HomeMy WebLinkAboutEMC 2024-2Appendix VI
Underground Storage Tank
Monitoring System Certification Form
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification,
ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, SW = Single-
Walled, UDC = Under-Dispenser Containment, UST = Underground Storage Tank,
VPH = Vacuum/Pressure/Hydrostatic
Page 1 of 6
TYPE OF ACTION ܆܆ Installation ܆ Repair ܆ 12 Month
1. FACILITY INFORMATION
CERS ID Certification Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that the monitoring system is operational in accordance with California Code
of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting
documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date Total # of Pages
10159161 03/04/24
Jaco #7721 Fastrip #22 (North)
4013 S Union Ave Bakersfield 93307
Nwestco LLC (800) 339-9930
2209 Zeus Court, Bakersfield, CA 93308
Mark Fisher
1073967
10278702 03/10/25
Veeder Root - C33847 07/24/25
03/04/24 5
Underground Storage Tank
Monitoring System Certification Form
Page 2 of 6
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Model of Monitoring System
Control Panel
Software Version Installed
Attach the post-certification reports if the monitoring system is capable of generating
either; ܆܆Monitoring System Set-up ܆܆ Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer’s specifications? ܆܆܆܆
Secondary containment systems are free of damage, debris, or liquid? ܆܆܆܆
Are the audible and visual alarms operational? ܆܆܆܆
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual
buildup on floats; and 2) tested for functionality and confirmed operational? ܆܆܆܆܆܆
Are all sensors installed to detect a release at the earliest opportunity in the
secondary containment? ܆܆܆܆܆܆
The monitoring system set-up was reviewed, and proper settings confirmed? ܆܆܆܆܆܆
Was the monitoring control panel’s backup battery visually inspected, functionally
tested, and confirmed operational? ܆܆܆܆܆܆
Does the flow of fuel stop at the dispenser if a release is detected in the under-
dispenser containment? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system fails to operate or is electrically disconnected? ܆܆܆܆܆܆
Does the turbine automatically shut down if the piping secondary containment
monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ܆ Sump ܆ UDC
܆܆܆܆܆܆
If monitoring system alarms are relayed to a remote monitoring center, is all
communication equipment operational? ܆܆܆܆܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
Veeder Root TLS350
336.02
Underground Storage Tank
Monitoring System Certification Form
Page 3 of 6
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List “Sensor ID” as labeled in system
programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
Describe all answers marked “No” or “Fail” and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
L1 208 87 STP
L2 420 87 Annular
L3 208 91 STP
L4 420 91 Annular
L5 208 Diesel STP
L6 420 Diesel Annular
L9 208 Dispenser 9/10
L10 208 Dispenser 11/12
L11 208 Dispenser 13/14
L12 208 Dispenser 15/16
L13 208 Dispenser 17/18
L14 208 Dispenser 19/20
Underground Storage Tank
Monitoring System Certification Form
Page 5 of 6
8. IN-TANK GAUGING TESTING
܆܆ Check this box if tank gauging is used only for inventory control.
܆܆ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and
termination; and 2) tested for ground faults? ܆܆ ܆܆ ܆܆
Were all in-tank gauging probes visually inspected for damage and residue buildup
to ensure that floats move freely, functionally tested, and confirmed operational? ܆܆ ܆܆
Was accuracy of system’s product level readings tested? ܆܆ ܆܆ ܆܆
Was accuracy of system’s water level readings tested? ܆܆ ܆܆ ܆܆
Were all probes reinstalled properly? ܆܆ ܆܆ ܆܆
Were all items on the equipment manufacturer’s maintenance checklist completed? ܆܆ ܆܆ ܆܆
Probe ID Probe Model Tanks Monitored Pass Fail
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
܆܆ ܆܆
9. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
܆܆
Strictly an electronic monitor certification. No mechanical LLDS were tested.
Underground Storage Tank
Monitoring System Certification Form
Page 6 of 6
10. MONITORING SITE PLAN
Date site plan was prepared:
If a site plan has been prepared that shows all required information, you may include it, rather than this page,
with your Monitoring System Certification Form. The site plan must show the general layout of tanks and
identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include
a legend for all symbols depicted.
03/04/24
F
EXISTING BUILDING
NOPARKING
56L11
#7-781
78L10 34L12
12L9
12,000 GALLON87-1 UNLEADED
12,000 GALLON87-2 UNLEADED
12,000 GALLONPREMIUM
12,000 GALLONDIESEL
V AL2 STPL1
FV AL6 STPL5
FV AL8 STPL7
F AL4 STPL3 109L91413L121211L101615L122019L141817L1312,000 GALLON87 UNLEADED12,000 GALLONPREMIUM12,000 GALLONDIESELFAL6STPL5FVAL4STPL3FVAL2STPL1NOPARKING
G
W
7-721
7-781
#7-721DUMPSTER H
H
PRICE SIGN
PRICE SIGN
40' STORAGE CONTA
INER
S. H ST.WHITE LN.PROPERTY LINE
PROPERTY LINE
N
CAT
C
HBAS
I
N
721 LEGEND
L1 87 STP
L2 87 ANNULAR
L3 91 STP
L4 91 ANNULAR
L5 DSL STP
L6 DSL ANNULAR
L9 UDC 9 - 10
L10 UDC 11 -12
L11 UDC 13 - 14
L12 UDC 15 - 16
L13 UDC 17 - 18
L14 UDC 19 - 20
781 LEGEND
L1 87-1 STP
L2 87-1 ANNULAR
L3 DSL STP
L4 DSL ANNULAR
L5 87-2 STP
L6 87-2 ANNULAR
L7 91 STP
L8 91 ANNULAR
L9 UDC 1 -2
L10 UDC 7 - 8
L11 UDC 5 -6
L12 UDC 3 - 4
87 GAS 3/2 INCH DBL WALLED PIPE
91 GAS 3/2 INCH DBL WALLED PIPE
DIESEL 3/2 INCH DBL WALLED PIPE
VAPOR RETURN 3 AND 2 INCH SINGLE WALL PIPE
VAPOR VENT 3/2 INCH DOUBLE WALLED PIPE
PRODUCT SPILL CONTAINER
VAPOR SPILL CONTAINER
ANNULAR
EMERGENCY SHUT-OFF
OVERFILL ALARM
FIRE EXTINGUISHER
GAS METER SHUT-OFF
WATER METER SHUT-SHUT OFF
HEALY CAS
EVACUATION MEETING POINT
CIRCUIT BREAKER
UST ELECTRICAL PANEL
AUTOMATIC TANK GAUGE
AIR AND WATER DISPENSER
HAZWASTE DRUM
W
G
A
H
P
V
SCALE:
SITE MAP
C1
VICINITY MAP
PROJECT DATA
3/32"=1'-0"
INCHES012
SHEET SIZE 22 X 34
4013 S. H ST.
BAKERSFIELD, CA 93304
PROJECT OWNER:
JAMIESON HILL
PO. BOX 82515
BAKERSFIELD, CA 93380
CONTACT:
SITE PLOT PLAN FOR:
FASTRIP #7721
FACILITY ID 15-021-100296
CERS ID 10159161
FASTRIP #7781
FACILITY ID 15-021-003022
CERS ID 10159163
4013 S. H ST.
BAKERSFIELD, CA 93304
03/02/17 REV.S. H ST.WHITE LN.
FASTRIP #7721 SYSTEM SETUP
Responses Received:
200
FASTRIP
4013 S H ST
BAKERSFIELD
MAR 4, 2024 9:05 AM
TANK PRODUCT GALLONS INCHES WATER DEG F ULLAGE
1 87 9976 74.38 0.0 61.0 2024
2 91 7288 56.13 0.0 63.7 4712
3 DSL 124 3.22 0.0 70.1 11876
I90500
MAR 4, 2024 9:05 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I50500
MAR 4, 2024 9:05 AM
SYSTEM TYPE AND LANGUAGE FLAG
SYSTEM UNITS
U.S.
SYSTEM LANGUAGE
ENGLISH
SYSTEM DATE/TIME FORMAT
MON DD YYYY HH:MM:SS xM
I50201
MAR 4, 2024 9:05 AM
SHIFT TIME 1 : 6:00 AM
I50202
MAR 4, 2024 9:05 AM
SHIFT TIME 2 : DISABLED
I50203
MAR 4, 2024 9:05 AM
SHIFT TIME 3 : DISABLED
I50204
MAR 4, 2024 9:06 AM
SHIFT TIME 4 : DISABLED
I54600
MAR 4, 2024 9:06 AM
TANK PER TST NEEDED WRN: DISABLED
I54900
MAR 4, 2024 9:06 AM
TANK ANN TST NEEDED WRN: DISABLED
I55300
MAR 4, 2024 9:06 AM
LINE RE-ENABLE METHOD
PASS LINE TEST
I55600
MAR 4, 2024 9:06 AM
LINE PER TST NEEDED WRN: DISABLED
I55900
MAR 4, 2024 9:06 AM
LINE ANN TST NEEDED WRN: DISABLED
I50D00
MAR 4, 2024 9:06 AM
PRINT TC VOLUMES
ENABLED
I50E00
MAR 4, 2024 9:06 AM
TEMP COMPENSATION
VALUE (DEG F ): 60.0
I60B00
MAR 4, 2024 9:06 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I51400
MAR 4, 2024 9:06 AM
H-PROTOCOL DATA FORMAT
HEIGHT
I51A01
MAR 4, 2024 9:06 AM
DAYLIGHT SAVING TIME
DISABLED
I51B00
MAR 4, 2024 9:06 AM
I51600
MAR 4, 2024 9:06 AM
RE-DIRECT LOCAL PRINTOUT
DISABLED
I50400
MAR 4, 2024 9:06 AM
232 SECURITY CODE
PORT SECURITY CODE STATUS
1 000000 DISABLED
2 000000 DISABLED
3 000000 DISABLED
4 000000 DISABLED
5 000000 DISABLED
6 000000 DISABLED
I21900
MAR 4, 2024 9:06 AM
TANK CHART SECURITY
DISABLED
I5BD00
MAR 4, 2024 9:06 AM
CUSTOM ALARM LABELS
DISABLED
I56000
MAR 4, 2024 9:06 AM
MASS/DENSITY
DISABLED
I88101
MAR 4, 2024 9:06 AM
PORT SETTINGS:
COMM BOARD : 1 (EDIM )
RS-232 SECURITY
CODE : DISABLED
I88102
MAR 4, 2024 9:06 AM
PORT SETTINGS:
COMM BOARD : 2 (RS-232)
BAUD RATE : 9600
PARITY : ODD
STOP BIT : 1 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88103
MAR 4, 2024 9:06 AM
PORT SETTINGS:
COMM BOARD : 3 (RS-232)
BAUD RATE : 9600
PARITY : NONE
STOP BIT : 2 STOP
DATA LENGTH: 7 DATA
RS-232 SECURITY
CODE : DISABLED
I88104
MAR 4, 2024 9:06 AM
I88105
MAR 4, 2024 9:06 AM
I88106
MAR 4, 2024 9:06 AM
I52000
MAR 4, 2024 9:06 AM
RECEIVER AUTO DIAL TYPE & START TIME
RCVR LOCATION LABEL DIAL TYPE START TIME
1 ON DATE JUN 30, 2022 DISABLED
2 ON DATE JUN 30, 2022 DISABLED
3 ON DATE JUN 30, 2022 DISABLED
4 ON DATE JUN 30, 2022 DISABLED
5 ON DATE JUN 30, 2022 DISABLED
6 ON DATE JUN 30, 2022 DISABLED
7 ON DATE JUN 30, 2022 DISABLED
8 ON DATE JUN 30, 2022 DISABLED
I60100
MAR 4, 2024 9:06 AM
TANK CONFIGURATION
DEVICE LABEL CONFIGURED
1 87 ON
2 91 ON
3 DSL ON
4 OFF
I60200
MAR 4, 2024 9:06 AM
TANK PRODUCT LABEL
TANK PRODUCT LABEL
1 87
2 91
3 DSL
4
I60300
MAR 4, 2024 9:06 AM
TANK PRODUCT CODE
TANK PRODUCT LABEL
1 87 1
2 91 2
3 DSL 3
4 4
I60900
MAR 4, 2024 9:06 AM
TANK THERMAL COEFFICIENT
TANK PRODUCT LABEL
1 87 0.000700
2 91 0.000700
3 DSL 0.000450
4 0.000000
I60700
MAR 4, 2024 9:06 AM
TANK DIAMETER
TANK PRODUCT LABEL INCHES
1 87 96.00
2 91 96.00
3 DSL 96.00
4 0.00
I60A00
MAR 4, 2024 9:06 AM
TANK FULL VOLUME
TANK PRODUCT LABEL TANK PROFILE GALLONS 1 87 1 PT
12000 2 91 1 PT 12000 3 DSL
1 PT 12000 4 1 PT 0
I60400
MAR 4, 2024 9:06 AM
TANK FULL VOLUME
TANK PRODUCT LABEL GALLONS
1 87 12000
2 91 12000
3 DSL 12000
4 0
I60500
MAR 4, 2024 9:06 AM
TANK 4 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 87 12000 0 0 0
2 91 12000 0 0 0
3 DSL 12000 0 0 0
4 0 0 0 0
I60600
MAR 4, 2024 9:06 AM
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 87 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
2 91 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
3 DSL 12000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
4 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
I61500
MAR 4, 2024 9:06 AM
TANK PRODUCT LABEL METER DATA
1 87 NO
2 91 NO
3 DSL NO
4 NO
I62F00
MAR 4, 2024 9:06 AM
MAG PROBE FLOAT SIZE
TANK PRODUCT LABEL FLOAT SIZE:
1 87 4.0 IN.
2 91 4.0 IN.
3 DSL 4.0 IN.
I62700
MAR 4, 2024 9:06 AM
TANK HIGH WATER WARNING LIMIT
TANK PRODUCT LABEL INCHES
1 87 2.0
2 91 2.0
3 DSL 2.0
I64200
MAR 4, 2024 9:06 AM
WATER ALARM FILTER
TANK PRODUCT LABEL
1 87 LOW
2 91 LOW
3 DSL LOW
I62400
MAR 4, 2024 9:06 AM
TANK HIGH WATER LEVEL LIMIT
TANK PRODUCT LABEL INCHES
1 87 3.0
2 91 3.0
3 DSL 3.0
I62800
MAR 4, 2024 9:06 AM
TANK MAXIMUM VOLUME LIMIT
TANK PRODUCT LABEL GALLONS
1 87 12000
2 91 12000
3 DSL 12000
4 0
I62300
MAR 4, 2024 9:06 AM
TANK OVERFILL LEVEL LIMIT
TANK PRODUCT LABEL GALLONS
1 87 10800
2 91 10800
3 DSL 10800
4 0
I62200
MAR 4, 2024 9:06 AM
TANK HIGH PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 87 11400
2 91 11400
3 DSL 11400
4 0
I62900
MAR 4, 2024 9:06 AM
TANK DELIVERY REQUIRED LIMIT
TANK PRODUCT LABEL GALLONS
1 87 1200
2 91 1200
3 DSL 120
4 0
I62100
MAR 4, 2024 9:06 AM
TANK LOW PRODUCT LIMIT
TANK PRODUCT LABEL GALLONS
1 87 1200
2 91 1200
3 DSL 100
4 0
I62600
MAR 4, 2024 9:06 AM
TANK LEAK ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 87 99
2 91 99
3 DSL 99
4 99
I62500
MAR 4, 2024 9:06 AM
TANK SUDDEN LOSS LIMIT
TANK PRODUCT LABEL GALLONS
1 87 99
2 91 99
3 DSL 99
4 99
I60800
MAR 4, 2024 9:06 AM
TANK TILT
TANK PRODUCT LABEL INCHES
1 87 0.00
2 91 0.00
3 DSL 0.00
4 0.00
I60B00
MAR 4, 2024 9:06 AM
STICK HEIGHT OFFSET ENABLE STATUS
DISABLED
I60C00
MAR 4, 2024 9:06 AM
TANK STICK HEIGHT OFFSET
TANK PRODUCT LABEL INCHES
1 87 0.00
2 91 0.00
3 DSL 0.00
4 0.00
I61200
MAR 4, 2024 9:06 AM
TANK MANIFOLDED PARTNERS
TANK PRODUCT LABEL SIPHON MANIFOLDED TANKS LINE MANIFOLDED TANKS
1 87 NONE NONE
2 91 NONE NONE
3 DSL NONE NONE
4 NONE NONE
I63600
MAR 4, 2024 9:06 AM
PERIODIC LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 87 120
2 91 120
3 DSL 120
4 0
I62A00
MAR 4, 2024 9:06 AM
ANNUAL LEAK TEST MIN VOLUME
TANK PRODUCT LABEL GALLONS
1 87 120
2 91 120
3 DSL 120
4 0
I62C00
MAR 4, 2024 9:06 AM
TANK PERIODIC TEST TYPE
TANK PRODUCT LABEL PERIODIC TEST TYPE
1 87 STANDARD
2 91 STANDARD
3 DSL STANDARD
4 STANDARD
I62D00
MAR 4, 2024 9:06 AM
TANK LEAK TEST FAIL ALARMS
TANK PRODUCT LABEL
1 87 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
2 91 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
3 DSL GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
4 GROSS TEST FAIL ALARM DISABLED
PERIODIC TEST FAIL ALARM DISABLED
ANNUAL TEST FAIL ALARM DISABLED
I63100
MAR 4, 2024 9:06 AM
TANK LEAK TEST AVERAGING
TANK PRODUCT LABEL ANNUAL PERIODIC
1 87 OFF OFF
2 91 OFF OFF
3 DSL OFF OFF
4 OFF OFF
I63000
MAR 4, 2024 9:06 AM
IN-TANK LEAK TEST NOTIFY
TANK PRODUCT LABEL TANK TEST NOTIFY:
1 87 OFF
2 91 OFF
3 DSL OFF
4 OFF
I63200
MAR 4, 2024 9:06 AM
TANK TEST SIPHON BREAK
TANK PRODUCT LABEL SIPHON BREAK
1 87 OFF
2 91 OFF
3 DSL OFF
4 OFF
I61000
MAR 4, 2024 9:06 AM
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 87 1
2 91 1
3 DSL 1
4 1
I63A00
MAR 4, 2024 9:06 AM
LOW LEVEL PUMP THRESHOLD FOR SEQUENTIAL LINE MANIFOLD
TANK PRODUCT LABEL PUMP THRESHOLD
1 87 10.00%
2 91 10.00%
3 DSL 1.00%
4 10.00%
I61100
MAR 4, 2024 9:06 AM
LEAK TEST METHOD
- - - - - - - - - - - -
TEST ON DATE : ALL TANK
FEB 13, 2021
START TIME : DISABLED
TEST RATE :0.20 GAL/HR
DURATION : 2 HOURS
TST EARLY STOP:DISABLED
I61300
MAR 4, 2024 9:06 AM
CSLD PROBABLITY OF DETECTION
I61400
MAR 4, 2024 9:06 AM
CSLD CLIMATE FACTOR
I61600
MAR 4, 2024 9:06 AM
TANK PRODUCT LABEL CAL UPDATE
1 87 IMMEDIATE
2 91 IMMEDIATE
3 DSL IMMEDIATE
4 IMMEDIATE
I61A00
MAR 4, 2024 9:06 AM
IN-TANK LEAK TEST EARLY STOP
TANK PRODUCT LABEL TST EARLY STOP:
1 87 DISABLED
2 91 DISABLED
3 DSL DISABLED
4 DISABLED
I61B00
MAR 4, 2024 9:06 AM
IN-TANK LEAK GROSS TEST AUTO-CONFIRM
I61C00
MAR 4, 2024 9:06 AM
CSLD REPORT ONLY
I62B00
MAR 4, 2024 9:06 AM
TANK LAST ANNUAL TEST
TANK PRODUCT LABEL DATE
1 87 ??? 0, 0
2 91 ??? 0, 0
3 DSL ??? 0, 0
4 ??? 0, 0
I63300
MAR 4, 2024 9:06 AM
LEAK TEST REPORT FORMAT: NORMAL
I63400
MAR 4, 2024 9:06 AM
RECONCILIATION WARNING LIMIT
TANK PRODUCT LABEL GALLONS
1 87 0
2 91 0
3 DSL 0
4 0
I63500
MAR 4, 2024 9:06 AM
RECONCILIATION ALARM LIMIT
TANK PRODUCT LABEL GALLONS
1 87 1
2 91 1
3 DSL 1
4 1
I63900
MAR 4, 2024 9:06 AM
ACCU CHART END SHAPE FACTOR
TANK PRODUCT LABEL
1 87
END FACTOR: NONE
2 91
END FACTOR: NONE
3 DSL
END FACTOR: NONE
4
END FACTOR: NONE
I78000
MAR 4, 2024 9:06 AM
I77700
MAR 4, 2024 9:06 AM
I77800
MAR 4, 2024 9:06 AM
I78C00
MAR 4, 2024 9:06 AM
I78300
MAR 4, 2024 9:06 AM
I78F00
MAR 4, 2024 9:06 AM
I78700
MAR 4, 2024 9:06 AM
I70200
MAR 4, 2024 9:06 AM
LIQUID LABEL
DEVICE LABEL
1 87 STP
2 87 ANN
3 91 STP
4 91 ANN
5 DEISE STP
6 DSL ANN
7
8
9 9-10
10 11-12
11 13-14
12 15-16
13 17-18
14 19-20
15
16
I70300
MAR 4, 2024 9:06 AM
LIQUID TYPE
SENSOR LOCATION TYPE
1 87 STP TRI-STATE (SINGLE FLOAT)
2 87 ANN TRI-STATE (SINGLE FLOAT)
3 91 STP TRI-STATE (SINGLE FLOAT)
4 91 ANN TRI-STATE (SINGLE FLOAT)
5 DEISE STP TRI-STATE (SINGLE FLOAT)
6 DSL ANN TRI-STATE (SINGLE FLOAT)
7 TRI-STATE (SINGLE FLOAT)
8 TRI-STATE (SINGLE FLOAT)
9 9-10 TRI-STATE (SINGLE FLOAT)
10 11-12 TRI-STATE (SINGLE FLOAT)
11 13-14 TRI-STATE (SINGLE FLOAT)
12 15-16 TRI-STATE (SINGLE FLOAT)
13 17-18 TRI-STATE (SINGLE FLOAT)
14 19-20 TRI-STATE (SINGLE FLOAT)
15 TRI-STATE (SINGLE FLOAT)
16 TRI-STATE (SINGLE FLOAT)
I70400
MAR 4, 2024 9:06 AM
LIQUID CATEGORY
SENSOR LOCATION CATEGORY
1 87 STP STP SUMP
2 87 ANN ANNULAR SPACE
3 91 STP STP SUMP
4 91 ANN ANNULAR SPACE
5 DEISE STP STP SUMP
6 DSL ANN ANNULAR SPACE
7 OTHER SENSORS
8 OTHER SENSORS
9 9-10 DISPENSER PAN
10 11-12 DISPENSER PAN
11 13-14 DISPENSER PAN
12 15-16 DISPENSER PAN
13 17-18 DISPENSER PAN
14 19-20 DISPENSER PAN
15 OTHER SENSORS
16 OTHER SENSORS
I74200
MAR 4, 2024 9:06 AM
I74300
MAR 4, 2024 9:06 AM
I74400
MAR 4, 2024 9:06 AM
I74700
MAR 4, 2024 9:06 AM
I74800
MAR 4, 2024 9:06 AM
I74900
MAR 4, 2024 9:06 AM
I7BC00
MAR 4, 2024 9:06 AM
I80200
MAR 4, 2024 9:06 AM
I80300
MAR 4, 2024 9:06 AM
I80400
MAR 4, 2024 9:06 AM
I80700
MAR 4, 2024 9:06 AM
RELAY LABEL
DEVICE LABEL
1 87
2 91
3 DSL
4 OVERFILL
I80900
MAR 4, 2024 9:06 AM
RELAY ORIENTATION
RELAY DESIGNATION ORIENTATION
1 87 NORMALLY OPEN
2 91 NORMALLY OPEN
3 DSL NORMALLY CLOSED
4 OVERFILL NORMALLY OPEN
I80B00
MAR 4, 2024 9:06 AM
RELAY TANK ASSIGNMENT
RELAY DESIGNATION TANK
1 87 1
2 91 2
3 DSL NONE
4 OVERFILL 4
I80A00
MAR 4, 2024 9:06 AM
RELAY TYPE
RELAY DESIGNATION TYPE
1 87 PUMP CONTROL OUTPUT
2 91 PUMP CONTROL OUTPUT
3 DSL STANDARD
4 OVERFILL STANDARD
I80C00
MAR 4, 2024 9:06 AM
I80800
MAR 4, 2024 9:06 AM
RELAY SETUP REPORT
R 1:87
TYPE:
PUMP CONTROL OUTPUT
TANK #: 1
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 1:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 1:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L14:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
ALL:GROSS COLLECT FAIL
ALL:DEGRD COLLECT FAIL
R 2:91
TYPE:
PUMP CONTROL OUTPUT
TANK #: 2
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 3:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 1:SENSOR OUT ALARM
L 3:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
L 1:SHORT ALARM
L 3:SHORT ALARM
L 9:SHORT ALARM
L10:SHORT ALARM
L11:SHORT ALARM
L12:SHORT ALARM
L13:SHORT ALARM
L14:SHORT ALARM
ISD SITE ALARMS
ISD GROSS PRES FAIL
ISD DEGRD PRES FAIL
ISD VAPOR LEAK FAIL
ISD VP PRES FAIL
ISD VP STATUS FAIL
ISD HOSE ALARMS
h13:GROSS COLLECT FAIL
h14:GROSS COLLECT FAIL
h15:GROSS COLLECT FAIL
h16:GROSS COLLECT FAIL
h17:GROSS COLLECT FAIL
h18:GROSS COLLECT FAIL
h19:GROSS COLLECT FAIL
h20:GROSS COLLECT FAIL
h21:GROSS COLLECT FAIL
h22:GROSS COLLECT FAIL
h23:GROSS COLLECT FAIL
h24:GROSS COLLECT FAIL
h25:GROSS COLLECT FAIL
h26:GROSS COLLECT FAIL
h27:GROSS COLLECT FAIL
h28:GROSS COLLECT FAIL
h29:GROSS COLLECT FAIL
h30:GROSS COLLECT FAIL
h31:GROSS COLLECT FAIL
h32:GROSS COLLECT FAIL
h33:GROSS COLLECT FAIL
h34:GROSS COLLECT FAIL
h35:GROSS COLLECT FAIL
h36:GROSS COLLECT FAIL
h37:GROSS COLLECT FAIL
h38:GROSS COLLECT FAIL
h39:GROSS COLLECT FAIL
h40:GROSS COLLECT FAIL
h41:GROSS COLLECT FAIL
h42:GROSS COLLECT FAIL
h43:GROSS COLLECT FAIL
h44:GROSS COLLECT FAIL
h45:GROSS COLLECT FAIL
h46:GROSS COLLECT FAIL
h47:GROSS COLLECT FAIL
h48:GROSS COLLECT FAIL
h49:GROSS COLLECT FAIL
h50:GROSS COLLECT FAIL
h51:GROSS COLLECT FAIL
h52:GROSS COLLECT FAIL
h53:GROSS COLLECT FAIL
h54:GROSS COLLECT FAIL
h55:GROSS COLLECT FAIL
h56:GROSS COLLECT FAIL
h57:GROSS COLLECT FAIL
h58:GROSS COLLECT FAIL
h59:GROSS COLLECT FAIL
h60:GROSS COLLECT FAIL
h61:GROSS COLLECT FAIL
h62:GROSS COLLECT FAIL
h63:GROSS COLLECT FAIL
h64:GROSS COLLECT FAIL
h65:GROSS COLLECT FAIL
h66:GROSS COLLECT FAIL
h67:GROSS COLLECT FAIL
h68:GROSS COLLECT FAIL
h69:GROSS COLLECT FAIL
h70:GROSS COLLECT FAIL
h71:GROSS COLLECT FAIL
h72:GROSS COLLECT FAIL
h73:GROSS COLLECT FAIL
h74:GROSS COLLECT FAIL
h75:GROSS COLLECT FAIL
h76:GROSS COLLECT FAIL
h77:GROSS COLLECT FAIL
h78:GROSS COLLECT FAIL
h79:GROSS COLLECT FAIL
h80:GROSS COLLECT FAIL
h81:GROSS COLLECT FAIL
h82:GROSS COLLECT FAIL
h83:GROSS COLLECT FAIL
h84:GROSS COLLECT FAIL
h85:GROSS COLLECT FAIL
h86:GROSS COLLECT FAIL
h87:GROSS COLLECT FAIL
h88:GROSS COLLECT FAIL
h89:GROSS COLLECT FAIL
h90:GROSS COLLECT FAIL
h91:GROSS COLLECT FAIL
h92:GROSS COLLECT FAIL
h93:GROSS COLLECT FAIL
h94:GROSS COLLECT FAIL
h95:GROSS COLLECT FAIL
h96:GROSS COLLECT FAIL
h97:GROSS COLLECT FAIL
h98:GROSS COLLECT FAIL
h99:GROSS COLLECT FAIL
h13:DEGRD COLLECT FAIL
h14:DEGRD COLLECT FAIL
h15:DEGRD COLLECT FAIL
h16:DEGRD COLLECT FAIL
h17:DEGRD COLLECT FAIL
h18:DEGRD COLLECT FAIL
h19:DEGRD COLLECT FAIL
h20:DEGRD COLLECT FAIL
h21:DEGRD COLLECT FAIL
h22:DEGRD COLLECT FAIL
h23:DEGRD COLLECT FAIL
h24:DEGRD COLLECT FAIL
h25:DEGRD COLLECT FAIL
h26:DEGRD COLLECT FAIL
h27:DEGRD COLLECT FAIL
h28:DEGRD COLLECT FAIL
h29:DEGRD COLLECT FAIL
h30:DEGRD COLLECT FAIL
h31:DEGRD COLLECT FAIL
h32:DEGRD COLLECT FAIL
h33:DEGRD COLLECT FAIL
h34:DEGRD COLLECT FAIL
h35:DEGRD COLLECT FAIL
h36:DEGRD COLLECT FAIL
h37:DEGRD COLLECT FAIL
h38:DEGRD COLLECT FAIL
h39:DEGRD COLLECT FAIL
h40:DEGRD COLLECT FAIL
h41:DEGRD COLLECT FAIL
h42:DEGRD COLLECT FAIL
h43:DEGRD COLLECT FAIL
h44:DEGRD COLLECT FAIL
h45:DEGRD COLLECT FAIL
h46:DEGRD COLLECT FAIL
h47:DEGRD COLLECT FAIL
h48:DEGRD COLLECT FAIL
h49:DEGRD COLLECT FAIL
h50:DEGRD COLLECT FAIL
h51:DEGRD COLLECT FAIL
h52:DEGRD COLLECT FAIL
h53:DEGRD COLLECT FAIL
h54:DEGRD COLLECT FAIL
h55:DEGRD COLLECT FAIL
h56:DEGRD COLLECT FAIL
h57:DEGRD COLLECT FAIL
h58:DEGRD COLLECT FAIL
h59:DEGRD COLLECT FAIL
h60:DEGRD COLLECT FAIL
h61:DEGRD COLLECT FAIL
h62:DEGRD COLLECT FAIL
h63:DEGRD COLLECT FAIL
h64:DEGRD COLLECT FAIL
h65:DEGRD COLLECT FAIL
h66:DEGRD COLLECT FAIL
h67:DEGRD COLLECT FAIL
h68:DEGRD COLLECT FAIL
h69:DEGRD COLLECT FAIL
h70:DEGRD COLLECT FAIL
h71:DEGRD COLLECT FAIL
h72:DEGRD COLLECT FAIL
h73:DEGRD COLLECT FAIL
h74:DEGRD COLLECT FAIL
h75:DEGRD COLLECT FAIL
h76:DEGRD COLLECT FAIL
h77:DEGRD COLLECT FAIL
h78:DEGRD COLLECT FAIL
h79:DEGRD COLLECT FAIL
h80:DEGRD COLLECT FAIL
h81:DEGRD COLLECT FAIL
h82:DEGRD COLLECT FAIL
h83:DEGRD COLLECT FAIL
h84:DEGRD COLLECT FAIL
h85:DEGRD COLLECT FAIL
h86:DEGRD COLLECT FAIL
h87:DEGRD COLLECT FAIL
h88:DEGRD COLLECT FAIL
h89:DEGRD COLLECT FAIL
h90:DEGRD COLLECT FAIL
h91:DEGRD COLLECT FAIL
h92:DEGRD COLLECT FAIL
h93:DEGRD COLLECT FAIL
h94:DEGRD COLLECT FAIL
h95:DEGRD COLLECT FAIL
h96:DEGRD COLLECT FAIL
h97:DEGRD COLLECT FAIL
h98:DEGRD COLLECT FAIL
h99:DEGRD COLLECT FAIL
R 3:DSL
TYPE:
STANDARD
NORMALLY CLOSED
TANK #: NONE
LIQUID SENSOR ALMS
L 1:FUEL ALARM
L 5:FUEL ALARM
L 9:FUEL ALARM
L10:FUEL ALARM
L11:FUEL ALARM
L12:FUEL ALARM
L13:FUEL ALARM
L14:FUEL ALARM
L 5:SENSOR OUT ALARM
L 9:SENSOR OUT ALARM
L10:SENSOR OUT ALARM
L11:SENSOR OUT ALARM
L12:SENSOR OUT ALARM
L13:SENSOR OUT ALARM
L14:SENSOR OUT ALARM
R 4:OVERFILL
TYPE:
STANDARD
NORMALLY OPEN
TANK #: 4
IN-TANK ALARMS
ALL:LEAK ALARM
ALL:OVERFILL ALARM
ALL:HIGH PRODUCT ALARM
I79000
MAR 4, 2024 9:07 AM
EDIM:1 VR:349634-003-C TD:06.05.11.11.15
I79100
MAR 4, 2024 9:07 AM
I72300
MAR 4, 2024 9:07 AM
FASTRIP
4013 S H ST
BAKERSFIELD
SMARTSENSOR ASSIGNMENT
DEVICE LABEL CATEGORY
01 VPS VAPOR PRESSURE
02 FM1 AIR FLOW METER
03 FM2 AIR FLOW METER
04 FM3 AIR FLOW METER
05 FM4 AIR FLOW METER
06 FM5 AIR FLOW METER
07 FM6 AIR FLOW METER
08 UNKNOWN
09 UNKNOWN
10 UNKNOWN
11 UNKNOWN
12 UNKNOWN
13 UNKNOWN
14 UNKNOWN
15 UNKNOWN
16 UNKNOWN
17 UNKNOWN
18 UNKNOWN
19 UNKNOWN
20 UNKNOWN
21 UNKNOWN
22 UNKNOWN
23 UNKNOWN
24 UNKNOWN
25 UNKNOWN
26 UNKNOWN
27 UNKNOWN
28 UNKNOWN
29 UNKNOWN
30 UNKNOWN
31 UNKNOWN
32 UNKNOWN
33 UNKNOWN
34 UNKNOWN
35 UNKNOWN
36 UNKNOWN
37 UNKNOWN
38 UNKNOWN
39 UNKNOWN
40 UNKNOWN
IV4E00
MAR 4, 2024 9:07 AM
FASTRIP
4013 S H ST
BAKERSFIELD
EVR/ISD SETUP
TYPE: VACUUM ASSIST
VACUUM ASSIST TYPE: HEALY VAC
IV4F00
MAR 4, 2024 9:07 AM
FASTRIP
4013 S H ST
BAKERSFIELD
NOZZLE A/L RANGE
A/L RATIO: 0.95 - 1.15
IV4000
MAR 4, 2024 9:07 AM
FASTRIP
4013 S H ST
BAKERSFIELD
VAPOR PROCESSOR TYPE
NONE
IV4700
MAR 4, 2024 9:07 AM
FASTRIP
4013 S H ST
BAKERSFIELD
ASSESSMENT TIME
START TIME: 10:00 AM
TIME DELAY MINUTES: 1
IV5200
MAR 4, 2024 9:07 AM
FASTRIP
4013 S H ST
BAKERSFIELD
ACCEPT HIGH ORVR: YES
IV4A00
MAR 4, 2024 9:07 AM
FASTRIP
4013 S H ST
BAKERSFIELD
ISD HOSE TABLE
HOSE FP FP AFM REL HOSE
ID ID LABEL ID ID LABEL
01 09 01 01 UU BLEND3
02 10 02 01 UU BLEND3
03 11 03 02 UU BLEND3
04 12 04 02 UU BLEND3
05 17 05 03 UU BLEND3
06 18 06 03 UU BLEND3
07 19 07 04 UU BLEND3
08 20 08 04 UU BLEND3
09 21 09 05 UU BLEND3
10 22 10 05 UU BLEND3
11 23 11 06 UU BLEND3
12 24 12 06 UU BLEND3
IV4B00
MAR 4, 2024 9:07 AM
FASTRIP
4013 S H ST
BAKERSFIELD
PRODUCT/HOSE MAP TABLE
FP AFID M1/H1 M2/H2 M3/H3 M4/H4
09 01 03/01 02/01 09/01 xx/xx
10 01 03/02 02/02 09/02 xx/xx
11 02 03/03 02/03 09/03 xx/xx
12 02 03/04 02/04 09/04 xx/xx
17 03 03/05 02/05 09/05 xx/xx
18 03 03/06 02/06 09/06 xx/xx
19 04 03/07 02/07 09/07 xx/xx
20 04 03/08 02/08 09/08 xx/xx
21 05 03/09 02/09 09/09 xx/xx
22 05 03/10 02/10 09/10 xx/xx
23 06 03/11 02/11 09/11 xx/xx
24 06 03/12 02/12 09/12 xx/xx
IV4900
MAR 4, 2024 9:07 AM
FASTRIP
4013 S H ST
BAKERSFIELD
LABEL TABLE
ID LABEL
01 UNASSIGNED
02 BLEND3
03 REGULAR
04 MID GRADE
05 PREMIUM
06 GOLD
07 BRONZE
08 SILVER
09 BLEND2
10 BLEND4
IV1000
MAR 4, 2024 9:07 AM
ISD VERSION: 01.07
FASTRIP #7721 ALRAM HISTORY
BEFORE:
Responses Received:
I10200
MAR 4, 2024 9:04 AM
FASTRIP
4013 S H ST
BAKERSFIELD
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 506348 505843
2 INTERSTITIAL BD 202119 201810
3 4 PROBE / G.T. 162852 162782
4 INTERSTITIAL BD 200886 200699
5 UNUSED 4893943 4895347
6 UNUSED 4889919 4889550
7 UNUSED 4887645 4890553
8 UNUSED 4887382 4889572
9 STP SENSE BOARD 33095 33095
10 RELAY BOARD 14985 14963
11 UNUSED 4892472 4894168
12 UNUSED 4889257 4888175
13 UNUSED 4887704 4892577
14 UNUSED 4886370 4889156
15 UNUSED 4890110 4887957
16 UNUSED 4888448 4889330
COMM 1 ELEC DISP INT. 101054 100917
COMM 2 RS232 SERIAL BD 14985 14985
COMM 3 RS232 SERIAL BD 14941 14919
COMM 4 UNUSED 4892669 4892708
COMM 5 UNUSED 4888667 4889919
COMM 6 UNUSED 4887245 4890529
I90200
MAR 4, 2024 9:04 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
MAR 4, 2024 9:04 AM
FASTRIP
4013 S H ST
BAKERSFIELD
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
T 1 TANK 87 OVERFILL ALARM CLEAR 2-24-24 10:21AM
T 1 TANK 87 OVERFILL ALARM ALARM 2-24-24 10:19AM
E 1 OTHER G COMMUNICATION ALARM CLEAR 2-23-24 12:00PM
E 1 OTHER G COMMUNICATION ALARM ALARM 2-23-24 11:59AM
OTHER MISSING HOSE SETUP CLEAR 2-12-24 12:54PM
OTHER MISS VAPOR FLOW MTR CLEAR 2-12-24 12:06PM
OTHER MISS VAPOR FLOW MTR ALARM 2-12-24 11:34AM
OTHER MISSING HOSE SETUP ALARM 2-12-24 11:34AM
f 5 OTHER FM5 CHK VAPOR FLOW MTR CLEAR 2-12-24 10:00AM
f 5 OTHER FM5 CHK VAPOR FLOW MTR ALARM 2-11-24 10:02AM
f 6 OTHER FM6 CHK VAPOR FLOW MTR CLEAR 2-10-24 10:00AM
f 6 OTHER FM6 CHK VAPOR FLOW MTR ALARM 2-09-24 10:04AM
f 3 OTHER FM3 CHK VAPOR FLOW MTR CLEAR 2-08-24 4:37PM
T 1 TANK 87 OVERFILL ALARM CLEAR 2-08-24 2:03PM
T 1 TANK 87 OVERFILL ALARM ALARM 2-08-24 1:57PM
f 3 OTHER FM3 CHK VAPOR FLOW MTR ALARM 2-07-24 10:03AM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L 5 STP SUMP DEISE STP SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L14 DISP PAN 19-20 SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L13 DISP PAN 17-18 SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L12 DISP PAN 15-16 SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L11 DISP PAN 13-14 SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L10 DISP PAN 11-12 SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L 9 DISP PAN 9-10 SENSOR OUT ALARM CLEAR 2-04-24 3:56PM
L14 DISP PAN 19-20 SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L13 DISP PAN 17-18 SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L12 DISP PAN 15-16 SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L11 DISP PAN 13-14 SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L10 DISP PAN 11-12 SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L 1 STP SUMP 87 STP SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L 9 DISP PAN 9-10 SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L 5 STP SUMP DEISE STP SENSOR OUT ALARM ALARM 2-04-24 3:56PM
L 1 STP SUMP 87 STP FUEL ALARM CLEAR 2-04-24 3:52PM
L 1 STP SUMP 87 STP FUEL ALARM ALARM 2-04-24 3:52PM
L 3 STP SUMP 91 STP FUEL ALARM CLEAR 2-04-24 3:52PM
L 3 STP SUMP 91 STP FUEL ALARM ALARM 2-04-24 3:52PM
L 5 STP SUMP DEISE STP FUEL ALARM CLEAR 2-04-24 3:51PM
L 5 STP SUMP DEISE STP FUEL ALARM ALARM 2-04-24 3:51PM
L12 DISP PAN 15-16 FUEL ALARM CLEAR 2-04-24 3:48PM
L12 DISP PAN 15-16 FUEL ALARM ALARM 2-04-24 3:48PM
L13 DISP PAN 17-18 FUEL ALARM CLEAR 2-04-24 3:48PM
L13 DISP PAN 17-18 FUEL ALARM ALARM 2-04-24 3:48PM
I11200
MAR 4, 2024 9:04 AM
FASTRIP
4013 S H ST
BAKERSFIELD
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 2-12-24 1:01PM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 2-12-24 1:01PM
SYSTEM SOFTWARE MODULE WARN CLEAR 2-12-24 11:56AM
SYSTEM SOFTWARE MODULE WARN ALARM 2-12-24 11:54AM
OTHER ISD SENSOR OUT WARN CLEAR 2-12-24 10:02AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 2-12-24 10:02AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 2-12-24 10:02AM
SYSTEM PRINTER ERROR CLEAR 2-11-24 1:12PM
SYSTEM PAPER OUT CLEAR 2-11-24 1:11PM
SYSTEM PRINTER ERROR ALARM 2-11-24 1:11PM
SYSTEM PAPER OUT ALARM 2-11-24 1:11PM
OTHER ISD SENSOR OUT WARN ALARM 2-11-24 10:02AM
OTHER ISD SENSOR OUT WARN CLEAR 2-10-24 10:02AM
OTHER ISD SENSOR OUT WARN ALARM 2-09-24 10:04AM
OTHER ISD SENSOR OUT WARN CLEAR 2-08-24 4:32PM
h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 2-08-24 4:31PM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 2-08-24 4:31PM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 2-08-24 4:31PM
h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 2-08-24 10:04AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 2-08-24 10:04AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 2-08-24 10:04AM
OTHER ISD SENSOR OUT WARN ALARM 2-07-24 10:03AM
T 3 TANK DSL INVALID FUEL LEVEL ALARM 2-13-21 8:05AM
I20600
MAR 4, 2024 9:04 AM
FASTRIP
4013 S H ST
BAKERSFIELD
TANK ALARM HISTORY
TANK 1 87
OVERFILL ALARM FEB 24, 2024 10:19 AM
FEB 8, 2024 1:57 PM
TANK 2 91
TANK 3 DSL
INVALID FUEL LEVEL FEB 13, 2021 8:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
MAR 4, 2024 9:04 AM
I30200
MAR 4, 2024 9:04 AM
FASTRIP
4013 S H ST
BAKERSFIELD
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 STP
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:52 PM FUEL ALARM
2 87 ANN
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:37 PM FUEL ALARM
3 91 STP
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:52 PM FUEL ALARM
4 91 ANN
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:39 PM FUEL ALARM
5 DEISE STP
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:51 PM FUEL ALARM
6 DSL ANN
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:38 PM FUEL ALARM
9 9-10
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:45 PM FUEL ALARM
10 11-12
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:46 PM FUEL ALARM
11 13-14
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:46 PM FUEL ALARM
12 15-16
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:48 PM FUEL ALARM
13 17-18
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:48 PM FUEL ALARM
14 19-20
FEB 4, 2024 3:56 PM SENSOR OUT ALARM
FEB 4, 2024 3:47 PM FUEL ALARM
I31600
MAR 4, 2024 9:04 AM
FASTRIP
4013 S H ST
BAKERSFIELD
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VPS
2 FM1
3 FM2
4 FM3
5 FM4
6 FM5
7 FM6
I40200
MAR 4, 2024 9:04 AM
I40300
MAR 4, 2024 9:04 AM
I34200
MAR 4, 2024 9:04 AM
I34700
MAR 4, 2024 9:04 AM
IV0100
MAR 4, 2024 9:04 AM
FASTRIP
4013 S H ST
BAKERSFIELD
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :PASS EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME :100%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-02-12 10:02:39 A/L RATIO DEGRADATION FP10 BLEND3 0.63
24-02-12 10:02:39 A/L RATIO DEGRADATION FP 6 BLEND3 0.76
24-02-11 10:02:57 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 5:FM5
24-02-09 10:04:50 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 6:FM6
24-02-08 10:04:04 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 3:FM3
24-02-08 10:04:04 A/L RATIO DEGRADATION FP12 BLEND3 0.55
24-02-08 10:04:03 A/L RATIO DEGRADATION FP 9 BLEND3 0.76
24-02-08 10:04:03 A/L RATIO DEGRADATION FP 6 BLEND3 0.62
24-02-07 10:03:20 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 3:FM3
23-12-21 10:02:53 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 5:FM5
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-02-15 10:02:41 READINESS ISD:PP EVR:PP ISD & EVR READY
24-02-14 10:02:37 READINESS ISD:PP EVR:NP EVR READINESS PENDING
24-02-13 10:03:04 READINESS ISD:PP EVR:NP EVR READINESS PENDING
24-02-12 13:01:22 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED
24-02-12 13:01:16 COLLECTION TEST HH06 GRADE TEST MANUALLY CLEARED
24-02-12 11:56:33 READINESS ISD:PP EVR:NN EVR READINESS PENDING
24-02-12 11:56:33 ISD STARTUP
24-02-12 11:53:54 ISD SHUTDOWN
24-02-12 10:02:40 READINESS ISD:PP EVR:NP EVR READINESS PENDING
24-02-11 10:02:57 READINESS ISD:PF EVR:NNN CHECK ISD SENSORS
AFTER:
Responses Received:
I10200
MAR 4, 2024 10:08 AM
FASTRIP
4013 S H ST
BAKERSFIELD
SYSTEM CONFIGURATION
SLOT BOARD TYPE POWER ON RESET CURRENT
1 7SMARTSENSOR BD 506348 506318
2 INTERSTITIAL BD 202119 202120
3 4 PROBE / G.T. 162852 162792
4 INTERSTITIAL BD 200886 200939
5 UNUSED 4893943 4905479
6 UNUSED 4889919 4898942
7 UNUSED 4887645 4901274
8 UNUSED 4887382 4903409
9 STP SENSE BOARD 33095 33117
10 RELAY BOARD 14985 14963
11 UNUSED 4892472 4903538
12 UNUSED 4889257 4898133
13 UNUSED 4887704 4902862
14 UNUSED 4886370 4903124
15 UNUSED 4890110 4901925
16 UNUSED 4888448 4901141
COMM 1 ELEC DISP INT. 101054 101026
COMM 2 RS232 SERIAL BD 14985 14963
COMM 3 RS232 SERIAL BD 14941 14919
COMM 4 UNUSED 4892669 4905259
COMM 5 UNUSED 4888667 4899615
COMM 6 UNUSED 4887245 4901838
I90200
MAR 4, 2024 10:08 AM
SOFTWARE REVISION LEVEL
VERSION 336.02
SOFTWARE# 346336-100-C
CREATED - 21.02.13.11.53
S-MODULE# 330160-004-a
SYSTEM FEATURES:
PERIODIC IN-TANK TESTS
ANNUAL IN-TANK TESTS
ISD/APM
I11100
MAR 4, 2024 10:08 AM
FASTRIP
4013 S H ST
BAKERSFIELD
PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
s 6 OTHER FM5 COMMUNICATION ALARM CLEAR 3-04-24 10:05AM
L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L 5 STP SUMP DEISE STP SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L11 DISP PAN 13-14 SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L10 DISP PAN 11-12 SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L14 DISP PAN 19-20 SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L12 DISP PAN 15-16 SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L 9 DISP PAN 9-10 SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L13 DISP PAN 17-18 SENSOR OUT ALARM CLEAR 3-04-24 10:04AM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L 1 STP SUMP 87 STP SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L 5 STP SUMP DEISE STP SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L12 DISP PAN 15-16 SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L11 DISP PAN 13-14 SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L10 DISP PAN 11-12 SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L14 DISP PAN 19-20 SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L 9 DISP PAN 9-10 SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L13 DISP PAN 17-18 SENSOR OUT ALARM ALARM 3-04-24 10:03AM
L11 DISP PAN 13-14 SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L14 DISP PAN 19-20 SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L13 DISP PAN 17-18 SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L10 DISP PAN 11-12 SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L12 DISP PAN 15-16 SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L 9 DISP PAN 9-10 SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L 3 STP SUMP 91 STP SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
s 6 OTHER FM5 COMMUNICATION ALARM ALARM 3-04-24 10:02AM
L 1 STP SUMP 87 STP SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L 5 STP SUMP DEISE STP SENSOR OUT ALARM CLEAR 3-04-24 10:02AM
L 6 ANNULAR DSL ANN SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L 5 STP SUMP DEISE STP SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L 4 ANNULAR 91 ANN SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L 3 STP SUMP 91 STP SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L 2 ANNULAR 87 ANN SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L14 DISP PAN 19-20 SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L 1 STP SUMP 87 STP SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L13 DISP PAN 17-18 SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L12 DISP PAN 15-16 SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L11 DISP PAN 13-14 SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L10 DISP PAN 11-12 SENSOR OUT ALARM ALARM 3-04-24 10:00AM
L 9 DISP PAN 9-10 SENSOR OUT ALARM ALARM 3-04-24 10:00AM
I11200
MAR 4, 2024 10:08 AM
FASTRIP
4013 S H ST
BAKERSFIELD
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE STATE DATE TIME
OTHER ISD SENSOR OUT WARN CLEAR 3-04-24 10:06AM
OTHER ISD SENSOR OUT WARN ALARM 3-04-24 10:02AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN CLEAR 2-12-24 1:01PM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 2-12-24 1:01PM
SYSTEM SOFTWARE MODULE WARN CLEAR 2-12-24 11:56AM
SYSTEM SOFTWARE MODULE WARN ALARM 2-12-24 11:54AM
OTHER ISD SENSOR OUT WARN CLEAR 2-12-24 10:02AM
h10 OTHER FP10: BLEND3 DEGRD COLLECT WARN ALARM 2-12-24 10:02AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 2-12-24 10:02AM
SYSTEM PRINTER ERROR CLEAR 2-11-24 1:12PM
SYSTEM PAPER OUT CLEAR 2-11-24 1:11PM
SYSTEM PRINTER ERROR ALARM 2-11-24 1:11PM
SYSTEM PAPER OUT ALARM 2-11-24 1:11PM
OTHER ISD SENSOR OUT WARN ALARM 2-11-24 10:02AM
OTHER ISD SENSOR OUT WARN CLEAR 2-10-24 10:02AM
OTHER ISD SENSOR OUT WARN ALARM 2-09-24 10:04AM
OTHER ISD SENSOR OUT WARN CLEAR 2-08-24 4:32PM
h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN CLEAR 2-08-24 4:31PM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN CLEAR 2-08-24 4:31PM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN CLEAR 2-08-24 4:31PM
h12 OTHER FP12: BLEND3 DEGRD COLLECT WARN ALARM 2-08-24 10:04AM
h 9 OTHER FP9: BLEND3 DEGRD COLLECT WARN ALARM 2-08-24 10:04AM
h 6 OTHER FP6: BLEND3 DEGRD COLLECT WARN ALARM 2-08-24 10:04AM
OTHER ISD SENSOR OUT WARN ALARM 2-07-24 10:03AM
T 3 TANK DSL INVALID FUEL LEVEL ALARM 2-13-21 8:05AM
I20600
MAR 4, 2024 10:08 AM
FASTRIP
4013 S H ST
BAKERSFIELD
TANK ALARM HISTORY
TANK 1 87
OVERFILL ALARM FEB 24, 2024 10:19 AM
FEB 8, 2024 1:57 PM
TANK 2 91
TANK 3 DSL
INVALID FUEL LEVEL FEB 13, 2021 8:05 AM
TANK 5
TANK 6
TANK 7
TANK 8
TANK 9
TANK 10
TANK 11
TANK 12
TANK 13
TANK 14
TANK 15
TANK 16
I38200
MAR 4, 2024 10:08 AM
I30200
MAR 4, 2024 10:08 AM
FASTRIP
4013 S H ST
BAKERSFIELD
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 87 STP
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:49 AM FUEL ALARM
2 87 ANN
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:46 AM FUEL ALARM
3 91 STP
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:44 AM FUEL ALARM
4 91 ANN
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:47 AM FUEL ALARM
5 DEISE STP
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:56 AM FUEL ALARM
6 DSL ANN
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:47 AM FUEL ALARM
9 9-10
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:50 AM FUEL ALARM
10 11-12
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:51 AM FUEL ALARM
11 13-14
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:51 AM FUEL ALARM
12 15-16
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:55 AM FUEL ALARM
13 17-18
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:54 AM FUEL ALARM
14 19-20
MAR 4, 2024 10:03 AM SENSOR OUT ALARM
MAR 4, 2024 10:00 AM SENSOR OUT ALARM
MAR 4, 2024 9:52 AM FUEL ALARM
I31600
MAR 4, 2024 10:08 AM
FASTRIP
4013 S H ST
BAKERSFIELD
SMART SENSOR ALARM HISTORY REPORT
SENSOR LOCATION
1 VPS
2 FM1
3 FM2
4 FM3
5 FM4
6 FM5
MAR 4, 2024 10:02 AM COMMUNICATION ALARM
7 FM6
I40200
MAR 4, 2024 10:08 AM
I40300
MAR 4, 2024 10:08 AM
I34200
MAR 4, 2024 10:08 AM
I34700
MAR 4, 2024 10:08 AM
IV0100
MAR 4, 2024 10:08 AM
FASTRIP
4013 S H ST
BAKERSFIELD
ISD ALARM STATUS REPORT
EVR TYPE: VACUUM ASSIST
ISD TYPE: 01.07
VAPOR PROCESSOR TYPE: NONE
OVERALL STATUS :WARN EVR VAPOR COLLECTION :PASS
EVR VAPOR CONTAINMENT :PASS
ISD MONITOR UP-TIME :100%
EVR/ISD PASS TIME : 0%
WARNING ALARMS
DATE TIME DESCRIPTION READING VALUE
24-03-04 10:02:25 SENSOR OUT SELFTEST s 6
24-02-12 10:02:39 A/L RATIO DEGRADATION FP10 BLEND3 0.63
24-02-12 10:02:39 A/L RATIO DEGRADATION FP 6 BLEND3 0.76
24-02-11 10:02:57 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 5:FM5
24-02-09 10:04:50 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 6:FM6
24-02-08 10:04:04 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 3:FM3
24-02-08 10:04:04 A/L RATIO DEGRADATION FP12 BLEND3 0.55
24-02-08 10:04:03 A/L RATIO DEGRADATION FP 9 BLEND3 0.76
24-02-08 10:04:03 A/L RATIO DEGRADATION FP 6 BLEND3 0.62
24-02-07 10:03:20 SENSOR OUT SELFTEST
CHECK VAPOR FLOW METER f 3:FM3
FAILURE ALARMS
DATE TIME DESCRIPTION READING VALUE
SHUTDOWN & MISCELLANEOUS EVENTS
DATE TIME DESCRIPTION ACTION/NAME
24-03-04 10:06:10 SENSOR OUT TEST MANUALLY CLEARED
24-03-04 10:03:23 READINESS ISD:PF EVR:NNN CHECK ISD SENSORS
24-03-04 10:03:23 ISD STARTUP
24-03-04 10:03:15 ISD SHUTDOWN
24-02-15 10:02:41 READINESS ISD:PP EVR:PP ISD & EVR READY
24-02-14 10:02:37 READINESS ISD:PP EVR:NP EVR READINESS PENDING
24-02-13 10:03:04 READINESS ISD:PP EVR:NP EVR READINESS PENDING
24-02-12 13:01:22 COLLECTION TEST HH10 GRADE TEST MANUALLY CLEARED
24-02-12 13:01:16 COLLECTION TEST HH06 GRADE TEST MANUALLY CLEARED
24-02-12 11:56:33 READINESS ISD:PP EVR:NN EVR READINESS PENDING