18 FUEL ALARM CLEAR 1-10-24 2:40PM L13 DISP PAN 17-18 FUEL ALARM ALARM 1-10-24 2:40PM L14 DISP PAN 19-20 FUEL ALARM CLEAR 1-10-24 2:39PM L14 DISP PAN 19-20 FUEL ALARM ALARM 1-10-24 2:39PM L11 DISP PAN 13-14 FUEL ALARM CLEAR 1-10-24 2:38PM L11 DISP PAN 13-14 FUEL ALARM ALARM 1-10-24 2:38PM L10 DISP PAN 11-12 FUEL ALARM CLEAR 1-10-24 2:37PM L10 DISP PAN 11-12 FUEL ALARM ALARM 1-10-24 2:37PM L 9 DISP PAN 9-10 FUEL ALARM CLEAR 1-10-24 2:36PM L 9 DISP PAN 9-10 FUEL ALARM ALARM 1-10-24 2:36PM L 5 STP SUMP DEISE STP FUEL ALARM CLEAR 1-10-24 2:34PM L 5 STP SUMP DEISE STP FUEL ALARM ALARM 1-10-24 2:34PM L 5 STP SUMP DEISE STP FUEL ALARM CLEAR 1-10-24 2:33PM L 5 STP SUMP DEISE STP FUEL ALARM ALARM 1-10-24 2:33PM L 3 STP SUMP 91 STP FUEL ALARM CLEAR 1-10-24 2:31PM L 3 STP SUMP 91 STP FUEL ALARM ALARM 1-10-24 2:31PM L 1 STP SUMP 87 STP FUEL ALARM CLEAR 1-10-24 2:29PM L 1 STP SUMP 87 STP FUEL ALARM ALARM 1-10-24 2:28PM L 2 ANNULAR 87 ANN FUEL ALARM CLEAR 1-10-24 2:27PM L 2 ANNULAR 87 ANN FUEL ALARM ALARM 1-10-24 2:26PM L 4 ANNULAR 91 ANN FUEL ALARM CLEAR 1-10-24 2:26PM L 4 ANNULAR 91 ANN FUEL ALARM ALARM 1-10-24 2:25PM L 6 ANNULAR DSL ANN FUEL ALARM CLEAR 1-10-24 2:23PM L 6 ANNULAR DSL ANN FUEL ALARM ALARM 1-10-24 2:23PM I11200 JAN 10, 2024 2:53 PM FASTRIP 4013 S H ST BAKERSFIELD NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 12-21-23 1:03PM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 12-21-23 1:03PM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 12-21-23 1:03PM OTHER ISD SENSOR OUT WARN CLEAR 12-21-23 1:01PM OTHER ISD SENSOR OUT WARN ALARM 12-21-23 10:02AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 12-19-23 10:02AM OTHER ISD SENSOR OUT WARN CLEAR 12-18-23 10:02AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 12-17-23 10:02AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 12-17-23 10:02AM OTHER ISD SENSOR OUT WARN ALARM 12-16-23 10:01AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 12-15-23 1:18PM OTHER ISD SENSOR OUT WARN CLEAR 12-14-23 10:01AM h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 12-14-23 10:01AM OTHER ISD SENSOR OUT WARN ALARM 12-13-23 10:01AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 12-12-23 12:21PM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 12-12-23 12:21PM OTHER ISD SENSOR OUT WARN CLEAR 12-12-23 10:02AM OTHER ISD SENSOR OUT WARN ALARM 12-11-23 10:01AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 12-11-23 10:01AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 12-11-23 10:01AM OTHER ISD SENSOR OUT WARN CLEAR 12-10-23 10:01AM OTHER ISD SENSOR OUT WARN ALARM 12-09-23 10:01AM OTHER ISD SENSOR OUT WARN CLEAR 12-08-23 12:19PM OTHER ISD SENSOR OUT WARN ALARM 12-08-23 10:03AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 4:15PM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 4:15PM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 4:14PM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN CLEAR 12-07-23 4:14PM OTHER ISD SENSOR OUT WARN CLEAR 12-07-23 10:02AM h11 OTHER FP11: BLEND3 DEGRD COLLECT WARN ALARM 12-07-23 10:02AM h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 12-07-23 10:02AM h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 12-07-23 10:02AM h 8 OTHER FP8: BLEND3 DEGRD COLLECT WARN ALARM 12-07-23 10:02AM OTHER ISD SENSOR OUT WARN ALARM 12-06-23 10:01AM OTHER ISD SENSOR OUT WARN CLEAR 12-04-23 12:44PM OTHER ISD SENSOR OUT WARN ALARM 12-04-23 10:01AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:08AM SYSTEM PAPER OUT CLEAR 2-13-21 8:08AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:08AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:08AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:08AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:08AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:08AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:07AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:07AM SYSTEM PRINTER ERROR CLEAR 2-13-21 8:07AM SYSTEM PRINTER ERROR ALARM 2-13-21 8:05AM SYSTEM PAPER OUT ALARM 2-13-21 8:05AM T 3 TANK DSL INVALID FUEL LEVEL ALARM 2-13-21 8:05AM I20600 JAN 10, 2024 2:53 PM FASTRIP 4013 S H ST BAKERSFIELD TANK ALARM HISTORY TANK 1 87 OVERFILL ALARM JAN 6, 2024 2:06 AM JAN 1, 2024 10:17 AM DEC 23, 2023 11:44 AM TANK 2 91 TANK 3 DSL INVALID FUEL LEVEL FEB 13, 2021 8:05 AM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JAN 10, 2024 2:53 PM I30200 JAN 10, 2024 2:53 PM FASTRIP 4013 S H ST BAKERSFIELD LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 STP JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:28 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 2 87 ANN JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:26 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 3 91 STP JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:31 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 4 91 ANN JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:25 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 5 DEISE STP JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:34 PM FUEL ALARM JAN 10, 2024 2:33 PM FUEL ALARM 6 DSL ANN JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:23 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 9 9-10 JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:36 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 10 11-12 JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:37 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 11 13-14 JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:38 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 12 15-16 JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:41 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 13 17-18 JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:40 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM 14 19-20 JAN 10, 2024 2:45 PM SENSOR OUT ALARM JAN 10, 2024 2:39 PM FUEL ALARM DEC 3, 2023 12:04 PM SENSOR OUT ALARM I31600 JAN 10, 2024 2:53 PM FASTRIP 4013 S H ST BAKERSFIELD SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 VPS 2 FM1 3 FM2 4 FM3 5 FM4 6 FM5 7 FM6 I40200 JAN 10, 2024 2:53 PM I40300 JAN 10, 2024 2:53 PM I34200 JAN 10, 2024 2:53 PM I34700 JAN 10, 2024 2:53 PM IV0100 JAN 10, 2024 2:53 PM FASTRIP 4013 S H ST BAKERSFIELD ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-12-21 10:02:53 SENSOR OUT SELFTEST CHECK VAPOR FLOW METER f 5:FM1 23-12-21 10:02:53 A/L RATIO DEGRADATION FP12 BLEND3 0.74 23-12-21 10:02:53 A/L RATIO DEGRADATION FP10 BLEND3 0.75 23-12-21 10:02:53 A/L RATIO DEGRADATION FP 9 BLEND3 0.60 23-12-20 10:02:46 A/L RATIO DEGRADATION FP12 BLEND3 0.71 23-12-20 10:02:46 A/L RATIO DEGRADATION FP10 BLEND3 0.75 23-12-20 10:02:46 A/L RATIO DEGRADATION FP 9 BLEND3 0.60 23-12-19 10:02:54 A/L RATIO DEGRADATION FP12 BLEND3 0.72 23-12-19 10:02:54 A/L RATIO DEGRADATION FP10 BLEND3 0.75 23-12-19 10:02:54 A/L RATIO DEGRADATION FP 9 BLEND3 0.55 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-01-10 14:47:39 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-01-10 14:47:39 ISD STARTUP 24-01-10 14:47:34 ISD SHUTDOWN 23-12-23 10:02:49 READINESS ISD:PP EVR:PP ISD & EVR READY 23-12-22 10:02:59 READINESS ISD:PP EVR:NP EVR READINESS PENDING 23-12-21 13:17:40 READINESS ISD:PF EVR:NNN CHECK ISD SENSORS 23-12-21 13:17:40 ISD STARTUP 23-12-21 13:17:29 ISD SHUTDOWN 23-12-21 13:16:03 READINESS ISD:PF EVR:NNN CHECK ISD SENSORS 23-12-21 13:16:03 ISD STARTUP