HomeMy WebLinkAbout2024 FMCAppendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10901998 01/25/2024
Skyway Liquors
4199 Union Ave Bakersfield 93305
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
VeederRoot TLS-3XX Technician - C32655 10/11/2024
Vaporless Manufacturing Inc. - #5265 10/21/2024
OPW - 1193585 04/14/2025
01/25/2024 6
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
VeederRoot TLS-350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 Dispenser 1-2 UDC
L2 304 Dispenser 1-2 UDC ANN
L3 208 Dispenser 3-4 UDC
L4 304 Dispenser 3-4 UDC ANN
L5 208 Dispenser 5-6 UDC
L6 304 Dispenser 5-6 UDC ANN
L7 208 Dispenser 7-8 UDC
L8 304 Dispenser 7-8 UDC ANN
L9 208 91 STP
L10 304 91 STP Annular
L11 208 91 Fill
L12 304 91 Fill Annular
L13 208 87 STP
L14 304 87 STP Annular
L15 208 87 Fill
L16 304 87 Fill Annular
L17 208 Diesel STP
L18 304 Diesel STP Annular
L19 208 Diesel Fill
L20 304 Diesel Fill Annular
L21 304 Vent Box ANN
L22 208 Vent Box
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
S6 463/464 91 Vacuum Product
S7 463/464 Tank Annular
S8 463/464 91 Vacuum Vent
S9 463/464 87 Vacuum Product
S10 463/464 87 Vacuum Vent
S11 463/464 87 Vacuum Vapor
S12 463/464 Diesel Vacuum Product
S13 463/464 Diesel Vacuum Vent
Underground Storage Tank
Monitoring System Certification Form
Page 4 of 6
7. LINE LEAK DETECTOR TESTING
܆܆ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
܆܆ 3 GPH ܆܆ 0.1 GPH ܆܆ 0.2 GPH Yes No NA
Has the testing apparatus been properly calibrated? ܆܆ ܆܆ ܆܆
For emergency generator tank systems, does the LLD create an audible and visual
alarm when a leak is detected? ܆܆ ܆܆ ܆܆
For mechanical LLDs, does the LLD restrict the flow through the pipe when a
release is detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off when a release is
detected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system is disabled or disconnected? ܆܆ ܆܆ ܆܆
For electronic LLDs, does the turbine automatically shut off if any portion of the
monitoring system malfunctions or fails a tightness test? ܆܆ ܆܆ ܆܆
For electronic LLDs, have all accessible wiring connections been visually inspected
for kinks and breaks? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Were all LLDs confirmed operational within regulatory requirements? ܆܆ ܆܆ ܆܆
LLD ID LLD Model Lines Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Q1 848480-001 87 Unleaded
Q2 848480-001 91 Premium
Q3 848480-001 Diesel
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
91 PNL Fill ANN reservoir cup leaks brine; repairs required. 304 sensor functions properly.
*Return Trip requested to repair and re-test 91 PNL Fill ANN brine reservoir.
APPENDIX C-10
SHEAR VALVE OPERATION INSPECTION )DFLOLW\1DPH2ZQHU$GGUHVV$GGUHVV&LW\6WDWH=LS&RGH&LW\6WDWH=LS&RGH)DFLOLW\,'3KRQH7HVWLQJ&RPSDQ\3KRQH7KLVGDWDVKHHWLVIRULQVSHFWLQJVKHDUYDOYHVORFDWHGLQVLGHGLVSHQVHUV6HH3(,536HFWLRQIRUWKHLQVSHFWLRQSURFHGXUH3URGXFW*UDGH'LVSHQVHU,' 6KHDU9DOYH7\SH3URGXFW9DSRU,VWKHVKHDUYDOYHULJLGO\DQFKRUHGWRWKHGLVSHQVHUER[IUDPHRUGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHVKHDUVHFWLRQSRVLWLRQHGEHWZHHQóLQFKDERYHRUEHORZWKHWRSVXUIDFHRIWKHGLVSHQVHULVODQG"<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R<HV1R,VWKHOHYHUDUPIUHHWRPRYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$'RHVWKHOHYHUDUPVQDSVKXWWKHSRSSHWYDOYH"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$&DQDQ\SURGXFWEHGLVSHQVHGZKHQWKHSURGXFWVKHDUYDOYHLVFORVHG"<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$<HV1R1$$´1RµWR/LQHVRUD´<HVµIRU/LQHLQGLFDWHVDWHVWIDLOXUHTest Results3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLO3DVV)DLOComments:7HVWHU·V1DPHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB7HVWHU·V6LJQDWXUHBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB1ZHVWFR//& Skyway Liquors4199 Union AveBakersfield 109019983-47-8MPDMPDMPDMPD1-25-6ProductProductProductProductBrandon Nunez
Appendix VIII
Underground Storage Tank
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code
Council
Page 1 of 2
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID
Test Date
Facility Name
Facility Address
City
ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Test
Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number
ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting
documentation is attached; and all information contained herein is accurate. I understand
that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
Total # of Pages
10901998 01/25/2024
Skyway Liquors
4199 Union Ave Bakersfield 93305
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Brandon Nunez
1073967
10226373 09/06/2024
OPW - 1193585 04/14/2025
PEI 1200 1 Hour Hydrostatic All Spill Containers
01/25/2024 2
Underground Storage Tank
Spill Container Testing Report Form
Additional copies of this page may be attached.
Page 2 of 2
6. SPILL CONTAINER DETAILS
Test Method Developed by ܆܆ Manufacturer ܆܆ Industry Standard ܆܆ Professional Engineer
Test Type ܆܆ Pressure ܆܆ Vacuum ܆܆ Hydrostatic
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
܆܆ Nonmetallic
܆܆ Other
Is the spill container minimum
capacity five gallons excluding
riser volume?
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
܆܆ Yes
܆܆ No*
Method to keep spill container
empty
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
܆܆ Drain
܆܆ Pump
܆܆ Other
Spill Container Test Results ܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
܆܆ Pass
܆܆ Fail
1 8. COMMENTS
Describe all answers marked “Other,” “No,” or “Fail” and each proposed remedy.
* Mark here if:
Spill containers do not have a minimum capacity of five gallons and require replacement.
T1: 87 UNL
OPW
T2: 91 PNL
OPW
T3: DSL
OPW
Skyway System Setup
Responses Received:
200
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
JAN 25, 2024 8:40 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 REGULAR 87 8684 56.30 0.0 61.2 11396
2 SUPER 91 3166 75.91 0.8 60.5 1863
3 DIESEL 2424 61.21 0.0 64.0 2605
I90500
JAN 25, 2024 8:40 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
JAN 25, 2024 8:40 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
JAN 25, 2024 8:40 AM
SHIFT TIME 1 : DISABLED
I50202
JAN 25, 2024 8:40 AM
SHIFT TIME 2 : DISABLED
I50203
JAN 25, 2024 8:40 AM
SHIFT TIME 3 : DISABLED
I50204
JAN 25, 2024 8:40 AM
SHIFT TIME 4 : DISABLED
I54600
JAN 25, 2024 8:40 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
JAN 25, 2024 8:40 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
JAN 25, 2024 8:40 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
JAN 25, 2024 8:40 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
JAN 25, 2024 8:40 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
JAN 25, 2024 8:40 AM
PRINT TC VOLUMES
ENABLED
I50E00
JAN 25, 2024 8:40 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
JAN 25, 2024 8:40 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
JAN 25, 2024 8:40 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
JAN 25, 2024 8:40 AM
DAYLIGHT SAVING TIME
DISABLED
I51B00
JAN 25, 2024 8:40 AM
I51600
JAN 25, 2024 8:40 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
JAN 25, 2024 8:40 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
JAN 25, 2024 8:40 AM
TANK CHART SECURITY
DISABLED
I5BD00
JAN 25, 2024 8:40 AM
CUSTOM ALARM LABELS
DISABLED
I56000
JAN 25, 2024 8:40 AM
MASS/DENSITY
DISABLED
I88101
JAN 25, 2024 8:40 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
JAN 25, 2024 8:40 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 1 STOP
DATA LENGTH: 8 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
JAN 25, 2024 8:40 AM
I88104
JAN 25, 2024 8:40 AM
I88105
JAN 25, 2024 8:40 AM
I88106
JAN 25, 2024 8:40 AM
I52000
JAN 25, 2024 8:40 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE MAR 11, 2023 DISABLED
2 ON DATE MAR 11, 2023 DISABLED
3 ON DATE MAR 11, 2023 DISABLED
4 ON DATE MAR 11, 2023 DISABLED
5 ON DATE MAR 11, 2023 DISABLED
6 ON DATE MAR 11, 2023 DISABLED
7 ON DATE MAR 11, 2023 DISABLED
8 ON DATE MAR 11, 2023 DISABLED
I60100
JAN 25, 2024 8:41 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 REGULAR 87 ON
2 SUPER 91 ON
3 DIESEL ON
4 OFF
I60200
JAN 25, 2024 8:41 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 REGULAR 87
2 SUPER 91
3 DIESEL
4
I60300
JAN 25, 2024 8:41 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 REGULAR 87 1
2 SUPER 91 2
3 DIESEL 3
4 4
I60900
JAN 25, 2024 8:41 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 REGULAR 87 0.000700
2 SUPER 91 0.000700
3 DIESEL 0.000450
4 0.000000
I60700
JAN 25, 2024 8:41 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 REGULAR 87 126.00
2 SUPER 91 126.00
3 DIESEL 126.00
4 0.00
I60A00
JAN 25, 2024 8:41 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 REGULAR 87
4 PTS 20080 2 SUPER 91 4 PTS 5029 3 DIESEL
1 PT 5029 4 1 PT 0
I60400
JAN 25, 2024 8:41 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 20080
2 SUPER 91 5029
3 DIESEL 5029
4 0
I60500
JAN 25, 2024 8:41 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 20080 16154 10040 3926
2 SUPER 91 5029 4046 2514 983
3 DIESEL 5029 0 0 0
4 0 0 0 0
I60600
JAN 25, 2024 8:41 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 20080 0 0 0
0 16154 0 0
0 0 10040 0
0 0 0 3926
0 0 0 0
2 SUPER 91 5029 0 0 0
0 4046 0 0
0 0 2514 0
0 0 0 983
0 0 0 0
3 DIESEL 5029 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
JAN 25, 2024 8:41 AM
TANK PRODUCT LABEL METER DATA
1 REGULAR 87 NO
2 SUPER 91 NO
3 DIESEL NO
4 NO
I62F00
JAN 25, 2024 8:41 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 REGULAR 87 3.0 IN.
2 SUPER 91 3.0 IN.
3 DIESEL 3.0 IN.
I62700
JAN 25, 2024 8:41 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 REGULAR 87 2.0
2 SUPER 91 2.0
3 DIESEL 2.0
I64200
JAN 25, 2024 8:41 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 REGULAR 87 LOW
2 SUPER 91 LOW
3 DIESEL LOW
I62400
JAN 25, 2024 8:41 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 REGULAR 87 3.0
2 SUPER 91 3.0
3 DIESEL 3.0
I62800
JAN 25, 2024 8:41 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 20080
2 SUPER 91 5029
3 DIESEL 5029
4 0
I62300
JAN 25, 2024 8:41 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 18072
2 SUPER 91 4526
3 DIESEL 4526
4 0
I62200
JAN 25, 2024 8:41 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 19076
2 SUPER 91 4778
3 DIESEL 4778
4 0
I62900
JAN 25, 2024 8:41 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 2008
2 SUPER 91 503
3 DIESEL 503
4 0
I62100
JAN 25, 2024 8:41 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 800
2 SUPER 91 500
3 DIESEL 500
4 0
I62600
JAN 25, 2024 8:41 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 99
2 SUPER 91 99
3 DIESEL 99
4 99
I62500
JAN 25, 2024 8:41 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 99
2 SUPER 91 99
3 DIESEL 99
4 99
I60800
JAN 25, 2024 8:41 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 REGULAR 87 0.00
2 SUPER 91 0.00
3 DIESEL 0.00
4 0.00
I60B00
JAN 25, 2024 8:41 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
JAN 25, 2024 8:41 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 REGULAR 87 0.00
2 SUPER 91 0.00
3 DIESEL 0.00
4 0.00
I61200
JAN 25, 2024 8:41 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 REGULAR 87 NONE NONE
2 SUPER 91 NONE NONE
3 DIESEL NONE NONE
4 NONE NONE
I63600
JAN 25, 2024 8:41 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 0
2 SUPER 91 0
3 DIESEL 0
4 0
I62A00
JAN 25, 2024 8:41 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 0
2 SUPER 91 0
3 DIESEL 0
4 0
I62C00
JAN 25, 2024 8:41 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 REGULAR 87 STANDARD
2 SUPER 91 STANDARD
3 DIESEL STANDARD
4 STANDARD
I62D00
JAN 25, 2024 8:41 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 REGULAR 87 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 SUPER 91 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DIESEL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
JAN 25, 2024 8:41 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 REGULAR 87 OFF OFF
2 SUPER 91 OFF OFF
3 DIESEL OFF OFF
4 OFF OFF
I63000
JAN 25, 2024 8:41 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 REGULAR 87 OFF
2 SUPER 91 OFF
3 DIESEL OFF
4 OFF
I63200
JAN 25, 2024 8:41 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 REGULAR 87 OFF
2 SUPER 91 OFF
3 DIESEL OFF
4 OFF
I61000
JAN 25, 2024 8:41 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 REGULAR 87 3
2 SUPER 91 3
3 DIESEL 3
4 1
I63A00
JAN 25, 2024 8:41 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 REGULAR 87 10.00%
2 SUPER 91 10.00%
3 DIESEL 10.00%
4 10.00%
I61100
JAN 25, 2024 8:41 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
APR 26, 2020
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
JAN 25, 2024 8:41 AM
CSLD PROBABLITY OF DETECTION
I61400
JAN 25, 2024 8:41 AM
CSLD CLIMATE FACTOR
I61600
JAN 25, 2024 8:41 AM
TANK PRODUCT LABEL CAL UPDATE
1 REGULAR 87 IMMEDIATE
2 SUPER 91 IMMEDIATE
3 DIESEL IMMEDIATE
4 IMMEDIATE
I61A00
JAN 25, 2024 8:41 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 REGULAR 87 DISABLED
2 SUPER 91 DISABLED
3 DIESEL DISABLED
4 DISABLED
I61B00
JAN 25, 2024 8:41 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
JAN 25, 2024 8:41 AM
CSLD REPORT ONLY
I62B00
JAN 25, 2024 8:41 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 REGULAR 87 ??? 0, 0
2 SUPER 91 ??? 0, 0
3 DIESEL ??? 0, 0
4 ??? 0, 0
I63300
JAN 25, 2024 8:41 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
JAN 25, 2024 8:41 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 0
2 SUPER 91 0
3 DIESEL 0
4 0
I63500
JAN 25, 2024 8:41 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 REGULAR 87 1
2 SUPER 91 1
3 DIESEL 1
4 1
I63900
JAN 25, 2024 8:41 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 REGULAR 87
END FACTOR: NONE
2 SUPER 91
END FACTOR: NONE
3 DIESEL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
JAN 25, 2024 8:41 AM
PRESSURE LINE LEAK SETUP
Q 1:REGULAR UNL
TYP:2.0/3.0IN FIBERGLASS
2.0IN DIA LEN: 150 FEET
3.0IN DIA LEN: 0 FEET
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE : 0 PSI
T 1:REGULAR 87
DISPENSE MODE:
STANDARD
SENSOR: NON-VENTED
PRESSURE OFFSET: 0.0PSI
MECHANICAL BLENDER: NO
Q 2:SUPER 91
TYP:2.0/3.0IN FIBERGLASS
2.0IN DIA LEN: 150 FEET
3.0IN DIA LEN: 0 FEET
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE : 0 PSI
T 2:SUPER 91
DISPENSE MODE:
STANDARD
SENSOR: NON-VENTED
PRESSURE OFFSET: 0.0PSI
MECHANICAL BLENDER: NO
Q 3:DIESEL
TYP:2.0/3.0IN FIBERGLASS
2.0IN DIA LEN: 150 FEET
3.0IN DIA LEN: 0 FEET
SHUTDOWN RATE: 3.0 GPH
LOW PRESSURE SHUTOFF:NO
LOW PRESSURE : 0 PSI
T 3:DIESEL
DISPENSE MODE:
STANDARD
SENSOR: NON-VENTED
PRESSURE OFFSET: 0.0PSI
MECHANICAL BLENDER: NO
I77700
JAN 25, 2024 8:41 AM
I77800
JAN 25, 2024 8:41 AM
I78C00
JAN 25, 2024 8:41 AM
I78300
JAN 25, 2024 8:41 AM
I78F00
JAN 25, 2024 8:41 AM
PRESSURE LINE LEAK DISPENSE THRESHOLD
LINE LOW PRESSURE
Q 1:REGULAR UNL 0 PSI
Q 2:SUPER 91 0 PSI
Q 3:DIESEL 0 PSI
I78700
JAN 25, 2024 8:41 AM
PRESSURE LLD SETUP REPORT
Q 1:REGULAR UNL
IN-TANK ALARMS
T 1:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 5:FUEL ALARM
L 7:FUEL ALARM
L13:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 5:SHORT ALARM
L 7:SHORT ALARM
L13:SHORT ALARM
SMARTSENSOR ALARMS
s 9:HIGH LIQUID ALARM
s10:HIGH LIQUID ALARM
s11:HIGH LIQUID ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
Q 2:SUPER 91
IN-TANK ALARMS
T 2:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 5:FUEL ALARM
L 7:FUEL ALARM
L 9:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 5:SHORT ALARM
L 7:SHORT ALARM
L 9:SHORT ALARM
SMARTSENSOR ALARMS
s 6:HIGH LIQUID ALARM
s 7:HIGH LIQUID ALARM
s 8:HIGH LIQUID ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
ALL:FLOW COLLECT FAIL
Q 3:DIESEL
IN-TANK ALARMS
T 3:LOW PRODUCT ALARM
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 5:FUEL ALARM
L 7:FUEL ALARM
L17:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 5:SENSOR OUT ALARM
L 7:SENSOR OUT ALARM
L17:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 5:SHORT ALARM
L 7:SHORT ALARM
L17:SHORT ALARM
SMARTSENSOR ALARMS
s12:HIGH LIQUID ALARM
s13:HIGH LIQUID ALARM
I70200
JAN 25, 2024 8:41 AM
LIQUID LABEL
DEVICE LABEL
1 DISP 1-2
2 DISP 1-2 ANN
3 DISP 3-4
4 DISP 3-4 ANN
5 DISP 5-6
6 DISP 5-6 ANN
7 DISP 7-8
8 DISP 7-8 ANN
9 91 STP
10 91 STP ANN
11 91 FILL
12 91 FILL ANN
13 87 STP
14 87 STP ANN
15 87 FILL
16 87 FILL ANN
17 DIESEL STP
18 DSL STP ANN
19 DIESEL FILL
20 DSL FILL ANN
21 VENT BOX ANN
22 VENT BOX
23
24
I70300
JAN 25, 2024 8:41 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 DISP 1-2 TRI-STATE (SINGLE FLOAT)
2 DISP 1-2 ANN TRI-STATE (SINGLE FLOAT)
3 DISP 3-4 TRI-STATE (SINGLE FLOAT)
4 DISP 3-4 ANN TRI-STATE (SINGLE FLOAT)
5 DISP 5-6 TRI-STATE (SINGLE FLOAT)
6 DISP 5-6 ANN TRI-STATE (SINGLE FLOAT)
7 DISP 7-8 TRI-STATE (SINGLE FLOAT)
8 DISP 7-8 ANN TRI-STATE (SINGLE FLOAT)
9 91 STP TRI-STATE (SINGLE FLOAT)
10 91 STP ANN TRI-STATE (SINGLE FLOAT)
11 91 FILL TRI-STATE (SINGLE FLOAT)
12 91 FILL ANN TRI-STATE (SINGLE FLOAT)
13 87 STP TRI-STATE (SINGLE FLOAT)
14 87 STP ANN TRI-STATE (SINGLE FLOAT)
15 87 FILL TRI-STATE (SINGLE FLOAT)
16 87 FILL ANN TRI-STATE (SINGLE FLOAT)
17 DIESEL STP TRI-STATE (SINGLE FLOAT)
18 DSL STP ANN TRI-STATE (SINGLE FLOAT)
19 DIESEL FILL TRI-STATE (SINGLE FLOAT)
20 DSL FILL ANN TRI-STATE (SINGLE FLOAT)
21 VENT BOX ANN TRI-STATE (SINGLE FLOAT)
22 VENT BOX TRI-STATE (SINGLE FLOAT)
23 TRI-STATE (SINGLE FLOAT)
24 TRI-STATE (SINGLE FLOAT)
I70400
JAN 25, 2024 8:41 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 DISP 1-2 DISPENSER PAN
2 DISP 1-2 ANN DISPENSER PAN
3 DISP 3-4 DISPENSER PAN
4 DISP 3-4 ANN DISPENSER PAN
5 DISP 5-6 DISPENSER PAN
6 DISP 5-6 ANN DISPENSER PAN
7 DISP 7-8 DISPENSER PAN
8 DISP 7-8 ANN DISPENSER PAN
9 91 STP STP SUMP
10 91 STP ANN STP SUMP
11 91 FILL PIPING SUMP
12 91 FILL ANN PIPING SUMP
13 87 STP STP SUMP
14 87 STP ANN STP SUMP
15 87 FILL PIPING SUMP
16 87 FILL ANN PIPING SUMP
17 DIESEL STP STP SUMP
18 DSL STP ANN STP SUMP
19 DIESEL FILL PIPING SUMP
20 DSL FILL ANN PIPING SUMP
21 VENT BOX ANN DISPENSER PAN
22 VENT BOX DISPENSER PAN
23 OTHER SENSORS
24 OTHER SENSORS
I74200
JAN 25, 2024 8:41 AM
I74300
JAN 25, 2024 8:41 AM
I74400
JAN 25, 2024 8:41 AM
I74700
JAN 25, 2024 8:41 AM
I74800
JAN 25, 2024 8:41 AM
I74900
JAN 25, 2024 8:41 AM
I7BC00
JAN 25, 2024 8:42 AM
I80200
JAN 25, 2024 8:42 AM
I80300
JAN 25, 2024 8:42 AM
I80400
JAN 25, 2024 8:42 AM
I80700
JAN 25, 2024 8:42 AM
RELAY LABEL
DEVICE LABEL
1 OVER FILL ALARM
2
3
4
I80900
JAN 25, 2024 8:42 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 OVER FILL ALARM NORMALLY OPEN
2 NORMALLY OPEN
3 NORMALLY OPEN
4 NORMALLY OPEN
I80B00
JAN 25, 2024 8:42 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 OVER FILL ALARM NONE
2 NONE
3 NONE
4 NONE
I80A00
JAN 25, 2024 8:42 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 OVER FILL ALARM STANDARD
2 STANDARD
3 STANDARD
4 STANDARD
I80C00
JAN 25, 2024 8:42 AM
I80800
JAN 25, 2024 8:42 AM
RELAY SETUP REPORT
R 1:OVER FILL ALARM
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 2:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 3:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
R 4:
TYPE:
STANDARD
NORMALLY OPEN
TANK #: NONE
- NO ALARM ASSIGNMENTS -
I79000
JAN 25, 2024 8:42 AM
EDIM:1 VR:349867-001-D TD:17.02.14.08.38
I79100
JAN 25, 2024 8:42 AM
I72300
JAN 25, 2024 8:42 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 DISP 1-2FM AIR FLOW METER
02 DISP 3-4FM AIR FLOW METER
03 DISP 5-6FM AIR FLOW METER
04 DISP 7-8FM AIR FLOW METER
05 DISP 1-2PS VAPOR PRESSURE
06 91 VACCUM PRODUCT VAC SENSOR
07 TANK ANN VAC SENSOR
08 91 VACCUM VENT VAC SENSOR
09 87 VACCUM PRODUCT VAC SENSOR
10 87 VACCUM VENT VAC SENSOR
11 87 VACCUM VAPOR VAC SENSOR
12 DIESEL VACCUM PRODUC VAC SENSOR
13 DIESEL VACCUM VENT VAC SENSOR
14 UNKNOWN
15 UNKNOWN
16 ATM P SENSOR ATM P SENSOR
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
JAN 25, 2024 8:42 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
EVR/ISD SETUP
TYPE: BALANCE
IV4F00
JAN 25, 2024 8:42 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
JAN 25, 2024 8:42 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
VAPOR PROCESSOR TYPE
NONE
IV4700
JAN 25, 2024 8:42 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
ASSESSMENT TIME
START TIME: 11:59 PM
TIME DELAY MINUTES: 1
IV5200
JAN 25, 2024 8:42 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
ACCEPT HIGH ORVR: NO
IV4A00
JAN 25, 2024 8:42 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 01 01 01 UU BLEND3
02 02 02 01 UU BLEND3
03 03 03 02 UU BLEND3
04 04 04 02 UU BLEND3
05 05 05 03 UU BLEND3
06 06 06 03 UU BLEND3
07 07 07 04 UU BLEND3
08 08 08 04 UU BLEND3
IV4B00
JAN 25, 2024 8:42 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
01 01 02/01 03/01 09/01 xx/xx
02 01 02/02 03/02 09/02 xx/xx
03 02 02/03 03/03 09/03 xx/xx
04 02 02/04 03/04 09/04 xx/xx
05 03 02/05 03/05 09/05 xx/xx
06 03 02/06 03/06 09/06 xx/xx
07 04 02/07 03/07 09/07 xx/xx
08 04 02/08 03/08 09/08 xx/xx
IV4900
JAN 25, 2024 8:42 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
JAN 25, 2024 8:42 AM
ISD VERSION: 01.06
Skyway Pre Alarm History
Responses Received:
I10200
JAN 25, 2024 8:43 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 UNUSED 9521986 9804044
2 4 PROBE / G.T. 161602 161771
3 INTERSTITIAL BD 200073 200156
4 INTERSTITIAL BD 199932 200017
5 INTERSTITIAL BD 200543 200597
6 PLLD SENSOR BD 3893 3895
7 8SMARTSENSOR BD 39113 39122
8 7SMARTSENSOR BD 505316 505611
9 RELAY BOARD 14916 14940
10 PLLD POWER BD 100056 99469
11 UNUSED 9491041 9688914
12 UNUSED 9471690 9659864
13 UNUSED 9473988 9657882
14 UNUSED 9467252 9653404
15 UNUSED 9471826 9652179
16 UNUSED 9472952 9649840
COMM 1 ELEC DISP INT. 100447 100447
COMM 2 RS232 SERIAL BD 14984 15007
COMM 3 UNUSED 9481873 9661981
COMM 4 UNUSED 9467951 9653671
COMM 5 UNUSED 9465856 9647879
COMM 6 UNUSED 9465000 9647835
I90200
JAN 25, 2024 8:43 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JAN 25, 2024 8:43 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
L10 STP SUMP 91 STP ANN FUEL ALARM ALARM 1-25-24 8:42AM
L 6 DISP PAN DISP 5-6 ANN FUEL ALARM CLEAR 1-16-24 9:12AM
L 6 DISP PAN DISP 5-6 ANN FUEL ALARM ALARM 1-16-24 9:03AM
L 6 DISP PAN DISP 5-6 ANN FUEL ALARM CLEAR 1-15-24 3:12PM
L 6 DISP PAN DISP 5-6 ANN FUEL ALARM ALARM 1-15-24 3:12PM
L 6 DISP PAN DISP 5-6 ANN FUEL ALARM CLEAR 1-15-24 12:10PM
L 6 DISP PAN DISP 5-6 ANN FUEL ALARM ALARM 1-15-24 11:17AM
L 6 DISP PAN DISP 5-6 ANN FUEL ALARM CLEAR 1-15-24 11:03AM
L16 PIPE 87 FILL ANN FUEL ALARM CLEAR 1-09-24 1:16PM
L16 PIPE 87 FILL ANN FUEL ALARM ALARM 1-09-24 1:16PM
L10 STP SUMP 91 STP ANN FUEL ALARM CLEAR 1-09-24 12:07PM
s 7 OTHER TANK ANN NO VACUUM ALARM CLEAR 1-09-24 12:04PM
L10 STP SUMP 91 STP ANN FUEL ALARM ALARM 1-09-24 12:03PM
s 8 OTHER 91 VACCUM VENT NO VACUUM ALARM CLEAR 1-09-24 12:01PM
s 7 OTHER TANK ANN NO VACUUM ALARM ALARM 1-09-24 11:17AM
s 7 OTHER TANK ANN NO VACUUM ALARM CLEAR 1-09-24 11:15AM
s 7 OTHER TANK ANN NO VACUUM ALARM ALARM 1-09-24 10:55AM
s 7 OTHER TANK ANN NO VACUUM ALARM CLEAR 1-09-24 10:35AM
s 7 OTHER TANK ANN NO VACUUM ALARM ALARM 1-09-24 10:34AM
s 7 OTHER TANK ANN NO VACUUM ALARM CLEAR 1-09-24 10:24AM
s 7 OTHER TANK ANN NO VACUUM ALARM ALARM 1-09-24 10:10AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM CLEAR 1-09-24 10:02AM
s 8 OTHER 91 VACCUM VENT HIGH LIQUID ALARM CLEAR 1-09-24 10:02AM
s 6 OTHER 91 VACCUM PRODUCT HIGH LIQUID ALARM CLEAR 1-09-24 10:02AM
s 6 OTHER 91 VACCUM PRODUCT HIGH LIQUID ALARM ALARM 1-09-24 10:01AM
s 8 OTHER 91 VACCUM VENT HIGH LIQUID ALARM ALARM 1-09-24 10:01AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM ALARM 1-09-24 10:01AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM CLEAR 1-09-24 9:33AM
s 7 OTHER TANK ANN HIGH LIQUID ALARM CLEAR 1-09-24 9:33AM
s 7 OTHER TANK ANN HIGH LIQUID ALARM ALARM 1-09-24 9:33AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM ALARM 1-09-24 9:33AM
s 8 OTHER 91 VACCUM VENT NO VACUUM ALARM ALARM 1-09-24 9:31AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM CLEAR 1-09-24 9:29AM
s 8 OTHER 91 VACCUM VENT HIGH LIQUID ALARM CLEAR 1-09-24 9:29AM
s 6 OTHER 91 VACCUM PRODUCT HIGH LIQUID ALARM CLEAR 1-09-24 9:29AM
s 6 OTHER 91 VACCUM PRODUCT HIGH LIQUID ALARM ALARM 1-09-24 9:25AM
s 8 OTHER 91 VACCUM VENT HIGH LIQUID ALARM ALARM 1-09-24 9:25AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM ALARM 1-09-24 9:25AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM CLEAR 1-09-24 9:07AM
s 6 OTHER 91 VACCUM PRODUCT HIGH LIQUID ALARM CLEAR 1-09-24 9:07AM
s 8 OTHER 91 VACCUM VENT HIGH LIQUID ALARM CLEAR 1-09-24 9:07AM
s 6 OTHER 91 VACCUM PRODUCT HIGH LIQUID ALARM ALARM 1-09-24 9:03AM
s 8 OTHER 91 VACCUM VENT HIGH LIQUID ALARM ALARM 1-09-24 9:03AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM ALARM 1-09-24 9:03AM
Q 1 OTHER REGULAR UNL PLLD SHUTDOWN ALARM CLEAR 1-09-24 9:02AM
s11 OTHER 87 VACCUM VAPOR HIGH LIQUID ALARM CLEAR 1-09-24 9:02AM
s10 OTHER 87 VACCUM VENT HIGH LIQUID ALARM CLEAR 1-09-24 9:02AM
s 9 OTHER 87 VACCUM PRODUCT HIGH LIQUID ALARM CLEAR 1-09-24 9:02AM
s11 OTHER 87 VACCUM VAPOR HIGH LIQUID ALARM ALARM 1-09-24 9:01AM
s10 OTHER 87 VACCUM VENT HIGH LIQUID ALARM ALARM 1-09-24 9:01AM
I11200
JAN 25, 2024 8:43 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 1-25-24 4:01AM
SYSTEM PAPER OUT CLEAR 1-25-24 4:01AM
SYSTEM PRINTER ERROR ALARM 1-25-24 3:52AM
SYSTEM PAPER OUT ALARM 1-25-24 3:52AM
SYSTEM PRINTER ERROR CLEAR 1-16-24 4:58PM
SYSTEM PAPER OUT CLEAR 1-16-24 4:58PM
SYSTEM PRINTER ERROR ALARM 1-16-24 4:57PM
SYSTEM PAPER OUT ALARM 1-16-24 4:57PM
SYSTEM PRINTER ERROR CLEAR 1-16-24 4:57PM
SYSTEM PAPER OUT CLEAR 1-16-24 4:57PM
SYSTEM PRINTER ERROR ALARM 1-16-24 4:57PM
SYSTEM PAPER OUT ALARM 1-16-24 4:57PM
SYSTEM PRINTER ERROR CLEAR 1-16-24 4:57PM
SYSTEM PAPER OUT CLEAR 1-16-24 4:57PM
SYSTEM PRINTER ERROR ALARM 1-16-24 4:57PM
SYSTEM PAPER OUT ALARM 1-16-24 4:57PM
T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR 1-05-24 8:44AM
T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM 1-05-24 8:44AM
T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR 12-11-23 5:40PM
T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM 12-11-23 4:51PM
T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR 12-08-23 9:45PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:39PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:39PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:38PM
SYSTEM PAPER OUT ALARM 12-08-23 7:38PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:37PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:37PM
SYSTEM PAPER OUT ALARM 12-08-23 7:37PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:37PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:36PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:36PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:36PM
SYSTEM PAPER OUT ALARM 12-08-23 7:36PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:36PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:36PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:36PM
SYSTEM PAPER OUT ALARM 12-08-23 7:36PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:36PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:36PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:35PM
SYSTEM PAPER OUT ALARM 12-08-23 7:35PM
T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM 12-08-23 6:16PM
T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR 11-28-23 7:46AM
T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM 11-27-23 3:16PM
SYSTEM PRINTER ERROR CLEAR 11-09-23 10:46AM
SYSTEM PAPER OUT CLEAR 11-09-23 10:46AM
SYSTEM PRINTER ERROR ALARM 11-09-23 10:45AM
SYSTEM PAPER OUT ALARM 11-09-23 10:45AM
SYSTEM PRINTER ERROR CLEAR 11-01-23 4:03AM
SYSTEM PRINTER ERROR ALARM 11-01-23 4:03AM
I20600
JAN 25, 2024 8:43 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
TANK ALARM HISTORY
TANK 1 REGULAR 87
HIGH WATER ALARM MAY 17, 2023 5:10 PM
MAY 13, 2023 9:00 PM
LOW PRODUCT ALARM NOV 28, 2023 7:31 AM
AUG 10, 2023 6:20 PM
MAY 13, 2023 3:26 PM
PROBE OUT JAN 5, 2024 8:45 AM
HIGH WATER WARNING MAY 17, 2023 5:10 PM
MAY 13, 2023 9:00 PM
DELIVERY NEEDED JAN 5, 2024 8:44 AM
DEC 11, 2023 4:51 PM
DEC 8, 2023 6:16 PM
TANK 2 SUPER 91
OVERFILL ALARM OCT 9, 2023 7:03 PM
HIGH PRODUCT ALARM OCT 9, 2023 7:06 PM
TANK 3 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JAN 25, 2024 8:43 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1:REGULAR UNL
JAN 9, 2024 9:01 AM PLLD SHUTDOWN ALARM
DEC 28, 2023 12:28 PM PLLD SHUTDOWN ALARM
DEC 28, 2023 10:07 AM PLLD SHUTDOWN ALARM
NOV 28, 2023 7:31 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 11:47 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 11:47 AM GROSS LINE FAIL
NOV 9, 2023 10:41 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 10:27 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 9:54 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 9:51 AM PLLD SHUTDOWN ALARM
Q 2:SUPER 91
JAN 9, 2024 10:01 AM PLLD SHUTDOWN ALARM
JAN 9, 2024 9:33 AM PLLD SHUTDOWN ALARM
JAN 9, 2024 9:25 AM PLLD SHUTDOWN ALARM
JAN 9, 2024 9:03 AM PLLD SHUTDOWN ALARM
DEC 28, 2023 1:38 PM PLLD SHUTDOWN ALARM
DEC 28, 2023 1:08 PM PLLD SHUTDOWN ALARM
DEC 28, 2023 10:02 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 11:56 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 11:56 AM GROSS LINE FAIL
NOV 9, 2023 10:39 AM PLLD SHUTDOWN ALARM
Q 3:DIESEL
NOV 9, 2023 11:38 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 11:38 AM GROSS LINE FAIL
NOV 9, 2023 10:42 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 9:55 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 9:51 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 9:51 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 9:50 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 9:49 AM PLLD SHUTDOWN ALARM
OCT 9, 2023 3:04 PM PLLD SHUTDOWN ALARM
OCT 9, 2023 2:49 PM PLLD SHUTDOWN ALARM
I30200
JAN 25, 2024 8:43 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2
NOV 9, 2023 9:51 AM FUEL ALARM
OCT 9, 2023 2:45 PM FUEL ALARM
JUN 12, 2023 11:48 AM FUEL ALARM
2 DISP 1-2 ANN
NOV 29, 2023 4:46 AM FUEL ALARM
NOV 9, 2023 9:23 AM FUEL ALARM
OCT 9, 2023 2:46 PM FUEL ALARM
3 DISP 3-4
NOV 9, 2023 9:49 AM FUEL ALARM
OCT 9, 2023 2:44 PM FUEL ALARM
JUN 12, 2023 1:38 PM FUEL ALARM
4 DISP 3-4 ANN
NOV 9, 2023 9:20 AM FUEL ALARM
OCT 9, 2023 2:45 PM FUEL ALARM
JUN 12, 2023 1:38 PM FUEL ALARM
5 DISP 5-6
NOV 9, 2023 9:51 AM FUEL ALARM
OCT 9, 2023 2:43 PM FUEL ALARM
OCT 9, 2023 9:43 AM FUEL ALARM
6 DISP 5-6 ANN
JAN 16, 2024 9:03 AM FUEL ALARM
JAN 15, 2024 3:12 PM FUEL ALARM
JAN 15, 2024 11:17 AM FUEL ALARM
7 DISP 7-8
NOV 9, 2023 9:50 AM FUEL ALARM
OCT 9, 2023 2:41 PM FUEL ALARM
JUN 12, 2023 1:40 PM FUEL ALARM
8 DISP 7-8 ANN
NOV 9, 2023 9:20 AM FUEL ALARM
OCT 9, 2023 2:42 PM FUEL ALARM
JUN 12, 2023 1:41 PM FUEL ALARM
9 91 STP
NOV 9, 2023 9:53 AM FUEL ALARM
OCT 9, 2023 2:46 PM FUEL ALARM
OCT 9, 2023 9:39 AM FUEL ALARM
10 91 STP ANN
JAN 25, 2024 8:42 AM FUEL ALARM
JAN 9, 2024 12:03 PM FUEL ALARM
JAN 2, 2024 9:16 AM FUEL ALARM
11 91 FILL
JAN 3, 2024 3:24 AM FUEL ALARM
NOV 9, 2023 9:53 AM FUEL ALARM
OCT 9, 2023 2:47 PM FUEL ALARM
12 91 FILL ANN
NOV 9, 2023 9:30 AM FUEL ALARM
OCT 9, 2023 2:47 PM FUEL ALARM
JUN 12, 2023 11:44 AM FUEL ALARM
13 87 STP
NOV 9, 2023 9:54 AM FUEL ALARM
OCT 9, 2023 2:48 PM FUEL ALARM
JUN 12, 2023 11:42 AM FUEL ALARM
14 87 STP ANN
JAN 2, 2024 9:19 AM FUEL ALARM
NOV 29, 2023 5:16 AM FUEL ALARM
NOV 9, 2023 9:38 AM FUEL ALARM
15 87 FILL
JAN 2, 2024 11:53 AM FUEL ALARM
NOV 9, 2023 9:54 AM FUEL ALARM
OCT 9, 2023 2:48 PM FUEL ALARM
16 87 FILL ANN
JAN 9, 2024 1:16 PM FUEL ALARM
JAN 3, 2024 9:02 AM FUEL ALARM
JAN 2, 2024 1:02 PM FUEL ALARM
17 DIESEL STP
NOV 9, 2023 9:55 AM FUEL ALARM
OCT 9, 2023 2:49 PM FUEL ALARM
JUN 12, 2023 11:15 AM FUEL ALARM
18 DSL STP ANN
NOV 28, 2023 9:54 AM FUEL ALARM
NOV 9, 2023 9:32 AM FUEL ALARM
OCT 9, 2023 2:49 PM FUEL ALARM
19 DIESEL FILL
NOV 9, 2023 9:55 AM FUEL ALARM
OCT 9, 2023 2:50 PM FUEL ALARM
JUN 12, 2023 11:11 AM FUEL ALARM
20 DSL FILL ANN
NOV 9, 2023 9:32 AM FUEL ALARM
OCT 9, 2023 2:50 PM FUEL ALARM
JUN 12, 2023 11:12 AM FUEL ALARM
21 VENT BOX ANN
NOV 9, 2023 9:27 AM FUEL ALARM
OCT 9, 2023 2:52 PM FUEL ALARM
JUN 12, 2023 12:46 PM FUEL ALARM
22 VENT BOX
NOV 9, 2023 9:52 AM FUEL ALARM
OCT 9, 2023 2:52 PM FUEL ALARM
JUN 12, 2023 1:45 PM FUEL ALARM
I31600
JAN 25, 2024 8:44 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2FM
2 DISP 3-4FM
3 DISP 5-6FM
4 DISP 7-8FM
5 DISP 1-2PS
6 91 VACCUM PRODUCT
JAN 9, 2024 10:01 AM HIGH LIQUID ALARM
JAN 9, 2024 9:25 AM HIGH LIQUID ALARM
JAN 9, 2024 9:03 AM HIGH LIQUID ALARM
7 TANK ANN
JAN 9, 2024 11:17 AM NO VACUUM ALARM
JAN 9, 2024 10:55 AM NO VACUUM ALARM
JAN 9, 2024 10:34 AM NO VACUUM ALARM
8 91 VACCUM VENT
JAN 9, 2024 10:01 AM HIGH LIQUID ALARM
JAN 9, 2024 9:31 AM NO VACUUM ALARM
JAN 9, 2024 9:25 AM HIGH LIQUID ALARM
9 87 VACCUM PRODUCT
JAN 9, 2024 9:01 AM HIGH LIQUID ALARM
DEC 28, 2023 12:28 PM HIGH LIQUID ALARM
DEC 28, 2023 10:07 AM HIGH LIQUID ALARM
10 87 VACCUM VENT
JAN 9, 2024 9:01 AM HIGH LIQUID ALARM
DEC 28, 2023 12:28 PM HIGH LIQUID ALARM
DEC 28, 2023 10:07 AM HIGH LIQUID ALARM
11 87 VACCUM VAPOR
JAN 9, 2024 9:01 AM HIGH LIQUID ALARM
DEC 28, 2023 12:28 PM HIGH LIQUID ALARM
NOV 9, 2023 11:07 AM NO VACUUM ALARM
12 DIESEL VACCUM PRODUC
JAN 9, 2024 8:24 AM COMMUNICATION ALARM
NOV 9, 2023 10:42 AM HIGH LIQUID ALARM
NOV 9, 2023 10:42 AM NO VACUUM ALARM
13 DIESEL VACCUM VENT
NOV 9, 2023 10:42 AM HIGH LIQUID ALARM
NOV 9, 2023 10:42 AM NO VACUUM ALARM
OCT 9, 2023 3:04 PM HIGH LIQUID ALARM
16 ATM P SENSOR
I40200
JAN 25, 2024 8:44 AM
I40300
JAN 25, 2024 8:44 AM
I34200
JAN 25, 2024 8:44 AM
I34700
JAN 25, 2024 8:44 AM
IV0100
JAN 25, 2024 8:44 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-10-18 00:01:24 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.05
23-10-17 00:01:32 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.54
23-05-04 00:03:16 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.95
23-05-03 00:02:54 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.77
23-04-24 00:05:36 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.88
23-04-23 00:05:19 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.29
23-04-22 00:04:37 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.20
23-04-16 00:04:20 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.99
23-04-15 00:03:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.96
23-04-14 00:03:46 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.30
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-03-20 00:00:09 SENSOR OUT SELFTEST s 1
23-03-19 00:02:37 SENSOR OUT SELFTEST s 1
23-03-18 00:02:55 SENSOR OUT SELFTEST s 1
23-03-17 00:02:45 SENSOR OUT SELFTEST s 1
23-03-16 00:02:33 SENSOR OUT SELFTEST s 1
23-03-15 00:02:40 SENSOR OUT SELFTEST s 1
23-03-14 00:03:01 SENSOR OUT SELFTEST s 1
23-03-13 00:02:23 SENSOR OUT SELFTEST s 1
23-03-12 00:04:00 SENSOR OUT SELFTEST s 1
23-03-11 00:03:04 SENSOR OUT SELFTEST s 1
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-11-17 00:01:34 READINESS ISD:PP EVR:PP ISD & EVR READY
23-11-16 06:08:35 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-11-16 06:08:35 ISD STARTUP
23-11-15 20:54:21 ISD SHUTDOWN
23-11-10 00:03:05 READINESS ISD:PP EVR:PP ISD & EVR READY
23-11-09 16:31:53 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-11-09 16:31:53 ISD STARTUP
23-11-09 16:31:42 ISD SHUTDOWN
23-11-09 08:32:00 TIME CHANGE DETECTED AT: 23-11-09 09:33:00
23-10-18 04:10:02 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED
Post Alarm History
Responses Received:
I10200
JAN 25, 2024 11:15 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 UNUSED 9521986 9804044
2 4 PROBE / G.T. 161602 161771
3 INTERSTITIAL BD 200073 200156
4 INTERSTITIAL BD 199932 200017
5 INTERSTITIAL BD 200543 200597
6 PLLD SENSOR BD 3893 3895
7 8SMARTSENSOR BD 39113 39122
8 7SMARTSENSOR BD 505316 505611
9 RELAY BOARD 14916 14940
10 PLLD POWER BD 100056 99469
11 UNUSED 9491041 9688914
12 UNUSED 9471690 9659864
13 UNUSED 9473988 9657882
14 UNUSED 9467252 9653404
15 UNUSED 9471826 9652179
16 UNUSED 9472952 9649840
COMM 1 ELEC DISP INT. 100447 100447
COMM 2 RS232 SERIAL BD 14984 15007
COMM 3 UNUSED 9481873 9661981
COMM 4 UNUSED 9467951 9653671
COMM 5 UNUSED 9465856 9647879
COMM 6 UNUSED 9465000 9647835
I90200
JAN 25, 2024 11:15 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
JAN 25, 2024 11:15 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
Q 1 OTHER REGULAR UNL PLLD SHUTDOWN ALARM CLEAR 1-25-24 10:22AM
Q 1 OTHER REGULAR UNL GROSS LINE FAIL CLEAR 1-25-24 10:22AM
L 6 DISP PAN DISP 5-6 ANN FUEL ALARM CLEAR 1-25-24 10:21AM
L 6 DISP PAN DISP 5-6 ANN FUEL ALARM ALARM 1-25-24 10:21AM
Q 1 OTHER REGULAR UNL PLLD SHUTDOWN ALARM ALARM 1-25-24 10:20AM
Q 1 OTHER REGULAR UNL GROSS LINE FAIL ALARM 1-25-24 10:20AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM CLEAR 1-25-24 10:16AM
Q 2 OTHER SUPER 91 GROSS LINE FAIL CLEAR 1-25-24 10:16AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM ALARM 1-25-24 10:15AM
Q 2 OTHER SUPER 91 GROSS LINE FAIL ALARM 1-25-24 10:15AM
Q 3 OTHER DIESEL PLLD SHUTDOWN ALARM CLEAR 1-25-24 10:07AM
Q 3 OTHER DIESEL GROSS LINE FAIL CLEAR 1-25-24 10:07AM
Q 3 OTHER DIESEL PLLD SHUTDOWN ALARM ALARM 1-25-24 10:06AM
Q 3 OTHER DIESEL GROSS LINE FAIL ALARM 1-25-24 10:06AM
L 6 DISP PAN DISP 5-6 ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L 2 DISP PAN DISP 1-2 ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L 8 DISP PAN DISP 7-8 ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
Q 3 OTHER DIESEL PLLD SHUTDOWN ALARM CLEAR 1-25-24 9:49AM
Q 2 OTHER SUPER 91 PLLD SHUTDOWN ALARM CLEAR 1-25-24 9:49AM
Q 1 OTHER REGULAR UNL PLLD SHUTDOWN ALARM CLEAR 1-25-24 9:49AM
L 7 DISP PAN DISP 7-8 SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L 5 DISP PAN DISP 5-6 SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L 4 DISP PAN DISP 3-4 ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L 3 DISP PAN DISP 3-4 SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L 1 DISP PAN DISP 1-2 SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L10 STP SUMP 91 STP ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L14 STP SUMP 87 STP ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L11 PIPE 91 FILL SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L 9 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L13 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L16 PIPE 87 FILL ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L15 PIPE 87 FILL SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L12 PIPE 91 FILL ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L18 STP SUMP DSL STP ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L17 STP SUMP DIESEL STP SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L22 DISP PAN VENT BOX SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L21 DISP PAN VENT BOX ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L20 PIPE DSL FILL ANN SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L19 PIPE DIESEL FILL SENSOR OUT ALARM CLEAR 1-25-24 9:49AM
L10 STP SUMP 91 STP ANN SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L16 PIPE 87 FILL ANN SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L15 PIPE 87 FILL SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L 9 STP SUMP 91 STP SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L14 STP SUMP 87 STP ANN SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L13 STP SUMP 87 STP SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L12 PIPE 91 FILL ANN SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L11 PIPE 91 FILL SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L 6 DISP PAN DISP 5-6 ANN SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L 2 DISP PAN DISP 1-2 ANN SENSOR OUT ALARM ALARM 1-25-24 9:48AM
L 8 DISP PAN DISP 7-8 ANN SENSOR OUT ALARM ALARM 1-25-24 9:48AM
I11200
JAN 25, 2024 11:15 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
SYSTEM PRINTER ERROR CLEAR 1-25-24 4:01AM
SYSTEM PAPER OUT CLEAR 1-25-24 4:01AM
SYSTEM PRINTER ERROR ALARM 1-25-24 3:52AM
SYSTEM PAPER OUT ALARM 1-25-24 3:52AM
SYSTEM PRINTER ERROR CLEAR 1-16-24 4:58PM
SYSTEM PAPER OUT CLEAR 1-16-24 4:58PM
SYSTEM PRINTER ERROR ALARM 1-16-24 4:57PM
SYSTEM PAPER OUT ALARM 1-16-24 4:57PM
SYSTEM PRINTER ERROR CLEAR 1-16-24 4:57PM
SYSTEM PAPER OUT CLEAR 1-16-24 4:57PM
SYSTEM PRINTER ERROR ALARM 1-16-24 4:57PM
SYSTEM PAPER OUT ALARM 1-16-24 4:57PM
SYSTEM PRINTER ERROR CLEAR 1-16-24 4:57PM
SYSTEM PAPER OUT CLEAR 1-16-24 4:57PM
SYSTEM PRINTER ERROR ALARM 1-16-24 4:57PM
SYSTEM PAPER OUT ALARM 1-16-24 4:57PM
T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR 1-05-24 8:44AM
T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM 1-05-24 8:44AM
T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR 12-11-23 5:40PM
T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM 12-11-23 4:51PM
T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR 12-08-23 9:45PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:39PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:39PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:38PM
SYSTEM PAPER OUT ALARM 12-08-23 7:38PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:37PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:37PM
SYSTEM PAPER OUT ALARM 12-08-23 7:37PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:37PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:36PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:36PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:36PM
SYSTEM PAPER OUT ALARM 12-08-23 7:36PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:36PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:36PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:36PM
SYSTEM PAPER OUT ALARM 12-08-23 7:36PM
SYSTEM PRINTER ERROR CLEAR 12-08-23 7:36PM
SYSTEM PAPER OUT CLEAR 12-08-23 7:36PM
SYSTEM PRINTER ERROR ALARM 12-08-23 7:35PM
SYSTEM PAPER OUT ALARM 12-08-23 7:35PM
T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM 12-08-23 6:16PM
T 1 TANK REGULAR 87 DELIVERY NEEDED CLEAR 11-28-23 7:46AM
T 1 TANK REGULAR 87 DELIVERY NEEDED ALARM 11-27-23 3:16PM
SYSTEM PRINTER ERROR CLEAR 11-09-23 10:46AM
SYSTEM PAPER OUT CLEAR 11-09-23 10:46AM
SYSTEM PRINTER ERROR ALARM 11-09-23 10:45AM
SYSTEM PAPER OUT ALARM 11-09-23 10:45AM
SYSTEM PRINTER ERROR CLEAR 11-01-23 4:03AM
SYSTEM PRINTER ERROR ALARM 11-01-23 4:03AM
I20600
JAN 25, 2024 11:15 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
TANK ALARM HISTORY
TANK 1 REGULAR 87
HIGH WATER ALARM MAY 17, 2023 5:10 PM
MAY 13, 2023 9:00 PM
LOW PRODUCT ALARM NOV 28, 2023 7:31 AM
AUG 10, 2023 6:20 PM
MAY 13, 2023 3:26 PM
PROBE OUT JAN 5, 2024 8:45 AM
HIGH WATER WARNING MAY 17, 2023 5:10 PM
MAY 13, 2023 9:00 PM
DELIVERY NEEDED JAN 5, 2024 8:44 AM
DEC 11, 2023 4:51 PM
DEC 8, 2023 6:16 PM
TANK 2 SUPER 91
OVERFILL ALARM OCT 9, 2023 7:03 PM
HIGH PRODUCT ALARM OCT 9, 2023 7:06 PM
TANK 3 DIESEL
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
JAN 25, 2024 11:15 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
PRESSURE LINE LEAK ALARM HISTORY REPORT
Q 1:REGULAR UNL
JAN 25, 2024 10:20 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 10:20 AM GROSS LINE FAIL
JAN 25, 2024 9:48 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:36 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:25 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:24 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:23 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:22 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:16 AM PLLD SHUTDOWN ALARM
JAN 9, 2024 9:01 AM PLLD SHUTDOWN ALARM
Q 2:SUPER 91
JAN 25, 2024 10:15 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 10:15 AM GROSS LINE FAIL
JAN 25, 2024 9:48 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:30 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:25 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:24 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:23 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:22 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:14 AM PLLD SHUTDOWN ALARM
JAN 9, 2024 10:01 AM PLLD SHUTDOWN ALARM
Q 3:DIESEL
JAN 25, 2024 10:06 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 10:06 AM GROSS LINE FAIL
JAN 25, 2024 9:47 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:40 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:25 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:24 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:23 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:22 AM PLLD SHUTDOWN ALARM
JAN 25, 2024 9:20 AM PLLD SHUTDOWN ALARM
NOV 9, 2023 11:38 AM PLLD SHUTDOWN ALARM
I30200
JAN 25, 2024 11:15 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:22 AM FUEL ALARM
NOV 9, 2023 9:51 AM FUEL ALARM
2 DISP 1-2 ANN
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:23 AM FUEL ALARM
NOV 29, 2023 4:46 AM FUEL ALARM
3 DISP 3-4
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:23 AM FUEL ALARM
NOV 9, 2023 9:49 AM FUEL ALARM
4 DISP 3-4 ANN
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:23 AM FUEL ALARM
NOV 9, 2023 9:20 AM FUEL ALARM
5 DISP 5-6
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:25 AM FUEL ALARM
NOV 9, 2023 9:51 AM FUEL ALARM
6 DISP 5-6 ANN
JAN 25, 2024 10:21 AM FUEL ALARM
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:26 AM FUEL ALARM
7 DISP 7-8
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:24 AM FUEL ALARM
NOV 9, 2023 9:50 AM FUEL ALARM
8 DISP 7-8 ANN
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:24 AM FUEL ALARM
NOV 9, 2023 9:20 AM FUEL ALARM
9 91 STP
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:14 AM FUEL ALARM
NOV 9, 2023 9:53 AM FUEL ALARM
10 91 STP ANN
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:14 AM FUEL ALARM
JAN 25, 2024 8:58 AM FUEL ALARM
11 91 FILL
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:15 AM FUEL ALARM
JAN 25, 2024 8:47 AM FUEL ALARM
12 91 FILL ANN
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:15 AM FUEL ALARM
NOV 9, 2023 9:30 AM FUEL ALARM
13 87 STP
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:16 AM FUEL ALARM
NOV 9, 2023 9:54 AM FUEL ALARM
14 87 STP ANN
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:16 AM FUEL ALARM
JAN 2, 2024 9:19 AM FUEL ALARM
15 87 FILL
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:18 AM FUEL ALARM
JAN 2, 2024 11:53 AM FUEL ALARM
16 87 FILL ANN
JAN 25, 2024 9:48 AM SENSOR OUT ALARM
JAN 25, 2024 9:18 AM FUEL ALARM
JAN 9, 2024 1:16 PM FUEL ALARM
17 DIESEL STP
JAN 25, 2024 9:47 AM SENSOR OUT ALARM
JAN 25, 2024 9:20 AM FUEL ALARM
NOV 9, 2023 9:55 AM FUEL ALARM
18 DSL STP ANN
JAN 25, 2024 9:47 AM SENSOR OUT ALARM
JAN 25, 2024 9:20 AM FUEL ALARM
NOV 28, 2023 9:54 AM FUEL ALARM
19 DIESEL FILL
JAN 25, 2024 9:46 AM SENSOR OUT ALARM
JAN 25, 2024 9:21 AM FUEL ALARM
NOV 9, 2023 9:55 AM FUEL ALARM
20 DSL FILL ANN
JAN 25, 2024 9:47 AM SENSOR OUT ALARM
JAN 25, 2024 9:21 AM FUEL ALARM
NOV 9, 2023 9:32 AM FUEL ALARM
21 VENT BOX ANN
JAN 25, 2024 9:46 AM SENSOR OUT ALARM
NOV 9, 2023 9:27 AM FUEL ALARM
OCT 9, 2023 2:52 PM FUEL ALARM
22 VENT BOX
JAN 25, 2024 9:47 AM SENSOR OUT ALARM
NOV 9, 2023 9:52 AM FUEL ALARM
OCT 9, 2023 2:52 PM FUEL ALARM
I31600
JAN 25, 2024 11:16 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 DISP 1-2FM
2 DISP 3-4FM
3 DISP 5-6FM
4 DISP 7-8FM
5 DISP 1-2PS
6 91 VACCUM PRODUCT
JAN 25, 2024 9:31 AM NO VACUUM ALARM
JAN 25, 2024 9:30 AM HIGH LIQUID ALARM
JAN 9, 2024 10:01 AM HIGH LIQUID ALARM
7 TANK ANN
JAN 25, 2024 9:32 AM NO VACUUM ALARM
JAN 9, 2024 11:17 AM NO VACUUM ALARM
JAN 9, 2024 10:55 AM NO VACUUM ALARM
8 91 VACCUM VENT
JAN 25, 2024 9:30 AM HIGH LIQUID ALARM
JAN 9, 2024 10:01 AM HIGH LIQUID ALARM
JAN 9, 2024 9:31 AM NO VACUUM ALARM
9 87 VACCUM PRODUCT
JAN 25, 2024 9:36 AM NO VACUUM ALARM
JAN 25, 2024 9:36 AM HIGH LIQUID ALARM
JAN 9, 2024 9:01 AM HIGH LIQUID ALARM
10 87 VACCUM VENT
JAN 25, 2024 9:37 AM NO VACUUM ALARM
JAN 25, 2024 9:36 AM HIGH LIQUID ALARM
JAN 9, 2024 9:01 AM HIGH LIQUID ALARM
11 87 VACCUM VAPOR
JAN 25, 2024 9:38 AM NO VACUUM ALARM
JAN 25, 2024 9:36 AM HIGH LIQUID ALARM
JAN 9, 2024 9:01 AM HIGH LIQUID ALARM
12 DIESEL VACCUM PRODUC
JAN 25, 2024 9:40 AM NO VACUUM ALARM
JAN 25, 2024 9:40 AM HIGH LIQUID ALARM
JAN 9, 2024 8:24 AM COMMUNICATION ALARM
13 DIESEL VACCUM VENT
JAN 25, 2024 9:41 AM NO VACUUM ALARM
JAN 25, 2024 9:40 AM HIGH LIQUID ALARM
NOV 9, 2023 10:42 AM HIGH LIQUID ALARM
16 ATM P SENSOR
I40200
JAN 25, 2024 11:16 AM
I40300
JAN 25, 2024 11:16 AM
I34200
JAN 25, 2024 11:16 AM
I34700
JAN 25, 2024 11:16 AM
IV0100
JAN 25, 2024 11:16 AM
SKYWAY GASOLINE
4199 UNION AVE
BAKESFIEL CA,93305
ISD ALARM STATUS REPORT
EVR TYPE: BALANCE
ISD TYPE: 01.06
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
23-10-18 00:01:24 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 2.05
23-10-17 00:01:32 CONTAINMENT GROSS OVER PRESSURE WEEKLY 95% 1.54
23-05-04 00:03:16 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.95
23-05-03 00:02:54 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.77
23-04-24 00:05:36 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 12.88
23-04-23 00:05:19 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.29
23-04-22 00:04:37 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.20
23-04-16 00:04:20 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 14.99
23-04-15 00:03:38 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.96
23-04-14 00:03:46 VAPOR CONTAINMENT LEAKAGE CFH@2 INCHES WC 13.30
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
23-03-20 00:00:09 SENSOR OUT SELFTEST s 1
23-03-19 00:02:37 SENSOR OUT SELFTEST s 1
23-03-18 00:02:55 SENSOR OUT SELFTEST s 1
23-03-17 00:02:45 SENSOR OUT SELFTEST s 1
23-03-16 00:02:33 SENSOR OUT SELFTEST s 1
23-03-15 00:02:40 SENSOR OUT SELFTEST s 1
23-03-14 00:03:01 SENSOR OUT SELFTEST s 1
23-03-13 00:02:23 SENSOR OUT SELFTEST s 1
23-03-12 00:04:00 SENSOR OUT SELFTEST s 1
23-03-11 00:03:04 SENSOR OUT SELFTEST s 1
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
23-11-17 00:01:34 READINESS ISD:PP EVR:PP ISD & EVR READY
23-11-16 06:08:35 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-11-16 06:08:35 ISD STARTUP
23-11-15 20:54:21 ISD SHUTDOWN
23-11-10 00:03:05 READINESS ISD:PP EVR:PP ISD & EVR READY
23-11-09 16:31:53 READINESS ISD:PP EVR:NN EVR READINESS PENDING
23-11-09 16:31:53 ISD STARTUP
23-11-09 16:31:42 ISD SHUTDOWN
23-11-09 08:32:00 TIME CHANGE DETECTED AT: 23-11-09 09:33:00
23-10-18 04:10:02 CONTAINMENT GROSS & DEGRD TEST MANUALLY CLEARED