Loading...
HomeMy WebLinkAboutFMC 2024Appendix VI Underground Storage Tank Monitoring System Certification Form CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single- Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic Page 1 of 6 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Certification Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Certification Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate. Service Technician Signature Date Total # of Pages 10022956 02/08/2024 Samco California 4100 California Avenue Bakersfield 93309 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Brandon Nunez 1073967 10226373 09/06/2024 VeederRoot TLS-3XX Technician - C32655 10/11/2024 Vaporless Manufacturing Inc. - #5265 10/21/2024 OPW - 1193585 04/14/2025 02/08/2024 5 Underground Storage Tank Monitoring System Certification Form Page 2 of 6 5. MONITORING SYSTEM AND PROGRAMMING A separate Monitoring System Certification Form must be prepared for each control panel. Make of Monitoring System Control Panel Model of Monitoring System Control Panel Software Version Installed Attach the post-certification reports if the monitoring system is capable of generating either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆ Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆ Are the audible and visual alarms operational? ܆܆܆܆ All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆ Are all sensors installed to detect a release at the earliest opportunity in the secondary containment? ܆܆܆܆܆܆ The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆ Was the monitoring control panel’s backup battery visually inspected, functionally tested, and confirmed operational? ܆܆܆܆܆܆ Does the flow of fuel stop at the dispenser if a release is detected in the under- dispenser containment? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆ Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ܆ Sump ܆ UDC ܆܆܆܆܆܆ If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational? ܆܆܆܆܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 VeederRoot TLS-350 336.01 Underground Storage Tank Monitoring System Certification Form Page 3 of 6 6. SENSOR TESTING RESULTS List only sensors tested on date of this certification. List “Sensor ID” as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested. Sensor ID Sensor Model Component(s) Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 L1 208 87-1 Unleaded STP (North) L2 208 91 Supreme STP L3 208 87-2 Unleaded Slave Tank STP L4 208 87-3 Unleaded STP (South) L5 208 Diesel STP L6 208 87-1 Unleaded Fill (North) L7 208 91 Supreme Fill L8 208 87-2 Unleaded Slave Tank Fill L9 208 87-3 Unleaded Fill (South) L10 208 Diesel Fill L11 409 87-1 Unleaded ANN (North) L12 409 91 Supreme ANN L13 409 87-2 Unleaded Slave Tank ANN L14 409 87-3 Unleaded ANN (South) L15 409 Diesel ANN Chain & Float Kit Dispenser 1-2 UDC Chain & Float Kit Dispenser 3-4 UDC Chain & Float Kit Dispenser 5-6 UDC Chain & Float Kit Dispenser 7-8 UDC Chain & Float Kit Dispenser 9-10 UDC Chain & Float Kit Dispenser 11-12 UDC Underground Storage Tank Monitoring System Certification Form Page 4 of 6 7. LINE LEAK DETECTOR TESTING ܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) Simulated release rate verified: (Check all that apply.) ܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆ For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected? ܆܆ ܆܆ ܆܆ For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off when a release is detected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆ For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆ For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆ LLD ID LLD Model Lines Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ Describe all answers marked “No” or “Fail” and proposed remedy in Section 9. List all monitoring equipment either replaced or repaired in Section 9 T1 FX1V 87-1 Unleaded T2 FX1V 91 Supreme T4 FX1V 87-2 Unleaded T5 FX1DV Diesel Underground Storage Tank Monitoring System Certification Form Page 5 of 6 8. IN-TANK GAUGING TESTING ܆܆ Check this box if tank gauging is used only for inventory control. ܆܆ Check this box if NO tank gauging equipment is installed. (Do not complete this section if either box is checked.) Yes No NA All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆ Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆ Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆ Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆ Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆ Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆ Probe ID Probe Model Tanks Monitored Pass Fail ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ ܆܆ 9. COMMENTS Describe all answers marked “No” or “Fail” and proposed remedy. List all monitoring equipment either replaced or repaired. ܆܆ APPENDIX C-10 SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,'    6KHDU9DOYH7\SH 3URGXFW9DSRU ,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//&  Samco California4100 California AvenueBakersfield10022956Disp 3-4Disp 7-8 Disp 11-12MPDMPDMPDMPDMPDMPDDisp 1-2Disp 5-6Disp 9-10ProductProductProductProductProductProductBrandon Nunez Appendix VIII Underground Storage Tank Spill Container Testing Report Form CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council Page 1 of 2 TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month 1. FACILITY INFORMATION CERS ID Test Date Facility Name Facility Address City ZIP Code 2. SERVICE TECHNICIAN INFORMATION Company Performing the Test Phone Mailing Address Service Technician Performing Test Contractor/Tank Tester License Number ICC Number ICC Expiration Date 3. TRAINING AND CERTIFICATIONS Manufacturer and Test Equipment Training Certifications Expiration Date 4. TEST PROCEDURE INFORMATION Test Procedures Used Components Tested 5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST I hereby certify that each spill container was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority. Service Technician Signature Date Total # of Pages 10022956 02/08/2024 Samco California 4100 California Avenue Bakersfield 93309 Nwestco LLC (800) 339-9930 2209 Zeus Court, Bakersfield, CA 93308 Brandon Nunez 1073967 10226373 09/06/2024 OPW - 1193585 04/14/2025 PEI 1200 1 Hour Hydrostatic All Spill Containers 02/08/2024 N/A Underground Storage Tank Spill Container Testing Report Form Additional copies of this page may be attached. Page 2 of 2 6. SPILL CONTAINER DETAILS Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail Tank ID Spill Container Manufacturer: Method of Cathodic Protection ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other ܆܆ Nonmetallic ܆܆ Other Is the spill container minimum capacity five gallons excluding riser volume? ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* ܆܆ Yes ܆܆ No* Method to keep spill container empty ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other ܆܆ Drain ܆܆ Pump ܆܆ Other Spill Container Test Results ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail ܆܆ Pass ܆܆ Fail 1 8. COMMENTS Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy. * Mark here if: Spill containers do not have a minimum capacity of five gallons and require replacement. T1: 87-1 UNL OPW T5: DSL CNI T2: 91 SUP OPW T3: 87-2 (Slave) OPW T4: 87-3 UNL OPW Samco California System Setup Responses Received: 200 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 FEB 8, 2024 9:01 AM TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE 1 UNLEADED NORTH 4194 39.77 0.0 61.0 5490 2 SUPREME 4081 38.97 0.0 65.3 5603 3 UNLEADED SIPHON 3765 36.71 0.0 62.1 5919 4 UNLEADED SOUTH 3783 36.84 0.0 63.5 5901 5 DIESEL 3197 32.57 0.0 69.2 6487 I90500 FEB 8, 2024 9:02 AM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I50500 FEB 8, 2024 9:02 AM SYSTEM TYPE AND LANGUAGE FLAG SYSTEM UNITS U.S. SYSTEM LANGUAGE ENGLISH SYSTEM DATE/TIME FORMAT MON DD YYYY HH:MM:SS xM I50201 FEB 8, 2024 9:02 AM SHIFT TIME 1 : 5:00 AM I50202 FEB 8, 2024 9:02 AM SHIFT TIME 2 : DISABLED I50203 FEB 8, 2024 9:02 AM SHIFT TIME 3 : DISABLED I50204 FEB 8, 2024 9:02 AM SHIFT TIME 4 : DISABLED I54600 FEB 8, 2024 9:02 AM TANK PER TST NEEDED WRN: DISABLED I54900 FEB 8, 2024 9:02 AM TANK ANN TST NEEDED WRN: DISABLED I55300 FEB 8, 2024 9:02 AM LINE RE-ENABLE METHOD PASS LINE TEST I55600 FEB 8, 2024 9:02 AM LINE PER TST NEEDED WRN: DISABLED I55900 FEB 8, 2024 9:02 AM LINE ANN TST NEEDED WRN: DISABLED I50D00 FEB 8, 2024 9:02 AM PRINT TC VOLUMES ENABLED I50E00 FEB 8, 2024 9:02 AM TEMP COMPENSATION VALUE (DEG F ): 60.0 I60B00 FEB 8, 2024 9:02 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I51400 FEB 8, 2024 9:02 AM H-PROTOCOL DATA FORMAT HEIGHT I51A01 FEB 8, 2024 9:02 AM DAYLIGHT SAVING TIME ENABLED OFF I51B00 FEB 8, 2024 9:02 AM DAYLIGHT SAVING TIME START DATE APR WEEK 1 SUN 2:00 AM END DATE OCT WEEK 6 SUN 2:00 AM I51600 FEB 8, 2024 9:02 AM RE-DIRECT LOCAL PRINTOUT DISABLED I50400 FEB 8, 2024 9:02 AM 232 SECURITY CODE PORT SECURITY CODE STATUS 1 000000 DISABLED 2 00 ENABLED 3 00 ENABLED 4 00 ENABLED 5 000000 DISABLED 6 00 ENABLED I21900 FEB 8, 2024 9:02 AM TANK CHART SECURITY DISABLED I5BD00 FEB 8, 2024 9:02 AM CUSTOM ALARM LABELS DISABLED I56000 FEB 8, 2024 9:02 AM MASS/DENSITY DISABLED I88101 FEB 8, 2024 9:02 AM PORT SETTINGS: COMM BOARD : 1 (RS-232) BAUD RATE : 9600 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : DISABLED I88102 FEB 8, 2024 9:02 AM PORT SETTINGS: COMM BOARD : 2 (RS-232) BAUD RATE : 1200 PARITY : ODD STOP BIT : 1 STOP DATA LENGTH: 7 DATA RS-232 SECURITY CODE : 00 I88103 FEB 8, 2024 9:02 AM PORT SETTINGS: COMM BOARD : 3 (EDIM ) RS-232 SECURITY CODE : 00 I88104 FEB 8, 2024 9:02 AM I88105 FEB 8, 2024 9:02 AM PORT SETTINGS: COMM BOARD : 5 (S-SAT ) BAUD RATE : 9600 PARITY : NONE STOP BIT : 1 STOP DATA LENGTH: 8 DATA RS-232 SECURITY CODE : DISABLED DTR NORMAL STATE: HIGH I88106 FEB 8, 2024 9:02 AM I52000 FEB 8, 2024 9:02 AM RECEIVER AUTO DIAL TYPE & START TIME RCVR LOCATION LABEL DIAL TYPE START TIME 1 WEEKLY SUN 4:19 PM 2 WEEKLY SUN 4:19 PM 3 WEEKLY SUN 4:19 PM 4 WEEKLY SUN 4:19 PM 5 WEEKLY SUN 4:19 PM 6 WEEKLY SUN 4:19 PM 7 WEEKLY SUN 4:19 PM 8 WEEKLY WED 4:20 PM I60100 FEB 8, 2024 9:02 AM TANK CONFIGURATION DEVICE LABEL CONFIGURED 1 UNLEADED NORTH ON 2 SUPREME ON 3 UNLEADED SIPHON ON 4 UNLEADED SOUTH ON 5 DIESEL ON 6 OFF 7 OFF 8 OFF I60200 FEB 8, 2024 9:02 AM TANK PRODUCT LABEL TANK PRODUCT LABEL 1 UNLEADED NORTH 2 SUPREME 3 UNLEADED SIPHON 4 UNLEADED SOUTH 5 DIESEL 6 7 8 I60300 FEB 8, 2024 9:02 AM TANK PRODUCT CODE TANK PRODUCT LABEL 1 UNLEADED NORTH 1 2 SUPREME 2 3 UNLEADED SIPHON 3 4 UNLEADED SOUTH 4 5 DIESEL 5 6 6 7 7 8 8 I60900 FEB 8, 2024 9:02 AM TANK THERMAL COEFFICIENT TANK PRODUCT LABEL 1 UNLEADED NORTH 0.000700 2 SUPREME 0.000700 3 UNLEADED SIPHON 0.000700 4 UNLEADED SOUTH 0.000700 5 DIESEL 0.000700 6 0.000000 7 0.000000 8 0.000000 I60700 FEB 8, 2024 9:02 AM TANK DIAMETER TANK PRODUCT LABEL INCHES 1 UNLEADED NORTH 89.75 2 SUPREME 89.75 3 UNLEADED SIPHON 89.75 4 UNLEADED SOUTH 89.75 5 DIESEL 89.75 6 0.00 7 0.00 8 0.00 I60A00 FEB 8, 2024 9:02 AM TANK FULL VOLUME TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED NORTH 4 PTS 9684 2 SUPREME 4 PTS 9684 3 UNLEADED SIPHON 4 PTS 9684 4 UNLEADED SOUTH 4 PTS 9684 5 DIESEL 4 PTS 9684 6 4 PTS 0 7 4 PTS 0 8 4 PTS 0 I60400 FEB 8, 2024 9:02 AM TANK FULL VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 9684 2 SUPREME 9684 3 UNLEADED SIPHON 9684 4 UNLEADED SOUTH 9684 5 DIESEL 9684 6 0 7 0 8 0 I60500 FEB 8, 2024 9:02 AM TANK 4 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 9684 7891 4918 1900 2 SUPREME 9684 7891 4918 1900 3 UNLEADED SIPHON 9684 7891 4918 1900 4 UNLEADED SOUTH 9684 7891 4918 1900 5 DIESEL 9684 7891 4918 1900 6 0 0 0 0 7 0 0 0 0 8 0 0 0 0 I60600 FEB 8, 2024 9:02 AM TANK 20 POINT VOLUMES TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 9684 0 0 0 0 7891 0 0 0 0 4918 0 0 0 0 1900 0 0 0 0 2 SUPREME 9684 0 0 0 0 7891 0 0 0 0 4918 0 0 0 0 1900 0 0 0 0 3 UNLEADED SIPHON 9684 0 0 0 0 7891 0 0 0 0 4918 0 0 0 0 1900 0 0 0 0 4 UNLEADED SOUTH 9684 0 0 0 0 7891 0 0 0 0 4918 0 0 0 0 1900 0 0 0 0 5 DIESEL 9684 0 0 0 0 7891 0 0 0 0 4918 0 0 0 0 1900 0 0 0 0 6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 7 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I61500 FEB 8, 2024 9:02 AM TANK PRODUCT LABEL METER DATA 1 UNLEADED NORTH NO 2 SUPREME NO 3 UNLEADED SIPHON NO 4 UNLEADED SOUTH NO 5 DIESEL NO 6 NO 7 NO 8 NO I62F00 FEB 8, 2024 9:02 AM MAG PROBE FLOAT SIZE TANK PRODUCT LABEL FLOAT SIZE: 1 UNLEADED NORTH 2.0 IN. 2 SUPREME 4.0 IN. 3 UNLEADED SIPHON 2.0 IN. 4 UNLEADED SOUTH 2.0 IN. 5 DIESEL 4.0 IN. I62700 FEB 8, 2024 9:02 AM TANK HIGH WATER WARNING LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED NORTH 2.0 2 SUPREME 2.0 3 UNLEADED SIPHON 2.0 4 UNLEADED SOUTH 2.0 5 DIESEL 2.0 I64200 FEB 8, 2024 9:02 AM WATER ALARM FILTER TANK PRODUCT LABEL 1 UNLEADED NORTH LOW 2 SUPREME LOW 3 UNLEADED SIPHON LOW 4 UNLEADED SOUTH LOW 5 DIESEL LOW I62400 FEB 8, 2024 9:02 AM TANK HIGH WATER LEVEL LIMIT TANK PRODUCT LABEL INCHES 1 UNLEADED NORTH 3.0 2 SUPREME 3.0 3 UNLEADED SIPHON 3.0 4 UNLEADED SOUTH 3.0 5 DIESEL 3.0 I62800 FEB 8, 2024 9:02 AM TANK MAXIMUM VOLUME LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 9684 2 SUPREME 9684 3 UNLEADED SIPHON 9684 4 UNLEADED SOUTH 9684 5 DIESEL 9684 6 0 7 0 8 0 I62300 FEB 8, 2024 9:02 AM TANK OVERFILL LEVEL LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 9000 2 SUPREME 9000 3 UNLEADED SIPHON 9000 4 UNLEADED SOUTH 9000 5 DIESEL 9000 6 0 7 0 8 0 I62200 FEB 8, 2024 9:02 AM TANK HIGH PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 9500 2 SUPREME 9500 3 UNLEADED SIPHON 9500 4 UNLEADED SOUTH 9500 5 DIESEL 9500 6 0 7 0 8 0 I62900 FEB 8, 2024 9:02 AM TANK DELIVERY REQUIRED LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 500 2 SUPREME 500 3 UNLEADED SIPHON 500 4 UNLEADED SOUTH 500 5 DIESEL 500 6 0 7 0 8 0 I62100 FEB 8, 2024 9:02 AM TANK LOW PRODUCT LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 500 2 SUPREME 500 3 UNLEADED SIPHON 500 4 UNLEADED SOUTH 500 5 DIESEL 500 6 0 7 0 8 0 I62600 FEB 8, 2024 9:02 AM TANK LEAK ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 99 2 SUPREME 99 3 UNLEADED SIPHON 99 4 UNLEADED SOUTH 99 5 DIESEL 99 6 99 7 99 8 99 I62500 FEB 8, 2024 9:02 AM TANK SUDDEN LOSS LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 99 2 SUPREME 99 3 UNLEADED SIPHON 99 4 UNLEADED SOUTH 99 5 DIESEL 99 6 99 7 99 8 99 I60800 FEB 8, 2024 9:02 AM TANK TILT TANK PRODUCT LABEL INCHES 1 UNLEADED NORTH 0.49 2 SUPREME 3.40 3 UNLEADED SIPHON 0.26 4 UNLEADED SOUTH 0.14 5 DIESEL 4.70 6 0.00 7 0.00 8 0.00 I60B00 FEB 8, 2024 9:02 AM STICK HEIGHT OFFSET ENABLE STATUS DISABLED I60C00 FEB 8, 2024 9:02 AM TANK STICK HEIGHT OFFSET TANK PRODUCT LABEL INCHES 1 UNLEADED NORTH 0.00 2 SUPREME 0.00 3 UNLEADED SIPHON 0.00 4 UNLEADED SOUTH 0.00 5 DIESEL 0.00 6 0.00 7 0.00 8 0.00 I61200 FEB 8, 2024 9:02 AM TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS 1 UNLEADED NORTH 3, 4 4 2 SUPREME NONE NONE 3 UNLEADED SIPHON 1, 4 NONE 4 UNLEADED SOUTH 1, 3 1 5 DIESEL NONE NONE 6 NONE NONE 7 NONE NONE 8 NONE NONE I63600 FEB 8, 2024 9:02 AM PERIODIC LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 100 2 SUPREME 100 3 UNLEADED SIPHON 100 4 UNLEADED SOUTH 100 5 DIESEL 100 6 0 7 0 8 0 I62A00 FEB 8, 2024 9:02 AM ANNUAL LEAK TEST MIN VOLUME TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 100 2 SUPREME 100 3 UNLEADED SIPHON 100 4 UNLEADED SOUTH 100 5 DIESEL 100 6 0 7 0 8 0 I62C00 FEB 8, 2024 9:02 AM TANK PERIODIC TEST TYPE TANK PRODUCT LABEL PERIODIC TEST TYPE 1 UNLEADED NORTH STANDARD 2 SUPREME STANDARD 3 UNLEADED SIPHON STANDARD 4 UNLEADED SOUTH STANDARD 5 DIESEL STANDARD 6 STANDARD 7 STANDARD 8 STANDARD I62D00 FEB 8, 2024 9:02 AM TANK LEAK TEST FAIL ALARMS TANK PRODUCT LABEL 1 UNLEADED NORTH GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 2 SUPREME GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 3 UNLEADED SIPHON GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 4 UNLEADED SOUTH GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 5 DIESEL GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 6 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 7 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED 8 GROSS TEST FAIL ALARM DISABLED PERIODIC TEST FAIL ALARM DISABLED ANNUAL TEST FAIL ALARM DISABLED I63100 FEB 8, 2024 9:02 AM TANK LEAK TEST AVERAGING TANK PRODUCT LABEL ANNUAL PERIODIC 1 UNLEADED NORTH OFF OFF 2 SUPREME OFF OFF 3 UNLEADED SIPHON OFF OFF 4 UNLEADED SOUTH OFF OFF 5 DIESEL OFF OFF 6 OFF OFF 7 OFF OFF 8 OFF OFF I63000 FEB 8, 2024 9:02 AM IN-TANK LEAK TEST NOTIFY TANK PRODUCT LABEL TANK TEST NOTIFY: 1 UNLEADED NORTH OFF 2 SUPREME OFF 3 UNLEADED SIPHON OFF 4 UNLEADED SOUTH OFF 5 DIESEL OFF 6 OFF 7 OFF 8 OFF I63200 FEB 8, 2024 9:02 AM TANK TEST SIPHON BREAK TANK PRODUCT LABEL SIPHON BREAK 1 UNLEADED NORTH OFF 2 SUPREME OFF 3 UNLEADED SIPHON OFF 4 UNLEADED SOUTH OFF 5 DIESEL OFF 6 OFF 7 OFF 8 OFF I61000 FEB 8, 2024 9:02 AM TANK DELIVERY DELAY TANK PRODUCT LABEL 1 UNLEADED NORTH 1 2 SUPREME 1 3 UNLEADED SIPHON 1 4 UNLEADED SOUTH 1 5 DIESEL 1 6 1 7 1 8 1 I63A00 FEB 8, 2024 9:02 AM LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD TANK PRODUCT LABEL PUMP THRESHOLD 1 UNLEADED NORTH 10.00% 2 SUPREME 10.00% 3 UNLEADED SIPHON 10.00% 4 UNLEADED SOUTH 10.00% 5 DIESEL 10.00% 6 10.00% 7 10.00% 8 10.00% I61100 FEB 8, 2024 9:02 AM LEAK TEST METHOD - - - - - - - - - - - - TEST ON DATE : ALL TANK FEB 6, 2007 START TIME : DISABLED TEST RATE :0.20 GAL/HR DURATION : 2 HOURS TST EARLY STOP:DISABLED I61300 FEB 8, 2024 9:02 AM CSLD PROBABLITY OF DETECTION I61400 FEB 8, 2024 9:02 AM CSLD CLIMATE FACTOR I61600 FEB 8, 2024 9:02 AM TANK PRODUCT LABEL CAL UPDATE 1 UNLEADED NORTH IMMEDIATE 2 SUPREME IMMEDIATE 3 UNLEADED SIPHON IMMEDIATE 4 UNLEADED SOUTH IMMEDIATE 5 DIESEL IMMEDIATE 6 IMMEDIATE 7 IMMEDIATE 8 IMMEDIATE I61A00 FEB 8, 2024 9:02 AM IN-TANK LEAK TEST EARLY STOP TANK PRODUCT LABEL TST EARLY STOP: 1 UNLEADED NORTH DISABLED 2 SUPREME DISABLED 3 UNLEADED SIPHON DISABLED 4 UNLEADED SOUTH DISABLED 5 DIESEL DISABLED 6 DISABLED 7 DISABLED 8 DISABLED I61B00 FEB 8, 2024 9:02 AM IN-TANK LEAK GROSS TEST AUTO-CONFIRM I61C00 FEB 8, 2024 9:02 AM CSLD REPORT ONLY I62B00 FEB 8, 2024 9:02 AM TANK LAST ANNUAL TEST TANK PRODUCT LABEL DATE 1 UNLEADED NORTH ??? 0, 0 2 SUPREME ??? 0, 0 3 UNLEADED SIPHON ??? 0, 0 4 UNLEADED SOUTH ??? 0, 0 5 DIESEL ??? 0, 0 6 ??? 0, 0 7 ??? 0, 0 8 ??? 0, 0 I63300 FEB 8, 2024 9:03 AM LEAK TEST REPORT FORMAT: NORMAL I63400 FEB 8, 2024 9:03 AM RECONCILIATION WARNING LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 0 2 SUPREME 0 3 UNLEADED SIPHON 0 4 UNLEADED SOUTH 0 5 DIESEL 0 6 0 7 0 8 0 I63500 FEB 8, 2024 9:03 AM RECONCILIATION ALARM LIMIT TANK PRODUCT LABEL GALLONS 1 UNLEADED NORTH 1 2 SUPREME 1 3 UNLEADED SIPHON 1 4 UNLEADED SOUTH 1 5 DIESEL 1 6 1 7 1 8 1 I63900 FEB 8, 2024 9:03 AM ACCU CHART END SHAPE FACTOR TANK PRODUCT LABEL 1 UNLEADED NORTH END FACTOR: NONE 2 SUPREME END FACTOR: NONE 3 UNLEADED SIPHON END FACTOR: NONE 4 UNLEADED SOUTH END FACTOR: NONE 5 DIESEL END FACTOR: NONE 6 END FACTOR: NONE 7 END FACTOR: NONE 8 END FACTOR: NONE I78000 FEB 8, 2024 9:03 AM I77700 FEB 8, 2024 9:03 AM I77800 FEB 8, 2024 9:03 AM I78C00 FEB 8, 2024 9:03 AM I78300 FEB 8, 2024 9:03 AM I78F00 FEB 8, 2024 9:03 AM I78700 FEB 8, 2024 9:03 AM I70200 FEB 8, 2024 9:03 AM LIQUID LABEL DEVICE LABEL 1 UNLEADED NORTH STP 2 SUPREME STP 3 UNLEADED SIPHON STP 4 UNLEADED SOUTH STP 5 DIESEL STP 6 UNL NORTH FILL 7 SUPREME FILL 8 UNL SIPHON FILL 9 UNL SOUTH FILL 10 DIESEL FILL 11 UNL ANNULAR 12 SUPREME ANNULAR 13 UNL SIPHON ANNULAR 14 UNL SOUTH ANNULAR 15 DIESEL ANNULAR 16 DIESEL FILL I70300 FEB 8, 2024 9:03 AM LIQUID TYPE SENSOR LOCATION TYPE 1 UNLEADED NORTH STP TRI-STATE (SINGLE FLOAT) 2 SUPREME STP TRI-STATE (SINGLE FLOAT) 3 UNLEADED SIPHON STP TRI-STATE (SINGLE FLOAT) 4 UNLEADED SOUTH STP TRI-STATE (SINGLE FLOAT) 5 DIESEL STP TRI-STATE (SINGLE FLOAT) 6 UNL NORTH FILL TRI-STATE (SINGLE FLOAT) 7 SUPREME FILL TRI-STATE (SINGLE FLOAT) 8 UNL SIPHON FILL TRI-STATE (SINGLE FLOAT) 9 UNL SOUTH FILL TRI-STATE (SINGLE FLOAT) 10 DIESEL FILL TRI-STATE (SINGLE FLOAT) 11 UNL ANNULAR TRI-STATE (SINGLE FLOAT) 12 SUPREME ANNULAR TRI-STATE (SINGLE FLOAT) 13 UNL SIPHON ANNULAR TRI-STATE (SINGLE FLOAT) 14 UNL SOUTH ANNULAR TRI-STATE (SINGLE FLOAT) 15 DIESEL ANNULAR TRI-STATE (SINGLE FLOAT) 16 DIESEL FILL NORMALLY CLOSED I70400 FEB 8, 2024 9:03 AM LIQUID CATEGORY SENSOR LOCATION CATEGORY 1 UNLEADED NORTH STP OTHER SENSORS 2 SUPREME STP OTHER SENSORS 3 UNLEADED SIPHON STP OTHER SENSORS 4 UNLEADED SOUTH STP OTHER SENSORS 5 DIESEL STP STP SUMP 6 UNL NORTH FILL OTHER SENSORS 7 SUPREME FILL OTHER SENSORS 8 UNL SIPHON FILL OTHER SENSORS 9 UNL SOUTH FILL OTHER SENSORS 10 DIESEL FILL OTHER SENSORS 11 UNL ANNULAR ANNULAR SPACE 12 SUPREME ANNULAR ANNULAR SPACE 13 UNL SIPHON ANNULAR ANNULAR SPACE 14 UNL SOUTH ANNULAR ANNULAR SPACE 15 DIESEL ANNULAR ANNULAR SPACE 16 DIESEL FILL OTHER SENSORS I74200 FEB 8, 2024 9:03 AM I74300 FEB 8, 2024 9:03 AM I74400 FEB 8, 2024 9:03 AM I74700 FEB 8, 2024 9:03 AM I74800 FEB 8, 2024 9:03 AM I74900 FEB 8, 2024 9:03 AM I7BC00 FEB 8, 2024 9:03 AM I80200 FEB 8, 2024 9:03 AM I80300 FEB 8, 2024 9:03 AM I80400 FEB 8, 2024 9:03 AM I80700 FEB 8, 2024 9:03 AM RELAY LABEL DEVICE LABEL 1 SUPREME 2 UNLEADED NORTH 3 UNLEADED SOUTH 4 DIESEL I80900 FEB 8, 2024 9:03 AM RELAY ORIENTATION RELAY DESIGNATION ORIENTATION 1 SUPREME NORMALLY CLOSED 2 UNLEADED NORTH NORMALLY OPEN 3 UNLEADED SOUTH NORMALLY OPEN 4 DIESEL NORMALLY CLOSED I80B00 FEB 8, 2024 9:03 AM RELAY TANK ASSIGNMENT RELAY DESIGNATION TANK 1 SUPREME 2 2 UNLEADED NORTH 1 3 UNLEADED SOUTH 4 4 DIESEL 5 I80A00 FEB 8, 2024 9:03 AM RELAY TYPE RELAY DESIGNATION TYPE 1 SUPREME STANDARD 2 UNLEADED NORTH PUMP CONTROL OUTPUT 3 UNLEADED SOUTH PUMP CONTROL OUTPUT 4 DIESEL STANDARD I80C00 FEB 8, 2024 9:03 AM I80800 FEB 8, 2024 9:03 AM RELAY SETUP REPORT R 1:SUPREME TYPE: STANDARD NORMALLY CLOSED TANK #: 2 LIQUID SENSOR ALMS L 2:FUEL ALARM L 2:SENSOR OUT ALARM L 2:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 2:UNLEADED NORTH TYPE: PUMP CONTROL OUTPUT TANK #: 1 LIQUID SENSOR ALMS L 1:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 1:SENSOR OUT ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 1:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS ALL:GROSS COLLECT FAIL ALL:DEGRD COLLECT FAIL ALL:FLOW COLLECT FAIL R 3:UNLEADED SOUTH TYPE: PUMP CONTROL OUTPUT TANK #: 4 LIQUID SENSOR ALMS L 1:FUEL ALARM L 3:FUEL ALARM L 4:FUEL ALARM L 3:SENSOR OUT ALARM L 4:SENSOR OUT ALARM L 1:SHORT ALARM L 3:SHORT ALARM L 4:SHORT ALARM ISD SITE ALARMS ISD GROSS PRES FAIL ISD DEGRD PRES FAIL ISD VAPOR LEAK FAIL ISD VP PRES FAIL ISD VP STATUS FAIL ISD HOSE ALARMS h13:GROSS COLLECT FAIL h14:GROSS COLLECT FAIL h15:GROSS COLLECT FAIL h16:GROSS COLLECT FAIL h17:GROSS COLLECT FAIL h18:GROSS COLLECT FAIL h19:GROSS COLLECT FAIL h20:GROSS COLLECT FAIL h21:GROSS COLLECT FAIL h22:GROSS COLLECT FAIL h23:GROSS COLLECT FAIL h24:GROSS COLLECT FAIL h25:GROSS COLLECT FAIL h26:GROSS COLLECT FAIL h27:GROSS COLLECT FAIL h28:GROSS COLLECT FAIL h29:GROSS COLLECT FAIL h30:GROSS COLLECT FAIL h31:GROSS COLLECT FAIL h32:GROSS COLLECT FAIL h33:GROSS COLLECT FAIL h34:GROSS COLLECT FAIL h35:GROSS COLLECT FAIL h36:GROSS COLLECT FAIL h37:GROSS COLLECT FAIL h38:GROSS COLLECT FAIL h39:GROSS COLLECT FAIL h40:GROSS COLLECT FAIL h41:GROSS COLLECT FAIL h42:GROSS COLLECT FAIL h43:GROSS COLLECT FAIL h44:GROSS COLLECT FAIL h45:GROSS COLLECT FAIL h46:GROSS COLLECT FAIL h47:GROSS COLLECT FAIL h48:GROSS COLLECT FAIL h49:GROSS COLLECT FAIL h50:GROSS COLLECT FAIL h51:GROSS COLLECT FAIL h52:GROSS COLLECT FAIL h53:GROSS COLLECT FAIL h54:GROSS COLLECT FAIL h55:GROSS COLLECT FAIL h56:GROSS COLLECT FAIL h57:GROSS COLLECT FAIL h58:GROSS COLLECT FAIL h59:GROSS COLLECT FAIL h60:GROSS COLLECT FAIL h61:GROSS COLLECT FAIL h62:GROSS COLLECT FAIL h63:GROSS COLLECT FAIL h64:GROSS COLLECT FAIL h65:GROSS COLLECT FAIL h66:GROSS COLLECT FAIL h67:GROSS COLLECT FAIL h68:GROSS COLLECT FAIL h69:GROSS COLLECT FAIL h70:GROSS COLLECT FAIL h71:GROSS COLLECT FAIL h72:GROSS COLLECT FAIL h73:GROSS COLLECT FAIL h74:GROSS COLLECT FAIL h75:GROSS COLLECT FAIL h76:GROSS COLLECT FAIL h77:GROSS COLLECT FAIL h78:GROSS COLLECT FAIL h79:GROSS COLLECT FAIL h80:GROSS COLLECT FAIL h81:GROSS COLLECT FAIL h82:GROSS COLLECT FAIL h83:GROSS COLLECT FAIL h84:GROSS COLLECT FAIL h85:GROSS COLLECT FAIL h86:GROSS COLLECT FAIL h87:GROSS COLLECT FAIL h88:GROSS COLLECT FAIL h89:GROSS COLLECT FAIL h90:GROSS COLLECT FAIL h91:GROSS COLLECT FAIL h92:GROSS COLLECT FAIL h93:GROSS COLLECT FAIL h94:GROSS COLLECT FAIL h95:GROSS COLLECT FAIL h96:GROSS COLLECT FAIL h97:GROSS COLLECT FAIL h98:GROSS COLLECT FAIL h99:GROSS COLLECT FAIL h13:DEGRD COLLECT FAIL h14:DEGRD COLLECT FAIL h15:DEGRD COLLECT FAIL h16:DEGRD COLLECT FAIL h17:DEGRD COLLECT FAIL h18:DEGRD COLLECT FAIL h19:DEGRD COLLECT FAIL h20:DEGRD COLLECT FAIL h21:DEGRD COLLECT FAIL h22:DEGRD COLLECT FAIL h23:DEGRD COLLECT FAIL h24:DEGRD COLLECT FAIL h25:DEGRD COLLECT FAIL h26:DEGRD COLLECT FAIL h27:DEGRD COLLECT FAIL h28:DEGRD COLLECT FAIL h29:DEGRD COLLECT FAIL h30:DEGRD COLLECT FAIL h31:DEGRD COLLECT FAIL h32:DEGRD COLLECT FAIL h33:DEGRD COLLECT FAIL h34:DEGRD COLLECT FAIL h35:DEGRD COLLECT FAIL h36:DEGRD COLLECT FAIL h37:DEGRD COLLECT FAIL h38:DEGRD COLLECT FAIL h39:DEGRD COLLECT FAIL h40:DEGRD COLLECT FAIL h41:DEGRD COLLECT FAIL h42:DEGRD COLLECT FAIL h43:DEGRD COLLECT FAIL h44:DEGRD COLLECT FAIL h45:DEGRD COLLECT FAIL h46:DEGRD COLLECT FAIL h47:DEGRD COLLECT FAIL h48:DEGRD COLLECT FAIL h49:DEGRD COLLECT FAIL h50:DEGRD COLLECT FAIL h51:DEGRD COLLECT FAIL h52:DEGRD COLLECT FAIL h53:DEGRD COLLECT FAIL h54:DEGRD COLLECT FAIL h55:DEGRD COLLECT FAIL h56:DEGRD COLLECT FAIL h57:DEGRD COLLECT FAIL h58:DEGRD COLLECT FAIL h59:DEGRD COLLECT FAIL h60:DEGRD COLLECT FAIL h61:DEGRD COLLECT FAIL h62:DEGRD COLLECT FAIL h63:DEGRD COLLECT FAIL h64:DEGRD COLLECT FAIL h65:DEGRD COLLECT FAIL h66:DEGRD COLLECT FAIL h67:DEGRD COLLECT FAIL h68:DEGRD COLLECT FAIL h69:DEGRD COLLECT FAIL h70:DEGRD COLLECT FAIL h71:DEGRD COLLECT FAIL h72:DEGRD COLLECT FAIL h73:DEGRD COLLECT FAIL h74:DEGRD COLLECT FAIL h75:DEGRD COLLECT FAIL h76:DEGRD COLLECT FAIL h77:DEGRD COLLECT FAIL h78:DEGRD COLLECT FAIL h79:DEGRD COLLECT FAIL h80:DEGRD COLLECT FAIL h81:DEGRD COLLECT FAIL h82:DEGRD COLLECT FAIL h83:DEGRD COLLECT FAIL h84:DEGRD COLLECT FAIL h85:DEGRD COLLECT FAIL h86:DEGRD COLLECT FAIL h87:DEGRD COLLECT FAIL h88:DEGRD COLLECT FAIL h89:DEGRD COLLECT FAIL h90:DEGRD COLLECT FAIL h91:DEGRD COLLECT FAIL h92:DEGRD COLLECT FAIL h93:DEGRD COLLECT FAIL h94:DEGRD COLLECT FAIL h95:DEGRD COLLECT FAIL h96:DEGRD COLLECT FAIL h97:DEGRD COLLECT FAIL h98:DEGRD COLLECT FAIL h99:DEGRD COLLECT FAIL h13:FLOW COLLECT FAIL h14:FLOW COLLECT FAIL h15:FLOW COLLECT FAIL h16:FLOW COLLECT FAIL h17:FLOW COLLECT FAIL h18:FLOW COLLECT FAIL h19:FLOW COLLECT FAIL h20:FLOW COLLECT FAIL h21:FLOW COLLECT FAIL h22:FLOW COLLECT FAIL h23:FLOW COLLECT FAIL h24:FLOW COLLECT FAIL h25:FLOW COLLECT FAIL h26:FLOW COLLECT FAIL h27:FLOW COLLECT FAIL h28:FLOW COLLECT FAIL h29:FLOW COLLECT FAIL h30:FLOW COLLECT FAIL h31:FLOW COLLECT FAIL h32:FLOW COLLECT FAIL h33:FLOW COLLECT FAIL h34:FLOW COLLECT FAIL h35:FLOW COLLECT FAIL h36:FLOW COLLECT FAIL h37:FLOW COLLECT FAIL h38:FLOW COLLECT FAIL h39:FLOW COLLECT FAIL h40:FLOW COLLECT FAIL h41:FLOW COLLECT FAIL h42:FLOW COLLECT FAIL h43:FLOW COLLECT FAIL h44:FLOW COLLECT FAIL h45:FLOW COLLECT FAIL h46:FLOW COLLECT FAIL h47:FLOW COLLECT FAIL h48:FLOW COLLECT FAIL h49:FLOW COLLECT FAIL h50:FLOW COLLECT FAIL h51:FLOW COLLECT FAIL h52:FLOW COLLECT FAIL h53:FLOW COLLECT FAIL h54:FLOW COLLECT FAIL h55:FLOW COLLECT FAIL h56:FLOW COLLECT FAIL h57:FLOW COLLECT FAIL h58:FLOW COLLECT FAIL h59:FLOW COLLECT FAIL h60:FLOW COLLECT FAIL h61:FLOW COLLECT FAIL h62:FLOW COLLECT FAIL h63:FLOW COLLECT FAIL h64:FLOW COLLECT FAIL h65:FLOW COLLECT FAIL h66:FLOW COLLECT FAIL h67:FLOW COLLECT FAIL h68:FLOW COLLECT FAIL h69:FLOW COLLECT FAIL h70:FLOW COLLECT FAIL h71:FLOW COLLECT FAIL h72:FLOW COLLECT FAIL h73:FLOW COLLECT FAIL h74:FLOW COLLECT FAIL h75:FLOW COLLECT FAIL h76:FLOW COLLECT FAIL h77:FLOW COLLECT FAIL h78:FLOW COLLECT FAIL h79:FLOW COLLECT FAIL h80:FLOW COLLECT FAIL h81:FLOW COLLECT FAIL h82:FLOW COLLECT FAIL h83:FLOW COLLECT FAIL h84:FLOW COLLECT FAIL h85:FLOW COLLECT FAIL h86:FLOW COLLECT FAIL h87:FLOW COLLECT FAIL h88:FLOW COLLECT FAIL h89:FLOW COLLECT FAIL h90:FLOW COLLECT FAIL h91:FLOW COLLECT FAIL h92:FLOW COLLECT FAIL h93:FLOW COLLECT FAIL h94:FLOW COLLECT FAIL h95:FLOW COLLECT FAIL h96:FLOW COLLECT FAIL h97:FLOW COLLECT FAIL h98:FLOW COLLECT FAIL h99:FLOW COLLECT FAIL R 4:DIESEL TYPE: STANDARD NORMALLY CLOSED TANK #: 5 LIQUID SENSOR ALMS L 5:FUEL ALARM L 5:SENSOR OUT ALARM L 5:SHORT ALARM I79000 FEB 8, 2024 9:04 AM EDIM:1 VR:349867-001-C TD:16.05.27.07.44 I79100 FEB 8, 2024 9:04 AM I72300 FEB 8, 2024 9:04 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 SMARTSENSOR ASSIGNMENT DEVICE LABEL CATEGORY 01 FM 1-2 AIR FLOW METER 02 FM 3-4 AIR FLOW METER 03 FM 5-6 AIR FLOW METER 04 FM 7-8 AIR FLOW METER 05 FM 9-10 AIR FLOW METER 06 FM 11-12 AIR FLOW METER 07 PS 7-8 VAPOR PRESSURE 08 UNKNOWN 09 UNKNOWN 10 UNKNOWN 11 UNKNOWN 12 UNKNOWN 13 UNKNOWN 14 UNKNOWN 15 UNKNOWN 16 UNKNOWN 17 UNKNOWN 18 UNKNOWN 19 UNKNOWN 20 UNKNOWN 21 UNKNOWN 22 UNKNOWN 23 UNKNOWN 24 UNKNOWN 25 UNKNOWN 26 UNKNOWN 27 UNKNOWN 28 UNKNOWN 29 UNKNOWN 30 UNKNOWN 31 UNKNOWN 32 UNKNOWN 33 UNKNOWN 34 UNKNOWN 35 UNKNOWN 36 UNKNOWN 37 UNKNOWN 38 UNKNOWN 39 UNKNOWN 40 UNKNOWN IV4E00 FEB 8, 2024 9:04 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 EVR/ISD SETUP TYPE: BALANCE IV4F00 FEB 8, 2024 9:04 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 NOZZLE A/L RANGE A/L RATIO: 0.95 - 1.15 IV4000 FEB 8, 2024 9:04 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 VAPOR PROCESSOR TYPE NONE IV4700 FEB 8, 2024 9:04 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 ASSESSMENT TIME START TIME: 8:00 AM TIME DELAY MINUTES: 1 IV5200 FEB 8, 2024 9:04 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 ACCEPT HIGH ORVR: YES IV4A00 FEB 8, 2024 9:04 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 ISD HOSE TABLE HOSE FP FP AFM REL HOSE ID ID LABEL ID ID LABEL 01 01 01 01 UU BLEND3 02 02 02 01 UU BLEND3 03 03 03 02 UU BLEND3 04 04 04 02 UU BLEND3 05 05 05 03 UU BLEND3 06 06 06 03 UU BLEND3 07 07 07 04 UU BLEND3 08 08 08 04 UU BLEND3 09 09 09 05 UU BLEND3 10 16 10 05 UU BLEND3 11 17 11 06 UU BLEND3 12 18 12 06 UU BLEND3 IV4B00 FEB 8, 2024 9:04 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 PRODUCT/HOSE MAP TABLE FP AFID M1/H1 M2/H2 M3/H3 M4/H4 01 01 02/01 09/01 01/01 xx/xx 02 01 01/02 02/02 09/02 xx/xx 03 02 02/03 09/03 01/03 xx/xx 04 02 02/04 09/04 01/04 xx/xx 05 03 02/05 09/05 01/05 xx/xx 06 03 02/06 09/06 01/06 xx/xx 07 04 02/07 09/07 01/07 xx/xx 08 04 02/08 09/08 01/08 xx/xx 09 05 09/09 02/09 01/09 xx/xx 16 05 02/10 09/10 01/10 xx/xx 17 06 01/11 02/11 09/11 xx/xx 18 06 02/12 09/12 01/12 xx/xx IV4900 FEB 8, 2024 9:04 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 LABEL TABLE ID LABEL 01 UNASSIGNED 02 BLEND3 03 REGULAR 04 MID GRADE 05 PREMIUM 06 GOLD 07 BRONZE 08 SILVER 09 BLEND2 10 BLEND4 IV1000 FEB 8, 2024 9:04 AM ISD VERSION: 01.05 Samco California Pre Alarm History Responses Received: I10200 FEB 8, 2024 9:05 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 507996 511214 2 4 PROBE / G.T. 163935 164139 3 4 PROBE / G.T. 163913 164160 4 INTERSTITIAL BD 201668 201940 5 INTERSTITIAL BD 201495 201875 6 UNUSED 9743067 9862448 7 UNUSED 9729335 9825860 8 UNUSED 9745647 9834551 9 RELAY BOARD 15007 14994 10 STP SENSE BOARD 33240 33265 11 UNUSED 9729983 9832908 12 UNUSED 9729067 9816489 13 UNUSED 9734726 9840800 14 UNUSED 9732313 9824155 15 UNUSED 9737618 9829772 16 UNUSED 9718810 9823151 COMM 1 RS232 SERIAL BD 14986 15055 COMM 2 RS232 SERIAL BD 15091 15076 COMM 3 ELEC DISP INT. 101121 101358 COMM 4 UNUSED 9732542 9824893 COMM 5 SERIAL SAT BD 479659 481019 COMM 6 UNUSED 9730960 9823336 I90200 FEB 8, 2024 9:05 AM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 FEB 8, 2024 9:05 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 1-02-24 8:16AM L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 1-01-24 11:02AM L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 12-26-23 9:16AM L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 12-26-23 9:15AM L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 12-26-23 9:15AM L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 12-26-23 9:15AM L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 12-26-23 9:13AM L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 12-26-23 9:12AM E 1 OTHER COMMUNICATION ALARM CLEAR 11-29-23 4:19PM E 1 OTHER COMMUNICATION ALARM ALARM 11-29-23 4:18PM L12 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-14-23 9:54AM L12 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-14-23 9:51AM L12 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-14-23 9:51AM L15 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 4:20PM L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 3:48PM L12 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-13-23 3:48PM L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM ALARM 11-13-23 3:48PM L12 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-13-23 3:48PM L15 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM ALARM 11-13-23 3:17PM L 2 OTHER SUPREME STP FUEL ALARM CLEAR 11-13-23 2:07PM L 2 OTHER SUPREME STP FUEL ALARM ALARM 11-13-23 2:07PM L14 ANNULAR UNL SOUTH ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 2:02PM L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 11-13-23 12:35PM L 7 OTHER SUPREME FILL FUEL ALARM CLEAR 11-13-23 12:34PM L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 11-13-23 12:33PM L14 ANNULAR UNL SOUTH ANNULAR SENSOR OUT ALARM ALARM 11-13-23 12:32PM L 7 OTHER SUPREME FILL FUEL ALARM ALARM 11-13-23 12:32PM L13 ANNULAR UNL SIPHON ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 12:29PM L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 11:25AM L12 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-13-23 11:25AM L13 ANNULAR UNL SIPHON ANNULAR SENSOR OUT ALARM ALARM 11-13-23 11:10AM L11 ANNULAR UNL ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 10:49AM L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM ALARM 11-13-23 9:37AM L12 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-13-23 9:37AM L12 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-13-23 9:36AM L11 ANNULAR UNL ANNULAR SENSOR OUT ALARM ALARM 11-13-23 9:03AM L 2 OTHER SUPREME STP FUEL ALARM CLEAR 11-13-23 8:24AM L 2 OTHER SUPREME STP FUEL ALARM ALARM 11-13-23 8:24AM OTHER ISD GROSS PRES FAIL CLEAR 10-30-23 8:20AM OTHER ISD GROSS PRES FAIL ALARM 10-30-23 8:02AM D 8 OTHER AUTODIAL FAILURE CLEAR 10-16-23 8:40AM D 8 OTHER AUTODIAL FAILURE ALARM 10-16-23 8:28AM D 8 OTHER AUTODIAL FAILURE CLEAR 10-16-23 8:28AM T 1 TANK UNLEADED NORTH OVERFILL ALARM CLEAR 10-16-23 3:18AM D 8 OTHER AUTODIAL FAILURE ALARM 10-16-23 3:14AM D 8 OTHER AUTODIAL FAILURE CLEAR 10-16-23 3:14AM T 1 TANK UNLEADED NORTH OVERFILL ALARM ALARM 10-16-23 3:13AM T 1 TANK UNLEADED NORTH OVERFILL ALARM CLEAR 10-16-23 3:08AM T 1 TANK UNLEADED NORTH OVERFILL ALARM ALARM 10-16-23 2:58AM T 1 TANK UNLEADED NORTH OVERFILL ALARM CLEAR 10-16-23 2:57AM I11200 FEB 8, 2024 9:05 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PAPER OUT ALARM 2-08-24 9:04AM SYSTEM PRINTER ERROR ALARM 2-08-24 9:04AM SYSTEM PRINTER ERROR CLEAR 12-27-23 9:14AM SYSTEM PAPER OUT CLEAR 12-27-23 9:14AM SYSTEM PAPER OUT ALARM 12-27-23 9:14AM SYSTEM PRINTER ERROR ALARM 12-27-23 9:14AM SYSTEM PRINTER ERROR CLEAR 12-27-23 9:14AM SYSTEM PAPER OUT CLEAR 12-27-23 9:14AM SYSTEM PAPER OUT ALARM 12-27-23 9:12AM SYSTEM PRINTER ERROR ALARM 12-27-23 9:12AM OTHER ISD DEGRD PRES WARN CLEAR 12-08-23 7:52AM OTHER ISD DEGRD PRES WARN ALARM 12-03-23 8:04AM OTHER ISD GROSS PRES WARN CLEAR 11-07-23 1:07PM SYSTEM PRINTER ERROR CLEAR 11-06-23 8:08AM SYSTEM PAPER OUT CLEAR 11-06-23 8:08AM SYSTEM PRINTER ERROR ALARM 11-06-23 8:07AM SYSTEM PAPER OUT ALARM 11-06-23 8:07AM SYSTEM PRINTER ERROR CLEAR 11-06-23 8:07AM SYSTEM PAPER OUT CLEAR 11-06-23 8:07AM SYSTEM PRINTER ERROR ALARM 11-06-23 8:07AM SYSTEM PAPER OUT ALARM 11-06-23 8:07AM OTHER ISD GROSS PRES WARN ALARM 11-06-23 8:03AM OTHER ISD GROSS PRES WARN CLEAR 10-30-23 8:00AM OTHER ISD GROSS PRES WARN ALARM 10-23-23 8:03AM OTHER ISD GROSS PRES WARN CLEAR 10-16-23 8:35AM OTHER ISD GROSS PRES WARN ALARM 10-16-23 8:03AM T 3 TANK UNLEADED SIPHON HIGH PRODUCT ALARM CLEAR 10-10-23 8:59AM T 3 TANK UNLEADED SIPHON HIGH PRODUCT ALARM ALARM 10-09-23 5:31PM OTHER ISD DEGRD PRES WARN CLEAR 10-09-23 8:34AM OTHER ISD GROSS PRES WARN CLEAR 10-09-23 8:34AM OTHER ISD DEGRD PRES WARN ALARM 10-07-23 8:03AM OTHER ISD GROSS PRES WARN ALARM 10-04-23 8:04AM SYSTEM PRINTER ERROR CLEAR 9-18-23 9:46AM SYSTEM PAPER OUT CLEAR 9-18-23 9:46AM SYSTEM PAPER OUT ALARM 9-18-23 9:46AM SYSTEM PRINTER ERROR ALARM 9-18-23 9:46AM SYSTEM PRINTER ERROR CLEAR 9-18-23 9:46AM SYSTEM PAPER OUT CLEAR 9-18-23 9:46AM SYSTEM PRINTER ERROR ALARM 9-18-23 9:42AM SYSTEM PAPER OUT ALARM 9-18-23 9:42AM SYSTEM PRINTER ERROR CLEAR 9-07-23 10:12PM SYSTEM PAPER OUT CLEAR 9-07-23 10:12PM SYSTEM PRINTER ERROR ALARM 9-07-23 10:11PM SYSTEM PAPER OUT ALARM 9-07-23 10:11PM SYSTEM PRINTER ERROR CLEAR 8-30-23 6:27PM SYSTEM PAPER OUT CLEAR 8-30-23 6:27PM SYSTEM PRINTER ERROR ALARM 8-30-23 6:26PM SYSTEM PAPER OUT ALARM 8-30-23 6:26PM SYSTEM PRINTER ERROR CLEAR 8-30-23 6:26PM SYSTEM PAPER OUT CLEAR 8-30-23 6:26PM I20600 FEB 8, 2024 9:05 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 TANK ALARM HISTORY TANK 1 UNLEADED NORTH OVERFILL ALARM OCT 16, 2023 3:13 AM OCT 16, 2023 2:58 AM OCT 16, 2023 2:54 AM SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM HIGH PRODUCT ALARM APR 12, 2023 8:54 PM INVALID FUEL LEVEL MAY 13, 2023 3:06 PM DEC 20, 2021 12:31 PM PROBE OUT OCT 7, 2020 8:11 AM LOW TEMP WARNING OCT 7, 2020 3:49 PM TANK 2 SUPREME HIGH WATER ALARM JUL 27, 2023 3:37 PM INVALID FUEL LEVEL JUL 28, 2023 1:23 PM JUL 27, 2023 4:51 PM MAY 13, 2023 1:28 PM PROBE OUT OCT 7, 2020 8:11 AM HIGH WATER WARNING JUL 27, 2023 3:37 PM TANK 3 UNLEADED SIPHON OVERFILL ALARM OCT 9, 2023 5:30 PM APR 12, 2023 8:58 PM SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM HIGH PRODUCT ALARM OCT 9, 2023 5:31 PM PROBE OUT OCT 7, 2020 8:13 AM TANK 4 UNLEADED SOUTH SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM INVALID FUEL LEVEL MAY 13, 2023 3:19 PM JAN 9, 2022 1:55 PM NOV 21, 2020 11:42 AM PROBE OUT OCT 7, 2020 8:14 AM TANK 5 DIESEL INVALID FUEL LEVEL JUL 10, 2023 3:26 PM TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 FEB 8, 2024 9:05 AM I30200 FEB 8, 2024 9:05 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNLEADED NORTH STP APR 25, 2023 8:58 AM SETUP DATA WARNING APR 25, 2023 7:38 AM SETUP DATA WARNING FEB 21, 2023 9:44 AM SENSOR OUT ALARM 2 SUPREME STP NOV 13, 2023 2:07 PM FUEL ALARM NOV 13, 2023 8:24 AM FUEL ALARM APR 25, 2023 8:58 AM SETUP DATA WARNING 3 UNLEADED SIPHON STP APR 25, 2023 8:58 AM SETUP DATA WARNING APR 25, 2023 8:47 AM SETUP DATA WARNING APR 25, 2023 7:38 AM SETUP DATA WARNING 4 UNLEADED SOUTH STP APR 25, 2023 8:58 AM SETUP DATA WARNING APR 25, 2023 8:47 AM SETUP DATA WARNING APR 25, 2023 7:38 AM SETUP DATA WARNING 5 DIESEL STP APR 25, 2023 8:58 AM SETUP DATA WARNING APR 25, 2023 7:38 AM SETUP DATA WARNING FEB 21, 2023 9:42 AM SENSOR OUT ALARM 6 UNL NORTH FILL APR 25, 2023 8:58 AM SETUP DATA WARNING APR 25, 2023 7:38 AM SETUP DATA WARNING FEB 21, 2023 9:42 AM SENSOR OUT ALARM 7 SUPREME FILL NOV 13, 2023 12:32 PM FUEL ALARM APR 25, 2023 8:58 AM SETUP DATA WARNING APR 25, 2023 7:38 AM SETUP DATA WARNING 8 UNL SIPHON FILL JAN 1, 2024 11:02 AM FUEL ALARM DEC 26, 2023 9:15 AM FUEL ALARM DEC 26, 2023 9:15 AM FUEL ALARM 9 UNL SOUTH FILL FEB 21, 2023 9:27 AM SENSOR OUT ALARM FEB 21, 2023 9:10 AM FUEL ALARM FEB 23, 2022 9:30 AM SENSOR OUT ALARM 10 DIESEL FILL FEB 21, 2023 9:27 AM SENSOR OUT ALARM FEB 21, 2023 9:09 AM FUEL ALARM FEB 23, 2022 9:30 AM SENSOR OUT ALARM 11 UNL ANNULAR NOV 13, 2023 9:03 AM SENSOR OUT ALARM FEB 21, 2023 9:47 AM FUEL ALARM FEB 21, 2023 9:27 AM SENSOR OUT ALARM 12 SUPREME ANNULAR NOV 14, 2023 9:51 AM FUEL ALARM NOV 13, 2023 3:48 PM FUEL ALARM NOV 13, 2023 3:48 PM SENSOR OUT ALARM 13 UNL SIPHON ANNULAR NOV 13, 2023 11:10 AM SENSOR OUT ALARM FEB 21, 2023 9:35 AM FUEL ALARM FEB 21, 2023 9:27 AM SENSOR OUT ALARM 14 UNL SOUTH ANNULAR NOV 13, 2023 12:32 PM SENSOR OUT ALARM FEB 21, 2023 9:29 AM FUEL ALARM FEB 21, 2023 9:27 AM SENSOR OUT ALARM 15 DIESEL ANNULAR NOV 13, 2023 3:17 PM SENSOR OUT ALARM FEB 21, 2023 9:29 AM FUEL ALARM FEB 21, 2023 9:27 AM SENSOR OUT ALARM I31600 FEB 8, 2024 9:05 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 FM 1-2 2 FM 3-4 3 FM 5-6 4 FM 7-8 5 FM 9-10 OCT 2, 2020 8:40 AM COMMUNICATION ALARM SEP 16, 2020 3:58 PM COMMUNICATION ALARM SEP 10, 2020 6:38 PM COMMUNICATION ALARM 6 FM 11-12 7 PS 7-8 I40200 FEB 8, 2024 9:05 AM I40300 FEB 8, 2024 9:05 AM I34200 FEB 8, 2024 9:05 AM I34700 FEB 8, 2024 9:05 AM IV0100 FEB 8, 2024 9:05 AM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-12-07 08:04:19 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.34 23-12-06 08:04:25 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37 23-12-05 08:04:27 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37 23-12-04 08:04:24 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.36 23-12-03 08:04:29 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37 23-11-07 08:04:07 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.06 23-11-06 08:03:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07 23-10-29 08:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16 23-10-28 08:02:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16 23-10-27 08:02:46 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.31 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-10-30 08:02:37 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.13 22-12-05 08:03:18 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 126.81 22-11-22 08:02:53 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 153.95 22-11-07 08:03:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 67.28 22-10-04 08:04:39 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 87.23 22-09-21 08:03:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 86.74 22-08-02 08:02:51 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 115.69 22-07-20 08:03:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.98 22-07-07 08:04:03 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.15 21-12-06 08:03:24 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.16 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-12-08 07:52:01 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-07 13:07:50 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-10-30 08:20:08 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-10-30 08:18:06 PUMPS MANUALLY RE-ENABLED 23-10-30 08:02:37 CONTAINMENT GROSS DISABLED DISPENSERS 23-10-29 01:00:00 TIME CHANGE DETECTED AT: 23-10-29 02:00:13 23-10-16 08:35:30 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-10-09 08:34:10 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-09-30 08:03:16 READINESS ISD:PP EVR:PP ISD & EVR READY 23-09-30 04:59:51 READINESS ISD:PP EVR:NN EVR READINESS PENDING Post Alarm History Responses Received: I10200 FEB 8, 2024 1:14 PM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 SYSTEM CONFIGURATION SLOT BOARD TYPE POWER ON RESET CURRENT 1 7SMARTSENSOR BD 507996 511214 2 4 PROBE / G.T. 163935 164139 3 4 PROBE / G.T. 163913 164160 4 INTERSTITIAL BD 201668 201940 5 INTERSTITIAL BD 201495 201875 6 UNUSED 9743067 9862448 7 UNUSED 9729335 9825860 8 UNUSED 9745647 9834551 9 RELAY BOARD 15007 14994 10 STP SENSE BOARD 33240 33265 11 UNUSED 9729983 9832908 12 UNUSED 9729067 9816489 13 UNUSED 9734726 9840800 14 UNUSED 9732313 9824155 15 UNUSED 9737618 9829772 16 UNUSED 9718810 9823151 COMM 1 RS232 SERIAL BD 14986 15055 COMM 2 RS232 SERIAL BD 15091 15076 COMM 3 ELEC DISP INT. 101121 101358 COMM 4 UNUSED 9732542 9824893 COMM 5 SERIAL SAT BD 479659 481019 COMM 6 UNUSED 9730960 9823336 I90200 FEB 8, 2024 1:14 PM SOFTWARE REVISION LEVEL VERSION 336.01 SOFTWARE# 346336-100-B CREATED - 20.04.26.20.30 S-MODULE# 330160-004-a SYSTEM FEATURES: PERIODIC IN-TANK TESTS ANNUAL IN-TANK TESTS ISD/APM I11100 FEB 8, 2024 1:14 PM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:34AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:34AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:34AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:33AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:33AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:32AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:32AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:31AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:29AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:29AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:29AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:28AM L14 ANNULAR UNL SOUTH ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L11 ANNULAR UNL ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L15 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L13 ANNULAR UNL SIPHON ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 4 OTHER UNLEADED SOUTH STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 2 OTHER SUPREME STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L10 OTHER DIESEL FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 9 OTHER UNL SOUTH FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 6 OTHER UNL NORTH FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 5 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 8 OTHER UNL SIPHON FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 3 OTHER UNLEADED SIPHON STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 7 OTHER SUPREME FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 1 OTHER UNLEADED NORTH STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM L 2 OTHER SUPREME STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM L 6 OTHER UNL NORTH FILL SENSOR OUT ALARM ALARM 2-08-24 10:51AM L 5 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM L 8 OTHER UNL SIPHON FILL SENSOR OUT ALARM ALARM 2-08-24 10:51AM L 7 OTHER SUPREME FILL SENSOR OUT ALARM ALARM 2-08-24 10:51AM L 4 OTHER UNLEADED SOUTH STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM L 3 OTHER UNLEADED SIPHON STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM L 1 OTHER UNLEADED NORTH STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM L15 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM L14 ANNULAR UNL SOUTH ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM L11 ANNULAR UNL ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM L13 ANNULAR UNL SIPHON ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM L10 OTHER DIESEL FILL SENSOR OUT ALARM ALARM 2-08-24 10:51AM L 9 OTHER UNL SOUTH FILL SENSOR OUT ALARM ALARM 2-08-24 10:50AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 10:46AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 10:45AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 10:45AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 10:44AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 10:43AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 10:43AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 10:42AM L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 10:41AM I11200 FEB 8, 2024 1:14 PM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 NON-PRIORITY ALARM HISTORY ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME SYSTEM PRINTER ERROR CLEAR 2-08-24 9:14AM SYSTEM PAPER OUT CLEAR 2-08-24 9:14AM SYSTEM PAPER OUT ALARM 2-08-24 9:04AM SYSTEM PRINTER ERROR ALARM 2-08-24 9:04AM SYSTEM PRINTER ERROR CLEAR 12-27-23 9:14AM SYSTEM PAPER OUT CLEAR 12-27-23 9:14AM SYSTEM PAPER OUT ALARM 12-27-23 9:14AM SYSTEM PRINTER ERROR ALARM 12-27-23 9:14AM SYSTEM PRINTER ERROR CLEAR 12-27-23 9:14AM SYSTEM PAPER OUT CLEAR 12-27-23 9:14AM SYSTEM PAPER OUT ALARM 12-27-23 9:12AM SYSTEM PRINTER ERROR ALARM 12-27-23 9:12AM OTHER ISD DEGRD PRES WARN CLEAR 12-08-23 7:52AM OTHER ISD DEGRD PRES WARN ALARM 12-03-23 8:04AM OTHER ISD GROSS PRES WARN CLEAR 11-07-23 1:07PM SYSTEM PRINTER ERROR CLEAR 11-06-23 8:08AM SYSTEM PAPER OUT CLEAR 11-06-23 8:08AM SYSTEM PRINTER ERROR ALARM 11-06-23 8:07AM SYSTEM PAPER OUT ALARM 11-06-23 8:07AM SYSTEM PRINTER ERROR CLEAR 11-06-23 8:07AM SYSTEM PAPER OUT CLEAR 11-06-23 8:07AM SYSTEM PRINTER ERROR ALARM 11-06-23 8:07AM SYSTEM PAPER OUT ALARM 11-06-23 8:07AM OTHER ISD GROSS PRES WARN ALARM 11-06-23 8:03AM OTHER ISD GROSS PRES WARN CLEAR 10-30-23 8:00AM OTHER ISD GROSS PRES WARN ALARM 10-23-23 8:03AM OTHER ISD GROSS PRES WARN CLEAR 10-16-23 8:35AM OTHER ISD GROSS PRES WARN ALARM 10-16-23 8:03AM T 3 TANK UNLEADED SIPHON HIGH PRODUCT ALARM CLEAR 10-10-23 8:59AM T 3 TANK UNLEADED SIPHON HIGH PRODUCT ALARM ALARM 10-09-23 5:31PM OTHER ISD DEGRD PRES WARN CLEAR 10-09-23 8:34AM OTHER ISD GROSS PRES WARN CLEAR 10-09-23 8:34AM OTHER ISD DEGRD PRES WARN ALARM 10-07-23 8:03AM OTHER ISD GROSS PRES WARN ALARM 10-04-23 8:04AM SYSTEM PRINTER ERROR CLEAR 9-18-23 9:46AM SYSTEM PAPER OUT CLEAR 9-18-23 9:46AM SYSTEM PAPER OUT ALARM 9-18-23 9:46AM SYSTEM PRINTER ERROR ALARM 9-18-23 9:46AM SYSTEM PRINTER ERROR CLEAR 9-18-23 9:46AM SYSTEM PAPER OUT CLEAR 9-18-23 9:46AM SYSTEM PRINTER ERROR ALARM 9-18-23 9:42AM SYSTEM PAPER OUT ALARM 9-18-23 9:42AM SYSTEM PRINTER ERROR CLEAR 9-07-23 10:12PM SYSTEM PAPER OUT CLEAR 9-07-23 10:12PM SYSTEM PRINTER ERROR ALARM 9-07-23 10:11PM SYSTEM PAPER OUT ALARM 9-07-23 10:11PM SYSTEM PRINTER ERROR CLEAR 8-30-23 6:27PM SYSTEM PAPER OUT CLEAR 8-30-23 6:27PM SYSTEM PRINTER ERROR ALARM 8-30-23 6:26PM SYSTEM PAPER OUT ALARM 8-30-23 6:26PM I20600 FEB 8, 2024 1:14 PM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 TANK ALARM HISTORY TANK 1 UNLEADED NORTH OVERFILL ALARM OCT 16, 2023 3:13 AM OCT 16, 2023 2:58 AM OCT 16, 2023 2:54 AM SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM HIGH PRODUCT ALARM APR 12, 2023 8:54 PM INVALID FUEL LEVEL MAY 13, 2023 3:06 PM DEC 20, 2021 12:31 PM PROBE OUT OCT 7, 2020 8:11 AM LOW TEMP WARNING OCT 7, 2020 3:49 PM TANK 2 SUPREME HIGH WATER ALARM JUL 27, 2023 3:37 PM INVALID FUEL LEVEL JUL 28, 2023 1:23 PM JUL 27, 2023 4:51 PM MAY 13, 2023 1:28 PM PROBE OUT OCT 7, 2020 8:11 AM HIGH WATER WARNING JUL 27, 2023 3:37 PM TANK 3 UNLEADED SIPHON OVERFILL ALARM OCT 9, 2023 5:30 PM APR 12, 2023 8:58 PM SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM HIGH PRODUCT ALARM OCT 9, 2023 5:31 PM PROBE OUT OCT 7, 2020 8:13 AM TANK 4 UNLEADED SOUTH SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM INVALID FUEL LEVEL MAY 13, 2023 3:19 PM JAN 9, 2022 1:55 PM NOV 21, 2020 11:42 AM PROBE OUT OCT 7, 2020 8:14 AM TANK 5 DIESEL INVALID FUEL LEVEL JUL 10, 2023 3:26 PM TANK 9 TANK 10 TANK 11 TANK 12 TANK 13 TANK 14 TANK 15 TANK 16 I38200 FEB 8, 2024 1:14 PM I30200 FEB 8, 2024 1:14 PM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 LIQUID ALARM HISTORY REPORT SENSOR LOCATION 1 UNLEADED NORTH STP FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:20 AM FUEL ALARM APR 25, 2023 8:58 AM SETUP DATA WARNING 2 SUPREME STP FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 10:17 AM SENSOR OUT ALARM FEB 8, 2024 10:17 AM FUEL ALARM 3 UNLEADED SIPHON STP FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:26 AM FUEL ALARM APR 25, 2023 8:58 AM SETUP DATA WARNING 4 UNLEADED SOUTH STP FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:27 AM FUEL ALARM APR 25, 2023 8:58 AM SETUP DATA WARNING 5 DIESEL STP FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:28 AM FUEL ALARM APR 25, 2023 8:58 AM SETUP DATA WARNING 6 UNL NORTH FILL FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:30 AM FUEL ALARM APR 25, 2023 8:58 AM SETUP DATA WARNING 7 SUPREME FILL FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:31 AM FUEL ALARM NOV 13, 2023 12:32 PM FUEL ALARM 8 UNL SIPHON FILL FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:31 AM FUEL ALARM JAN 1, 2024 11:02 AM FUEL ALARM 9 UNL SOUTH FILL FEB 8, 2024 10:50 AM SENSOR OUT ALARM FEB 8, 2024 9:32 AM FUEL ALARM FEB 21, 2023 9:27 AM SENSOR OUT ALARM 10 DIESEL FILL FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:33 AM FUEL ALARM FEB 21, 2023 9:27 AM SENSOR OUT ALARM 11 UNL ANNULAR FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:43 AM FUEL ALARM FEB 8, 2024 9:42 AM FUEL ALARM 12 SUPREME ANNULAR FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:38 AM FUEL ALARM FEB 8, 2024 9:38 AM FUEL ALARM 13 UNL SIPHON ANNULAR FEB 8, 2024 11:34 AM FUEL ALARM FEB 8, 2024 11:33 AM FUEL ALARM FEB 8, 2024 11:32 AM FUEL ALARM 14 UNL SOUTH ANNULAR FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 10:03 AM FUEL ALARM FEB 8, 2024 9:46 AM FUEL ALARM 15 DIESEL ANNULAR FEB 8, 2024 10:51 AM SENSOR OUT ALARM FEB 8, 2024 9:55 AM FUEL ALARM FEB 8, 2024 9:53 AM FUEL ALARM I31600 FEB 8, 2024 1:14 PM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 SMART SENSOR ALARM HISTORY REPORT SENSOR LOCATION 1 FM 1-2 2 FM 3-4 3 FM 5-6 4 FM 7-8 5 FM 9-10 OCT 2, 2020 8:40 AM COMMUNICATION ALARM SEP 16, 2020 3:58 PM COMMUNICATION ALARM SEP 10, 2020 6:38 PM COMMUNICATION ALARM 6 FM 11-12 7 PS 7-8 I40200 FEB 8, 2024 1:14 PM I40300 FEB 8, 2024 1:14 PM I34200 FEB 8, 2024 1:14 PM I34700 FEB 8, 2024 1:14 PM IV0100 FEB 8, 2024 1:14 PM 204121 CALIFORNIA CH 4100 CALIFORNIA AVE BKRSFLD CA 93309 661-336-0263 ISD ALARM STATUS REPORT EVR TYPE: BALANCE ISD TYPE: 01.05 VAPOR PROCESSOR TYPE: NONE OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS EVR VAPOR CONTAINMENT :PASS ISD MONITOR UP-TIME :100% EVR/ISD PASS TIME :100% WARNING ALARMS DATE TIME DESCRIPTION READING VALUE 23-12-07 08:04:19 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.34 23-12-06 08:04:25 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37 23-12-05 08:04:27 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37 23-12-04 08:04:24 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.36 23-12-03 08:04:29 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37 23-11-07 08:04:07 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.06 23-11-06 08:03:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07 23-10-29 08:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16 23-10-28 08:02:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16 23-10-27 08:02:46 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.31 FAILURE ALARMS DATE TIME DESCRIPTION READING VALUE 23-10-30 08:02:37 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.13 22-12-05 08:03:18 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 126.81 22-11-22 08:02:53 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 153.95 22-11-07 08:03:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 67.28 22-10-04 08:04:39 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 87.23 22-09-21 08:03:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 86.74 22-08-02 08:02:51 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 115.69 22-07-20 08:03:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.98 22-07-07 08:04:03 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.15 21-12-06 08:03:24 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.16 SHUTDOWN & MISCELLANEOUS EVENTS DATE TIME DESCRIPTION ACTION/NAME 23-12-08 07:52:01 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-11-07 13:07:50 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-10-30 08:20:08 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-10-30 08:18:06 PUMPS MANUALLY RE-ENABLED 23-10-30 08:02:37 CONTAINMENT GROSS DISABLED DISPENSERS 23-10-29 01:00:00 TIME CHANGE DETECTED AT: 23-10-29 02:00:13 23-10-16 08:35:30 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-10-09 08:34:10 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED 23-09-30 08:03:16 READINESS ISD:PP EVR:PP ISD & EVR READY 23-09-30 04:59:51 READINESS ISD:PP EVR:NN EVR READINESS PENDING