HomeMy WebLinkAboutFMC 2024Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10022566 1/23/2024
Mt. Vernon & Columbus ARCO
2698 Mt. Vernon Avenue Bakersfield 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fisher
1073967
10278702 3/10/25
Veeder Root - C33847 07/24/25
Vaporless Manufacturing LLC 3/14/25
OPW - 1193587 8/4/25
1/23/2024 7
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VEEDER ROOT TLS350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 87 STP
L2 409 87 Annular
L3 208 91 STP
L4 409 91 Annular
L5 208 Dispenser 1/2
L6 208 Dispenser 3/4
L7 208 Dispenser 5/6
L8 208 Dispenser 7/8
L9 208 87 Fill
L10 208 91 Fill
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87 Unleaded
T2 FX1V 91 Premium
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
1/23/24
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Mt. Vernon & Columbus ARCO2698 Mt. Vernon AvenueBakersfield100225663/47/8MPDMPDMPDMPD1/25/6ProductProductProductProductMark Fisher
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10022566 1/23/2024
Mt. Vernon & Columbus ARCO
2698 Mt. Vernon Avenue Bakersfield 93306
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fisher
1073967
10278702 3/10/25
OPW - 1193587 8/4/25
PEI1200, 1 hour hydrostatic test All Spill Buckets
1/23/2024 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
87-1
OPW
87-2
OPW
91
OPW
Mt. Vernon & Columbus Arco AMPM System Setup:
Responses Received:
200
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
JAN 23, 2024 8:58 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED R 11399 65.24 0.0 65.2 8304
2 UL PREMIUM 3314 38.36 0.0 69.5 8535
I90500
JAN 23, 2024 8:58 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JAN 23, 2024 8:58 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JAN 23, 2024 8:58 AM
SHIFT TIME 1 : 6:00 AM
I50202
JAN 23, 2024 8:58 AM
SHIFT TIME 2 : DISABLED
I50203
JAN 23, 2024 8:58 AM
SHIFT TIME 3 : DISABLED
I50204
JAN 23, 2024 8:58 AM
SHIFT TIME 4 : DISABLED
I54600
JAN 23, 2024 8:58 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JAN 23, 2024 8:58 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JAN 23, 2024 8:58 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JAN 23, 2024 8:58 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JAN 23, 2024 8:58 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JAN 23, 2024 8:58 AM
PRINT TC VOLUMES
ENABLED
I50E00
JAN 23, 2024 8:58 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JAN 23, 2024 8:58 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JAN 23, 2024 8:58 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JAN 23, 2024 8:58 AM
DAYLIGHT SAVING TIME
ENABLED OFF
I51B00
JAN 23, 2024 8:58 AM
DAYLIGHT SAVING TIME
START DATE MAR WEEK 2 SUN 2:00 AM
END DATE NOV WEEK 1 SUN 2:00 AM
I51600
JAN 23, 2024 8:58 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JAN 23, 2024 8:58 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JAN 23, 2024 8:58 AM
TANK CHART SECURITY
DISABLED
I5BD00
JAN 23, 2024 8:58 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JAN 23, 2024 8:58 AM
MASS/DENSITY
DISABLED
I88101
JAN 23, 2024 8:58 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JAN 23, 2024 8:58 AM
PORT SETTINGS:
COMM BOARD : 2 (S-SAT )
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
DTR NORMAL STATE: HIGH
I88103
JAN 23, 2024 8:58 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
JAN 23, 2024 8:58 AM
I88105
JAN 23, 2024 8:58 AM
I88106
JAN 23, 2024 8:58 AM
I52000
JAN 23, 2024 8:58 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE AUG 6, 2018 DISABLED
2 ON DATE AUG 6, 2018 DISABLED
3 ON DATE AUG 6, 2018 DISABLED
4 ON DATE AUG 6, 2018 DISABLED
5 ON DATE AUG 6, 2018 DISABLED
6 ON DATE AUG 6, 2018 DISABLED
7 ON DATE AUG 6, 2018 DISABLED
8 ON DATE AUG 6, 2018 DISABLED
I60100
JAN 23, 2024 8:58 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED R ON
2 UL PREMIUM ON
3 OFF
4 OFF
I60200
JAN 23, 2024 8:58 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED R
2 UL PREMIUM
3
4
I60300
JAN 23, 2024 8:58 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED R 1
2 UL PREMIUM 3
3 3
4 4
I60900
JAN 23, 2024 8:58 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED R 0.000700
2 UL PREMIUM 0.000700
3 0.000000
4 0.000000
I60700
JAN 23, 2024 8:58 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED R 117.50
2 UL PREMIUM 117.50
3 0.00
4 0.00
I60A00
JAN 23, 2024 8:58 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED R 20 PTS
19703 2 UL PREMIUM 20 PTS 11849 3
1 PT 0 4 1 PT 0
I60400
JAN 23, 2024 8:58 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 19703
2 UL PREMIUM 11849
3 0
4 0
I60500
JAN 23, 2024 8:58 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 19703 16062 9961 3824
2 UL PREMIUM 11849 9717 5992 2243
3 0 0 0 0
4 0 0 0 0
I60600
JAN 23, 2024 8:58 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 19703 19389 18791 18010
17091 16062 14923 13739
12507 11269 9961 8678
7409 6170 4977 3824
2780 1878 1049 400
2 UL PREMIUM 11849 11676 11334 10963
10334 9717 9027 8307
7554 6795 5992 5204
4426 3652 2941 2243
1616 1079 594 221
3 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JAN 23, 2024 8:58 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED R NO
2 UL PREMIUM NO
3 NO
4 NO
I62F00
JAN 23, 2024 8:58 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED R 4.0 IN.
2 UL PREMIUM 4.0 IN.
I62700
JAN 23, 2024 8:58 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED R 2.0
2 UL PREMIUM 2.0
I64200
JAN 23, 2024 8:58 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED R LOW
2 UL PREMIUM LOW
I62400
JAN 23, 2024 8:58 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED R 3.0
2 UL PREMIUM 3.0
I62800
JAN 23, 2024 8:58 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 19703
2 UL PREMIUM 11849
3 0
4 0
I62300
JAN 23, 2024 8:59 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 17733
2 UL PREMIUM 10664
3 0
4 0
I62200
JAN 23, 2024 8:59 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 18718
2 UL PREMIUM 11257
3 0
4 0
I62900
JAN 23, 2024 8:59 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 2955
2 UL PREMIUM 1777
3 0
4 0
I62100
JAN 23, 2024 8:59 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 1000
2 UL PREMIUM 500
3 0
4 0
I62600
JAN 23, 2024 8:59 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 99
2 UL PREMIUM 99
3 99
4 99
I62500
JAN 23, 2024 8:59 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 99
2 UL PREMIUM 99
3 99
4 99
I60800
JAN 23, 2024 8:59 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED R 1.00
2 UL PREMIUM 0.00
3 0.00
4 0.00
I60B00
JAN 23, 2024 8:59 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JAN 23, 2024 8:59 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED R 0.00
2 UL PREMIUM 0.00
3 0.00
4 0.00
I61200
JAN 23, 2024 8:59 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED R NONE NONE
2 UL PREMIUM NONE NONE
3 NONE NONE
4 NONE NONE
I63600
JAN 23, 2024 8:59 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 5713
2 UL PREMIUM 3436
3 0
4 0
I62A00
JAN 23, 2024 8:59 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 5713
2 UL PREMIUM 3436
3 0
4 0
I62C00
JAN 23, 2024 8:59 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED R STANDARD
2 UL PREMIUM STANDARD
3 STANDARD
4 STANDARD
I62D00
JAN 23, 2024 8:59 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED R GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 UL PREMIUM GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JAN 23, 2024 8:59 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED R OFF OFF
2 UL PREMIUM OFF OFF
3 OFF OFF
4 OFF OFF
I63000
JAN 23, 2024 8:59 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED R OFF
2 UL PREMIUM OFF
3 OFF
4 OFF
I63200
JAN 23, 2024 8:59 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED R OFF
2 UL PREMIUM OFF
3 OFF
4 OFF
I61000
JAN 23, 2024 8:59 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED R 5
2 UL PREMIUM 2
3 1
4 1
I63A00
JAN 23, 2024 8:59 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED R 10.00%
2 UL PREMIUM 10.00%
3 10.00%
4 10.00%
I61100
JAN 23, 2024 8:59 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
JAN 9, 2017
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
JAN 23, 2024 8:59 AM
CSLD PROBABLITY OF DETECTION
I61400
JAN 23, 2024 8:59 AM
CSLD CLIMATE FACTOR
I61600
JAN 23, 2024 8:59 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED R IMMEDIATE
2 UL PREMIUM IMMEDIATE
3 IMMEDIATE
4 IMMEDIATE
I61A00
JAN 23, 2024 8:59 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED R DISABLED
2 UL PREMIUM DISABLED
3 DISABLED
4 DISABLED
I61B00
JAN 23, 2024 8:59 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JAN 23, 2024 8:59 AM
CSLD REPORT ONLY
I62B00
JAN 23, 2024 8:59 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED R ??? 0, 0
2 UL PREMIUM ??? 0, 0
3 ??? 0, 0
4 ??? 0, 0
I63300
JAN 23, 2024 8:59 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JAN 23, 2024 8:59 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 0
2 UL PREMIUM 0
3 0
4 0
I63500
JAN 23, 2024 8:59 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED R 1
2 UL PREMIUM 1
3 1
4 1
I63900
JAN 23, 2024 8:59 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED R
END FACTOR: NONE
2 UL PREMIUM
END FACTOR: NONE
3
END FACTOR: NONE
4
END FACTOR: NONE
I78000
JAN 23, 2024 8:59 AM
I77700
JAN 23, 2024 8:59 AM
I77800
JAN 23, 2024 8:59 AM
I78C00
JAN 23, 2024 8:59 AM
I78300
JAN 23, 2024 8:59 AM
I78F00
JAN 23, 2024 8:59 AM
I78700
JAN 23, 2024 8:59 AM
I70200
JAN 23, 2024 8:59 AM
LIQUID LABEL
DEVICE LABEL
1 87 STP
2 87 ANN
3 91 STP
4 91 ANN
5 DISP 1-2
6 DISP 3-4
7 DISP 5-6
8 DISP 7-8
9 87 FILL
10 91 FILL
11
12
13
14
15
16
I70300
JAN 23, 2024 9:00 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87 STP TRI-STATE (SINGLE FLOAT)
2 87 ANN TRI-STATE (SINGLE FLOAT)
3 91 STP TRI-STATE (SINGLE FLOAT)
4 91 ANN TRI-STATE (SINGLE FLOAT)
5 DISP 1-2 TRI-STATE (SINGLE FLOAT)
6 DISP 3-4 TRI-STATE (SINGLE FLOAT)
7 DISP 5-6 TRI-STATE (SINGLE FLOAT)
8 DISP 7-8 TRI-STATE (SINGLE FLOAT)
9 87 FILL TRI-STATE (SINGLE FLOAT)
10 91 FILL TRI-STATE (SINGLE FLOAT)
11 TRI-STATE (SINGLE FLOAT)
12 TRI-STATE (SINGLE FLOAT)
13 TRI-STATE (SINGLE FLOAT)
14 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
JAN 23, 2024 9:00 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 87 STP STP SUMP
2 87 ANN ANNULAR SPACE
3 91 STP STP SUMP
4 91 ANN ANNULAR SPACE
5 DISP 1-2 DISPENSER PAN
6 DISP 3-4 DISPENSER PAN
7 DISP 5-6 DISPENSER PAN
8 DISP 7-8 DISPENSER PAN
9 87 FILL PIPING SUMP
10 91 FILL PIPING SUMP
11 OTHER SENSORS
12 OTHER SENSORS
13 OTHER SENSORS
14 OTHER SENSORS
15 OTHER SENSORS
16 OTHER SENSORS
I74200
JAN 23, 2024 9:00 AM
I74300
JAN 23, 2024 9:00 AM
I74400
JAN 23, 2024 9:00 AM
I74700
JAN 23, 2024 9:00 AM
I74800
JAN 23, 2024 9:00 AM
I74900
JAN 23, 2024 9:00 AM
I7BC00
JAN 23, 2024 9:00 AM
I80200
JAN 23, 2024 9:00 AM
I80300
JAN 23, 2024 9:00 AM
I80400
JAN 23, 2024 9:00 AM
I80700
JAN 23, 2024 9:00 AM
RELAY LABEL
DEVICE LABEL
1 87 STP
2 91 STP
3
4 OVERFILL ALARM
I80900
JAN 23, 2024 9:00 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 87 STP NORMALLY CLOSED
2 91 STP NORMALLY CLOSED
3 NORMALLY OPEN
4 OVERFILL ALARM NORMALLY OPEN
I80B00
JAN 23, 2024 9:00 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 87 STP 1
2 91 STP 2
3 NONE
4 OVERFILL ALARM NONE
I80A00
JAN 23, 2024 9:00 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 87 STP STANDARD
2 91 STP STANDARD
3 STANDARD
4 OVERFILL ALARM STANDARD
I80C00
JAN 23, 2024 9:00 AM
I80800
JAN 23, 2024 9:00 AM
RELAY SETUP REPORT
R 1:87 STP
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 1:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 1:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 2:91 STP
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
LIQUID SENSOR ALMS
L 3:FUEL ALARM
L 5:FUEL ALARM
L 6:FUEL ALARM
L 7:FUEL ALARM
L 8:FUEL ALARM
L 3:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 6:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 8:SENSOR OUT ALARM
L 3:SHORT ALARM
L 5:SHORT ALARM
L 6:SHORT ALARM
L 7:SHORT ALARM
L 8:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 3:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 4:OVERFILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
IN-TANK ALARMS
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
ALL:MAX PRODUCT ALARM
LIQUID SENSOR ALMS
ALL:FUEL ALARM
ALL:SENSOR OUT ALARM
ALL:SHORT ALARM
I79000
JAN 23, 2024 9:03 AM
EDIM:1 VR:330273-002-C TD:97.11.13.15.52
I79100
JAN 23, 2024 9:03 AM
I72300
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 1-2 PS VAPOR PRESSURE
02 1-2 FM AIR FLOW METER
03 3-4 FM AIR FLOW METER
04 5-6 FM AIR FLOW METER
05 7-8 FM AIR FLOW METER
06 UNKNOWN
07 UNKNOWN
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
VAPOR PROCESSOR TYPE
NONE
IV4700
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
ACCEPT HIGH ORVR: YES
IV4A00
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 00 01 01 02 BLEND3
02 01 02 01 02 BLEND3
03 02 03 04 02 BLEND3
04 03 04 04 02 BLEND3
05 04 05 02 02 BLEND3
06 05 06 02 02 BLEND3
07 06 07 03 02 BLEND3
08 07 08 03 02 BLEND3
IV4B00
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
00 01 01/01 09/01 00/01 xx/xx
01 01 01/02 09/02 00/02 xx/xx
02 04 01/03 09/03 00/03 xx/xx
03 04 01/04 09/04 00/04 xx/xx
04 02 01/05 09/05 00/05 xx/xx
05 02 01/06 09/06 00/06 xx/xx
06 03 01/07 09/07 00/07 xx/xx
07 03 01/08 09/08 00/08 xx/xx
IV4900
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JAN 23, 2024 9:03 AM
ISD VERSION: 01.07
Mt. Vernon & Columbus Arco AMPM Alarm History:
BEFORE:
Responses Received:
I10200
JAN 23, 2024 9:03 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 UNUSED 9561025 9530914
2 UNUSED 9534016 9507078
3 UNUSED 9526570 9496669
4 UNUSED 9528531 9505591
5 4 PROBE / G.T. 163997 163983
6 INTERSTITIAL BD 202153 201986
7 8SMARTSENSOR BD 39445 39433
8 INTERSTITIAL BD 202038 202194
9 UNUSED 9534355 9512028
10 RELAY BOARD 15007 15029
11 UNUSED 9536162 9514270
12 UNUSED 9526314 9506014
13 UNUSED 9521446 9506302
14 UNUSED 9523406 9507301
15 UNUSED 9525984 9506036
16 UNUSED 9526226 9508788
COMM 1 ELEC DISP INT. 101305 101454
COMM 2 SERIAL SAT BD 484597 484351
COMM 3 RS232 SERIAL BD 15051 15051
COMM 4 UNUSED 9531205 9510630
COMM 5 UNUSED 9527526 9506014
COMM 6 UNUSED 9528143 9505259
I90200
JAN 23, 2024 9:04 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JAN 23, 2024 9:04 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
E 1 OTHER G COMMUNICATION ALARM CLEAR 1-22-24 11:36AM
E 1 OTHER G COMMUNICATION ALARM ALARM 1-22-24 11:30AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 1-22-24 11:07AM
E 1 OTHER G COMMUNICATION ALARM ALARM 1-22-24 11:03AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 1-20-24 1:30PM
E 1 OTHER G COMMUNICATION ALARM ALARM 1-20-24 1:27PM
E 1 OTHER G COMMUNICATION ALARM CLEAR 1-20-24 8:25AM
E 1 OTHER G COMMUNICATION ALARM ALARM 1-20-24 8:23AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 1-11-24 2:45AM
E 1 OTHER G COMMUNICATION ALARM ALARM 1-11-24 2:44AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 1-11-24 2:21AM
E 1 OTHER G COMMUNICATION ALARM ALARM 1-11-24 2:19AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 11-29-23 8:31AM
E 1 OTHER G COMMUNICATION ALARM ALARM 11-29-23 8:29AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 11-24-23 3:49PM
E 1 OTHER G COMMUNICATION ALARM ALARM 11-24-23 3:47PM
f 2 OTHER 5-6 FM CHK VAPOR FLOW MTR CLEAR 11-10-23 2:00PM
f 2 OTHER 5-6 FM CHK VAPOR FLOW MTR ALARM 11-10-23 10:01AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 11-10-23 9:24AM
E 1 OTHER G COMMUNICATION ALARM ALARM 11-10-23 9:22AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 11-10-23 3:59AM
E 1 OTHER G COMMUNICATION ALARM ALARM 11-10-23 3:57AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 11-09-23 4:36PM
E 1 OTHER G COMMUNICATION ALARM ALARM 11-09-23 4:35PM
E 1 OTHER G COMMUNICATION ALARM CLEAR 10-27-23 1:02AM
E 1 OTHER G COMMUNICATION ALARM ALARM 10-27-23 12:59AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 10-10-23 4:52AM
E 1 OTHER G COMMUNICATION ALARM ALARM 10-10-23 4:50AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 10-10-23 4:20AM
E 1 OTHER G COMMUNICATION ALARM ALARM 10-10-23 4:19AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 10-09-23 10:57PM
E 1 OTHER G COMMUNICATION ALARM ALARM 10-09-23 10:56PM
E 1 OTHER G COMMUNICATION ALARM CLEAR 9-28-23 1:15AM
E 1 OTHER G COMMUNICATION ALARM ALARM 9-28-23 1:13AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 9-28-23 12:55AM
E 1 OTHER G COMMUNICATION ALARM ALARM 9-28-23 12:53AM
h 7 OTHER FP7: BLEND3 GROSS COLLECT FAIL CLEAR 9-11-23 12:13PM
h 7 OTHER FP7: BLEND3 GROSS COLLECT FAIL ALARM 9-11-23 10:03AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 8-23-23 10:27AM
E 1 OTHER G COMMUNICATION ALARM ALARM 8-23-23 10:25AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 8-23-23 9:15AM
E 1 OTHER G COMMUNICATION ALARM ALARM 8-23-23 8:45AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 8-23-23 8:14AM
E 1 OTHER G COMMUNICATION ALARM ALARM 8-23-23 8:11AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 7-06-23 2:35AM
E 1 OTHER G COMMUNICATION ALARM ALARM 7-06-23 2:33AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 6-25-23 8:54AM
E 1 OTHER G COMMUNICATION ALARM ALARM 6-25-23 8:52AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 6-21-23 12:30PM
E 1 OTHER G COMMUNICATION ALARM ALARM 6-21-23 12:28PM
I11200
JAN 23, 2024 9:04 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
OTHER ISD GROSS PRES WARN CLEAR 1-22-24 10:34AM
OTHER ISD GROSS PRES WARN ALARM 1-22-24 10:03AM
SYSTEM PRINTER ERROR CLEAR 1-17-24 11:42PM
SYSTEM PAPER OUT CLEAR 1-17-24 11:42PM
SYSTEM PAPER OUT ALARM 1-17-24 11:42PM
SYSTEM PRINTER ERROR ALARM 1-17-24 11:42PM
SYSTEM PRINTER ERROR CLEAR 1-17-24 11:42PM
SYSTEM PAPER OUT CLEAR 1-17-24 11:42PM
SYSTEM PRINTER ERROR ALARM 1-17-24 11:40PM
SYSTEM PAPER OUT ALARM 1-17-24 11:40PM
OTHER ISD GROSS PRES WARN CLEAR 1-15-24 10:03AM
OTHER ISD GROSS PRES WARN ALARM 1-15-24 10:02AM
h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 1-11-24 3:26PM
h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 1-10-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 1-08-24 10:51AM
OTHER ISD GROSS PRES WARN ALARM 1-08-24 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 1-01-24 10:25AM
OTHER ISD GROSS PRES WARN ALARM 1-01-24 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 12-25-23 12:15PM
OTHER ISD GROSS PRES WARN ALARM 12-25-23 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 12-18-23 10:39AM
OTHER ISD GROSS PRES WARN ALARM 12-18-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM
SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM
SYSTEM PRINTER ERROR ALARM 12-17-23 2:47AM
SYSTEM PAPER OUT ALARM 12-17-23 2:47AM
SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM
SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM
SYSTEM PRINTER ERROR ALARM 12-17-23 2:47AM
SYSTEM PAPER OUT ALARM 12-17-23 2:47AM
SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM
SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM
SYSTEM PRINTER ERROR ALARM 12-17-23 2:46AM
SYSTEM PAPER OUT ALARM 12-17-23 2:46AM
OTHER ISD GROSS PRES WARN CLEAR 12-12-23 8:45AM
OTHER ISD GROSS PRES WARN ALARM 12-11-23 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 12-04-23 11:14AM
OTHER ISD GROSS PRES WARN ALARM 12-04-23 10:02AM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 12-04-23 9:45AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 12-04-23 9:45AM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN ALARM 12-03-23 10:02AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN ALARM 12-03-23 10:02AM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN CLEAR 12-01-23 5:08PM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN CLEAR 12-01-23 5:08PM
h 2 OTHER FP2: BLEND3 GROSS COLLECT WARN ALARM 12-01-23 10:02AM
h 1 OTHER FP1: BLEND3 GROSS COLLECT WARN ALARM 12-01-23 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 11-27-23 1:55PM
OTHER ISD GROSS PRES WARN ALARM 11-27-23 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 11-20-23 10:07AM
OTHER ISD GROSS PRES WARN ALARM 11-20-23 10:01AM
I20600
JAN 23, 2024 9:04 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
TANK ALARM HISTORY
TANK 1 UNLEADED R
PROBE OUT JUL 14, 2022 9:26 AM
DELIVERY NEEDED SEP 8, 2023 7:23 PM
JUL 20, 2023 11:50 PM
MAY 26, 2023 9:12 PM
TANK 2 UL PREMIUM
PROBE OUT JUL 14, 2022 9:26 AM
DELIVERY NEEDED OCT 17, 2023 10:32 AM
OCT 11, 2023 6:47 PM
OCT 6, 2023 12:58 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JAN 23, 2024 9:04 AM
I30200
JAN 23, 2024 9:04 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 STP
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 9:49 AM FUEL ALARM
SEP 19, 2022 12:43 PM FUEL ALARM
2 87 ANN
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 9:55 AM FUEL ALARM
JUL 14, 2022 9:26 AM SENSOR OUT ALARM
3 91 STP
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 9:50 AM FUEL ALARM
JUL 14, 2022 9:26 AM SENSOR OUT ALARM
4 91 ANN
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 9:53 AM FUEL ALARM
JUL 14, 2022 9:26 AM SENSOR OUT ALARM
5 DISP 1-2
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 9:59 AM FUEL ALARM
JUL 14, 2022 9:26 AM SENSOR OUT ALARM
6 DISP 3-4
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 9:59 AM FUEL ALARM
JUL 14, 2022 9:26 AM SENSOR OUT ALARM
7 DISP 5-6
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 10:01 AM FUEL ALARM
JUL 14, 2022 9:26 AM SENSOR OUT ALARM
8 DISP 7-8
MAR 23, 2023 2:06 PM FUEL ALARM
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 10:00 AM FUEL ALARM
9 87 FILL
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 9:50 AM FUEL ALARM
JUL 14, 2022 9:26 AM SENSOR OUT ALARM
10 91 FILL
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
JAN 17, 2023 9:51 AM FUEL ALARM
JUL 14, 2022 9:26 AM SENSOR OUT ALARM
I31600
JAN 23, 2024 9:04 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 1-2 PS
2 1-2 FM
3 3-4 FM
4 5-6 FM
5 7-8 FM
I40200
JAN 23, 2024 9:04 AM
I40300
JAN 23, 2024 9:04 AM
I34200
JAN 23, 2024 9:04 AM
I34700
JAN 23, 2024 9:04 AM
IV0100
JAN 23, 2024 9:04 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :WARN
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-01-22 10:03:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.05
24-01-15 10:02:19 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.67
24-01-11 10:02:51 A/L RATIO DEGRADATION FP 5 BLEND3 0.80
24-01-10 10:02:58 A/L RATIO DEGRADATION FP 5 BLEND3 0.80
24-01-08 10:03:01 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.06
24-01-01 10:03:31 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.42
23-12-25 10:03:39 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.01
23-12-18 10:02:34 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.22
23-12-11 10:03:13 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16
23-12-04 10:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.02
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-09-11 10:03:19 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
19-09-22 10:02:52 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
19-07-23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
19-07-23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
18-08-11 10:03:51 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 1.97
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-01-22 10:34:50 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-01-15 10:03:28 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-01-11 15:26:02 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED
24-01-08 10:51:20 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-01-01 10:25:43 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-12-25 12:15:51 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-12-18 10:39:34 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-12-12 08:45:57 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-12-04 11:14:41 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-12-04 09:45:04 COLLECTION TEST HH02 GRADE TEST MANUALLY CLEARED
AFTER:
Responses Received:
I10200
JAN 23, 2024 10:34 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 UNUSED 9561025 9605303
2 UNUSED 9534016 9584440
3 UNUSED 9526570 9570539
4 UNUSED 9528531 9572301
5 4 PROBE / G.T. 163997 163733
6 INTERSTITIAL BD 202153 201879
7 8SMARTSENSOR BD 39445 39378
8 INTERSTITIAL BD 202038 201879
9 UNUSED 9534355 9582863
10 RELAY BOARD 15007 15007
11 UNUSED 9536162 9589031
12 UNUSED 9526314 9579977
13 UNUSED 9521446 9569953
14 UNUSED 9523406 9568410
15 UNUSED 9525984 9572773
16 UNUSED 9526226 9581056
COMM 1 ELEC DISP INT. 101305 101278
COMM 2 SERIAL SAT BD 484597 483694
COMM 3 RS232 SERIAL BD 15051 15051
COMM 4 UNUSED 9531205 9577245
COMM 5 UNUSED 9527526 9566428
COMM 6 UNUSED 9528143 9579073
I90200
JAN 23, 2024 10:34 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JAN 23, 2024 10:34 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 7 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 1-23-24 9:56AM
L 6 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 1-23-24 9:56AM
L 8 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 1-23-24 9:56AM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 1-23-24 9:56AM
L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 1-23-24 9:56AM
L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 1-23-24 9:56AM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 1-23-24 9:56AM
L 5 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 1-23-24 9:56AM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 1-23-24 9:56AM
L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 1-23-24 9:56AM
L 8 DISP PAN DISP 7-8 SENSOR OUT ALARM ALARM 1-23-24 9:56AM
L 7 DISP PAN DISP 5-6 SENSOR OUT ALARM ALARM 1-23-24 9:56AM
L 6 DISP PAN DISP 3-4 SENSOR OUT ALARM ALARM 1-23-24 9:56AM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM ALARM 1-23-24 9:56AM
L 5 DISP PAN DISP 1-2 SENSOR OUT ALARM ALARM 1-23-24 9:56AM
L 1 STP SUMP 87 STP SENSOR OUT ALARM ALARM 1-23-24 9:56AM
L 2 ANNULAR 87 ANN FUEL ALARM CLEAR 1-23-24 9:55AM
L 2 ANNULAR 87 ANN FUEL ALARM ALARM 1-23-24 9:55AM
L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 1-23-24 9:42AM
L 8 DISP PAN DISP 7-8 FUEL ALARM CLEAR 1-23-24 9:42AM
L10 PIPE 91 FILL SENSOR OUT ALARM CLEAR 1-23-24 9:42AM
L 7 DISP PAN DISP 5-6 FUEL ALARM CLEAR 1-23-24 9:42AM
L 2 ANNULAR 87 ANN FUEL ALARM CLEAR 1-23-24 9:42AM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 1-23-24 9:42AM
L 1 STP SUMP 87 STP FUEL ALARM CLEAR 1-23-24 9:42AM
L 6 DISP PAN DISP 3-4 FUEL ALARM CLEAR 1-23-24 9:42AM
L 5 DISP PAN DISP 1-2 FUEL ALARM CLEAR 1-23-24 9:42AM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 1-23-24 9:41AM
L 4 ANNULAR 91 ANN FUEL ALARM CLEAR 1-23-24 9:41AM
L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 1-23-24 9:41AM
L 3 STP SUMP 91 STP FUEL ALARM CLEAR 1-23-24 9:41AM
L 9 PIPE 87 FILL SENSOR OUT ALARM CLEAR 1-23-24 9:41AM
L10 PIPE 91 FILL SENSOR OUT ALARM ALARM 1-23-24 9:41AM
L 8 DISP PAN DISP 7-8 FUEL ALARM ALARM 1-23-24 9:40AM
L 7 DISP PAN DISP 5-6 FUEL ALARM ALARM 1-23-24 9:40AM
L 4 ANNULAR 91 ANN FUEL ALARM ALARM 1-23-24 9:40AM
L 3 STP SUMP 91 STP FUEL ALARM ALARM 1-23-24 9:40AM
L 2 ANNULAR 87 ANN FUEL ALARM ALARM 1-23-24 9:40AM
L 6 DISP PAN DISP 3-4 FUEL ALARM ALARM 1-23-24 9:40AM
L 1 STP SUMP 87 STP FUEL ALARM ALARM 1-23-24 9:40AM
L 5 DISP PAN DISP 1-2 FUEL ALARM ALARM 1-23-24 9:40AM
L 9 PIPE 87 FILL SENSOR OUT ALARM ALARM 1-23-24 9:40AM
L 4 ANNULAR 91 ANN FUEL ALARM CLEAR 1-23-24 9:35AM
L 4 ANNULAR 91 ANN FUEL ALARM ALARM 1-23-24 9:35AM
L 2 ANNULAR 87 ANN FUEL ALARM CLEAR 1-23-24 9:33AM
L 2 ANNULAR 87 ANN FUEL ALARM ALARM 1-23-24 9:33AM
L 7 DISP PAN DISP 5-6 FUEL ALARM CLEAR 1-23-24 9:30AM
L 7 DISP PAN DISP 5-6 FUEL ALARM ALARM 1-23-24 9:30AM
L 8 DISP PAN DISP 7-8 FUEL ALARM CLEAR 1-23-24 9:29AM
L 8 DISP PAN DISP 7-8 FUEL ALARM ALARM 1-23-24 9:29AM
I11200
JAN 23, 2024 10:34 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L16 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM
L15 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM
L13 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM
L12 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM
L11 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:42AM
L13 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM
L14 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM
L13 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM
L12 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM
L12 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM
L16 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM
L16 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM
L16 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM
L14 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM
L16 OTHER SETUP DATA WARNING CLEAR 1-23-24 9:41AM
L16 OTHER SETUP DATA WARNING ALARM 1-23-24 9:41AM
L15 OTHER SETUP DATA WARNING ALARM 1-23-24 9:40AM
L12 OTHER SETUP DATA WARNING ALARM 1-23-24 9:40AM
L13 OTHER SETUP DATA WARNING ALARM 1-23-24 9:40AM
L11 OTHER SETUP DATA WARNING ALARM 1-23-24 9:40AM
OTHER ISD GROSS PRES WARN CLEAR 1-22-24 10:34AM
OTHER ISD GROSS PRES WARN ALARM 1-22-24 10:03AM
SYSTEM PRINTER ERROR CLEAR 1-17-24 11:42PM
SYSTEM PAPER OUT CLEAR 1-17-24 11:42PM
SYSTEM PAPER OUT ALARM 1-17-24 11:42PM
SYSTEM PRINTER ERROR ALARM 1-17-24 11:42PM
SYSTEM PRINTER ERROR CLEAR 1-17-24 11:42PM
SYSTEM PAPER OUT CLEAR 1-17-24 11:42PM
SYSTEM PRINTER ERROR ALARM 1-17-24 11:40PM
SYSTEM PAPER OUT ALARM 1-17-24 11:40PM
OTHER ISD GROSS PRES WARN CLEAR 1-15-24 10:03AM
OTHER ISD GROSS PRES WARN ALARM 1-15-24 10:02AM
h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN CLEAR 1-11-24 3:26PM
h 5 OTHER FP5: BLEND3 DEGRD COLLECT WARN ALARM 1-10-24 10:02AM
OTHER ISD GROSS PRES WARN CLEAR 1-08-24 10:51AM
OTHER ISD GROSS PRES WARN ALARM 1-08-24 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 1-01-24 10:25AM
OTHER ISD GROSS PRES WARN ALARM 1-01-24 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 12-25-23 12:15PM
OTHER ISD GROSS PRES WARN ALARM 12-25-23 10:03AM
OTHER ISD GROSS PRES WARN CLEAR 12-18-23 10:39AM
OTHER ISD GROSS PRES WARN ALARM 12-18-23 10:02AM
SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM
SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM
SYSTEM PRINTER ERROR ALARM 12-17-23 2:47AM
SYSTEM PAPER OUT ALARM 12-17-23 2:47AM
SYSTEM PRINTER ERROR CLEAR 12-17-23 2:47AM
SYSTEM PAPER OUT CLEAR 12-17-23 2:47AM
SYSTEM PRINTER ERROR ALARM 12-17-23 2:47AM
SYSTEM PAPER OUT ALARM 12-17-23 2:47AM
I20600
JAN 23, 2024 10:34 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
TANK ALARM HISTORY
TANK 1 UNLEADED R
PROBE OUT JUL 14, 2022 9:26 AM
DELIVERY NEEDED SEP 8, 2023 7:23 PM
JUL 20, 2023 11:50 PM
MAY 26, 2023 9:12 PM
TANK 2 UL PREMIUM
PROBE OUT JUL 14, 2022 9:26 AM
DELIVERY NEEDED OCT 17, 2023 10:32 AM
OCT 11, 2023 6:47 PM
OCT 6, 2023 12:58 PM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JAN 23, 2024 10:34 AM
I30200
JAN 23, 2024 10:34 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 STP
JAN 23, 2024 9:56 AM SENSOR OUT ALARM
JAN 23, 2024 9:40 AM FUEL ALARM
JAN 23, 2024 9:23 AM FUEL ALARM
2 87 ANN
JAN 23, 2024 9:56 AM SENSOR OUT ALARM
JAN 23, 2024 9:55 AM FUEL ALARM
JAN 23, 2024 9:40 AM FUEL ALARM
3 91 STP
JAN 23, 2024 9:56 AM SENSOR OUT ALARM
JAN 23, 2024 9:41 AM SENSOR OUT ALARM
JAN 23, 2024 9:40 AM FUEL ALARM
4 91 ANN
JAN 23, 2024 9:56 AM SENSOR OUT ALARM
JAN 23, 2024 9:41 AM SENSOR OUT ALARM
JAN 23, 2024 9:40 AM FUEL ALARM
5 DISP 1-2
JAN 23, 2024 9:56 AM SENSOR OUT ALARM
JAN 23, 2024 9:40 AM FUEL ALARM
JAN 23, 2024 9:28 AM FUEL ALARM
6 DISP 3-4
JAN 23, 2024 9:56 AM SENSOR OUT ALARM
JAN 23, 2024 9:40 AM FUEL ALARM
JAN 23, 2024 9:29 AM FUEL ALARM
7 DISP 5-6
JAN 23, 2024 9:56 AM SENSOR OUT ALARM
JAN 23, 2024 9:40 AM FUEL ALARM
JAN 23, 2024 9:30 AM FUEL ALARM
8 DISP 7-8
JAN 23, 2024 9:56 AM SENSOR OUT ALARM
JAN 23, 2024 9:40 AM FUEL ALARM
JAN 23, 2024 9:29 AM FUEL ALARM
9 87 FILL
JAN 23, 2024 9:40 AM SENSOR OUT ALARM
JAN 23, 2024 9:27 AM FUEL ALARM
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
10 91 FILL
JAN 23, 2024 9:41 AM SENSOR OUT ALARM
JAN 23, 2024 9:26 AM FUEL ALARM
JAN 17, 2023 10:10 AM SENSOR OUT ALARM
I31600
JAN 23, 2024 10:34 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 1-2 PS
2 1-2 FM
3 3-4 FM
4 5-6 FM
5 7-8 FM
I40200
JAN 23, 2024 10:34 AM
I40300
JAN 23, 2024 10:34 AM
I34200
JAN 23, 2024 10:34 AM
I34700
JAN 23, 2024 10:34 AM
IV0100
JAN 23, 2024 10:34 AM
ARCO AMPM 83781
2698 MT VERNON AVE
BAKERSFIELD CA 93306
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME : 99%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-01-22 10:03:15 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.05
24-01-15 10:02:19 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.67
24-01-11 10:02:51 A/L RATIO DEGRADATION FP 5 BLEND3 0.80
24-01-10 10:02:58 A/L RATIO DEGRADATION FP 5 BLEND3 0.80
24-01-08 10:03:01 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.06
24-01-01 10:03:31 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.42
23-12-25 10:03:39 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.01
23-12-18 10:02:34 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.22
23-12-11 10:03:13 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16
23-12-04 10:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.02
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-09-11 10:03:19 A/L RATIO GROSS BLOCKAGE FP 7 BLEND3 BLKD
19-09-22 10:02:52 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 BLKD
19-07-23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 2 BLEND3 BLKD
19-07-23 10:02:50 A/L RATIO GROSS BLOCKAGE FP 1 BLEND3 BLKD
18-08-11 10:03:51 A/L RATIO GROSS BLOCKAGE FP 3 BLEND3 1.97
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-01-23 10:03:01 READINESS ISD:PP EVR:NP EVR READINESS PENDING
24-01-23 09:47:20 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-01-23 09:47:20 ISD STARTUP
24-01-23 09:47:15 ISD SHUTDOWN
24-01-22 10:34:50 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-01-15 10:03:28 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-01-11 15:26:02 COLLECTION TEST HH05 GRADE TEST MANUALLY CLEARED
24-01-08 10:51:20 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
24-01-01 10:25:43 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-12-25 12:15:51 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED