HomeMy WebLinkAboutFMC 2024Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10022956 02/08/2024
Samco California
4100 California Avenue Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
VeederRoot TLS-3XX Technician - C32655 10/11/2024
Vaporless Manufacturing Inc. - #5265 10/21/2024
OPW - 1193585 04/14/2025
02/08/2024 5
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS-350
336.01
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 87-1 Unleaded STP (North)
L2 208 91 Supreme STP
L3 208 87-2 Unleaded Slave Tank STP
L4 208 87-3 Unleaded STP (South)
L5 208 Diesel STP
L6 208 87-1 Unleaded Fill (North)
L7 208 91 Supreme Fill
L8 208 87-2 Unleaded Slave Tank Fill
L9 208 87-3 Unleaded Fill (South)
L10 208 Diesel Fill
L11 409 87-1 Unleaded ANN (North)
L12 409 91 Supreme ANN
L13 409 87-2 Unleaded Slave Tank ANN
L14 409 87-3 Unleaded ANN (South)
L15 409 Diesel ANN
Chain & Float Kit Dispenser 1-2 UDC
Chain & Float Kit Dispenser 3-4 UDC
Chain & Float Kit Dispenser 5-6 UDC
Chain & Float Kit Dispenser 7-8 UDC
Chain & Float Kit Dispenser 9-10 UDC
Chain & Float Kit Dispenser 11-12 UDC
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
T1 FX1V 87-1 Unleaded
T2 FX1V 91 Supreme
T4 FX1V 87-2 Unleaded
T5 FX1DV Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Samco California4100 California AvenueBakersfield10022956Disp 3-4Disp 7-8 Disp 11-12MPDMPDMPDMPDMPDMPDDisp 1-2Disp 5-6Disp 9-10ProductProductProductProductProductProductBrandon Nunez
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10022956 02/08/2024
Samco California
4100 California Avenue Bakersfield 93309
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
OPW - 1193585 04/14/2025
PEI 1200 1 Hour Hydrostatic All Spill Containers
02/08/2024 N/A
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1: 87-1 UNL
OPW
T5: DSL
CNI
T2: 91 SUP
OPW
T3: 87-2 (Slave)
OPW
T4: 87-3 UNL
OPW
Samco California System Setup
Responses Received:
200
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
FEB 8, 2024 9:01 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 UNLEADED NORTH 4194 39.77 0.0 61.0 5490
2 SUPREME 4081 38.97 0.0 65.3 5603
3 UNLEADED SIPHON 3765 36.71 0.0 62.1 5919
4 UNLEADED SOUTH 3783 36.84 0.0 63.5 5901
5 DIESEL 3197 32.57 0.0 69.2 6487
I90500
FEB 8, 2024 9:02 AM
SOFTWARE REVISION LEVEL
VERSION 336.01
SOFTWARE# 346336-100-B
CREATED - 20.04.26.20.30
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
FEB 8, 2024 9:02 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
FEB 8, 2024 9:02 AM
SHIFT TIME 1 : 5:00 AM
I50202
FEB 8, 2024 9:02 AM
SHIFT TIME 2 : DISABLED
I50203
FEB 8, 2024 9:02 AM
SHIFT TIME 3 : DISABLED
I50204
FEB 8, 2024 9:02 AM
SHIFT TIME 4 : DISABLED
I54600
FEB 8, 2024 9:02 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
FEB 8, 2024 9:02 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
FEB 8, 2024 9:02 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
FEB 8, 2024 9:02 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
FEB 8, 2024 9:02 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
FEB 8, 2024 9:02 AM
PRINT TC VOLUMES
ENABLED
I50E00
FEB 8, 2024 9:02 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
FEB 8, 2024 9:02 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
FEB 8, 2024 9:02 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
FEB 8, 2024 9:02 AM
DAYLIGHT SAVING TIME
ENABLED OFF
I51B00
FEB 8, 2024 9:02 AM
DAYLIGHT SAVING TIME
START DATE APR WEEK 1 SUN 2:00 AM
END DATE OCT WEEK 6 SUN 2:00 AM
I51600
FEB 8, 2024 9:02 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
FEB 8, 2024 9:02 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 00 ENABLED
3 00 ENABLED
4 00 ENABLED
5 000000 DISABLED
6 00 ENABLED
I21900
FEB 8, 2024 9:02 AM
TANK CHART SECURITY
DISABLED
I5BD00
FEB 8, 2024 9:02 AM
CUSTOM ALARM LABELS
DISABLED
I56000
FEB 8, 2024 9:02 AM
MASS/DENSITY
DISABLED
I88101
FEB 8, 2024 9:02 AM
PORT SETTINGS:
COMM BOARD : 1 (RS-232)
BAUD RATE : 9600
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88102
FEB 8, 2024 9:02 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 1200
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : 00
I88103
FEB 8, 2024 9:02 AM
PORT SETTINGS:
COMM BOARD : 3 (EDIM )
RS-232 SECURITY
CODE : 00
I88104
FEB 8, 2024 9:02 AM
I88105
FEB 8, 2024 9:02 AM
PORT SETTINGS:
COMM BOARD : 5 (S-SAT )
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
DTR NORMAL STATE: HIGH
I88106
FEB 8, 2024 9:02 AM
I52000
FEB 8, 2024 9:02 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 WEEKLY SUN 4:19 PM
2 WEEKLY SUN 4:19 PM
3 WEEKLY SUN 4:19 PM
4 WEEKLY SUN 4:19 PM
5 WEEKLY SUN 4:19 PM
6 WEEKLY SUN 4:19 PM
7 WEEKLY SUN 4:19 PM
8 WEEKLY WED 4:20 PM
I60100
FEB 8, 2024 9:02 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 UNLEADED NORTH ON
2 SUPREME ON
3 UNLEADED SIPHON ON
4 UNLEADED SOUTH ON
5 DIESEL ON
6 OFF
7 OFF
8 OFF
I60200
FEB 8, 2024 9:02 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 UNLEADED NORTH
2 SUPREME
3 UNLEADED SIPHON
4 UNLEADED SOUTH
5 DIESEL
6
7
8
I60300
FEB 8, 2024 9:02 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 UNLEADED NORTH 1
2 SUPREME 2
3 UNLEADED SIPHON 3
4 UNLEADED SOUTH 4
5 DIESEL 5
6 6
7 7
8 8
I60900
FEB 8, 2024 9:02 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 UNLEADED NORTH 0.000700
2 SUPREME 0.000700
3 UNLEADED SIPHON 0.000700
4 UNLEADED SOUTH 0.000700
5 DIESEL 0.000700
6 0.000000
7 0.000000
8 0.000000
I60700
FEB 8, 2024 9:02 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 UNLEADED NORTH 89.75
2 SUPREME 89.75
3 UNLEADED SIPHON 89.75
4 UNLEADED SOUTH 89.75
5 DIESEL 89.75
6 0.00
7 0.00
8 0.00
I60A00
FEB 8, 2024 9:02 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 UNLEADED NORTH 4 PTS
9684 2 SUPREME 4 PTS 9684 3 UNLEADED
SIPHON 4 PTS 9684 4 UNLEADED SOUTH 4 PTS
9684 5 DIESEL 4 PTS 9684 6
4 PTS 0 7 4 PTS 0 8
4 PTS 0
I60400
FEB 8, 2024 9:02 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 9684
2 SUPREME 9684
3 UNLEADED SIPHON 9684
4 UNLEADED SOUTH 9684
5 DIESEL 9684
6 0
7 0
8 0
I60500
FEB 8, 2024 9:02 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 9684 7891 4918 1900
2 SUPREME 9684 7891 4918 1900
3 UNLEADED SIPHON 9684 7891 4918 1900
4 UNLEADED SOUTH 9684 7891 4918 1900
5 DIESEL 9684 7891 4918 1900
6 0 0 0 0
7 0 0 0 0
8 0 0 0 0
I60600
FEB 8, 2024 9:02 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 9684 0 0 0
0 7891 0 0
0 0 4918 0
0 0 0 1900
0 0 0 0
2 SUPREME 9684 0 0 0
0 7891 0 0
0 0 4918 0
0 0 0 1900
0 0 0 0
3 UNLEADED SIPHON 9684 0 0 0
0 7891 0 0
0 0 4918 0
0 0 0 1900
0 0 0 0
4 UNLEADED SOUTH 9684 0 0 0
0 7891 0 0
0 0 4918 0
0 0 0 1900
0 0 0 0
5 DIESEL 9684 0 0 0
0 7891 0 0
0 0 4918 0
0 0 0 1900
0 0 0 0
6 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
7 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
8 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
FEB 8, 2024 9:02 AM
TANK PRODUCT LABEL METER DATA
1 UNLEADED NORTH NO
2 SUPREME NO
3 UNLEADED SIPHON NO
4 UNLEADED SOUTH NO
5 DIESEL NO
6 NO
7 NO
8 NO
I62F00
FEB 8, 2024 9:02 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 UNLEADED NORTH 2.0 IN.
2 SUPREME 4.0 IN.
3 UNLEADED SIPHON 2.0 IN.
4 UNLEADED SOUTH 2.0 IN.
5 DIESEL 4.0 IN.
I62700
FEB 8, 2024 9:02 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED NORTH 2.0
2 SUPREME 2.0
3 UNLEADED SIPHON 2.0
4 UNLEADED SOUTH 2.0
5 DIESEL 2.0
I64200
FEB 8, 2024 9:02 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 UNLEADED NORTH LOW
2 SUPREME LOW
3 UNLEADED SIPHON LOW
4 UNLEADED SOUTH LOW
5 DIESEL LOW
I62400
FEB 8, 2024 9:02 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 UNLEADED NORTH 3.0
2 SUPREME 3.0
3 UNLEADED SIPHON 3.0
4 UNLEADED SOUTH 3.0
5 DIESEL 3.0
I62800
FEB 8, 2024 9:02 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 9684
2 SUPREME 9684
3 UNLEADED SIPHON 9684
4 UNLEADED SOUTH 9684
5 DIESEL 9684
6 0
7 0
8 0
I62300
FEB 8, 2024 9:02 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 9000
2 SUPREME 9000
3 UNLEADED SIPHON 9000
4 UNLEADED SOUTH 9000
5 DIESEL 9000
6 0
7 0
8 0
I62200
FEB 8, 2024 9:02 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 9500
2 SUPREME 9500
3 UNLEADED SIPHON 9500
4 UNLEADED SOUTH 9500
5 DIESEL 9500
6 0
7 0
8 0
I62900
FEB 8, 2024 9:02 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 500
2 SUPREME 500
3 UNLEADED SIPHON 500
4 UNLEADED SOUTH 500
5 DIESEL 500
6 0
7 0
8 0
I62100
FEB 8, 2024 9:02 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 500
2 SUPREME 500
3 UNLEADED SIPHON 500
4 UNLEADED SOUTH 500
5 DIESEL 500
6 0
7 0
8 0
I62600
FEB 8, 2024 9:02 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 99
2 SUPREME 99
3 UNLEADED SIPHON 99
4 UNLEADED SOUTH 99
5 DIESEL 99
6 99
7 99
8 99
I62500
FEB 8, 2024 9:02 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 99
2 SUPREME 99
3 UNLEADED SIPHON 99
4 UNLEADED SOUTH 99
5 DIESEL 99
6 99
7 99
8 99
I60800
FEB 8, 2024 9:02 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 UNLEADED NORTH 0.49
2 SUPREME 3.40
3 UNLEADED SIPHON 0.26
4 UNLEADED SOUTH 0.14
5 DIESEL 4.70
6 0.00
7 0.00
8 0.00
I60B00
FEB 8, 2024 9:02 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
FEB 8, 2024 9:02 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 UNLEADED NORTH 0.00
2 SUPREME 0.00
3 UNLEADED SIPHON 0.00
4 UNLEADED SOUTH 0.00
5 DIESEL 0.00
6 0.00
7 0.00
8 0.00
I61200
FEB 8, 2024 9:02 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 UNLEADED NORTH 3, 4 4
2 SUPREME NONE NONE
3 UNLEADED SIPHON 1, 4 NONE
4 UNLEADED SOUTH 1, 3 1
5 DIESEL NONE NONE
6 NONE NONE
7 NONE NONE
8 NONE NONE
I63600
FEB 8, 2024 9:02 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 100
2 SUPREME 100
3 UNLEADED SIPHON 100
4 UNLEADED SOUTH 100
5 DIESEL 100
6 0
7 0
8 0
I62A00
FEB 8, 2024 9:02 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 100
2 SUPREME 100
3 UNLEADED SIPHON 100
4 UNLEADED SOUTH 100
5 DIESEL 100
6 0
7 0
8 0
I62C00
FEB 8, 2024 9:02 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 UNLEADED NORTH STANDARD
2 SUPREME STANDARD
3 UNLEADED SIPHON STANDARD
4 UNLEADED SOUTH STANDARD
5 DIESEL STANDARD
6 STANDARD
7 STANDARD
8 STANDARD
I62D00
FEB 8, 2024 9:02 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 UNLEADED NORTH GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 SUPREME GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 UNLEADED SIPHON GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 UNLEADED SOUTH GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
5 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
6 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
7 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
8 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
FEB 8, 2024 9:02 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 UNLEADED NORTH OFF OFF
2 SUPREME OFF OFF
3 UNLEADED SIPHON OFF OFF
4 UNLEADED SOUTH OFF OFF
5 DIESEL OFF OFF
6 OFF OFF
7 OFF OFF
8 OFF OFF
I63000
FEB 8, 2024 9:02 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 UNLEADED NORTH OFF
2 SUPREME OFF
3 UNLEADED SIPHON OFF
4 UNLEADED SOUTH OFF
5 DIESEL OFF
6 OFF
7 OFF
8 OFF
I63200
FEB 8, 2024 9:02 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 UNLEADED NORTH OFF
2 SUPREME OFF
3 UNLEADED SIPHON OFF
4 UNLEADED SOUTH OFF
5 DIESEL OFF
6 OFF
7 OFF
8 OFF
I61000
FEB 8, 2024 9:02 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 UNLEADED NORTH 1
2 SUPREME 1
3 UNLEADED SIPHON 1
4 UNLEADED SOUTH 1
5 DIESEL 1
6 1
7 1
8 1
I63A00
FEB 8, 2024 9:02 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 UNLEADED NORTH 10.00%
2 SUPREME 10.00%
3 UNLEADED SIPHON 10.00%
4 UNLEADED SOUTH 10.00%
5 DIESEL 10.00%
6 10.00%
7 10.00%
8 10.00%
I61100
FEB 8, 2024 9:02 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
FEB 6, 2007
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
FEB 8, 2024 9:02 AM
CSLD PROBABLITY OF DETECTION
I61400
FEB 8, 2024 9:02 AM
CSLD CLIMATE FACTOR
I61600
FEB 8, 2024 9:02 AM
TANK PRODUCT LABEL CAL UPDATE
1 UNLEADED NORTH IMMEDIATE
2 SUPREME IMMEDIATE
3 UNLEADED SIPHON IMMEDIATE
4 UNLEADED SOUTH IMMEDIATE
5 DIESEL IMMEDIATE
6 IMMEDIATE
7 IMMEDIATE
8 IMMEDIATE
I61A00
FEB 8, 2024 9:02 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 UNLEADED NORTH DISABLED
2 SUPREME DISABLED
3 UNLEADED SIPHON DISABLED
4 UNLEADED SOUTH DISABLED
5 DIESEL DISABLED
6 DISABLED
7 DISABLED
8 DISABLED
I61B00
FEB 8, 2024 9:02 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
FEB 8, 2024 9:02 AM
CSLD REPORT ONLY
I62B00
FEB 8, 2024 9:02 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 UNLEADED NORTH ??? 0, 0
2 SUPREME ??? 0, 0
3 UNLEADED SIPHON ??? 0, 0
4 UNLEADED SOUTH ??? 0, 0
5 DIESEL ??? 0, 0
6 ??? 0, 0
7 ??? 0, 0
8 ??? 0, 0
I63300
FEB 8, 2024 9:03 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
FEB 8, 2024 9:03 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 0
2 SUPREME 0
3 UNLEADED SIPHON 0
4 UNLEADED SOUTH 0
5 DIESEL 0
6 0
7 0
8 0
I63500
FEB 8, 2024 9:03 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 UNLEADED NORTH 1
2 SUPREME 1
3 UNLEADED SIPHON 1
4 UNLEADED SOUTH 1
5 DIESEL 1
6 1
7 1
8 1
I63900
FEB 8, 2024 9:03 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 UNLEADED NORTH
END FACTOR: NONE
2 SUPREME
END FACTOR: NONE
3 UNLEADED SIPHON
END FACTOR: NONE
4 UNLEADED SOUTH
END FACTOR: NONE
5 DIESEL
END FACTOR: NONE
6
END FACTOR: NONE
7
END FACTOR: NONE
8
END FACTOR: NONE
I78000
FEB 8, 2024 9:03 AM
I77700
FEB 8, 2024 9:03 AM
I77800
FEB 8, 2024 9:03 AM
I78C00
FEB 8, 2024 9:03 AM
I78300
FEB 8, 2024 9:03 AM
I78F00
FEB 8, 2024 9:03 AM
I78700
FEB 8, 2024 9:03 AM
I70200
FEB 8, 2024 9:03 AM
LIQUID LABEL
DEVICE LABEL
1 UNLEADED NORTH STP
2 SUPREME STP
3 UNLEADED SIPHON STP
4 UNLEADED SOUTH STP
5 DIESEL STP
6 UNL NORTH FILL
7 SUPREME FILL
8 UNL SIPHON FILL
9 UNL SOUTH FILL
10 DIESEL FILL
11 UNL ANNULAR
12 SUPREME ANNULAR
13 UNL SIPHON ANNULAR
14 UNL SOUTH ANNULAR
15 DIESEL ANNULAR
16 DIESEL FILL
I70300
FEB 8, 2024 9:03 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 UNLEADED NORTH STP TRI-STATE (SINGLE FLOAT)
2 SUPREME STP TRI-STATE (SINGLE FLOAT)
3 UNLEADED SIPHON STP TRI-STATE (SINGLE FLOAT)
4 UNLEADED SOUTH STP TRI-STATE (SINGLE FLOAT)
5 DIESEL STP TRI-STATE (SINGLE FLOAT)
6 UNL NORTH FILL TRI-STATE (SINGLE FLOAT)
7 SUPREME FILL TRI-STATE (SINGLE FLOAT)
8 UNL SIPHON FILL TRI-STATE (SINGLE FLOAT)
9 UNL SOUTH FILL TRI-STATE (SINGLE FLOAT)
10 DIESEL FILL TRI-STATE (SINGLE FLOAT)
11 UNL ANNULAR TRI-STATE (SINGLE FLOAT)
12 SUPREME ANNULAR TRI-STATE (SINGLE FLOAT)
13 UNL SIPHON ANNULAR TRI-STATE (SINGLE FLOAT)
14 UNL SOUTH ANNULAR TRI-STATE (SINGLE FLOAT)
15 DIESEL ANNULAR TRI-STATE (SINGLE FLOAT)
16 DIESEL FILL NORMALLY CLOSED
I70400
FEB 8, 2024 9:03 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 UNLEADED NORTH STP OTHER SENSORS
2 SUPREME STP OTHER SENSORS
3 UNLEADED SIPHON STP OTHER SENSORS
4 UNLEADED SOUTH STP OTHER SENSORS
5 DIESEL STP STP SUMP
6 UNL NORTH FILL OTHER SENSORS
7 SUPREME FILL OTHER SENSORS
8 UNL SIPHON FILL OTHER SENSORS
9 UNL SOUTH FILL OTHER SENSORS
10 DIESEL FILL OTHER SENSORS
11 UNL ANNULAR ANNULAR SPACE
12 SUPREME ANNULAR ANNULAR SPACE
13 UNL SIPHON ANNULAR ANNULAR SPACE
14 UNL SOUTH ANNULAR ANNULAR SPACE
15 DIESEL ANNULAR ANNULAR SPACE
16 DIESEL FILL OTHER SENSORS
I74200
FEB 8, 2024 9:03 AM
I74300
FEB 8, 2024 9:03 AM
I74400
FEB 8, 2024 9:03 AM
I74700
FEB 8, 2024 9:03 AM
I74800
FEB 8, 2024 9:03 AM
I74900
FEB 8, 2024 9:03 AM
I7BC00
FEB 8, 2024 9:03 AM
I80200
FEB 8, 2024 9:03 AM
I80300
FEB 8, 2024 9:03 AM
I80400
FEB 8, 2024 9:03 AM
I80700
FEB 8, 2024 9:03 AM
RELAY LABEL
DEVICE LABEL
1 SUPREME
2 UNLEADED NORTH
3 UNLEADED SOUTH
4 DIESEL
I80900
FEB 8, 2024 9:03 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 SUPREME NORMALLY CLOSED
2 UNLEADED NORTH NORMALLY OPEN
3 UNLEADED SOUTH NORMALLY OPEN
4 DIESEL NORMALLY CLOSED
I80B00
FEB 8, 2024 9:03 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 SUPREME 2
2 UNLEADED NORTH 1
3 UNLEADED SOUTH 4
4 DIESEL 5
I80A00
FEB 8, 2024 9:03 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 SUPREME STANDARD
2 UNLEADED NORTH PUMP CONTROL OUTPUT
3 UNLEADED SOUTH PUMP CONTROL OUTPUT
4 DIESEL STANDARD
I80C00
FEB 8, 2024 9:03 AM
I80800
FEB 8, 2024 9:03 AM
RELAY SETUP REPORT
R 1:SUPREME
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 2
LIQUID SENSOR ALMS
L 2:FUEL ALARM
L 2:SENSOR OUT ALARM
L 2:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 2:UNLEADED NORTH
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
R 3:UNLEADED SOUTH
TYPE:
PUMP CONTROL OUTPUT
TANK #: 4
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 4:FUEL ALARM
L 3:SENSOR OUT ALARM
L 4:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 4:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
h13:GROSS COLLECT FAIL
h14:GROSS COLLECT FAIL
h15:GROSS COLLECT FAIL
h16:GROSS COLLECT FAIL
h17:GROSS COLLECT FAIL
h18:GROSS COLLECT FAIL
h19:GROSS COLLECT FAIL
h20:GROSS COLLECT FAIL
h21:GROSS COLLECT FAIL
h22:GROSS COLLECT FAIL
h23:GROSS COLLECT FAIL
h24:GROSS COLLECT FAIL
h25:GROSS COLLECT FAIL
h26:GROSS COLLECT FAIL
h27:GROSS COLLECT FAIL
h28:GROSS COLLECT FAIL
h29:GROSS COLLECT FAIL
h30:GROSS COLLECT FAIL
h31:GROSS COLLECT FAIL
h32:GROSS COLLECT FAIL
h33:GROSS COLLECT FAIL
h34:GROSS COLLECT FAIL
h35:GROSS COLLECT FAIL
h36:GROSS COLLECT FAIL
h37:GROSS COLLECT FAIL
h38:GROSS COLLECT FAIL
h39:GROSS COLLECT FAIL
h40:GROSS COLLECT FAIL
h41:GROSS COLLECT FAIL
h42:GROSS COLLECT FAIL
h43:GROSS COLLECT FAIL
h44:GROSS COLLECT FAIL
h45:GROSS COLLECT FAIL
h46:GROSS COLLECT FAIL
h47:GROSS COLLECT FAIL
h48:GROSS COLLECT FAIL
h49:GROSS COLLECT FAIL
h50:GROSS COLLECT FAIL
h51:GROSS COLLECT FAIL
h52:GROSS COLLECT FAIL
h53:GROSS COLLECT FAIL
h54:GROSS COLLECT FAIL
h55:GROSS COLLECT FAIL
h56:GROSS COLLECT FAIL
h57:GROSS COLLECT FAIL
h58:GROSS COLLECT FAIL
h59:GROSS COLLECT FAIL
h60:GROSS COLLECT FAIL
h61:GROSS COLLECT FAIL
h62:GROSS COLLECT FAIL
h63:GROSS COLLECT FAIL
h64:GROSS COLLECT FAIL
h65:GROSS COLLECT FAIL
h66:GROSS COLLECT FAIL
h67:GROSS COLLECT FAIL
h68:GROSS COLLECT FAIL
h69:GROSS COLLECT FAIL
h70:GROSS COLLECT FAIL
h71:GROSS COLLECT FAIL
h72:GROSS COLLECT FAIL
h73:GROSS COLLECT FAIL
h74:GROSS COLLECT FAIL
h75:GROSS COLLECT FAIL
h76:GROSS COLLECT FAIL
h77:GROSS COLLECT FAIL
h78:GROSS COLLECT FAIL
h79:GROSS COLLECT FAIL
h80:GROSS COLLECT FAIL
h81:GROSS COLLECT FAIL
h82:GROSS COLLECT FAIL
h83:GROSS COLLECT FAIL
h84:GROSS COLLECT FAIL
h85:GROSS COLLECT FAIL
h86:GROSS COLLECT FAIL
h87:GROSS COLLECT FAIL
h88:GROSS COLLECT FAIL
h89:GROSS COLLECT FAIL
h90:GROSS COLLECT FAIL
h91:GROSS COLLECT FAIL
h92:GROSS COLLECT FAIL
h93:GROSS COLLECT FAIL
h94:GROSS COLLECT FAIL
h95:GROSS COLLECT FAIL
h96:GROSS COLLECT FAIL
h97:GROSS COLLECT FAIL
h98:GROSS COLLECT FAIL
h99:GROSS COLLECT FAIL
h13:DEGRD COLLECT FAIL
h14:DEGRD COLLECT FAIL
h15:DEGRD COLLECT FAIL
h16:DEGRD COLLECT FAIL
h17:DEGRD COLLECT FAIL
h18:DEGRD COLLECT FAIL
h19:DEGRD COLLECT FAIL
h20:DEGRD COLLECT FAIL
h21:DEGRD COLLECT FAIL
h22:DEGRD COLLECT FAIL
h23:DEGRD COLLECT FAIL
h24:DEGRD COLLECT FAIL
h25:DEGRD COLLECT FAIL
h26:DEGRD COLLECT FAIL
h27:DEGRD COLLECT FAIL
h28:DEGRD COLLECT FAIL
h29:DEGRD COLLECT FAIL
h30:DEGRD COLLECT FAIL
h31:DEGRD COLLECT FAIL
h32:DEGRD COLLECT FAIL
h33:DEGRD COLLECT FAIL
h34:DEGRD COLLECT FAIL
h35:DEGRD COLLECT FAIL
h36:DEGRD COLLECT FAIL
h37:DEGRD COLLECT FAIL
h38:DEGRD COLLECT FAIL
h39:DEGRD COLLECT FAIL
h40:DEGRD COLLECT FAIL
h41:DEGRD COLLECT FAIL
h42:DEGRD COLLECT FAIL
h43:DEGRD COLLECT FAIL
h44:DEGRD COLLECT FAIL
h45:DEGRD COLLECT FAIL
h46:DEGRD COLLECT FAIL
h47:DEGRD COLLECT FAIL
h48:DEGRD COLLECT FAIL
h49:DEGRD COLLECT FAIL
h50:DEGRD COLLECT FAIL
h51:DEGRD COLLECT FAIL
h52:DEGRD COLLECT FAIL
h53:DEGRD COLLECT FAIL
h54:DEGRD COLLECT FAIL
h55:DEGRD COLLECT FAIL
h56:DEGRD COLLECT FAIL
h57:DEGRD COLLECT FAIL
h58:DEGRD COLLECT FAIL
h59:DEGRD COLLECT FAIL
h60:DEGRD COLLECT FAIL
h61:DEGRD COLLECT FAIL
h62:DEGRD COLLECT FAIL
h63:DEGRD COLLECT FAIL
h64:DEGRD COLLECT FAIL
h65:DEGRD COLLECT FAIL
h66:DEGRD COLLECT FAIL
h67:DEGRD COLLECT FAIL
h68:DEGRD COLLECT FAIL
h69:DEGRD COLLECT FAIL
h70:DEGRD COLLECT FAIL
h71:DEGRD COLLECT FAIL
h72:DEGRD COLLECT FAIL
h73:DEGRD COLLECT FAIL
h74:DEGRD COLLECT FAIL
h75:DEGRD COLLECT FAIL
h76:DEGRD COLLECT FAIL
h77:DEGRD COLLECT FAIL
h78:DEGRD COLLECT FAIL
h79:DEGRD COLLECT FAIL
h80:DEGRD COLLECT FAIL
h81:DEGRD COLLECT FAIL
h82:DEGRD COLLECT FAIL
h83:DEGRD COLLECT FAIL
h84:DEGRD COLLECT FAIL
h85:DEGRD COLLECT FAIL
h86:DEGRD COLLECT FAIL
h87:DEGRD COLLECT FAIL
h88:DEGRD COLLECT FAIL
h89:DEGRD COLLECT FAIL
h90:DEGRD COLLECT FAIL
h91:DEGRD COLLECT FAIL
h92:DEGRD COLLECT FAIL
h93:DEGRD COLLECT FAIL
h94:DEGRD COLLECT FAIL
h95:DEGRD COLLECT FAIL
h96:DEGRD COLLECT FAIL
h97:DEGRD COLLECT FAIL
h98:DEGRD COLLECT FAIL
h99:DEGRD COLLECT FAIL
h13:FLOW COLLECT FAIL
h14:FLOW COLLECT FAIL
h15:FLOW COLLECT FAIL
h16:FLOW COLLECT FAIL
h17:FLOW COLLECT FAIL
h18:FLOW COLLECT FAIL
h19:FLOW COLLECT FAIL
h20:FLOW COLLECT FAIL
h21:FLOW COLLECT FAIL
h22:FLOW COLLECT FAIL
h23:FLOW COLLECT FAIL
h24:FLOW COLLECT FAIL
h25:FLOW COLLECT FAIL
h26:FLOW COLLECT FAIL
h27:FLOW COLLECT FAIL
h28:FLOW COLLECT FAIL
h29:FLOW COLLECT FAIL
h30:FLOW COLLECT FAIL
h31:FLOW COLLECT FAIL
h32:FLOW COLLECT FAIL
h33:FLOW COLLECT FAIL
h34:FLOW COLLECT FAIL
h35:FLOW COLLECT FAIL
h36:FLOW COLLECT FAIL
h37:FLOW COLLECT FAIL
h38:FLOW COLLECT FAIL
h39:FLOW COLLECT FAIL
h40:FLOW COLLECT FAIL
h41:FLOW COLLECT FAIL
h42:FLOW COLLECT FAIL
h43:FLOW COLLECT FAIL
h44:FLOW COLLECT FAIL
h45:FLOW COLLECT FAIL
h46:FLOW COLLECT FAIL
h47:FLOW COLLECT FAIL
h48:FLOW COLLECT FAIL
h49:FLOW COLLECT FAIL
h50:FLOW COLLECT FAIL
h51:FLOW COLLECT FAIL
h52:FLOW COLLECT FAIL
h53:FLOW COLLECT FAIL
h54:FLOW COLLECT FAIL
h55:FLOW COLLECT FAIL
h56:FLOW COLLECT FAIL
h57:FLOW COLLECT FAIL
h58:FLOW COLLECT FAIL
h59:FLOW COLLECT FAIL
h60:FLOW COLLECT FAIL
h61:FLOW COLLECT FAIL
h62:FLOW COLLECT FAIL
h63:FLOW COLLECT FAIL
h64:FLOW COLLECT FAIL
h65:FLOW COLLECT FAIL
h66:FLOW COLLECT FAIL
h67:FLOW COLLECT FAIL
h68:FLOW COLLECT FAIL
h69:FLOW COLLECT FAIL
h70:FLOW COLLECT FAIL
h71:FLOW COLLECT FAIL
h72:FLOW COLLECT FAIL
h73:FLOW COLLECT FAIL
h74:FLOW COLLECT FAIL
h75:FLOW COLLECT FAIL
h76:FLOW COLLECT FAIL
h77:FLOW COLLECT FAIL
h78:FLOW COLLECT FAIL
h79:FLOW COLLECT FAIL
h80:FLOW COLLECT FAIL
h81:FLOW COLLECT FAIL
h82:FLOW COLLECT FAIL
h83:FLOW COLLECT FAIL
h84:FLOW COLLECT FAIL
h85:FLOW COLLECT FAIL
h86:FLOW COLLECT FAIL
h87:FLOW COLLECT FAIL
h88:FLOW COLLECT FAIL
h89:FLOW COLLECT FAIL
h90:FLOW COLLECT FAIL
h91:FLOW COLLECT FAIL
h92:FLOW COLLECT FAIL
h93:FLOW COLLECT FAIL
h94:FLOW COLLECT FAIL
h95:FLOW COLLECT FAIL
h96:FLOW COLLECT FAIL
h97:FLOW COLLECT FAIL
h98:FLOW COLLECT FAIL
h99:FLOW COLLECT FAIL
R 4:DIESEL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: 5
LIQUID SENSOR ALMS
L 5:FUEL ALARM
L 5:SENSOR OUT ALARM
L 5:SHORT ALARM
I79000
FEB 8, 2024 9:04 AM
EDIM:1 VR:349867-001-C TD:16.05.27.07.44
I79100
FEB 8, 2024 9:04 AM
I72300
FEB 8, 2024 9:04 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 FM 1-2 AIR FLOW METER
02 FM 3-4 AIR FLOW METER
03 FM 5-6 AIR FLOW METER
04 FM 7-8 AIR FLOW METER
05 FM 9-10 AIR FLOW METER
06 FM 11-12 AIR FLOW METER
07 PS 7-8 VAPOR PRESSURE
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
FEB 8, 2024 9:04 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
FEB 8, 2024 9:04 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
FEB 8, 2024 9:04 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
VAPOR PROCESSOR TYPE
NONE
IV4700
FEB 8, 2024 9:04 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
ASSESSMENT TIME
START TIME: 8:00 AM
TIME DELAY MINUTES: 1
IV5200
FEB 8, 2024 9:04 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
ACCEPT HIGH ORVR: YES
IV4A00
FEB 8, 2024 9:04 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 UU BLEND3
02 02 02 01 UU BLEND3
03 03 03 02 UU BLEND3
04 04 04 02 UU BLEND3
05 05 05 03 UU BLEND3
06 06 06 03 UU BLEND3
07 07 07 04 UU BLEND3
08 08 08 04 UU BLEND3
09 09 09 05 UU BLEND3
10 16 10 05 UU BLEND3
11 17 11 06 UU BLEND3
12 18 12 06 UU BLEND3
IV4B00
FEB 8, 2024 9:04 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 09/01 01/01 xx/xx
02 01 01/02 02/02 09/02 xx/xx
03 02 02/03 09/03 01/03 xx/xx
04 02 02/04 09/04 01/04 xx/xx
05 03 02/05 09/05 01/05 xx/xx
06 03 02/06 09/06 01/06 xx/xx
07 04 02/07 09/07 01/07 xx/xx
08 04 02/08 09/08 01/08 xx/xx
09 05 09/09 02/09 01/09 xx/xx
16 05 02/10 09/10 01/10 xx/xx
17 06 01/11 02/11 09/11 xx/xx
18 06 02/12 09/12 01/12 xx/xx
IV4900
FEB 8, 2024 9:04 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
FEB 8, 2024 9:04 AM
ISD VERSION: 01.05
Samco California Pre Alarm History
Responses Received:
I10200
FEB 8, 2024 9:05 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 507996 511214
2 4 PROBE / G.T. 163935 164139
3 4 PROBE / G.T. 163913 164160
4 INTERSTITIAL BD 201668 201940
5 INTERSTITIAL BD 201495 201875
6 UNUSED 9743067 9862448
7 UNUSED 9729335 9825860
8 UNUSED 9745647 9834551
9 RELAY BOARD 15007 14994
10 STP SENSE BOARD 33240 33265
11 UNUSED 9729983 9832908
12 UNUSED 9729067 9816489
13 UNUSED 9734726 9840800
14 UNUSED 9732313 9824155
15 UNUSED 9737618 9829772
16 UNUSED 9718810 9823151
COMM 1 RS232 SERIAL BD 14986 15055
COMM 2 RS232 SERIAL BD 15091 15076
COMM 3 ELEC DISP INT. 101121 101358
COMM 4 UNUSED 9732542 9824893
COMM 5 SERIAL SAT BD 479659 481019
COMM 6 UNUSED 9730960 9823336
I90200
FEB 8, 2024 9:05 AM
SOFTWARE REVISION LEVEL
VERSION 336.01
SOFTWARE# 346336-100-B
CREATED - 20.04.26.20.30
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
FEB 8, 2024 9:05 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 1-02-24 8:16AM
L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 1-01-24 11:02AM
L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 12-26-23 9:16AM
L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 12-26-23 9:15AM
L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 12-26-23 9:15AM
L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 12-26-23 9:15AM
L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 12-26-23 9:13AM
L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 12-26-23 9:12AM
E 1 OTHER COMMUNICATION ALARM CLEAR 11-29-23 4:19PM
E 1 OTHER COMMUNICATION ALARM ALARM 11-29-23 4:18PM
L12 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-14-23 9:54AM
L12 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-14-23 9:51AM
L12 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-14-23 9:51AM
L15 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 4:20PM
L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 3:48PM
L12 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-13-23 3:48PM
L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM ALARM 11-13-23 3:48PM
L12 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-13-23 3:48PM
L15 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM ALARM 11-13-23 3:17PM
L 2 OTHER SUPREME STP FUEL ALARM CLEAR 11-13-23 2:07PM
L 2 OTHER SUPREME STP FUEL ALARM ALARM 11-13-23 2:07PM
L14 ANNULAR UNL SOUTH ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 2:02PM
L 8 OTHER UNL SIPHON FILL FUEL ALARM CLEAR 11-13-23 12:35PM
L 7 OTHER SUPREME FILL FUEL ALARM CLEAR 11-13-23 12:34PM
L 8 OTHER UNL SIPHON FILL FUEL ALARM ALARM 11-13-23 12:33PM
L14 ANNULAR UNL SOUTH ANNULAR SENSOR OUT ALARM ALARM 11-13-23 12:32PM
L 7 OTHER SUPREME FILL FUEL ALARM ALARM 11-13-23 12:32PM
L13 ANNULAR UNL SIPHON ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 12:29PM
L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 11:25AM
L12 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-13-23 11:25AM
L13 ANNULAR UNL SIPHON ANNULAR SENSOR OUT ALARM ALARM 11-13-23 11:10AM
L11 ANNULAR UNL ANNULAR SENSOR OUT ALARM CLEAR 11-13-23 10:49AM
L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM ALARM 11-13-23 9:37AM
L12 ANNULAR SUPREME ANNULAR FUEL ALARM CLEAR 11-13-23 9:37AM
L12 ANNULAR SUPREME ANNULAR FUEL ALARM ALARM 11-13-23 9:36AM
L11 ANNULAR UNL ANNULAR SENSOR OUT ALARM ALARM 11-13-23 9:03AM
L 2 OTHER SUPREME STP FUEL ALARM CLEAR 11-13-23 8:24AM
L 2 OTHER SUPREME STP FUEL ALARM ALARM 11-13-23 8:24AM
OTHER ISD GROSS PRES FAIL CLEAR 10-30-23 8:20AM
OTHER ISD GROSS PRES FAIL ALARM 10-30-23 8:02AM
D 8 OTHER AUTODIAL FAILURE CLEAR 10-16-23 8:40AM
D 8 OTHER AUTODIAL FAILURE ALARM 10-16-23 8:28AM
D 8 OTHER AUTODIAL FAILURE CLEAR 10-16-23 8:28AM
T 1 TANK UNLEADED NORTH OVERFILL ALARM CLEAR 10-16-23 3:18AM
D 8 OTHER AUTODIAL FAILURE ALARM 10-16-23 3:14AM
D 8 OTHER AUTODIAL FAILURE CLEAR 10-16-23 3:14AM
T 1 TANK UNLEADED NORTH OVERFILL ALARM ALARM 10-16-23 3:13AM
T 1 TANK UNLEADED NORTH OVERFILL ALARM CLEAR 10-16-23 3:08AM
T 1 TANK UNLEADED NORTH OVERFILL ALARM ALARM 10-16-23 2:58AM
T 1 TANK UNLEADED NORTH OVERFILL ALARM CLEAR 10-16-23 2:57AM
I11200
FEB 8, 2024 9:05 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PAPER OUT ALARM 2-08-24 9:04AM
SYSTEM PRINTER ERROR ALARM 2-08-24 9:04AM
SYSTEM PRINTER ERROR CLEAR 12-27-23 9:14AM
SYSTEM PAPER OUT CLEAR 12-27-23 9:14AM
SYSTEM PAPER OUT ALARM 12-27-23 9:14AM
SYSTEM PRINTER ERROR ALARM 12-27-23 9:14AM
SYSTEM PRINTER ERROR CLEAR 12-27-23 9:14AM
SYSTEM PAPER OUT CLEAR 12-27-23 9:14AM
SYSTEM PAPER OUT ALARM 12-27-23 9:12AM
SYSTEM PRINTER ERROR ALARM 12-27-23 9:12AM
OTHER ISD DEGRD PRES WARN CLEAR 12-08-23 7:52AM
OTHER ISD DEGRD PRES WARN ALARM 12-03-23 8:04AM
OTHER ISD GROSS PRES WARN CLEAR 11-07-23 1:07PM
SYSTEM PRINTER ERROR CLEAR 11-06-23 8:08AM
SYSTEM PAPER OUT CLEAR 11-06-23 8:08AM
SYSTEM PRINTER ERROR ALARM 11-06-23 8:07AM
SYSTEM PAPER OUT ALARM 11-06-23 8:07AM
SYSTEM PRINTER ERROR CLEAR 11-06-23 8:07AM
SYSTEM PAPER OUT CLEAR 11-06-23 8:07AM
SYSTEM PRINTER ERROR ALARM 11-06-23 8:07AM
SYSTEM PAPER OUT ALARM 11-06-23 8:07AM
OTHER ISD GROSS PRES WARN ALARM 11-06-23 8:03AM
OTHER ISD GROSS PRES WARN CLEAR 10-30-23 8:00AM
OTHER ISD GROSS PRES WARN ALARM 10-23-23 8:03AM
OTHER ISD GROSS PRES WARN CLEAR 10-16-23 8:35AM
OTHER ISD GROSS PRES WARN ALARM 10-16-23 8:03AM
T 3 TANK UNLEADED SIPHON HIGH PRODUCT ALARM CLEAR 10-10-23 8:59AM
T 3 TANK UNLEADED SIPHON HIGH PRODUCT ALARM ALARM 10-09-23 5:31PM
OTHER ISD DEGRD PRES WARN CLEAR 10-09-23 8:34AM
OTHER ISD GROSS PRES WARN CLEAR 10-09-23 8:34AM
OTHER ISD DEGRD PRES WARN ALARM 10-07-23 8:03AM
OTHER ISD GROSS PRES WARN ALARM 10-04-23 8:04AM
SYSTEM PRINTER ERROR CLEAR 9-18-23 9:46AM
SYSTEM PAPER OUT CLEAR 9-18-23 9:46AM
SYSTEM PAPER OUT ALARM 9-18-23 9:46AM
SYSTEM PRINTER ERROR ALARM 9-18-23 9:46AM
SYSTEM PRINTER ERROR CLEAR 9-18-23 9:46AM
SYSTEM PAPER OUT CLEAR 9-18-23 9:46AM
SYSTEM PRINTER ERROR ALARM 9-18-23 9:42AM
SYSTEM PAPER OUT ALARM 9-18-23 9:42AM
SYSTEM PRINTER ERROR CLEAR 9-07-23 10:12PM
SYSTEM PAPER OUT CLEAR 9-07-23 10:12PM
SYSTEM PRINTER ERROR ALARM 9-07-23 10:11PM
SYSTEM PAPER OUT ALARM 9-07-23 10:11PM
SYSTEM PRINTER ERROR CLEAR 8-30-23 6:27PM
SYSTEM PAPER OUT CLEAR 8-30-23 6:27PM
SYSTEM PRINTER ERROR ALARM 8-30-23 6:26PM
SYSTEM PAPER OUT ALARM 8-30-23 6:26PM
SYSTEM PRINTER ERROR CLEAR 8-30-23 6:26PM
SYSTEM PAPER OUT CLEAR 8-30-23 6:26PM
I20600
FEB 8, 2024 9:05 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
TANK ALARM HISTORY
TANK 1 UNLEADED NORTH
OVERFILL ALARM OCT 16, 2023 3:13 AM
OCT 16, 2023 2:58 AM
OCT 16, 2023 2:54 AM
SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM
HIGH PRODUCT ALARM APR 12, 2023 8:54 PM
INVALID FUEL LEVEL MAY 13, 2023 3:06 PM
DEC 20, 2021 12:31 PM
PROBE OUT OCT 7, 2020 8:11 AM
LOW TEMP WARNING OCT 7, 2020 3:49 PM
TANK 2 SUPREME
HIGH WATER ALARM JUL 27, 2023 3:37 PM
INVALID FUEL LEVEL JUL 28, 2023 1:23 PM
JUL 27, 2023 4:51 PM
MAY 13, 2023 1:28 PM
PROBE OUT OCT 7, 2020 8:11 AM
HIGH WATER WARNING JUL 27, 2023 3:37 PM
TANK 3 UNLEADED SIPHON
OVERFILL ALARM OCT 9, 2023 5:30 PM
APR 12, 2023 8:58 PM
SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM
HIGH PRODUCT ALARM OCT 9, 2023 5:31 PM
PROBE OUT OCT 7, 2020 8:13 AM
TANK 4 UNLEADED SOUTH
SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM
INVALID FUEL LEVEL MAY 13, 2023 3:19 PM
JAN 9, 2022 1:55 PM
NOV 21, 2020 11:42 AM
PROBE OUT OCT 7, 2020 8:14 AM
TANK 5 DIESEL
INVALID FUEL LEVEL JUL 10, 2023 3:26 PM
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
FEB 8, 2024 9:05 AM
I30200
FEB 8, 2024 9:05 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNLEADED NORTH STP
APR 25, 2023 8:58 AM SETUP DATA WARNING
APR 25, 2023 7:38 AM SETUP DATA WARNING
FEB 21, 2023 9:44 AM SENSOR OUT ALARM
2 SUPREME STP
NOV 13, 2023 2:07 PM FUEL ALARM
NOV 13, 2023 8:24 AM FUEL ALARM
APR 25, 2023 8:58 AM SETUP DATA WARNING
3 UNLEADED SIPHON STP
APR 25, 2023 8:58 AM SETUP DATA WARNING
APR 25, 2023 8:47 AM SETUP DATA WARNING
APR 25, 2023 7:38 AM SETUP DATA WARNING
4 UNLEADED SOUTH STP
APR 25, 2023 8:58 AM SETUP DATA WARNING
APR 25, 2023 8:47 AM SETUP DATA WARNING
APR 25, 2023 7:38 AM SETUP DATA WARNING
5 DIESEL STP
APR 25, 2023 8:58 AM SETUP DATA WARNING
APR 25, 2023 7:38 AM SETUP DATA WARNING
FEB 21, 2023 9:42 AM SENSOR OUT ALARM
6 UNL NORTH FILL
APR 25, 2023 8:58 AM SETUP DATA WARNING
APR 25, 2023 7:38 AM SETUP DATA WARNING
FEB 21, 2023 9:42 AM SENSOR OUT ALARM
7 SUPREME FILL
NOV 13, 2023 12:32 PM FUEL ALARM
APR 25, 2023 8:58 AM SETUP DATA WARNING
APR 25, 2023 7:38 AM SETUP DATA WARNING
8 UNL SIPHON FILL
JAN 1, 2024 11:02 AM FUEL ALARM
DEC 26, 2023 9:15 AM FUEL ALARM
DEC 26, 2023 9:15 AM FUEL ALARM
9 UNL SOUTH FILL
FEB 21, 2023 9:27 AM SENSOR OUT ALARM
FEB 21, 2023 9:10 AM FUEL ALARM
FEB 23, 2022 9:30 AM SENSOR OUT ALARM
10 DIESEL FILL
FEB 21, 2023 9:27 AM SENSOR OUT ALARM
FEB 21, 2023 9:09 AM FUEL ALARM
FEB 23, 2022 9:30 AM SENSOR OUT ALARM
11 UNL ANNULAR
NOV 13, 2023 9:03 AM SENSOR OUT ALARM
FEB 21, 2023 9:47 AM FUEL ALARM
FEB 21, 2023 9:27 AM SENSOR OUT ALARM
12 SUPREME ANNULAR
NOV 14, 2023 9:51 AM FUEL ALARM
NOV 13, 2023 3:48 PM FUEL ALARM
NOV 13, 2023 3:48 PM SENSOR OUT ALARM
13 UNL SIPHON ANNULAR
NOV 13, 2023 11:10 AM SENSOR OUT ALARM
FEB 21, 2023 9:35 AM FUEL ALARM
FEB 21, 2023 9:27 AM SENSOR OUT ALARM
14 UNL SOUTH ANNULAR
NOV 13, 2023 12:32 PM SENSOR OUT ALARM
FEB 21, 2023 9:29 AM FUEL ALARM
FEB 21, 2023 9:27 AM SENSOR OUT ALARM
15 DIESEL ANNULAR
NOV 13, 2023 3:17 PM SENSOR OUT ALARM
FEB 21, 2023 9:29 AM FUEL ALARM
FEB 21, 2023 9:27 AM SENSOR OUT ALARM
I31600
FEB 8, 2024 9:05 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 FM 1-2
2 FM 3-4
3 FM 5-6
4 FM 7-8
5 FM 9-10
OCT 2, 2020 8:40 AM COMMUNICATION ALARM
SEP 16, 2020 3:58 PM COMMUNICATION ALARM
SEP 10, 2020 6:38 PM COMMUNICATION ALARM
6 FM 11-12
7 PS 7-8
I40200
FEB 8, 2024 9:05 AM
I40300
FEB 8, 2024 9:05 AM
I34200
FEB 8, 2024 9:05 AM
I34700
FEB 8, 2024 9:05 AM
IV0100
FEB 8, 2024 9:05 AM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-12-07 08:04:19 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.34
23-12-06 08:04:25 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37
23-12-05 08:04:27 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37
23-12-04 08:04:24 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.36
23-12-03 08:04:29 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37
23-11-07 08:04:07 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.06
23-11-06 08:03:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07
23-10-29 08:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16
23-10-28 08:02:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16
23-10-27 08:02:46 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.31
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-10-30 08:02:37 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.13
22-12-05 08:03:18 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 126.81
22-11-22 08:02:53 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 153.95
22-11-07 08:03:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 67.28
22-10-04 08:04:39 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 87.23
22-09-21 08:03:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 86.74
22-08-02 08:02:51 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 115.69
22-07-20 08:03:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.98
22-07-07 08:04:03 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.15
21-12-06 08:03:24 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.16
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-12-08 07:52:01 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-07 13:07:50 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-10-30 08:20:08 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-10-30 08:18:06 PUMPS MANUALLY RE-ENABLED
23-10-30 08:02:37 CONTAINMENT GROSS DISABLED DISPENSERS
23-10-29 01:00:00 TIME CHANGE DETECTED AT: 23-10-29 02:00:13
23-10-16 08:35:30 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-10-09 08:34:10 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-09-30 08:03:16 READINESS ISD:PP EVR:PP ISD & EVR READY
23-09-30 04:59:51 READINESS ISD:PP EVR:NN EVR READINESS PENDING
Post Alarm History
Responses Received:
I10200
FEB 8, 2024 1:14 PM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 507996 511214
2 4 PROBE / G.T. 163935 164139
3 4 PROBE / G.T. 163913 164160
4 INTERSTITIAL BD 201668 201940
5 INTERSTITIAL BD 201495 201875
6 UNUSED 9743067 9862448
7 UNUSED 9729335 9825860
8 UNUSED 9745647 9834551
9 RELAY BOARD 15007 14994
10 STP SENSE BOARD 33240 33265
11 UNUSED 9729983 9832908
12 UNUSED 9729067 9816489
13 UNUSED 9734726 9840800
14 UNUSED 9732313 9824155
15 UNUSED 9737618 9829772
16 UNUSED 9718810 9823151
COMM 1 RS232 SERIAL BD 14986 15055
COMM 2 RS232 SERIAL BD 15091 15076
COMM 3 ELEC DISP INT. 101121 101358
COMM 4 UNUSED 9732542 9824893
COMM 5 SERIAL SAT BD 479659 481019
COMM 6 UNUSED 9730960 9823336
I90200
FEB 8, 2024 1:14 PM
SOFTWARE REVISION LEVEL
VERSION 336.01
SOFTWARE# 346336-100-B
CREATED - 20.04.26.20.30
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
FEB 8, 2024 1:14 PM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:34AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:34AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:34AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:33AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:33AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:32AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:32AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:31AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:29AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:29AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 11:29AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 11:28AM
L14 ANNULAR UNL SOUTH ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L11 ANNULAR UNL ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L15 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L13 ANNULAR UNL SIPHON ANNULAR SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 4 OTHER UNLEADED SOUTH STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 2 OTHER SUPREME STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L10 OTHER DIESEL FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 9 OTHER UNL SOUTH FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 6 OTHER UNL NORTH FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 5 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 8 OTHER UNL SIPHON FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 3 OTHER UNLEADED SIPHON STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 7 OTHER SUPREME FILL SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 1 OTHER UNLEADED NORTH STP SENSOR OUT ALARM CLEAR 2-08-24 10:52AM
L 2 OTHER SUPREME STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L 6 OTHER UNL NORTH FILL SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L 5 STP SUMP DIESEL STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L 8 OTHER UNL SIPHON FILL SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L 7 OTHER SUPREME FILL SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L 4 OTHER UNLEADED SOUTH STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L 3 OTHER UNLEADED SIPHON STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L 1 OTHER UNLEADED NORTH STP SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L15 ANNULAR DIESEL ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L14 ANNULAR UNL SOUTH ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L12 ANNULAR SUPREME ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L11 ANNULAR UNL ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L13 ANNULAR UNL SIPHON ANNULAR SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L10 OTHER DIESEL FILL SENSOR OUT ALARM ALARM 2-08-24 10:51AM
L 9 OTHER UNL SOUTH FILL SENSOR OUT ALARM ALARM 2-08-24 10:50AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 10:46AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 10:45AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 10:45AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 10:44AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 10:43AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 10:43AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM CLEAR 2-08-24 10:42AM
L13 ANNULAR UNL SIPHON ANNULAR FUEL ALARM ALARM 2-08-24 10:41AM
I11200
FEB 8, 2024 1:14 PM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 2-08-24 9:14AM
SYSTEM PAPER OUT CLEAR 2-08-24 9:14AM
SYSTEM PAPER OUT ALARM 2-08-24 9:04AM
SYSTEM PRINTER ERROR ALARM 2-08-24 9:04AM
SYSTEM PRINTER ERROR CLEAR 12-27-23 9:14AM
SYSTEM PAPER OUT CLEAR 12-27-23 9:14AM
SYSTEM PAPER OUT ALARM 12-27-23 9:14AM
SYSTEM PRINTER ERROR ALARM 12-27-23 9:14AM
SYSTEM PRINTER ERROR CLEAR 12-27-23 9:14AM
SYSTEM PAPER OUT CLEAR 12-27-23 9:14AM
SYSTEM PAPER OUT ALARM 12-27-23 9:12AM
SYSTEM PRINTER ERROR ALARM 12-27-23 9:12AM
OTHER ISD DEGRD PRES WARN CLEAR 12-08-23 7:52AM
OTHER ISD DEGRD PRES WARN ALARM 12-03-23 8:04AM
OTHER ISD GROSS PRES WARN CLEAR 11-07-23 1:07PM
SYSTEM PRINTER ERROR CLEAR 11-06-23 8:08AM
SYSTEM PAPER OUT CLEAR 11-06-23 8:08AM
SYSTEM PRINTER ERROR ALARM 11-06-23 8:07AM
SYSTEM PAPER OUT ALARM 11-06-23 8:07AM
SYSTEM PRINTER ERROR CLEAR 11-06-23 8:07AM
SYSTEM PAPER OUT CLEAR 11-06-23 8:07AM
SYSTEM PRINTER ERROR ALARM 11-06-23 8:07AM
SYSTEM PAPER OUT ALARM 11-06-23 8:07AM
OTHER ISD GROSS PRES WARN ALARM 11-06-23 8:03AM
OTHER ISD GROSS PRES WARN CLEAR 10-30-23 8:00AM
OTHER ISD GROSS PRES WARN ALARM 10-23-23 8:03AM
OTHER ISD GROSS PRES WARN CLEAR 10-16-23 8:35AM
OTHER ISD GROSS PRES WARN ALARM 10-16-23 8:03AM
T 3 TANK UNLEADED SIPHON HIGH PRODUCT ALARM CLEAR 10-10-23 8:59AM
T 3 TANK UNLEADED SIPHON HIGH PRODUCT ALARM ALARM 10-09-23 5:31PM
OTHER ISD DEGRD PRES WARN CLEAR 10-09-23 8:34AM
OTHER ISD GROSS PRES WARN CLEAR 10-09-23 8:34AM
OTHER ISD DEGRD PRES WARN ALARM 10-07-23 8:03AM
OTHER ISD GROSS PRES WARN ALARM 10-04-23 8:04AM
SYSTEM PRINTER ERROR CLEAR 9-18-23 9:46AM
SYSTEM PAPER OUT CLEAR 9-18-23 9:46AM
SYSTEM PAPER OUT ALARM 9-18-23 9:46AM
SYSTEM PRINTER ERROR ALARM 9-18-23 9:46AM
SYSTEM PRINTER ERROR CLEAR 9-18-23 9:46AM
SYSTEM PAPER OUT CLEAR 9-18-23 9:46AM
SYSTEM PRINTER ERROR ALARM 9-18-23 9:42AM
SYSTEM PAPER OUT ALARM 9-18-23 9:42AM
SYSTEM PRINTER ERROR CLEAR 9-07-23 10:12PM
SYSTEM PAPER OUT CLEAR 9-07-23 10:12PM
SYSTEM PRINTER ERROR ALARM 9-07-23 10:11PM
SYSTEM PAPER OUT ALARM 9-07-23 10:11PM
SYSTEM PRINTER ERROR CLEAR 8-30-23 6:27PM
SYSTEM PAPER OUT CLEAR 8-30-23 6:27PM
SYSTEM PRINTER ERROR ALARM 8-30-23 6:26PM
SYSTEM PAPER OUT ALARM 8-30-23 6:26PM
I20600
FEB 8, 2024 1:14 PM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
TANK ALARM HISTORY
TANK 1 UNLEADED NORTH
OVERFILL ALARM OCT 16, 2023 3:13 AM
OCT 16, 2023 2:58 AM
OCT 16, 2023 2:54 AM
SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM
HIGH PRODUCT ALARM APR 12, 2023 8:54 PM
INVALID FUEL LEVEL MAY 13, 2023 3:06 PM
DEC 20, 2021 12:31 PM
PROBE OUT OCT 7, 2020 8:11 AM
LOW TEMP WARNING OCT 7, 2020 3:49 PM
TANK 2 SUPREME
HIGH WATER ALARM JUL 27, 2023 3:37 PM
INVALID FUEL LEVEL JUL 28, 2023 1:23 PM
JUL 27, 2023 4:51 PM
MAY 13, 2023 1:28 PM
PROBE OUT OCT 7, 2020 8:11 AM
HIGH WATER WARNING JUL 27, 2023 3:37 PM
TANK 3 UNLEADED SIPHON
OVERFILL ALARM OCT 9, 2023 5:30 PM
APR 12, 2023 8:58 PM
SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM
HIGH PRODUCT ALARM OCT 9, 2023 5:31 PM
PROBE OUT OCT 7, 2020 8:13 AM
TANK 4 UNLEADED SOUTH
SUDDEN LOSS ALARM SEP 16, 2020 1:22 PM
INVALID FUEL LEVEL MAY 13, 2023 3:19 PM
JAN 9, 2022 1:55 PM
NOV 21, 2020 11:42 AM
PROBE OUT OCT 7, 2020 8:14 AM
TANK 5 DIESEL
INVALID FUEL LEVEL JUL 10, 2023 3:26 PM
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
FEB 8, 2024 1:14 PM
I30200
FEB 8, 2024 1:14 PM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 UNLEADED NORTH STP
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:20 AM FUEL ALARM
APR 25, 2023 8:58 AM SETUP DATA WARNING
2 SUPREME STP
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 10:17 AM SENSOR OUT ALARM
FEB 8, 2024 10:17 AM FUEL ALARM
3 UNLEADED SIPHON STP
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:26 AM FUEL ALARM
APR 25, 2023 8:58 AM SETUP DATA WARNING
4 UNLEADED SOUTH STP
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:27 AM FUEL ALARM
APR 25, 2023 8:58 AM SETUP DATA WARNING
5 DIESEL STP
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:28 AM FUEL ALARM
APR 25, 2023 8:58 AM SETUP DATA WARNING
6 UNL NORTH FILL
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:30 AM FUEL ALARM
APR 25, 2023 8:58 AM SETUP DATA WARNING
7 SUPREME FILL
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:31 AM FUEL ALARM
NOV 13, 2023 12:32 PM FUEL ALARM
8 UNL SIPHON FILL
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:31 AM FUEL ALARM
JAN 1, 2024 11:02 AM FUEL ALARM
9 UNL SOUTH FILL
FEB 8, 2024 10:50 AM SENSOR OUT ALARM
FEB 8, 2024 9:32 AM FUEL ALARM
FEB 21, 2023 9:27 AM SENSOR OUT ALARM
10 DIESEL FILL
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:33 AM FUEL ALARM
FEB 21, 2023 9:27 AM SENSOR OUT ALARM
11 UNL ANNULAR
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:43 AM FUEL ALARM
FEB 8, 2024 9:42 AM FUEL ALARM
12 SUPREME ANNULAR
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:38 AM FUEL ALARM
FEB 8, 2024 9:38 AM FUEL ALARM
13 UNL SIPHON ANNULAR
FEB 8, 2024 11:34 AM FUEL ALARM
FEB 8, 2024 11:33 AM FUEL ALARM
FEB 8, 2024 11:32 AM FUEL ALARM
14 UNL SOUTH ANNULAR
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 10:03 AM FUEL ALARM
FEB 8, 2024 9:46 AM FUEL ALARM
15 DIESEL ANNULAR
FEB 8, 2024 10:51 AM SENSOR OUT ALARM
FEB 8, 2024 9:55 AM FUEL ALARM
FEB 8, 2024 9:53 AM FUEL ALARM
I31600
FEB 8, 2024 1:14 PM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 FM 1-2
2 FM 3-4
3 FM 5-6
4 FM 7-8
5 FM 9-10
OCT 2, 2020 8:40 AM COMMUNICATION ALARM
SEP 16, 2020 3:58 PM COMMUNICATION ALARM
SEP 10, 2020 6:38 PM COMMUNICATION ALARM
6 FM 11-12
7 PS 7-8
I40200
FEB 8, 2024 1:14 PM
I40300
FEB 8, 2024 1:14 PM
I34200
FEB 8, 2024 1:14 PM
I34700
FEB 8, 2024 1:14 PM
IV0100
FEB 8, 2024 1:14 PM
204121 CALIFORNIA CH
4100 CALIFORNIA AVE
BKRSFLD CA 93309
661-336-0263
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.05
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-12-07 08:04:19 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.34
23-12-06 08:04:25 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37
23-12-05 08:04:27 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37
23-12-04 08:04:24 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.36
23-12-03 08:04:29 CONTAINMENT PRESSURE DEGRADATIONMONTHLY 75% 0.37
23-11-07 08:04:07 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.06
23-11-06 08:03:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.07
23-10-29 08:02:51 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16
23-10-28 08:02:49 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.16
23-10-27 08:02:46 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.31
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-10-30 08:02:37 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 3.13
22-12-05 08:03:18 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 126.81
22-11-22 08:02:53 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 153.95
22-11-07 08:03:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 67.28
22-10-04 08:04:39 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 87.23
22-09-21 08:03:09 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 86.74
22-08-02 08:02:51 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 115.69
22-07-20 08:03:49 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 18.98
22-07-07 08:04:03 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.15
21-12-06 08:03:24 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.16
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-12-08 07:52:01 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-11-07 13:07:50 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-10-30 08:20:08 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-10-30 08:18:06 PUMPS MANUALLY RE-ENABLED
23-10-30 08:02:37 CONTAINMENT GROSS DISABLED DISPENSERS
23-10-29 01:00:00 TIME CHANGE DETECTED AT: 23-10-29 02:00:13
23-10-16 08:35:30 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-10-09 08:34:10 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
23-09-30 08:03:16 READINESS ISD:PP EVR:PP ISD & EVR READY
23-09-30 04:59:51 READINESS ISD:PP EVR:NN EVR READINESS PENDING