Loading...
HomeMy WebLinkAboutFMC 2024Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10022566 1/23/2024 Mt. Vernon & Columbus ARCO 2698 Mt. Vernon Avenue Bakersfield 93306 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fisher 1073967 10278702 3/10/25 Veeder Root - C33847 07/24/25 Vaporless Manufacturing LLC 3/14/25 OPW - 1193587 8/4/25 1/23/2024 7 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 VEEDER ROOT TLS350 336.02 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 87 STP L2 409 87 Annular L3 208 91 STP L4 409 91 Annular L5 208 Dispenser 1/2 L6 208 Dispenser 3/4 L7 208 Dispenser 5/6 L8 208 Dispenser 7/8 L9 208 87 Fill L10 208 91 Fill Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V 87 Unleaded T2 FX1V 91 Premium Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ Underground Storage Tank Monitoring System Certification Form Page 6 of 6 10. MONITORING SITE PLAN Date site plan was prepared: If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted. 1/23/24 APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Mt. Vernon & Columbus ARCO2698 Mt. Vernon AvenueBakersfield100225663/47/8MPDMPDMPDMPD1/25/6ProductProductProductProductMark Fisher Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10022566 1/23/2024 Mt. Vernon & Columbus ARCO 2698 Mt. Vernon Avenue Bakersfield 93306 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Mark Fisher 1073967 10278702 3/10/25 OPW - 1193587 8/4/25 PEI1200, 1 hour hydrostatic test All Spill Buckets 1/23/2024 2 Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. 87-1 OPW 87-2 OPW 91 OPW Mt. Vernon & Columbus Arco AMPM System Setup: Responses Received: 200 ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 JAN 23, 2024 8:58 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED R 11399 65.24 0.0 65.2 8304 2 UL PREMIUM 3314 38.36 0.0 69.5 8535 I90500 JAN 23, 2024 8:58 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 JAN 23, 2024 8:58 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 JAN 23, 2024 8:58 AM SHIFT TIME 1 : 6:00 AM I50202 JAN 23, 2024 8:58 AM SHIFT TIME 2 : DISABLED I50203 JAN 23, 2024 8:58 AM SHIFT TIME 3 : DISABLED I50204 JAN 23, 2024 8:58 AM SHIFT TIME 4 : DISABLED I54600 JAN 23, 2024 8:58 AM TANK PER TST NEEDED WRN: DISABLED I54900 JAN 23, 2024 8:58 AM TANK ANN TST NEEDED WRN: DISABLED I55300 JAN 23, 2024 8:58 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 JAN 23, 2024 8:58 AM LINE PER TST NEEDED WRN: DISABLED I55900 JAN 23, 2024 8:58 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 JAN 23, 2024 8:58 AM PRINT TC VOLUMES ENABLED I50E00 JAN 23, 2024 8:58 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 JAN 23, 2024 8:58 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 JAN 23, 2024 8:58 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 JAN 23, 2024 8:58 AM DAYLIGHT SAVING TIME ENABLED OFF I51B00 JAN 23, 2024 8:58 AM DAYLIGHT SAVING TIME START DATE MAR WEEK 2 SUN 2:00 AM END DATE NOV WEEK 1 SUN 2:00 AM I51600 JAN 23, 2024 8:58 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 JAN 23, 2024 8:58 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 000000 DISABLED 3 000000 DISABLED 4 000000 DISABLED 5 000000 DISABLED 6 000000 DISABLED I21900 JAN 23, 2024 8:58 AM TANK CHART SECURITY DISABLED I5BD00 JAN 23, 2024 8:58 AM CUSTOM ALARM LABELS DISABLED I56000 JAN 23, 2024 8:58 AM MASS/DENSITY DISABLED I88101 JAN 23, 2024 8:58 AM PORT SETTINGS: COMM BOARD : 1 (EDIM ) RS-232 SECURITY CODE : DISABLED I88102 JAN 23, 2024 8:58 AM PORT SETTINGS: COMM BOARD : 2 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88103 JAN 23, 2024 8:58 AM PORT SETTINGS: COMM BOARD : 3 (RS-232) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED I88104 JAN 23, 2024 8:58 AM I88105 JAN 23, 2024 8:58 AM I88106 JAN 23, 2024 8:58 AM I52000 JAN 23, 2024 8:58 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 ON DATE AUG 6, 2018 DISABLED 2 ON DATE AUG 6, 2018 DISABLED 3 ON DATE AUG 6, 2018 DISABLED 4 ON DATE AUG 6, 2018 DISABLED 5 ON DATE AUG 6, 2018 DISABLED 6 ON DATE AUG 6, 2018 DISABLED 7 ON DATE AUG 6, 2018 DISABLED 8 ON DATE AUG 6, 2018 DISABLED I60100 JAN 23, 2024 8:58 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED R ON 2 UL PREMIUM ON 3 OFF 4 OFF I60200 JAN 23, 2024 8:58 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED R 2 UL PREMIUM 3 4 I60300 JAN 23, 2024 8:58 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED R 1 2 UL PREMIUM 3 3 3 4 4 I60900 JAN 23, 2024 8:58 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED R 0.000700 2 UL PREMIUM 0.000700 3 0.000000 4 0.000000 I60700 JAN 23, 2024 8:58 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED R 117.50 2 UL PREMIUM 117.50 3 0.00 4 0.00 I60A00 JAN 23, 2024 8:58 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED R 20 PTS 19703 2 UL PREMIUM 20 PTS 11849 3 1 PT 0 4 1 PT 0 I60400 JAN 23, 2024 8:58 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED R 19703 2 UL PREMIUM 11849 3 0 4 0 I60500 JAN 23, 2024 8:58 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED R 19703 16062 9961 3824 2 UL PREMIUM 11849 9717 5992 2243 3 0 0 0 0 4 0 0 0 0 I60600 JAN 23, 2024 8:58 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED R 19703 19389 18791 18010 17091 16062 14923 13739 12507 11269 9961 8678 7409 6170 4977 3824 2780 1878 1049 400 2 UL PREMIUM 11849 11676 11334 10963 10334 9717 9027 8307 7554 6795 5992 5204 4426 3652 2941 2243 1616 1079 594 221 3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 JAN 23, 2024 8:58 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED R NO 2 UL PREMIUM NO 3 NO 4 NO I62F00 JAN 23, 2024 8:58 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED R 4.0 IN. 2 UL PREMIUM 4.0 IN. I62700 JAN 23, 2024 8:58 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED R 2.0 2 UL PREMIUM 2.0 I64200 JAN 23, 2024 8:58 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED R LOW 2 UL PREMIUM LOW I62400 JAN 23, 2024 8:58 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED R 3.0 2 UL PREMIUM 3.0 I62800 JAN 23, 2024 8:58 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED R 19703 2 UL PREMIUM 11849 3 0 4 0 I62300 JAN 23, 2024 8:59 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED R 17733 2 UL PREMIUM 10664 3 0 4 0 I62200 JAN 23, 2024 8:59 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED R 18718 2 UL PREMIUM 11257 3 0 4 0 I62900 JAN 23, 2024 8:59 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED R 2955 2 UL PREMIUM 1777 3 0 4 0 I62100 JAN 23, 2024 8:59 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED R 1000 2 UL PREMIUM 500 3 0 4 0 I62600 JAN 23, 2024 8:59 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED R 99 2 UL PREMIUM 99 3 99 4 99 I62500 JAN 23, 2024 8:59 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED R 99 2 UL PREMIUM 99 3 99 4 99 I60800 JAN 23, 2024 8:59 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED R 1.00 2 UL PREMIUM 0.00 3 0.00 4 0.00 I60B00 JAN 23, 2024 8:59 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 JAN 23, 2024 8:59 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED R 0.00 2 UL PREMIUM 0.00 3 0.00 4 0.00 I61200 JAN 23, 2024 8:59 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED R NONE NONE 2 UL PREMIUM NONE NONE 3 NONE NONE 4 NONE NONE I63600 JAN 23, 2024 8:59 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED R 5713 2 UL PREMIUM 3436 3 0 4 0 I62A00 JAN 23, 2024 8:59 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED R 5713 2 UL PREMIUM 3436 3 0 4 0 I62C00 JAN 23, 2024 8:59 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED R STANDARD 2 UL PREMIUM STANDARD 3 STANDARD 4 STANDARD I62D00 JAN 23, 2024 8:59 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED R GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 UL PREMIUM GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 JAN 23, 2024 8:59 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED R OFF OFF 2 UL PREMIUM OFF OFF 3 OFF OFF 4 OFF OFF I63000 JAN 23, 2024 8:59 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED R OFF 2 UL PREMIUM OFF 3 OFF 4 OFF I63200 JAN 23, 2024 8:59 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED R OFF 2 UL PREMIUM OFF 3 OFF 4 OFF I61000 JAN 23, 2024 8:59 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED R 5 2 UL PREMIUM 2 3 1 4 1 I63A00 JAN 23, 2024 8:59 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED R 10.00% 2 UL PREMIUM 10.00% 3 10.00% 4 10.00% I61100 JAN 23, 2024 8:59 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK JAN 9, 2017 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 JAN 23, 2024 8:59 AM CSLD PROBABLITY OF DETECTION I61400 JAN 23, 2024 8:59 AM CSLD CLIMATE FACTOR I61600 JAN 23, 2024 8:59 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED R IMMEDIATE 2 UL PREMIUM IMMEDIATE 3 IMMEDIATE 4 IMMEDIATE I61A00 JAN 23, 2024 8:59 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED R DISABLED 2 UL PREMIUM DISABLED 3 DISABLED 4 DISABLED I61B00 JAN 23, 2024 8:59 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 JAN 23, 2024 8:59 AM CSLD REPORT ONLY I62B00 JAN 23, 2024 8:59 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED R ??? 0, 0 2 UL PREMIUM ??? 0, 0 3 ??? 0, 0 4 ??? 0, 0 I63300 JAN 23, 2024 8:59 AM LEAK TEST REPORT FORMAT: NORMAL I63400 JAN 23, 2024 8:59 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED R 0 2 UL PREMIUM 0 3 0 4 0 I63500 JAN 23, 2024 8:59 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED R 1 2 UL PREMIUM 1 3 1 4 1 I63900 JAN 23, 2024 8:59 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED R END FACTOR: NONE 2 UL PREMIUM END FACTOR: NONE 3 END FACTOR: NONE 4 END FACTOR: NONE I78000 JAN 23, 2024 8:59 AM I77700 JAN 23, 2024 8:59 AM I77800 JAN 23, 2024 8:59 AM I78C00 JAN 23, 2024 8:59 AM I78300 JAN 23, 2024 8:59 AM I78F00 JAN 23, 2024 8:59 AM I78700 JAN 23, 2024 8:59 AM I70200 JAN 23, 2024 8:59 AM LIQUID LABEL DEVICE LABEL 1 87 STP 2 87 ANN 3 91 STP 4 91 ANN 5 DISP 1-2 6 DISP 3-4 7 DISP 5-6 8 DISP 7-8 9 87 FILL 10 91 FILL 11 12 13 14 15 16 I70300 JAN 23, 2024 9:00 AM LIQUID TYPE SENSOR LOCATION TYPE 1 87 STP TRI-STATE (SINGLE FLOAT) 2 87 ANN TRI-STATE (SINGLE FLOAT) 3 91 STP TRI-STATE (SINGLE FLOAT) 4 91 ANN TRI-STATE (SINGLE FLOAT) 5 DISP 1-2 TRI-STATE (SINGLE FLOAT) 6 DISP 3-4 TRI-STATE (SINGLE FLOAT) 7 DISP 5-6 TRI-STATE (SINGLE FLOAT) 8 DISP 7-8 TRI-STATE (SINGLE FLOAT) 9 87 FILL TRI-STATE (SINGLE FLOAT) 10 91 FILL TRI-STATE (SINGLE FLOAT) 11 TRI-STATE (SINGLE FLOAT) 12 TRI-STATE (SINGLE FLOAT) 13 TRI-STATE (SINGLE FLOAT) 14 TRI-STATE (SINGLE FLOAT) 15 TRI-STATE (SINGLE FLOAT) 16 TRI-STATE (SINGLE FLOAT) I70400 JAN 23, 2024 9:00 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 87 STP STP SUMP 2 87 ANN ANNULAR SPACE 3 91 STP STP SUMP 4 91 ANN ANNULAR SPACE 5 DISP 1-2 DISPENSER PAN 6 DISP 3-4 DISPENSER PAN 7 DISP 5-6 DISPENSER PAN 8 DISP 7-8 DISPENSER PAN 9 87 FILL PIPING SUMP 10 91 FILL PIPING SUMP 11 OTHER SENSORS 12 OTHER SENSORS 13 OTHER SENSORS 14 OTHER SENSORS 15 OTHER SENSORS 16 OTHER SENSORS I74200 JAN 23, 2024 9:00 AM I74300 JAN 23, 2024 9:00 AM I74400 JAN 23, 2024 9:00 AM I74700 JAN 23, 2024 9:00 AM I74800 JAN 23, 2024 9:00 AM I74900 JAN 23, 2024 9:00 AM I7BC00 JAN 23, 2024 9:00 AM I80200 JAN 23, 2024 9:00 AM I80300 JAN 23, 2024 9:00 AM I80400 JAN 23, 2024 9:00 AM I80700 JAN 23, 2024 9:00 AM RELAY LABEL DEVICE LABEL 1 87 STP 2 91 STP 3 4 OVERFILL ALARM I80900 JAN 23, 2024 9:00 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 87 STP NORMALLY CLOSED 2 91 STP NORMALLY CLOSED 3 NORMALLY OPEN 4 OVERFILL ALARM NORMALLY OPEN I80B00 JAN 23, 2024 9:00 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 87 STP 1 2 91 STP 2 3 NONE 4 OVERFILL ALARM NONE I80A00 JAN 23, 2024 9:00 AM RELAY TYPE RELAY DESIGNATION TYPE 1 87 STP STANDARD 2 91 STP STANDARD 3 STANDARD 4 OVERFILL ALARM STANDARD I80C00 JAN 23, 2024 9:00 AM I80800 JAN 23, 2024 9:00 AM RELAY SETUP REPORT R 1:87 STP TYPE: STANDARD NORMALLY CLOSED TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 1:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 1:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL R 2:91 STP TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 3:FUEL ALARM L 5:FUEL ALARM L 6:FUEL ALARM L 7:FUEL ALARM L 8:FUEL ALARM L 3:SENSOR OUT ALARM L 5:SENSOR OUT ALARM L 6:SENSOR OUT ALARM L 7:SENSOR OUT ALARM L 8:SENSOR OUT ALARM L 3:SHORT ALARM L 5:SHORT ALARM L 6:SHORT ALARM L 7:SHORT ALARM L 8:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL R 3: TYPE: STANDARD NORMALLY OPEN TANK #: NONE - NO ALARM ASSIGNMENTS - R 4:OVERFILL ALARM TYPE: STANDARD NORMALLY OPEN TANK #: NONE IN-TANK ALARMS ALL:OVERFILL ALARM ALL:HIGH PRODUCT ALARM ALL:MAX PRODUCT ALARM LIQUID SENSOR ALMS ALL:FUEL ALARM ALL:SENSOR OUT ALARM ALL:SHORT ALARM I79000 JAN 23, 2024 9:03 AM EDIM:1 VR:330273-002-C TD:97.11.13.15.52 I79100 JAN 23, 2024 9:03 AM I72300 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 1-2 PS VAPOR PRESSURE 02 1-2 FM AIR FLOW METER 03 3-4 FM AIR FLOW METER 04 5-6 FM AIR FLOW METER 05 7-8 FM AIR FLOW METER 06 UNKNOWN 07 UNKNOWN 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 EVR/ISD SETUP TYPE: VACUUM ASSIST VACUUM ASSIST TYPE: HEALY VAC IV4F00 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 VAPOR PROCESSOR TYPE NONE IV4700 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 ASSESSMENT TIME START TIME: 10:00 AM TIME DELAY MINUTES: 1 IV5200 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 ACCEPT HIGH ORVR: YES IV4A00 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 00 01 01 02 BLEND3 02 01 02 01 02 BLEND3 03 02 03 04 02 BLEND3 04 03 04 04 02 BLEND3 05 04 05 02 02 BLEND3 06 05 06 02 02 BLEND3 07 06 07 03 02 BLEND3 08 07 08 03 02 BLEND3 IV4B00 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 00 01 01/01 09/01 00/01 xx/xx 01 01 01/02 09/02 00/02 xx/xx 02 04 01/03 09/03 00/03 xx/xx 03 04 01/04 09/04 00/04 xx/xx 04 02 01/05 09/05 00/05 xx/xx 05 02 01/06 09/06 00/06 xx/xx 06 03 01/07 09/07 00/07 xx/xx 07 03 01/08 09/08 00/08 xx/xx IV4900 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 JAN 23, 2024 9:03 AM ISD VERSION: 01.07 Mt. Vernon & Columbus Arco AMPM Alarm History: BEFORE: Responses Received: I10200 JAN 23, 2024 9:03 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9561025 9530914 2 UNUSED 9534016 9507078 3 UNUSED 9526570 9496669 4 UNUSED 9528531 9505591 5 4 PROBE / G.T. 163997 163983 6 INTERSTITIAL BD 202153 201986 7 8SMARTSENSOR BD 39445 39433 8 INTERSTITIAL BD 202038 202194 9 UNUSED 9534355 9512028 10 RELAY BOARD 15007 15029 11 UNUSED 9536162 9514270 12 UNUSED 9526314 9506014 13 UNUSED 9521446 9506302 14 UNUSED 9523406 9507301 15 UNUSED 9525984 9506036 16 UNUSED 9526226 9508788 COMM 1 ELEC DISP INT. 101305 101454 COMM 2 SERIAL SAT BD 484597 484351 COMM 3 RS232 SERIAL BD 15051 15051 COMM 4 UNUSED 9531205 9510630 COMM 5 UNUSED 9527526 9506014 COMM 6 UNUSED 9528143 9505259 I90200 JAN 23, 2024 9:04 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JAN 23, 2024 9:04 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME E 1 OTHER G COMMUNICATION ALARM CLEAR 1-22-24 11:36AM E 1 OTHER G COMMUNICATION ALARM ALARM 1-22-24 11:30AM E 1 OTHER G COMMUNICATION ALARM CLEAR 1-22-24 11:07AM E 1 OTHER G COMMUNICATION ALARM ALARM 1-22-24 11:03AM E 1 OTHER G COMMUNICATION ALARM CLEAR 1-20-24 1:30PM E 1 OTHER G COMMUNICATION ALARM ALARM 1-20-24 1:27PM E 1 OTHER G COMMUNICATION ALARM CLEAR 1-20-24 8:25AM E 1 OTHER G COMMUNICATION ALARM ALARM 1-20-24 8:23AM E 1 OTHER G COMMUNICATION ALARM CLEAR 1-11-24 2:45AM E 1 OTHER G COMMUNICATION ALARM ALARM 1-11-24 2:44AM E 1 OTHER G COMMUNICATION ALARM CLEAR 1-11-24 2:21AM E 1 OTHER G COMMUNICATION ALARM ALARM 1-11-24 2:19AM E 1 OTHER G COMMUNICATION ALARM CLEAR 11-29-23 8:31AM E 1 OTHER G COMMUNICATION ALARM ALARM 11-29-23 8:29AM E 1 OTHER G COMMUNICATION ALARM CLEAR 11-24-23 3:49PM E 1 OTHER G COMMUNICATION ALARM ALARM 11-24-23 3:47PM f 2 OTHER 5-6 FM CHK VAPOR FLOW MTR CLEAR 11-10-23 2:00PM f 2 OTHER 5-6 FM CHK VAPOR FLOW MTR ALARM 11-10-23 10:01AM E 1 OTHER G COMMUNICATION ALARM CLEAR 11-10-23 9:24AM E 1 OTHER G COMMUNICATION ALARM ALARM 11-10-23 9:22AM E 1 OTHER G COMMUNICATION ALARM CLEAR 11-10-23 3:59AM E 1 OTHER G COMMUNICATION ALARM ALARM 11-10-23 3:57AM E 1 OTHER G COMMUNICATION ALARM CLEAR 11-09-23 4:36PM E 1 OTHER G COMMUNICATION ALARM ALARM 11-09-23 4:35PM E 1 OTHER G COMMUNICATION ALARM CLEAR 10-27-23 1:02AM E 1 OTHER G COMMUNICATION ALARM ALARM 10-27-23 12:59AM E 1 OTHER G COMMUNICATION ALARM CLEAR 10-10-23 4:52AM E 1 OTHER G COMMUNICATION ALARM ALARM 10-10-23 4:50AM E 1 OTHER G COMMUNICATION ALARM CLEAR 10-10-23 4:20AM E 1 OTHER G COMMUNICATION ALARM ALARM 10-10-23 4:19AM E 1 OTHER G COMMUNICATION ALARM CLEAR 10-09-23 10:57PM E 1 OTHER G COMMUNICATION ALARM ALARM 10-09-23 10:56PM E 1 OTHER G COMMUNICATION ALARM CLEAR 9-28-23 1:15AM E 1 OTHER G COMMUNICATION ALARM ALARM 9-28-23 1:13AM E 1 OTHER G COMMUNICATION ALARM CLEAR 9-28-23 12:55AM E 1 OTHER G COMMUNICATION ALARM ALARM 9-28-23 12:53AM h 7 OTHER FP7: BLEND3 GROSS COLLECT FAIL CLEAR 9-11-23 12:13PM h 7 OTHER FP7: BLEND3 GROSS COLLECT FAIL ALARM 9-11-23 10:03AM E 1 OTHER G COMMUNICATION ALARM CLEAR 8-23-23 10:27AM E 1 OTHER G COMMUNICATION ALARM ALARM 8-23-23 10:25AM E 1 OTHER G COMMUNICATION ALARM CLEAR 8-23-23 9:15AM E 1 OTHER G COMMUNICATION ALARM ALARM 8-23-23 8:45AM E 1 OTHER G COMMUNICATION ALARM CLEAR 8-23-23 8:14AM E 1 OTHER G COMMUNICATION ALARM ALARM 8-23-23 8:11AM E 1 OTHER G COMMUNICATION ALARM CLEAR 7-06-23 2:35AM E 1 OTHER G COMMUNICATION ALARM ALARM 7-06-23 2:33AM E 1 OTHER G COMMUNICATION ALARM CLEAR 6-25-23 8:54AM E 1 OTHER G COMMUNICATION ALARM ALARM 6-25-23 8:52AM E 1 OTHER G COMMUNICATION ALARM CLEAR 6-21-23 12:30PM E 1 OTHER G COMMUNICATION ALARM ALARM 6-21-23 12:28PM I11200 JAN 23, 2024 9:04 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME OTHER ISD GROSS PRES WARN CLEAR 1-22-24 10:34AM OTHER ISD GROSS PRES WARN ALARM 1-22-24 10:03AM SYSTEM PRINTER ERROR CLEAR 1-17-24 11:42PM SYSTEM PAPER OUT CLEAR 1-17-24 11:42PM SYSTEM PAPER OUT ALARM 1-17-24 11:42PM SYSTEM PRINTER ERROR ALARM 1-17-24 11:42PM SYSTEM PRINTER ERROR CLEAR 1-17-24 11:42PM SYSTEM PAPER OUT CLEAR 1-17-24 11:42PM SYSTEM PRINTER ERROR ALARM 1-17-24 11:40PM SYSTEM PAPER OUT ALARM 1-17-24 11:40PM OTHER ISD GROSS PRES WARN CLEAR 1-15-24 10:03AM OTHER ISD GROSS PRES WARN ALARM 1-15-24 10:02AM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 1-11-24 3:26PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 1-10-24 10:02AM OTHER ISD GROSS PRES WARN CLEAR 1-08-24 10:51AM OTHER ISD GROSS PRES WARN ALARM 1-08-24 10:03AM OTHER ISD GROSS PRES WARN CLEAR 1-01-24 10:25AM OTHER ISD GROSS PRES WARN ALARM 1-01-24 10:03AM OTHER ISD GROSS PRES WARN CLEAR 12-25-23 12:15PM OTHER ISD GROSS PRES WARN ALARM 12-25-23 10:03AM OTHER ISD GROSS PRES WARN CLEAR 12-18-23 10:39AM OTHER ISD GROSS PRES WARN ALARM 12-18-23 10:02AM SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM SYSTEM PRINTER ERROR ALARM 12-17-23 2:47AM SYSTEM PAPER OUT ALARM 12-17-23 2:47AM SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM SYSTEM PRINTER ERROR ALARM 12-17-23 2:47AM SYSTEM PAPER OUT ALARM 12-17-23 2:47AM SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM SYSTEM PRINTER ERROR ALARM 12-17-23 2:46AM SYSTEM PAPER OUT ALARM 12-17-23 2:46AM OTHER ISD GROSS PRES WARN CLEAR 12-12-23 8:45AM OTHER ISD GROSS PRES WARN ALARM 12-11-23 10:03AM OTHER ISD GROSS PRES WARN CLEAR 12-04-23 11:14AM OTHER ISD GROSS PRES WARN ALARM 12-04-23 10:02AM h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 12-04-23 9:45AM h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 12-04-23 9:45AM h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN ALARM 12-03-23 10:02AM h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN ALARM 12-03-23 10:02AM h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 12-01-23 5:08PM h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 12-01-23 5:08PM h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN ALARM 12-01-23 10:02AM h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN ALARM 12-01-23 10:02AM OTHER ISD GROSS PRES WARN CLEAR 11-27-23 1:55PM OTHER ISD GROSS PRES WARN ALARM 11-27-23 10:03AM OTHER ISD GROSS PRES WARN CLEAR 11-20-23 10:07AM OTHER ISD GROSS PRES WARN ALARM 11-20-23 10:01AM I20600 JAN 23, 2024 9:04 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 TANK ALARM HISTORY TANK 1 UNLEADED R PROBE OUT JUL 14, 2022 9:26 AM DELIVERY NEEDED SEP 8, 2023 7:23 PM JUL 20, 2023 11:50 PM MAY 26, 2023 9:12 PM TANK 2 UL PREMIUM PROBE OUT JUL 14, 2022 9:26 AM DELIVERY NEEDED OCT 17, 2023 10:32 AM OCT 11, 2023 6:47 PM OCT 6, 2023 12:58 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JAN 23, 2024 9:04 AM I30200 JAN 23, 2024 9:04 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 STP JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 9:49 AM FUEL ALARM SEP 19, 2022 12:43 PM FUEL ALARM 2 87 ANN JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 9:55 AM FUEL ALARM JUL 14, 2022 9:26 AM SENSOR OUT ALARM 3 91 STP JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 9:50 AM FUEL ALARM JUL 14, 2022 9:26 AM SENSOR OUT ALARM 4 91 ANN JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 9:53 AM FUEL ALARM JUL 14, 2022 9:26 AM SENSOR OUT ALARM 5 DISP 1-2 JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 9:59 AM FUEL ALARM JUL 14, 2022 9:26 AM SENSOR OUT ALARM 6 DISP 3-4 JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 9:59 AM FUEL ALARM JUL 14, 2022 9:26 AM SENSOR OUT ALARM 7 DISP 5-6 JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 10:01 AM FUEL ALARM JUL 14, 2022 9:26 AM SENSOR OUT ALARM 8 DISP 7-8 MAR 23, 2023 2:06 PM FUEL ALARM JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 10:00 AM FUEL ALARM 9 87 FILL JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 9:50 AM FUEL ALARM JUL 14, 2022 9:26 AM SENSOR OUT ALARM 10 91 FILL JAN 17, 2023 10:10 AM SENSOR OUT ALARM JAN 17, 2023 9:51 AM FUEL ALARM JUL 14, 2022 9:26 AM SENSOR OUT ALARM I31600 JAN 23, 2024 9:04 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 1-2 PS 2 1-2 FM 3 3-4 FM 4 5-6 FM 5 7-8 FM I40200 JAN 23, 2024 9:04 AM I40300 JAN 23, 2024 9:04 AM I34200 JAN 23, 2024 9:04 AM I34700 JAN 23, 2024 9:04 AM IV0100 JAN 23, 2024 9:04 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :WARN ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME : 0% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-01-22 10:03:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.05 24-01-15 10:02:19 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.67 24-01-11 10:02:51 A/L RATIO DEGRADATION FP 5 BLEND3 0.80 24-01-10 10:02:58 A/L RATIO DEGRADATION FP 5 BLEND3 0.80 24-01-08 10:03:01 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.06 24-01-01 10:03:31 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.42 23-12-25 10:03:39 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.01 23-12-18 10:02:34 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.22 23-12-11 10:03:13 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16 23-12-04 10:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.02 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-09-11 10:03:19 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 19-09-22 10:02:52 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 19-07-23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 19-07-23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 18-08-11 10:03:51 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 1.97 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-01-22 10:34:50 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-01-15 10:03:28 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-01-11 15:26:02 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED 24-01-08 10:51:20 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-01-01 10:25:43 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-12-25 12:15:51 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-12-18 10:39:34 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-12-12 08:45:57 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-12-04 11:14:41 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-12-04 09:45:04 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED AFTER: Responses Received: I10200 JAN 23, 2024 10:34 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 UNUSED 9561025 9605303 2 UNUSED 9534016 9584440 3 UNUSED 9526570 9570539 4 UNUSED 9528531 9572301 5 4 PROBE / G.T. 163997 163733 6 INTERSTITIAL BD 202153 201879 7 8SMARTSENSOR BD 39445 39378 8 INTERSTITIAL BD 202038 201879 9 UNUSED 9534355 9582863 10 RELAY BOARD 15007 15007 11 UNUSED 9536162 9589031 12 UNUSED 9526314 9579977 13 UNUSED 9521446 9569953 14 UNUSED 9523406 9568410 15 UNUSED 9525984 9572773 16 UNUSED 9526226 9581056 COMM 1 ELEC DISP INT. 101305 101278 COMM 2 SERIAL SAT BD 484597 483694 COMM 3 RS232 SERIAL BD 15051 15051 COMM 4 UNUSED 9531205 9577245 COMM 5 UNUSED 9527526 9566428 COMM 6 UNUSED 9528143 9579073 I90200 JAN 23, 2024 10:34 AM SOFTWARE REVISION LEVEL VERSION 336.02 SOFTWARE# 346336-100-C CREATED - 21.02.13.11.53 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 JAN 23, 2024 10:34 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 7 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 1-23-24 9:56AM L 6 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 1-23-24 9:56AM L 8 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 1-23-24 9:56AM L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 1-23-24 9:56AM L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 1-23-24 9:56AM L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 1-23-24 9:56AM L 2 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 1-23-24 9:56AM L 5 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 1-23-24 9:56AM L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 1-23-24 9:56AM L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 1-23-24 9:56AM L 8 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 1-23-24 9:56AM L 7 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 1-23-24 9:56AM L 6 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 1-23-24 9:56AM L 2 ANNULAR 87 ANN SENSOR OUT ALARM ALARM 1-23-24 9:56AM L 5 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 1-23-24 9:56AM L 1 STP SUMP 87 STP SENSOR OUT ALARM ALARM 1-23-24 9:56AM L 2 ANNULAR 87 ANN FUEL ALARM CLEAR 1-23-24 9:55AM L 2 ANNULAR 87 ANN FUEL ALARM ALARM 1-23-24 9:55AM L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 1-23-24 9:42AM L 8 DISP PAN DISP 7-8 FUEL ALARM CLEAR 1-23-24 9:42AM L10 PIPE 91 FILL SENSOR OUT ALARM CLEAR 1-23-24 9:42AM L 7 DISP PAN DISP 5-6 FUEL ALARM CLEAR 1-23-24 9:42AM L 2 ANNULAR 87 ANN FUEL ALARM CLEAR 1-23-24 9:42AM L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 1-23-24 9:42AM L 1 STP SUMP 87 STP FUEL ALARM CLEAR 1-23-24 9:42AM L 6 DISP PAN DISP 3-4 FUEL ALARM CLEAR 1-23-24 9:42AM L 5 DISP PAN DISP 1-2 FUEL ALARM CLEAR 1-23-24 9:42AM L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 1-23-24 9:41AM L 4 ANNULAR 91 ANN FUEL ALARM CLEAR 1-23-24 9:41AM L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 1-23-24 9:41AM L 3 STP SUMP 91 STP FUEL ALARM CLEAR 1-23-24 9:41AM L 9 PIPE 87 FILL SENSOR OUT ALARM CLEAR 1-23-24 9:41AM L10 PIPE 91 FILL SENSOR OUT ALARM ALARM 1-23-24 9:41AM L 8 DISP PAN DISP 7-8 FUEL ALARM ALARM 1-23-24 9:40AM L 7 DISP PAN DISP 5-6 FUEL ALARM ALARM 1-23-24 9:40AM L 4 ANNULAR 91 ANN FUEL ALARM ALARM 1-23-24 9:40AM L 3 STP SUMP 91 STP FUEL ALARM ALARM 1-23-24 9:40AM L 2 ANNULAR 87 ANN FUEL ALARM ALARM 1-23-24 9:40AM L 6 DISP PAN DISP 3-4 FUEL ALARM ALARM 1-23-24 9:40AM L 1 STP SUMP 87 STP FUEL ALARM ALARM 1-23-24 9:40AM L 5 DISP PAN DISP 1-2 FUEL ALARM ALARM 1-23-24 9:40AM L 9 PIPE 87 FILL SENSOR OUT ALARM ALARM 1-23-24 9:40AM L 4 ANNULAR 91 ANN FUEL ALARM CLEAR 1-23-24 9:35AM L 4 ANNULAR 91 ANN FUEL ALARM ALARM 1-23-24 9:35AM L 2 ANNULAR 87 ANN FUEL ALARM CLEAR 1-23-24 9:33AM L 2 ANNULAR 87 ANN FUEL ALARM ALARM 1-23-24 9:33AM L 7 DISP PAN DISP 5-6 FUEL ALARM CLEAR 1-23-24 9:30AM L 7 DISP PAN DISP 5-6 FUEL ALARM ALARM 1-23-24 9:30AM L 8 DISP PAN DISP 7-8 FUEL ALARM CLEAR 1-23-24 9:29AM L 8 DISP PAN DISP 7-8 FUEL ALARM ALARM 1-23-24 9:29AM I11200 JAN 23, 2024 10:34 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L16 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM L15 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM L13 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM L12 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM L11 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM L13 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM L14 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM L13 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM L12 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM L12 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM L16 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM L16 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM L16 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM L14 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM L16 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM L16 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM L15 OTHER SETUP DATA WARNING ALARM 1-23-24 9:40AM L12 OTHER SETUP DATA WARNING ALARM 1-23-24 9:40AM L13 OTHER SETUP DATA WARNING ALARM 1-23-24 9:40AM L11 OTHER SETUP DATA WARNING ALARM 1-23-24 9:40AM OTHER ISD GROSS PRES WARN CLEAR 1-22-24 10:34AM OTHER ISD GROSS PRES WARN ALARM 1-22-24 10:03AM SYSTEM PRINTER ERROR CLEAR 1-17-24 11:42PM SYSTEM PAPER OUT CLEAR 1-17-24 11:42PM SYSTEM PAPER OUT ALARM 1-17-24 11:42PM SYSTEM PRINTER ERROR ALARM 1-17-24 11:42PM SYSTEM PRINTER ERROR CLEAR 1-17-24 11:42PM SYSTEM PAPER OUT CLEAR 1-17-24 11:42PM SYSTEM PRINTER ERROR ALARM 1-17-24 11:40PM SYSTEM PAPER OUT ALARM 1-17-24 11:40PM OTHER ISD GROSS PRES WARN CLEAR 1-15-24 10:03AM OTHER ISD GROSS PRES WARN ALARM 1-15-24 10:02AM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 1-11-24 3:26PM h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 1-10-24 10:02AM OTHER ISD GROSS PRES WARN CLEAR 1-08-24 10:51AM OTHER ISD GROSS PRES WARN ALARM 1-08-24 10:03AM OTHER ISD GROSS PRES WARN CLEAR 1-01-24 10:25AM OTHER ISD GROSS PRES WARN ALARM 1-01-24 10:03AM OTHER ISD GROSS PRES WARN CLEAR 12-25-23 12:15PM OTHER ISD GROSS PRES WARN ALARM 12-25-23 10:03AM OTHER ISD GROSS PRES WARN CLEAR 12-18-23 10:39AM OTHER ISD GROSS PRES WARN ALARM 12-18-23 10:02AM SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM SYSTEM PRINTER ERROR ALARM 12-17-23 2:47AM SYSTEM PAPER OUT ALARM 12-17-23 2:47AM SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM SYSTEM PRINTER ERROR ALARM 12-17-23 2:47AM SYSTEM PAPER OUT ALARM 12-17-23 2:47AM I20600 JAN 23, 2024 10:34 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 TANK ALARM HISTORY TANK 1 UNLEADED R PROBE OUT JUL 14, 2022 9:26 AM DELIVERY NEEDED SEP 8, 2023 7:23 PM JUL 20, 2023 11:50 PM MAY 26, 2023 9:12 PM TANK 2 UL PREMIUM PROBE OUT JUL 14, 2022 9:26 AM DELIVERY NEEDED OCT 17, 2023 10:32 AM OCT 11, 2023 6:47 PM OCT 6, 2023 12:58 PM TANK 5 TANK 6 TANK 7 TANK 8 TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 JAN 23, 2024 10:34 AM I30200 JAN 23, 2024 10:34 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 87 STP JAN 23, 2024 9:56 AM SENSOR OUT ALARM JAN 23, 2024 9:40 AM FUEL ALARM JAN 23, 2024 9:23 AM FUEL ALARM 2 87 ANN JAN 23, 2024 9:56 AM SENSOR OUT ALARM JAN 23, 2024 9:55 AM FUEL ALARM JAN 23, 2024 9:40 AM FUEL ALARM 3 91 STP JAN 23, 2024 9:56 AM SENSOR OUT ALARM JAN 23, 2024 9:41 AM SENSOR OUT ALARM JAN 23, 2024 9:40 AM FUEL ALARM 4 91 ANN JAN 23, 2024 9:56 AM SENSOR OUT ALARM JAN 23, 2024 9:41 AM SENSOR OUT ALARM JAN 23, 2024 9:40 AM FUEL ALARM 5 DISP 1-2 JAN 23, 2024 9:56 AM SENSOR OUT ALARM JAN 23, 2024 9:40 AM FUEL ALARM JAN 23, 2024 9:28 AM FUEL ALARM 6 DISP 3-4 JAN 23, 2024 9:56 AM SENSOR OUT ALARM JAN 23, 2024 9:40 AM FUEL ALARM JAN 23, 2024 9:29 AM FUEL ALARM 7 DISP 5-6 JAN 23, 2024 9:56 AM SENSOR OUT ALARM JAN 23, 2024 9:40 AM FUEL ALARM JAN 23, 2024 9:30 AM FUEL ALARM 8 DISP 7-8 JAN 23, 2024 9:56 AM SENSOR OUT ALARM JAN 23, 2024 9:40 AM FUEL ALARM JAN 23, 2024 9:29 AM FUEL ALARM 9 87 FILL JAN 23, 2024 9:40 AM SENSOR OUT ALARM JAN 23, 2024 9:27 AM FUEL ALARM JAN 17, 2023 10:10 AM SENSOR OUT ALARM 10 91 FILL JAN 23, 2024 9:41 AM SENSOR OUT ALARM JAN 23, 2024 9:26 AM FUEL ALARM JAN 17, 2023 10:10 AM SENSOR OUT ALARM I31600 JAN 23, 2024 10:34 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 1-2 PS 2 1-2 FM 3 3-4 FM 4 5-6 FM 5 7-8 FM I40200 JAN 23, 2024 10:34 AM I40300 JAN 23, 2024 10:34 AM I34200 JAN 23, 2024 10:34 AM I34700 JAN 23, 2024 10:34 AM IV0100 JAN 23, 2024 10:34 AM ARCO AMPM 83781 2698 MT VERNON AVE BAKERSFIELD CA 93306 ISD ALARM STATUS REPORT EVR TYPE: VACUUM ASSIST ISD TYPE: 01.07 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME : 99% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 24-01-22 10:03:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.05 24-01-15 10:02:19 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.67 24-01-11 10:02:51 A/L RATIO DEGRADATION FP 5 BLEND3 0.80 24-01-10 10:02:58 A/L RATIO DEGRADATION FP 5 BLEND3 0.80 24-01-08 10:03:01 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.06 24-01-01 10:03:31 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.42 23-12-25 10:03:39 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.01 23-12-18 10:02:34 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.22 23-12-11 10:03:13 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16 23-12-04 10:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.02 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-09-11 10:03:19 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD 19-09-22 10:02:52 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD 19-07-23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD 19-07-23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD 18-08-11 10:03:51 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 1.97 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 24-01-23 10:03:01 READINESS ISD:PP EVR:NP EVR READINESS PENDING 24-01-23 09:47:20 READINESS ISD:PP EVR:NN EVR READINESS PENDING 24-01-23 09:47:20 ISD STARTUP 24-01-23 09:47:15 ISD SHUTDOWN 24-01-22 10:34:50 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-01-15 10:03:28 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-01-11 15:26:02 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED 24-01-08 10:51:20 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 24-01-01 10:25:43 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-12-25 12:15:51 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED